  • EE 706

    ELECTRICAL MACHINES LABORATORY II

    2006 Scheme

    July 5, 2010

  • ACKNOWLEDGEMENT

    This manual is the result of contributions from the following sta members.

    Ms. Sheena K. M.Mr. Anith KrishnanMr. Naveen T. R.Mr. Jobiraj C.Mr. Manoj M. S.Mr. Gireesh G.Mr. Vaishak L. S.

  • INTRODUCTION

    A few words about the lab.

  • INSTRUCTIONS

    All students should wear shoes. Male students should tuck in their shirts. Female students should tie up their hair properly. Students should not lean on the work bench. Do not switch on the supply before the circuit is veried by the concerned lab faculty. Use of mobile phone inside the laboratory is strictly prohibited.

    All the students are to strictly abide by the instructions given here and any additionalinstruction given during the lab session, failing to which he/she will have to face disciplinaryaction.

  • Contents

    Load test on SCIM. 1

    No load and blocked rotor test on SRIM. 4

    Load test on single phase induction motor 9

    Alternator regulation by direct loading. 11

    Alternator regulation by indirect method 13

    V curves and inverted V curves of synchronous motor 18

    No load and blocked rotor test on SCIM. 21

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Experiment No.: 1

    LOAD TEST ON SQUIRREL CAGE INDUCTION MOTOR

    Aim:

    To study the performance of the machine when loaded and to plot the following charac-teristics of a squirrel cage induction motor.

    Vs o/pN Vs o/pIa Vs o/pcos Vs o/p%s Vs o/p

    Machine details:

    Refer name plate of the machine.

    Precautions:

    1. All the connections should be tight.

    2. The autotransformer should be in minimum position initially.

    3. The motor should be on no load at the time of starting.

    Procedure:

    1. Make the connections as shown in the circuit diagram.

    2. After taking care of the precautions, switch on the supply.

    3. Adjust the autotransformer till rated voltage is applied across the motor terminals.

    4. Note down all the meter readings in no-load condition.

    5. Increase the load in steps until the ammeter reads the rated current and note downall the meter reading for each applied load.

    6. Reduce the load to zero, bring the autotransformer to the minimum position andswitch o the supply.

    Division of Electrical Engineering, S.O.E., CUSAT 1

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Circuit Diagram:

    4

    4

    0

    V

    ,

    5

    0

    H

    z

    3

    Observation Table:

    Sl. V1 A1 W1 W2 N S1 S2 i/p T o/p cos %s No. (V) (A) (W) (W) (rpm) (kg) (kg) (W) (Nm) (W)123456

    Division of Electrical Engineering, S.O.E., CUSAT 2

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Equations and Calculations:

    Voltage V = : : : : : :V

    Current I = : : : : : :A

    W1 = : : : : : :W

    W2 = : : : : : :W

    I/P power =W1 +W2 = : : : : : :W

    Speed N = : : : : : : rpm

    S1 = : : : : : : kg

    S2 = : : : : : : kg

    Torque T = (S1 S2)rg = : : : : : :NmO/P power =

    2NT

    60= : : : : : :W

    Power Factor cos = : : : : : :

    Slip s =Ns NNs

    100 = : : : : : :%

    Eciency =O/P

    I/P 100 = : : : : : :%

    Here r is the radius of the break drum and g is the acceleration due to gravity.

    Result:

    Division of Electrical Engineering, S.O.E., CUSAT 3

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Experiment No.: 2

    NO LOAD AND BLOCKED ROTOR TEST ONSLIP-RING INDUCTION MOTOR

    Aim:

    To conduct no load and blocked rotor test on slip-ring induction motor and to draw itsequivalent circuit and circle diagram.

    Machine Details:

    Refer name plate of the machine.

