Power systembasics
-
7/25/2019 EE6702-Protection and Switchgear R2013
4/356
Electric Power SystemElectric Power System
Electricity is generated at a power plant (1),voltage is stepped-up for transmission(2)
Energy travels along a transmission line to the area where the power is needed (3)
voltage is decreased or stepped-down, at another substation (4),& a distribution power line (5)
carries that electricity until it reaches a home or business (6).
-
7/25/2019 EE6702-Protection and Switchgear R2013
5/356
SINGLE LINE DIAGRAM
-
7/25/2019 EE6702-Protection and Switchgear R2013
6/356
INTRODUCTION
UNITUNIT
11
6
Presented byC.GOKUL,AP/EEE
Velalar College of Engg & Tech , Erode
-
7/25/2019 EE6702-Protection and Switchgear R2013
7/356
UNIT 1 PROTECTION SCHEMES
Syllabus
Principles and need for protective schemes
Nature and causes of faults
Types of faults
components
Methods of Neutral groundingZones of protection and essential qualities of
protection
Protection schemes 7
-
7/25/2019 EE6702-Protection and Switchgear R2013
8/356
Principles & need forprotective schemes
8Presented by C.GOKUL,AP/EEE, Velalar College of Engg & Tech , Erode
-
7/25/2019 EE6702-Protection and Switchgear R2013
9/356
PROTECTION SYMBOL
t w o - w i n d i n gt r a n s f o r m e r
c u r r e n t t r a n s f o r m e r
t w o - w i n d i n g
t r a n s f o r m e r
g e n e r a t o r
v o l t a g e t r a n s f o r m e r
c a p a c i t o r
t r a n s m i s s i o n l i n e
d e l t a c o n n e c t i o n
w y e c o n n e c t i o n
c i r c u i t b r e a k e r
f u s e
s u r g e a r r e s t o r
s t a t i c l o a d d i s c o n n e c t
-
7/25/2019 EE6702-Protection and Switchgear R2013
10/356
Primary Equipment & ComponentsPrimary Equipment & Components
Transformers - to step up or step down voltage level
Breakers - to energize equipment and interrupt fault current to
isolate faulted equipment
Insulators - to insulate equipment from ground and other phases
Isolators (switches) - to create a visible and permanent isolation
of primary equipment for maintenance purposes and route power
flow over certain buses.
Bus - to allow multiple connections (feeders) to the same source
of power (transformer).
-
7/25/2019 EE6702-Protection and Switchgear R2013
11/356
Primary Equipment & ComponentsPrimary Equipment & Components
Grounding - to operate and maintain equipment safely
Arrester - to protect primary equipment of sudden overvoltage
(lightning strike).
Switchgear integrated components to switch, protect, meter
and control ower flow
Reactors - to limit fault current (series) or compensate for charge
current (shunt)
VT and CT - to measure primary current and voltage and supply
scaled down values to P&C, metering, SCADA, etc.
Regulators - voltage, current, VAR, phase angle, etc.
-
7/25/2019 EE6702-Protection and Switchgear R2013
12/356
Why A System Needs Protection?
There is no fault free system.
Ensure safety of personnel.
Usually faults are caused by breakdown
system over current, over voltage,
lighting, etc.
-
7/25/2019 EE6702-Protection and Switchgear R2013
13/356
13
-
7/25/2019 EE6702-Protection and Switchgear R2013
14/356
14
-
7/25/2019 EE6702-Protection and Switchgear R2013
15/356
15
-
7/25/2019 EE6702-Protection and Switchgear R2013
16/356
POWER SYSTEM WITHOUT PROTECTION
Short circuits and other abnormal conditions
often occur on the power system. The heavy
current associated with short circuits is likely to
-
7/25/2019 EE6702-Protection and Switchgear R2013
17/356
Element of protection system
(1)Current and Voltage Transformers
(2)Relays
(3)Circuit breakers
(4)Batteries
(5)Fuses
(6)Lighting Arresters
-
7/25/2019 EE6702-Protection and Switchgear R2013
18/356
Current transformer Current transformer consists at least of two secondary windings.
The first winding is usually designed for measuring, the second is
used for protection.
The secondary of current transformers are almost connected in star
-
7/25/2019 EE6702-Protection and Switchgear R2013
19/356
Voltage transformer Voltage transformer is often consists of two windings.
The first winding is connected in star, and the stare
point must be earthed.
The second winding is connected as open delta.
VVPP
VVSS
Relay
-
7/25/2019 EE6702-Protection and Switchgear R2013
20/356
Relay Purpose Isolate controlling circuit from controlled circuit.
Control high voltage system with low voltage.
Control high current system with low current. Logic Functions
-
7/25/2019 EE6702-Protection and Switchgear R2013
21/356
Advantages for Using
Protective Relays Detect system failures when they occur
and isolate the faulted section from the
remaining of the system. Mitigating the effects of failures after
they occur.
Minimize risk of fire, danger to personaland other high voltage systems.
-
7/25/2019 EE6702-Protection and Switchgear R2013
22/356
CIRCUIT BREAKER
Low voltage circuit breaker
Magnetic circuit breaker
Medium voltage circuit breaker High voltage circuit breaker
-
7/25/2019 EE6702-Protection and Switchgear R2013
23/356
Battery bank Battery bank are called as
backbone of protection system
mergency use or power
system
-
7/25/2019 EE6702-Protection and Switchgear R2013
24/356
Fuse Fuses are selected to allow passage of normalcurrent and of excessive current only for short
periods. s use o pro ec e ow vo age or curren
rating devices
-
7/25/2019 EE6702-Protection and Switchgear R2013
25/356
Lighting arrester
A lightning arrester is a device used on
electrical power system to protect the
insulation damaging effect of lightning. All lighting arrester are earthed
-
7/25/2019 EE6702-Protection and Switchgear R2013
26/356
What is Switchgear ?
Switchgearis the combination ofswitches,fuses or circuit breakers(CB) used tocontrol , protect & isolate electrical
.
It is usedde-energizeequipment &clearfaults.
-
7/25/2019 EE6702-Protection and Switchgear R2013
27/356
Different elements of switchgear
Circuit breakerAir ckt breaker ACBVacuumed ckt breaker VCB
Oil filled ckt breaker OCB
SF6 Ckt Breaker
Load Breaking Switch LBS
By pass and changeover
switches
Isolators(switches)
MCCB (Moulded Case CktBreakers)
MCB(Miniature Circuit Breaker)
RCCB
Residual current circuit breaker
Fuses
-
7/25/2019 EE6702-Protection and Switchgear R2013
28/356
Function wise categories
Automatic & Manual operation
{ example: Circuit breaker ,MCB , MCCB }
Only automatic operation
Fuse
Only manually activated / operated
Isolator, LBS
-
7/25/2019 EE6702-Protection and Switchgear R2013
29/356
Voltage wise switchgear categories
Low voltage Switchgearup to 11KV
Medium voltage switchgear
up to 66KV Hig Vo tage switc gear
up to 400KV
Extra High Voltage switchgear
up to 765KV
HVDC Switchgear
-
7/25/2019 EE6702-Protection and Switchgear R2013
30/356
Nature and causes offaults
Types of faults
Presented by C.GOKUL,AP/EEE, Velalar College of Engg & Tech , Erode
-
7/25/2019 EE6702-Protection and Switchgear R2013
31/356
NATURE & CAUSES OF FAULTS
Insulation failure.
Conducting path failure.
Over voltages due to lightening or switching surges.unc ur ng or rea ng o nsu a ors.
Failure of conducting path due to broken conductors.
Failure of solid insulation due to aging, heat, moisture,overvoltage , accidental contact with earth or earth screens,flash over voltages and etc.,
-
7/25/2019 EE6702-Protection and Switchgear R2013
32/356
A power system fault may be defined as any
condition or abnormality of the system which
involves the electrical failure of primary
equipment such as generators, transformers,
busbars, overhead lines and cables and all other
FAULT IN POWER SYSTEM
voltage.
Electrical failure generally implies one or the
other (or both) of two types of failure, namely
insulation failure resulting in a short-circuitcondition or conducting path failure resulting in
an open-circuit condition, the former being by far
the more common type of failure.
-
7/25/2019 EE6702-Protection and Switchgear R2013
33/356
Symmetrical faultFaults giving rise to equal currents in linesdisplaced by
equal phase angles i.e 120o in three phasesystems.
Example: short circuit ofall three phase
FAULT IN POWER SYSTEM
con uctors o a ca e at a s ng e ocat on
Unsymmetrical fault
Faults in which not all the line currents are equaland not all have the same phase.
Example (any one): single phase line to groundfault (L-G), two phase to ground (LL-G) fault andphase to phase (L-L) fault.
