    The E ljo I nstallationb us consists of a two-wire bus cable

    and connected bus-adapted installation units, such as

    sensors, electrical units, and system components. E ljo

    Installationbus units are certified by E IB A according to

    European Installation Bus (EIB) standards.

    Sensors convert information and send it out on the

    bus cable in the form of data telegrams . Sensors could

    include rocker switches and binary inlets for the

    connection of potential free contacts.

    The electrical units receive dat a t elegrams and convert

    these to connection a nd dimmer signals. Examples of

    electrical units are breakers, dimmers, and a nalogue

    outlets.

    System-units and components are needed to operate

    the system. These are primarily current supply forgenerat ing bus volta ge, connectors for bus sections, and

    interfa ces for connecting progra mme-units.

    The bus two-wire cable carries both informat ion and

    electricity for the bus units electronics. The bus cable is

    connected to ea ch bus-unit.

    System information

    Task-specific sensors and units are selected and consist

    of bus connectors and application mod ules with

    corresponding application programs.

    The application progra ms are part o f E ljos product

    data base and are loaded with projection andoperational start-up software ETS from the serial

    interface in a P C d own via the bus and into the

    participants. Eljos product dat aba se can be obtained

    free of charge on request.

    The E ljo I nstallationb us is a decentra lised bus system.

    E ach unit ha s its own micro-contro ls. The units can

    communicate directly via the bus, without a centra l unit.

    All units are eq ual bus participants (multi-master

    operation).

    The CSMA/CA method is used to avo id telegram

    collisions and data destruction.

    The E ljo I nstallationb us runs on low tension voltage

    SE LV. The bus volta ge is D C 24V (+ 6/-4V). P art icipants

    using under 20V are disconnected

    from the bus. D ata transfer takes

    place a t a speed o f 9.6 kbit/s.

    Area line

    Main line

    Area 12

    3

    56

    78

    4

    9

    1011

    1213

    1415

    CS AC 1

    LK 1

    Line 1 Line 15

    LC 15

    CS

    P 1

    P 63

    P 1

    P 63AC . Area coupler

    LC : Line couplerP: Participants

    CF: Current supply

    Current supply

    CS

    Wind meterM ovementdetector

    L ightsensor

    Rockerswitch

    L ightingM otors

    Curtains/

    blinds

    H eat/climate/

    ventilation

    Bus cable

    230/400V

    ELJO

    INSTALLATIONSBUS

    Eljo Installationbus-EIB

    TopologyThe E ljo I nstallationb us is divided into sections with a

    hierarchical structure. The smallest unit is the line.

    A line conta ins a maximum of 64 bus participants (D )

    and a current supply with o utlet. (SF). Through line

    couplers (LC), which are connected together via a main

    line, up to 15 lines can be connected. These form an

    area . In larger installations, up to 15 area s be

    connected via a n area couplers (AC ). The main lines

    and area lines require their own power supply with

    outlet.

    More tha n 14,400 bus participants can be connected

    to the Eljo Installationbus if all lines and areas are put

    into use.

    -

    +

    B ackbone Line

  • 7/28/2019 eib53_e

    2/4189

    TEKNISK

    IN

    FORMATION

    ELJO

    INSTALLATIONSBUS

    Connection of units

    Busskopplarenhet

    A pplikationsmodul

    El jo I nstallation bus - EI B i n Tr end design El jo I nstallation bus - EI B i n D ecora design

    The bus installation units consist of:

    1. B us connectors

    2. Application modules3. Application programs

    Info rmat ion which is to be processed reaches the bus

    connector via the b us. This sends and receives da ta ,

    ensures the supply of power to the electronics, and

    stores important data, e.g. its own physical address.

    The bus connector a lso stores the a pplicat ion progra m

    with its ow n para meters and group a ddresses.

    The application module and application progra m

    define the bus participants function. The application

    program and application module must be tuned to each

    other. The functioning of a unit is guara nteed only oncondition that the bus connector, application module,

    and application program originate from E ljo.

    Units in Trend designThese units are supplied complete and consist of inset

    (application module and bus connector integrated into

    a unit), supporting fra me, 1-compartment Trend fra me,

    and bus connection clamps (exception: room

    thermostat PI flush where t he application module andflush mounted bus connector are ordered separately).

    The supporting fra me is screwed onto a mounting box

    or surface box and the inset a nd Trend frame a re then

    snapped onto the supporting frame.

    Units in Decora design

    The application mod ule and bus connector a re of stick-

    in design. The a pplication module, flush bus connector,

    and D ecora frame a re ordered separately. The bus

    connector is fitted into the mount ing box or surface

    box and the application module and D ecora frame are

    then pressed on over the bus connector.

