electrical protection ppt

Upload: wijayasekara-buddhika

Post on 03-Apr-2018

305 views

Category:

Documents


11 download

TRANSCRIPT

  • 7/29/2019 electrical Protection Ppt

    1/79

    1

    August

  • 7/29/2019 electrical Protection Ppt

    2/79

    Def: A COMPLETE ARRANGEMENT OF PROTECTIONEQUIPMENT AND OTHER DEVICES REQUIRED TO ACHIEVE A

    SPECIFIED FUNCTION BASED ON A PROTECTION PRINCIPLE.

    Need: WHEN EQUIPMENT FAILS, THE ENERGY IS RELEASEDAND EVERY COMPONENT IN THE SYSTEM IS AT RISK. THE

    PROTECTIVE RELAYING SYSTEM MONITORS THE SYSTEM

    AND INITIATE ACTION ACCORDINGLY.

    What is Protection System ?

    2

  • 7/29/2019 electrical Protection Ppt

    3/79

    Purpose of Protection System:

    The protective relaying system senses the abnormal condition of powersystem and gives an alarm or isolates the defective system from the

    healthy system.

    A fault in an electrical system is defined as a defect in its electrical

    circuit due to which the current is diverted from the intended path.

    Faults are generally caused by breaking of conductors or failure ofinsulation. Some other causes of fault conditions include:

    Mechanical failure

    Environment disturbances

    Excessive internal & external stresses

    Operating error

    Equipment malfunctions

    The fault impedance being low, the fault current are relatively very

    high and flows towards the fault.

    3

  • 7/29/2019 electrical Protection Ppt

    4/79

    Requirements of Protection system:

    Selectivity - ability to select the faulty part of in system &disconnect the faulty part without disturbing rest of the

    healthy system.

    Speed of Operation The faulty section should be isolated

    as fast as possible to minimize the damage to equipmentsand increase the stability of operation of healthy system.

    Sensitivity - ability to operate with low value of actuatingquantities.

    Reliability - ability to operate under the faulty conditionsonly.

    4

  • 7/29/2019 electrical Protection Ppt

    5/79

    Types of Protective equipment

    FUSES

    MINIATURE CIRCUIT BREAKERS (MCB)

    PROTECTIVE RELAYS

    5

  • 7/29/2019 electrical Protection Ppt

    6/79

    FUSES

    A Fuse is a short piece of metal,

    inserted in the circuit, which melts

    when excessive current flows

    through the circuit and thus breaks

    the faulty circuit.

    The fuse element is generally made of material having low

    of low melting point, high conductivity and leastdeterioration due to oxidation, e.g. silver, copper etc. it is

    inserted in series in the circuit to be protected.

    6

  • 7/29/2019 electrical Protection Ppt

    7/79

    Classification of Fuses:

    i. Low-voltage fuses

    Semi-enclosed rewirable fuse

    High rupturing capacity (HRC) cartridge fuse

    HRC fuse with tripping device

    ii. High-voltage fuses

    Cartridge type Liquid type

    Metal clad fuses

    7

  • 7/29/2019 electrical Protection Ppt

    8/79

    Miniature Circuit Breakers (MCBs)

    MCBs is a type of switch with thermal contacts. It can

    open or close a circuit under all conditions viz. no load, full

    load or fault conditions. It can be operated manually

    under normal conditions and automatically under faultconditions.

    8

  • 7/29/2019 electrical Protection Ppt

    9/79

    Protection Relay

    A protection relay is a device that detects the fault and

    initiates the operation of the circuit breaker to isolate the

    defective system from the rest of the healthy system.

    The relay detects the abnormal condition by constantlymeasuring the electrical quantities e.g. voltage, current,

    frequency, phase angle, status of circuit breakers , etc.

    In changes of one or more quantities, the relay senses the

    faults, its type and location of the fault.

