Easy9 & Resi9Affordable circuit protection you can depend on
™
Compliant metal consumer unit
BS 7671:2008Amendment 3 (2015)
1
Schneider Electric is a global specialist in energy management. Established as a circuit breaker designer and manufacturer in France since 1920, Schneider Electric are the worldwide leader of electrical protection technologies, present in more than 100 countries.
Domestic Circuit Protection BS7671 Amendment 3
Regulation 421.1.201 – What is it and when does it come into force?
> From January 2015 Amendment No. 3 to BS7671 IET Wiring Regulations prescribes that within domestic (household) premises, consumer units and similar switchgear assemblies shall have their enclosures manufactured from non-combustible material, or be enclosed in a cabinet or enclosure constructed of non-combustible material and comply with product standard BS EN 61439-3.
> Although regulation 421.1.201 will appear in BS7671 from January 2015, it is expected that the implementation date for this regulation with be 1st January 2016, however this does not preclude compliance particularly in terms of design and specification prior to this date.
What is the intention behind this change to BS7671?
> As far as it is reasonably practical, to contain any fire within the enclosure and minimise flames from escaping, caused mainly as a result of poorly installed connections.
What is a non-combustible enclosure?
> At the time of this publication it is expected that regulation 421.1.201 will advise that an example of a non combustible materials is a ferrous metal e.g. steel. Therefore a non combustible enclosure includes base, cover, door and any components e.g. hinges necessary to contain the fire. Blanks and devices are contained within the non combustible enclosure.
2
Easy9Affordable circuit protection you can depend on
IntroductionA complete range of modular devices ..................................................................................... p.3
New Easy9 circuit protection provides long-lasting protection ................................................. p.5
Product informationMetal enclosures .................................................................................................................... p.9
Switch-disconnectors ........................................................................................................... p.10
RCCB residual current circuit breakers ................................................................................. p.11
Miniature circuit breaker ....................................................................................................... p.12
RCBO residual current devices ............................................................................................. p.13
Product selector ................................................................................................................... p.14
TechnicalTechnical information ........................................................................................................... p.17
Resi9The complete residentialcircuit protection offer
IntroductionResi9 Consumer Units .......................................................................................................... p.28
Features & benefits ............................................................................................................... p.29
Resi9 overview ..................................................................................................................... p.30
Resi9 overview diagram ........................................................................................................ p.31
Product informationResi9 ..................................................................................................................................... p33
Switch-disconnector ............................................................................................................. p.34
RCCB Residual Current Circuit Breaker ................................................................................ p.35
RCBO Residual Current Device ............................................................................................ p.36
Miniature Circuit Breaker ........................................................................................................ p37
Terminal Block ...................................................................................................................... p.38
Quick SelectorSelect consumer unit ............................................................................................................ p.40
Select devices ...................................................................................................................... p.41
Technical GuideResi9 - metal unit dimensions ............................................................................................... p.43
Easy9Affordable circuit protection you can depend on
A complete range of modular devices
Just what you need from circuit protection
We work closely with electricians worldwide to help bring safe electricity to homes and buildings around the globe. Now you can take pride in delivering to your customers the enhanced safety and peace of mind they deserve.
3
“I would recommend Easy9 to anyone”
New, robust circuit protection from a brand you trust
The new Easy9 range better supports your business as an electrician, helping you to be more effective through:> A high-quality, user-friendly design> Availability when and where you need it> Reliability you can count on
4
New Easy9 circuit protection provides long-lasting protectionEasy9 brings you the quality, peace of mind, and reliability of a high-end device at a mid-range price. Thanks to consistent design and high manufacturing standards, Easy9 is a durable range you can be proud to install.> Guaranteed compliance to product standards> Certification by independent authorities
Since
1920Leader in electrical switchgear
Easy9Affordable circuit protection you can depend on
55
Quality- 100% designed and manufactured by Schneider Electric- All sites with ISO 9000 certification - Brand selected everywhere for industry, hospitals and airports
Availability- Always available at your distributor- Complete coverage of protection features- Large assortment of ratings
Safety- Protection from electric shocks, overloads and short circuits- Compliance to standards
Customer satisfaction- Highly reliable and safe circuit protection- Dependable power supply
Time saving- Consistent design and connection features- One-stop shopping for all parts- Proven robustness to withstand wear and tear
6 6
Easy 9 at a glanceEasy9Affordable circuit protection you can depend on
Installer-friendly wiring with only 1 screwdriver
Schneider Electric warranty
Comprehensive range
Full compliance with international IEC standards 3rd party certification
7
Neutral terminal identification engraved
Full trip indication on the front panel by position of handle On-Off engraved
Clear and visible production information.Whatever the toggle position
Full range coherence
Class II front face
8
™
Compliant metal consumer unit
BS 7671:2008Amendment 3 (2015)
9
Easy9 Metal enclosuresBS7671 Amendment 3 Compliant
DescriptionThe surface mounting enclosure consists of:
■ Metal surface mounting enclosure with: ■ Multiple cable entry points and rear knock out slots ■ Secure fixed DIN rail ■ Earth terminal block and a neutral terminal blocks fitted as standard ■ Secure busbar shield ■ Standard consumer units up to 20 usable ways ■ Earthed cover ■ Enclosure colour: White RAL 9003.