-
7/25/2019 EE6702-Protection and Switchgear R2013
34/356
Abnormalities in PowerAbnormalities in Power
SystemsSystems
Abnormalities in PowerAbnormalities in Power
SystemsSystems
OvercurrentOvercurrent (overload, short circuit, open(overload, short circuit, open
circuit)circuit)
,,
touch potentials, step potentials)touch potentials, step potentials)
Surge VoltagesSurge Voltages (lightning strokes, switching(lightning strokes, switching
surges, harmonics)surges, harmonics)
-
7/25/2019 EE6702-Protection and Switchgear R2013
35/356
Fault Types (Shunt)
-
7/25/2019 EE6702-Protection and Switchgear R2013
36/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
37/356
Frequency of Types ofFrequency of Types of
FaultsFaults
Frequency of Types ofFrequency of Types of
FaultsFaults
Type of
Fault%
Occurrence
LL
DLG
3L
8
5
2 or less
-
7/25/2019 EE6702-Protection and Switchgear R2013
38/356
Frequency of Fault OccurrenceFrequency of Fault OccurrenceFrequency of Fault OccurrenceFrequency of Fault Occurrence
Equipment % of Total
Overhead lines
50Cables
Switchgear
Transformers
CTs and PTs
Control EquipmentMiscellaneous
10
15
12
2
38
-
7/25/2019 EE6702-Protection and Switchgear R2013
39/356
SYMMETRICAL FAULT
THREETHREE-- PHASE FAULTPHASE FAULT
FAULTFAULT
THREE PHASETHREE PHASE -- EARTHEARTHFAULTFAULT
-
7/25/2019 EE6702-Protection and Switchgear R2013
40/356
UNSYMMETRICAL FAULT
PHASEPHASE PHASE FAULTPHASE FAULT
FAULTFAULT
SINGLE PHASESINGLE PHASE -- EARTHEARTH
FAULTFAULT
-
7/25/2019 EE6702-Protection and Switchgear R2013
41/356
OPEN CIRCUIT FAULT
SINGLESINGLE-- PHASE OPENPHASE OPEN
CIRCUITCIRCUIT
TWOTWO-- PHASE OPENPHASE OPEN
CIRCUITCIRCUIT
THREETHREE-- PHASE OPENPHASE OPEN
CIRCUITCIRCUIT
-
7/25/2019 EE6702-Protection and Switchgear R2013
42/356
Equipments
&% of total fault
Causes of Faults
Over head lines
(50%)
Lighting Stroke
Earthquake
Icing
Birds
Tree branchesKite Strings
Internal Overvoltage
Under ground Cable
(9%)
Damage due to digging
Insulation failure due to temperature rise
Failure of Joints
Alternator
(7%)
Stator & Rotor faults
-
7/25/2019 EE6702-Protection and Switchgear R2013
43/356
Equipments &
% of total fault
Causes of Faults
Transformer
(10%)
Insulation Failure
Faults in tap changer
Overloading
Current Transformer
&
Potential Transformer
(12%)
Overvoltage
Insulation Failure
Break of Conductors
Wrong Connections
Switch Gear
(12%)
Insulation failure
Leakage of air/oil/gas
Mechanical defect
Lack of Maintenance
-
7/25/2019 EE6702-Protection and Switchgear R2013
44/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
45/356
Fault Minimization Improving the quality of machines, equipments,
installation etc., by improving the design techniques.
Ade uate & reliable rotection s stem control
Regular maintenance by trained professionals
Effective management of electrical plant
Presented byC.GOKUL,AP/EEE Velalar College of Engg & Tech , Erode
-
7/25/2019 EE6702-Protection and Switchgear R2013
46/356
Merits of Fast fault clearingHelps to avoidpermanent damage to equipment &
components of the apparatus
Reduces the chances of risks likefire hazards
Maintains the continuity of the power supply
Brings back the power system to the normal state
sooner
-
7/25/2019 EE6702-Protection and Switchgear R2013
47/356
Fault current
calculation using
symmetrical
components
47
-
7/25/2019 EE6702-Protection and Switchgear R2013
48/356
48
-
7/25/2019 EE6702-Protection and Switchgear R2013
49/356
49
-
7/25/2019 EE6702-Protection and Switchgear R2013
50/356
50
-
7/25/2019 EE6702-Protection and Switchgear R2013
51/356
51
-
7/25/2019 EE6702-Protection and Switchgear R2013
52/356
52
-
7/25/2019 EE6702-Protection and Switchgear R2013
53/356
53
-
7/25/2019 EE6702-Protection and Switchgear R2013
54/356
54
-
7/25/2019 EE6702-Protection and Switchgear R2013
55/356
55
-
7/25/2019 EE6702-Protection and Switchgear R2013
56/356
Regions (zones) of power system that can be protectedRegions (zones) of power system that can be protected
adequately with fault recognition and removal resulting inadequately with fault recognition and removal resulting in
isolation of a minimum amount of equipment.isolation of a minimum amount of equipment.
Zones of ProtectionZones of Protection
encompassed by at least one zoneencompassed by at least one zone
Zones of protection must overlap to prevent any systemZones of protection must overlap to prevent any system
element from being unprotected (no blind spots).element from being unprotected (no blind spots).
-
7/25/2019 EE6702-Protection and Switchgear R2013
57/356
Zones of ProtectionZones of Protection
52
87B
50/511
3
5
6
CT REQUIREMENTS FOROVERLAPPING ZONES
G42
50/51
52
87B
-
7/25/2019 EE6702-Protection and Switchgear R2013
58/356
Zones of ProtectionZones of Protection
Overlapping zones of protection
-
7/25/2019 EE6702-Protection and Switchgear R2013
59/356
1 - Bus Protection
2 - Generator Protection
3
5
Zones of ProtectionZones of Protection
G
1
2
3 - Subtrans Line Protection
4
4 - Feeder Protection
5 - Transformer Protection
-
7/25/2019 EE6702-Protection and Switchgear R2013
60/356
Feeder Protection
G
Fault
-
7/25/2019 EE6702-Protection and Switchgear R2013
61/356
us Protection
Fault
G
Presented by C.GOKUL,AP/EEE, Velalar College of Engg & Tech , Erode
-
7/25/2019 EE6702-Protection and Switchgear R2013
62/356
Transformer Protection
Fault
G
-
7/25/2019 EE6702-Protection and Switchgear R2013
63/356
Sub transmission Line Protection
Fault
G
-
7/25/2019 EE6702-Protection and Switchgear R2013
64/356
Generator Protection
G
Fault
-
7/25/2019 EE6702-Protection and Switchgear R2013
65/356
Essential Qualities of
protectionor
Requirement of Protective
y
-
7/25/2019 EE6702-Protection and Switchgear R2013
66/356
Reliability
Selectivity
assurance that the protection will
perform correctly.
maximum continuity of service with
minimum system disconnection.
To detect even the smallest fault,
current or system abnormalities and
Speed
minimum protective equipment andassociated circuitry to achieve theprotection objectives.Simplicity
minimum fault duration and
consequent equipment damage and
system instability.
operate correctly at its setting
-
7/25/2019 EE6702-Protection and Switchgear R2013
67/356
Reliability
The level of assurance that the relay will functionThe level of assurance that the relay will function
as intended.as intended.
Reliability denotes:Reliability denotes:
Dependability -- certainty of correct operationcertainty of correct operation
Security -- assurance against incorrect operationassurance against incorrect operation
Sensitivity
Relaying equipment must be sufficiently sensitiveRelaying equipment must be sufficiently sensitive
so that it will operate when requiredso that it will operate when required Must discriminate normal from abnormalMust discriminate normal from abnormal
conditions.conditions.
-
7/25/2019 EE6702-Protection and Switchgear R2013
68/356
Selectivity
Performance of protective devices to select betweenPerformance of protective devices to select between
those conditions for which prompt operation andthose conditions for which prompt operation and
those for which no operation, or time delaythose for which no operation, or time delayoperation is required.operation is required.
Isolate faulted circuit resulting in minimumIsolate faulted circuit resulting in minimum
interruptions.interruptions.
Implemented through Zone of ProtectionImplemented through Zone of Protection
Speed
Remove a fault from the power system as quicklyRemove a fault from the power system as quickly
as possibleas possible
Classification:Classification:
InstantaneousInstantaneous -- no intentional delayno intentional delay
High SpeedHigh Speed -- less than 3 cyclesless than 3 cycles
TimeTime--DelayDelay -- intentional time delayintentional time delay
-
7/25/2019 EE6702-Protection and Switchgear R2013
69/356
Methods of Neutral
grounding(OR)
Power System Earthing
Neutral Earthing/Grounding
Peterson coilArcing Grounds
-
7/25/2019 EE6702-Protection and Switchgear R2013
70/356
The process of connecting the metallic frame(i.e.non-current carrying part) of electricalequipment or some electrical partof the systemto earth (i.e. soil) is called grounding orearthing.
Grounding or earthing may be classified as :
(i) Equipment grounding
(ii) System grounding
-
7/25/2019 EE6702-Protection and Switchgear R2013
71/356
Equipment GroundingThe process of connecting non-current-carrying
metal parts of the electrical equipment to earth.
The process of connecting some electrical part of thepower system to earth (i.e. soil) is called systemgrounding.
-
7/25/2019 EE6702-Protection and Switchgear R2013
72/356
Neutral
Earthing
-
7/25/2019 EE6702-Protection and Switchgear R2013
73/356
Neutral GroundingConnecting neutral point to earth (i.e. soil) either
directly or some circuit element
(e.g. resistance, reactance , Peterson coil etc.).
Neutral grounding provides protection to equipment.
(during earth fault, the current path is completedneutral)
-
7/25/2019 EE6702-Protection and Switchgear R2013
74/356
Advantages of Neutral Grounding(i) Voltages of the healthy phases do not exceed line to
ground voltages i.e. they remain nearly constant.
(ii) The high voltages due to arcing grounds are
eliminated.iii i e o insu ation is ong.
(iv) The over voltages is reduced.
(v) It provides greater safety to personnel and equipment.
