Titre de la présentation en Arial, 45Alpican capacitors
F.Dupré09/11/2012
DIVISION EDIA DEPARTEMENT
WHY POWER FACTOR CORRECTION?
To run properly an installation needs active and reactive energy Utilities set penalties if reactive energy used is too high (no interest for them to supply it) This is often measured considering power factor or cos φ
Installing PFC systems allows to avoid penalties by increasing cos φ (by supplying reactive energy)
0,7 0,95 (Example)
2
cos φ
Penalties No penalties
DIVISION EDIA DEPARTEMENT
WHY POWER FACTOR CORRECTION?
Example: before power factor correction cos φ = 0,7 (100/142) using power factor correction system provides reactive energy, expressed in kVAr, apparent energy decreases new cos φ = 0,95 (100/105), penalties are cancelled as target cos φ is reached
3
kVA
kW
kVArφ
kVA
kWPF )cos(
Apparent power
Real power = 100 kW
Re
ac
tiv
e p
ow
erBefore = 142 kVA
Before =
100 kVAr
After = 105 kVAAfter = 33 kVAr
Capacitance added
= 67 kVAr
Power Factor Calculations
• Before PF = 100/142 = 0.70 or 70 %• After PF = 100/105 = 0.95 or 95%
Saved power 37 kVA
Only without harmonics
DIVISION EDIA DEPARTEMENT
FIXED AND AUTOMATIC SYSTEMS
Fixed system : for constant loads, ex: motors (20% of applications) Reactive energy supplied is linear
Automatic system : for variable loads (80% of applications) Reactive energy supplied varies according to the load (kW)
4
kvar
kvar
DIVISION EDIA DEPARTEMENT
LOCATION OF PFC SYSTEMS
DIVISION EDIA DEPARTEMENT
COMPONENTS FOR PFC SYSTEMS
6
capacitor step
contactorswitches the steps on/off
capacitor
power factor controller: monitors the steps to reach target cos φ
DIVISION EDIA DEPARTEMENT
TECHNICAL CHARACTERISTICS OF ALPICAN
Capacitors declined in 400V, 415V, 440V and 480V (nominal voltage) Legrand 6 digits ref no. Powers from 5 kvar to 30 kvar 3 phase 50 Hz / 60 Hz Life cycle up to 100 000 hours Overcurrent capability: 1.3 In Inrush capability: up to 200 In Conform to IEC 60831-1&2
7
DIVISION EDIA DEPARTEMENT
BENEFITS OF THE RANGE
Dielectric: self healing polypropylene film In case of short circuits, the film repairs itself (to a certain limit), preventing the destruction of the capacitor This is a first level of protection
8
DIVISION EDIA DEPARTEMENT
BENEFITS OF THE RANGE
Impregnant: non PCB semi-dry resin Reduces the risk of leaking Reduces the risk of fire as there is no liquid inside (oil) Vacuum technology insures perfect electrical contacts as there is no moisture inside
9
DIVISION EDIA DEPARTEMENT
BENEFITS OF THE RANGE
3 pole in overpressure disconnector Prevents the capacitor from bursting if pressure inside is too high Special design allows smooth pressure increase and safe disconnection of fuses “Pop up” deformation avoids brutal opening Dedicated “cut off” zones and arc extinguisher
10
DIVISION EDIA DEPARTEMENT
BENEFITS OF THE RANGE
Terminal connection Straight forward connection Protection against electric shocks (IP 20) Cable cross section up to 16 mm²
11
DIVISION EDIA DEPARTEMENT
BENEFITS OF THE RANGE
Discharge resistors Discharge capacitor and prevent from electric shocks Need to switch capacitor in automatic systems Pre mounted, time saving for assembly Made in ceramic:protection against electric shocks (IP 2X) Centered position allows connection of capacitor on both sides
12
DIVISION EDIA DEPARTEMENT
BENEFITS OF THE RANGE
Mounting bottom stud The stud forms a solid permanent earthing
13
DIVISION EDIA DEPARTEMENT
REFERENCE NUMBERS
14
Range 400 V Ref. No.