Consumer UnitReference Description No. Usable WaysEZ92MCUL EZ9 2 Way Metal CU 2EZ94MCUL EZ9 4 Way Metal CU 4EZ96MCUL EZ9 6 Way Metal CU 6EZ98MCUL EZ9 8 Way Metal CU 8EZ912MCUL EZ9 12 Way Metal CU 12EZ916MCUL EZ9 16 Way Metal CU 16EZ920MCUL EZ9 20 Way Metal CU 20
Consumer unit with switch/RCDs fitted Reference Description No. Usable WaysEZ9R4R4MCUL EZ9 4+4W 100A Sw, 63A RCCBx2 Metal 4+4 dual RCCBEZ9R6R6MCUL EZ9 6+6W 100A Sw, 63A RCCBx2 Metal 6+6 dual RCCBEZ9R6R6DMCUL EZ9 6+6W 100A Sw, 80A RCCBx2 Metal 6+6 dual RCCBEZ9R8R8DMCUL EZ9 8+8W 100A Sw, 80A RCCBx2 Metal 8+8 dual RCCBEZ9S2R5R5DMCUL EZ9 2+5+5 100A Sw, 80A RCCBx2 Metal cw 2 unprotected ways 2,5,5 dual RCCBEZ9S2R7R7DMCUL EZ9 2+7+7 100A Sw, 80A RCCBx2 Metal cw 2 unprotected ways 2,7,7 dual RCCB
Consumer unit with switch/RCDs fitted Reference Description No. Usable WaysFlexible Split Consumer Unit Including Incomers
EZ9FS12MCUL EZ9 12 Way FS 100A Sw, 80A RCCBx2 Metalup to 4 unprotected ways with max splits of 4/7/7 12 way flex split
EZ9FS16MCUL EZ9 16 Way FS 100A Sw, 80A RCCBx2 Metalup to 4 unprotected ways with max splits of 4/9/9 16 way flex split
Populated consumer unit with switch/RCDs/MCBs fittedReference Description No. Usable WaysEZ9R6R6MREL EZ9 6+6 Kitbox cw 8 MCB Metal 6+6 dual RCCB EZ9S2R5R5DMREL EZ9 2+5+5 Kitbox cw 8 MCB Metal Metal cw 2 unprotected ways 2,5,5 dual RCCB
Garage consumer unit Reference Description No. Usable WaysEZ9GARAGE63L EZ9 garage unit cw 63A RCCB and 6 & 16A mcbs 2
™
Compliant metal consumer unit
BS 7671:2008Amendment 3 (2015)
10
Easy9 Switch-disconnectors
2PEasy9 control switchesRating (Ie)
63 A EZ9S16263100 A EZ9S16291Voltage rating (Ue) 400 V, 50/60 HzWidth in 9-mm modules 4
FunctionsThe switch-disconnectors are used for:
■ Control (opening and closing of circuits under load). ■ Disconnection of on-load electrical circuits already protected against overloads
and short-circuits.
Certified compliant BSEN60947-3Connection
6.5 mm
PZ2
20 mm
Rigid copper cablesy 50 mm2 Tightening torque: 3.5 Nm
Flexible copper cablesy 35 mm2 Tightening torque: 3.5 Nm
11
Easy9
Functions ■ Tripping in case of leakage current only. ■ One RCCB protects several circuits when fitted upstream of a group of
circuit breakers.
Certified compliant BSEN61008-1Additional featureEndurance (O-C) Electrical 2000 cycles
Mechanical 5000 cyclesConditional rated short circuit current (Inc/IDc)
With fuse 3000 AWith Easy9 MCB 3000 A
Operating temperature -5°C to +60°CStorage temperature -40°C to +85°CElectrical feeding By the top and the bottom
RCCB residual current circuit breakers
2P Residual current circuit breakers AC Rating (In) 30 mA
63 A EZ9R3326380 A EZ9R33280Voltage rating (Ue) 127 - 230 V, 50/60 HzWidth in 9-mm modules 4
Connection
DB
4060
37 6.5 mm
16 mm
PZ2
Rigid copper cables1 to 35 mm2 Tightening torque: 3.5 Nm
Flexible copper cables1 to 25 mm2 Tightening torque: 3.5 Nm
12
Easy9
Certified compliant BS EN 60898-1Additional featureAccording to EN 60898-1Breaking capacity (Icn)Ph/N 230 V AC 6000 A
Additional characteristics Endurance (O-C) Electrical 4,000 cycles
Mechanical 10,000 cyclesOperating temperature -5°C to +60°CStorage temperature -40°C to +85°C
1PCircuit breakersRating (In) Curve B Curve C
3 A EZ9F16103 -6 A EZ9F16106 EZ9F6610610 A EZ9F16110 EZ9F6611016 A EZ9F16116 EZ9F6611620 A EZ9F16120 EZ9F6612025 A EZ9F16125 -32 A EZ9F16132 EZ9F6613240 A EZ9F16140 EZ9F6614050 A EZ9F16150 EZ9F66150Width in 9-mm modules 2
Miniature circuit breaker
Connection
6.5 mm
PZ2
16 mm
Rigid copper cables3 to 25 A 1 to 25 mm2 Tightening torque: 2 Nm32 to 50 A 1 to 35 mm2 Tightening torque: 3.5 Nm
Flexible copper cables3 to 25 A 1 to 16 mm2 Tightening torque: 2 Nm32 to 50 A 1 to 25 mm2 Tightening torque: 3.5 Nm
13
Easy9
Connection
14 mm
5.5 mm
PZ2
16 mm
Rigid copper cablesL in 1 to 25 mm2 Tightening torque: 2 NmL and N out 1 to 16 mm2 Tightening torque: 2 Nm
Flexible copper cablesL in 1 to 16 mm2 Tightening torque: 2 NmL and N out 1 to 10 mm2 Tightening torque: 2 Nm
RCBO residual current devices
Functions ■ Protection from short-circuits. ■ Protection of cable from overloads. ■ Protection of persons from electric shocks by direct contact (30 mA sensitivity) ■ Can be fitted instead of a miniature circuit breaker for complete protection of one
circuit.The Earth Reference Cable "FE": enables RCD to protect users from electric shocks, even in case of supply neutral loss, neutral conductor breakage or supply voltage drop (FE= Functional Earth).
