e3.3 tat specifications - university of south floridausfweb2.usf.edu/bids...

11
220 West 7th Ave, Suite 210 Tampa, Florida 33602 TEL 888.891.9713 COA 27158 Project No. 13104 Sheet List Table Sheet Number Sheet Title 0.0 TAT COVER E0.1 TAT FIRE ALARM SYMBOL LEGEND RISER AND NOTES E1.1 TAT BASEMENT FLOOR DEMOLITION PLAN - FIRE ALARM E1.2 TAT FIRST FLOOR DEMOLITION PLAN - FIRE ALARM E1.3 TAT SECOND FLOOR DEMOLITION PLAN - FIRE ALARM E2.1 TAT BASEMENT FLOOR PLAN - FIRE ALARM E2.2 TAT FIRST FLOOR PLAN - FIRE ALARM E2.3 TAT SECOND FLOOR PLAN - FIRE ALARM FACILITIES PLANNING AND CONSTRUCTION TAT BUILDING AREA OF WORK E3.1 TAT SPECIFICATIONS E3.1 TAT SPECIFICATIONS E3.1 TAT SPECIFICATIONS

Upload: others

Post on 26-May-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: E3.3 TAT SPECIFICATIONS - University of South Floridausfweb2.usf.edu/BIDS 2014-15/15-002-ppb-tat-fire-alarm/15-002-ppb-upgrades.pdfe3.1 tat specifications e3.1 tat specifications e3.1

220 West 7th Ave, Suite 210

Tampa, Florida 33602 TEL 888.891.9713

COA 27158 Project No. 13104

Sheet List TableSheet Number Sheet Title

0.0 TAT COVER

E0.1 TAT FIRE ALARM SYMBOL LEGEND RISER AND NOTES

E1.1 TAT BASEMENT FLOOR DEMOLITION PLAN - FIRE ALARM

E1.2 TAT FIRST FLOOR DEMOLITION PLAN - FIRE ALARM

E1.3 TAT SECOND FLOOR DEMOLITION PLAN - FIRE ALARM

E2.1 TAT BASEMENT FLOOR PLAN - FIRE ALARM

E2.2 TAT FIRST FLOOR PLAN - FIRE ALARM

E2.3 TAT SECOND FLOOR PLAN - FIRE ALARM

FACILITIES PLANNING AND CONSTRUCTION

TAT BUILDINGAREA OF WORK

E3.1 TAT SPECIFICATIONS

E3.1 TAT SPECIFICATIONS

E3.1 TAT SPECIFICATIONS

Page 2: E3.3 TAT SPECIFICATIONS - University of South Floridausfweb2.usf.edu/BIDS 2014-15/15-002-ppb-tat-fire-alarm/15-002-ppb-upgrades.pdfe3.1 tat specifications e3.1 tat specifications e3.1

SD SD

FIRE ALARMCONTROL PANEL(FACP)

NOTES:1. SIZE CONDUIT PER FIRE ALARM MANUFACTURER RECOMMENDATION, PROVIDE 3/4" CONDUIT MINIMUM.2. SEE FLOOR PLANS FOR QUANTITY AND LOCATION OF DEVICES.3. SPEAKER, STROBE, AND OTHER INDICATING FIRE ALARM DEVICES SHALL BE MOUNTED 80" AFF TO BOTTOM OF DEVICE.4. CONTRACTOR SHALL PROVIDE FIRE ALARM SHOP DRAWINGS TO INCLUDE THE FOLLOWING PER NFPA 72:

A. INDICATE TYPE OF BUILDING CONSTRUCTION AND OCCUPANCYB. INDICATE TYPE OF FIRE ALARM SYSTEM, FIRE ALARM DEVICES, AND AREA OF COVERAGE.C. INDICATE ALL FIRE ALARM DEVICES AND EQUIPMENT ON PLANS AND WIRING DIAGRAMS.D. INDICATE ALL FIRE ALARM DEVICES AND EQUIPMENT ON PLANS, WIRING DIAGRAMS, CALCUALTIONS SHOWING SECONDARY SUPPLY AND VOLTAGE

DROP, AND RESPONSE POINTS.E. COMPLETE LIST OF DETECTION, EVACUATION SIGNALING AND ANNUCIATOR ZONES.F. INDICATE CANDELA RATINGS FOR ALL VISUAL NOTIFICATION DEVICES.G. COMPLETE LIST OF SAFETY CONTROL FUNCTIONS, SEQUENCE OF OPERATIONS DETAILING ALL INPUTS AND OUTPUTS.H. NOTE ON PLAN INDICATING THAT THE INSTALLATION SHALL BE CERTIFICATED AND THE INSTALLATION SHALL BE PLACARDED.

5. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL BOXES AND CONDUIT AS DIRECTED BY FIRE ALARM CONTRACTOR.6. PROVIDE PLEMUN RATED CABLE.

NTSFIRE ALARM RISER DIAGRAM

1" CONDUIT TO MAIN TELE/DATA ROOM

BASEMENT FLOOR

FIRST FLOOR

SECOND FLOOR

FIRE ALARMANNUNCIATOR PANEL(FAAN) WITH REMOTEMICROPHONE

NO SCALEELEVATOR, FULLY SPRINKLED BUILDINGFIRE ALARM DETAIL FOR HYDRAULIC

SMOKE DETECTOR AND 135 DEG F FIXED TEMPRATURE HEAT DETECTOR IN ELEVATOR MACHINE ROOM.

SHUNT TRIP CONTACT-TYPICAL (AUXILIARY CONTACT IN HEAT DETECTOR)

FLASHING WARNING LIGHT LOCATED ADJACENT TO ELEVATOR "PHASE 1" RECALL SWITCH

FLASHING WARNING LIGHTS LOCATED ADJACENT TO ELEVATOR CALL BUTTON AT PRIMARY & ALTERNATE ACCESS LEVELS

FIRE SPRINKLER VALVE TAMPER SWITCH

SMOKE DETECTOR LOCATED IN ELEVATOR LOBBY.

1. DERIVE POWER FOR FLASHING WARNING LIGHT FROM VISUAL ALARM CIRCUIT IN FIRE ALARM CONTROL PANEL.

2. COORDINATED HEAT DETECTOR SHALL BE FIXED TEMPERATURE 135 DEG F & SPRINKLER HEAD SHALL BE 286 DEG F.

3. INITIATION OF ELEVATOR LOBBY, TOP OF SHAFT, OR MACHINE ROOM SMOKE DETECTOR LOOP SHALL PLACE

NOTES:

LEGEND

ELEVATORMACHINEROOM

FIRE ALARMMODULEANNUCIATIONCKT.

ELEVATOR PIT

1ST. FLOOR

FIRE ALARM FLOOR ZONE

FIRE ALARMTROUBLE CIRCUIT

TOP FLOORS (TYP)

FIRE ALARM MODULEANNUNCATION CKT.

FIRE ALARM ZONEFOR ELEVATOR

TO SHUNT TRIP CIRCUIT BREAKEROF ELEVATORPOWER CKT.

TROUBLE CIRCUITFIRE ALARM

WARNING LIGHT"DO NOT USE ELEVATOR"

FIRE ALARM FLOOR ZONE

2ND. FLOOR

FIRE ALARM FLOOR ZONE

ELEVATOR CONTROL INTO PHASE 1 RECALL MODE & RETURN ELEVATOR TO DESIGNATED SAFE PLACE.

FIRE ALARM SEQUENCE OF OPERATIONA. GENERAL OPERATION: THE ALARM ACTIVATION OF ANY AREA SMOKE DETECTOR, HEAT DETECTOR, MANUAL PULL

STATION, SPRINKLER WATERFLOW, THE FOLLOWING FUNCTIONS SHALL AUTOMATICALLY OCCUR:

1. THE INTERNAL AUDIBLE DEVICE SHALL SOUND AT THE CONTROL PANEL AND REMOTE ANNUNCIATOR.2. THE LCD DISPLAY SHALL INDICATE ALL APPLICABLE INFORMATION ASSOCIATED WITH THE ALARM CONDITION

INCLUDING; DEVICE TYPE, DEVICE LOCATION AND TIME/DATE.3. ALL SYSTEM ACTIVITY/EVENTS SHALL BE DOCUMENTED IN SYSTEM HISTORY.4. ANY REMOTE OR LOCAL ANNUNCIATOR LCD/LED'S ASSOCIATED WITH THE ALARM SHALL BE ILLUMINATED.5. ACTIVATE AN EVACUATION MESSAGE THROUGHOUT THE BUILDING. IT SHALL BE THE INTENT OF THIS MESSAGE TO

ADVICE OCCUPANTS HEARING THIS MESSAGE THAT THEY ARE TO EVACUATE THE BUILDING, VIA THE QUICKESTROUTE, IMMEDIATELY.

6. ACTIVATE VISUAL STROBES NOTIFICATION APPLIANCES THROUGHOUT THE BUILDING. THE VISUAL STROBE SHALLCONTINUE TO FLASH UNTIL THE SYSTEM HAS BEEN RESET. THE VISUAL STROBE SHALL NOT STOP OPERATINGWHEN THE "ALARM SILENCE" IS PRESSED.

7. TRANSMIT AN ALARM SIGNAL TO THE CENTRAL STATION.8. ALL AUTOMATIC EVENTS PROGRAMMED TO THE ALARM POINT SHALL BE EXECUTED AND THE ASSOCIATED OUTPUTS

ACTIVATED.

B. SUPERVISORY DUCT SMOKE OPERATION: THE ALARM ACTIVATION OF ANY DUCT SMOKE DETECTOR, THE FOLLOWINGFUNCTIONS SHALL AUTOMATICALLY OCCUR:

1. THE INTERNAL AUDIBLE DEVICE SHALL SOUND AT THE CONTROL PANEL AND REMOTE ANNUNCIATOR.2. THE LCD DISPLAY SHALL INDICATE ALL APPLICABLE INFORMATION ASSOCIATED WITH THE ALARM CONDITION

INCLUDING; DEVICE TYPE, DEVICE LOCATION AND TIME/DATE.3. ALL SYSTEM ACTIVITY/EVENTS SHALL BE DOCUMENTED IN SYSTEM HISTORY.4. ANY REMOTE OR LOCAL ANNUNCIATOR LCD/LED'S ASSOCIATED WITH THE ALARM SHALL BE ILLUMINATED.5. TRANSMIT AN ALARM SIGNAL TO THE CENTRAL STATION.6. SHUTDOWN THE LOCAL AIR HANDLING UNIT.7. ALL AUTOMATIC EVENTS PROGRAMMED TO THE ALARM POINT SHALL BE EXECUTED AND THE ASSOCIATED OUTPUTS

ACTIVATED.

C. TROUBLE OPERATION: UPON ACTIVATION OF A TROUBLE CONDITION OR SIGNAL FROM ANY DEVICE ON THE SYSTEM, THEFOLLOWING FUNCTIONS SHALL AUTOMATICALLY OCCUR:

1. THE INTERNAL AUDIBLE DEVICE SHALL SOUND AT THE CONTROL PANEL AND REMOTE ANNUNCIATOR.2. THE LCD DISPLAY SHALL INDICATE ALL APPLICABLE INFORMATION ASSOCIATED WITH THE TROUBLE CONDITION

INCLUDING; DEVICE TYPE, DEVICE LOCATION AND TIME/DATE.3. ALL SYSTEM ACTIVITY/EVENTS SHALL BE DOCUMENTED IN SYSTEM HISTORY.4. ANY REMOTE OR LOCAL ANNUNCIATOR LCD/LED'S ASSOCIATED WITH THE TROUBLE ZONE SHALL BE ILLUMINATED.5. TRANSMIT A TROUBLE SIGNAL TO THE CENTRAL STATION.

CONNECT TO 120V FIRE ALARMCIRCUIT C-24

F S

ROOF

P

DEMOLITION NOTES:

1. FIRE ALARM DEVICES SHOWN AS DASHED SHALL BE REMOVED. EXISTING WIRING, RACEWAYS, AND SUPPORT

APPARATUS TO BE REMOVED BACK TO ITS SOURCE PANEL AND SEAL OPENINGS.

2. DEVICES SHOWN LIGHT IN COLOR ARE EXISTING TO REMAIN. MAINTAIN CONTINUITY OF EXISTING CIRCUITS OF WIRING

DEVICES AND EQUIPMENT TO REMAIN. EXISTING CIRCUITS OF EQUIPMENT SHALL REMAIN ENERGIZED. CIRCUITS WHICH

ARE TO REMAIN BUT WERE DISTURBED DURING DEMOLITION SHALL HAVE WIRING AND POWER RESTORED BACK TO

ORIGINAL CONDITION.

3. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REMOVE AND LEGALLY DISPOSE OF DEMOLISHED

MATERIALS.

4. THE OWNER RESERVES THE RIGHT TO INSPECT THE MATERIAL SCHEDULED FOR REMOVAL AND SALVAGE ANY ITEMS

DEEMED USEABLE AS SPARE PARTS.

5. EXISTING CONDITIONS INDICATED ON THIS DRAWING ARE TAKEN FROM EXISTING DOCUMENTS AND FIELD

INVESTIGATION. IT IS RECOMMENDED FOR CONTRACTOR TO VISIT SITE AND VERIFY EXISTING CONDITIONS PRIOR TO

BID.

