Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Printed in U.S.A. Form MMY-AP2646FT9P-UL_01 Pg 1 8-16 Replaces: NEW Submittal Data Job Data _________________________________ Location _______________________________ Buyer ______________________ Buyer PO # ____________ Carrier # _____________________ Unit Number ________________________ Model Number ________________________________ Performance Data Certified By _______________________________Date ____________________ SHRMe VRF Heat Recovery Features 12 and 10-ton modules are com- bined to form a 22-ton system Capable of simultaneous cooling and heating (flow selector boxes required) Modules have 2 inverter-driven twin rotary compressors Backup capability due to multiple compressors Compressor speed varied in 0.1 Hz increments for comfort and effi- ciency Direct drive, inverter-driven 64-step outdoor motor Up to 3281 ft (1000 m) actual total system piping (liquid line) Up to 591 ft (180 m) actual piping length from outdoor unit to furthest fan coil Up to 330 ft (100 m) outdoor control wiring Up to 6560 ft (2000 m) control wiring between outdoor and indoor units Operating temperature range Cooling (db): 14 to 122 F (–10 to 50 C) Heating (wb): –13 to 60 F (–25 to 15.6 C) Protection: high pressure switch, low pressure sensor and switch, PC board fuse, inverter overload protec- tion 7-year compressor limited warranty, 5-year parts limited warranty Header Unit Model MMY-MAP1446FT9P-UL Follower Unit Model MMY-MAP1206FT9P-UL PERFORMANCE Nominal Cooling Capacity Btu/h 264,000 Nominal Heating Capacity Btu/h 297,000 Maximum Total Connected Indoor Unit Capacity Up to 150% SIMULTANEOUS COOLING AND HEATING EFFICIENCY* SCHE, Ducted FCUs 27.70 SCHE, Ductless FCUs 27.70 COOLING EFFICIENCY* EER/IEER, Ducted FCUs 11.40/22.50 EER/IEER, Ductless FCUs 11.20/23.80 HEATING EFFICIENCY* COP at 47 F, Ducted FCUs 3.50 COP at 47 F, Ductless FCUs 3.40 Fan Type (Qty) Propeller (3) Airflow, Standard Range CFM 10,852 + 7700 Combined System Sound Pressure, Cooling/Heating dBA 65.5/67.0 External Static Pressure† in. wg 0.16 ELECTRICAL Power Supply V/Ph/Hz 208-230/3/60 Minimum Circuit Amps (MCA)** A 52.1 + 45.4 Recommended Fuse Size** A 60 + 50 COMPRESSORS Type (Number) Inverter Twin Rotary (4) Motor Output kW 2 x 5.4 + 2 x 4.0 FAN MOTOR Motor Type (Steps) Inverter Direct Driven (64) Motor Output kW 1.0 + 1.0 + 1.0 PHYSICAL DATA Main Pipe Connection Size - Liquid (High Pressure)†† in. 7/8 (Flare) Main Pipe Connection Size - Gas (Low Pressure)†† in. 1-3/8 (Brazed) Main Discharge (High Pressure)†† in. 1-1/8 (Flare) Balance in. 3/8 (Flare) Refrigerant R-410A Factory Charge*** lb 2 x 24.3 External Finish Munsell 1Y8.5/0.5 Header Unit/Follower Unit Width in. 63.0 / 47.6 Header Unit/Follower Unit Height in. 72.9 / 72.9 Header Unit/Follower Unit Depth in. 30.7/ 30.7 Header Unit/Follower Unit Net Weight lb 838 + 684 REQUIRED ACCESSORY Connection Kit RBM-BT24FUL *Rated per AHRI (Air-Conditioning, Heating and Refrigeration Institute) 1230 Standard. Cooling: Indoor 80 F (35 C) db/67 F (27 C) wb; Outdoor 95 F (35 C) db Heating: Indoor 70 F (21 C) db; Outdoor 47 F (8 C) db/43 F (6 C) wb †Requires setting by DIP switches. **Separate power supply is required. MCA and fuse size for both units are given. ††Main pipe size leaving connection kit. ***Additional charges required. NOTE: Unit cabinet and coil slab shall be capable of withstanding 500-hour salt spray test in accordance with the ASTM (American Society for Testing and Mate- rials, U.S.A.) B-117 Standard. LEGEND db Dry Bulb COP Coefficient of Performance EER Energy Efficiency Ratio FCU Fan Coil Unit IEER Integrated Energy Efficiency Ratio SCHE Simultaneous Cooling and Heating Efficiency wb Wet Bulb SHRMe VRF Outdoor Unit MMY-AP2646FT9P-UL - Heat Recovery

