2015-03-03 ST0028 4...20 mA Loop Powered - LCD Display Unit APPLICATION MANUAL The loop-powered ST0028 reads any 4-20mA signal and displays the information with high accuracy in engineering units. The ST0028 is arranged to be inserted in a 70 mm Head. The indicator may be used in conjunction with a "Head mounted" temperature transmitter or other devices like pressure transmitter. ST0028 is supplied through a small voltage drop on the 4÷20mA loop (max 2,5V ; 22mA). Three buttons allows you to easily calibrate the display and program the configuration parameters: Engineering zero and Full-scale; decimal point position; reading resolution, reading filter, over-range limits and linear or square root scale. Configuration and calibration data are stored in a non-volatile memory. The ST0028 features a “pass through” connection; this means that it is inserted between the loop (with 2 terminal blocks) and the transmitter (with 2 wires). Three holes allow fixing the indicator to the head. Page 1/4 ____________________________________________________________________________________________________________ www.limathermcomponents.com, e-mail: [email protected] Kapitał zakładowy: 2.050.000 PLN, NIP: 6342641389, REGON: 240666167, KRS: 0000287965, Sąd Rejonowy Katowice-Wschód, Wydz. VIII Gospodarczy Limatherm Components Sp. z o.o. ul. Żelazna 5, 41-506 Chorzów tel.: 32 783 16 00, faks: 32 783 16 01

Upload: others

Post on 10-Jul-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: E0028-MI01Eimg.iap.pl/s/466/205736/Edytor/Application_manual_ST0028.pdf · SPECIFICATIONS ELECTRICAL AND PHYSICAL Loop wiring: 2 terminal blocks max 1mm2 (AWG 16) Transmitter wiring:

2015-03-03

ST00284...20 mA Loop Powered - LCD Display Unit

APPLICATION MANUAL

The loop-powered ST0028 reads any 4-20mA signal and displays the information with high accuracy in engineering units. The ST0028 is arranged to be inserted in a 70 mm Head. The indicator may be used in conjunction with a "Head mounted" temperature transmitter or other devices like pressure transmitter.ST0028 is supplied through a small voltage drop on the 4÷20mA loop (max 2,5V ; 22mA). Three buttons allows you to easily calibrate the display and program the configuration parameters: Engineering zero and Full-scale; decimal point position; reading resolution, reading filter, over-range limits and linear or square root scale. Configuration and calibration data are stored in a non-volatile memory. The ST0028 features a “pass through” connection; this means that it is inserted between the loop (with 2 terminalblocks) and the transmitter (with 2 wires). Three holes allow fixing the indicator to the head.

Page 1/4____________________________________________________________________________________________________________

www.limathermcomponents.com, e-mail: [email protected]ł zakładowy: 2.050.000 PLN, NIP: 6342641389, REGON: 240666167,

KRS: 0000287965, Sąd Rejonowy Katowice-Wschód, Wydz. VIII Gospodarczy

Limatherm Components Sp. z o.o.ul. Żelazna 5, 41-506 Chorzów

tel.: 32 783 16 00, faks: 32 783 16 01

Page 2: E0028-MI01Eimg.iap.pl/s/466/205736/Edytor/Application_manual_ST0028.pdf · SPECIFICATIONS ELECTRICAL AND PHYSICAL Loop wiring: 2 terminal blocks max 1mm2 (AWG 16) Transmitter wiring:

SPECIFICATIONS ELECTRICAL AND PHYSICAL

Loop wiring: 2 terminal blocks max 1mm2 (AWG 16)

Transmitter wiring: 2 wire 0.5mm2

Working temperature range: -20 ÷ +60°C (-4.0 to 140°F)Storage temperature range: -30 ÷+80°C ( -22 to 176°F) Humidity: 0÷90% non-condensing Dimensions: 59 mm / 20 mm Input signal: 4÷20 mA Input Operating Range: 3,6÷22 mA Max input overload: 2,5 ÷30 mA Loop drop-out: max 2,5V ( 22mA) Display: 4 digits LCD 7 segments, h=12 mm Data storage: Flash memory Data retention time: 10 years Mounting: three fixing hole 3 mm ∅

OPERATIONDisplay setting: Zero, Full-scale and Decimal point Display limits: -1999÷9999 Working range: any within the display limits Decimal point setting: 0, 1, 2 or 3 decimals Reading function setting: filter, over-load limits, resolution Filter setting: mean value of 1 to 8 readings Refresh time: 0,25 ÷ 2 sec. according to filter setting Over-load limits: 3,6 ÷ 22 mA Resolution: 1 to 10 digits Calibration: zero (4 mA) and full-scale (20 mA)

PERFORMANCES Accuracy: 0,1% of working range, ± 1digit Temperature drift: 100 ppm/°C EMC: EN61000-6-4 and EN61000-6-2 with instrument correctly installed.

