edge
DESCRIPTION
bracket designTRANSCRIPT
Page 1 (1/8)
Sormat Trustfix
version: 3.0.0.5
project data
Constructor Name ECO
Author Processor AS
Date 5/16/2014
Comments
CEILING BRACKET AT INSIDE
S-KAH M10
European Technical Approval ETA-08/0173Diameter 10 mmMaterial A4Effective anchorage depth, hef 60 mmNominal drill bit diameter, d0 10 mmDrill hole depth, h1 75 mmMinimum member thickness, hmin 120 mmAnchor length in concrete, hnom 68 mmInstallation torque, Tinst 35 Nmrecommended installation torque, Tinst 35 Nm
SORMAT S-KAH 10/20
Available Items:
Art. No. Designation tfix Packing unitsLength
05135 25 piece20 mm102 mmSORMAT S-KAH 10/20
05136 25 piece30 mm112 mmSORMAT S-KAH 10/3005138 25 piece50 mm132 mmSORMAT S-KAH 10/50On request 0 piece100 mm0 mmSORMAT S-KAH 10/...
Geometry
Anchor plate dimensions
Width 90 mmLength 150 mmDistance syr,1 45 mmDistance syr,2 45 mmCentre spacing sz1 110 mmDistance szr,1 20 mm
File: EDGE ANCHOR.sorSormat OyHarjutie 5, FIN-21290 Rusko
www.sormat.comphone: +358 (207) 940 200fax: +358 (201) 76 - 3888
Page 2 (2/8)
Sormat Trustfix
version: 3.0.0.5
Distance szr,2 20 mmFixture thickness 14 mmThickness of non load-bearing layer, e.g.plaster etc. 0 mmMaterial S235Clearance hole diameter met: df ≤ 12.00 mm
relevant edge distances
Edge right 50 mmEdge bottom 100 mm
Eccentricity
ey 0 mmez 0 mm
Member thickness 200 mmBuilding material class C30/37non-cracked concrete (verifiedcompression zone)Without edge reinforcementclose spacing between bars of surfacereinforcement
File: EDGE ANCHOR.sorSormat OyHarjutie 5, FIN-21290 Rusko
www.sormat.comphone: +358 (207) 940 200fax: +358 (201) 76 - 3888
Page 3 (3/8)
Sormat Trustfix
version: 3.0.0.5
Load
Design values
Nd 0.600 kN
Vyd 1.500 kN
Vzd 0.300 kN
Mxd 0.010 kNm
Myd 0.010 kNm
Mzd 0.200 kNm
File: EDGE ANCHOR.sorSormat OyHarjutie 5, FIN-21290 Rusko
www.sormat.comphone: +358 (207) 940 200fax: +358 (201) 76 - 3888
Page 4 (4/8)
Sormat Trustfix
version: 3.0.0.5
Anchor bending
The following requirements are met:: - Fixture made of metal - Fixture rests fully against the anchorage material - Fixture rests fully against anchor
Design actions (Design values)
Anchor-nr. Nd Vd Md
Anchor 1 2.892 kN 0.676 kN 0.000 Nm
Anchor 2 2.824 kN 0.854 kN 0.000 Nm
Calculation according ETAG 001 (August 2010) - Design Method A
Total capacity due to steel failure
= 2.89 kN Design load valuesNh Sd
= 24.00 kN European Technical ApprovalNRk,s
= 1.40 European Technical ApprovalγMs
File: EDGE ANCHOR.sorSormat OyHarjutie 5, FIN-21290 Rusko
www.sormat.comphone: +358 (207) 940 200fax: +358 (201) 76 - 3888
Page 5 (5/8)
Sormat Trustfix
version: 3.0.0.5
= NRk,s / γMs European Technical ApprovalNRd,s
= 17.14 kN European Technical Approval
= Nh Sd / NRd,sβN
= 16.87 % Total capacity due to tension loading
Total capacity due to pullout
= 2.89 kN Design load valuesNh Sd
= 16.00 kN European Technical ApprovalNRk,p
= 1.80 European Technical ApprovalγMp
= 1.10 European Technical Approvalψc
= NRk,p × ψc / γMp European Technical ApprovalNRd,p
= 9.78 kN European Technical Approval
= Nh Sd / NRd,pβN
= 29.58 % Total capacity due to tension loading