    9

  • 7/29/2019 electrical Protection Ppt

    10/79

    10

  • 7/29/2019 electrical Protection Ppt

    11/79

    Essential Requirements of ProtectiveSystem:-

    1. Current Transformers or CT :-

    CT,s are required to scale down theprimery current to suitable level so that

    relay can use it. CT,s can be single coreor multi core. Each core can be singleratio or multi-ratio. Separate cores are

    needed for metering or protectionpurposes. Normally secondary current is1A or 5A as per requirement.

    11

  • 7/29/2019 electrical Protection Ppt

    12/79

    2. Potential Transformers or VoltageTransformers or PT/ VT,s :-

    PT,s are needed to scale down thePrimery voltage to suitable level so that

    it is useful for the relay. Normallysecondary voltage is 110 V or 110/3Volts as per requirement. PTs or VT,s

    are of single or three phase system.

    12

  • 7/29/2019 electrical Protection Ppt

    13/79

    3-Auxiliary AC or DC Supply:-

    Reliable and steady auxiliary supply is needed sothat in all adverse operating conditions, it isavailable to the protective system to detect thefaulty condition, and the relay could isolate the

    faulty system from the healthy system with theaid of circuit breakers.

    Normally DC with battery chargers are used asreliable and steady auxiliary supply system.

    Normally 12 V, 24 V, 48 V, 110 V or 220 V DCauxiliary supply system are used.

    13

  • 7/29/2019 electrical Protection Ppt

    14/79

    4. Circuit Breakers:

    Circuit breakers or CB,s are very much needed tooperate the electrical circuits in all the operatingconditions i.e. on no-Load, on Full-load.

    CB are also required to isolate the faulty systemfrom healthy system on receipt of command fromthe protective system in the shortest possibletime.

    CB status is also available to the protective systemto properly take the decision of the fault.

    14

  • 7/29/2019 electrical Protection Ppt

    15/79

    5.Precautions while developing/ studyingschematics:

    - All the schematics are made withoutany ac/dc supplies,

    - All the pressure switches are in zeropressure state,

    - All relays are in non-operating state andtheir contacts are in normal state,

    - No current/ voltage from CT/ PT isavailable.

    15

  • 7/29/2019 electrical Protection Ppt

    16/79

    Various types of Relays according to principleof operation are as follows:

    1) Electromagnetic Attraction Relayi. Attracted armature type

    ii. Solenoid type

    iii. Balanced beam type

    The relay operates by virtue of a plunger being attracted into a

    solenoid or an armature being attracted towards the pole of

    an electromagnet which in turn operates the associated

    contacts bank. These types of relays may be operated by dc

    or ac quantities like as voltage, current etc. Normally this

    type of relays are used for supply status, CB status, Contact

    multiplication etc. 16

  • 7/29/2019 electrical Protection Ppt

    17/79

    2) Electromagnetic Induction RelayThese relays operate on the principle of Induction motor and

    are widely used for protective relaying purposesinvolving a.c. quantities. An Induction relay essentially

    consists of a pivoted aluminium disc placed in two

    alternating magnetic fields of same frequency but

    displaced in time and space. The torque is produced in

    the disc by the interaction of one of the magnetic fields

    with the currents induced in the disc by the other.

    In order to obtain the phase difference in the flux and hence

    the operating torque, following three types of structures

    are used:

    a) Shaded-pole structure

    b) Watt-hour meter structure

    c) Induction cup structure.17

    El t ti I d ti R l

  • 7/29/2019 electrical Protection Ppt

    18/79

    Electromagnetic Induction Relay

    18

  • 7/29/2019 electrical Protection Ppt

    19/79

    STATIC RELAY

    In Static Relays, the measurement is performed by

    electronic/magnetic/optical or other components

    without mechanical motion. Static relays have

    versatile characteristics, offer low burden andincorporate several protective/control/monitoring

    functions in one compact unit.

    19

  • 7/29/2019 electrical Protection Ppt

    20/79

    MICROPROCESSOR based Numerical Relays:In 1980s, programmable static relays incorporating

    Microprocessorhave been introduced.