(vi) It provides improved service reliability.(vii)Operating and maintenance expenditures arereduced.
-
7/25/2019 EE6702-Protection and Switchgear R2013
75/356
Methods of Neutral Grounding(i) Solid or effective grounding
(ii) Resistance grounding
eactance groun ng
(iv) Peterson-coil grounding
(v) Voltage transformer earthing
-
7/25/2019 EE6702-Protection and Switchgear R2013
76/356
(i) Solid or effective grounding
-
7/25/2019 EE6702-Protection and Switchgear R2013
77/356
When theneutral pointof a 3-phase system isdirectly connected toearth(i.e. soil) is calledsolid grounding or effective grounding.
When an earth fault occurs between earth and
any one phase , the voltage to earth of the faultyp ase ecomes zero, u e ea y p asesremains at normal phase values.
Fault current(IF) completely nullified by
capacitive current(IC)
-
7/25/2019 EE6702-Protection and Switchgear R2013
78/356
(ii) Resistance grounding
When the neutral pointof a 3-phase system (e.g. 3-phase generator,3-phase transformer etc.) is connected to earth(i.e. soil) through a resistor,it is called resistance grounding.
-
7/25/2019 EE6702-Protection and Switchgear R2013
79/356
Advantages: By adjusting the value of R, the arcing grounds can be minimized. It improves the stability Less interference Minimize hazards
Disadvantages:
By adjusting the value of R, the arcing grounds can be minimized. It improves the stability Less interference Minimize hazards
-
7/25/2019 EE6702-Protection and Switchgear R2013
80/356
(iii) Reactance grounding
In this system, a reactance is inserted between the neutral and groundThe purpose of reactance is to limit the earth fault current.
Disadvantages :(i) In this system, the fault current required to operate the protective deviceis higher than that of resistance grounding for the same fault conditions.
(ii) High transient voltages appear under fault conditions.
-
7/25/2019 EE6702-Protection and Switchgear R2013
81/356
Presented byC.GOKUL,AP/EEE Velalar College of Engg & Tech , Erode
-
7/25/2019 EE6702-Protection and Switchgear R2013
82/356
If inductance L of appropriate value is connected in
parallel with the capacitance of the system, the faultcurrent IF flowing through L will be in phaseopposition to the capacitive current ICof the system.If L is so adjusted that
IL = ICthen resultant current in the fault will be zero. Thiscondition is known as Resonant Grounding.
When the value of L of arc suppression coil is
such that the fault current IFexactly balances thecapacitive currentIC , it is calledresonant grounding.
-
7/25/2019 EE6702-Protection and Switchgear R2013
83/356
An arc suppression coil (also called Peterson coil) is an iron-cored coilconnected between the neutral and earth.
The reactor is provided with tappings to change the inductance of thecoil.
By adjusting the tappings on the coil, the coil can be tuned with thecapacitance of the system i.e. resonant grounding can be achieved.
l d f l h l
-
7/25/2019 EE6702-Protection and Switchgear R2013
84/356
Suppose line to ground fault occurs in theline Bat point
F. The fault currentIFand capacitive currentsIRandIYwillflow as shown in Fig Note that IF flows through the Peterson coil (or Arcsuppression coil) to neutral and back through the fault. Thetotal capacitive current ICis the phasor sum of IR & IYas shown in phasor diagram in Fig.The voltage of the faulty phase is applied across the arc. ,
phase voltage by 90. The current IF is in phase opposition to capacitivecurrent IC[See Fig].
By adjusting the tappings on the Peterson coil, theresultant current in the fault can be reduced. If inductanceof the coil is so adjusted that IL= IC, then resultant currentin the fault will be zero.
-
7/25/2019 EE6702-Protection and Switchgear R2013
85/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
86/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
87/356
v. Voltage Transformer EarthingIn this method of neutral earthing , the primary of a
single-phase voltage transformer is connectedbetween the neutral and the earth as shown in Fig
across the secondary of the voltage transformer. Thevoltage transformer provides a high reactance in theneutral earthing circuit and operates virtually as an
ungrounded neutral system.
-
7/25/2019 EE6702-Protection and Switchgear R2013
88/356
Advantages:Arcing grounds are reduced.Transient overvoltage are reduced
-
7/25/2019 EE6702-Protection and Switchgear R2013
89/356
Protectionschemes
REFER BOOKPresented byC.GOKUL,AP/EEE, Velalar College of Engg & Tech , Erode
UNITUNIT
-
7/25/2019 EE6702-Protection and Switchgear R2013
90/356
Electromagnetic
UNITUNIT
22RELAY
1
Presented by
C.GOKUL,AP/EEEVelalar College of Engg & Tech , Erode
-
7/25/2019 EE6702-Protection and Switchgear R2013
91/356
2
ll b l l
-
7/25/2019 EE6702-Protection and Switchgear R2013
92/356
UNIT 2 Syllabus - Electromagnetic relays
Operating principles of relays
The Universal relay - Torque equation
R-X diagram
Electromagnetic Relays
Overcurrent relays
Directional relays
Distance relays
Differential relays
Negative sequence relays
Under frequency relays3
-
7/25/2019 EE6702-Protection and Switchgear R2013
93/356
Relay Overview
principles of relays4
-
7/25/2019 EE6702-Protection and Switchgear R2013
94/356
Relays are electricalswitches that open or closeanother circuit under certain
-
7/25/2019 EE6702-Protection and Switchgear R2013
95/356
Protective relays are devices whichmonitor power system conditions andoperate to quickly and accurately isolate
designed protective system can limitdamage to equipment, as well as minimizethe extent of associated service
interruption.
-
7/25/2019 EE6702-Protection and Switchgear R2013
96/356
Isolate controlling circuit from controlled circuit.
Control high voltage system with low voltage.
Control high current system with low current.
Logic Functions
-
7/25/2019 EE6702-Protection and Switchgear R2013
97/356
Electromagnetic Relays (EMRs)
Solid-state Relays (SSRs) There is no mechanical contacts to switch the circuit.
Microprocessor Based Relays
Commonly used in power system monitoring and protection.
-
7/25/2019 EE6702-Protection and Switchgear R2013
98/356
Electromagnetic Relays (EMRs)
Simplicity
Not expensive
Solid-state Relays (SSRs) o ec an ca movements
Faster than EMR
Microprocessor-based Relay Much higher precision and more reliable and durable.
Capable of both digital and analog I/O. Higher cost
-
7/25/2019 EE6702-Protection and Switchgear R2013
99/356
Detect system failures when they occur andisolate the faulted section from the remaining ofthe system.
Miti atin the effects of failures after the occur.Minimize risk of fire, danger to personal and
other high voltage systems.
-
7/25/2019 EE6702-Protection and Switchgear R2013
100/356
Components of Power System ProtectionComponents of Power System Protection
-
7/25/2019 EE6702-Protection and Switchgear R2013
101/356
Transducers
PT & CT
Decides whether system
quantities are normal orabnormal (Brain of the
System Protection)
CircuitPower
Components of Power System ProtectionComponents of Power System Protection
* If quantities are normal,
no signal is sent to breaker
* If quantities are abnormal,
signal is sent to breaker to
trip
These devices change
electrical quantities to
level relays can use, i.e.,
5 amperes, 115 volts
Breakerys em
-
7/25/2019 EE6702-Protection and Switchgear R2013
102/356
Rela -definitions
Primary Relay: relay connecteddirectlyin the circuit
-
7/25/2019 EE6702-Protection and Switchgear R2013
103/356
Secondary Relay: relay connected to theprotected circuitthrough CT & VT.
Auxiliary Relay: relay operate in response toopeningorclosingofanotherrelay.
Measuring Relay: It performs the measurement ofnormal&abnormalconditions in the power system.
Electro Magnetic Relay: It operates on the principle ofE ectromagnetic in uction.
Static Relay(Solid-state relay): They use diodes ,transistors,SCRs, Logic gates etc.
(Static circuit is the measuring circuit & no moving parts)
Microprocessor Based Relay: All functions of a relay candone by using microprocessor . Relays areprogrammable.
P cancompare,computeandsend tripsignals.
Thermal Relay: It operates on the principle of Electro-
-
7/25/2019 EE6702-Protection and Switchgear R2013
104/356
y p p pthermaleffect.
Distance Relay: relay measures the impedance or
reactanceoradmittance.Impedance Relay: relay measures theimpedanceof the
transmission line.
Reactance Relay: relay measures the reactance of the
transmission line.Over-current Relay: relay operates when the current
exceedsa pre-set value.
Under-voltage Relay: relay operates when the voltagefallsa pre-set value.
Directional Relay: relay able to sense whether fault lies inforwardorreverse direction.
Polarized Relay: relay depends on the directionof thecurrent.
Differential Relay: it measures the difference b/w 2 actual
-
7/25/2019 EE6702-Protection and Switchgear R2013
105/356
Differential Relay: it measures thedifferenceb/w 2 actualquantities.
Earth fault Relay: It is used for protection of element of a
power system againstEarthfaults.
Phase fault Relay: It is used for protection of element of apower system againstphasefaults.
Negative Sequence Relay: relay usesnegative sequence
currentas its actuating quantity.Zero Sequence Relay: relay useszero sequence currentas
its actuating quantity.