6. THE DEMOLITION PLAN IS NOT INCLUSIVE OF ALL ELECTRICAL DEVICES, FITTINGS, CONDUITS, ETC. IT IS INTENDED TO

PROVIDE THE CONTRACTOR WITH A GENERAL KNOWLEDGE OF EXISTING CONDITIONS WITHIN THE PROJECT AREA.

7. THE CONTRACTOR SHALL INSURE THAT CONDUITS REMAINING WITHIN THE PROJECT AREA ARE SUPPORTED IN

ACCORDANCE WITH THE SPECIFICATIONS. CONDUITS THAT ARE ATTACHED TO ITEMS BEING REMOVED DURING

DEMOLITION SHALL BE SUPPORTED FROM THE STRUCTURE PRIOR TO REMOVING ITEM.

8. EXISTING PANEL DIRECTORIES SHALL BE UPDATED TO REFLECT CURRENT CONDITIONS.

9. CONTRACTOR SHALL PATCH, PAINT, AND MATCH FINISH WITH EXISTING SURFACES TO REMAIN WHERE ELECTRICAL

DEVICES ARE BEING REMOVED.

10. CONTRACTOR SHALL REVIEW NEW FLOOR PLANS FOR DEVICES TO REMAIN PRIOR TO DEMOLITION. EXISTING DEVICES

TO REMAIN ARE SHOWN LIGHT IN COLOR.

11. THE BUILDING WILL BE IN OPERATION DURING DEMOLITION AND CONSTRUCTION. CONTRACTOR SHALL REFER TO

DRAWINGS ON PHASING INSTRUCTIONS. CONTRACTOR SHALL COORDINATE WITH OWNER ON DEMOLITION AND

CONSTRUCTION SCHEDULE AND NOTIFY OWNER A MINIMUM OF 72 HOURS PRIOR TO POWER SHUTDOWN OR

COMMENCING WORK IN EACH AREA.

12. REFER TO DEMOLITION DRAWINGS FOR FURTHER DEMOLITION INFORMATION. CONTRACTOR SHALL REMOVE

ASSOCIATED ELECTRICAL DEVICES, EQUIPMENT AND OTHER EXISTING SYSTEMS SERVING ITEMS BEING REMOVED.

13. BEFORE DEMOLITION OF ANY CONDUIT OR WIRING VERIFY ALL CIRCUITS BEING SERVED OUTSIDE CONSTRUCTION

AREA. VERIFY WITH OWNER OR DEPARTMENT SUPERVISOR BEFORE DISRUPTING ANY SERVICES AFFECTED OUTSIDE

THE CONSTRUCTION AREA. ANY EXISTING DEVICES AND NORMAL, OR LIFE SAFETY SYSTEMS DISRUPTED BY

DEMOLITION ARE TO BE RESTORED TO OPERATION IMMEDIATELY OR WITHIN TIME AGREED UPON WITH OWNER.

M TS FS

FF

HD F

SD SD

F SP

M TS FS

FF

HD F

SD SD

F SP

M TS FS

FF

HD F

TSE

F

E

D

C

B

A

HB

E

E

DE

F

DE

F

H

A

E

TS

F

B

H

GENERAL NOTES:

1. REFER TO USF DESIGN AND CONSTRUCTION GUIDELINES, DIVISION 16720 FIRE ALARM AND SMOKE DETECTION

SYSTEMS, FOR ALL USF FIRE ALARM STANDARDS.

1. PROVIDE NEW ADDRESSABLE VOICE EVACUATION FIRE ALARM CONTROL PANEL AND NEW FIRE ALARM CIRCUITS ANDZONES AS REQUIRED.

2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THE ENTIRE FACILITY IS COMPLETELY PROTECTED BY THEFIRE ALARM SYSTEM AND ALL REQUIRED TESTING.

3. EVERY TIME THE THE CONSTRUCTION PERSONNEL LEAVES FOR THE DAY, BOTH FIRE ALARM PANELS SHALL PROVIDECONTINUOUS PROTECTION TO THE FACILITY. THE PANELS SHALL BE FREE OF ANY TROUBLE AND ALARM CONDITIONSAND ALSO REPORT TO THE MONITORING STATION. A FIRE WATCH SHALL THEN BE IMPLEMENTED BEFORE ANYPERSONNEL LEAVES THE SITE.

4. COORDINATE ALL REQUIRED WORKING HOURS WITH OWNER AND THE PHASING PLAN TO ENSURE NO PART OF THEFIRE ALARM SYSTEM IS OUT OF SERVICE FOR MORE THAN FOUR (4) HOURS.

5. IF THE FIRE ALARM SYSTEM COVERAGE IS EXPECTED TO EXCEED A PERIOD FOUR (4) HOURS, A FIRE WATCH WILL BEREQUIRED TO BE PROVIDED AT CONTRACTORS EXPENSE.

6. ANY PERSON OR FIRM CONTRACTED TO PERFORM THE FIRE WATCH SHALL NOT BE ENGAGED IN OTHERCONSTRUCTION DUTIES OR FUNCTIONS THAT MAY INTERFERE WITH THE FIRE WATCH FUNCTION.

7. CONTRACTOR SHALL FIRE SEAL AND ENSURE ALL FIRE RATED WALLS CONTINUE TO MAINTAIN THE EXISTING WALLRATINGS.

8. THE ENTIRE FIRE ALARM SYSTEM CABLING SHALL BE INSTALLED IN RIGID METAL CONDUIT MIN 3/4"

FIRE ALARM SCOPE OF WORK

ELECTRICAL SYMBOLS LEGEND

ALL SYMBOLS SHOWN MAY NOT BE USED.

UNLESS OTHERWISE NOTED(UON)

2P/60AF:50A

DUPLEX RECEPTACLE

TELECOMMUNICATIONS OUTLET (RACEWAY ONLY)

WIRE IN CONDUIT CONCEALED BELOW SLAB

WIRE IN CONDUIT CONCEALED, #12AWG SIZE

HOMERUN TO PANEL, NUMBER OF ARROWS

PANEL BOARD - SURFACE MOUNT, 240V AC

60 AMP, FUSED AT 50 AMP. NF = NON-FUSEDDISCONNECT SWITCH, SHOWN SIZE - 2-POLE,

INDICATE NUMBER CIRCUITS IN CONDUIT

WIRE IN i" CONDUIT MINIMUM, UNLESSNOTED OTHERWISE

OR GRADE

CONDUIT EXPOSED

FLEXIBLE CONDUIT

3/4" PLYWOOD TELEPHONE BACKBOARD

JUNCTION BOX

JUNCTION BOX- WALL MOUNTED

MOTOR CONNECTION. HP DENOTES HORSEPOWER RATING

CONDUIT TURNING UP

CONDUIT TURNING DOWN

3R

3R = NEMA 3R ENCLOSURE

EMPTY CONDUIT

CONDUIT STUB

PANEL BOARD - SURFACE MOUNT, ABOVE 240V AC

F MANUAL PULL STATION DEVICE

SMOKE DETECTOR - CEILING MOUNTEDSD

HEAT DETECTOR - CEILING MOUNTED

FACP DENOTES FIRE ALARM CONTROL PANELFACPFATC DENOTES FIRE ALARM TERMINAL CABINET

HD

FAAP DENOTES FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM DUCT SMOKE DETECTORSDS = SUPPLY, R = RETURN

FIRE ALARM CONNECTION TO TAMPER SWITCH

FIRE ALARM CONNECTION TO FLOW SWITCH

FIRE ALARM RELAY

3P/60ANEMA 0 SHOWN SIZE 3-POLE, 60 AMP, NEMA 0 RATED

COMBINATION STARTER/DISCONNECT SWITCH,3R

3R = NEMA 3R ENCLOSURE

SURGE PROTECTION DEVICESPD

ELECTRIC METER

TRANSFORMERT

UNDERGROUND COMMUNICATIONS CONDUIT

UNDERGROUND ELECTRICAL CONDUIT

UGC

UGE

FIRE ALARM DOOR HOLD OPEN DEVICE

F

FIRE ALARM CEILING MOUNTED COMBINATIONSPEAKER/STROBE DEVICE

FIRE ALARM CEILING MOUNTED STROBE DEVICE

P

FIRE ALARM CEILING MOUNTED SPEAKER DEVICES

FIRE ALARM COMBINATION SPEAKER/STROBE DEVICE

FIRE ALARM STROBE ONLY DEVICE

HP

S

F

F

M

R

FS

TS

J

J

FIRE ALARM REMOTE TEST SWITCH

FIRE ALARMTERMINAL CABINET(FATC)

FIRE ALARM DIALER PANELSILENT KNIGHT 5104

E0.1

FAC

ILIT

IES

PLA

NN

ING

AN

D C

ON

STR

UC

TIO

N

US

F TA

T B

UIL

DIN

G F

IRE

ALA

RM

UP

GR

AD

ES

Tam

pa, F

lorid

a

Page 3: E3.3 TAT SPECIFICATIONS - University of South Floridausfweb2.usf.edu/BIDS 2014-15/15-002-ppb-tat-fire-alarm/15-002-ppb-upgrades.pdfe3.1 tat specifications e3.1 tat specifications e3.1

E1.1

FAC

ILIT

IES

PLA

NN

ING

AN

D C

ON

STR

UC

TIO

N

US

F TA

T B

UIL

DIN

G F

IRE

ALA

RM

UP

GR

AD

ES

Tam

pa, F

lorid

a

Page 4: E3.3 TAT SPECIFICATIONS - University of South Floridausfweb2.usf.edu/BIDS 2014-15/15-002-ppb-tat-fire-alarm/15-002-ppb-upgrades.pdfe3.1 tat specifications e3.1 tat specifications e3.1

DIALERPANEL

LOCATED IN FLY LOFT (VERIFY LOCATION)

EXISTING FIRE CURTAINCONTROLS TO REMAIN

VERIFY LOCATION OF A/C #3ON UPPER LEVEL

EXISTING FIRE ALARM CONTROL PANELAND DIALER TO REMAIN ACTIVE DURINGCONSTRUCTION AND BE REMOVEDAFTER ALL NEW CIRCUITS ARE ACTIVE INNEW PANELS.

FACP

HEAT DETECTORS MOUNTED ABOVE CEILINGIN CATWALK AREA (TYPICAL OF 4)

E1.2

FAC

ILIT

IES

PLA

NN

ING

AN

D C

ON

STR

UC

TIO

N

US

F TA

T B

UIL

DIN

G F

IRE

ALA

RM

UP

GR

AD

ES

Tam

pa, F

lorid

a

Page 5: E3.3 TAT SPECIFICATIONS - University of South Floridausfweb2.usf.edu/BIDS 2014-15/15-002-ppb-tat-fire-alarm/15-002-ppb-upgrades.pdfe3.1 tat specifications e3.1 tat specifications e3.1

E1.3

FAC

ILIT

IES

PLA

NN

ING

AN

D C

ON

STR

UC

TIO

N

US

F TA

T B

UIL

DIN

G F

IRE

ALA

RM

UP

GR

AD

ES

Tam

pa, F

lorid

a

Page 6: E3.3 TAT SPECIFICATIONS - University of South Floridausfweb2.usf.edu/BIDS 2014-15/15-002-ppb-tat-fire-alarm/15-002-ppb-upgrades.pdfe3.1 tat specifications e3.1 tat specifications e3.1

E2.1

TAT

BA

SE

ME

NT

FLO

OR

PLA

N -

FIR

E A

LAR

M

FAC

ILIT

IES

PLA

NN

ING

AN

D C

ON

STR

UC

TIO

N

US

F TA

T B

UIL

DIN

G F

IRE

ALA

RM

UP

GR

AD

ES

Tam

pa, F

lorid

a

Page 7: E3.3 TAT SPECIFICATIONS - University of South Floridausfweb2.usf.edu/BIDS 2014-15/15-002-ppb-tat-fire-alarm/15-002-ppb-upgrades.pdfe3.1 tat specifications e3.1 tat specifications e3.1

DIALERPANEL

LOCATED IN FLY LOFT (VERIFY LOCATION)

EXISTING FIRE CURTAINCONTROLS TO REMAIN -RECONNECT TO NEW FIREALARM SYSTEM

VERIFY LOCATION OF A/C #3ON UPPER LEVEL

FAAP

CONTRACTOR TO PROVIDE MODULE TO SHUNT THEBUILDING'S INTERNAL AUDIO SPEAKER SYSTEM CIRCUITINGDURING GENERAL ALARM SO VOICE EVACUATION MESSAGETAKES PRECEDENCE. COORDINATE EXACT LOCATION WITHOWNER/BUILDING OPERATOR.