KEYBOARD

The configuration of parameters is done using three keys placed on the back or in front of instrument: the middle key (F) is the “Enter” function, while the lateral keys are “Increment” (↑) and “Decrement” (↓). The ↓ and ↑ keys pushed at the same time, make the "Escape" function. All configuration functions are supported by the display (see Table 1).

Key Function

F Access the configuration menu; menu scrolling; data storage.

↓ Digit decrement; parameter selection and/or setting

↑ Digit increment; parameter selection and/or setting

↑ + ↓ Escape

Push and hold for 3 seconds the F key to enter the configuration menu: the first configuration item, thedecimal point position [dP], will appear. Use the ↑ and ↓ keys for cycling among the items, while the F keypushed again, will lead to set the parameter. Changes are stored in non-volatile memory at the end ofconfiguration using the “F” key.

Note: in the following description, the display indication is marked between [ ] symbols.

Page 2/4____________________________________________________________________________________________________________

www.limathermcomponents.com, e-mail: [email protected]ł zakładowy: 2.050.000 PLN, NIP: 6342641389, REGON: 240666167,

KRS: 0000287965, Sąd Rejonowy Katowice-Wschód, Wydz. VIII Gospodarczy

Limatherm Components Sp. z o.o.ul. Żelazna 5, 41-506 Chorzów

tel.: 32 783 16 00, faks: 32 783 16 01

Page 3: E0028-MI01Eimg.iap.pl/s/466/205736/Edytor/Application_manual_ST0028.pdf · SPECIFICATIONS ELECTRICAL AND PHYSICAL Loop wiring: 2 terminal blocks max 1mm2 (AWG 16) Transmitter wiring:

CONFIGURATION ITEMS

Decimal point [dP]

Use ↑ and ↓ keys to select the decimal point position (from none to 3 decimals).

Default = 1 decimal

Engineering zero setting [ZerO] Use ↑ and ↓ keys to set the zero value ( -1999 to +9999 ). Default =0

Engineering full-scale setting [SPAn] Use ↑ and ↓ keys to set the full-scale value ( -1999 to +9999 ). Default = 100.0

Reading limits selection [Li]This item allows to select the display indication limits when the input goes out of 4÷20 mA range (under/overload). WithLi=0, the display indicate [OL] when the input is over 20 mA and [-OL] when under 4mA. With Li=1 the indication will be10% extended beyond the 4÷20 mA range. In both of case the [OL] [-OL] indications appears when the engineeringlimits are exceeded (-1999 +9999). Default = 0.

Filter setting [FiLt] Press ↑ key to increase or ↓ key to decrease the number of samples in the mean function on the input signal. Availablevalues goes from 1 to 8: Filt=1 sets no average and the display will be updated every 250 ms. Should spikes, noise orother disturbances be on input signal, increasing the filter value will lead the measure to be more stable; the displayupdate time will be increased. Updating time is 250 ms multiplied by the selected Filt number. Default = 1

Resolution [riS] Press ↑ key to increase or ↓ key to decrease the display resolution. Available values are 1, 2, 5 and 10; the numbermeans the minimum change between consecutive readings. Higher values should be used only when large engineering range are set or when the input signal is not steady. Default = 1

Transfer function [Lin] / [root] (*)Use ↑ and ↓ keys to select the transfer function for the visualization: Lin ( linear ) and root ( Square root ).Default = Lin

(*) Item available on demand

Table 2 : Configuration

Key FUNCTION DISPLAY

↑ or ↓

Decimal point settingEngineering zeroEngineering full-scaleOver-Load limitsInput filter settingResolution settingTransfer function

DP / 0.000ZerO / 0.000SPAn / 1.000

LI / 0FILt / 1RIS / 0

Lin / Root (*)

F Menu enter / Menu exit saving changes

↓Digit decrement 9 … 0

↑Digit increment 0 … 9

↑ + ↓Escape / Menu exit without saving

(*) Item available on demand

Page 3/4____________________________________________________________________________________________________________

www.limathermcomponents.com, e-mail: [email protected]ł zakładowy: 2.050.000 PLN, NIP: 6342641389, REGON: 240666167,

KRS: 0000287965, Sąd Rejonowy Katowice-Wschód, Wydz. VIII Gospodarczy

Limatherm Components Sp. z o.o.ul. Żelazna 5, 41-506 Chorzów

tel.: 32 783 16 00, faks: 32 783 16 01

Page 4: E0028-MI01Eimg.iap.pl/s/466/205736/Edytor/Application_manual_ST0028.pdf · SPECIFICATIONS ELECTRICAL AND PHYSICAL Loop wiring: 2 terminal blocks max 1mm2 (AWG 16) Transmitter wiring:

Other warnings for the installation. The input parameters of the equipment are defined on the following table; all parameters must be compatibles with other connected apparatus:

Ui [V] Ii [mA] Pi [W] Ci [nF] Li [mH]

30 100 1 20 0

ELECTRICAL CONNECTIONS

Page 4/4____________________________________________________________________________________________________________