ef205, ef370 electronic overload relays 63 to 380 a
TRANSCRIPT
2CD
C10
7040
C02
01
C2 | ABB
EF205, EF370 electronic overload relays63 to 380 A
DescriptionThe EF205 and EF370 are self-supplied electronic overload relays, which means no extra external supply is needed. It offers reliable protection for motors in the event of overload or phase failure. Easy to use like a thermal overload relay and compatible with standard motor applications, the electronic overload relay is convincing, above all, due to its wide setting range, high accuracy, high operational temperature range and the possibility to select a trip class (10E, 20E, 30E). Further features are the temperature compensation, trip contact (N.C.), signal contact (N.O.), automatic or manual reset selectable, trip-free mechanism, STOP and TEST function and a trip indication. The overload relays are connected directly to the contactors.
Ordering detailsSetting range Short-circuit
protective device Trip class Type Order code Weight
(1 pce)A kg63 ... 210 1250 A, Fuse type gG 10E, 20E, 30E EF205-210 1SAX531001R1101 1.210
115 ... 380 1600 A, Fuse type gG 10E, 20E, 30E EF370-380 1SAX611001R1101 1.430
2CD
C23
1010
V00
12
EF205-210
2CD
C23
1013
V00
12
EF370-380
Main dimensions mm, inches
105 4.13"
7.4 0.29" 17.9 0.7"
18.5
0.
73"
5 0.
2"
11
0.43
"
122
4.
8"
151
5.
9"10
0.
39"
17.5 0.69"
35 1.38"
Ø 8.5 Ø 0.33"
10
0.39
"
30 1.18" 5 0.2"
116.5 4.59"
122.8 4.83"
5 0.2"35 1.38"
121.7 4.79"35 1.38"
2CD
C23
2004
F001
2
EF205-210
122.8 4.83"
30 1.18"
116.5 4.59"
5 0.2"
35 1.38" 5 0.2"
121.7 4.79"
14
0.55
"16
3.6
6.
4"10
0.
39"
22.8
0.
9"
93.8
3.
69"
7.4 0.29"
105 4.13"
17.9 0.7"
20 0.79"
43.8 1.72"43.8 1.72"
Ø 11 Ø 0.43"
11
0.43
"
122
0.
4'5 0
.2"
2CD
C23
2005
F001
2
EF370-380
2CD
C10
7040
C02
01
ABB | C3
Main circuit – Utilization characteristics according to IEC/EN
Type EF205, EF370
Standards IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1Rated operational voltage Ue 1000 V ACRated frequency 50/60 HzTrip class 10E, 20E, 30E, selectableNumber of poles 3Duty time 100 %Operating frequency without early tripping Up to 15 operations/h, see "Technical diagram – Intermittent periodic duty"Rated impulse withstand voltage Uimp 8 kVRated insulation voltage Ui 1000 V
Auxiliary circuit according to IEC/EN
Type EF205, EF370Rated operational voltage Ue 600 V AC / DCConventional free air thermal current Ith 6 ARated frequency DC, 50/60 HzNumber of poles 1 N.C. + 1 N.O.Ie / Rated operational current AC-15acc. to IEC/EN 60947-5-1 for utilization category
110-120 V 50/60 Hz 3.00 A220-230-240 V 50/60 Hz 3.00 A400 V 50/60 Hz 1.10 A480-500 V 50/60 Hz 0.75 A
Ie / Rated operational current DC-13acc. to IEC/EN 60947-5-1 for utilization category
24 V 1.50 A60 V 0.55 A110-120-125 V 0.55 A250 V 0.27 A
Minimum switching capacity 12 V / 3 mAShort-circuit protective device 6 A, Fuse type gGRated impulse withstand voltage Uimp 6 kVRated insulation voltage Ui 690 V
Technical diagram – Intermittent periodic duty
140
120
0
20
40
60
80
100
0 20 40 60 80 100 (%)
t = 1 s
a
t = 1.5 s
a
t = 3 sa
t = 5 sa
t = 0.5 sa
duty ratio
switc
hing
freq
uenc
y
(Op/h)
2CD
C23
2005
F021
1
ta: Motor starting time
EF205, EF370 electronic overload relaysTechnical data
2CD
C10
7040
C02
01
C4 | ABB
Main circuit – Utilization characteristics according to UL/CSA
Type EF205, EF370Standards UL 508, CSA 22.2 No. 14, UL 60947-4-1AMaximum operational voltage 600 V ACTrip rating 125 % of FLAFull load amps (FLA) See table "Full load amps and short-circuit protective device"Short-circuit rating RMS symmetrical See table "Full load amps and short-circuit protective device"Short-circuit protective device See table "Full load amps and short-circuit protective device"
Auxiliary circuit according to UL/CSA
Type EF205, EF370Contact rating N.C., 95-96 B600, Q600
N.O., 97-98 B600, Q600Conventional thermal current 6 A
Full load amps and short-circuit protective device
Type Full load amps (FLA) Short-circuit protective device
480 V AC 600 V ACSCCR Fuse type SCCR Fuse type SCCR Fuse type
EF205-210 210 A 10 kA 400 A, R5/RK5 10kA 400 A, R5/RK5 100 kA 400 A, JEF370-380 380 A 18 kA 800 A, L/T 18kA 800 A, L/T - -
EF205, EF370 electronic overload relaysTechnical data
2CD
C10
7040
C02
01
ABB | C5
General data
Type EF205, EF370Pollution degree 3Phase loss sensitive YesAmbient air temperature
Operation Open - compensated acc. to IEC/EN 60947-4-1 -25 ... +70 °CStorage -50 ... +85 °C
Ambient air temperature compensation Acc. to IEC/EN 60947-4-1Maximum operating altitude permissible 2000 mResistance to shock acc. to IEC 60068-2-27 25 g / 11 msResistance to vibrations acc. to IEC 60068-2-6 5 g / 3 … 150 HzMounting position Position 1-6Mounting Mount on the contactor and tighten the screws of the main circuit terminalsDegree of protection housing IP20
main circuit terminals IP00
Electrical connection
Main circuitType EF205 EF370Connecting capacity
Rigid 1 x2 x
16 ... 185 mm²16 ... 120 mm²
50 ... 240 mm²50 ... 150 mm²
Flexible 1 x2 x
16 ... 185 mm²16 ... 120 mm²
50 ... 240 mm²50 ... 150 mm²
Lugs L ≤ 24 mm 32 mmBars Ø > 8 mm 10 mmStranded acc. to UL/CSA 1 x
2 xAWG 6-0000AWG 6-0000
AWG 1-500 kcmilAWG 1-500 kcmil
Flexible acc. to UL/CSA 1 x2 x
AWG 6-0000AWG 6-0000
AWG 1-500 kcmilAWG 1-500 kcmil
Stripping length - -Tightening torques 18 Nm / 160 lb.in 28 Nm / 247 lb.in
Connection screw M8 M10
Auxiliary circuitType EF205, EF370Connecting capacity
Rigid 1 or 2 x 1 ... 4 mm²Flexible with ferrule 1 or 2 x 0.75 ... 2.5 mm²Flexible with insulated ferrule 1 or 2 x 0.75 ... 2.5 mm²Flexible 1 or 2 x 0.75 ... 2.5 mm²Stranded acc. to UL/CSA 1 or 2 x AWG 18-10Flexible acc. to UL/CSA 1 or 2 x AWG 18-10
Stripping length 9 mmTightening torques 0.8 ... 1.2 Nm / 7 ... 11 Ib.inConnection screw M3.5 (Pozidriv 2)
EF205, EF370 electronic overload relaysTechnical data