e702.1 allowable stress design of rc masonry shear wall 2006-03-29
TRANSCRIPT
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
1/17
American Concrete Institute®
Advancing concrete knowledge
Designing Concrete Structures:
E702.1
Allowable-Stress Design of Reinforced
Concrete Masonry Shear Wall
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
2/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
1
Example #1: Allowable-Stress Design of Reinforced Concrete Masonry Shear Wall
Using the allowable-stress provisions of the 2005 MSJC Code (ACI 530), design the reinforced concrete
masonry shear wall shown below. In the context of an entire building design, design loads would be
obtained using the appropriate provisions of the legally adopted building code (which usually references
ASCE 7). For this facet of the design, unfactored loads are shown below, and are assumed to be due to
earthquake. Corresponding shear and moment diagrams are also shown.
24 ft
10 ft
10 ft
10 ft
10 ft
1 224 ft
10 ft
10 ft
10 ft
10 ft
1 2
30
60
90
120
300
900
1800
3000
Lateral Loads Shear, kips Moment, kip-ft
30 kips
30 kips
30 kips
30 kips
30
60
90
120
300
900
1800
3000
Lateral Loads Shear, kips Moment, kip-ft
30 kips
30 kips
30 kips
30 kips
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
3/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
2
Assume an 8-in. nominal concrete masonry wall, grouted solid, with Type S PCL mortar. The total
plan length of the wall is 24 ft (288 in.), and its specified thickness is 7.63 in. Assume an effective
depth d of 285 in.
Concrete MasonryUnit Strength (C90) 1900 psi
Mortar Type S
f ′ m or f g 1,500 psi
E m or E g 1.35 × 106 psi
Reinforcement = Grade 60; E s = 29 × 106 psi
Unfactored axial loads on the wall are given in the table below.
Level DL LL
(Top of Wall) (kips) (kips)
4 90 15
3 180 35
2 270 55
1 360 75
Check shear for the assumed wall thickness.
Use ASCE 7-05 ASD Load Combination 5: 0.6 D + 0.7 E
V = 0.7 x 120,000 lb = 84,000 lb
M = 0.7 x 3000 kip-ft = 2100 kip-ft
P = 0.6 x 360 kips = 216 kips
By Code Section 2.3.5.2.1,
psi6.3828563.7
lb000,84=
×==
bd
V f v
05.1
.in285kips201
/ft.in12ftkip3000=
×
×−=
Vd
M
By Code Section 2.3.5.2.2(b), where shear reinforcement is not provided to resist the calculated
shear:
psi1.381500)05.14(4 3131 =−=′⎟ ⎠
⎞⎜⎝
⎛ −= mv f
Vd
M F
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
4/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
3
but [ ] GOVERNS 8.32)05.1(4580)(4580 ⇐=−=−≤ psiVd M F v
needed isentreinforcemShear psi6.38 ∴>=vv F f
Now check against the higher allowable shear stresses of Code Section 2.3.5.2.3:
GOVERNS psi13.571500)05.14(4 2121 ⇐=−=′⎟ ⎠
⎞⎜⎝
⎛ −= mv f
Vd
M F
but [ ] OK psi38.6 psi75.72)/(45120 >=−≤ Vd M F v
Design shear reinforcement using Code Section 2.3.2.1 and Code Section 2.3.5.3:
F s = 24,000 psi
2in.29.0.285000,24
.24000,84=
××
=⎟⎟ ⎠
⎞⎜⎜⎝
⎛ =
in psi
inkips
d F
Vs A
s
v
Use No. 5 bars horizontally at 24 inches on center
Now consider the flexural design. The attached spreadsheet for this problem illustrates how to
calculate an allowable-stress moment-axial force interaction diagram for this wall. That spreadsheet
is first used to check the wall with reinforcement consisting of #5 bars @ 4 ft. Because the space
between extreme bars is not quite a multiple of 48 in., the spacing of the interior bars is adjusted
slightly to fit the 16-in. nominal length of the concrete masonry units.
Depending on the building’s Seismic Design Category, prescriptive seismic provisions might require
more reinforcement or a closer spacing of reinforcement than those calculated above.
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
5/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
4
Al lowable-Stress Interact ion Diagram by Spreadsheet
Concrete Masonry Shear Wall of Example Problem
f'm=1500 psi, 24 ft long, 7.63 in. thick, #5 bars @ 4'
0
100
200
300
400
500
600
700
800
900
0 500 1000 1500 2000 2500 3000
Al lowable M, f t-k ips
A l l o w a b l e P ,
k i p s
The interaction diagram shows that the wall, as designed above, can resist the combination of axial
load and moment (216 kips, 2100 kip-ft).