1P+N
Easy9 RCBO type A 30 mARating (In) B curve
6 A EZ9D1680610 A EZ9D1681016 A EZ9D1681620 A EZ9D1682025 A EZ9D1682532 A EZ9D1683240 A EZ9D1684050 A EZ9D16850Voltage rating (Ue) 230 V AC, 50 HzWidth in 9-mm modules 2
Certified compliant BS EN 61009-1
14
Easy9 Product selector
Consumer UnitReference Description No WaysEZ92MCUL EZ9 2 Way Metal CU 2EZ94MCUL EZ9 4 Way Metal CU 4EZ96MCUL EZ9 6 Way Metal CU 6EZ98MCUL EZ9 8 Way Metal CU 8EZ912MCUL EZ9 12 Way Metal CU 12EZ916MCUL EZ9 16 Way Metal CU 16EZ920MCUL EZ9 20 Way Metal CU 20
Select consumer units with switch/RCD’s fittedReference Description Total ways Un/P ways RCD1 ways RCD2 waysEZ9R4R4MCUL EZ9 4+4W 100A Sw, 63A RCCBx2 Metal 8 4 4EZ9R6R6MCUL EZ9 6+6W 100A Sw, 63A RCCBx2 Metal 12 6 6
EZ9R6R6DMCUL EZ9 6+6W 100A Sw, 80A RCCBx2 Metal 12 6 6
EZ9R8R8DMCUL EZ9 8+8W 100A Sw, 80A RCCBx2 Metal 16 8 8EZ9S2R5R5DMCUL EZ9 2+5+5 100A Sw, 80A RCCBx2 Metal 12 2 5 5
EZ9S2R7R7DMCUL EZ9 2+7+7 100A Sw, 80A RCCBx2 Metal 16 2 7 7
Flexible Split Consumer Unit Including Incomers Total ways Max Un/P ways Max RCD1 ways Max RCD2 waysEZ9FS12MCUL EZ9 12 Way FS 100A Sw, 80A RCCBx2 Metal 12 4 7 7EZ9FS16MCUL EZ9 16 Way FS 100A Sw, 80A RCCBx2 Metal 16 4 9 9
Amendment 3 metal populated consumer unit with switch/RCDs/MCBs fitted Total ways Max Un/P ways Max RCD1 ways Max RCD2 ways
EZ9R6R6MREL EZ9 6+6 Kitbox cw 8 MCB Metal 12 6 6
EZ9S2R5R5DMREL EZ9 2+5+5 Kitbox cw 8 MCB Metal 12 2 5 5EZ9GARAGE63L Garage unit cw 63A RCCB and 6 & 16A mcbs 2 - 2 -
Incoming DevicesReference Device Rating DescriptionEZ9S16263 Switch 63A EZ9 Switch Disconnector 2P 63A 400VEZ9S16291 Switch 100A EZ9 Switch Disconnector 2P 100A 400VEZ9R33263 RCCB 63A, 30mA EZ9 RCCB 2P 63A 30mA AC-type 230V
Residual Current Circuit BreakerEZ9R33280 RCCB 80A, 30mA EZ9 RCCB 2P 80A 30mA AC-type 230V
Residual Current Circuit Breaker
For split load applications select a split load kitReference Description RatingEZ963R30KIT2 RCCB and cables 63A 30mAEZ980R30KIT2 RCCB and cables 80A 30mA
OR
15
Easy9 Product selector Select devices and accessories
Select outgoing devices or accessories
SP 6kA MCBs (B curve)Reference Description Current RatingEZ9F16103 MCB (B curve) 3AEZ9F16106 MCB (B curve) 6AEZ9F16110 MCB (B curve) 10AEZ9F16116 MCB (B curve) 16AEZ9F16120 MCB (B curve) 20AEZ9F16125 MCB (B curve) 25AEZ9F16132 MCB (B curve) 32AEZ9F16140 MCB (B curve) 40AEZ9F16150 MCB (B curve) 50A
Accessories
Reference DescriptionEZ9LKITL Door lock kit (for amendment 3 metal enclosure only)EZ9EARTHKIT Additional earth terminals for clean earth or high integrity earthingEZ916BKIT Replacement/spare main busbarSEDNBP3 3 module blanking plate
SP 6kA MCBs (C curve)Reference Description Current RatingEZ9F66106 MCB (C curve) 6AEZ9F66110 MCB (C curve) 10AEZ9F66116 MCB (C curve) 16AEZ9F66120 MCB (C curve) 20AEZ9F66132 MCB (C curve) 32AEZ9F66140 MCB (C curve) 40AEZ9F66150 MCB (C curve) 50A
SP 6kA 1 module RCBO (B curve)Reference Description Current ratingEZ9D16806 RCBO 30mA 1 Module 1P&N 6AEZ9D16810 RCBO 30mA 1 Module 1P&N 10AEZ9D16816 RCBO 30mA 1 Module 1P&N 16AEZ9D16820 RCBO 30mA 1 Module 1P&N 20AEZ9D16825 RCBO 30mA 1 Module 1P&N 25AEZ9D16832 RCBO 30mA 1 Module 1P&N 32AEZ9D16840 RCBO 30mA 1 Module 1P&N 40AEZ9D16850 RCBO 30mA 1 Module 1P&N 50A
16
Easy9
Technicalinformation
17
Easy9
Metal UnitsRef No. Type No Ways Height (mm) Width (mm) Depth (mm)EZ92MCUL Standard 2 247 186 100EZ94MCUL Standard 4 247 222 100EZ96MCUL Standard 6 247 258 100EZ98MCUL Standard 8 247 294 100EZ912MCUL Standard 12 247 366 100EZ916MCUL Standard 16 247 438 100EZ920MCUL Standard 20 247 510 100EZ9R4R4MCUL Split 8 247 366 100EZ9R6R6MCUL Split 12 247 438 100EZ9R6R6DMCUL Split 12 247 438 100EZ9R8R8DMCUL Split 16 247 510 100EZ9S2R5R5DMCUL Multiple 12 247 438 100EZ9S2R7R7DMCUL Multiple 16 247 510 100EZ9FS12MCUL Flex Split 12 247 438 100EZ9FS16MCUL Flex Split 16 247 510 100EZ9R6R6MREL Multiple 12 247 438 100EZ9S2R5R5DMREL Multiple 12 247 438 100EZ9GARAGE63L garage 2 247 186 100
Technical information
Note: Incoming and outgoing devices must be selected separately from the devices section -only applies to EZ9**MCULIncoming devices available• Switch disconnector 63A & 100A• RCCB’s 63A/30mA 80A/30mAMax. busbar splits - for split load8 way 2+4 to 4+212 way 4+6 to 6+416 way 6+8 to 8+6
Technical dataMax. busbar current (A) 100AMax. operating voltage 230/240V @ 50HzMax. cable capacity 25 mm2 (earth and neutral bars)Certification BS EN 61439-3
No. Of knockoutsDimensions (mm) 25 x
90mm32mm 25mm 20mm 18mm
Ref No. A B D E F G
EZ92MCUL 180 140 - 2* - 2 -
EZ94MCUL 217 176 1 1 1 2 -
EZ96MCUL 253 212 1 1 1 3 -
EZ98MCUL 289 248 1 1 2 3 -
EZ912MCUL 361 320 2 1 3 4 -
EZ916MCUL 433 392 2 1 3 5 -
EZ920MCUL 505 464 2 1 3 5 1
EZ9S2R5R5DMREL 433 392 2 1 3 5 -
EZ9S2R5R5DMCUL 433 392 2 1 3 5 -
EZ9S2R7R7DMCUL 505 464 2 1 3 5 1
EZ9R8R8DMCUL 505 464 2 1 3 5 1
EZ9R5R5DMCUL 433 392 2 1 3 5 -
EZ9R6R6DMCUL 433 392 2 1 3 5 -
EZ9R6R6MCUL 433 392 2 1 3 5 -
EZ9R6R6MREL 433 392 2 1 3 5 -
EZ9R4R4MCUL 361 320 2 1 3 4 -
EZ9FS12MCUL 433 392 2 1 3 5 -
EZ9FS16MCUL 505 464 2 1 3 5 1
EZ9GARAGE63L 180 140 - 2* - 2 -
20 20
200
86
29 41
80
36
21
30
E
GGGGG FFF
B
A
D D
* 2W Version only, 1 x 32mm K/O in upper wall, 1 x K/O in back of box.