Presented byC.GOKUL,AP/EEE Velalar College of Engg & Tech , Erode
-
7/25/2019 EE6702-Protection and Switchgear R2013
106/356
REFER BOOK
-
7/25/2019 EE6702-Protection and Switchgear R2013
107/356
ElectromagneticRelay
18
They work on the following two main operating principles :
(i) Electromagnetic attraction(ii) Electromagnetic induction
-
7/25/2019 EE6702-Protection and Switchgear R2013
108/356
Electromagnetic Attraction Relays
(i) Attracted armature type relay
(ii) Solenoid type relay
(iii)Balanced beam type relay
19
Induction Relays / Electromagnetic
induction
(i) Induction type overcurrent Relay (Non DirectionalRelay)
(ii) Induction Cup Relay (Directional Relay)
1 Attracted Armat re T pe Rela s
-
7/25/2019 EE6702-Protection and Switchgear R2013
109/356
1. Attracted Armature Type Relays
These have a coil or
electromagnet energized by a
coil .The coil is energized by
operating quantity like V or I.
the coil cannot attract the
plunger due to spring force.
Under fault condition the fault
current increases so armature
or plunger gets attracted to
close the contacts .
-
7/25/2019 EE6702-Protection and Switchgear R2013
110/356
Attracted Armature Type RelaysThese have a coil or
electromagnet energized by a
coil .The coil is energized by
operating quantity like V or I.
Under normal conditions the coil
to spring force. Under fault
condition the fault current
increases so armature or
plunger gets attracted to close
the contacts .
Attracted Armature Type Relays
-
7/25/2019 EE6702-Protection and Switchgear R2013
111/356
Attracted Armature Type Relays
Applications
1.For over current protection
2.Differential Protection
3.Auxiliary Relays
. e n e me ag over curren
and earth fault protection
-
7/25/2019 EE6702-Protection and Switchgear R2013
112/356
(ii) Solenoid type relay
It consists of a solenoid and movable iron plungerarranged as shown.
Under normal operating conditions, the currentthrough the relay coil C is such that it holds the
lun er b ravit or s rin in the osition shown. However, on the occurrence of a fault, the current
through the relay coil becomes more than thepickup value, causing the plunger to be attracted to
the solenoid. The upward movement of the plungercloses the trip circuit, thus opening the circuitbreaker and disconnecting the faulty circuit.
23
-
7/25/2019 EE6702-Protection and Switchgear R2013
113/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
114/356
(iii) Balanced beam type relay
It consists of an iron armature fastened to abalance beam. Under normal operatingconditions , the current through the relay coil is
such that the beam is held in the horizontalposition by the spring.
When a fault occurs, the current through therelay coil becomes greater than the pickup value
and the beam is attracted to close the trip circuit.This causes the opening of the circuit breaker toisolate the faulty circuit.
25
-
7/25/2019 EE6702-Protection and Switchgear R2013
115/356
26Balanced beam type relay
-
7/25/2019 EE6702-Protection and Switchgear R2013
116/356
27
It most closely resembles an induction motor, except thatth t i i t ti l th t d t
-
7/25/2019 EE6702-Protection and Switchgear R2013
117/356
the rotor iron is stationary, only the rotor conductorportion being free to rotate.
The moving element is a hollow cylindrical rotor whichturns on its axis. The rotating field is produced by twopairs of coils wound on four poles as shown.
The rotating field induces currents in the cup to providethe necessary driving torque.
28
If 1 and 2 represent the fluxes produced by the
-
7/25/2019 EE6702-Protection and Switchgear R2013
118/356
If 1 and 2 represent the fluxes produced by therespective pairs of poles, then torque produced is
proportional to1 2 sin . where is the phase difference between the two fluxes.
A control spring and the back stop for closing of thecontacts carried on an arm are attached to the spindle ofthe cup to prevent the continuous rotation.
producers than either the shaded-pole or the watthourmeter structures. Therefore, this type of relay has veryhigh speed and may have an operating time less then 0.1second.
29
-
7/25/2019 EE6702-Protection and Switchgear R2013
119/356
Induction type
(Non Directional Relay)
30
Thi f l k h i d i
-
7/25/2019 EE6702-Protection and Switchgear R2013
120/356
This type of relay works on the inductionprinciple and initiates corrective measureswhen current in the circuit exceeds thepredetermined value.
The actuating source is a current in the
transformer. These relays are used on a.c.circuits only and can operate for faultcurrent flow in either direction.
31
-
7/25/2019 EE6702-Protection and Switchgear R2013
121/356
32
Constructional details
-
7/25/2019 EE6702-Protection and Switchgear R2013
122/356
Constructional detailsIt consists of a metallic (aluminium) disc which is free to rotate
in between the poles of two electromagnets. The upperelectromagnet has a primary and a secondary winding. The primaryis connected to the secondary of a C.T. in the line to be protectedand is tapped at intervals. The tappings are connected to a plug-setting bridge by which the number of active turns on the relayoperating coil can be varied, thereby giving the desired current
setting.The secondary winding is energized by induction from
primary and is connected in series with the winding on the lowermagnet. The controlling torque is provided by a spiral spring.
The spindle of the disc carries a moving contact which bridgestwo fixed contacts (connected to trip circuit) when the disc rotatesthrough a pre-set angle. This angle can be adjusted to any valuebetween 0 and 360 . By adjusting this angle, the travel of themoving contact can be adjusted and hence the relay can be givenany desired time setting.
33
O ti
-
7/25/2019 EE6702-Protection and Switchgear R2013
123/356
Operation
The driving torque on the aluminium disc is set up due to
the induction principle. This torque is opposed by the
restraining torque provided by the spring.
Under normal operating conditions, restraining torque is
current. Therefore, the aluminium disc remains stationary.
If the current in the protected circuit exceeds the pre-set
value, the driving torque becomes greater than the restraining
torque. Consequently, the disc rotates and the moving contact
bridges the fixed contacts when the disc has rotated through a
pre-set angle. The trip circuit operates the circuit breaker
which isolates the faulty section.
34
-
7/25/2019 EE6702-Protection and Switchgear R2013
124/356
DIRECTIONAL
RELAY
35
induction relays are two types
-
7/25/2019 EE6702-Protection and Switchgear R2013
125/356
y yp
non directional directional relays
relays
Difference between the two:?
non directional relays are activated by only current flowing inthe circuit to be protected.
directional relays are activated by power flowing in the specific
direction. Hence it requires both current and voltage of the circuit to be
protected.
* it requires specific direction of current flow*
-
7/25/2019 EE6702-Protection and Switchgear R2013
126/356
DIRECTIONAL POWER RELAY
-
7/25/2019 EE6702-Protection and Switchgear R2013
127/356
Constructional details:
1) upper magnet which is E- shaped
2) lower magnet which is U- shaped.
The upper maget consits of primary winding on
the central limb which is energised by voltage from secondary of P.T
lower magnet houses secondary winding which
is energised by current of the circuit from secondary of C.T.
Further lower magnet is connected to PSM as
previous case (not shown)
-
7/25/2019 EE6702-Protection and Switchgear R2013
128/356
In between this two electro magnets we have aluminium disc pivoted as
shown
This alumunium disc carries a moving contact which can bridge fixed
contact by rotating though a pre set angle.
The time of operation depends upon the pre set angle
Restraining torque is provide by spring which twists in reverse direction.
Operation:
from the diagram we can conclude that we have two flux quantaties: 1 & 2 .
always 1 laggs V by 900
2 inphase with current I
-
7/25/2019 EE6702-Protection and Switchgear R2013
129/356
Due to phase difference between two flux quantaties i.e., = 90-
1 V & 2 I
Hence T = 1 2 sin
= 1 2 sin(90-)
= VI COS
= POWER
Hence the rela activated onl when there is a s ecific directionof power flowof power flow
when power flows in normal direction both driving torque and
restraining torque twists in same direction and relay does not operates.
when the power flow is in reverse direction, driving torque and
restraining torque acts in opposite direction and relay operates.therefore
CB operates and disconnects faulty section.
DIRECTIONAL OVER CURRENT RELAY:
-
7/25/2019 EE6702-Protection and Switchgear R2013
130/356
From the previous discussion
T = V I COS
Under abnormal condition
under abnormal conditions voltage in the circuit is too low.
Therefore the driving torque becomes abnormally too small
.Hence the relay does not operate.
ie., the directional power relay is not suitable for
short circuit conditions.
This problem can be overcome by directional over
current relay.
Directional overcurrent relay:
-
7/25/2019 EE6702-Protection and Switchgear R2013
131/356
Directional overcurrent relay makes use of two relays
i) directional power relay ( directional element)
-
7/25/2019 EE6702-Protection and Switchgear R2013
132/356
i) directional power relay ( directional element)
ii) Non directional current relay (non-directional element)
Construction:
1) Directional element :
It is similar in construction to directional power relay.
it consists of upper magnet which is E-shaped and carries
pr mary w n ng w c s exc e y vo age o e c rcu o e pro ec e
through secondary of PT.
The lower magnet is U-shaped carries secondary winding which
is excited by current of the circuit to be protected through secondary of CT.
The secondary winding is extended to lower magnet primary winding as
shown. The trip contacts 1 & 2 are connected in series with secondary winding of
lower magnet.
therefore for the relay to operate, at first directional element should be
activated first.
2) Non directional element:
-
7/25/2019 EE6702-Protection and Switchgear R2013
133/356
* It is activated only by current flowing in the circuit*
it is similar in construction to non-directional over current relay.
For this element to operate ,at first directional element should be activated
first.
the secondary winding is further connected to PSM( not shown),
for current setting.