Upload: others

Post on 19-May-2020

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: e VRF Outdoor Unit MMY-AP2646FT9P-UL - Heat Recovery€¦ · MMY-AP2646FT9P-UL MMY-MAP1446FT9P-UL MMY-MAP1206FT9P-UL 19.3"(490) or more 36.2"(920) 7.9"(200) or more 47.6"(1210) 8-0.6"×0.8"

SHRMe VRF Outdoor UnitMMY-AP2646FT9P-UL - Heat Recovery

Submittal DataJob Data _________________________________ Location_______________________________Buyer ______________________ Buyer PO # ____________ Carrier # _____________________Unit Number ________________________Model Number ________________________________Performance Data Certified By _______________________________Date____________________

SHRMe VRF Heat Recovery Features• 12 and 10-ton modules are com-

bined to form a 22-ton system• Capable of simultaneous cooling

and heating (flow selector boxesrequired)

• Modules have 2 inverter-driven twinrotary compressors

• Backup capability due to multiplecompressors

• Compressor speed varied in 0.1 Hzincrements for comfort and effi-ciency

• Direct drive, inverter-driven 64-stepoutdoor motor

• Up to 3281 ft (1000 m) actual totalsystem piping (liquid line)

• Up to 591 ft (180 m) actual pipinglength from outdoor unit to furthestfan coil

• Up to 330 ft (100 m) outdoor controlwiring

• Up to 6560 ft (2000 m) control wiringbetween outdoor and indoor units

• Operating temperature rangeCooling (db): 14 to 122 F (–10 to50 C)Heating (wb): –13 to 60 F (–25 to15.6 C)

• Protection: high pressure switch, lowpressure sensor and switch, PCboard fuse, inverter overload protec-tion

• 7-year compressor limited warranty,5-year parts limited warranty

Header Unit Model MMY-MAP1446FT9P-ULFollower Unit Model MMY-MAP1206FT9P-ULPERFORMANCE

Nominal Cooling Capacity Btu/h 264,000Nominal Heating Capacity Btu/h 297,000Maximum Total Connected Indoor Unit Capacity Up to 150%

SIMULTANEOUS COOLING AND HEATING EFFICIENCY*SCHE, Ducted FCUs 27.70SCHE, Ductless FCUs 27.70

COOLING EFFICIENCY*EER/IEER, Ducted FCUs 11.40/22.50EER/IEER, Ductless FCUs 11.20/23.80

HEATING EFFICIENCY*COP at 47 F, Ducted FCUs 3.50COP at 47 F, Ductless FCUs 3.40Fan Type (Qty) Propeller (3)Airflow, Standard Range CFM 10,852 + 7700Combined System Sound Pressure, Cooling/Heating dBA 65.5/67.0

External Static Pressure† in. wg 0.16ELECTRICAL

Power Supply V/Ph/Hz 208-230/3/60Minimum Circuit Amps (MCA)** A 52.1 + 45.4Recommended Fuse Size** A 60 + 50

COMPRESSORS

Type (Number) Inverter Twin Rotary (4)

Motor Output kW 2 x 5.4 + 2 x 4.0FAN MOTOR

Motor Type (Steps) Inverter Direct Driven (64)Motor Output kW 1.0 + 1.0 + 1.0

PHYSICAL DATAMain Pipe Connection Size - Liquid (High Pressure)†† in. 7/8 (Flare)

Main Pipe Connection Size - Gas (Low Pressure)†† in. 1-3/8 (Brazed)