FACP

HEAT DETECTORS MOUNTED ABOVE CEILINGIN CATWALK AREA (TYPICAL OF 4)

E2.2

TAT

FIR

ST

FLO

OR

PLA

N -

FIR

E A

LAR

M

FAC

ILIT

IES

PLA

NN

ING

AN

D C

ON

STR

UC

TIO

N

US

F TA

T B

UIL

DIN

G F

IRE

ALA

RM

UP

GR

AD

ES

Tam

pa, F

lorid

a

Page 8: E3.3 TAT SPECIFICATIONS - University of South Floridausfweb2.usf.edu/BIDS 2014-15/15-002-ppb-tat-fire-alarm/15-002-ppb-upgrades.pdfe3.1 tat specifications e3.1 tat specifications e3.1

E2.3

TAT

SE

CO

ND

FLO

OR

PLA

N -

FIR

E A

LAR

M

FAC

ILIT

IES

PLA

NN

ING

AN

D C

ON

STR

UC

TIO

N

US

F TA

T B

UIL

DIN

G F

IRE

ALA

RM

UP

GR

AD

ES

Tam

pa, F

lorid

a

Page 9: E3.3 TAT SPECIFICATIONS - University of South Floridausfweb2.usf.edu/BIDS 2014-15/15-002-ppb-tat-fire-alarm/15-002-ppb-upgrades.pdfe3.1 tat specifications e3.1 tat specifications e3.1

ELECTRICAL SPECIFICATIONS

H. SAFETY SWITCHES:

GENERAL: ALL DISCONNECT SWITCHES SHALL BE HEAVY-DUTY TYPE, UNLESS SPECIFICALLY NOTEDOTHERWISE. SWITCHES SHALL BE FUSIBLE OR NON-FUSIBLE AND SIZED AS NOTED ON THE DRAWINGS.SWITCHES SHALL BE 240 VOLT RATED ON SYSTEMS UP TO AND INCLUDING 120/240V. ALL SWITCHESSERVING MOTOR LOADS SHALL BE HORSEPOWER RATED.

PROVIDE SWITCHES WITH AN EXTERNALLY OPERATED HANDLE; QUICK MAKE QUICK BREAK MECHANISM;THE HANDLE SHALL BE INTERLOCKED WITH THE SWITCH COVER BY MEANS OF A DEFEATABLEINTERLOCK DEVICE. THE SWITCH SHALL BE LOCKABLE IN THE "OFF" POSITION WITH A PADLOCK.

I. LIGHTING FIXTURES:

LIGHTING FIXTURES SHALL BE FURNISHED AS SHOWN IN FIXTURE SCHEDULE. IT SHALLSPECIFICALLY BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY EXACT TYPE OF CEILINGAND RECESSING DEPTH OF ALL RECESSED FIXTURES AND TO FURNISH THE MOUNTING TRIMS ANDACCESSORIES OF THE SPECIFIED AND/OR APPROVED FIXTURES FOR THE CEILING TO BE INSTALLED.FIXTURES SHALL BE SUPPORTED INDEPENDENTLY OF CEILING SYSTEMS.

FLUORESCENT LAMPS SHALL BE T8, 28W, 3500 DEGREES K, 85 CRI MINIMUM.FOR THE COLLEGE OF MEDICINE CLINICAL BUILDINGS (MDA, MDC, MDH, MDL, MDN, AND MDT)FLUORESCENT LAMPS SHALL BE T8, 28W, 4100 DEGREES K, 85 CRI MINIMUM.

LAMP DESIGN SELECTION: OSRAM-SYLVANIA, GE, OR PHILLIPS.

I. SCOPE OF WORK

A. ALL WORK SHALL BE IN COMPLIANCE WITH THE LATEST APPLICABLE CODES, LAWS AND ORDINANCES,AND THE NATIONAL ELECTRICAL CODE. PROVIDE AND FURNISH ALL LABOR, MATERIALS, PERMITS, ANDINCIDENTALS REQUIRED TO COMPLETE ALL WORK AS SHOWN ON CONTRACT DOCUMENTS.

B. CONTRACTOR SHALL INSPECT ALL NEW MATERIAL AND EQUIPMENT PRIOR TO INSTALLATIONS FORDAMAGES, AND SHALL VERIFY EQUIPMENT OPERATES SATISFACTORILY.

C. CONTRACTOR SHALL WARRANT ALL MATERIAL AND EQUIPMENT FURNISHED TO COMPLETE ALL WORKFOR ONE YEAR AFTER FINAL ACCEPTANCE OF COMPLETION. MATERIALS AND EQUIPMENT DEFECTS OFFAILURES DUE TO ABUSE, OR WORKMANSHIP NEGLECT SHALL BE MADE GOOD BY THE CONTRACTORWITHOUT COST TO THE OWNER.

D. PROVIDE ONLY NEW, STANDARD UNDERWRITER'S LABORATORY INC. LISTED FIRST-GRADE MATERIALSTHROUGHOUT, AND SHALL BE MARKED WITH UNDERWRITER'S LABORATORY INC. LISTED AND WITHMANUFACTURER'S BRAND OR TRADEMARK. ALL MATERIALS SHALL BE OF ONE MANUFACTURER.

E. CONTRACTOR SHALL BE EXPERIENCED IN THEIR TRADE. CONTRACTOR'S WORK SHALL PRESENT A NEATAPPEARANCE UPON COMPLETION. MATERIALS AND EQUIPMENT INSTALLED SHALL BE PLUMB, STRAIGHT,AND LEVEL.

F. CONTRACTOR SHALL COORDINATE WITH THE ARCHITECT AND OWNER ON EXACT LOCATION OF WIRINGDEVICES AND RACEWAY FOR OWNER-FURNISHED EQUIPMENT PRIOR TO ROUGH-IN.

G. UPON COMPLETION OF WORK, THE CONTRACTOR SHALL TEST ALL WIRING AND EQUIPMENTINSTALLATION, AND SHALL BE IN PERFECT WORKING CONDITION IN ACCORDANCE WITH THE INTENT OFTHE CONTRACT DOCUMENTS.

II. ELECTRICAL IDENTIFICATION

A. NAMEPLATES:

ENGRAVED PLASTIC LAMINATE NAMEPLATES: PROVIDE ENGRAVING PHENOLIC PLASTIC LAMINATE, INSIZES AND THICKNESS INDICATED, ENGRAVED WITH 1/16 INCH THICK LINES WITH SQUARE STANDARD PICALETTERING AND WORDING AS SPECIFIED HEREIN, BLACK FACE AND WHITE LETTER FOR NORMALSYSTEMS AND RED AND WHITE FOR FIRE ALARM AND WHERE NOTED IN THE SPECIFICATIONS. PUNCH FORMECHANICAL FASTENING, EXCEPT WHERE ADHESIVE MOUNTING IS NECESSARY BECAUSE OF SUBSTRATE.MATERIAL THICKNESS SHALL BE 1/16 INCH. PROVIDE BEVELED EDGE IN ORDER TO ELIMINATE SHARPCORNERS. PROVIDE SELF-TAPPING STAINLESS STAINLESS STEEL ROUND HEAD SCREWS. PROVIDECONTACT TYPE PERMANENT ADHESIVE WHERE SCREWS CANNOT OR SHALL NOT PENETRATE THESUBSTRATE. ADHESIVE NAMEPLATE SHALL BE PERMANENTLY INSTALLED. TITLES SHALL BE 1/2 INCH HIGHAND ALL OTHER LETTERING SHALL BE 1/4 INCH HIGH.

B. JUNCTION BOXES:

JUNCTION BOX IDENTIFICATION: PROVIDE NEAT INDELIBLE FELT TIP, STENCILED MARKING ON JUNCTIONBOXES AND PULL BOX COVERS. LETTER SIZES SHALL BE 1 INCH HIGH MINIMUM. PROVIDENON-STENCILED MARKINGS INSIDE THE JUNCTION BOX AND ON THE EXTERIOR EDGE TO MATCH THECOVER MARKINGS.

III. BASIC MATERIALS AND METHODS

A. PANEL BOARDS:

PROVIDE PANEL BOARDS WITH MAIN BREAKER OR MAIN LUGS WHERE SHOWN ON THE DRAWINGS, OF ADEAD FRONT, DISTRIBUTED PHASE SEQUENCE DESIGN. PANEL BOARDS SHALL BE EQUIPPED WITHTHERMAL-MAGNETIC MOLDED CASE CIRCUIT BREAKERS WITH FRAME AND TRIP RATINGS AS INDICATED INTHE SCHEDULES.

DIRECTORIES: A TYPED PANEL BOARD DIRECTORY SHALL BE PROVIDED FOR EACH PANEL BOARD ANDSHALL INDICATE THE ACTUAL CIRCUIT NUMBER USED, ROOM NAME AND TYPE OF LOAD. ROOM NAMESSHALL BE THE ACTUAL NAME OR ROOM NUMBER USED NOT NECESSARILY AS SHOWN ON THE DRAWING.PANEL DIRECTORIES SHALL INCLUDE ALL ROOM NUMBERS AND NAMES. WHERE PANEL SCHEDULES AREINDICATED ON THE DRAWINGS AS "RECEPTACLES OR "LIGHTING", ETC, IT SHALL BE THE RESPONSIBILITY OFTHE CONTRACTOR TO INCLUDE THE SPECIFIC AREA SERVED.

B. CIRCUIT BREAKERS:

CIRCUIT BREAKERS SHALL BE BOLT-ON QUICK-MAKE, QUICK-BREAK THERMAL-MAGNETIC TYPE, FORALTERNATING CURRENT. BREAKERS SHALL TRIP FREE OF THE HANDLE AND TRIPPING SHALL BE INDICATEDBY THE HANDLE ASSUMING A POSITION BETWEEN OFF AND ON. MULTI- POLE BREAKERS SHALL BEINTERNAL, COMMON TRIP WITH SINGLE OPERATING HANDLE; EXTERNAL HANDLE TIES ARE NOTACCEPTABLE.

G. BASIC DEVICES:

PROVIDE IVORY COLORED DEVICES WHERE AVAILABLE, UNLESS OTHERWISE NOTED.

20-AMP, 120/277 VAC, HEAVY DUTY, QUIET TYPE, SPECIFICATION GRADE:

1. SINGLE POLE TOGGLE: PASS AND SEYMOUR NO. CS20AC1W.2. THREE-WAY TOGGLE: PASS AND SEYMOUR NO. CS20AC3W.

FLUORESCENT DIMMERS:1. PRESET SLIDE CONTROL: LUTRON "DIVA" SERIES DVF-103P-277, 277-VOLT.

OCCUPANCY SENSOR SWITCHES, 120/277 VAC:1. WALL MOUNTED SINGLE POLE- LEVITON NO. OSSMT-GDI.

RECEPTACLES:

SPECIFICATION GRADE 20A, 125V, 2P, 3W GROUNDED, MOUNTED 18"AFF TO THE CENTERLINEUNLESS NOTED OTHERWISE. COLOR SHALL MATCH TOGGLE SWITCHES.

1. 20A DUPLX, 3W, 125V, NEMA 5-20R LEVITON #5362

PROVIDE CAST ALLOY OR STAMPED METAL PLATES ON EXPOSED SWITCHES AND RECEPTACLES.

INSTALL DEVICE PLATES IN FULL CONTACT WITH WALL SURFACE. PLATES SHALL NOT PROJECT OUTFROM THE WALL.

INSTALL DEVICE PLATES IN FULL CONTACT WITH SURFACE MOUNTED BOX. PLATES SHALL NOTPROJECT OUT FROM THE EDGE OF THE BOX.

ALL DEVICE PLATES FOR RECEPTACLES AND SWITCHES SHALL BE LABELED. SHOW PANELDESIGNATION AND BRANCH CIRCUIT SERVING EACH RECEPTACLE. USE ENGRAVED PLATES UNLESSOTHERWISE NOTED.

ACCEPTABLE MANUFACTURERS: PASS & SEYMOUR, G.E., LEVITON

J. GROUNDING:

GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ANDLOCAL CODES AND REQUIREMENTS.

FEEDERS AND BRANCH CIRCUITS SHALL HAVE INSTALLED IN THE SAME RACEWAY AS THE CIRCUITCONDUCTORS, AN INSULATED COPPER GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITHNEC.

DESCRIPTION OF SYSTEM: IN GENERAL, ALL ELECTRICAL EQUIPMENT (METALLIC CONDUIT, MOTORFRAMES, PANEL BOARDS, ETC.) SHALL BE BONDED TOGETHER WITH A GREEN INSULATED OR BARECOPPER SYSTEM GROUNDING CONDUCTOR IN ACCORDANCE WITH SPECIFIC RULES OF ARTICLE 250OF THE N.E.C. EQUIPMENT GROUNDING CONDUCTORS THROUGH THE RACEWAY SYSTEM SHALL BECONTINUOUS FROM MAIN SWITCH GROUND BUS TO PANEL GROUND BAR OF EACH PANEL BOARD,AND FROM PANEL GROUNDING BAR OF EACH PANEL BOARD TO BRANCH CIRCUIT EQUIPMENT ANDDEVICES.

C. CONDUIT:

RIGID SHALL BE MINIMUM 1", GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING, E.M.T. SHALL BEMINIMUM 1/2" AND SHALL BE ELECTRO-GALVANIZED. CONDUITS SHALL BE AS MANUFACTURED BYREPUBLIC, PITTSBURGH STANDARD, WHEATLAND, TRIANGLE, ALLIED, OR YOUNGSTOWN.

TYPE "MC" CABLE IS NOT ACCEPTABLE FOR BRANCH CIRCUIT WIRING. TYPE "MC" CABLE IS ONLYACCEPTABLE TO MAKE FINAL CONNECTIONS FROM SOURCE JUNCTION BOXES TO LIGHT FIXTURES,MAXIMUM LENGTH 6'-0" (DO NOT DAISY CHAIN).

PROVIDE END BUSHINGS ON ALL CONDUITS. PROVIDE PULL STRINGS IN ALL EMPTY RACEWAYS. PULLSTRINGS SHALL BE NYLON AND SHALL BE IMPERVIOUS TO MOISTURE. PULL STRINGS SHALL HAVE ATENSILE STRENGTH NOT LESS THAN 200 LBS.

CONDUIT ABOVE GRADE SHALL BE EMT (INTERIOR ONLY), IMC, OR GALVANIZED.