When short circuit occurs current tend to be reversed .Hence
directional element starts operating and closes the trip contact.
with closing of trip contact, the secondary winding of non
directional element is complete and disc starts rotating. When moving contactbridges fixed contact the circuit breaker operates and separates the faulty
section.
-
7/25/2019 EE6702-Protection and Switchgear R2013
134/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
135/356
Distance Relay
(mho relay)
46
y
-
7/25/2019 EE6702-Protection and Switchgear R2013
136/356
Distance relay :-
1.IMPEDANCE RELAY
o +ve (operative)Torque by
current element
o -
At normal condition
operative torque = restraining torque
At fault
operative torque > restraining torque
Also called voltage restrained over current relay.
-
7/25/2019 EE6702-Protection and Switchgear R2013
137/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
138/356
2 Reactance relay :
-
7/25/2019 EE6702-Protection and Switchgear R2013
139/356
2.Reactance relay :-
o Operative Torque by current
o Restraining Torque by Current-Voltage Directional relay
+ve torque by over current element
-
Directional element designed for maxi. Torque angle =
90 degree
-
7/25/2019 EE6702-Protection and Switchgear R2013
140/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
141/356
3 Mho relay :
-
7/25/2019 EE6702-Protection and Switchgear R2013
142/356
3.Mho relay :-
Induction cup type structure.
oOperative Torque produced by V & I element.
o Restraining Torque by Voltage element.
Also called Adm ittance relay.
-
7/25/2019 EE6702-Protection and Switchgear R2013
143/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
144/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
145/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
146/356
NEGATIVE SEQUENCE RELAY
The negative relays are also called phase unbalancerelays because these relays provide protection
a ainst ne ative se uence com onent of unbalancedcurrents existing due to unbalanced loads or phase-phase faults.
The unbalanced currents are dangerous fromgenerators and motors point of view as these currents
can cause overheating. Negative sequence relays aregenerally used to give protection to generators andmotors against unbalanced currents.
-
7/25/2019 EE6702-Protection and Switchgear R2013
147/356
DIAGRAM:
-
7/25/2019 EE6702-Protection and Switchgear R2013
148/356
CONSTRUCTION: It consists of a resistance bridge network. The magnitudes of the impedances of all the branches
of the network are equal.
1 3impedances Z2 and Z4 are the combinations of resistance and reactance.
The currents in the branches Z2 and Z4 lag by 60o from
the currents in the branches Z1 and Z3. The vertical branch B-D consists of inverse time
characteristics relay. The relay has negligibleimpedance.
-
7/25/2019 EE6702-Protection and Switchgear R2013
149/356
PHASOR DIAGRAM:
-
7/25/2019 EE6702-Protection and Switchgear R2013
150/356
The current IRgets divided into two equal parts I1 and I2. AndI2 lags I1 by 60o.
1 + 2= rsLet I1 = I2 = I
The perpendicular is drawn from point A on the diagonalmeeting it at point B. This bisects the diagonal.
... OB = IR/2
Now in triangle OAB,
cos 30 = OB/OA
... 3/2 = (IR/2)/I
... I = IR/3 = I1 = I2 ............(1)
-
7/25/2019 EE6702-Protection and Switchgear R2013
151/356
Now I1 leads IRby 30owhile I2 lags IRby 30
o.
Similarly the current IB gets divided into two equal partsI3 and I4. The current I3 lags I4 by 60
o. From equation (1) wecan write,
IB /3 = I3 = I4 ...............(2)
The current I leads b IBwhile current I la s IB b 30o
.The current entering the relay at the junction point B inthe Fig. 1 is the vector sum of , and .
Irelay = 1 + 3 + Y= I
Y
+ (IR
/3) (leads IR
by 30o) + IB
/3(lags IB
by30o)
when the load is balanced and nonegative sequence currents exist.
-
7/25/2019 EE6702-Protection and Switchgear R2013
152/356
1 + 3 = -Y... 1 + 3 + Y= 0
Thus the current entering the relay at point B is zero.Similarly the resultant current at junction D is alsozero. Thus the relay is inoperative for a balanced
system.
-
7/25/2019 EE6702-Protection and Switchgear R2013
153/356
UNDER FAULTY CONDITION:Now consider that there is unbalanced load on
generator or motor due to which negative sequencecurrents exist.
1 3 each other at the junction point B. Hence I1 andI3 cancel each other. Now the relay coil carries thecurrent IYand when this current is more than a
predetermined value, the relay trips closing thecontacts of trip circuit which opens the circuit breaker.
-
7/25/2019 EE6702-Protection and Switchgear R2013
154/356
ZERO SEQUENCE CURRENT: Under zero sequence currents the total current of
twice the zero sequence current flows through therelay. Hence the relay operates to open the circuit
.
To make the relay sensitive to only negativesequence currents by making it inoperative under theinfluence of zero sequence currents is possible by
connecting the current transformers in delta .Underdelta connection of current transformers, no zerosequence current can flow in the network.
-
7/25/2019 EE6702-Protection and Switchgear R2013
155/356
D fi iti
-
7/25/2019 EE6702-Protection and Switchgear R2013
156/356
Definition
A two-winding relay that operates when the difference
between the currents in the two windings reaches a
predetermined value is called differential relays.
A two-winding relay that operates when the difference
between the currents in the two windings reaches a
predetermined value.
In case of electrical quantities exceed a predetermined
value, a current differential relay is one that compares the
-
7/25/2019 EE6702-Protection and Switchgear R2013
157/356
value, a current differential relay is one that compares the
current entering a section of the system with current leaving
the section. Under normal operating conditions, the two currents are
equal but as soon as fault occurs, this condition no longer
applies. The difference between the incoming and outgoing
currents is arranged to flow through relay operating coil. If
this difference is equal to or greater than the pick up value
the relay will operate and open the circuit breaker and
isolate the faulty section.
Any type of relay when connected in a particular way can be
made to operate as a differential relay. It is not the relay
construction but the way in which relay is connected in a
circuit makes it a differential relay.
There are three fundamental systems of differential or balanced protection:
I. current differential relay
-
7/25/2019 EE6702-Protection and Switchgear R2013
158/356
cu e t d e e t a e ay
II. voltage differential relay
III. Biased beam relay or percentage differential relay
(i) Current balance protection
Fig 16 a shows an arrangement of an over current relay connected to operate as a
differential relay. A pair ofidentical current transfonners is fitted on either end of the
section to be rotected alternator windin in this case . The secondaries of CTs areconnected in series in such a way that they carry the induced currents in the same
direction. The operating coil of over current relay is connected across the CT
secondary circuit. This differential relay compares the current at the two ends of the
alternator winding.
Under normal operating conditions, suppose the alternator winding carries a normal
current of 1000 A. Then the current in the two secondaries of CTs are equal as in
figure These currents will merely circulate between the two CTs and no current will
-
7/25/2019 EE6702-Protection and Switchgear R2013
159/356
figure. These currents will merely circulate between the two CT s and no current will
flow through the differential relay as shown in the diagram fig 16 a. Therefore, the
relay remains inoperative.
If a ground fault occurs on the alternator winding as shown in fig 16 b. the two
secondary currents will not be equal and the current flows through the operating coil
of the relay, causing the relay to operate. The amount of current flow through the
relay will depend upon the way the fault is being fed.
Disadvantages
-
7/25/2019 EE6702-Protection and Switchgear R2013
160/356
The impedance of the pilot cables generally
causes a slight difference between the currents at thetwo ends of the section to be protected, then the small
differential current flowing through the relay may
cause it to operate even under no fault conditions.
Pilot cable capacitance causes incorrect
operation of the relay when a large current flows
Accurate matching of current transformerscannot be achieved due to pilot circuit impedance
(ii) voltage differential relay
Fi 18 h th t f lt b l
-
7/25/2019 EE6702-Protection and Switchgear R2013
161/356
Fig. 18 shows the arrangement of voltage balance
protection.In this scheme of protection, two similar current
transformers are connected at either end of the
element to be protected (e.g. an alternator winding)
b means of ilot of wires.The secondaries of current transformers are
connected in series with a relay in such a way that
under normal conditions, their induced e.m.fs are in
opposition
Under healthy conditions, equal currents will flow
in both primary windings. Therefore, the secondary
-
7/25/2019 EE6702-Protection and Switchgear R2013
162/356
p y g y
voltages of the two transformers are balanced
against each other and no current will flow throughthe relay-operating coil.
When a fault occurs in the protected zone, the
another and their secondary voltages will no longer
be in balance.
This voltage difference will cause a current to flowthrough the operating coil of the relay, which closes
the trip circuit.
Disadvantages
-
7/25/2019 EE6702-Protection and Switchgear R2013
163/356
The voltage balance system suffers from the
following drawbacks
A multi-gap transformer construction is required
to achieve the accurate balance between current
.
The system is suitable for protection of cables of
relatively short, lengths due to the capacitance of
pilot wires.
The biased beam relay also called percentage differential relay is designed to
III. Biased beam relay or percentage differential relay
-
7/25/2019 EE6702-Protection and Switchgear R2013
164/356
y p g y g
respond to the differential current in terms of its fractional relation to the current
flowing through the protected section.
Its called percentage differential relay because the ratio of differential operating
current to average restraining current is a fixed percentage.