    Precautions:

    1. The autotransformer should be in minimum position while switching on the supply.

    2. The motor should not be on load while starting.

    Procedure:

    No-load test

    1. After taking care of the precautions, switch on the supply.

    2. Adjust the autotransformer gradually such that the rated voltage is applied to thestator.

    3. Note down all the meter readings under no-load condition.

    4. Reduce the autotransformer to minimum position.

    5. Switch o the supply.

    Blocked rotor test

    1. After taking care of the precautions, switch on the supply.

    2. Adjust the autotransformer till the rated current ows through the stator.

    3. Take all the meter readings.

    4. Reduce the autotransformer to minimum position.

    5. Switch o the supply.

    Division of Electrical Engineering, S.O.E., CUSAT 4

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Circuit Diagram:

    4

    4

    0

    V

    ,

    5

    0

    H

    z

    ,

    3

    Figure 1: Circuit diagram for no-load test.

    4

    4

    0

    V

    ,

    5

    0

    H

    z

    ,

    3

    Figure 2: Circuit diagram for blocked rotor test.

    3

    0

    V

    D

    C

    Figure 3: Measurement of stator resistance.

    Division of Electrical Engineering, S.O.E., CUSAT 5

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Observation Table:

    No-load test

    Sl. V0 I0 W1 W2 W0No. (V) (A) (W) (W) (W)123456

    Blocked rotor test

    Sl. Vsc Isc W1 W2 WscNo. (V) (A) (W) (W) (W)123456

    Stator Resistance

    Sl. V I Ra =12 V

    I

    No. (V) (A) ()123456

    Division of Electrical Engineering, S.O.E., CUSAT 6

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Equations and Calculations:

    From no-load test

    Supply voltage V0 = : : : : : :V

    Circuit current I0 = : : : : : :A

    No-load power W0 =W1 +W2 : : : : : :W

    cos0 =W0p3V0I0

    = : : : : : :

    Magnetising current I = I0 sin0 = : : : : : :A

    Working current Iw = I0 cos0 = : : : : : :A

    R0 =V0Iw

    = : : : : : :

    X0 =V0I

    = : : : : : :

    From blocked rotor test

    Supply Voltage Vsc = : : : : : :V

    Circuit current Isc = : : : : : :A

    Power consumed Wsc =W1 +W2 = : : : : : :W

    Z01 =VscIsc

    = : : : : : :

    R01 =Wsc3I2sc

    = : : : : : :

    X01 =qZ201 R201 = : : : : : :

    From stator resistance test

    DC resistance Rdc =1

    6

    6XSl:No:=1

    Ra = : : : : : :

    AC resistance Rac = 1:2Rdc = : : : : : :

    Rest of the parameters can be calculated as

    R02 = R01 Rac = : : : : : :

    X1 = X

    02 =

    X012

    = : : : : : :

    Division of Electrical Engineering, S.O.E., CUSAT 7

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    R0 X0

    R1 X1 R02

    X 02

    R021s 1

    Figure 4: Equivalent Circuit.

    Figure 5: Circle Diagram.

    Result:

    Division of Electrical Engineering, S.O.E., CUSAT 8

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Experiment No.: 3

    LOAD TEST ON SINGLE PHASE INDUCTION MOTOR

    Aim:

    To conduct load test on a single phase induction motor and to plot the following charac-teristics.

    Vs o/pN Vs o/pIa Vs o/pcos Vs o/p%s Vs o/pT Vs o/p

    Machine details:

    Refer name plate of the machine.

    Precautions:

    1. All the connections should be tight.

    2. The motor should not be on load while starting.

    Procedure:

    1. Close DPST and start the motor on no load at rated voltage.

    2. Note down all the meter readings at no load.

    3. Gradually apply the load in steps till the ammeter reads rated current. Note downall the meter readings for each load.

    4. Gradually decrease the load to zero and switch o the supply.

    Circuit Diagram:

    2

    3

    0

    V

    ,

    5

    0

    H

    z

    A

    .

    C

    .