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
6/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
5
Example #2: Allowable-Stress Design of Reinforced Concrete Masonry Shear Wall (SI Units)
Using the allowable-stress provisions of the 2005 MSJC Code (ACI 530), design the reinforced concrete
masonry shear wall shown below. In the context of an entire building design, design loads would be
obtained using the appropriate provisions of the legally adopted building code (which usually references
ASCE 7). For this facet of the design, unfactored loads are shown below, and are assumed to be due to
earthquake. Corresponding shear and moment diagrams are also shown.
7.32 m
3.05 m
3.05 m
3.05 m
3.05 m
1 27.32 m
3.05 m
3.05 m
3.05 m
3.05 m
1 2
133.44
266.88
400.32
533.76
406.8
1220.4
2440.8
4068
Lateral Loads Shear, kN Moment, kN-m
133.44 kN
133.44 kN
133.44 kN
133.44 kN
133.44
266.88
400.32
533.76
406.8
1220.4
2440.8
4068
Lateral Loads Shear, kN Moment, kN-m
133.44 kN
133.44 kN
133.44 kN
133.44 kN
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
7/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
6
Assume an 203.2-mm nominal concrete masonry wall, grouted solid, with Type S PCL mortar. The
total plan length of the wall is 7.315 m, and its specified thickness is 193.8 mm. Assume an effective
depth d of 7.239 m.
Concrete MasonryUnit Strength (C90) 13.10 MPa
Mortar Type S
f ′ m or f g 10.34 MPa
E m or E g 9308 MPa
Reinforcement = Grade 60; E s = 199,955 MPa
Unfactored axial loads on the wall are given in the table below.
Level DL LL
(Top of Wall) (kN) (kN)
4 400.32 66.72
3 800.64 155.68
2 1200.96 244.64
1 1601.28 333.60
Check shear for the assumed wall thickness.
Use ASCE 7-05 ASD Load Combination 5: 0.6 D + 0.7 E
V = 0.7 x 533.76 kN = 373.63 kN
M = 0.7 x 4068 kN-m = 2847.6 kN-m
P = 0.6 x 1601 kN = 960.77 kN
By Code Section 2.3.5.2.1,
MPa26632.072398.193
kN63.3732 =
×==
mmbd
V f v
05.1
239.763.373
2847=
×
−=
mkN
mkN
Vd
M
By Code Section 2.3.5.2.2(b), where shear reinforcement is not provided to resist the calculated
shear:
MPa26.034.10)05.14(028.04028.0 =−=′⎟ ⎠
⎞⎜⎝
⎛ −= mv f
Vd
M F
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
8/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
7
but [ ] GOVERNS 22.0)05.1(31.055.0)(31.055.0 ⇐=−=−≤ MPaVd M F v
needed isentreinforcemShearMPai266.0 ∴>=vv F f
Now check against the higher allowable shear stresses of Code Section 2.3.5.2.3:
GOVERNS MPa40.034.10)05.14(42.04042.0 ⇐=−=′⎟ ⎠
⎞⎜⎝
⎛ −= mv f Vd
M F
but [ ] OK MPa266.0MPa49.0)/(31.082.0 =>=−≤ vv f Vd M F
Design shear reinforcement using Code Section 2.3.2.1 and Code Section 2.3.5.3:
F s = 165.48 MPa
2mm190723948.165
6.60963.373=
×
×=⎟⎟
⎠
⎞⎜⎜⎝
⎛ =
mm MPa
mmkN
d F
Vs A
s
v
Use 16-mm bars horizontally at 609.6 mm on center
Now consider the flexural design. The attached spreadsheet for this problem illustrates how to
calculate an allowable-stress moment-axial force interaction diagram for this wall. That spreadsheet
is first used to check the wall with reinforcement consisting of 16-mm bars @ 1.22 m. Because the
space between extreme bars is not quite a multiple of 1.22 m., the spacing of the interior bars is
adjusted slightly to fit the 406.4-mm nominal length of the concrete masonry units.
Depending on the building’s Seismic Design Category, prescriptive seismic provisions might require
more reinforcement or a closer spacing of reinforcement than those calculated above.