Its called bias relay because restraining known as biased coil produces the bias
force. Fig 17 a, shows the schematic arrangements of biased beam relay. It is
essen a y an over curren a ance eam ype re ay w an a ona res ra n ngcoil. The restraining coil produces a bias force in the opposite direction to the
operating force.
Under normal and through load conditions, the bias
force due to restraining coil is greater than operating
-
7/25/2019 EE6702-Protection and Switchgear R2013
165/356
force. Therefore, the relay remains inoperative.
When an internal fault occurs, the operating
force exceeds the bias force Consequently the
-
7/25/2019 EE6702-Protection and Switchgear R2013
166/356
force exceeds the bias force. Consequently the
trip contacts are closed to open the circuitbreaker.
The bias force can be adjusted by varying the
number of turns on the restraining coil.
-
7/25/2019 EE6702-Protection and Switchgear R2013
167/356
Under
relays78
-
7/25/2019 EE6702-Protection and Switchgear R2013
168/356
79
-
7/25/2019 EE6702-Protection and Switchgear R2013
169/356
80
-
7/25/2019 EE6702-Protection and Switchgear R2013
170/356
81
UNITUNIT
-
7/25/2019 EE6702-Protection and Switchgear R2013
171/356
Apparatus Protection33
1
Presented by
C.GOKUL,AP/EEEVelalar College of Engg & Tech , Erode
UNIT 3 Syllabus
-
7/25/2019 EE6702-Protection and Switchgear R2013
172/356
Protection of transformer.
Protection of generator.
Protection of motor.
Protection of busbars.
Protection of transmission line.
2
-
7/25/2019 EE6702-Protection and Switchgear R2013
173/356
Introduction
-
7/25/2019 EE6702-Protection and Switchgear R2013
174/356
The two major items of equipment in apower system are the generators and transformers.They have very high chance of fault occurrenceand usually takes much time and money to repair
the damage.
Fault and Abnormal
Conditions
-
7/25/2019 EE6702-Protection and Switchgear R2013
175/356
Conditions Generator : Over Current, Over Voltage, Under Voltage, Under
Frequency, Unbalanced Current, Loss of Excitation, Reverse Power,
Winding Inter turn Fault, Winding Earth Fault etc.
Transformer : Over Current, Winding Inter turn fault, Excessive
empera ure se, n a ance urren , ver ux ng e c.
Motors : Over Current, Under Voltage, Unbalance Current, Winding
Short Circuit, Stator Earth Fault, etc.
Transmission Line : Single Phase to ground fault, Phase to PhaseFault, three phase to ground fault, Over Current etc.
-
7/25/2019 EE6702-Protection and Switchgear R2013
176/356
-
7/25/2019 EE6702-Protection and Switchgear R2013
177/356
Faults occurring in Transformers Open-Circuit faults
Earth faults
Phase-to-Phase faults
Inter-Turn faults
Overheating
Factors in choosing Protective Gear
-
7/25/2019 EE6702-Protection and Switchgear R2013
178/356
for a Transformer Type of Transformer
Size of the Transformer
Type of Cooling
System where used
Importance of service for which it is required
-
7/25/2019 EE6702-Protection and Switchgear R2013
179/356
Transformer Relaying Scheme
-
7/25/2019 EE6702-Protection and Switchgear R2013
180/356
Buchholz ProtectionAlso known as gas accumulator relay, commonly used onall oil-immersed transformer provided with conservator.
or ng r nc p e:Whenever a fault occur inside the transformer, the
oil of the tank gets overheated and gases are generated.The heat generated by the high local current causes the
transformer oil to decompose and produce gas which canbe used to detect the winding faults
-
7/25/2019 EE6702-Protection and Switchgear R2013
181/356
Buchholz Protection
-
7/25/2019 EE6702-Protection and Switchgear R2013
182/356
Core-Balance Leakage ProtectionThis system is used to provide protection against earthfaults on high voltage winding. When earth fault occurs,the sum of the three currents is no longer zero and a
the trip relay to operate and isolate the transformer fromthe bus-bars.
-
7/25/2019 EE6702-Protection and Switchgear R2013
183/356
Combined Leakage and Overload
-
7/25/2019 EE6702-Protection and Switchgear R2013
184/356
ProtectionThe core-balance protection cannot provide protectionagainst overload. It is usual practice to provide combinedleakage and overload protection for transformer. The
earth faults only. The overload relays havehigh currentsetting and are arrange to operate against faultsbetween the phases
In this system, two overload relay and one earth relayare connected. The two overload relays are sufficient toprotect against phase to phase faults The trip contacts
-
7/25/2019 EE6702-Protection and Switchgear R2013
185/356
protect against phase to phase faults. The trip contacts
of overload relays and earth fault relay are connectedin parallel. Therefore the energizing of either one ofthem, the circuit breaker will tripped.
Transformer Protection
-
7/25/2019 EE6702-Protection and Switchgear R2013
186/356
Overheating
Normal maximum working temp. = 95 C
8-10 C rise will halve the life of the transformer.
Overcurrent
Fuses for distribution transformer
Overcurrent relaying for 5MVA and above
Characteristics: Must be below the damage curve
Must be above magnetizing inrush
-
7/25/2019 EE6702-Protection and Switchgear R2013
187/356
Conclusion Open-circuit faults, earth faults, phase-to-phase faults,inter-turn faults and overheating are the fault that arelikely occur in a transformer
power.
Safety is increased
Protective relays are essential for keeping faults in the
system isolated and keep equipment from beingdamaged.
-
7/25/2019 EE6702-Protection and Switchgear R2013
188/356
IntroductionIntroduction
-
7/25/2019 EE6702-Protection and Switchgear R2013
189/356
Generator is the electrical end of a turboGenerator is the electrical end of a turbo--generator set.generator set.Without Generator, turbine/boiler/any Power Plant EquipmentWithout Generator, turbine/boiler/any Power Plant Equipmentis meaningless. Generator is the most precious/valuableis meaningless. Generator is the most precious/valuableequipment in PP which actually converts the mechanicalequipment in PP which actually converts the mechanicalenergy of turbine into electricity. So, Generator should beenergy of turbine into electricity. So, Generator should beprotected from faults occurring within generator and also fromprotected from faults occurring within generator and also from
externa au ts a norma operat ng con t on n t eexterna au ts a norma operat ng con t on n t ewhich affected the generator.which affected the generator.
Various relays/devices are used to detect the abnormalities inVarious relays/devices are used to detect the abnormalities inoperations and whenever fault conditions appear, they can giveoperations and whenever fault conditions appear, they can givewarning alarms to the operators or trip the unit automatically.warning alarms to the operators or trip the unit automatically.
Generally automatic tripping are provided if the time forGenerally automatic tripping are provided if the time foroperator to take corrective action is less or the fault is likely tooperator to take corrective action is less or the fault is likely tocause serious damage to the unit.cause serious damage to the unit.
FAULT IN THE GENERATORFAULT IN THE GENERATOR
-
7/25/2019 EE6702-Protection and Switchgear R2013
190/356
StatorStator Phase to Phase fault.Phase to Phase fault.
InterInterturn faultturn fault
Earth fault (80% & 100%)Earth fault (80% & 100%)
RotorRotor
Rotor E/FRotor E/F Two stage relay: a) Alarm b) TripTwo stage relay: a) Alarm b) Trip
Over voltage in the rotor.Over voltage in the rotor.
ABNORMAL OPERATINGABNORMAL OPERATING
CONDITIONS:CONDITIONS:
-
7/25/2019 EE6702-Protection and Switchgear R2013
191/356
Which affects the generatorWhich affects the generator
Negative Phase sequenceNegative Phase sequence
Loss of ExcitationLoss of Excitation
Over fluxing protectionOver fluxing protection
Reverse powerReverse power
OverOver--speedingspeeding
Pole slipping/ Out of StepPole slipping/ Out of Step
PROTECTION CATEGORYPROTECTION CATEGORY
-
7/25/2019 EE6702-Protection and Switchgear R2013
192/356
Complete Generator protection is divided into two category i.e.Complete Generator protection is divided into two category i.e. ClassClassA ProtectionA Protection
ClassClassB ProtectionB Protection
CLASSCLASSA: Protection where electrical isolation is an emergency.(A: Protection where electrical isolation is an emergency.(Insulation failure, ,S.C. etc.). Trip the GCB/Turbine/Boiler withoutInsulation failure, ,S.C. etc.). Trip the GCB/Turbine/Boiler withouttime delay or Generator automatic trips.time delay or Generator automatic trips.
.Class.ClassA followsA follows
Gen. Differential Prot.Gen. Differential Prot.
Gen. 100% E/FGen. 100% E/F
Gen. SB E/FGen. SB E/F
Gen. NVDGen. NVD
Gen. O/CGen. O/C
Rotor 2nd stage E/FRotor 2nd stage E/F
Gen. Brg. Temp. highGen. Brg. Temp. high
CLASSCLASS -- BB
-
7/25/2019 EE6702-Protection and Switchgear R2013
193/356
CLASSCLASS
B: Protection where externalB: Protection where externalabnormalities come into picture, such as temp.abnormalities come into picture, such as temp.rise. Generator trips through LFP relay.rise. Generator trips through LFP relay.
ClassClassBB follows;follows;
Voltage restrained O/CVoltage restrained O/C
Thermal O/CThermal O/C
Negative Phase sequenceNegative Phase sequence
U/V and O/V 2nd stageU/V and O/V 2nd stage
Over fluxing/ Field failureOver fluxing/ Field failure
Gen. over/under frequency.Gen. over/under frequency.