Main Discharge (High Pressure)†† in. 1-1/8 (Flare)Balance in. 3/8 (Flare)Refrigerant R-410AFactory Charge*** lb 2 x 24.3External Finish Munsell 1Y8.5/0.5Header Unit/Follower Unit Width in. 63.0 / 47.6Header Unit/Follower Unit Height in. 72.9 / 72.9Header Unit/Follower Unit Depth in. 30.7/ 30.7Header Unit/Follower Unit Net Weight lb 838 + 684

REQUIRED ACCESSORYConnection Kit RBM-BT24FUL

*Rated per AHRI (Air-Conditioning, Heating and Refrigeration Institute) 1230 Standard. Cooling: Indoor 80 F (35 C) db/67 F (27 C) wb; Outdoor 95 F (35 C) db Heating: Indoor 70 F (21 C) db; Outdoor 47 F (8 C) db/43 F (6 C) wb†Requires setting by DIP switches.**Separate power supply is required. MCA and fuse size for both units are given.††Main pipe size leaving connection kit.***Additional charges required.NOTE: Unit cabinet and coil slab shall be capable of withstanding 500-hour salt spray test in accordance with the ASTM (American Society for Testing and Mate-rials, U.S.A.) B-117 Standard.

LEGEND

db — Dry BulbCOP — Coefficient of PerformanceEER — Energy Efficiency RatioFCU — Fan Coil UnitIEER — Integrated Energy Efficiency RatioSCHE — Simultaneous Cooling and Heating Efficiencywb — Wet Bulb

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Printed in U.S.A. Form MMY-AP2646FT9P-UL_01 Pg 1 8-16 Replaces: NEW

Page 2: e VRF Outdoor Unit MMY-AP2646FT9P-UL - Heat Recovery€¦ · MMY-AP2646FT9P-UL MMY-MAP1446FT9P-UL MMY-MAP1206FT9P-UL 19.3"(490) or more 36.2"(920) 7.9"(200) or more 47.6"(1210) 8-0.6"×0.8"

2

DIMENSIONAL DRAWINGOUTDOOR UNIT COMBINATION HEAT RECOVERY MMY-AP2646FT9P-UL

MODELOUTDOOR UNIT

HEADER UNIT FOLLOWER UNIT MMY-AP2646FT9P-UL MMY-MAP1446FT9P-UL MMY-MAP1206FT9P-UL

19.3"(490)or more 36.2"(920)

7.9"(200)or more 47.6"(1210)

8-0.6"×0.8"(8-15×20)(Long hole)

29.7

"(75

5)(A

ncho

r bol

t hol

e pi

tch)

30.7

"(78

0)31

.1"(

790)

(Incl

udin

g st

eady

leg)

(Anchor bolt hole pitch)

ab

ba

(Not

e 3)

( g

)

Front sideFront side Front side

Front side Front side

Front side Front side

Front sideFront sideFront side

Front side Front side

Space required for service

2

eF

h

aa e f e

d

c

eF

ab

a

eF

aa

(Not

e 3)

( g

)

(Anchor bolt hole pitch)51.6"(1310)

63.0"(1600)

4-0.6"×0.8"(4-15×20)

(For additional strength)(Long hole)

3.3"

(85)

27.0

"(68

6.5)

62.8

"(15

95)

72.9

"(18

50)

2.0"

(50)

2.0"

(50)

1

59.1"(1500)

Two units connected

39.4"(1000)

70.1"(1780)119.3"(3030)d

hg

e

31.5"(800)

0.4"(10)

cba _

23.6"(600)19.7"(500)>

>__>>__>

>_>_

7.9"(200)>_f

NOTES: 1. If there is an obstacle at the upper side of the outdoor unit, set the top end of the outdoor unit 78.7 in. (2000 mm) apart from the obstacle. 2. Limit the height of the obstacle surrounding the outdoor unit to 31.5 in. (800 mm) or less from the bottom end of the outdoor unit. 3. Draw out the pipe procured locally to the front of the outdoor unit horizontally,and keep 19.7 in. (500 mm) or more between the outdoor unit and traversing pipe if placing pipe

(Header unit ① ≥ Follower unit ②)

transversely. 4. Arrange each outdoor unit in order of its capacity.