CONDUIT BELOW GRADE SHALL BE RIGID GALVANIZED (HEAVY WALL), IMC, OR PVC (SCHEDULE 40).

SEALANT: PROVIDE A CLOSED CELL SILICONE FOAM SEALANT RATED TO PROVIDE A RATING EQUALTO THE WALL, CEILING, OR FLOOR ASSEMBLY RATING. PROVIDE SEALS FOR THE EXTERIOR OFCONDUIT PENETRATIONS CONSISTING OF A CAST-IN-PLACE SLEEVE WITH A COMPRESSIBLE RUBBERGASKET BETWEEN THE CONDUIT AND THE SLEEVE. PROVIDE SEALS FOR THE INTERIOR OF THECONDUIT PENETRATIONS CONSISTING OF GLAND TYPE SEALING BUSHING OR CLOSED CELL SILICONEFOAM. PROVIDE DUCT SEAL INSIDE AN APPROPRIATE SEAL-OFF FITTING TO SEAL THE INTERIOR OFTHE CONDUIT SYSTEM FROM WATER SEEPAGE OR HAZARDOUS GASES.

D. ALL COUPLINGS AND CONNECTORS FOR EMT SHALL BE OF COMPRESSION TYPE.

E. OUTLET BOXES:

SHALL BE STANDARD TYPE, WITH KNOCKOUTS, MADE OF HOT DIPPED GALVANIZED STEEL ASMANUFACTURED BY STEEL CITY, RACO OR APPLETON.

CEILING OUTLET BOXES SHALL BE 4-INCH OCTAGON 1-1/2 INCH DEEP OR LARGER WHEN REQUIREDDUE FOR NUMBER OF CONDUCTORS OR CONDUIT ENTRY.

BOXES SHALL BE PROVIDED WITH APPROVED 3/8 INCH FIXTURE STUDS WHERE REQUIRED. PROVIDEJUNCTION OR PULL BOXES WHERE SHOWN ON THE DRAWINGS AS REQUIRED TO FACILITATEINSTALLING CONDUCTORS. SUCH BOXES SHALL BE "CODE" SIZED. ALL JUNCTION BOXES SHALL BEACCESSIBLE.

F. WIRE AND CABLE 600 VOLT:

GENERAL: CONDUCTORS SHALL HAVE CURRENT CARRYING CAPACITIES AS PER N.E.C. AND WITH600 VOLT INSULATION, #12 MINIMUM EXCEPT FOR CONTROLS, AND FIXTURE WIRE. CONDUCTORSSHALL BE COPPER.

GENERAL USE: #12 AND #10 SHALL BE SOLID, INSULATION TYPE THHN OR THWN.

FEEDERS AND GENERAL USE: #8 AND LARGER AND ALL MOTORS CONDUCTORS SHALL BESTRANDED TYPE XHHW OR THWN.

COLOR-CODING FOR CONDUCTORS SHALL BE CONSISTENT THROUGHOUT ENTIRE LENGTH. PHASETAPE COLOR CODING IS NOT ACCEPTABLE. APPLIES TO FEEDERS AND BRANCH CIRCUITCONDUCTORS OF ALL SIZES. COLOR CODING SHALL BE BLACK, RED, AND BLUE (WHITE NEUTRAL)FOR 120/208 VOLT 3-PHASE WIRING, AND BROWN, ORANGE, AND YELLOW (GREY NEUTRAL) FOR277/480 VOLT 3-PHASE WIRING. GROUND CONDUCTORS SHALL BE GREEN.

E3.1

TAT

SP

EC

IFIC

ATI

ON

S

FAC

ILIT

IES

PLA

NN

ING

AN

D C

ON

STR

UC

TIO

N

US

F TA

T B

UIL

DIN

G F

IRE

ALA

RM

UP

GR

AD

ES

Tam

pa, F

lorid

a

Page 10: E3.3 TAT SPECIFICATIONS - University of South Floridausfweb2.usf.edu/BIDS 2014-15/15-002-ppb-tat-fire-alarm/15-002-ppb-upgrades.pdfe3.1 tat specifications e3.1 tat specifications e3.1

SECTION 28 31 00 FIRE DETECTION AND ALARM

PART 1 – GENERAL

1.1. SUMMARY NETWORK FIRE ALARM CONTROL PANEL (NODE)

A. Network fire alarm control panels shall include all features as described in this specification for stand-alone FACPs and shall havenetwork communication capabilities as described herein.

1. All points monitored and controlled by a single node shall be capable of being programmed as "Public". Each point made public tothe network may be programmed to be operated by any other node connected to the network.

2. Network communications shall be capable of supporting "point lists" that can be handled as though they were a single point.

B. The network shall provide a means to log into any node on the system via a laptop computer or CRT/Keyboard and have completenetwork access (Set Host) for diagnostics, maintenance reporting, and information gathering of all nodes in the system. [The meansshall include the capability to log into any node on the system via TCP/IP Ethernet network communications protocol compatible withIEEE Standard 802.3. Ethernet access to any fire alarm panel shall be capable of providing access only to authenticated users througha cryptographically authenticated and secure SLL tunnel. Provisions for a standard RJ-45 Ethernet connection to the owner's Ethernetnetwork must be provided at each node as part of the contract.] Systems not meeting this requirement must provide all diagnostic toolsrequired to support this function from selected points on the network. This Section covers fire alarm systems, including initiatingdevices, notification appliances, controls, and supervisory devices.

C. Work covered by this section includes the furnishing of labor, equipment, and materials for installation of the fire alarm system asindicated on the drawings and specifications.

D. The Fire Alarm System shall consist of all necessary hardware equipment and software programming to perform the followingfunctions:

1. Fire alarm system detection and notification operations.

2. Control and monitoring of elevators, smoke control equipment, door hold-open devices, fire suppression systems, emergency powersystems and other equipment as indicated in the drawings and specifications.

3. One-way supervised automatic voice alarm operations.

1.2. SCOPE OF WORK

A. Provide a new Voice Fire Alarm Control Panel and associated peripheral devices as indicated on the drawings.

1.3. ACCEPTABLE EQUIPMENT AND SERVICE PROVIDERS

A. Manufacturers: The equipment and service described in this specification are those supplied and supported by SimplexGrinnell andrepresent the base bid for the equipment.

1. Subject to compliance with the requirements of this specification, provide alternate products by one of the following:

a) SimplexGrinnell

b) Notifier

B. Being listed as an acceptable Manufacturer in no way relieves obligation to provide all equipment and features in accordance withthese specifications.

C. Alternate products must be submitted to the Engineer two weeks prior to bid for approval. Alternate or as-equal products submittedunder this contract must provide a detailed line-by-line comparison of how the submitted product meets, exceeds, or does not complywith this specification.

D. The equipment and service provider shall be a nationally recognized company specializing in fire alarm and detection systems. Thisprovider shall employ factory trained and NICET Level III certified technicians, and shall maintain a service organization within 50 milesof this project location. The equipment and service provider shall have a minimum of 10 years experience in the fire protective signalingsystems industry.

1.4. RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 SpecificationSections, apply to this section.

B. The work covered by this section is to be coordinated with related work as specified elsewhere in the specifications.

C. The system and all associated operations shall be in accordance with the following:

1. NFPA 72, National Fire Alarm Code, 2007Edition

2. NFPA 70, National Electrical Code, 2008 Edition

3. NFPA 101, Life Safety Code, 2009 Edition

4. NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, 2009 Edition

5. Local Jurisdictional Adopted Codes and Standards

6. ADA Accessibility Guidelines

1.5. SYSTEM DESCRIPTION

A. General: Provide a complete, non-coded addressable microprocessor-based fire alarm system with initiating devices, notificationappliances, and monitoring and control devices as indicated on the drawings and as specified herein.

B. Software: The fire alarm system shall allow for loading and editing instructions and operating sequences as necessary.

1. The system shall be capable of on-site programming to accommodate system expansion and facilitate changes in operation.

2. All software operations shall be stored in a non-volatile programmable memory within the fire alarm control unit. Loss of primary andsecondary power shall not erase the instructions stored in memory.

3. Panels shall be capable of full system operation during new site specific configuration download, master exec downloads, and slaveexec downloads.

4. Remote panel site-specific software and executive firmware downloads shall be capable of being performed over proprietary firealarm network communications and via TCP/IP Ethernet network communications. Ethernet access to any fire alarm panel shall becapable of providing access only to authenticated users through a cryptographically authenticated and secure SSL tunnel.

5. Panels shall automatically store all program changes to the panel's non-volatile memory each time a new program is downloaded.Panels shall be capable of storing the active site-specific configuration program and no less than 9 previous revisions in reserve. Acompare utility program shall also be available to authorized users to compare any two of the saved programs. The compare utilityshall provide a deviation report highlighting the changes between the two compared programs.

6. Panels shall provide electronic file storage with a means to retrieve a record copy of the site-specific software and up to 9 previousrevisions. Sufficient file storage shall be provided for other related system documentation such as record drawings, record ofcompletion, owner's manuals, testing and maintenance records, etc.

7. The media used to store the record copy of site-specific software and other related system documentation shall be electricallysupervised. If the media is removed a trouble shall be reported on the fire alarm control panel.

C. History Logs: The system shall provide a means to recall alarms and trouble conditions in chronological order for the purpose ofrecreating an event history. A separate alarm and trouble log shall be provided.

D. Recording of Events: Provide the optional hardware and software capability to record all alarm, supervisory, and trouble events bymeans of system printer. The printout should include the type of signal (alarm, supervisory, or trouble) the device identification, dateand time of the occurrence. The printout differentiates alarm signals from all other printed indications.

E. Wiring/Signal Transmission:

1. Transmission shall be hard-wired using separate individual circuits for each zone of alarm operation, as required or addressablesignal transmission, dedicated to fire alarm service only.

2. System connections for initiating device circuits shall be Class B signaling line circuits shall be Class B, Style 6 and notificationappliance circuits shall be Class B.

3. Circuit Supervision: Circuit faults shall be indicated by a trouble signal at the FACP. Provide a distinctive indicating audible tone andalphanumeric annunciation.

4. Constant Supervision Audio: When provided, audio notification appliance circuits shall be supervised during standby by monitoringfor DC continuity to end-of-line resistors.

F. Supplemental Notification and Remote User Access (Fire Panel Internet Interface)

1. Fire Alarm Control Panel (FACP) shall provide the necessary hardware to provide supplemental notification and remote user accessto the FACP using Ethernet and TCP/IP communications protocol compatible with IEEE Standard 802.3.

2. A standard RJ-45 Ethernet connection shall connect to the owners Ethernet network. Provisions for that connection must beprovided at each fire alarm control panel by the owner as part of the contract.

3. The means of providing supplemental email and SMS text messaging notification shall be agency listed for specific interfaces andfor the purpose described in this section. The use of non-listed external third party products and interfaces is not acceptable.

4. The fire panel internet interface shall be capable of sending automated notification of discrete system events via email and SMS textmessaging to up to 50 individual user accounts and via email to up to 5 distribution list.

5. Each user account and distribution list shall be capable of being configurable for the specific type of events to be received. Eachaccount shall be configurable to receive notification upon any combination of the following types of events:

a) Fire Alarm,

b) Priority 2,

c) Supervisory,

d) Trouble,

e) Custom Action Messages,

f) Fire Panel Internet Interface Security Violations

6. Each user account and distribution list shall be capable of being configurable for the specific content to be received. Each accountshall be configurable to receive any combination of the following message content:

a) Summary,

b) Event Information,

c) Message,

d) Emergency Contacts,

e) Host Fire Alarm Control Panel Information

7. Each user account and distribution list shall be capable of being configurable for the type of Fire Alarm Control Panel Logs andReports to be received. Each account shall be configurable to receive any combination of the following Logs and Reports via email:

a) Alarm Log,

b) Trouble Log,

c) Analog Sensor Status Report,

d) Analog Sensor Service Report,

e) Almost Dirty, Dirty and Excessively Dirty Sensor Report,

f) CO Analog Sensor Service Report,

g) Addressable Appliance Candela Report,

h) Addressable Appliance Status Report

8. Each user account and distribution list shall be capable of receiving email distribution of Fire Alarm Control Panel Logs and ReportsOn-Demand or automatically on a Pre-Determined schedule. Receipt of Logs and Reports shall be capable of being scheduled asfollows:

a) Weekly, or

b) Bi-weekly, or

c) Monthly

9. The Fire Alarm Control Panel Logs and Reports shall be sent in CSV file format which can be imported into common databaseapplications for viewing, sorting, and customization.

a) Each user account shall be capable of being configured to receive system events via email and/or SMS text messaging.

b) Each distribution list shall be capable of supporting up to 20 email address recipients.

10.The means to provide email notification shall be compatible with SMTP mail servers, ISP email services, and Internet emailservices. Communication with the email server shall be verified at selectable intervals of 5 to 30 minutes.

11.Email operation shall be capable of being disabled for service by the system administrator.

12.An email log shall be accessible to authorized users. The email log shall display the 25 most recent email notifications sent.

