Efficiencies of High Density Cabling & ConnectivityTIA Data Center Workshop
Oct 17, 2017Jim DavisRegional Marketing EngineerFluke Networks
![Page 2: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/2.jpg)
Agenda• Intro to Fluke Networks• Typical Connectors used in Data Centers
• Single Fiber SC, LC• Ribbon Fiber MPO/MTP
• Certification and Field Testing of Installed Links• Tier I – Loss (Attenuation Testing) budgets• Tier II testing – OTDR and Troubleshooting
2
![Page 3: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/3.jpg)
Who We AreFluke Networks is the worldwide leader in certification, troubleshooting, and installation tools for professionals who install and maintain critical network cabling infrastructure.
We help network professionals ensure the performance and reliability of our connected world.
Datacom Contractors
Datacenter / Network Managers
Communications Service Technicians
![Page 4: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/4.jpg)
Fiber Connector Types
![Page 5: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/5.jpg)
Different fibers and fiber connectors• Most Common Today are LC and SC for duplex/serial transmission• MPO/MTP connectors for high density and parallel transmission• Single Mode or Multimode – jacket color• Multimode 50 µm or 62.5µm – do not mix
SCLC
24 fiber MPO MPO Cassette
![Page 6: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/6.jpg)
16 Fiber – For SAN market, where switch & director blades come in eight fiber increments
24 Fiber – High density for the data center server side
Also available in more “rows” 36, 48, even higher fiber counts
12 Fiber – For plug and play cassettes in datacom environment
Also available in 8 and 10 fiber, but the form factor is the same
Multi-Fiber Connectors (MPO/MTP)
Notice PinnedAnd Unpinned
![Page 7: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/7.jpg)
MPO Connectors offer flexibility in current and future deployments
High Density Ports on Switches can be Broken out in to Smaller Fiber Counts for Servers
7
![Page 8: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/8.jpg)
Field Certification of Installed Fibers
![Page 9: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/9.jpg)
Please be sure to Inspect ALL Connectors before installing, clean them if necessary
9
Video Microscope Clean Fiber End-face Finger Print on Fiber End-face
![Page 10: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/10.jpg)
Tier One Testing Confirms how much Light is Lost in Transmission – “a Loss Budget”
Traditional Duplex field tester
Dedicated MPO field tester
![Page 11: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/11.jpg)
Optical Loss Test Set (OLTS) for Two Fibers
11
Multimode Light Source
Single-mode Light Source
Power MeterFor SingleAnd Multi-mode
![Page 12: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/12.jpg)
Field Tester with MPO Port Light Source and Power Meter
12
![Page 13: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/13.jpg)
Loss Budget Calculated from TIA/ISO Specifications “Length Dependent” vs IEEE/Application specifications
• Cabling specifications have a variable loss budget
# Connectors * X dB +# Splices * Y dB +Km of Fiber * Z dB/km += Total Loss Budget
• Application Limits are based on fixed values for loss and distance
• Gigabit Ethernet allows 3.5 dB of loss and 500 meters
• 10 Gigabit Ethernet allows 2.6 dB of loss and 300 meters
• 40/100 Gigabit Ethernet allow 1.4 dB of loss and 150 meters
The best solution is to choose a custom loss budget that takes into account element of both limits – variable budgets based on the length and number of components, without exceeding the application limits
![Page 14: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/14.jpg)
A Test Result!
14
![Page 15: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/15.jpg)
A Test Result! – Did the Test Pass?
15
Yes!
![Page 16: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/16.jpg)
A Test Result! What Test Limit was Passed?
16
TIA Length Based Limit for Multimode Fiber
![Page 17: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/17.jpg)
Finding the distance to a fault with an OTDR
![Page 18: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/18.jpg)
18
OTDR in Action
The OTDR measures reflected energy and NOT the transmitted light level.
Distance
Loss
![Page 19: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/19.jpg)
A Bad Fiber – Problem at 107 meters
![Page 20: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/20.jpg)
A Good Fiber
![Page 21: Efficiencies of High Density Cabling & Connectivity TIA ... · PDF fileswitch & director blades come ... (OLTS) for Two Fibers 11 Multimode Light ... A Test Result! What Test Limit](https://reader033.vdocuments.us/reader033/viewer/2022042708/5a7979727f8b9a22028b5abc/html5/thumbnails/21.jpg)
In Conclusion• MPO/MTP connectors work well for parallel transmissions• LC connectors are the trend for duplex transmissions• Inspection and cleaning are the first steps in troubleshooting• Tier I loss testing is essential to confirm that installed fiber will
support your applications• Consider using a custom loss budget
• Use an OTDR for Troubleshooting to find the distance to the fault