EARTH FAULT:EARTH FAULT:
-
7/25/2019 EE6702-Protection and Switchgear R2013
194/356
When fault current flows through earth return path,When fault current flows through earth return path,
the fault is called Earth Fault.the fault is called Earth Fault.
Possible causes are ;(a) Insulation failure, (b) due toPossible causes are ;(a) Insulation failure, (b) due to
over heating (Failure of water/air circulation throughover heating (Failure of water/air circulation through
stator conductor).stator conductor).
Earth fault may occur between any phase conductorEarth fault may occur between any phase conductor
and core.and core.
It is usually practice to limit the earth fault current toIt is usually practice to limit the earth fault current toavoid extensive damage to the stator core.avoid extensive damage to the stator core.
STAND BY EARTH FAULT:STAND BY EARTH FAULT:
-
7/25/2019 EE6702-Protection and Switchgear R2013
195/356
This protection is practically protects 95% ofThis protection is practically protects 95% of
generator winding. Therefore a current setting ofgenerator winding. Therefore a current setting of
5% of in to be set.5% of in to be set.
E/F current is generally limited to about 15/20Amps.E/F current is generally limited to about 15/20Amps.
Earth fault current of even 100A for few seconds canEarth fault current of even 100A for few seconds can
cause external damage. So the earth fault is restrictedcause external damage. So the earth fault is restricted
to 100Amps. By providing NGR of 63.5 ohms atto 100Amps. By providing NGR of 63.5 ohms at
11KV Voltage Level.11KV Voltage Level.
This is a BackThis is a Back--Up protection.Up protection.
-
7/25/2019 EE6702-Protection and Switchgear R2013
196/356
100% STATOR EARTH FAULT:100% STATOR EARTH FAULT:
-
7/25/2019 EE6702-Protection and Switchgear R2013
197/356
In this protection, where neutral voltage measurement is madeIn this protection, where neutral voltage measurement is madeat generator terminals, (By Broken Delta), the third harmonicat generator terminals, (By Broken Delta), the third harmonicvoltage element is used.voltage element is used.
First earth fault very near to neutral produces negligibleFirst earth fault very near to neutral produces negligiblecurrent as driving voltage is nearly zero. But if a 2nd earthcurrent as driving voltage is nearly zero. But if a 2nd earth
au t occurs at mac ne term na , ne to groun au t s notau t occurs at mac ne term na , ne to groun au t s notlimited by NGR. The resulting fault current can be high.limited by NGR. The resulting fault current can be high.Hence, the 1st E/F very near to neutral has to be detected earlyHence, the 1st E/F very near to neutral has to be detected earlyand isolated.and isolated.
All generators produce continuous current of 3rd harmonicAll generators produce continuous current of 3rd harmonic
voltage. Under normal condition, 3rd harmonic voltage isvoltage. Under normal condition, 3rd harmonic voltage ispresent. If there is a fault near neutral, the amount of 3rdpresent. If there is a fault near neutral, the amount of 3rdharmonic voltage comes down and this is used for detection.harmonic voltage comes down and this is used for detection.
STATOR EARTH FAULT PROTECTIONSTATOR EARTH FAULT PROTECTION
Generator
-
7/25/2019 EE6702-Protection and Switchgear R2013
198/356
Yellow
Red
Blue
RelayCT
Neutral Earth
Resistance
ROTOR EARTH FAULT:ROTOR EARTH FAULT:
-
7/25/2019 EE6702-Protection and Switchgear R2013
199/356
Since rotorSince rotor circuits operate ungrounded, a single earth fault iscircuits operate ungrounded, a single earth fault iscaused by insulation failure due to moisture, ageing ofcaused by insulation failure due to moisture, ageing ofinsulation or vibration of rotor etc. But existence of singleinsulation or vibration of rotor etc. But existence of singleground fault increases the chance of a second ground fault.ground fault increases the chance of a second ground fault.The occurrence of second earth fault can cause fault currentThe occurrence of second earth fault can cause fault current
. .. .gap flux is badly distorted. The rotor is displaced enough togap flux is badly distorted. The rotor is displaced enough torub stator leading to severe vibrations and can damage therub stator leading to severe vibrations and can damage thebearing.bearing.
Although a machine can continuously run on a single earthAlthough a machine can continuously run on a single earth
fault but second rotor earth fault, if allowed to occur,fault but second rotor earth fault, if allowed to occur,should be detected immediately and generator should beshould be detected immediately and generator should betripped.tripped.
-
7/25/2019 EE6702-Protection and Switchgear R2013
200/356
DIFFERENTIAL PROTECTIONDIFFERENTIAL PROTECTION
-
7/25/2019 EE6702-Protection and Switchgear R2013
201/356
Differential protection is very reliable method for statorDifferential protection is very reliable method for statorwinding phase to phase fault. In this, currents on bothwinding phase to phase fault. In this, currents on bothsides of the generator are compared.sides of the generator are compared.
Under normal condition or for a fault outside of theUnder normal condition or for a fault outside of theprotected zone, current i1s is equal to current i2s.protected zone, current i1s is equal to current i2s.
ere ore, e curren s n e s secon ar es are a soere ore, e curren s n e s secon ar es are a soequal, i1s=i2s and no current flows through the currentequal, i1s=i2s and no current flows through the currentrelays.relays.
If a fault develops inside of the protected zone, current i1sIf a fault develops inside of the protected zone, current i1sand i2s are no longer equal, therefore i1s and i2s are notand i2s are no longer equal, therefore i1s and i2s are not
equal and therefore a current flowing in the current relay.equal and therefore a current flowing in the current relay.
-
7/25/2019 EE6702-Protection and Switchgear R2013
202/356
Negative Phase Sequence Protection:Negative Phase Sequence Protection:
-
7/25/2019 EE6702-Protection and Switchgear R2013
203/356
When the generator is connected to a balanced load, the phase currents areWhen the generator is connected to a balanced load, the phase currents areequal in magnitude and displaced electrically by 120equal in magnitude and displaced electrically by 120. The ATs wave. The ATs waveproduced by the stator currents rotate synchronously with the rotor and noproduced by the stator currents rotate synchronously with the rotor and noeddy currents are induced in the rotor parts.eddy currents are induced in the rotor parts.
If there is an unbalanced loading of the generator, and then the statorIf there is an unbalanced loading of the generator, and then the statorcurrents have acurrents have ave sequence component. The stator field due to theseve sequence component. The stator field due to thesevevesequence currents rotates at synchronous speed but in a direction oppositesequence currents rotates at synchronous speed but in a direction opposite
to t e rect on o t e e structure on t e rotor. us, t eto t e rect on o t e e structure on t e rotor. us, t eve sequenceve sequencestator armature mmf rotates at a speedstator armature mmf rotates at a speedNs, while the rotor field speed isNs, while the rotor field speed is+Ns. There is a relative velocity of 2Ns between the two.+Ns. There is a relative velocity of 2Ns between the two.
These causes double frequency currents, of large amplitude to be inducedThese causes double frequency currents, of large amplitude to be inducedin the rotor conductors and iron part. So both the eddy currents as well asin the rotor conductors and iron part. So both the eddy currents as well asthe hystersis losses increase due to these double frequencies inducedthe hystersis losses increase due to these double frequencies inducedcurrents in the rotor.currents in the rotor.
Unbalanced loading affects ;(a) Rotor heating (b) Severe vibration &Unbalanced loading affects ;(a) Rotor heating (b) Severe vibration &heating of stator.heating of stator.
FIELD FAILURE PROTECTION:FIELD FAILURE PROTECTION:
-
7/25/2019 EE6702-Protection and Switchgear R2013
204/356
Acts as an Induction Generator.Acts as an Induction Generator. Possible Causes;Possible Causes;
AVR FaultAVR Fault
Tripping of Field C.B.Tripping of Field C.B.
Open circuit or Short circuit occurring in the D.C. circuit.Open circuit or Short circuit occurring in the D.C. circuit.
PMG failurePMG failure
,,system. If excitation fails, synchronous generator runs at a supersystem. If excitation fails, synchronous generator runs at a super--synchronoussynchronousspeed, draws reactive power from the power system instead of supplying the Qe.speed, draws reactive power from the power system instead of supplying the Qe.In case, the other generators cant meet the requirement of reactive power, thisIn case, the other generators cant meet the requirement of reactive power, thisshall result in large voltage drop which may ultimately result in instability.shall result in large voltage drop which may ultimately result in instability.
In this case, slip becomesIn this case, slip becomesVe result in slip frequency currents. Rotor getsVe result in slip frequency currents. Rotor getsheated up due to induced currents in the rotor winding, core or damage theheated up due to induced currents in the rotor winding, core or damage thewinding if this condition is sustained. Stator heats up due to high stator currentswinding if this condition is sustained. Stator heats up due to high stator currents
due to increase in reactive current from the system.due to increase in reactive current from the system. By monitor (i) Field current, IfBy monitor (i) Field current, If
(ii) Phase current & voltage.(ii) Phase current & voltage.
REVERSE POWERREVERSE POWER
PROTECTION:PROTECTION:
-
7/25/2019 EE6702-Protection and Switchgear R2013
205/356
This protection is provided to protect against motoring.This protection is provided to protect against motoring. A generator is expected to supply active power to the connected system inA generator is expected to supply active power to the connected system in
normal operation. If the generator primover fails, a generator that is connectednormal operation. If the generator primover fails, a generator that is connectedin parallel with another source of electrical supply will to begin to motor. Thisin parallel with another source of electrical supply will to begin to motor. Thisreversal of power flow due to loss of prime mover can be detected by reversereversal of power flow due to loss of prime mover can be detected by reversepower element.power element.
