TEKNISK
IN
FORMATION
The E ljo I nstallationb us consists of a two-wire bus cable
and connected bus-adapted installation units, such as
sensors, electrical units, and system components. E ljo
Installationbus units are certified by E IB A according to
European Installation Bus (EIB) standards.
Sensors convert information and send it out on the
bus cable in the form of data telegrams . Sensors could
include rocker switches and binary inlets for the
connection of potential free contacts.
The electrical units receive dat a t elegrams and convert
these to connection a nd dimmer signals. Examples of
electrical units are breakers, dimmers, and a nalogue
outlets.
System-units and components are needed to operate
the system. These are primarily current supply forgenerat ing bus volta ge, connectors for bus sections, and
interfa ces for connecting progra mme-units.
The bus two-wire cable carries both informat ion and
electricity for the bus units electronics. The bus cable is
connected to ea ch bus-unit.
System information
Task-specific sensors and units are selected and consist
of bus connectors and application mod ules with
corresponding application programs.
The application progra ms are part o f E ljos product
data base and are loaded with projection andoperational start-up software ETS from the serial
interface in a P C d own via the bus and into the
participants. Eljos product dat aba se can be obtained
free of charge on request.
The E ljo I nstallationb us is a decentra lised bus system.
E ach unit ha s its own micro-contro ls. The units can
communicate directly via the bus, without a centra l unit.
All units are eq ual bus participants (multi-master
operation).
The CSMA/CA method is used to avo id telegram
collisions and data destruction.
The E ljo I nstallationb us runs on low tension voltage
SE LV. The bus volta ge is D C 24V (+ 6/-4V). P art icipants
using under 20V are disconnected
from the bus. D ata transfer takes
place a t a speed o f 9.6 kbit/s.
Area line
Main line
Area 12
3
56
78
4
9
1011
1213
1415
CS AC 1
LK 1
Line 1 Line 15
LC 15
CS
P 1
P 63
P 1
P 63AC . Area coupler
LC : Line couplerP: Participants
CF: Current supply
Current supply
CS
Wind meterM ovementdetector
L ightsensor
Rockerswitch
L ightingM otors
Curtains/
blinds
H eat/climate/
ventilation
Bus cable
230/400V
ELJO
INSTALLATIONSBUS
Eljo Installationbus-EIB
TopologyThe E ljo I nstallationb us is divided into sections with a
hierarchical structure. The smallest unit is the line.
A line conta ins a maximum of 64 bus participants (D )
and a current supply with o utlet. (SF). Through line
couplers (LC), which are connected together via a main
line, up to 15 lines can be connected. These form an
area . In larger installations, up to 15 area s be
connected via a n area couplers (AC ). The main lines
and area lines require their own power supply with
outlet.
More tha n 14,400 bus participants can be connected
to the Eljo Installationbus if all lines and areas are put
into use.
-
+
B ackbone Line
-
7/28/2019 eib53_e
2/4189
TEKNISK
IN
FORMATION
ELJO
INSTALLATIONSBUS
Connection of units
Busskopplarenhet
A pplikationsmodul
El jo I nstallation bus - EI B i n Tr end design El jo I nstallation bus - EI B i n D ecora design
The bus installation units consist of:
1. B us connectors
2. Application modules3. Application programs
Info rmat ion which is to be processed reaches the bus
connector via the b us. This sends and receives da ta ,
ensures the supply of power to the electronics, and
stores important data, e.g. its own physical address.
The bus connector a lso stores the a pplicat ion progra m
with its ow n para meters and group a ddresses.
The application module and application progra m
define the bus participants function. The application
program and application module must be tuned to each
other. The functioning of a unit is guara nteed only oncondition that the bus connector, application module,
and application program originate from E ljo.
Units in Trend designThese units are supplied complete and consist of inset
(application module and bus connector integrated into
a unit), supporting fra me, 1-compartment Trend fra me,
and bus connection clamps (exception: room
thermostat PI flush where t he application module andflush mounted bus connector are ordered separately).
The supporting fra me is screwed onto a mounting box
or surface box and the inset a nd Trend frame a re then
snapped onto the supporting frame.