18
Easy9 Switch-disconnectors
CharacteristicsMain characteristicsOperating category AC-22 APermissible rated short-time withstand current (Icw) 12 Ie, 1 secondConditional rated short-circuit current (Inc) 5000 ARated short-circuit closing current (Icm) 15 Ie
Additional characteristics Degree of protection(IEC 60529)
Device only IP20
Endurance (O-C) Mechanical 40 -100 A 8500 cycles
Electrical 40-100 A 1500 cycles
Operating temperature -5°C to +55°CStorage temperature -5°C to +70°CTropicalisation (IEC 60068-1) Treatment 2
(relative humidity 95 % to 55°C)
Weight (g)Type Easy9 switch-disconnector2P 175
Dimensions (mm)
2P
456173
5.5
45
36
82
3
Position contact indication
Suitable for isolation according to BSEN 60947-3 standard
Manual control on front face by O-I lever
19
Easy9
CharacteristicsMain characteristicsRated impulse withstand voltage (Uimp) 4 kV
According to IEC 61008-1Making and breaking capacity (Im/IDm) 500 A
Additional characteristics Degree of protection(IEC 60529)
Device only IP20
Hazardous substances RoHS 2003 compliantTropicalisation (IEC 60068-1) Treatment 2 (relative humidity 95 % to 55°C)
Dimensions (mm)
5.5
68
4561
45
62
2P
82
7
36
RCCB residual current circuit breakers
Positive contact indication.
Fault tripping indication on the front panel by the position of the handle (O - I engraved)
Weight (g)Type Easy9 RCCB2P 195
20
Easy9
CharacteristicsMain characteristicsVoltage rating (Ue) 230/400 V ACOperating frequency 50/60 HzElectrical feeding By the top and bottom
Additional characteristics Degree of protection(IEC 60529)
Device only IP20
Hazardous substances RoHS 2003 compliantTropicalisation (IEC 60068-1) Treatment 2 (relative
humidity 95 % to 55°C)
Weight (g)Type Easy9 MCB1P 100
Dimensions (mm)
455.5
61
72
45
5 70
181P
82
Miniature circuit breaker 6 kA
Fault tripping indication on the front panel by the position of the handle (O - I engraved)
Easy9 circuit breakers combine the following functions:
Circuit protection against short-circuit currents.
Circuit protection against overload currents.
21
Easy9
Weight (g)Type Easy9 RCBO1P+N 180
CharacteristicsMain characteristicsEndurance (O-C) Electrical 4000 cycles
Mechanical 10000 cycles
Additional characteristics Degree of protection Device only IP20Overvoltage category (IEC 60364) IVOperating temperature -15°C to +60°CStorage temperature -40°C to +85°CHazardous substances RoHS 2003 compliantTropicalisation (IEC 60068-1) Treatment 2 (relative
humidity 95 % to 55°C)
Test "T" Operating test button, on the front panel
RCBO residual current devices6 kA
Dimensions (mm)
505.5
61
72
45
5
110
18
44
Fault tripping indication on the front panel by the position of the handle (O - I engraved)
Certified compliant BS EN 61009-1
Cable length
1000 mm
22
Easy9
MCB selection chart for household appliances
Appliance Capacity MCB rating (A) Tripping curves
Air conditioner 1 ton 16 "C" 1.5 ton 202 ton 203 ton 25
Refrigerator 165 litres 2285 litres 2
Water heater 1 kW 6 "B" 3 kW 16
Electric kettle 1.5 kW 10
Food processor (50 % load)
200 W 1 "C"
Vacuum cleaner 50 W 0.5
Toaster 1.2 kW 6 "B"
Cooking range
750 W 42 kW 104.5 kW 25
Room heater 1 kW 62 kW 10
Washing machine
300 W 2 "C" 1.3 kW 10
Electric iron 750 W 6 "B" 1.25 kW 6
Time current tripping curves
t(s)
0,01
0,1
1
10
100
1000
I / In1 3...5 6.4...9.6
CB
Miniature circuit breakersSelection
Easy9
23
Circuit protection
MCB current rating Single-phase circuitCable cross section (in mm2) 1.5 2.5 4 6 10 16 25 35Type of installation Maximum rating of the circuit breaker used there (in Ampere)A: in conduit or directly in thermally insulated wall, moulding, architrave, window frame
Single core 10 16 25 32 40 50 80 80
Multicore 10 16 25 32 40 50 70 80
B: in conduit in a wall, in conduit trunking or cable duct on a wall, in building cavitySingle core 16 20 32 40 50 70 100 125
Multicore 16 20 25 32 50 50 80 80
C: direct on a wall, suspended from ceilings, on unperforated cable tray, in masonry wallSingle core or multicore
16 25 32 40 63 80 100 125
D: in conduit in the groundMulticore or single core
20 25 32 40 50 70 80 80
D: directly in the groundMulticore or single core
20 25 32 40 63 80 100 125
E: in free-air, on cable ladder, on perforated cable trayMulticore
du 0.3 d 20 25 40 40 70 80 100 125
Miniature circuit breakers
Selection of circuit breakers according to the cables to be protected (BS 7671)
■ PVC-insulated, copper, flexible or rigid cable. ■ Ambient temperature: ■ 30°C in the open air (methods A, B, C, E) ■ 20°C if buried (method D), ■ For other situations, refer to BS 7671standard (or UK wiring regulations).