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
9/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
8
Al lowable-Stress Interact ion Diagram by Spreadsheet (SI)
Concrete Masonry Shear Wall of Example Problem
f'm=10.34 MPa, 7.32 m long, 193.8 mm thick, 16-mm bars @ 1.22 m
0
500
1000
1500
2000
2500
3000
3500
4000
0 500 1000 1500 2000 2500 3000 3500 4000
Al lowable M, kN-m
A l l o w a b l e P ,
k N
The interaction diagram shows that the wall, as designed above, can resist the combination of axial load
and moment (960.77 kN, 2847.6 kN-m).
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
10/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
9
Example #3: Strength Design of Reinforced Concrete Masonry Shear Wall
Using the strength provisions of the 2005 MSJC Code (ACI 530), design the reinforced concrete
masonry shear wall shown below. In the context of an entire building design, design loads would be
obtained using the appropriate provisions of the legally adopted building code (which usually references
ASCE 7). For this facet of the design, unfactored loads are shown below, and are assumed to be due to
earthquake. Corresponding shear and moment diagrams are also shown.
24 ft
10 ft
10 ft
10 ft
10 ft
1 224 ft
10 ft
10 ft
10 ft
10 ft
1 2
30
60
90
120
300
900
1800
3000
Lateral Loads Shear, kips Moment, kip-ft
30 kips
30 kips
30 kips
30 kips
30
60
90
120
300
900
1800
3000
Lateral Loads Shear, kips Moment, kip-ft
30 kips
30 kips
30 kips
30 kips
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
11/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
10
Assume an 8-in. nominal concrete masonry wall, grouted solid, with Type S PCL mortar. The total
plan length of the wall is 24 ft (288 in.), and its specified thickness is 7.63 in. Assume an effective
depth d of 285 in.
Concrete MasonryUnit Strength 1,900
Mortar Type S
f ′ m or f g (psi) 1,500
Reinforcement = Grade 60; E s = 29 × 106 psi
Unfactored axial loads on the wall are given in the table below.
Level DL LL
(Top of Wall) (kips) (kips)
4 90 15
3 180 35
2 270 55
1 360 75
Use ASCE 7-05 Basic Strength Load Combination 7: 0.9 D + 1.0 E
Check shear for assumed wall thickness. By Section 3.3.4.1.2 of the 2005 MSJC Code,
smn
V V V +=
M u = 3,000 x 12 x 1,000 in.-lb = 36.0 x 106 in.-lb
V u = 120,000 lb d v = 285 in.
05.1in.)(285lb120,000
lb-in.1036/
6
=×
=vuu d V M
By Code 3.3.4.1.2.1, (Mu / Vu d v) need not be taken greater than 1.0.
P f Ad V
M V
mnvu
u
m
25.0'75.10.4 +⎥⎥⎦
⎤
⎢⎢⎣
⎡
⎟⎟ ⎠
⎞
⎜⎜⎝
⎛ −=
( )[ ]
kipskipsV
ininV
m
m
5.2790.905.189
lb)000,360(25.0 psi1500.285.63.70.175.10.4
=+=
+×−=
un V V >φ 80.0=φ kipsV V mn 5.279==
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
12/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
11
kipsV kipskips u 1206.223)5.279(80.0 =≥=
Shear design is satisfactory so far, even without shear reinforcement. Code Section 3.1.3 will be checked
later.
Now check flexural capacity using a spreadsheet-generated moment-axial force interaction diagram. Try
#5 bars @ 4 ft.
Strength Interaction Diagram by Spreadsheet
Concrete Masonry Shear Wall of Example Problem
f'm=1500 psi, 24 ft long, 7.63 in. thick , #5 bars @ 4'
0
200
400
600
800
1000
1200
1400
1600
1800
2000
0 1000 2000 3000 4000 5000 6000 7000 8000
Mn, ft-kips
P n ,
k i p s
At a factored axial load of 0.9D, or 0.9 x 360 kips = 324 kips, the design flexural capacity of this wall is
about 4000 ft-kips, and the design is satisfactory for flexure.
Now check Code Section 3.1.3. First try to meet the capacity design provisions of that section. At an
axial load of 324 kips, the nominal flexural capacity of this wall is 4000 ft-kips, divided by the strength
reduction factor of 0.9, or 4,444 ft-kips. The ratio of this nominal flexural capacity to the factored designmoment is 4,444 divided by 3,000, or 1.48. Including the additional factor of 1.25, that gives a ratio of
1.85.
kipsV V V V
V V
uuun
un
5.27712031.231.28.0
85.185.1
85.1
=×===≥
≥
φ
φ
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
13/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
12
The wall requires shear reinforcement. Prescriptive seismic reinforcement (for example, for SDC C) will
probably be satisfied with #5 bars horizontally @ 24 in.
kipskipsV
ininksiin
sd f AkipsV V V
n
yvsmn
9.3894.1105.329
.24.28560.31.0
215.279
215.379 2
=+=
×⎟ ⎠ ⎞⎜
⎝ ⎛ +=⎟
⎠ ⎞⎜
⎝ ⎛ +=+=
Prescriptive seismic reinforcement is sufficient for shear. Use #5 bars at 2 ft.