2.5 kVAr 4 151 60
5 kVAr 4 151 61
6.3 kVAr 4 151 62
7.5 kVAr 4 151 63
10 kVAr 4 151 64
12.5 kVAr 4 151 65
15 kVAr 4 151 66
20 kVAr 4 151 67
25 kVAr 4 151 68
Range 415 V Ref. No.
2.5 kVAr 4 151 69
5 kVAr 4 151 70
6.3 kVAr 4 151 71
7.5 kVAr 4 151 72
10 kVAr 4 151 73
12.5 kVAr 4 151 74
15 kVAr 4 151 75
20 kVAr 4 151 76
25 kVAr 4 151 77
Range 440V Ref. No.
2.5 kVAr 4 151 78
5 kVAr 4 151 79
6.3 kVAr 4 151 80
7.5 kVAr 4 151 81
10 kVAr 4 151 82
12.5 kVAr 4 151 83
15 kVAr 4 151 84
20 kVAr 4 151 85
25 kVAr 4 151 86
30 kVAr 4 151 87
Range 480 V Ref. No.
5 kVAr 4 151 88
10.4 kVAr 4 151 89
12.5 kVAr 4 151 90
15 kVAr 4 151 91
20.8 kVAr 4 151 92
25 kVAr 4 151 93
30 kVAr 4 151 94
Products stocked in Verneuil
DIVISION EDIA DEPARTEMENT
DIMENSIONS OVERVIEW
15
Exa
mpl
e fo
r 44
0 V
ran
ge
2.5 kVAr
6.3 kVAr
5 kVAr
7.5 kVAr
12.5 kVAr
10 kVAr
15 kVAr
25 kVAr
20 kVAr
30 kVAr
DIVISION EDIA DEPARTEMENT
COMPOSITION OF A CAPACITOR BANK
An automatic capacitor bank is made of steps with different powers expressed in kvar
Example: 100 kvar ( at 400V) cabinet made of:
Step 1: 12.5 kvar (4151 65) Step 2: 12.5 kvar (4151 65) Step 3 : 25 kvar (4151 68) Step 4 : 50 kvar (2x 4151 68)
16
DIVISION EDIA DEPARTEMENT
PRODUCTS ASSOCIATED TO ALPICAN
Those products needed to build automatic capacitor banks can be sold together with Alpican to provide added value: power factor controllers: select the steps in automatic systems to reach the targeted power factor contactors: switch steps in automatic systems detuned reactors: protect capacitors against harmonics if the network is polluted (speed variators, UPS etc..)
17
Power factor controllers
CTX-C contactors
Detuned reactors
DIVISION EDIA DEPARTEMENT
DEFINITION OF HARMONICS
Short definition for harmonics
• Harmonics are current or voltage with frequencies of n x Nominal Networks frequency (50 Hz or 60 Hz) added to this nominal frequency
• They are generated by non-linear loads like electrical equipment with power electronic (converters, inverters,…) or variable impedance load using electric arcs
• They can be measured with THDi (current) and THDu (Voltage) values expressed in %
Order 1 (50 Hz) = fondamental
Order 3 (150 Hz)
Order 5 (250 Hz)
Order 7 (350 Hz)
Order 9 (450 Hz)
=+
+
++
DIVISION EDIA DEPARTEMENT
DETUNED REACTORS ASSOCIATED
Power (kvar) 440/400V
Ref. No.Reactor 189 Hz
Associated capacitorRange 440V
10 kVAr/ 8 kVAr SAH-4.31-16.2 4151 82
12.5 kVAr / 10 kVAr SAH-3.45-20.2 4151 83
25 kVAr / 20 kVAr SAH-1.73-40.4 41 51 86
50 kVAr / 40 kVAr SAH-0.86-80.8 2x 4151 86
75 kVAr / 60 kVAr SAH-0.58-121.2 3x 4151 86
100 kVAr / 80 kVAr SAH-0.43-161.6 4x 4151 86
Detuned reactors are protecting capacitors against harmonic pollution of the network (expressed in THDU % and THDI %)There are connected in series with Alpican
For general applications Range 189 Hz/p%=7 When harmonic rank 3 is important Range 135 Hz/p%=14
Power (kvar)480V
Ref. No.Reactor 135 Hz
Associated capacitorRange 480V
12.5 kVAr SAH-8.1-15.7 4151 90
25 kVAr SAH-4.05-28.9 4151 93
50 kVAr SAH-2.02-62.8 2x41 51 93
100 kVAr SAH-1.35-94.2 3x 4151 93
DIVISION EDIA DEPARTEMENT
ITEM NUMBERS FOR CONTACTORS
CTX-Cref. No.