13.The fire panel internet interface for supplemental notification and remote user access shall support:

a) Secure HTTPS/SSL encrypted connections,

b) Up to 50 individual password protected user accounts,

c) Dynamic and Static IP addressing,

d) IP Address Blocking,

e) Restricted number of log-in attempts before lock-out configurable from 1 to 20,

f) Lock-out duration after unsuccessful log-in attempts configurable from 0 to 24 hours,

g) Email notification to Administrators of unsuccessful log-in attempts,

h) Automatic lock-out reset upon a new event,

i) Automatic inactivity logout configurable from 10 minutes to 24 hours,

j) Firmware updates over ethernet,

k) Set-up and configuration via Local Service Port or via Remote Services over LAN/WAN connection

14.Authorized users shall be capable of accessing the fire alarm panel using a compatible web browser (Internet Explorer 6.0 or higher)and a secure HTTPS/SSL encrypted connection.

15.The fire panel internet interface shall support concurrent connections for up to 5 users plus 1 administrator.

16.Authorized users with remote access shall be capable of:

a) Viewing the fire panel internet interface web home page

(a) The fire panel internet interface home page shall display system status information and provide links to detailedstatus information and fire alarm panel reports and history logs

(b) The web browser on the user's computer shall automatically refresh system status information upon a new event

(i) Systems that require a manual refresh to acquire updated system status information shall not be acceptedb) Viewing the fire alarm panel detailed card status information

c) Viewing the fire alarm panel detailed point status information

d) Viewing the fire alarm panel reports and history logs

e) Viewing the fire panel internet interface email log

f) Viewing system summary information

g) Accessing Custom Hypertext Links

17.The fire panel internet interface home page shall support customization to display the following information:

a) Customer Name and Address,

b) Fire Panel Location or Building Name,

c) Up to 10 Custom Hypertext Links with Text Descriptions

G. Remote Services Access:

1. Fire Alarm Control Panel (FACP) shall have the capability to provide a remote service access feature using Ethernet and TCP/IPcommunications protocol compatible with IEEE Standard 802.3. The Remote Access feature shall provide automatic notification ofsystem faults and remote diagnostics of system status for responding technicians prior to arrival on site.

2. A standard RJ-45 Ethernet connection shall connect to the owners Ethernet network. Provisions for that connection must beprovided at each fire alarm control panel as part of the contract.

3. The Ethernet access feature shall be agency listed for specific interfaces and for the purpose described in this section. The use ofnon-listed external third party interfaces is not acceptable.

4. The internet remote access service function shall provide automated real time off-site reporting of discrete system events to aremote service support center with details of internal FACP fault conditions allowing a pre-site visit analysis of repair requirements.

5. Existing FACP controls shall be capable of retrofitting the Remote Service module as a plug-in upgrade feature.

6. The remote service network shall work on the customers Ethernet infrastructure and be Fire-Wall friendly for two-waycommunications for off-site reporting. The feature shall be compatible with existing proxy servers and firewalls shall not require anyspecial changes or modifications.

7. The remote service system shall be able to connect to the remote service center without the need for a VPN account or similartunnel.

8. The remote service system shall be a non Windows based application to protect against conventional virus attacks.

9. The remote service system shall support a secure connection with strong encryption, 128 bit or better, and an optional secondaryencryption method if required.

10.The remote service system shall be compatible with virtual LANS (VLAN).

11.The remote service system shall work on an outbound communication premise (panel calls home) in order to eliminate thepossibility of any inbound connection into the network (from trusted or non trusted sites).

12.The remote service system shall provide an audit trail of all events and service connections.

13.The Remote Service connection will provide access for panel software downloads and uploads for archiving job specific programsback at the enterprise server.

14.The supplier shall provide a service contract for the Remote Service program that provides the following requirements:

a) 24/7 recording of FACP service activity.

b) Off-site diagnostics by a technical specialist to provide repair and parts guidance to the service technician prior to a sitevisit.

H. Network communication:

1. Network node communication shall be through a token ring, hub, or star topology configuration, or combination thereof.

2. A single open, ground or short on the network communication loop shall not degrade network communications. Token shall bepassed in opposite direction to maintain communications throughout all network nodes. At the same time the status of thecommunication link shall be reported.

PART 2 – If a group of nodes becomes isolated from the rest of the network due to multiple fault conditions, that group shall automaticallyform a sub-network with all common interaction of monitoring and control remaining intact. The network shall be notified with the exact details ofthe lost communications.

1. Fiber optics communication shall be provided as an option via a fiber optics modem. Modem shall multiplex audio signals and digitalcommunication via full duplex transmission over a single fiber optic cable, either single mode or multi mode.

2. The communication method shall be NFPA 72 style 7.

B. Network Synchronization of Notification Appliances

1. The fire alarm and emergency communications network shall be capable of providing UL Listed synchronization across all thenotification appliance circuits for all panels on a network loop in accordance with the requirements of UL 1971.

2. Systems that require all notification appliances to be connected to a single panel for synchronization thus creating a potential singlepoint of failure shall not be acceptable.

3. Up to 99 panels on a network loop shall be capable of UL Listed synchronization of all notification appliance circuits across thenetwork loop in accordance with the requirements of UL 1971.

4. Should network communications be disrupted, re-synchronization shall occur across all nodes that continue to communicatetogether after network re-initialization is completed and restored to affected nodes.

5. Building Automation and Control Network (BACnet) Integration

a) The fire alarm control unit shall be capable of providing a one-way communications interface between the fire alarm controlunit and an industry-standard Building Automation and Control Network (BACnet) using ASHRAE® BACnet® IP (internetprotocol) compliant with ANSI/ASHRAE Standard 135.

b) The BACnet communications module shall be agency listed to UL Standard 864.

c) The fire alarm control unit shall be capable of communicating up to 1000 status changes to the building automation system.

d) MS/TP Master and MS/TP Slave data link layer options communicating at baud rates up to 76,800 bps shall be supported.

e) The interface shall be capable of supporting ANSI X3.4, ISO 10656 (ICS-4), ISO 10656 (UCS-2), ISO 8859-1, orIBM/Microsoft DBCS character sets.

f) A standard RJ-45 Ethernet connection to the Building Automation System Ethernet network shall be provided at the firealarm control unit as part of the contract.

g) Systems using relay interfaces shall not be accepted.

C. Required Functions: The following are required system functions and operating features:

1. Priority of Signals: Fire alarm events have highest priority. Subsequent alarm events are queued in the order received and do notaffect existing alarm conditions. Priority Two, Supervisory and Trouble events have second-, third-, and fourth-level priority,respectively. Signals of a higher-level priority take precedence over signals of lower priority even though the lower-priority conditionoccurred first. Annunciate all events regardless of priority or order received.

2. Non-interfering: An event on one zone does not prevent the receipt of signals from any other zone. All zones are manuallyresettable from the FACP after the initiating device or devices are restored to normal. The activation of an addressable device doesnot prevent the receipt of signals from subsequent addressable device activations.

3. Transmission to an approved Supervising Station: Automatically route alarm, supervisory, and trouble signals to an approvedsupervising station service provider, under another contract.

4. Annunciation: Operation of alarm and supervisory initiating devices shall be annunciated at the FACP and the remote annunciator,indicating the type of device, the operational state of the device (i.e. alarm, trouble or supervisory) and shall display the custom labelassociated with the device.

5. Selective Alarm: A system alarm shall include:

a) Indication of alarm condition at the FACP and the annunciator(s).

b) Identification of the device /zone that is the source of the alarm at the FACP and the annunciator(s).

c) Operation of audible and visible notification appliances until silenced at FACP.

d) Selectively closing doors normally held open by magnetic door holders on the fire floor, floor above and floor below.

e) Unlocking designated doors.

f) Shutting down supply and return fans serving zone where alarm is initiated.

g) Closing smoke dampers on system serving zone where alarm is initiated.

h) Initiation of smoke control sequence.

i) Transmission of signal to the supervising station.

j) Initiation of elevator Phase I functions (recall, shunt trip, illumination of indicator in cab, etc.) in accordance withASME/ANSI A17.1, when specified detectors or sensors are activated, as appropriate.

6. Supervisory Operations: Upon activation of a supervisory device such as a fire pump power failure, low air pressure switch ortamper switch, the system shall operate as follows:

a) Activate the system supervisory service audible signal and illuminate the LED at the control unit and the remoteannunciator.

b) Pressing the Supervisory Acknowledge Key will silence the supervisory audible signal while maintaining the SupervisoryLED "on" indicating off-normal condition.

c) Record the event in the FACP historical log.

d) Transmission of supervisory signal to the supervising station.

e) Restoring the condition shall cause the Supervisory LED to clear and restore the system to normal.

7. Alarm Silencing: If the "Alarm Silence" button is pressed, all audible alarm signals shall cease operation.

8. System Reset

a) The "System Reset" button shall be used to return the system to its normal state. Display messages shall provide operatorassurance of the sequential steps ("IN PROGRESS", "RESET COMPLETED") as they occur. The system shall verify allcircuits or devices are restored prior to resetting the system to avoid the potential for re-alarming the system. The displaymessage shall indicate "ALARM PRESENT, SYSTEM RESET ABORTED."

b) Should an alarm condition continue, the system will remain in an alarmed state.

9. A manual evacuation (drill) switch shall be provided to operate the notification appliances without causing other control circuits to beactivated.

10.WALKTEST: The system shall have the capacity of 8 programmable passcode protected one person testing groups, such that onlya portion of the system need be disabled during testing. The actuation of the "enable one person test" program at the control unitshall activate the "One Person Testing" mode of the system as follows:

a) The city circuit connection and any suppression release circuits shall be bypassed for the testing group.

b) Control relay functions associated with one of the 8 testing groups shall be bypassed.

c) The control unit shall indicate a trouble condition.

d) The alarm activation of any initiating device in the testing group shall cause the audible notification appliances assignedonly to that group to sound a code to identify the device or zone.

e) The unit shall automatically reset itself after signaling is complete.

f) Any opening of an initiating device or notification appliance circuit wiring shall cause the audible signals to sound for 4seconds indicating the trouble condition.

11.Install Mode: The system shall provide the capability to group all non-commissioned points and devices into a single "Install Mode"trouble condition allowing an operator to clearly identify event activations from commissioned points and devices in occupied areas.

a) It shall be possible to individually remove points from Install Mode as required for phased system commissioning.

b) It shall be possible to retrieve an Install Mode report listing that includes a list of all points assigned to the Install Mode.Panels not having an install mode shall be reprogrammed to remove any non-commissioned points and devices.

12.Service Gateway: A Service Gateway software application shall be provided that allows an authorized service person to remotelyquery panel status during testing, commissioning, and service without the need to return to the panel using standard email or instantmessaging tools. For systems without a service gateway application the service provider shall provide a minimum of two techniciansfor any system testing or commissioning.

D. Analog Smoke Sensors:

1. Monitoring: FACP shall individually monitor sensors for calibration, sensitivity, and alarm condition, and shall individually adjust forsensitivity. The control unit shall determine the condition of each sensor by comparing the sensor value to the stored values.

2. Environmental Compensation: The FACP shall maintain a moving average of the sensor's smoke chamber value to automaticallycompensate for dust, dirt, and other conditions that could affect detection operations.

3. Programmable Sensitivity: Photoelectric Smoke Sensors shall have 7 selectable sensitivity levels ranging from 0.2% to 3.7%,programmed and monitored from the FACP.

4. Sensitivity Testing Reports: The FACP shall provide sensor reports that meet NFPA 72 calibrated test method requirements. Thereports shall be viewed on a CRT Display or printed for annual recording and logging of the calibration maintenance schedule.

5. The FACP shall automatically indicate when an individual sensor needs cleaning. The system shall provide a means toautomatically indicate when a sensor requires cleaning. When a sensor's average value reaches a predetermined value, (3)progressive levels of reporting are provided. The first level shall indicate if a sensor is close to a trouble reporting condition and willbe indicated on the FACP as "ALMOST DIRTY." This condition provides a means to alert maintenance staff of a sensorapproaching dirty without creating a trouble in the system. If this indicator is ignored and the second level is reached, a "DIRTYSENSOR" condition shall be indicated at the FACP and subsequently a system trouble is reported to the Supervising Station. Thesensor base LED shall glow steady giving a visible indication at the sensor location. The "DIRTY SENSOR" condition shall not affectthe sensitivity level required to alarm the sensor. If a "DIRTY SENSOR" is left unattended, and its average value increases to a thirdpredetermined value, an "EXCESSIVELY DIRTY SENSOR" trouble condition shall be indicated at the control unit.

6. The FACP shall continuously perform an automatic self-test on each sensor that will check sensor electronics and ensure theaccuracy of the values being transmitted. Any sensor that fails this test shall indicate a "SELF TEST ABNORMAL" trouble condition.

7. Multi-Sensors shall combine photoelectric smoke sensing and heat sensing technologies. An alarm shall be determined by eithersmoke detection, with selectable sensitivity from 0.2 to 3.7 %/ft obscuration; or heat detection, selectable as fixed temperature orfixed with selectable rate-of-rise; or based on an analysis of the combination of smoke and heat activity.

8. Programmable Bases. It shall be possible to program relay and sounder bases to operate independently of their associated sensor.

9. Magnet test activation of smoke sensors shall be distinguished by its label and history log entry as being activated by a magnet.

E. Smoke Detectors: A, optional maintenance and testing service providing the following shall be provided to the owner, separate fromthis bid.

1. Biannual sensitivity reading and logging for each smoke sensor.

2. Scheduled biannual threshold adjustments to maintain proper sensitivity for each smoke sensor.

3. Threshold adjustment to any smoke sensor that has alarmed the system without the presence of particles of combustion.

4. Scheduled biannual cleaning or replacement of each smoke detector or sensor within the system.

5. Semi-annual functional testing of each smoke detector or sensor using the manufacturer's calibrated test tool.

6. Written documentation of all testing, cleaning, replacing, threshold adjustment, and sensitivity reading for each smoke detector orsensor device within the system.