Units in Decora design
The application mod ule and bus connector a re of stick-
in design. The a pplication module, flush bus connector,
and D ecora frame a re ordered separately. The bus
connector is fitted into the mount ing box or surface
box and the application module and D ecora frame are
then pressed on over the bus connector.
Units in flush (not design products), surfaceand built-in designs
The units have integra ted d esign with bus connector
and application mo dule in a single casing. The bus
connection is supplied w ith bus connecting clamp.
-
7/28/2019 eib53_e
3/4
-
7/28/2019 eib53_e
4/4191
TEKNISK
IN
FORMATION
ELJO
INSTALLATIONSBUS
P 1
P 2
P 22
P 23
P 24
P 42
P 43
P 44
P 62
350 m
300 m
350 m
Current supply
Summary ofsystem data
AddressingFor E IB addressing, a distinction is made betw een the
physical a ddress and the group add ress. The physicaladdressis the eq uivalent of the bus participants nameand is given as Area . Line. Pa rticipant (e.g. 5.4.23).
The group addressestablishes the identity o f the buspart icipant s. With the exception o f servicing and
progra mming measures, a part icipant is alwa ys called
up via it s group a ddress/es. The group address isdivided into up to 15 main groups, each with a maxi-
mum of 2048 sub-groups. This is denot ed b y the
structure Ma in group/Sub-group (e.g. 1/127).
Wiring specifications:The following types of w iring can be used as bus
wiring:
Type Construction Placing
YCYM2 x 2 x 0,8
J-Y (St)Y 2 x 2 x 0,8
in EI B -design*
EI B A guideline
(Base: D IN VDE
0207 and 0815)
Wire red (+ EIB )
black (-EIB )
yellow (reserve)
white(reserve)
D IN VD E 0815
(Ba se: D IN VD E 0915)
Wire red (+EIB)black (-EIB )
yellow (reserve)
white(reserve)
Fixed installation:In dry, damp, and
wet spaces, surface,
flush, and in pipes.
Outdo ors, if
protected from
direct sunlight.
Fixed installationIn dry and damp
operationa l spaces,
surface, flush, and in
pipes.
Outdo ors, flush.
Wiring lengthWhen installing bus wiring, the fo llowing values must be
observed:
Max wiring length between voltage supply and bus
participants: 350m
Max wiring length between tw o bus part icipant s: 700m
Tota l length of wiring in one line: 1000m
* The D IN VD E 0829 sta nda rd specifies 4 kV a s the
value for test-voltage for a further test between wiring
and external surface areas a ccording to D IN VD E 0472
part 508. It can be expected that this value will be
changed to 2.5 kV within the framewo rk for E uropean
harmonisation.
If the bus wirings second, yellow -white (reserve)
wire pa ir is used, the f ollowing points should be
noted:
Only SEL V low voltage is permitted.
Max. permitted permanent current 2.5A(short-circuit and overload protection required).
Speech transference is permitted, but not as
telephone wire in public telephone netw ork.
There must be no erroneous exchanging in the wiring
used.
Transfer medium: Twisted pair cable
Functions: Connection, control, regulating,
display, measuring, indicato r,monitoring
No. of participants 64
in one line:
No . o f lines per a rea : ma x. 15 + 1 ma in line
Number of areas: max. 15
B us wiring: Standard telecommunication
circuit , J -Y (ST) 2x2x0.8, and/or
MSR-wiring, YCYM 2x2x0.8.
One w ire pair for signal transfer
and volta ge supply. One wire
pair as reserve
Length o f w ire per line: max. 1000 m
D ista nce pa rticipa nt- ma x. 350 m
voltage supply:
Wiring structure: L ine, sta r or tree structure, or
combinations there of
A ddressing: Individual units or functions
B us ma na gement: Multi-ma ster opera tion, i.e. ea ch
participant is equal, no central
unit. D ecentralised accessibility,
CSMA /CA principle (collision
detection and resolution without
loss of telegram)
Tra nsf er techno lo gy : Seria l t elegra m tra nsf er,baseband, Twisted pair
technology, symmetric transfer
Transfer speed: 9.6 kbits/s
Feed voltage: D C 24V (+ 6/-4 V), short-circuit
protection, low voltage
protection (SE LV), 100 ms
buffered
Operating -5C to + 45C
temperature:
D isturba nce (E MV ) Sta nda rds a nd guidelines
according to IEC and VD E