5. Dimensional drawing of corrosion protection and corrosion heavy protection model is the same as that of standard model. 6. Dimensions are in inches (mm).

Page 3: e VRF Outdoor Unit MMY-AP2646FT9P-UL - Heat Recovery€¦ · MMY-AP2646FT9P-UL MMY-MAP1446FT9P-UL MMY-MAP1206FT9P-UL 19.3"(490) or more 36.2"(920) 7.9"(200) or more 47.6"(1210) 8-0.6"×0.8"

DIMENSIONAL DRAWING OUTDOOR UNIT HEAT RECOVERY/SINGLE UNIT MMY-MAP1446FT9P-UL

6.3"

(160

.2)

8.7"

(220

)

(*1)Cutting position of L-shape pipe

3.0"(75)(*1)

(*1)

568

3.7"(94)4.5"(115)

10.3"(261)

Holes for piping/wiring

5.9"

(150

)

8.5"

(215

)4.

6"(1

17.5

)

(Anchor bolt hole pitch)51.6"(1310)

63.0"(1600)

4-0.6"×0.8"(4-15×20)

29.7

"(75

5)(A

ncho

r bol

t hol

e pi

tch)

30.7

"(78

0)31

.1"(

790)

(Incl

udin

g st

eady

leg)

4-0.6"×0.8"(4-15×20)

(Long hole)

(For additional strength)(Long hole)

3.3"

(85)

27.0

"(68

6.5)

62.8

"(15

95)

72.9

"(18

50)

2.0"

(50)

2.0"

(50)

28.3"(720)

910

a 19.7"(500)b 23.6"(600)

de

63.8"(1620)0.4"(10)

c 70.1"(1780)

hg

31.5"(800)39.4"(1000)

>_

>

>__>__>

>__>

Front sideFront side

Front side

Front sideFront side

Front side(For work and service)

Space required for service

e e

(Note 2)

c

aa

d

h

(Not

e 3)

ab

a(

g )

ab

ba

(Not

e 3)

( g

)

Foundation

(Anchor bolt hole pitch)59.1"(1500)

2.4"

(60)

3.9"

(100

)

29.7

"(75

5)(A

ncho

r bol

t hol

e pi

tch)

Mounting surfaceof bottom plate

Foundation2.4"

(60)

3.9"

(100

)

26.4

"(67

0)

24.0

"(61

0)

51.6"(1310)

2.9"

(73)

5.4"

(136

)

3.8"

(97) 3.2"(82)

5.8"(148)

3.1"(79)

7.3"(186)

9.6"(243)

4.8"(122)

11.7"(298)

4.6"

(116

)

5.6"

(143

)

4.3"

(108

)

2.4"

(57)

3.0"

(75)

7.9"

(200

)8.

6"(2

19)

10.2

"(25

9)1

2

3

4

Holes for piping/wiring(Plan view)

4

7

321

outdoor unit, set the top end of the outdoor1. If there is an obstacle at the upper side of theNOTES:

unit 78.7 in. (2000 mm) apart from the obstacle.2. Limit the height of the obstacle surrounding the

outdoor unit to 31.5 in. (800 mm) or less from the bottom end of the outdoor unit.

3. Draw out the pipe procured locally to the front of the outdoor unit horizontally,and keep 19.7 in. (500 mm) or more between the outdoor unit and traversing pipe if placing pipe transversely.

Suction gas pipe connection portDischarge gas pipe connection portLiquid pipe connection port

Parts nameA

1-1/8"(28.6)

RemarksNo1

Balance pipe connection port

Knockout hole for power wiring 2Knockout hole for power wiring 1

B

3/8"(9.5)

1.7"(43.7)

1.1"(27)

234567

Knockout hole for control wiring8Square hole (for freight handling) 4-2.4"×7.9"(4-60×200)9Square hole (for hanging) 4-1.6"×2.2"(4-40×55)10

Knockout hole for power wiring 2 1.9"(48)

0.9"(22.2)

Model NameMAP 1446 typeMAP 1686 type

5/8"(15.9)3/4"(19.1)

A1"(25.4)

1-1/8"(28.6)