    A programmable protection & control system has a

    Microprocessor or Microcomputer in its circuit. With

    the help of the logic and the Microprocessor, the

    integrated system can perform several functions of

    Data acquisition, Data processing, Data transmission,

    protection & control.

    Earlier for each of these functions, separateElectromagnetic or Static units were used along with

    complex inter module wiring.

    20

  • 7/29/2019 electrical Protection Ppt

    21/79

    A/DConverter

    MICROPROCESSORInput Unit

    Data Logger

    Data Request& Display

    VT

    CTCB

    Trip coil

    Block Diagram of a simple Microprocessor based Digital Static Relay

    Setting

    Input Unit

    21

  • 7/29/2019 electrical Protection Ppt

    22/79

    Relay Based on actuating parameters

    -Over-current Relays,

    -Under/ Over voltage relays,

    -Over/ under frequency relays,

    -Power directional relays,

    -Over-fluxing relays etc.

    22

  • 7/29/2019 electrical Protection Ppt

    23/79

    Relays based on OperatingCharacteristics:-

    -Instantaneous Relays,

    -Definite time delay relays,

    -Inverse definite minimum time delayrelays (IDMT),

    -Voltage restraint over current relay,

    23

  • 7/29/2019 electrical Protection Ppt

    24/79

    Relays based on their uses:

    1-Differential Protection Relay

    2.Restricted E/F Relay,

    3.Distance Protection Relay,

    4. Negative Phase Sequence Relay,

    5. Neutral Over-current Relay,

    6. Neutral Voltage Displacement Relay,

    7. Over Fluxing Relay,

    24

  • 7/29/2019 electrical Protection Ppt

    25/79

    8. Over/ under voltage Relay,

    9. Over-current Relay,10. Bus-bar Protection Relay,

    11. Breaker Failure Relay,

    12.Direction O/C & Directional E/FRelays

    13.Over/ Under Frequency Relay,

    25

  • 7/29/2019 electrical Protection Ppt

    26/79

  • 7/29/2019 electrical Protection Ppt

    27/79

  • 7/29/2019 electrical Protection Ppt

    28/79

    The Protection scheme of Vishnuprayag

    Hydro Power Project(4x100MW)isclassified as :

    Generator Protection

    Generator Transformer Protection

    Bus-bar Protection

    Bus Coupler protection

    Transmission Line Protection

    Shunt Reactor protection

    28

  • 7/29/2019 electrical Protection Ppt

    29/79

    Generator/ Unit ProtectionsRelay : Model-REG216, Make-ABB

    Main-I (GRP-1) Protection comprising :

    i. Generator Differential

    ii. Under Impedance

    iii. Negative Phase Sequenceiv. Gen. Over Current (Inst. & IDMT type)

    v. 100% Stator Earth Fault

    vi. Reverse Power

    vii. Over Voltageviii. Loss of Excitation

    ix. Balance Voltage

    x. Gen. Thermal Protection29

  • 7/29/2019 electrical Protection Ppt

    30/79

    Main-II (GRP-2) Protection comprising :

    i. Gen.-transformer Over all Differential

    ii. 95% Stator Earth Fault

    iii. Under Frequency

    iv. Over Frequency

    v. Under Voltage

    vi. Over Flux

    vii. UAT Restricted Earth Fault

    viii. UAT Over Current

    ix. UAT Earth fault

    30

  • 7/29/2019 electrical Protection Ppt

    31/79

    31

    SingleLineDiagramo

    fProtectionsc

    hemeof

    GeneratorU

    nit

  • 7/29/2019 electrical Protection Ppt

    32/79

    32

    SingleLineDiagramo

    fProtectionsc

    hemeof

    GeneratorU

    nit

    Trip Logic of Protection scheme of GRP-1 (Main-I)

  • 7/29/2019 electrical Protection Ppt

    33/79

    Trip Logic of Protection scheme of GRP 1 (Main I)

    33

    LED Indications provided on GRP 1 (Main I)