Possible Causes:Possible Causes:
may happen due to some fault in the system or some delay by the operatingmay happen due to some fault in the system or some delay by the operatingpersonnel.personnel.
In case of sudden closure of stop valves or control valves when the generatorIn case of sudden closure of stop valves or control valves when the generatorunit is still connected to the grid.unit is still connected to the grid.
Reverse power operation is harmful to the turbine since without steam flow inReverse power operation is harmful to the turbine since without steam flow inthe turbine. If the turbine continues to rotate, it will result in heating of turbinethe turbine. If the turbine continues to rotate, it will result in heating of turbineblades due to churning action. However, the period for the turbine to overheatblades due to churning action. However, the period for the turbine to overheat
may vary from a few seconds to minutes depending upon the turbine &may vary from a few seconds to minutes depending upon the turbine &operating conditions.operating conditions.
-
7/25/2019 EE6702-Protection and Switchgear R2013
206/356
OVER FLUXING PROTECTION:OVER FLUXING PROTECTION:
-
7/25/2019 EE6702-Protection and Switchgear R2013
207/356
Fundamental VoltageFundamental Voltage-- Flux relation:Flux relation: V = 4.44 * N * f * V = 4.44 * N * f *
V/f = 4.44 * N * V/f = 4.44 * N *
= K * = K * B/A= K * = K * B/A
V/f is a measure of flux in machine. That means, over fluxing can occur if the ratioV/f is a measure of flux in machine. That means, over fluxing can occur if the ratioof voltage to frequency exceeds certain limits. High voltage or low frequency,of voltage to frequency exceeds certain limits. High voltage or low frequency,causing a rise in the V/f ratio, will produce high flux densities in the magnetic corecausing a rise in the V/f ratio, will produce high flux densities in the magnetic core
o t e generator. s cou cause t e core o t e mac ne to saturate stray ux too t e generator. s cou cause t e core o t e mac ne to saturate stray ux tobe induced in the unlamilated components that have not designed to carry flux. Thebe induced in the unlamilated components that have not designed to carry flux. Theresulting eddy currents in the solid components e.g. core bolts & clamps and end ofresulting eddy currents in the solid components e.g. core bolts & clamps and end ofcore laminations can cause rapid overheating and damage.core laminations can cause rapid overheating and damage.
POSSIBLE CAUSES:POSSIBLE CAUSES:
AVR failureAVR failure
Load rejection under manual AVR controlLoad rejection under manual AVR control
Excessive excitation with Generator Offline.Excessive excitation with Generator Offline. Decreasing Speed with operator tries to maintain rated stator voltage.Decreasing Speed with operator tries to maintain rated stator voltage.
AUTO to Manual transfer of AVR.AUTO to Manual transfer of AVR.
-
7/25/2019 EE6702-Protection and Switchgear R2013
208/356
Fan, Blower
Various Industry Motor Applications
-
7/25/2019 EE6702-Protection and Switchgear R2013
209/356
,
Pump, Compressor
Conveyor
Mixer
Cranes
Types of Fault in Motors
-
7/25/2019 EE6702-Protection and Switchgear R2013
210/356
External Fault Internal Fault
Mechanical Load Bearing Failure
Unbalance SupplyVoltage
Winding phase andearth fault
Single Phasing
Phase Reversal
Motor Protection Summary
-
7/25/2019 EE6702-Protection and Switchgear R2013
211/356
y
THERMAL OVERLOAD
SHORT CIRCUIT
EARTH FAULT
UNBALANCE
BLOCKED ROTOR/STALLING PROTECTION
Thermal Stress Causes Motor Failure
Most of the motor failure contributors and failed motor components arerelated to motor overheating.
-
7/25/2019 EE6702-Protection and Switchgear R2013
212/356
Thermal stress potentially can cause the failure of all the major motorparts: Stator, Rotor, Bearings, Shaft and Frame.
Thermal Overload
-
7/25/2019 EE6702-Protection and Switchgear R2013
213/356
Consider a motor is as homogenous bodyDeveloping heat at constant rate.Dissipating heat at constant rate.
Heat disspation is proportional to temperature
riseT = KIR
2 (1-e t/ )
Rotor I2t Protection
-
7/25/2019 EE6702-Protection and Switchgear R2013
214/356
I I1I2
I = I1 (positive sequence) + k * I2 (negativesequence)
(Overload protection includes additional heating effect of negative sequence curr
Main Factors and Elements Comprisingthe Thermal Model are:
Overload Protection - Thermal Model
-
7/25/2019 EE6702-Protection and Switchgear R2013
215/356
Overload Pickup Level
Overload Curve
Cooling Time Constants
Hot/Cold Stall Time Ratio
THERMAL OVERLOAD cont
SETTING CRITERIA : Thermal Element
-
7/25/2019 EE6702-Protection and Switchgear R2013
216/356
SETTING CRITERIA : Thermal Element
Motor running
Time in sec
Current
(Amperes)1 3 7 0 A2 9 3 A
Starting
t ime :10s
1 7 2 0 A
Short- circuit
e l e m e n t
SHORT CIRCUIT PROTECTION
-
7/25/2019 EE6702-Protection and Switchgear R2013
217/356
What is:-Motor short-circuit protection -provided to cater for major stator winding faultsand terminal flashovers.
Settings - Definite time over current relay
e ement, set to a out 130 o motor startingcurrent and time delay set at 100ms.
Differential Protection
Differential protection may be considered the firstline of protection for internal phase-to-phase or
-
7/25/2019 EE6702-Protection and Switchgear R2013
218/356
phase-to-ground faults.
Summation method with six CTs:
If six CTs are used in a summingconfiguration, during motor starting, the
values from the two CTs on each phase
may not be equal as the CTs are notperfectly identical and asymmetricalcurrents may cause the CTs on each phaseto have different outputs.
The running differential delay can then befine tuned to an application such that itresponds very fast and is sensitive to low
differential current levels.
What is:-A ground fault is a fault thatcreates a path for current to flow from one
Ground Fault Protection
-
7/25/2019 EE6702-Protection and Switchgear R2013
219/356
creates a path for current to flow from oneof the phases directly to the neutral throughthe earth bypassing the load
Ground faults in a motor occur:
When its phase conductors insulation
is damaged for example due to voltagestress, moisture or internal fault occursbetween the conductor and ground
To limit :-the level of the ground faultcurrent connect an resistance known as
stablising resistance
Phase Unbalance
-
7/25/2019 EE6702-Protection and Switchgear R2013
220/356
What is:-In a balanced system the three line-neutralvoltages are equal in magnitude and are 120 degrees
out of phase with each other. Otherwise, the system is
unbalanced.
Positive Sequence Negative Sequence
Main causes of current unbalance
-
7/25/2019 EE6702-Protection and Switchgear R2013
221/356
Blown fuses Loose connections
Stator turn-to-turn faults
System voltage distortion and
FaultsEffects Motor winding overheating Excessive vibrations
Cause motor insulation/winding/bearingdamage
Motor Protection Stalling
-
7/25/2019 EE6702-Protection and Switchgear R2013
222/356
What is:-It happens when motor circuits are energized,
but motor rotor is not rotating. It is also called locked
.
Effects:
This will result in excessive currents flow given the
same load. This will cause thermal damage to the
motor winding and insulation.
Motor Protection Stalling
-
7/25/2019 EE6702-Protection and Switchgear R2013
223/356
Required for
Stalling during starting Stalling during running
Cases
Starting time < Stall withstand timeStall withstand time< Starting time
CURRENT RELAYS
-
7/25/2019 EE6702-Protection and Switchgear R2013
224/356
IDMT RELAYS :
These relays have inverse characteristic and the operatingtime decreases as the magnitude of current increases.
GENERAL RELAY EQUATION :
t = TMS X K/((I/In)^n 1)t = RELAY OPERATING TIME
I = FAULT CURRENT
n = CONSTANT
K = CONSTANT
In = RELAY PLUG SETTING ( PICK UP )
TMS = TIME MULTIPLIER SETTING
Pilot Relays
Why needed:-Overcome diffculties of overcurrentRelay ie
-
7/25/2019 EE6702-Protection and Switchgear R2013
225/356
yCoordinationExcessive fault clearance timesPrinciple:-Measurement of current at each end feeders
Transmission o in ormationNo time and current gradation requiredSupervision facility.Merz price Circulating scheme
-
7/25/2019 EE6702-Protection and Switchgear R2013
226/356
Bus Bar Protection
-
7/25/2019 EE6702-Protection and Switchgear R2013
227/356
Bus Differential: Current into bus must equalcurrent out of bus
Bus ProtectionBus Fault
-
7/25/2019 EE6702-Protection and Switchgear R2013
228/356
Busbar Protection
-
7/25/2019 EE6702-Protection and Switchgear R2013
229/356
Typical Bus Arrangements:
Single bus
Double bus, double breaker
- - -
Main and transfer buses with single breaker
Ring bus
Busbar Protection
-
7/25/2019 EE6702-Protection and Switchgear R2013
230/356
Bus differential connection (single-bus)
87B
86B
TRIPS AND LOCKS-OU