e-001 electrical legend and abbreviations e ...- 01/23/17bid set this document is released on...
TRANSCRIPT
DIMMITT ISDIMPROVEMENTS - PHASE 2HIGH SCHOOL AND MIDDLE
SCHOOL SECURITYIMPROVEMENTS
VOLUME IV
DIMMITT, TEXASCASTRO COUNTY
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
AMARILLO 7966.16
-
01/23/17 BID SET
THIS DOCUMENT IS RELEASED ON 12/23/2016
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
THIS DOCUMENT IS RELEASED ON 12/23/2016
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
RE
G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
S
T
A
T
E
OF
T
E
X
A
S
19104
P
A
U
L
S.
H
A
R
E
01/23/17
COVER SHEETAND INDEX
G-001SET NUMBER:
SHEET INDEX
VOLUME I - SITE & LANDSCAPE
VOLUME II - ELEMENTARY SCHOOL
VOLUME III - EARLY CHILDHOOD CENTER
VOLUME IV - SECURITY IMPROVEMENTS
GENERALG-001 COVER SHEET AND INDEX
G-002SYMBOLS, LEGENDS & ABBREVIATIONS
G-003 ACCESSIBILITY STANDARDS
G-004 ACCESSIBILITY STANDARDS
ARCHITECTURALA-101 SECURITY PLAN - HIGH SCHOOL
A-102 SECURITY PLAN - MIDDLE SCHOOL
A-401 SECURITY PLAN - MIDDLE SCHOOL - ENLARGED PLANS AND DETAILS
MECHANICALM-101 MIDDLE SCHOOL MECHANICAL PLANS
ELECTRICALE-001 ELECTRICAL LEGEND AND ABBREVIATIONS
E-101 SECURITY PLAN - HIGH SCHOOL
E-102 SECURITY PLAN - MIDDLE SCHOOL
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
AMARILLO 7966.16
-
01/23/17 BID SET
THIS DOCUMENT IS RELEASED ON 12/23/2016
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
THIS DOCUMENT IS RELEASED ON 12/23/2016
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
RE
G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
S
T
A
T
E
OF
T
E
X
A
S
19104
P
A
U
L
S.
H
A
R
E
01/23/17
SYMBOLS, LEGENDS& ABBREVIATIONS
G-002
AA00
CL
99.6
99.6
X X
320.10 TC
319.60 G
319.60
+TC
+G
+FL
WP
A
x
3
1
9
.
6
0
DS
FD
RD
OD
CJ
S
MCJ
GENERAL DRAWING LEGEND FLOOR PLAN LEGENDSITE PLAN LEGEND ROOF PLAN LEGEND RCP LEGEND DETAIL LEGENDABBREVIATIONS
SD
SHEET TYPE DESIGNATORS
AANNNSHEET IDENTIFICATION FORMAT
0 GENERAL (COVER SHEETS, INDEX, SYMBOLS LEGEND, NOTES, ETC.)
1 PLANS (HORIZONTAL VIEWS)
2 ELEVATIONS (VERTICAL VIEWS)
3 SECTIONS (SECTIONAL VIEWS)
4 LARGE SCALE VIEWS (ENLARGED PLANS, ELEVATIONS, OR SECTIONS
THAT ARE NOT DETAILS)
5 DETAILS
6 SCHEDULES AND DIAGRAMS
7 USER DEFINED (FOR TYPES THAT DO NOT FALL IN OTHER CATEGORIES
OR STANDARD DETAILS)
8 USER DEFINED (FOR TYPES THAT DO NOT FALL IN OTHER CATEGORIES)
9 3D REPRESENTATIONS (ISOMETRICS, PERSPECTIVES, PHOTOGRAPHS)
SHEET TYPE
DESIGNATOR
(SEE BELOW)
DISCIPLINE
DESIGNATOR
SHEET SEQUENCE
NUMBER
ROOM NAME
ROOM NUMBER
DOOR NUMBER
WINDOW MARK
EQUIPMENT
LOUVER MARK
HOLLOW METAL FRAME
MARK
ALUMINUM FRAME MARK
KEY NOTE
KEY NOTE-DEMOLITION
PARTITION TYPE
DISPLAY BOARD
REVISION
STRUCTURAL COLUMN