    Units in flush (not design products), surfaceand built-in designs

    The units have integra ted d esign with bus connector

    and application mo dule in a single casing. The bus

    connection is supplied w ith bus connecting clamp.

  • 7/28/2019 eib53_e

    3/4

  • 7/28/2019 eib53_e

    4/4191

    TEKNISK

    IN

    FORMATION

    ELJO

    INSTALLATIONSBUS

    P 1

    P 2

    P 22

    P 23

    P 24

    P 42

    P 43

    P 44

    P 62

    350 m

    300 m

    350 m

    Current supply

    Summary ofsystem data

    AddressingFor E IB addressing, a distinction is made betw een the

    physical a ddress and the group add ress. The physicaladdressis the eq uivalent of the bus participants nameand is given as Area . Line. Pa rticipant (e.g. 5.4.23).

    The group addressestablishes the identity o f the buspart icipant s. With the exception o f servicing and

    progra mming measures, a part icipant is alwa ys called

    up via it s group a ddress/es. The group address isdivided into up to 15 main groups, each with a maxi-

    mum of 2048 sub-groups. This is denot ed b y the

    structure Ma in group/Sub-group (e.g. 1/127).

    Wiring specifications:The following types of w iring can be used as bus

    wiring:

    Type Construction Placing

    YCYM2 x 2 x 0,8

    J-Y (St)Y 2 x 2 x 0,8

    in EI B -design*

    EI B A guideline

    (Base: D IN VDE

    0207 and 0815)

    Wire red (+ EIB )

    black (-EIB )

    yellow (reserve)

    white(reserve)

    D IN VD E 0815

    (Ba se: D IN VD E 0915)

    Wire red (+EIB)black (-EIB )

    yellow (reserve)

    white(reserve)

    Fixed installation:In dry, damp, and

    wet spaces, surface,

    flush, and in pipes.

    Outdo ors, if

    protected from

    direct sunlight.

    Fixed installationIn dry and damp

    operationa l spaces,

    surface, flush, and in

    pipes.

    Outdo ors, flush.

    Wiring lengthWhen installing bus wiring, the fo llowing values must be

    observed:

    Max wiring length between voltage supply and bus

    participants: 350m

    Max wiring length between tw o bus part icipant s: 700m

    Tota l length of wiring in one line: 1000m

    * The D IN VD E 0829 sta nda rd specifies 4 kV a s the

    value for test-voltage for a further test between wiring

    and external surface areas a ccording to D IN VD E 0472

    part 508. It can be expected that this value will be

    changed to 2.5 kV within the framewo rk for E uropean

    harmonisation.

    If the bus wirings second, yellow -white (reserve)

    wire pa ir is used, the f ollowing points should be

    noted:

    Only SEL V low voltage is permitted.

    Max. permitted permanent current 2.5A(short-circuit and overload protection required).

    Speech transference is permitted, but not as

    telephone wire in public telephone netw ork.

    There must be no erroneous exchanging in the wiring

    used.

    Transfer medium: Twisted pair cable

    Functions: Connection, control, regulating,

    display, measuring, indicato r,monitoring

    No. of participants 64

    in one line:

    No . o f lines per a rea : ma x. 15 + 1 ma in line

    Number of areas: max. 15

    B us wiring: Standard telecommunication

    circuit , J -Y (ST) 2x2x0.8, and/or

    MSR-wiring, YCYM 2x2x0.8.

    One w ire pair for signal transfer

    and volta ge supply. One wire

    pair as reserve

    Length o f w ire per line: max. 1000 m

    D ista nce pa rticipa nt- ma x. 350 m

    voltage supply:

    Wiring structure: L ine, sta r or tree structure, or

    combinations there of

    A ddressing: Individual units or functions

    B us ma na gement: Multi-ma ster opera tion, i.e. ea ch

    participant is equal, no central

    unit. D ecentralised accessibility,

    CSMA /CA principle (collision

    detection and resolution without

    loss of telegram)

    Tra nsf er techno lo gy : Seria l t elegra m tra nsf er,baseband, Twisted pair

    technology, symmetric transfer

    Transfer speed: 9.6 kbits/s

    Feed voltage: D C 24V (+ 6/-4 V), short-circuit

    protection, low voltage

    protection (SE LV), 100 ms

    buffered

    Operating -5C to + 45C

    temperature:

    D isturba nce (E MV ) Sta nda rds a nd guidelines

    according to IEC and VD E