Function ■ Protection from short-circuits. ■ Protection of cable from overload.
24
Easy9
Residual current devices
Research worldwide shows that the intensity of current flowing through the body determines the extent and severity of an electric shock.
Operating principleProtection from electric shocks by direct contact:
■ Injuries become serious when currents exceed 40 to 50 mA during one second.
■ Theoretically, a 150 mA current flows through the body when a person touches a 230 V energised conductor under dry conditions.
By measuring the intensity difference between live and neutral conductors, RCDs actually detect the current flowing through the human body.If this current reaches the 30 mA limit, the RCD trips within a few milliseconds, so preventing injury or worse.
Check RCDs regularlyTest
Perception
0.5 mA
10 mA 40 mA
80 mA
1 ACardiac arrest
Muscularcontraction
Burnsrespiratory
Severe burnsventricularfibrilation
Function ■ Protection of persons against electric shock by direct contact (30 mA). ■ Protection of installations against the risk of fire (300 mA). ■ Protection of persons against electric shock by indirect contact
(100 mA to 300 mA).
30 mA16 A
30 mARCD
Testing the RCD every 3 months enables detection of any event that may have impaired its operation
25
Easy9
Selection Residual current sensitivity
Protection from Residential Non-residential SensitivityElectric shocks by direct contact
b Mandatory protection for all socket outlets
b Mandatory protection for all electrical equipment in bathroom
b Recommended for lighting circuits
b Mandatory protection for all socket outlets
b Mandatory protection for all equipement located
b Close to water points
b 30 mA b 10 mA for all applications
where required by the standard (e.g.: jacuzzi, swimming pools, etc.)
Fire ignited by leakage current b Recommended in old buildings
(presence of dust or moisture) b Mandatory in all locations under
risk of fire or explosion b Recommended in all premises
under presence of dust, moisture, chemical agents…
b 300 mA
Electric shock by indirect contact b All circuits in case of "TT" earthing
system b All circuits in case of "TT"
earthing system b 100 mA or 300 mA
Requirements from wiring regulation (411.3.3)Protection by means of a residual current protective device (RCD), shall be provided for:
■ Socket outlets with a rated current not exceeding 20 A, that are for ordinary persons and intended for general use, mobile equipment with a current rating not exceeding 32 A for use outdoors.
■ In rooms containing a bath or a shower.
Current rating: shall not be in excess of upstream MCB current rating
Bathroom
Residual current devicesSelection guide
Easy9
26
Easy9
Notes
Resi9 The complete residential circuit protection offer
Resi9 consumer units
The Resi9 range of consumer units provides arguably the highest levels of residential circuit protection safety. With a wide range of switch disconnectors, RCDs and MCBs, complimented by a single pole RCBO.
Providing speed of installation with safety in mind.
All outgoing devices can be connected in seconds and with no incoming terminal to tighten, the correct mechanical connection force is guaranteed every time. For unused ways, Resi9’s unique fully encapsulated busbar system means that the highest levels of installer and end user protection are always guaranteed.
Even with the front cover of the enclosure removed, the main busbar is protected to IP2X, meaning it remains finger safe but allows access with test probes by the installer. For energy management and safety, Resi9 can also accept a wide range of control devices.
“What really sets Resi9 apart is the plug-on breaker concept and fully encapsulated busbars.”
™
Compliant metal consumer unit
BS 7671:2008Amendment 3 (2015)
Features and benefits
Unique MCB/RCBO fixing system. Provides complete finger safety to IP2XB, bringing increased levels of safety to consumer unit design Tested in accordance with BS EN 61439-3 Unrestricted cable entry can be made from any side Totally encapsulated busbar system Incoming devices can be ordered separately giving a multitude of combinations Type A single pole RCBO Increased levels of user safety with Class II device front faces Retains plug-on philosophy for speed of installation and guaranteed connections Insulated safety pull up shuttered terminals limit incorrect cable insertion Control devices may be installed on any outgoing way No extra mounting accessories required Lockable cover option also available
30
Resi9
Option 1Incoming switch disconnector and outgoing RCBO’s
Option 3Incoming switch disconnector supplying two RCD protected sections
Option 2Split load consumer unit using RCBO’s
Option 4Incoming switch disconnector with RCBO ways and two RCD protected sections
31
Insulated, safety pull up shuttered terminals
Finger touch proof terminals (FTPT)
Class II Front face
Guaranteed plug-on connections
Clear and visible product information whatever the toggle position
Resi9The complete solution
32
Unique plug on system
Type A RCBO devices
Quick and easy to install
50% less connections to torque test
BS7671 compliant enclosures
Guaranteed compliance to standards
33
Resi9The complete residential circuit protection offer
34
Resi9 Switch-disconnector
Compliance with standards BS EN 60947-3-1
Type Width Operating voltage
Rating Cat. no.
9 mm module
(V AC) (A)
2P 4 400 100 R9S87291
1
2
3
4
Degree of pollution: 2.Degree of protection (BS EN 60529): IP20B.Connection:
> copper cable: - rigid: Max. 50 mm² - flexible: Max. 35 mm². > tightening torque: 3.5 N.m.
Switch-disconnectorTo ensure:
> control and disconnection of loaded electrical circuits.It must be protected: - against short circuits occurring downstream - against overloads; its rating must be at least equal to the rating of the upstream
circuit breaker.
ON/OFF
35
Resi9 RCBO residual current circuit breaker
Type AC Width Operating voltage
Sensitivity Rating Cat. no.
9 mm module
(V AC) (mA) (A)
2P 4 230 30 63 R9R81263
30 100 R9R81291
300TD 100 R9R85291
Degree of pollution: 2.Degree of protection (BS EN 60529): IP20B.Connection:
> Copper cable: - rigid: Max. 35 mm² - flexible: Max. 25 mm². > tightening torque: 3.5 N.m.