Total capacity due to concrete cone failure
= 5.72 kNNg Sd Design load values
= 10.1 × √fck,cube × hef 1.5N0 Rk,c
= 28.55 kN ETAG - Annex C (5.2a)
= 406.00 cm²Ac,N ETAG - Annex C 5.2.2.4b
= 324 cm²A0 c,N ETAG - Annex C 5.2.2.4b
= 0.87ψs,N ETAG - Annex C (5.2c)
= 0.80ψre,N ETAG - Annex C (5.2d)
= 0.99ψec,N ETAG - Annex C (5.2e)
= 1.00ψc European Technical Approval
= N0 Rk,c × (Ac,N / A0 c,N) × ψs,N × ψre,N × ψec,N × ψcNRk,c
= 24.63 kN ETAG - Annex C (5.2)
= 1.80γMc European Technical Approval
= NRk,c / γMcNRd,c
= 13.68 kN European Technical Approval
= Ng Sd / NRd,cβN
= 41.78 % Total capacity due to tension loading
Total capacity due to splitting
= 5.72 kN Design load valuesNg Sd
= 10.1 × √fck,cube × hef 1.5N0 Rk,c
= 28.55 kN ETAG - Annex C (5.2a)
= 561.00 cm² ETAG - Annex C 5.2.2.4bAc,N
= 576.00 cm² ETAG - Annex C 5.2.2.4bA0 c,N
= 0.83 ETAG - Annex C (5.2c)ψs,N
= 0.80 ETAG - Annex C (5.2d)ψre,N
= 0.99 ETAG - Annex C (5.2e)ψec,N
= 1.41 ETAG - Annex C (5.3a)ψh,sp
= N0 Rk,c × (Ac,N / A0 c,N) × ψs,N × ψre,N × ψec,N × ψh,spNRk,sp
File: EDGE ANCHOR.sorSormat OyHarjutie 5, FIN-21290 Rusko
www.sormat.comphone: +358 (207) 940 200fax: +358 (201) 76 - 3888
Page 6 (6/8)
Sormat Trustfix
version: 3.0.0.5
= 25.66 kN ETAG - Annex C (5.3)
= 1.80 European Technical ApprovalγMsp
= NRk,sp / γMsp European Technical ApprovalNRd,sp
= 14.26 kN European Technical Approval
= Ng Sd / NRd,spβN
= 40.10 % Total capacity due to tension loading
Total capacity due to steel failure resulting from shear load
= 0.85 kN Design load valuesVh Sd
= 17.00 kN European Technical ApprovalVRk,s
= 1.50 European Technical ApprovalγMs
= VRk,s / γMs European Technical ApprovalVRd,s
= 11.33 kN European Technical Approval
= Vh Sd / VRd,sβV
= 7.54 % Total capacity due to shear loading
Total capacity due to pryout
= 1.53 kN Design load valuesVg Sd
= 10.1 × √fck,cube × hef 1.5N0 Rk,c
= 28.55 kN ETAG - Annex C (5.2a)
= 406.00 cm² ETAG - Annex C 5.2.2.4bAc,V
= 324.00 cm² ETAG - Annex C 5.2.2.4bA0 c,V
= 0.87 ETAG - Annex C (5.2c)ψs,V
= 0.80 ETAG - Annex C (5.2d)ψre,V
= 1.00 European Technical Approvalψc
= 24.22 kN ETAG - Annex C 5.2.2.4NRk,c
= 2.00 European Technical Approvalk
= k × NRk,cVRk,cp
= 48.44 kN ETAG - Annex C (5.6)
= 1.50 European Technical ApprovalγMc
= VRk,cp / γMcVRd,cp
= 32.29 kN European Technical Approval
= Vg Sd / VRd,cpβV
= 4.74 % Total capacity due to shear loading
Total capacity due to pryout (single anchor)
Vg Sd = 0.85 kN Design load values
N0 Rk,c = 10.1 × √fck,cube × hef 1.5
= 28.55 kN ETAG - Annex C (5.2a)
Ac,V = 203.00 cm² ETAG - Annex C 5.2.2.4b
A0 c,V = 324.00 cm² ETAG - Annex C 5.2.2.4b
ψs,V = 0.87 ETAG - Annex C (5.2c)
ψre,V = 0.80 ETAG - Annex C (5.2d)
ψc = 1.00 European Technical Approval
File: EDGE ANCHOR.sorSormat OyHarjutie 5, FIN-21290 Rusko
www.sormat.comphone: +358 (207) 940 200fax: +358 (201) 76 - 3888
Page 7 (7/8)
Sormat Trustfix
version: 3.0.0.5
NRk,c = 12.40 kN ETAG - Annex C 5.2.2.4
k = 2.00 European Technical Approval
VRk,cp = k × NRk,c
= 24.81 kN ETAG - Annex C (5.6)
γMc = 1.50 European Technical Approval
VRd,cp = VRk,cp / γMc European Technical Approval