    S

    W

    Division of Electrical Engineering, S.O.E., CUSAT 9

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Observation Table:

    Sl. V1 A1 W1 N S1 S2 T o/p cos No. (V) (A) (W) (rpm) (kg) (kg) (Nm) (W)123456

    Equations and Calculations:

    Voltage V = : : : : : :V

    Current I = : : : : : :A

    I/P power =W1 = : : : : : :W

    Speed N = : : : : : : rpm

    S1 = : : : : : : kg

    S2 = : : : : : : kg

    Torque T = (S1 S2)rg = : : : : : :NmO/P power =

    2NT

    60= : : : : : :W

    Power Factor cos = : : : : : :

    Eciency =O/P

    I/P 100 = : : : : : :%

    Here r is the radius of the break drum and g is the acceleration due to gravity.

    Result:

    Division of Electrical Engineering, S.O.E., CUSAT 10

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Experiment No.: 4

    ALTERNATOR REGULATION BY DIRECT LOADING

    Aim:

    To determine the regulation of a 3 alternator by direct loading and to plot the followinggraphs.

    Machine Details:

    Refer name plate of the machine.

    Precautions:

    1. The eld rheostat of D.C. motor should be kept at minimum position and that ofthe alternator should be at maximum position while starting the experiment.

    2. All the switches should be in open position before giving the supply.

    Procedure:

    1. Wire up the circuit as shown in the circuit diagram.

    2. DC supply is given to the prime mover by closing DPST and is started using thestarter.

    3. By varying the eld rheostat, the prime mover is made to run in the rated speed ofthe alternator.

    4. Close SPST to energize the eld of alternator.

    5. Adjust the alternator eld rheostat so as to get rated voltage across the alternatoropen circuited terminals.

    6. Close TPST switch (the alternator is now connected to the load).

    7. Add some load to the alternator. This causes the terminal voltage to change (it candecrease or increase).

    8. Adjust the alternator eld rheostat such that the rated voltage is applied across theload. Note down the ammeter readings.

    9. The entire load is now thrown o the alternator by bringing the TPST switch to theopen position.

    10. The open circuit or no-load voltage (E0) is noted.

    11. Repeat 7-10 until the ammeter reads the rated current of the machine.

    12. De-energise the alternator eld and switch o the supply.

    Division of Electrical Engineering, S.O.E., CUSAT 11

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Circuit Diagram:

    2

    2

    0

    V

    D

    .

    C

    .

    D

    P

    S

    T

    T

    P

    S

    T

    Observation Table:

    Sl. VL IL If E0 RegulationNo. (V) (A) (A) (V) (%)123456

    Equations and Calculations:

    Voltage across the load VL = : : : : : :V

    Load current IL = : : : : : :A

    Field current If = : : : : : :A

    % Regulation =E0 VLVL

    100 = : : : : : :%

    where E0, VL, IL and If are per-phase values.

    Result:

    Division of Electrical Engineering, S.O.E., CUSAT 12

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Experiment No.: 5

    ALTERNATOR REGULATION BY INDIRECT METHOD

    Aim:

    To pre-determine the regulation of a 3 alternator by indirect methods at dierent loads(14, 34and full load) for various power factors (0.8 lead, 0.8 lag, upf) and draw the regulation

    vs. load current curve by conducting suitable tests.

    Machine Details:

    Refer name plate of the machine.

    Precautions:

    1. All the switches should be in open position before switching on the supply.

    2. The eld rheostat of D.C. motor should be kept at minimum position and that ofthe alternator should be at maximum position while starting the experiment.

    Procedure:

    OC Test

    1. Wire up the circuit as shown in the circuit diagram.

    2. DC supply is given to the prime mover by closing DPST and is started using thestarter.

    3. By varying the eld rheostat, the prime mover is made to run in the rated speed ofthe alternator.

    4. Close SPST to energize the eld of alternator.

    5. By adjusting the alternator eld rheostat, increase the alternator eld current insteps and note down If and open circuit voltage E0.