Compliance with standards
BS EN 61008-1
Residual current circuit breakersHigh sensitivity (30 mA) Protection against electric shocks by direct contact.Use at the incoming end of several feeders:
> recommended for all power sockets. > compulsory for all equipment in bathrooms, outdoors, etc.
Medium sensitivity (300mA) TDProtection against:
> fire following an insulation fault. > electric shocks by indirect contact. > in the event of tripping of a high-sensitivity residual current protection device
downstream, maintains power for the other circuits.Use in residential units at the incoming end of the main switchboard.
36
Resi9 RCBO Residual current device
Compliance with standards
BS EN 61009-1
Type A Width Operating voltage
Sensitivity Rating Cat. no.
9 mm module
(V AC) (mA) (A) B curve
1P+N 2 230 30 6 R9D87806
10 R9D87810
16 R9D87816
20 R9D87820
32 R9D87832
40 R9D87840
50 R9D87850
Class Type ABreaking capacity: 6000 A.Degree of pollution: 2.Degree of protection (BS EN 60529): IP20B.Connection:
> copper cable: - rigid: Max. 25 mm² - flexible: Max. 16 mm². > tightening torque: 2 N.m.
Residual current devices Protection against:
> cable overloads. > short circuits. > electric shocks by direct contact.
Use in place of a circuit breaker, for circuits requiring protection against direct contacts: > recommended for all power sockets. > compulsory for all equipment in bathrooms, outdoors, etc.
L in
N out L out
N in
I Δ
FE
37
Resi9 Circuit breaker
Type Width Operating voltage
Rating Cat. no.
9 mm module
(V AC) (A) B curve C curve
1P 2 230 3 R9F87103 R9F64103
1
2
6 R9F87106 R9F6410610 R9F87110 R9F6411016 R9F87116 R9F6411620 R9F87120 R9F6412025 R9F87125 R9F6412532 R9F87132 R9F6413240 R9F87140 R9F6414050 R9F87150 R9F6415063 R9F87163 R9F64163
Compliance with standards
BS EN 60898-1
- Breaking capacity: 6000 A. - Degree of pollution: 2. - Degree of protection (BS EN 60529): IP20B. - Type C MCB’s denoted by grey appearance - Connection: - > copper cable: - - rigid: ≤ 25 A: Max. 25 mm2, ≥ 32 A: Max. 35 mm2 - - flexible: ≤ 25 A: Max. 16 mm2, ≥ 32 A: Max. 25 mm2. - > tightening torque: - - ≤ 25 A: 2 N.m. - - ≥ 32 A: 3.5 N.m.
Circuit breakersProtection against:
> cable overloads. > short circuits.
38
Resi9 Terminal block
Compliance with standards
BS EN 60998-1
Terminal block > Distribution and sub-distribution of the electric > power supply.
Terminal block Width Cat. no.
1P
100 A 18 mm SE1100L
Degree of protection (BS EN 60529): IP20B.
39
Easy9
Quick selector
Quick selector
40
Select Consumer Unit
™
Compliant metal consumer unit
BS 7671:2008Amendment 3 (2015)
Consumer UnitReference Description No of waysR9BM2L 2 Way Resi9 metal CU 2R9BM4L 4 Way Resi9 metal CU 4
R9BM6L 6 Way Resi9 metal CU 6
R9BM8L 8 Way Resi9 metal CU 8R9BM12L 12 Way Resi9 metal CU 12
R9BM16L 16 Way Resi9 metal CU 16
Dual bankReference Description No of waysR9BM24L 24 Way Resi9 metal CU 24
Split LoadReference Description No of ways
R9BMS4R6L 4+6 Resi9 metal CU 4+6 split load
R9BMS6R4L 6+4 Resi9 metal CU 6+4 split load
R9BMS5R5L 5+5 Resi9 metal CU 4+4 split load
R9BMS7R7L 7+7 Resi9 metal CU 7+7 split load
Dual RCCB - Including IncomersReference Description No of ways
R9BMSR6R6L 6+6 Resi9 metal CU inc 100a Sw & 2 x 63a RCCBs 6+6 dual split
R9BMS2R5R5L 2+5+5 Resi9 metal CU inc 100a Sw & 2 x 63a RCCBs cw 2 unprotected ways 2,5,5, multiple split
R9BMDS2R5R5L 2+5+5 Resi9 metal CU inc 100a Sw & 2 x 100a RCCBs cw 2 unprotected ways 2,5,5, multiple split
The surface mounting enclosure consists of: > Metal surface mounting enclosure with:
> Multiple cable entry points and rear knock out slots > Secure fixed plug on assembly > Fully encapsulated bus bar assembly > Earth terminal block and neutral blocks fitted as standard > Standard consumer units up to 24 ways > Earthed cover > Enclosure colour: White RAL 9003
41
Control devices
May be installed at any outgoing point on the RCD protected or unprotected side
Select devices
Incoming Devices R9R81263 63A/30mA RCCB R9R81291 100A/30mA RCCB R9R85291 100A/300mA RCCB TD R9S87291 100A Switch Disconnector SE1100L 100A 1P Terminal Block
Outgoing Device
MCB’s type B MCB’s type C R9F87103 Single Pole 3A Type B MCB 6kA R9F64103 Single Pole 3A Type C MCB 6kA R9F87106 Single Pole 6A Type B MCB 6kA R9F64106 Single Pole 6A Type C MCB 6kA R9F87110 Single Pole 10A Type B MCB 6kA R9F64110 Single Pole 10A Type C MCB 6kA R9F87116 Single Pole 16A Type B MCB 6kA R9F64116 Single Pole 16A Type C MCB 6kA R9F87120 Single Pole 20A Type B MCB 6kA R9F64120 Single Pole 20A Type C MCB 6kA R9F87125 Single Pole 25A Type B MCB 6kA R9F64125 Single Pole 25A Type C MCB 6kA R9F87132 Single Pole 32A Type B MCB 6kA R9F64132 Single Pole 32A Type C MCB 6kA R9F87140 Single Pole 40A Type B MCB 6kA R9F64140 Single Pole 40A Type C MCB 6kA R9F87150 Single Pole 50A Type B MCB 6kA R9F64150 Single Pole 50A Type C MCB 6kA R9F87163 Single Pole 63A Type B MCB 6kA R9F64163 Single Pole 63A Type C MCB 6kA