Check ρmax , assuming that the wall is classified as an intermediate reinforced masonry shear wall.
smu
ymu
mu
ymu
y
y
u
yma
mum
E f
bd
P f
ε ε ε
ε
ε ε
ε ε ε
ε
ρ
⎟⎟ ⎠
⎞⎜⎜⎝
⎛
+−⎟
⎟ ⎠
⎞⎜⎜⎝
⎛
+
−⎟⎟
⎠
⎞⎜⎜
⎝
⎛
+=
35.0
3
33
64.0 '
max
In accordance with MSJC Code Section 3.3.3.5.1(d), the governing axial load combination is
D + 0.75 L + 0.525 QE , and the axial load is (360,000 + 0.75 x 75,000 lb), or 416,250 lb.
( )
00127.0
10290025.0)00207.0(30025.0
0025.0
5.0(0.00207)30.0025
3(0.00207)
psi)000,60(
in.285in.)(7.63
lb250,416
(0.00207)30.0025
0.0025 psi)500,1(64.0
max
6
max
=
××⎥⎦
⎤
⎢⎣
⎡
+−⎥⎦
⎤
⎢⎣
⎡
+
−⎥⎦
⎤⎢⎣
⎡
+=
ρ
ρ
psi
Check maximum area of flexural reinforcement per 48 in. of wall length
2
maxmax in.0.46in.48in.)63.7(00127.0.48 ==×= inb As ρ
We have 0.31 in.2 every 48 in., and the design is satisfactory.
Summary:
Use #5 @ 4 ft vertically, #5 @ 2 ft horizontally.
Because the space between extreme bars is not quite a multiple of 48 in., the spacing of the interior
bars is adjusted slightly to fit the nominal 16-in. length of the concrete masonry units.
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
14/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
13
Example #4: Strength Design of Reinforced Concrete Masonry Shear Wall (SI Units)
Using the strength provisions of the 2005 MSJC Code (ACI 530), design the reinforced concrete
masonry shear wall shown below. In the context of an entire building design, design loads would be
obtained using the appropriate provisions of the legally adopted building code (which usually references
ASCE 7). For this facet of the design, unfactored loads are shown below, and are assumed to be due to
earthquake. Corresponding shear and moment diagrams are also shown.
7.32 m
3.05 m
3.05 m
3.05 m
3.05 m
1 27.32 m
3.05 m
3.05 m
3.05 m
3.05 m
1 2
133.44
266.88
400.32
533.76
406.8
1220.4
2440.8
4068
Lateral Loads Shear, kN Moment, kN-m
133.44 kN
133.44 kN
133.44 kN
133.44 kN
133.44
266.88
400.32
533.76
406.8
1220.4
2440.8
4068
Lateral Loads Shear, kN Moment, kN-m
133.44 kN
133.44 kN
133.44 kN
133.44 kN
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
15/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
14
Assume an 203.2-mm nominal concrete masonry wall, grouted solid, with Type S PCL mortar. The
total plan length of the wall is 7.315 m, and its specified thickness is 193.8 mm. Assume an effective
depth d of 7.239 m.
Concrete MasonryUnit Strength 13.10 MPa
Mortar Type S
f ′ m or f g 10.34 MPa
Reinforcement = Grade 60; E s = 199,955 MPa
Unfactored axial loads on the wall are given in the table below.
Level DL LL
(Top of Wall) (kN) (kN)
4 400.32 66.72
3 800.64 155.68
2 1200.96 244.64
1 1601.28 333.60
Use ASCE 7-05 Basic Strength Load Combination 7: 0.9 D + 1.0 E
Check shear for assumed wall thickness. By Section 3.3.4.1.2 of the 2005 MSJC Code,
smn
V V V +=
05.1m)(7.239kN533.76
m-kN4068/ ==vuu d V M
By Code 3.3.4.1.2.1, (Mu / Vu d v) need not be taken greater than 1.0.