  • 7/29/2019 electrical Protection Ppt

    34/79

    LED Indications provided on GRP-1 (Main-I)

    34

    Details of LED Indications provided on GRP-1 (Main-I)

  • 7/29/2019 electrical Protection Ppt

    35/79

    Details of LED Indications provided on GRP 1 (Main I)

    35

  • 7/29/2019 electrical Protection Ppt

    36/79

    LED Indications provided on GRP 2 (Main II)

  • 7/29/2019 electrical Protection Ppt

    37/79

    LED Indications provided on GRP-2 (Main-II)

    37

    Details of LED Indications provided on GRP-2 (Main-II)

  • 7/29/2019 electrical Protection Ppt

    38/79

    Details of LED Indications provided on GRP 2 (Main II)

    38

  • 7/29/2019 electrical Protection Ppt

    39/79

    Unit Protection Settings

    Main-1 Settings ( GRP-1 Panel )

    Sl.No. ProtectionLED

    No.Function Curve/Setting Time Delay

    1 Over Voltage Stage-1 (59) 06 Alarm 1.15 Un 2.00 sec

    2 Over Voltage Stage-2 (59) 23 ESD 1.25 Un Inst.

    3 Under Voltage (27) 07 Alarm 0.70 Un 2.00 sec

    4 Balance Voltage-1 (60) 05 Alarm 0.20 Un 0.04 sec

    5 Balance Voltage-2 (60) 28 PSD 0.20 Un 1.00 sec

    6 Inst. Over current (50) 21 ESD 1.60 Un 0.50 sec

    7 Time Delayed Over Current (51) 22 ESD 1.30 In 2.00 sec8 UAT E/f Protn. (51) 31 PSD 5.00 In 0.02 sec

    9 UAT O/C Protn (Inverse time) (51) 30 PSD IB =0.50 In, k=0.05 IDMT

    10 Definite Time NPS-1 (46) 04 PSD I2 =0.05 In 5.00 sec

    11 Inverse Time NPS-2 (46) 26 PSD IB =0.78 In IDMT

    12 Reverse Power (32) 25 PSD -0.05 PN 3 sec

    13 Loss of Excitation (40) 32 ESD XA = -1.11 Un/In

    XB = -0.18 Un/In

    0.2 sec

    14 GT Restricted E/F Protn. (51 N) 29 ESD IB =0.10 In As per curve

    15 100% Stator E/F(64 S) 24 ESDT/f ratio-50

    REs-0.91k1 sec

    16 Under Impedance (21) 18 ESD 0.176 Un/ In 3 sec

    17 Gen Differential (87 G) 17 ESD g setting = 0.10 Inv setting = 0.25

    Inst. 39

  • 7/29/2019 electrical Protection Ppt

    40/79

    Unit Protection Settings

    Main-2 Settings : ( GRP-2 Panel )

    Sl.No

    .Protection

    LED

    No.Function Curve/Setting Time Delay

    1 Over Voltage Stage-1 (59) 03 Alarm 1.15 Un 2.00 sec

    2 Over Voltage Stage-2 (59) 17 ESD 1.25 Un 0.00 sec

    3 Under Voltage Stage-1 (27) 04 Alarm 0.85 Un 10.0 sec

    4 Under Voltage Stage-2 (27) 20 ESD 0.80 Un 3.20 sec

    5 Over Frequency Stage-1 (81) 07 Alarm 52.0 Hz 1.00 sec

    6 Over Frequency Stage-2 (81) 23 PSD 52.5 Hz 1.00 sec

    7 Under Frequency Stage-1 (81) 06 Alarm 48.5 Hz 1.00 sec

    8 Under Frequency Stage-2 (81) 22 PSD 47.0 Hz 2.00 sec

    9 Over Fluxing Stage-1 (24) 05 Alarm 1.15 Un/fn 2.00 sec

    10 Over Fluxing Stage-2 (24) 21 PSD 1.1 UB/fn 0.05 min

    11 UAT Restricted E/F Protn. (51 N) 26 PSD IB =0.4 In, k=0.01As per curve

    12 GT/F Time Delayed O/C (51) 27 ESD 1.3 In 3.00 sec

    13 Gen. Trans. Neu. O/C (51 N) 18 PSD IB =0.30 InAs per curve

    14 95% Stator E/F(59/27) 24 ESD 0.05 Un 0.05 sec

    15 Overall Differential (87 T) 25 ESD

    g setting = 0.20 In

    v setting = 0.5 Inst. 40

    G t T f

  • 7/29/2019 electrical Protection Ppt

    41/79

    Generator TransformerProtection :