    6. Repeat the above step till the voltmeter reads 1.25 times the rated voltage of themachine.

    7. De-energise the alternator eld and switch o the supply.

    SC Test

    1. Wire up the circuit as shown in the circuit diagram.

    2. DC supply is given to the prime mover by closing DPST and is started using thestarter.

    3. Close SPST switch such that the alternator is now short-circuited.

    4. By varying the eld rheostat, the prime mover is made to run in the rated speed ofthe alternator.

    Division of Electrical Engineering, S.O.E., CUSAT 13

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    5. Close SPST to energize the eld of alternator.

    6. By adjusting the alternator eld rheostat, increase the alternator eld current insteps and note down If and the armature current Ia.

    7. Repeat the above step till the ammeter reads 1.25 times the rated current of themachine.

    8. De-energise the alternator eld and switch o the supply.

    Circuit Diagram:

    OC Test

    2

    2

    0

    V

    D

    .

    C

    .

    D

    P

    S

    T

    SC Test

    2

    2

    0

    V

    D

    .

    C

    .

    D

    P

    S

    T

    T

    P

    S

    T

    Division of Electrical Engineering, S.O.E., CUSAT 14

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Resistance measurement

    3

    0

    V

    D

    C

    Observation Table:

    OC Test SC TestSl. E0 If Sl. If IaNo. (V) (A) No. (V) (A)1. 1.2. 2.3. 3.4. 4.5. 5.6. 6.

    Resistance Measurement

    Sl. V I RdcNo. (V) (A) ()123456

    Division of Electrical Engineering, S.O.E., CUSAT 15

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Sample Graph:

    V

    0

    f

    r

    o

    m

    O

    C

    T

    e

    s

    t

    (

    V

    )

    I

    a

    f

    r

    o

    m

    S

    C

    T

    e

    s

    t

    (

    A

    )

    Equations and Calculations:

    EMF Method

    Synchronous Impedance Zs =E0Isc

    = : : : : : :

    AC resistance of armature Ra = 1:2 16

    6XSl:No:=1

    Rdc = : : : : : :

    1. Lagging p.f.

    E0 =p(V cos+ IRe)2 + (V sin+ IXs)2

    2. Unity p.f.E0 =

    p(V + IRe)2 + (IXs)2

    Division of Electrical Engineering, S.O.E., CUSAT 16

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    3. Leading p.f.E0 =

    p(V cos+ IRe)2 + (V sin IXs)2

    MMF MethodThe students are expected to complete this section by themselves and write it in thelaboratory record.

    Result:

    Division of Electrical Engineering, S.O.E., CUSAT 17

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Experiment No.: 6

    V CURVES AND INVERTED V CURVES OFSYNCHRONOUS MOTOR

    Aim:

    To obtain V and inverted V curves of the given synchronous motor.

    Machine Details:

    Refer name plate of the machine.

    Precautions:

    1. Synchronizing switch should be in open position.

    2. The synchronous machine eld regulator should be in maximum resistance positionat the time of starting.

    3. The DC machine eld regulator should be in minimum resistance position at thetime of starting.

    4. DPST and SPST switch should be in open position before giving supply to the circuit.

    5. DPDT switch should be position 1-1 when supply is switched on.

    Procedure:

    1. Close the DPST switch and start the DC machine by cutting down the starter resis-tance.

    2. Adjust the eld regulator of DC motor and drive the synchronous machine in syn-chronous speed.

    3. Close TPST switch and note down the supply voltage level using voltmeter Vs.

    4. Close SPST switch and increase the eld current of the synchronous machine suchthat the terminal voltage becomes the same as supply voltage i.e., VL=Vs.

    5. Observe the manner in which the lamps (across the synchronizing switch) are glowing.

    6. If the 3 sets of lamps become bright and dark one after another (indicating wrongphase sequence) bring the TPST switch to open position.