P f Ad V
M V mn
vu
um 25.0'75.10.4083.0 +
⎥⎥⎦
⎤
⎢⎢⎣
⎡⎟⎟ ⎠
⎞⎜⎜⎝
⎛ −=
( )[ ] ( )kN kN V mmmmV
m
m
5.12424005.842kN)1601(25.0MPa34.1072398.1930.175.10.4083.0
=+=+×−=
un V V >φ 80.0=φ kN V V mn 5.1242==
kN V kN kN u 76.5330.994)5.1242(80.0 =≥=
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
16/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
15
Shear design is satisfactory so far, even without shear reinforcement. Code Section 3.1.3 will be checked
later.
Now check flexural capacity using a spreadsheet-generated moment-axial force interaction diagram. Try
16-mm bars @ 1.22 m.
Strength Interaction Diagram by Spreadsheet (SI units)
Concrete Masonry Shear Wall of Example Problem
f'm=10.34 MPa, 7.32 m long, 193.8 in. thick, 16-mm bars @ 1.22 m
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
0 2000 4000 6000 8000 10000 12000
Mn, kN-m
P n ,
k N
At a factored axial load of 0.9D, or 0.9 x 1601 kN = 1441 kN, the design flexural capacity of this wall is
about 5400 kN-m, and the design is satisfactory for flexure.
Now check Code Section 3.1.3. First try to meet the capacity design provisions of that section. At an
axial load of 1441 kN, the nominal flexural capacity of this wall is 5424 kN-m, divided by the strength
reduction factor of 0.9, or 6,027 kN-m. The ratio of this nominal flexural capacity to the factored design
moment is 6,027 divided by 4068, or 1.48. Including the additional factor of 1.25, that gives a ratio of
1.85.
kN V V V V
V V
uuun
un
123376.53331.231.28.0
85.185.1
85.1
=×===≥
≥
φ
φ
The wall requires shear reinforcement. Prescriptive seismic reinforcement (for example, for SDC C) will
probably be satisfied with 16-mm bars horizontally @ 609.6 mm.
-
8/9/2019 E702.1 Allowable Stress Design of RC Masonry Shear Wall 2006-03-29
17/17
March 29, 2006 E702 Example Problems -- Concrete Masonry Shear Wall R. E. Klingner
16
kN kipsV
mm
mm MPamm
s
d f AkN V V V
n
yvsmn
17341.4915.1242
6.609
72397.4139.197
2
15.1242
2
15.1242 2
=+=
×⎟ ⎠
⎞⎜⎝
⎛ +=⎟ ⎠
⎞⎜⎝
⎛ +=+=
Prescriptive seismic reinforcement is sufficient for shear. Use 16-mm bars at 609.6 mm.
Check ρmax , assuming that the wall is classified as an intermediate reinforced masonry shear wall.
smu
ymu
mu
ymu
y
y
u
yma
mum
E f
bd
P f
ε
ε ε
ε
ε ε
ε
ε ε
ε
ρ
⎟⎟
⎠
⎞⎜⎜
⎝
⎛
+
−⎟⎟
⎠
⎞⎜⎜
⎝
⎛
+
−⎟⎟ ⎠
⎞⎜⎜⎝
⎛
+=
3
5.0
3
3
364.0
'
max
In accordance with MSJC Code Section 3.3.3.5.1(d), the governing axial load combination is
D + 0.75 L + 0.525 QE , and the axial load is (1601 + 0.75 x 333.6 kN), or 1851.2 kN.
( )
00127.0
995,1990025.0)00207.0(30025.0
0025.05.0
(0.00207)30.0025
3(0.00207)MPa)7.413(
mm7239mm)(193.8
1000kN2.1851
(0.00207)30.0025
0.0025MPa)34.10(64.0
max
max
=
×⎥⎦
⎤⎢⎣
⎡
+−⎥
⎦
⎤⎢⎣
⎡
+
×−⎥
⎦
⎤⎢⎣
⎡
+=
ρ
ρ
MPa
Check maximum area of flexural reinforcement per 1.22 m of wall length
2
maxmax mm27.300mm1220mm)8.193(00127.01220 ==×= mmb As ρ
We have 197.9 mm2 every 1.22 m, and the design is satisfactory.
Summary:
Use 16-mm bars @ 1.22 m vertically, 16-mm bars @ 606.9 mm horizontally.
Because the space between extreme bars is not quite a multiple of 1.22 m, the spacing of the interior
bars is adjusted slightly to fit the nominal 406.4-mm length of the concrete masonry units.