= 16.54 kN European Technical Approval
βV = Vg Sd / VRd,cp
= 5.16 % Total capacity due to shear loading
Total capacity due to concrete edge failure Edge right
= 1.53 kNVg Sd Design load values
= 2.4 × dnomα × hnom
β ×√fck,cube × c1 1.5V0 Rk,c
= 8.94 kN ETAG - Annex C (5.7a)
= 195.00 cm²Ac,V ETAG - Annex C 5.2.3.4b
= 0.11α ETAG - Annex C (5.7c)
= 0.07β ETAG - Annex C (5.7d)
= 112.50 cm²A0 c,V ETAG - Annex C (5.7d)
= 1.00ψs,V ETAG - Annex C (5.7e)
= 1.00ψh,V ETAG - Annex C (5.7f)
= 1.02ψα,V ETAG - Annex C (5.7g)
= 0.92ψec,V ETAG - Annex C (5.7h)
= V0 Rk,c × (Ac,V / A0 c,V) × ψs,V × ψh,V × ψα,V × ψec,V VRk,c
= 14.48 kN ETAG - Annex C (5.7)
= 1.50γMc European Technical Approval
= VRk,c / γMcVRd,c
= 9.66 kN European Technical Approval
= Vg Sd / VRd,cβV
= 15.84 % Total capacity due to shear loading
Total capacity due to concrete edge failure Edge bottom
= 0.84 kNVg Sd Design load values
= 2.4 × dnomα × hnom
β ×√fck,cube × c1 1.5V0 Rk,c
= 22.59 kN ETAG - Annex C (5.7a)
= 300.00 cm²Ac,V ETAG - Annex C 5.2.3.4b
= 0.08α ETAG - Annex C (5.7c)
= 0.06β ETAG - Annex C (5.7d)
= 450.00 cm²A0 c,V ETAG - Annex C (5.7d)
= 0.80ψs,V ETAG - Annex C (5.7e)
= 1.00ψh,V ETAG - Annex C (5.7f)
= 2.50ψα,V ETAG - Annex C (5.7g)
= 1.00ψec,V ETAG - Annex C (5.7h)
= V0 Rk,c × (Ac,V / A0 c,V) × ψs,V × ψh,V × ψα,V × ψec,V VRk,c
File: EDGE ANCHOR.sorSormat OyHarjutie 5, FIN-21290 Rusko
www.sormat.comphone: +358 (207) 940 200fax: +358 (201) 76 - 3888
Page 8 (8/8)
Sormat Trustfix
version: 3.0.0.5
= 30.12 kN ETAG - Annex C (5.7)
= 1.50γMc European Technical Approval
= VRk,c / γMcVRd,c
= 20.08 kN European Technical Approval
= Vg Sd / VRd,cβV
= 4.19 % Total capacity due to shear loading
Total capacity due to interaction of combined tension and shear loads
The selected Anchor is suitable.
βN = 0.42 <= 1
βV = 0.16 <= 1
(βN)α + (βV)α = 0.421.5 + 0.161.5 = 0.33 <= 1
Thickness of anchor plate
Because of the missing information about the connected profile, the calculation of the required anchor platethickness can not be carried out. It has to be done by the responsible designer.
Annotations
Information regarding calculationThe following documents are referenced for the verification of the anchor load capacity:- - ETA approvalThe following assumptions are made for the calculations:- - The selected building material class has been verified- - all of the anchors in a group are of the same type and size- - The anchor plate remains even during loadingThe verification of the local transfer of loads into the anchorage material has been performed. The transfer ofthese loads to the rest of the structure must be shown.The design is based on numerous anchor-specific values. In case of using an alternative anchor or when the dataentered has changed, the calculations have to be redone.The requirements and regulations of the approval have to be considered.Additional requirements of the anchor approvals have to be taken into account, especially if the anchors areloaded dynamically.
File: EDGE ANCHOR.sorSormat OyHarjutie 5, FIN-21290 Rusko
www.sormat.comphone: +358 (207) 940 200fax: +358 (201) 76 - 3888