    i. Differential Protection

    ii. Back-up Over Current

    iii. Neutral Over Current

    iv. Restricted Earth Fault

    v. Winding Temperature High

    vi. Oil Temperature High

    vii. Buchholz Gas Relayviii. Pressure Relief Valve

    41

    k

  • 7/29/2019 electrical Protection Ppt

    42/79

    Bus-Bar Protection & Breakerfailure Protection :Relay : Model-REB500, Make-ABB

    -Bus bar protection is provided so that in case

    of fault on any of the bus-bar, the faulty

    bus will be isolated and other bus willcontinue to function without any

    interruption.

    - Breaker failure protection is provided toisolate the faulty breaker from the system,

    in case CB fail to isolate the fault.

    42

  • 7/29/2019 electrical Protection Ppt

    43/79

    The Central unit & Bay relay comprising of :

    i. Bus bar Differential protection,

    ii. Breaker Failure Protection (LBB)

    43

  • 7/29/2019 electrical Protection Ppt

    44/79

  • 7/29/2019 electrical Protection Ppt

    45/79

  • 7/29/2019 electrical Protection Ppt

    46/79

    Bus-Coupler ProtectionRelay : Model-SPAJ140C, Make-ABB

    Provided to trip the buscoupler CB in case

    of over-loading of bus-coupler or fault

    on any of the bus-bar

    i . Over Current Protection,

    ii. Earth Fault Protection

    46

  • 7/29/2019 electrical Protection Ppt

    47/79

    Single Line Diagram of Protection scheme of Bus Coupler

    47

  • 7/29/2019 electrical Protection Ppt

    48/79

    Trip Logic of Protection scheme of Bus Coupler

    48

  • 7/29/2019 electrical Protection Ppt

    49/79

    Transmission Line Protections

    Main-I (Relay-REL521), Main-II (Relay-REL316) &Back-up (Relay-REX521) protection comprises of

    following functions :

    i. Under Impedance

    ii. Over Voltage

    iii. Back-up Over Current

    iv. Back-up Earth fault

    v. Breaker Failure protectionvi. Auto-Reclosure Scheme

    49

    Single Line Diagram of Protection scheme of Transmission Lines

  • 7/29/2019 electrical Protection Ppt

    50/79

    Single Line Diagram of Protection scheme of Transmission Lines

    50

    Trip Logic of Protection scheme of Transmission Lines

  • 7/29/2019 electrical Protection Ppt

    51/79

    51

  • 7/29/2019 electrical Protection Ppt

    52/79

    Setting Criterion of Line Protection:

    1. Zone-1: 80% of Principal Line Section;

    2. Zone-2: 100% of Principal Line Section+ 50% of the Adjoining Shortest Line

    (check that Zone-2 > 120% of Principal

    Line Section

    52

  • 7/29/2019 electrical Protection Ppt

    53/79

    3. Zone-3: 1.2 x (100% of Principal LineSection + 100% of the Adjoining

    longest Line )

    4. Zone-4 : 1.2 x (100% of Principal Line

    Section + Single T/F of remote end )

    5. Reverse Zone: 25% of Zone-1

    53

  • 7/29/2019 electrical Protection Ppt

    54/79

    Shunt Reactor ProtectionRelay : Model-REG316, Make-ABB

    i. Differential Protection

    ii. Restricted Earth Fault

    iii. Back-up Impedance Protection,

    iv. Winding Temperature High

    v. Oil Temperature High

    vi. Buchholz Gas Relay protection

    vii.Pressure Relief Valve

    54

    S ddi i l / S h

  • 7/29/2019 electrical Protection Ppt

    55/79

    Some Additional Features/ SchemesUsed in Protective Circuits:

    1.Trip Circuit Supervision Scheme: It isused to continuously monitor the

    tripping circuit & trip coil of circuitbreakers,

    2.Trip Coil supervision Scheme: It is used

    to continuously monitor the trip coil ofthe tripping relays,

    55

    3 Pole discrepancy scheme : In single

  • 7/29/2019 electrical Protection Ppt

    56/79

    3.Pole discrepancy scheme : In singlepole circuit breakers, If due to any

    reason, one or two poles of the CBtrips, the remaining pole trips after ashort time delay. Normally it is of theorder of 0.8 to 1.0 sec. It may be with

    CB schematic or outside.

    4. Auto-reclosing Scheme: On tripping ofLine CB on Temporary line fault, the

    scheme provides auto Reclosure of LineCB after a pre-set short time delay.

    56

  • 7/29/2019 electrical Protection Ppt

    57/79

    The scheme may be single phase auto-

    reclosing or three phase auto-reclosingor both.

    Normally single phase auto-reclosing

    scheme are employed. Three phaseauto-reclosing scheme are best suitedfor radial lines.

    57

    5 C i I t t i i S h

  • 7/29/2019 electrical Protection Ppt

    58/79

    5. Carrier Inter-tripping Schemes :-

    Normally 80% of Principal Line Section is

    covered by Zone-1 of the Lineprotection, the rest of the 20% iscovered by Zone-2 protection with a

    minimum delay of 0.4 sec.

    To cover end 20% line fault in Zone-1

    time also, Various carrier based carrierinter-tripping schemes are used:-

    58

  • 7/29/2019 electrical Protection Ppt

    59/79

    A. Permissive Under-reach carrier intertripping Scheme,

    B. Permissive Over-reach carrier intertripping Scheme,

    C. Carrier Blocking Scheme,D. Carrier Acceleration Scheme

    59

  • 7/29/2019 electrical Protection Ppt

    60/79

    Testing of ProtectiveRelays schemes&

    Associated Equipments.

    60

  • 7/29/2019 electrical Protection Ppt

    61/79

    Testing of Current Transformers :

    - Insulation Test

    1. Primary winding to Earth by 5kVmegger

    2. Secondary winding to Earth (Foreach core) by 250V or 500 V megger,

    3. Primary winding to all the secondarywinding by 5kV megger,

    4. Core to core of secondary windingsby 250V or 500 V megger,

    61

    R ti T t f h b P i

  • 7/29/2019 electrical Protection Ppt

    62/79

    - Ratio Test of each core by Primaryinjection,

    - Polarity Test of cores,- Magnetizing Characteristics or knee

    point voltage test for identifying

    metering/ Protection cores

    62

  • 7/29/2019 electrical Protection Ppt

    63/79

    Testing of Potential Transformers:

    - Insulation Test

    1. Primary winding to Earth by 5kVmegger after isolating from earth

    2. Secondary winding to Earth (Foreach core) by 250V or 500 V megger,

    3. Primary winding to all the secondarywinding by 5kV megger,

    4. Core to core of secondary windingsby 250V or 500 V megger,

    63

  • 7/29/2019 electrical Protection Ppt

    64/79

    - Ratio Test of each core by injectingvoltage on Primary terminal andmeasuring voltages on secondary cores,

    - Polarity Test of cores with reference toPrimary Terminal,

    64

  • 7/29/2019 electrical Protection Ppt

    65/79

    Primary Injection of CT,s:

    - Primary injection of currenttransformers is carried out with the

    help of Primary Injection Test Kits. Thecurrent is measured in all the currentcircuits of all the phases one by one toensure that during actual operationcurrent will flow only in the correctphase and not otherwise,

    65

  • 7/29/2019 electrical Protection Ppt

    66/79

    - During Primary injection we have toensure that the current in metering circuitis flowing from the metering core only andcurrent in protection circuit is flowing fromthe protection core only otherwise theprotection is likely fail during faultconditions.