B

4. Dimensions are in inches (mm).

3

Page 4: e VRF Outdoor Unit MMY-AP2646FT9P-UL - Heat Recovery€¦ · MMY-AP2646FT9P-UL MMY-MAP1446FT9P-UL MMY-MAP1206FT9P-UL 19.3"(490) or more 36.2"(920) 7.9"(200) or more 47.6"(1210) 8-0.6"×0.8"

© Carrier Corporation 2016

DIMENSIONAL DRAWING OUTDOOR UNIT HEAT RECOVERY/SINGLE UNIT MMY-MAP1206FT9P-UL

6.3"

(160

.2)

8.7"

(220

)

(*1)Cutting position of L-shape pipe

3.0"(75)(*1)

(*1) 568

3.7"(94)4.5"(115)

10.3"(261)

Holes for piping/wiring

5.9"

(150

)

8.5"

(215

)4.

6"(1

17.5

)

Holes for piping/wiring

(Anchor bolt hole pitch)36.2"(920)

47.6"(1210)

4-0.6"×0.8"(4-15×20)(Long hole)

29.7

"(75

5)(A

ncho

r bol

t hol

e pi

tch)

30.7

"(78

0)31

.1"(

790)

(Incl

udin

g st

eady

leg)

24.4"(620)

3.0"

(75)

7.9"

(200

)8.

6"(2

19)

3.3"

(85)

910

27.0

"(68

6.5)

62.8

"(15

95)

72.9

"(18

50)

2.0"

(50)

2.0"

(50)

1

2

3

a 19.7"(500)b 23.6"(600)

de

48.4"(1230)0.4"(10)

c 70.1"(1780)

hg

31.5"(800)39.4"(1000)

>_

>

>__>__>

>__>

24.0

"(61

0)

29.7

"(75

5)

26.4

"(67

0)

(Anc

hor b

olt h

ole

pitc

h)

Mounting surfaceof bottom plate

Foundation

Foundation

(Anchor bolt hole pitch)36.2"(920)

2.4"

(60)

2.4"

(60)

3.9"

(100

)3.

9"(1

00)

Front sideFront side

Front sideFront side

Front side

Front side

(Note 2)

ab

ba

(Not

e 3)

( g

)

(Not

e 3)

ab

a(

g )

c

d

aa

Space required for service

e e

h

2.9"

(73)

5.4"

(136

)

3.8"

(96) 3.2"(82)

5.8"(148)

3.1"(79)

7.3"(186)

9.6"(243)

4.8"(122)

11.7"(298)

4.6"

(116

)

5.6"

(143

)

4.3"

(108

)

2.2"

(57)

10.2

"(25

9)

4

321

4

7

outdoor unit, set the top end of the outdoor1. If there is an obstacle at the upper side of theNOTES:

unit 78.7 in. (2000 mm) apart from the obstacle.2. Limit the height of the obstacle surrounding the

outdoor unit to 31.5 in. (800 mm) or less from the bottom end of the outdoor unit.

3. Draw out the pipe procured locally to the front of the outdoor unit horizontally,and keep 19.7 in. (500 mm) or more between the outdoor unit and traversing pipe if placing pipe transversely.

Suction gas pipe connection portDischarge gas pipe connection portLiquid pipe connection port

Parts name1/2"(12.7)

A

RemarksNo1

Balance pipe connection port

Knockout hole for power wiring 2Knockout hole for power wiring 1

3/4"(19.1)

3/8"(9.5)

1.7"(43.7)

1.1"(27)

234567

Knockout hole for control wiring8Square hole (for freight handling) 4-2.4"×7.9"(4-60×200)9Square hole (for hanging) 4-1.6"×2.2"(4-40×55)10

Knockout hole for power wiring 2 1.9"(48)

0.9"(22.2)

Model NameMAP 0966 typeMAP 1206 type

1/2"(12.7)5/8"(15.9)

A

4. Dimensions are in inches (mm).

Variable Refrigerant Flow (VRF) Multi-Split AC and HPAHRI Standard 1230

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Printed in U.S.A. Form MMY-AP2646FT9P-UL_01 Pg 4 8-16 Replaces: NEW