Up to 12.5 kvar 296 05
Up to16.7 kvar 296 15
Up to 20 kvar 296 25
Up to 30 kvar 296 35
Up to 45 kvar 296 45
Up to 55 kvar 296 55
For capacitors banks without detuned reactors, contactors with series resistors have to be used (CTX-C contactors) For capacitor banks with detuned reactors, power contactors can be used
DIVISION EDIA DEPARTEMENT
ITEM NUMBERS FOR CONTROLLERS
Number of controlled steps Ref. No.
Up to 4 Alpetc4
Up to 6 Alptec6
Up to 12 Alptec 12B
Controllers monitor the steps within automatic capacitor banks Exist in 4,6 and 12 steps devices
DIVISION EDIA DEPARTEMENT
Powers of capacitor is proportional to ratio of square voltages Ex : 30 kvar at 440V = 25 kvar at 400V , (440²/400²)*25= 30
Selection to be made according to the grid, 400V, 415 V etc.. When used with detuned reactors, voltage increases so it is necessary to upgrade the rated voltage of capacitor
CHOICE OF CAPACITORS
22
Un 50 Hz 60 Hz
440 V 30 kvar 36 kvar
415 V 27 kvar 32 kvar
400 V 25 kvar 30 kvar2
22
1
21
P
U
P
U
Frequency effect : + 20 %
DIVISION EDIA DEPARTEMENT
Example Installation with network voltage of 400V Need for 20 kvar, no harmonic pollution, choose capacitor 400V/ 20 kvar : 4151 68
Same installation but with harmonic pollution where reactors are necessary Choose capacitor in 440V rated voltage + associated reactor: (25 kvar 440V = 20 kvar 400 V) 4151 86 + SAH-1.73-40.4
CHOICE OF CAPACITORS
23
DIVISION EDIA DEPARTEMENT
A COMPLETE RANGE OF CAPACITORS
Access range: Alpican for all type of sites
Premium range: Alpivar² can sometimes substitute Alpican for sites with high technical constraints (industry)
24
DIVISION EDIA DEPARTEMENT
SEGMENTS
25
IndustryLarge commercialSmall commercial
Alpican can be sold on nearly all segments in commercial and industrial areas All installation need power factor correction systems
DIVISION EDIA DEPARTEMENT
CUSTOMER TARGETS
Distributors: stock fixed capacitors, for flow business
Panel builders, generalists or specialists in PFC, they use capacitors to assemble automatic banks
26
DIVISION EDIA DEPARTEMENT
ADDED VALUE IN POWER DISTRIBUTION
PFC can represent up to 10 % of added value in a power project in addition to others products: ACBs, MCCBS, transformers, busbars…
Most countries worldwide consider penalties for reactive energy, increasing need for energy will emphasis it
ROI for installations is quite fast with a maximum of around 2 years
27
DIVISION EDIA DEPARTEMENT
COMPETITORS
28
International electrical distribution leaders focus on big project propose a complete power package including PFC
International PFC specialists have international presence but some strong areas as per their country of origin propose either components (capacitors) or complete systems (capacitor banks)
Locals manufacturers only present on their domestic markets, have an aggressive price policy
DIVISION EDIA DEPARTEMENT
PRICE POSITIONING
Local integrators
International specialists
Major power distribution leaders
price
quality
DIVISION EDIA DEPARTEMENT
TOOLS AVAILABLE
Alpican leafletSamplesTechnical data sheetsPricing tool