    7. Bring the eld rheostat of the synchronous machine to minimum position.

    8. Open SPST switch and interchange any two terminal connection on the TPST switch.Follow steps 4 and 5.

    9. If the 3 sets of lamps become bright and dark simulataneously, the phase sequence iscorrect.

    10. Reduce the rate of ickering of synchronizing lamps as low as possible by adjustingthe DC motor eld energizing rheostat.

    Division of Electrical Engineering, S.O.E., CUSAT 18

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    11. Close the synchronizing switch at the middle of the dark period of the lamps.

    12. Open DPDT switch. The synchronous machine will now work as synchronous motorand the DC machine will work as a self-excited DC shunt generator.

    13. For this no load position, the exciting eld current of synchronous motor is variedin steps till the ammeter reads the rated line current. The meter readings are noteddown for each eld current.

    14. Put the switch to 2-2 position and apply a constant load by using loading rheostatRL.

    15. Vary the eld current and note down the eld current and armature current. Repeatthe same for dierent loads.

    Circuit Diagram:

    2

    2

    0

    V

    D

    .

    C

    .

    D

    P

    S

    T

    4

    1

    5

    V

    ,

    5

    0

    H

    z

    3

    (

    0

    3

    0

    0

    V

    )

    M

    C

    (

    0

    2

    0

    A

    )

    M

    C

    Observation Table:

    No Load Load Current = : : : : : :ASl. Ia If I/P cos

    Ia If I/P cosNo. (A) (A) (W) (A) (A) (W)1.2.3.4.5.6.

    Division of Electrical Engineering, S.O.E., CUSAT 19

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Equations and Calculations:

    Armature Current Ia = : : : : : :A

    Field Current If = : : : : : :A

    Power Factor cos =I=Pp3VLIa

    = : : : : : :

    Result:

    Division of Electrical Engineering, S.O.E., CUSAT 20

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Experiment No.: 7

    NO LOAD AND BLOCKED ROTOR TEST ONSQUIRREL CAGE INDUCTION MOTOR

    Aim:

    To conduct no load and blocked rotor test on squirrel cage induction motor and to drawits equivalent circuit and circle diagram.

    Machine Details:

    Refer name plate of the machine.

    Precautions:

    1. The autotransformer should be in minimum position while switching on the supply.

    2. The motor should not be on load while starting.

    Procedure:

    No Load Test

    1. After taking care of the precautions, switch on the supply.

    2. Adjust the autotransformer gradually such that the rated voltage is applied to thestator.

    3. Note down all the meter readings under no-load condition.

    4. Reduce the autotransformer to minimum position.

    5. Switch o the supply.

    Blocked rotor test

    1. After taking care of the precautions, switch on the supply with the rotor blocked.

    2. Adjust the autotransformer till the rated current ows through the stator.

    3. Take all the meter readings.

    4. Reduce the autotransformer to minimum position.

    5. Switch o the supply.

    Division of Electrical Engineering, S.O.E., CUSAT 21

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Circuit Diagram:

    4

    4

    0

    V

    ,

    5

    0

    H

    z

    3

    Figure 6: Circuit diagram for no-load test.

    4

    4

    0

    V

    ,

    5

    0

    H

    z

    3

    Figure 7: Circuit diagram for blocked rotor test.

    3

    0

    V

    D

    C

    Figure 8: Measurement of stator resistance.

    Division of Electrical Engineering, S.O.E., CUSAT 22

  • Lab Manual: Electrical Machines Laboratory II (EE 706) 2006 Scheme

    Observation Table:

    No-load test

    Sl. V0 I0 W1 W2 W0No. (V) (A) (W) (W) (W)123456

    Blocked rotor test

    Sl. Vsc Isc W1 W2 WscNo. (V) (A) (W) (W) (W)123456

    Stator Resistance

    Sl. V I RaNo. (V) (A) ()123456

    Division of Electrical Engineering, S.O.E., CUSAT 23