F. Audible Alarm Notification: By voice evacuation and tone signals on loudspeakers in areas as indicated on drawings.

1. Automatic Voice Evacuation Sequence:

a) The audio alarm signal shall consist of an alarm tone for a maximum of five seconds followed by an automatic digital voicemessage. At the end of the voice message, the alarm tone shall resume. This sequence shall sound continuously until the"Alarm Silence" switch is activated.

b) All audio operations shall be activated by the system software so that any required future changes can be facilitated byauthorized personnel without any component rewiring or hardware additions.

C) Interface to the American Signal platform is required.

G. Speaker: Speaker notification appliances shall be listed to UL 1480.

1. The speaker shall operate on a standard 25VRMS or 70.7VRMS NAC using twisted/shielded wire.

2. The following taps are available: 0.25W, 0.50W, 1.0W and 2.0W. At the 1.0W tap, the speaker has minimum UL rated soundpressure level of 84dBA at 10 feet.

3. The speaker shall have a frequency response of 400 to 4000 Hz for Fire Alarm and 125 to 12 kHz for general signaling.

H. Manual Voice Paging

1. The system shall be configured to allow voice paging. Upon activation of any speaker manual control switch, the alarm tone shall besounded over all speakers in that group.

2. The control panel operator shall be able to make announcements via the push-to-talk paging microphone over the pre-selectedspeakers.

3. Total building paging shall be accomplished by the means of an "All Call" switch.

I. Constant Supervision of Non-Alarm Audio Functions

1. When required, the system shall be configured to allow Non-Alarm Audio (NAA) functions such as background music orgeneral/public address paging.

2. During NAA operation, the speaker circuit shall be electrically supervised to provide continuous monitoring of the speaker circuit.

3. During an alarm condition, supervision shall be disabled and alarm signals delivered to speakers.

J. Fire Suppression Monitoring:

1. Water flow: Activation of a water flow switch shall initiate general alarm operations.

2. Sprinkler valve tamper switch: The activation of any valve tamper switch shall activate system supervisory operations.

3. WSO: Water flow switch and sprinkler valve tamper switch shall be capable of existing on the same initiating zone. Activation ofeither device shall distinctly report which device is in alarm on the initiating zone.

K. Power Requirements

1. The control unit shall receive AC power via a dedicated fused disconnect circuit.

2. The system shall be provided with sufficient battery capacity to operate the entire system upon loss of normal AC power in a normalsupervisory mode for a period of 24hours with 15 minutes of alarm operation at the end of this period. The system shallautomatically transfer to battery standby upon power failure. All battery charging and recharging operations shall be automatic.

3. All circuits requiring system-operating power shall be 24 VDC and shall be individually fused at the control unit.

4. The incoming power to the system shall be supervised so that any power failure will be indicated at the control unit. A green "poweron" LED shall be displayed continuously at the user interface while incoming power is present.

5. The system batteries shall be supervised so that a low battery or a depleted battery condition, or disconnection of the battery shallbe indicated at the control unit and displayed for the specific fault type.

6. The system shall support NAC Lockout feature to prevent subsequent activation of Notification Appliance Circuits after a DepletedBattery condition occurs in order to make use of battery reserve for front panel annunciation and control.

7. The system shall support 100% of addressable devices in alarm or operated at the same time, under both primary (AC) andsecondary (battery) power conditions.

8. Loss of primary power shall sound a trouble signal at the FACP. FACP shall indicate when the system is operating on an alternatepower supply.

2.2. SUBMITTALS

A. General: Submit the following according to Conditions of Contract and Division 1 Specification Sections.

1. Product data sheets for system components highlighted to indicate the specific products, features, or functions required to meet thisspecification. Alternate or as-equal products submitted under this contract must provide a detailed line-by-line comparison of howthe submitted product meets, exceeds, or does not comply with this specification.

2. Wiring diagrams from manufacturer.

3. Shop drawings showing system details including location of FACP, all devices, circuiting and details of graphic annunciator, ifrequired and indicated on the project drawings.

4. System power and battery charts with performance graphs and voltage drop calculations to assure that the system will operate inaccordance with the prescribed backup time periods and under all voltage conditions per UL and NFPA standards.

5. System operation description including method of operation and supervision of each type of circuit and sequence of operations forall manually and automatically initiated system inputs and outputs. A list of all input and output points in the system shall be providedwith a label indicating location or use of IDC, SLC, NAC, relay, sensor, and auxiliary control circuits.

6. Operating instructions for FACP.

7. Operation and maintenance data for inclusion in Operating and Maintenance Manual. Include data for each type product, includingall features and operating sequences, both automatic and manual. Provide the names, addresses, and telephone numbers ofservice organizations.

8. Product certification signed by the manufacturer of the fire alarm system components certifying that their products comply withindicated requirements.

9. Record of field tests of system.

B. Submission to Authority Having Jurisdiction: In addition to routine submission of the above material, make an identical submission tothe authority having jurisdiction. Include copies of shop drawings as required to depict component locations to facilitate review. Uponreceipt of comments from the Authority, make resubmissions, if required, to make clarifications or revisions to obtain approval.

2.3. QUALITY ASSURANCE

A. Installer Qualifications: A factory authorized installer is to perform the work of this section.

B. Each and every item of the Fire Alarm System shall be listed under the appropriate category by Underwriters Laboratories, Inc. (UL),and shall bear the "UL" label.

2.4. MAINTENANCE SERVICE

A. Maintenance Service Contract: Provide an optional proposal to the owner for the maintenance of fire alarm systems and equipment fora period of 12 months, using factory-authorized service representatives.

B. Basic Services: Systematic, routine maintenance visits on a quarterly basis at times scheduled with the Owner. In addition, respond toservice calls within 24 hours of notification of system trouble. Adjust and replace defective parts and components with originalmanufacturer's replacement parts, components, and supplies.

C. Additional Services: Perform services within the above 12-month period not classified as routine maintenance or as warranty workwhen authorized in writing. Compensation for additional services must be agreed upon in writing prior to performing services.

D. Renewal of Maintenance Service Contract: No later than 60 days prior to the expiration of the maintenance services contract, deliver tothe Owner a proposal to provide contract maintenance and repair services for an additional one-year term. Owner will be under noobligation to accept maintenance service contract renewal proposal.

2.5. EXTRA MATERIALS

A. General: Furnish extra materials, packaged with protective covering for storage, and identified with labels clearly describing contents asfollows:

1. Break Rods for Manual Stations: Furnish quantity equal to 15 percent of the number of manual stations installed; minimum of 6 rods.

2. Notification Appliances: Furnish quantity equal to 5 percent of each type and number of units installed, but not less than one of eachtype.

3. Smoke Detectors or Sensors, Fire Detectors, and Flame Detectors: Furnish quantity equal to 5 percent of each type and number ofunits installed but not less than one of each type.

4. Detector or Sensor Bases: Furnish quantity equal to 2 percent of each type and number of units installed but not less than one ofeach type.

5. Printer Ribbons: Furnish 6 spare printer ribbons if a printer is indicated on the project drawings.

6. Provide a lockable storage cabinet for all spare parts. This cabinet shall have the exact same lock cylinder as the Fire Alarm ControlPanel, Remote Annunciator(s) and Manual Pull Stations. One key shall open all of the devices as indicated above. The cabinet shallbe painted beige to match the Fire Alarm Control Panel.

E3.2

TAT

SP

EC

IFIC

ATI

ON

S

FAC

ILIT

IES

PLA

NN

ING

AN

D C

ON

STR

UC

TIO

N

US

F TA

T B

UIL

DIN

G F

IRE

ALA

RM

UP

GR

AD

ES

Tam

pa, F

lorid

a

Page 11: E3.3 TAT SPECIFICATIONS - University of South Floridausfweb2.usf.edu/BIDS 2014-15/15-002-ppb-tat-fire-alarm/15-002-ppb-upgrades.pdfe3.1 tat specifications e3.1 tat specifications e3.1

PART 3 – PRODUCTS

3.1. FIRE ALARM CONTROL PANEL (FACP)

A. General: Comply with UL 864, "Control Units and Accessories for Fire Alarm Systems".

B. The following FACP hardware shall be provided:

1. Power Limited base panel with platinum cabinet and door, 120 VAC input power.

2. 2,000 point capacity where (1) point equals (1) monitor (input) or (1) control (output).

3. 2,500 points of Network Annunciation at FACP Display when applied as a Network Node.

4. 2000 points of annunciation where one (1) point of annunciation equals:

a) 1 LED driver output on a graphic driver or 1 switch input on a graphic switch input module.

b) 1 LED on panel or 1 switch on panel.

5. From all battery charging circuits in the system provide battery voltage and ammeter readouts on the FACP LCD Display.

6. Municipal City Circuit Connection with Disconnect switch, 24VDC Remote Station (reverse polarity), local energy, shunt master box,or a form "C" contact output.

7. One Auxiliary electronically resettable fused 2A @24VDC Output, with programmable disconnect operation for 4-wire detector reset.

8. One Auxiliary Relay, SPDT 2A @32VDC, programmable as a trouble relay, either as normally energized or de-energized, or as anauxiliary control.

9. Three (3) Class B or A (Style Y/Z) Notification Appliance Circuits (NAC; rated 3A@24VDC, resistive).

10.Where required provide Intelligent Remote Battery Charger for charging up to 110Ah batteries.

11.Power Supplies with integral intelligent Notification Appliance Circuit Class B for system expansion.

12.Four (4) form "C" Auxiliary Relay Circuits (Form C contacts rated 2A @ 24VDC, resistive), operation is programmable for trouble,alarm, supervisory of other fire response functions. Relays shall be capable of switching up to ½ A @ 120VAC, inductive.

13.The FACP shall support up to (5) RS-232-C ports and one service port. All (5) RS-232 Ports shall be capable of two-waycommunications.

14.Remote Unit Interface: supervised serial communication channel for control and monitoring of remotely located annunciators and I/Opanels.

15.Modular Network Communications Card.

16.Programmable DACT for either Common Event Reporting or per Point Reporting.

17.Service Port Modem for dial in passcode access to all fire control panel information.

C. Voice Alarm: Provide an emergency communication system, integral with the FACP, including voice alarm system components,microphones, amplifiers, and tone generators. Features include:

1. Amplifiers comply with UL 1711, "Amplifiers for Fire Protective Signaling Systems." Amplifiers shall provide an onboard local modetemporal coded horn tone as a default backup tone. Test switches on the amplifier shall be provided to test and observe amplifierbackup switchover. Each amplifier shall communicate to the host panel amplifier and NAC circuit voltage and current levels fordisplay on the user interface. Each amplifier shall be capable of performing constant supervision for non-alarm audio functions suchas background music and general paging.

2. Dual alarm channels permit simultaneous transmission of different announcements to different zones or floors automatically or byuse of the central control microphone. All announcements are made over dedicated, supervised communication lines. All risers shallsupport Class A wiring for each audio channel.

3. Provide the capability to add eight channel digitally multiplexed audio for systems that require more than two channels ofsimultaneous audio. Up to 8 channels of audio shall be multiplexed on either a style 4 or style 7 twisted pair.

4. Emergency voice communication audio controller module shall provide up to 32 minutes of message memory for digitally storedmessages. Provide supervised connections for master microphone and up to 5 remote microphones.

5. Status annunciator indicating the status of the various voice alarm speaker zones and the status of fire fighter telephone two-waycommunication zones.

6. When required, Redundant Voice Command Centers shall be capable of generating voice paging from more than one node in anetwork audio system.

D. Evacuation System - Non-Alarm Audio

1. The fire alarm control panel shall provide non-alarm audio from an owner supplied paging and/or music source over the fire alarmevacuation speakers. This feature shall be an integral part of the fire alarm system, and shall use some or all of the audiocomponents from the fire alarm evacuation system.

2. The fire alarm system and the non-alarm audio operation shall comply with NFPA 72 requirements for non-emergency purposes at afire command center that is not constantly attended by a trained operator.

3. All fire alarm system hardware and software shall be U.L. listed for non-alarm audio use. The fire alarm system shall supervise forsystem hardware and field wiring faults while playing non-alarm audio over the evacuation speakers. Any hardware failure orspeaker circuit fault detected when the system is playing non-alarm audio shall report a trouble on the fire alarm control panel. Allaudio components used for both the non-alarm audio and the fire alarm evacuation system shall be manufactured by the samesupplier.

4. The non-alarm audio shall have two dedicated audio inputs to the fire alarm control panel. Terminal strip connections and anindustry standard RCA receptacle shall be provided at the fire alarm control panel for terminating the owner's audio source. The firealarm input shall be 600-Ohm impedance. The inputs on the fire alarm control panel shall be electrically isolated via an isolationtransformer.

5. The fire alarm control panel shall accept industry standard “line level audio input" from the owner's non-alarm audio source. The firealarm system hardware and software shall distribute the audio over the fire alarm evacuation speakers. The selection of whichspeaker zones to distribute the non-alarm audio to the building occupants shall be coordinated with the owner's representative.

6. The fire alarm control panel shall be able to make audio input level adjustments from the owner's non-alarm audio source. Thisadjustment will match the non-alarm audio source to the fire alarm input. After the audio levels are adjusted, the owner shall controlthe volume level from the non-alarm audio source.