    66

  • 7/29/2019 electrical Protection Ppt

    67/79

    Secondary Injection Of PT,s:

    - Injection of Potential circuit is carriedout with the help of Secondary Injection

    Test Kits or with the help of Singlephase variac, Rheostat etc. The voltageis measured in all voltage circuits of allthe phases one by one to ensure thatduring actual operation voltage will flowin the correct phase only and nototherwise,

    67

  • 7/29/2019 electrical Protection Ppt

    68/79

    Checking of DC Schemes:

    -The wiring of complete scheme ischecked and corrected according to

    scheme.- Auxiliary DC supply is given to the panel

    and DC supply is checked at various

    points in the scheme/ Relays- The operation of DC relays checked as

    per schematics.

    68

  • 7/29/2019 electrical Protection Ppt

    69/79

    Testing Of Relays:

    -All the relays are tested for operation onvarious settings with the help of

    Secondary Relay Testing Kit Like asDoble, Omricon, TURH, ZFB etc.

    -The operating time of the relays is also

    measured to ensure the operation ofrelays within permissible limits.

    69

    Power System Simulator (DOBLE Test Kit)

  • 7/29/2019 electrical Protection Ppt

    70/79

    70

    Power System Simulator (DOBLE Test Kit)

  • 7/29/2019 electrical Protection Ppt

    71/79

    71

  • 7/29/2019 electrical Protection Ppt

    72/79

    72

    Closing/ Opening operation of Circuit

  • 7/29/2019 electrical Protection Ppt

    73/79

    Closing/ Opening operation of CircuitBreakers:

    -Closing/ Opening operation of CircuitBreaker is checked from Control/Relay

    Panels- Tripping of Circuit Breaker is checked by

    operation of Protective Scheme with the

    aid of secondary injection test Kit.

    73

  • 7/29/2019 electrical Protection Ppt

    74/79

    Checking of Alarm & Indications:

    - All the alarms & Indications areactuated one by one and theiroperation is checked/ ensured on the

    panels.Checking of Stability of Relays :

    - Check for the stability of Differential

    Relays, Restricted Earth Fault Relays,Bus-bar protection Relays etc.

    74

    On load checking the system:

  • 7/29/2019 electrical Protection Ppt

    75/79

    On load checking the system:

    After the system is energized, the

    following checks are required to becarried out :-

    - Checking of DC auxiliary supply at

    various points in the panels,- Checking of CT/ PT supplies to relays,

    meters etc.,

    - Checking of healthiness of relays- Checking of proper operation of

    voltmeter/ Ampere meter in all the

    phases 75

  • 7/29/2019 electrical Protection Ppt

    76/79

    - Operation of MW meter, PF meter,

    Energy meter etc and their running inproper direction,

    - Trip circuit supervision in healthy state,

    - Relays are measuring correct voltage &currents as per load condition.

    76

    Testing Of Transformers

  • 7/29/2019 electrical Protection Ppt

    77/79

    Testing Of TransformersFollowing Tests are performed to Check

    the healthiness of Transformers:-1.Insulation Resistance- HV-E, LV-E, HV-

    LV by 5KV/ 10KV Megger.

    2. Turn ratio Test3. Open circuit Test from HV & LV side,

    4. Short Circuit Test from HV to LV,

    5. Magnetic Balance Test from Star side

    6. Checking proper operation of OLTC.

    77

  • 7/29/2019 electrical Protection Ppt

    78/79

    Testing Of Reactors:

    Following Tests are performed to Checkthe healthiness of Reactors:-

    1. Insulation Resistance- HV-E by 5KV/10KV Megger.

    2. Open circuit Test from HV,

    3. Magnetic Balance Test from HV

    78

  • 7/29/2019 electrical Protection Ppt

    79/79