RCBO’s - Type A R9D87806 Single Pole 6A/30mA B Curve RCBO R9D87810 Single Pole 10A/30mA B Curve RCBO R9D87816 Single Pole 16A/30mA B Curve RCBO R9D87820 Single Pole 20A/30mA B Curve RCBO R9D87825 Single Pole 25A/30mA B Curve RCBO R9D87832 Single Pole 32A/30mA B Curve RCBO R9D87840 Single Pole 40A/30mA B Curve RCBO R9D87850 Single Pole 50A/30mA B Curve RCBO
Control devices and accessories
A9C20732 ICT 25A 2NO 230...240VAC 50HZ Contactor A9C20834 ICT 25A 4NO 220...240VAC 50HZ Contactor A9C20842 ICT 40A 2NO 220...240VAC 50HZ Contactor A9C20843 ICT 40A 3NO 220...240VAC 50HZ Contactor A9C20844 ICT 40A 4NO 220...240VAC 50HZ Contactor A9C20863 ICT 63A 3NO 220...240VAC 50HZ Contactor A9C30811 ITL16A 1NO 230/240VAC 110VDC 50-60 A9C30812 ITL16A 2NO 230/240VAC 50-60HZ 110V A9E15535 CHANGEOVER RELAY IRLI 10A 2P UC 230V-240 A9A15321 ISO BELL 8 12V A9A15214 BELL TRANSFORMER 4VA 230VCA 8VCA A9A15323 BUZZER 8..12 VCA 70DBA 50..60HZ CCT15368 IC2000 light sensitive switch 15336 24HR analogue time switch with reserve CCT15720 1 Channel IHP program time switch CCT15722 2 Channel IHP program time switch 15363 MIN time switch 1-7mins (delayed off) A9A27062 5X Spacer 9MM - 1/2 module blank SEPLMCB MCB Padlock attachment (pk10) MCB SEPLRCBO RCBO Padlock attachment (pk10) RCBO SEPL Padlock (can be used with MCB or RCBO attachment) EZ9LKITL Door lock kit (for AMD3 metal enclosure only) SEDNBP3 3 module blanking plate module
42
Easy9
Select devices
Incoming Devices R9R81263 63A/30mA RCCB R9R81291 100A/30mA RCCB R9R85291 100A/300mA RCCB TD R9S87291 100A Switch Disconnector SE1100L 100A 1P Terminal Block
Outgoing Device
MCB’s type B MCB’s type C R9F87103 Single Pole 3A Type B MCB 6kA R9F64103 Single Pole 3A Type C MCB 6kA R9F87106 Single Pole 6A Type B MCB 6kA R9F64106 Single Pole 6A Type C MCB 6kA R9F87110 Single Pole 10A Type B MCB 6kA R9F64110 Single Pole 10A Type C MCB 6kA R9F87116 Single Pole 16A Type B MCB 6kA R9F64116 Single Pole 16A Type C MCB 6kA R9F87120 Single Pole 20A Type B MCB 6kA R9F64120 Single Pole 20A Type C MCB 6kA R9F87125 Single Pole 25A Type B MCB 6kA R9F64125 Single Pole 25A Type C MCB 6kA R9F87132 Single Pole 32A Type B MCB 6kA R9F64132 Single Pole 32A Type C MCB 6kA R9F87140 Single Pole 40A Type B MCB 6kA R9F64140 Single Pole 40A Type C MCB 6kA R9F87150 Single Pole 50A Type B MCB 6kA R9F64150 Single Pole 50A Type C MCB 6kA R9F87163 Single Pole 63A Type B MCB 6kA R9F64163 Single Pole 63A Type C MCB 6kA
RCBO’s - Type A R9D87806 Single Pole 6A/30mA B Curve RCBO R9D87810 Single Pole 10A/30mA B Curve RCBO R9D87816 Single Pole 16A/30mA B Curve RCBO R9D87820 Single Pole 20A/30mA B Curve RCBO R9D87825 Single Pole 25A/30mA B Curve RCBO R9D87832 Single Pole 32A/30mA B Curve RCBO R9D87840 Single Pole 40A/30mA B Curve RCBO R9D87850 Single Pole 50A/30mA B Curve RCBO
Control devices and accessories
A9C20732 ICT 25A 2NO 230...240VAC 50HZ Contactor A9C20834 ICT 25A 4NO 220...240VAC 50HZ Contactor A9C20842 ICT 40A 2NO 220...240VAC 50HZ Contactor A9C20843 ICT 40A 3NO 220...240VAC 50HZ Contactor A9C20844 ICT 40A 4NO 220...240VAC 50HZ Contactor A9C20863 ICT 63A 3NO 220...240VAC 50HZ Contactor A9C30811 ITL16A 1NO 230/240VAC 110VDC 50-60 A9C30812 ITL16A 2NO 230/240VAC 50-60HZ 110V A9E15535 CHANGEOVER RELAY IRLI 10A 2P UC 230V-240 A9A15321 ISO BELL 8 12V A9A15214 BELL TRANSFORMER 4VA 230VCA 8VCA A9A15323 BUZZER 8..12 VCA 70DBA 50..60HZ CCT15368 IC2000 light sensitive switch 15336 24HR analogue time switch with reserve CCT15720 1 Channel IHP program time switch CCT15722 2 Channel IHP program time switch 15363 MIN time switch 1-7mins (delayed off) A9A27062 5X Spacer 9MM - 1/2 module blank SEPLMCB MCB Padlock attachment (pk10) MCB SEPLRCBO RCBO Padlock attachment (pk10) RCBO SEPL Padlock (can be used with MCB or RCBO attachment) EZ9LKITL Door lock kit (for AMD3 metal enclosure only) SEDNBP3 3 module blanking plate module
Technical guide
Technical guide
43
Resi9 - metal unit dimensions
Metal units Dimensions (mm) No. of knockouts Reference number No. of ways Type A B D E F G H