7. The fire alarm system will provide "buttons" have the capability to provide operator "buttons" that will adjust the volume level ofpre-assigned non-alarm audio zones. The volume level of non-alarm audio that is being broadcast to any audio zone will also beindividually adjustable by time of day via a pre-specified schedule.

8. The non-alarm audio shall be the lowest priory audio on the fire alarm system. The non-alarm audio shall not interfere with any ofthe fire alarm emergency signals that may include live voice, pre-recorded emergency voice messages, or any alert tones. Switchesshall be located on the fire alarm control panel to turn on or off the non-alarm audio system feature. The fire alarm control panelshall have LED lamps to indicate the ON vs. OFF status of the non-alarm audio feature. Speaker circuits that are activelybroadcasting non-alarm audio will also be indicated by LEDs.

9. The non-alarm audio shall be synchronized throughout the fire alarm life safety system amplifiers and speaker circuits. Any remoteamplifier panels located on the fire alarm system network shall also be synchronized. The system shall be capable of accepting asystem-wide non-alarm audio input at the main fire alarm control or another local non-alarm audio input at a remote amplifier panelto serve only the areas served by that remote panel.

10.Multiple non-alarm audio sources must be accessible by the fire alarm non-alarm audio system. Each separate non-alarm audiosource will have the ability to be broadcast into a distinct fire zone, depending on occupant preference. Any system restricted to alimited number of non-audio sources will not be accepted. The system must have the capability of broadcasting an unlimited numberof non-alarm sources, except as determined by the number of individual fire zones served by the fire alarm system.

11.Non-alarm audio shall be automatically turned off in the event of primary power failure to the fire alarm control panel or any of theremote amplifier panels controlled by the main fire alarm control panel.

E. Distributed Module Operation: FACP shall be capable of allowing remote location of the following modules; interface of such modulesshall be through a Style 7 (Class A) supervised serial communications channel (SLC):

1. Amplifiers, voice and telephone control circuits

2. Addressable Signaling Line Circuits

3. Initiating Device Circuits

4. Notification Appliance Circuits

5. Auxiliary Control Circuits

6. Graphic Annunciator LED/Switch Control Modules

a) In systems with two or more Annunciators and/or Command Centers, each Annunciator/Command Center shall beprogrammable to allow multiple Annunciators/Command Centers to have equal operation priority or to allow hierarchalpriority control to be assigned to individual Annunciator/Command Center locations.

F. Cabinet: Lockable steel enclosure. Arrange unit so all operations required for testing or for normal care and maintenance of the systemare performed from the front of the enclosure. If more than a single unit is required to form a complete control unit, provide exactlymatching modular unit enclosures.

G. Alphanumeric Display and System Controls: Panel shall include an 80 character LCD display to indicate alarm, supervisory, andcomponent status messages and shall include a keypad for use in entering and executing control commands.

1. The system shall have the capability include the necessary hardware] to provide expanded content, multi-line, operator interfacedisplays as indicated on the drawings and specifications. The expanded content multi-line displays shall be Quarter-VGA (QVGA) orlarger and be capable of supporting a minimum of 854 standard ASCII characters to minimize or eliminate the levels of navigationrequired for access to information when responding to critical emergencies and abnormal system conditions. The QVGA operatorinterface shall provide operator prompts and six context sensitive soft-keys for intuitive operation.

a) Expanded content, multi-line operator interfaces shall be capable of providing the following functions:

(a) Dual language operation with Instant-Switch language selection during runtime.

(b) Activity display choices for:

(i) First 8 Events.

(ii) First 5 Events and Most Recent Event (with first and most recent event time and date stamps).

(iii)First Event and Most Recent Event (with first and most recent event time and date stamps).

(iv) Scrollable List Display [displays a scrollable list of active points for the event category (alarm, priority 2,supervisory, or trouble) selected. The position in this list will be the last acknowledged point (not flashing) at the topfollowed by the next 7 unacknowledged points (flashing)].

(v) General Event Status (alarm, priority 2, supervisory, or trouble in system)

(vi) Site Plan

(c) Equal or hierarchal priority assignment. In systems with two or more operator interfaces, each operator interfaceshall be programmable to allow multiple operator interfaces to have equal operation priority or to allow hierarchalpriority control to be assigned to individual operator interfaces (locations).

(d) Up to 50 custom point detail messages for providing additional point specific information in detailed point statusscreens.

(e) Bitmap file import for operator interface display of site plan and background watermark images. [Site plan statusicons shall indicate area status for highest priority active events.]

b) Expanded content, multi-line displays shall have the capability to provide Dual-Language operation.

(a) Language selection shall be via a switch on the operator interface panel. Operator interface panels shall supportinstant-language-switchover during runtime to allow the operator to toggle between languages each time thelanguage selection switch is operated, without requiring complicated multi-step processes.

(b) Both one-byte and two-byte characters shall be supported.

3.2. SMOKE CONTROL SYSTEM

A. Smoke Control System: If indicated on the drawings, provide a smoke control system which is UL 864 (UUKL product category) listedfor smoke control system service. The system shall provide automatic operation of smoke exhaust fans, makeup air fans, air handlingunits, and dampers in accordance with the smoke control sequence indicated on the drawings. The smoke control system shall belocated in the fire command center.

B. Provide and install smoke control relays within 3 feet of each smoke exhaust fan controller, makeup air fan controller, air handling unit'scontroller, and damper controlled by the smoke control system. The building automation/temperature control system contractor shallterminate the relays to the fan controllers, air handling unit controllers, and dampers.

C. Provide and install addressable modules to monitor status/operation of each smoke exhaust fan, makeup air fan, air handling unit, anddamper controlled by the smoke control system. The fire alarm contractor shall terminate the modules to status indicators.

D. Enclosure: Finish to match Fire Alarm Control Units. The locking cover/display assembly is hinged on the left. Key and lock shall becommon to all secured fire alarm system enclosures.

3.3. REMOTE CRTS, PC ANNUNCIATOR AND PRINTERs

A. Fire Alarm Control Unit shall be capable of operating remote CRT's and/or printers; output shall be ASCII from an RS-232-C connectionwith an adjustable baud rate.

B. Fire Alarm Control Unit shall be capable of operating an Agency Listed PC Annunciator Client/Server which provides statusannunciation and limited system control using a convenient and familiar Microsoft Vista Business operating system based interface.Other compatible Operating Systems shall include Microsoft XP Professional and Windows® 2000 Professional. The PC AnnunciatorClient/Server shall provide the following functions:

1. Login/logout password protection with time duration selectable automatic logout.

2. Display Alarm, Supervisory, Priority 2, and Trouble conditions with numerical tallies for each.

3. Display first and last alarms.

4. Different event types have separate visible indicators with a common audible indicator.

5. Event logs can be searched and printed.

6. View and/or print TrueAlarm status reports and service reports. (printing requires an available local or network printer).

7. Alarm Silence; System Reset; and Priority 2 Reset.

8. Global and individual point acknowledge.

9. Set system time and date and clear event log.

10.Individual point access for control or parameter revisions.

11.WALKTEST system test is supported for service convenience.

12.Up to (8) Simultaneous Client connections shall be supported by the PC Annunciator Server. Remote Clients shall be capable ofconnecting to the PC Annunciator Server via Ethernet LAN/WAN connections.

C. Each RS-232-C port shall be capable of supporting and supervising a remote Printer, CRT/Keyboard, or PC Annunciator; the FACPshall support as many as five (5) remote RS-232 devices in any combination. The Fire Alarm Control Panel shall support five (5)RS-232-C ports.

3.4. REMOTE LCD ANNUNCIATOR

A. Provide a remote LCD Annunciator, where indicated, with the same "look and feel" as the FACP operator interface. The Remote LCDAnnunciator shall use the same Primary Acknowledge, Silence, and Reset Keys; Status LEDs and LCD Display as the FACP.

B. Annunciator shall have super-twist LCD display with two lines of 40 characters each. Annunciator shall be provided with four (4)programmable control switches and associated LEDs.

C. Under normal conditions the LCD shall display a "SYSTEM IS NORMAL" message and the current time and date.

D. Should an abnormal condition be detected the appropriate LED (Alarm, Supervisory or Trouble) shall flash. The unit audible signalshall pulse for alarm conditions and sound steady for trouble and supervisory conditions.

E. The LCD shall display the following information relative to the abnormal condition of a point in the system:

1. 40 character custom location label.

2. Type of device (e.g., smoke, pull station, waterflow).

3. Point status (e.g., alarm, trouble).

F. Operator keys shall be key switch enabled to prevent unauthorized use. The key shall only be removable in the disabled position.Acknowledge, Silence and Reset operation shall be the same as the FACP.

3.5. SYSTEM PRINTER

A. General: If indicated on the building drawing, provide a dot-matrix type, listed and labeled as an integral part of the fire alarm system.

3.6. EMERGENCY POWER SUPPLY

A. General: Components include battery, charger, and an automatic transfer switch.

B. Battery: Sealed lead-acid or nickel cadmium type. Provide sufficient capacity to operate the complete alarm system in normal orsupervisory (non-alarm) mode for a period of 24 hours. Following this period of operation on battery power, the battery shall havesufficient capacity to operate all components of the system, including all alarm notification devices in alarm mode for a period of 15minutes.

3.7. ADDRESSABLE MANUAL PULL STATIONS

A. Description: Addressable single- or double-action type, red LEXAN, with molded, raised-letter operating instructions of contrastingcolor. Station will mechanically latch upon operation and remain so until manually reset by opening with a key common with the controlunits.

B. Protective Shield: Where required, as indicated on the drawings, provide a tamperproof, clear LEXAN shield and red frame that easilyfit over manual pull stations. When shield is lifted to gain access to the station, a battery powered piercing warning horn shall beactivated. The horn shall be silenced by lowering and realigning the shield. The horn shall provide 85dB at 10 feet and shall bepowered by a 9 VDC battery.

3.8. SMOKE SENSORS

A. General: Comply with UL 268, "Smoke Detectors for Fire Protective Signaling Systems." Include the following features:

1. Factory Nameplate: Serial number and type identification.

2. Operating Voltage: 24 VDC, nominal.

3. Self-Restoring: Detectors do not require resetting or readjustment after actuation to restore normal operation.

4. Plug-In Arrangement: Sensor and associated electronic components are mounted in a module that connects to a fixed base with atwist-locking plug connection. Base shall provide break-off plastic tab that can be removed to engage the head/base lockingmechanism. No special tools shall be required to remove head once it has been locked. Removal of the detector head shallinterrupt the supervisory circuit of the fire alarm detection loop and cause a trouble signal at the control unit.

5. Quick Connect Arrangement: Photoelectric sensor and electronics in a single piece construction which shall twist-lock onto amounting base that attaches to a standard electrical box.

6. Each sensor base shall contain an LED that will flash each time it is scanned by the Control Unit (once every 4 seconds). In alarmcondition, the sensor base LED shall be on steady.

7. Each sensor base shall contain a magnetically actuated test switch to provide for easy alarm testing at the sensor location.

8. Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent substitution of another sensor type.Upon detection of a "wrong device", the control unit shall operate with the installed device at the default alarm settings for thatsensor; 2.5% obscuration for photoelectric sensor, 135-deg F and 15-deg F rate-of-rise for the heat sensor, but shall indicate a"Wrong Device" trouble condition.

9. The sensor's electronics shall be immune from nuisance alarms caused by EMI and RFI.

10.Sensors include a communication transmitter and receiver in the mounting base having a unique identification and capability forstatus reporting to the FACP. Sensor address shall be located in base to eliminate false addressing when replacing sensors.

11.Removal of the sensor head for cleaning shall not require the setting of addresses.

B. Type: Smoke sensors shall be of the photoelectric or combination photoelectric / heat type.

C. Bases: Relay output, sounder and isolator bases shall be supported alternatives to the standard base.

D. Duct Smoke Sensor: Photoelectric type, with sampling tube of design and dimensions as recommended by the manufacturer for thespecific duct size and installation conditions were applied. Sensor includes relay as required for fan shutdown.

1. Environmental compensation, programmable sensitivity settings, status testing, and monitoring of sensor dirt accumulation for theduct smoke sensor shall be provided by the FACP.

2. The Duct Housing shall provide a supervised relay driver circuit for driving up to 15 relays with a single "Form C" contact rated at7A@ 28VDC or 10A@ 120VAC. This auxiliary relay output shall be fully programmable. Relay shall be mounted within 3 feet ofHVAC control circuit.

3. Duct Housing shall provide a relay control trouble indicator Yellow LED.

4. Duct Housing shall have a transparent cover to monitor for the presence of smoke. Cover shall secure to housing by means of four(4) captive fastening screws.

5. Duct Housing shall provide two (2) Test Ports for measuring airflow and for testing. These ports will allow aerosol injection in orderto test the activation of the duct smoke sensor.

6. Duct Housing shall provide a magnetic test area and Red sensor status LED.

7. For maintenance purposes, it shall be possible to clean the duct housing sampling tubes by accessing them through the ducthousing front cover.

8. Each duct smoke sensor shall have a Remote Test Station with an alarm LED and test switch.

9. Where indicated provide NEMA 4X weatherproof duct housing enclosure that shall provide for the circulation of conditioned airaround the internally mounted addressable duct sensor housing to maintain the sensor housing at its rated temperature range. Thehousing shall be UL Listed to Standard 268A.

10.Provide an Air Aspiration Detector in lieu of a standard Smoke Detector at the top of each elevator shaft, as indicated on thedrawings.

11.Provide an Air Aspiration Duct Detector in lieu of a standard Duct Detectors in each high bay AHU requiring a standard DuctDetectors.

3.9. HEAT SENSORS

A. Thermal Sensor: Combination fixed-temperature and rate-of-rise unit with plug-in base and alarm indication lamp; 135-deg Ffixed-temperature setting except as indicated.

B. Thermal sensor shall be of the epoxy encapsulated electronic design. It shall be thermistor-based, rate-compensated, self-restoringand shall not be affected by thermal lag.

C. Sensor fixed temperature sensing shall be independent of rate-of-rise sensing and] programmable to operate at 135-deg F or 155-degF. Sensor rate-of-rise temperature detection shall be selectable at the FACP for either 15-deg F or 20-deg F per minute.

D. Sensor shall have the capability to be programmed as a utility monitoring device to monitor for temperature extremes in the range from32-deg F to 155-deg F.

3.10. ADDRESSABLE CIRCUIT INTERFACE MODULES

A. Addressable Circuit Interface Modules: Arrange to monitor or control one or more system components that are not otherwise equippedfor addressable communication. Modules shall be used for monitoring of waterflow, valve tamper, non-addressable devices, and forcontrol of AHU systems.

B. Addressable Circuit Interface Modules will be capable of mounting in a standard electric outlet box. Modules will include cover plates toallow surface or flush mounting. Modules will receive their operating power from the signaling line circuit or a separate two wire pairrunning from an appropriate power supply, as required.

C. There shall be the following types of modules:

1. Type 1: Monitor Circuit Interface Module:

a) For conventional 2-wire smoke detector and/or contact device monitoring with Class B or Class A wiring supervision. Thesupervision of the zone wiring will be Class B. This module will communicate status (normal, alarm, trouble) to the FACP.

b) For conventional 4-wire smoke detector with Class B wiring supervision. The module will provide detector reset capabilityand over-current power protection for the 4-wire detector. This module will communicate status (normal, alarm, trouble) tothe FACP.

2. Type 2: Line Powered Monitor Circuit Interface Module

a) This type of module is an individually addressable module that has both its power and its communications supplied by thetwo wire signaling line circuit. It provides location specific addressability to an initiating device by monitoring normally opendry contacts. This module shall have the capability of communicating four zone status conditions (normal, alarm, currentlimited, trouble) to the FACP.

b) This module shall provide location specific addressability for up to five initiating devices by monitoring normally closed ornormally open dry contact security devices. The module shall communicate four zone status conditions (open, normal,abnormal, and short). The two-wire signaling line circuit shall supply power and communications to the module.

3. Type 3: Single Address Multi-Point Interface Modules

a) This multipoint module shall provide location specific addressability for four initiating circuits and control two output relaysfrom a single address. Inputs shall provide supervised monitoring of normally open, dry contacts and be capable ofcommunicating four zone status conditions (normal, open, current limited, and short). The input circuits and output relayoperation shall be controlled independently and disabled separately.

b) This dual point module shall provide a supervised multi-state input and a relay output, using a single address. The inputshall provide supervised monitoring of two normally open, dry contacts with a single point and be capable of communicatingfour zone status conditions (normal, open, current limited, and short). The two-wire signaling line circuit shall supply powerand communications to the module.

c) This dual point module shall monitor an unsupervised normally open, dry contact with one point and control an output relaywith the other point, using a single address. The two-wire signaling line circuit shall supply power and communications tothe module.

4. Type 4: Line Powered Control Circuit Interface Module

a) This module shall provide control and status tracking of a Form "C" contact. The two-wire signaling line circuit shall supplypower and communications to the module.

5. Type 5: 4-20 mA Analog Monitor Circuit Interface Module

a) This module shall communicate the status of a compatible 4-20 mA sensor to the FACP. The FACP shall annunciate up tothree threshold levels, each with custom action message; display and archive actual sensor analog levels; and permitsensor calibration date recording.

D. All Circuit Interface Modules shall be supervised and uniquely identified by the control unit. Module identification shall be transmitted tothe control unit for processing according to the program instructions. Modules shall have an on-board LED to provide an indication thatthe module is powered and communicating with the FACP. The LEDs shall provide a troubleshooting aid since the LED blinks on pollwhenever the peripheral is powered and communicating.

3.11. MAGNETIC DOOR HOLDERS

A. Description: Units shall be listed to UL 228. Units are equipped for wall or floor mounting as indicated and are complete with matchingdoor plate. Unit shall operate from a 120VAC, a 24VAC or a 24VDC source, and develop a minimum of 25 lbs. holding force.

B. Material and Finish: Match door hardware.

3.13. TrueAlert Addressable Appliances NAC Power Extender

A. The TrueAlert Addressable Controller shall be a stand-alone panel capable of powering a minimum of 3 TrueAlert Signaling linecircuits. Each channel shall be rated for 2.5 amps and support up to 63 TrueAlert addressable notification appliances. Power andcommunication for the notification appliances shall be provided on the same pair of wires.

B. Addressable SLC notification appliance circuits shall be Class A, Style 6.

C. The internal power supply & battery charger shall be capable of charging up 12.7 Ah batteries internally mounted or 18Ah batteriesmounted in an external cabinet.

D. The NAC extender panel may be mounted close to the host control panel or can be remotely located.

3.14. Network System Integrator (NSI)

A. The Network System Integrator shall provide Agency Listed integration capable of communicating the status information from multiplebrands and/or vintages of control panels onto the fire alarm network for reporting at a central command center location and at othernetwork nodes (panels).

1. Protocol communication interfaces for systems integration that require ongoing protocol development necessary to maintaincompatibility and agency listings with new versions of software releases shall not be substituted.

B. The Network System Integrator shall receive primary and secondary power from an alternate source

C. The Network System Integrator shall provide 8 isolated voltage monitor inputs for status communication onto the network

1. Inputs shall be rated to monitor voltages from 10 to 33 VDC

2. Inputs shall be compatible with direct switched or reverse polarity circuits

D. The Network System Integrator shall provide 8 dry contact relay outputs for interface to monitored equipment

1. Each output shall be configurable for normally open or normally closed contact operation.

2. Output contacts shall be rated for 1A @ 24VDC / 25VAC or 0.5A @ 70VAC

3. 7 relay outputs shall be programmable

4. 1 relay output shall be normally energized and dedicated for trouble operation

E. The Network System Integrator shall be capable of maintaining Fire Alarm Network communications with other network nodes (panels)when the monitored interface panel is powered down for service (i.e., repeater mode)

PART 4 – EXECUTION

4.1. INSTALLATION, GENERAL

A. Install system components and all associated devices in accordance with applicable NFPA Standards and manufacturer'srecommendations.

B. Installation personnel shall be supervised by persons who are qualified and experienced in the installation, inspection, and testing offire alarm systems. Examples of qualified personnel shall include, but not be limited to, the following:

1. Factory trained and certified personnel.

2. National Institute of Certification in Engineering Technologies (NICET) fire alarm level II certified personnel.

3. Personnel licensed or certified by state or local authority.

4.2. EQUIPMENT INSTALLATION

A. Furnish and install a complete Fire Alarm System as described herein and as shown on the plans. Include sufficient control unit(s),annunciator(s), manual stations, automatic fire detectors, smoke detectors, audible and visible notification appliances, wiring,terminations, electrical boxes, ethernet drops, and all other necessary material for a complete operating system.

B. Existing Fire Alarm Equipment shall be maintained fully operational until the new equipment has been tested and accepted.

C. Equipment Removal: After acceptance of the new fire alarm system, disconnect and remove the existing fire alarm equipment andrestore damaged surfaces. Package operational fire alarm and detection equipment that has been removed and deliver to the Owner.Remove from the site and legally dispose of the remainder of the existing material.

D. Water-Flow and Valve Supervisory Switches: Connect for each sprinkler valve required to be supervised.

E. Device Location-Indicating Lights: Locate in the public space immediately adjacent to the device they monitor.

F. Install manual station with operating handle 48 inches (1.22 m) above floor. Install wall mounted audible and visual notificationappliances not less than 80 inches (2.03 m) above floor to bottom of lens and not greater than 96 inches (2.44 m) above floor to bottomof lens.

G. Mount outlet box for electric door holder to withstand 80 pounds pulling force.

H. Make conduit and wiring connections to [door release devices,] [sprinkler flow switches,] [sprinkler valve tamper switches,] [firesuppression system control panels,] [duct smoke detectors] [edit paragraph].

I. Automatic Detector Installation: Conform to NFPA 72.

J. Ethernet Drop: A standard RJ-45 Ethernet connection to the owner's Ethernet network shall be provided at each fire alarm controlpanel as part of the contract.

4.3. PREPARATION

A. Coordinate work of this Section with other affected work and construction schedule.

4.4. WIRING INSTALLATION

A. System Wiring: Wire and cable shall be a type listed for its intended use by an approval agency acceptable to the Authority HavingJurisdiction and shall be installed in accordance with the appropriate articles from the current approved edition of NFPA 70: NationalElectric Code (NEC).

B. Contractor shall obtain from the Fire Alarm System Manufacturer written instruction regarding the appropriate wire/cable to be used forthis installation. No deviation from the written instruction shall be made by the Contractor without the prior written approval of the FireAlarm System Manufacturer.

C. Color Coding: Color-code fire alarm conductors differently from the normal building power wiring. Use one color code for alarm initiatingdevice circuits wiring and a different color code for supervisory circuits. Color-code notification appliance circuits differently fromalarm-initiating circuits. Paint fire alarm system junction boxes and covers red.

D. Terminate circuit in control panel for Class supervision.

E. Ethernet circuits shall be provided to the Fire Alarm Control Panel and Graphical Workstation Remote Clients, PC Annunciator RemoteClients as shown on the plans.

4.5. FIELD QUALITY CONTROL

A. Manufacturer's Field Services: Provide services of a factory-authorized service representative to supervise the field assembly andconnection of components and the pretesting, testing, and adjustment of the system.

B. Service personnel shall be qualified and experienced in the inspection, testing, and maintenance of fire alarm systems. Examples ofqualified personnel shall be permitted to include, but shall not be limited to, individuals with the following qualifications:

1. Factory trained and certified.

2. National Institute for Certification in Engineering Technologies (NICET) fire alarm certified.

3. International Municipal Signal Association (IMSA) fire alarm certified.

4. Certified by a state or local authority.

5. Trained and qualified personnel employed by an organization listed by a national testing laboratory for the servicing of fire alarmsystems.

C. Pretesting: Determine, through pretesting, the conformance of the system to the requirements of the Drawings and Specifications.Correct deficiencies observed in pretesting. Replace malfunctioning or damaged items with new and retest until satisfactoryperformance and conditions are achieved.

D. Inspection:

1. Inspect equipment installation, interconnection with system devices, mounting locations, and mounting methods.

2. Verify that units and controls are properly installed, connected, and labeled and that interconnecting wires and terminals areidentified.

E. Acceptance Operational Tests:

1. Perform operational system tests to verify conformance with specifications:

a) Each alarm initiating device installed shall be operationally tested. Each device shall be tested for alarm and troubleconditions. Contractor shall submit a written certification that the Fire Alarm System installation is complete including allpunch-list items. Test battery operated emergency power supply. Test emergency power supply to minimum durationsspecified. Test Supervising Station Signal Transmitter. Coordinate testing with Supervising Station monitoring firm/entity.

b) Test each Notification Appliance installed for proper operation. Submit written report indicating sound pressure levels atspecified distances.

c) Test Fire Alarm Control Panel and Remote Annunciator.

2. Provide minimum 10 days notice of acceptance test performance schedule to Owner, and local Authority Having Jurisdiction.

F. Retesting: Correct deficiencies indicated by tests and completely retest work affected by such deficiencies. Verify by the system testthat the total system meets the Specifications and complies with applicable standards.

G. Report of Tests and Inspections: Provide a written record of inspections, tests, and detailed test results in the form of a test log. UseNFPA 72 Forms for documentation.

H. Final Test, Record of Completion, and Certificate of Occupancy:

1. Test the system as required by the Authority Having Jurisdiction in order to obtain a certificate of occupancy. Provide completedNFPA 72 Record of Completion form to Owner and AHJ.

4.6. CLEANING AND ADJUSTING

A. Cleaning: Remove paint splatters and other spots, dirt, and debris. Clean unit internally using methods and materials recommended bymanufacturer.

B. Occupancy Adjustments: When requested within one year of date of Substantial Completion, provide on-site assistance in adjustingsound pressure levels and adjusting controls and sensitivities to suit actual occupied conditions. Provide up to three visits to the site forthis purpose.

4.7. TRAINING

A. Provide the services of a factory-authorized service representative to demonstrate the system and train Owner's maintenancepersonnel as specified below.

1. Train Owner's maintenance personnel in the procedures and schedules involved in operating, troubleshooting, servicing, andpreventive maintaining of the system. Provide a minimum of 8 hours' training.

2. Schedule training with the Owner at least seven days in advance.

END OF SECTION

E3.3

TAT

SP

EC

IFIC

ATI

ON

S

FAC

ILIT

IES

PLA

NN

ING

AN

D C

ON

STR

UC

TIO

N

US

F TA

T B

UIL

DIN

G F

IRE

ALA

RM

UP

GR

AD

ES

Tam

pa, F

lorid

a