25 x 89 30mm 25mm 20mm R9BM2 2 Standard 181 119 – 2 2 8 – R9BM4 4 Standard 222 155 2 2 2 8 – R9BM6 R9BM6SG 6 Standard 258 191 – 2 4 8 – R9BM8 R9BM8SG 8 Standard 294 227 – 2 4 10 2 R9BM12 R9BM12SG 12 Standard 366 299 4 4 4 12 – R9BM16 16 Standard 438 371 4 4 4 16 – R9BM24 24 Standard 366 299 6 4 4 8 – R9BMS4R6 4+6 Split 378 299 4 4 4 12 – R9BMS5R5 5+5 Split 378 299 4 4 4 12 – R9BMS6R4 6+4 Split 378 299 4 4 4 12 – R9BMS7R7 7+7 Split 450 371 4 4 4 16 – R9BMSR6R6 R9BMSR6R6SG 6+6 Multiple 450 371 4 4 4 16 – R9BMDS2R5R5 R9BMDS2R5R5SG 2+5+5 Multiple 450 371 4 4 4 16 – R9BMS2R5R5 R9BMS2R5R5SG 2+5+5 Multiple 450 371 4 4 4 16 –
Note: Rear of enclosure = 242mm high Incoming and outgoing devices must be selected separately from the Resi9 devices section. The following ref’s are supplied with switch disconnector and RCDs fitted:- R9BMSR6R6L, R9BMDS2R5R5L, R9BMS2R5R5L
Cable entry sizes (mm)
116
39
27
247 (surface)259 (flush)
111
86
(all dimensions in mm)
44 54
27
43
12 & 16 Way only
4 to 16 Way only
6 to 16 Way only
27
GGGGGG
E EFF
2 WAY ONLY
5461
180
Dotted lineindicates cover
DFH
D
DF
H
D
635.5Ø
9.5Ø
5.5Ø 73
31 B
A
Height 247mm Depth 111mm
Metal UnitsRef No. Type Useable No Ways Height (mm) Width (mm) Depth (mm)
R9BM2L Standard 2 247 186 112
R9BM4L Standard 4 247 222 112
R9BM6L Standard 6 247 258 112
R9BM8L Standard 8 247 294 112
R9BM12L Standard 12 247 366 112
R9BM16L Standard 16 247 438 112
R9BM24L Standard 24 487 366 112
R9BMS4R6L Split 10 247 366 112
R9BMS6R4L Split 10 247 366 112
R9BMS5R5L Split 10 247 366 112
R9BMSR6R6L Split 12 247 438 112
R9BMS7R7L Split 14 247 438 112
R9BMS2R5R5L Multiple 12 247 438 112
R9BMDS2R5R5L Multiple 12 247 438 112
44
No. Of knockouts
Dimensions (mm) 25 x 90mm
32mm 25mm 20mm
Ref No. A B D E F G
R9BM2L 181 119 - 2 2 8
R9BM4L 217 155 2 2 2 8
R9BM6L 253 191 2 2 4 8
R9BM8L 289 227 2 2 4 10
R9BM12L 361 299 4 4 4 12
R9BM16L 433 371 4 4 4 16
R9BM24L 361 299 6 4 4 8
R9BMS4R6L 361 299 4 4 4 12
R9BMS6R4L 361 299 4 4 4 12
R9BMS5R5L 361 299 4 4 4 12
R9BMSR6R6L 433 371 4 4 4 16
R9BMS7R7L 433 371 4 4 4 16
R9BMDS2R5R5L 433 371 4 4 4 16
R9BMS2R5R5L 433 371 4 4 4 16
For short circuit back-up protection, maximum fuse rating:- Residual current breakers Reference number Description Cable capacity Dimensions Weight mm2 Height Width Depth kg SED25032 25A RCCB 30mA trip 2 pole 35 81 36 75 0.227 SED25302 25A RCCB 300mA trip 2 pole 35 81 36 75 0.227 SED40032 40A RCCB 30mA trip 2 pole 35 81 36 75 0.227 SED40102 40A RCCB 100mA trip 2 pole 35 81 36 75 0.227 SED40302 40A RCCB 300mA trip 2 pole 35 81 36 75 0.227 SED63032 63A RCCB 30mA trip 2 pole 35 81 36 75 0.227 SED63102 63A RCCB 100mA trip 2 pole 35 81 36 75 0.227 SED63302 63A RCCB 300mA trip 2 pole 35 81 36 75 0.227 SED80032 80A RCCB 30mA trip 2 pole 50 81 36 75 0.227 SED100032 100A RCCB 30mA trip 2 pole 50 81 36 75 0.227 SED100102 100A RCCB 100mA trip 2 pole 50 81 36 75 0.227
Technical data Metal
Max. busbar current rating (A) 100 Max. operating voltage (V) 240 Operating frequency (Hz) 50 Max. incoming cable capacity mm2 (phase and neutral) 50 Max. outgoing cable capacity mm2 25 Certification BS EN 61439-3 IP rating BS EN 60529 (internal) IP2XB
UK contact details -
0870 608 8 608Fax 0870 608 8 606
Ireland contact details -
01 601 2200Fax 01 601 2201
As the global specialist in energy management with operations in more than 100 countries, Schneider Electric offers integrated solutions across multiple market segments, including leadership positions in energy and infrastructure, industrial processes, building automation, and data centres/networks, as well as a broad presence in residential applications.
Schneider Electric is dedicated to making individuals’ and organisations’ energy safe, reliable, efficient, productive and green from Power Plant to PlugTM.
We are changing our brand names and becoming one Schneider Electric. You’ll get the same great quality products, but from one name you can remember and trust. This provides you and your customers with the reassurance associated with Schneider Electric.
Some of our market leading brands have already become Schneider Electric including Merlin Gerin, Telemecanique, Square D, GET, Mita, Sarel, Himel, Thorsman, Tower and TAC.
Working as one Schneider Electric makes it clearer that our ranges are highly compatible for integrated solutions.
Schneider Electric Ltd
Schneider Electric Limited is a company registered in England and Wales.Registered number: 1407228. Registered office: Stafford Park 5, Telford, Shropshire TF3 3BL.
© 2014 Schneider Electric. All Rights Reserved. Schneider Electric, Active Energy Management, Compact, EcoStruxure, ION Enterprise, iRIO, Make the most of your energy, Masterpact, Micrologic, Power Plant To Plug, Modbus, and PowerLogic are owned by Schneider Electric Industries SAS, or its affiliated companies in the United States and other countries.