LINE
DATUM ELEVATION
(EXISTING)
DATUM ELEVATION
(NEW)
BREAK LINE
CENTER LINE
SHEET NUMBER WHERE REFERENCED
REFERENCE NUMBER
DRAWING BLOCK TITLE
PLAN DETAIL MARK
SECTION MARK
ELEVATION MARK
NORTH ARROW
NORTH ARROW FOR
SITE PLANS
EXISTING DOOR
NEW DOOR
MATCH/DIVIDE LINE
PROPERTY LINE
EXISTING
CONSTRUCTION TO
REMAIN
EXISTING
CONSTRUCTION TO BE
REMOVED
PROPERTY LINE
FENCE
NEW ASPHALT PAVING
NEW CONCRETE
WALK/PAVING
NEW CONTROL JOINT
NEW EXPANSION JOINT
NEW CONTOUR LINES
EXISTING CONTOUR
LINES TO REMAIN
NEW SPOT ELEVATION
EXISTING SPOT
ELEVATION
TOP OF CURB
GUTTER
FLOW LINE
WORKING POINT
ACCESSIBLE PARKING
SIGN
PARKING SIGN
LIGHT POLE
TREE
SLOPE
FLOOR DRAIN
DOWN SPOUT
FURNITURE/EQUIPMENT
NIC
FIRE EXTINGUISHER AND
BRACKET
FIRE EXTINGUISHER AND
CABINET
HANDRAIL
WALL GUARD
END WALL GUARD
CORNER GUARD
WIRE MESH OR FABRIC
PARTITION
GLAZING SYSTEM
NEW PARTIAL HEIGHT
WALLS
NEW METAL STUD
WALLS
EXISTING
CONSTRUCTION TO BE
REMOVED
EXISTING
CONSTRUCTION TO
REMAIN
MASONRY CONTROL
JOINT
CMU WALL
FACE BRICK
CONCRETE WALL ROOF DRAIN
OVERFLOW DRAIN
SLOPE
MECHANICAL
EQUIPMENT
VENT THROUGH ROOF
(VTR)
SKYLIGHT
ROOF HATCH
SMOKE DETECTOR
ACCESS PANEL
SPEAKER
CONTROL JOINT
CEILING TRACK
SKYLIGHT
LIGHT FIXTURES
EXIT LIGHTS
RETURN AIR OR
EXHAUST GRILLE
SUPPLY AIR GRILLE
LAY-IN CEILING PANEL
LAY-IN CEILING PANEL
SUSPENDED METAL
LATH AND PLASTER
CEILING
GYP BD CEILING COMPACTED SOIL
UNDISTURBED SOIL
STONE/MARBLE
PLASTER OR STUCCO
ON METAL LATH
STEEL
CONCRETE IN SECTION
BRICK
CMU
BATT INSULATION
ACOUSTICAL TILE
RIGID INSULATION
WOOD CONTINUOUS
WOOD DISCONTINUOUS
PLASTER, SAND OR
CEMENT GROUT
POUROUS FILL, GRAVEL
(CAPILLARY WATER
BARRIER PAVEMENT BASE)
TERRAZZO (IN SECTION)
ROOM NAME
000
000
00
00
LV00
HM00
AL00
00
00
00
0
NORTH
N
A1/G-001
A1/G-001
A1/G-001
/
A1
TITLE
1/8"=1'-0"
FEB
FEC
A
ACC ACCESSIBLE
AB ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADDL ADDITIONAL
ADJ ADJUSTABLE
ADDM ADDENDUM
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF ARCHITECTS
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATE
ARCH ARCHITECT
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASTM AMERICAN SOCIETY OF TESTING MATERIALS
AUTO AUTOMATIC
AVG AVERAGE
AWG AMERICAN WIRE GAGE
AWS AMERICAN WELDING SOCIETY
A/C AIR CONDITIONING
B
BAL BALANCE
BC BACK OF CURB
BIA BRICK INSTITUTE OF AMERICA
BITUM BITUMINOUS
BL BUILDING LINE
BLDG BUILDING
BM BENCH MARK
BOCA BUILDING OFFICIALS AND CODE ADMINISTRATORS
INTERNATIONAL, INC
BOS BOTTOM OF STEEL
BOT BOTTOM (BOTTOM FACE, LAYER, SIDE)
B PL BASE PLATE
BRDG BRIDGING
BRG BEARING
BTWN BETWEEN
BUR BUILT-UP ROOFING
C
C AMERICAN STANDARD CHANNEL (STRUCTURAL
SHAPE)
CU FT CUBIC FOOT
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CG CORNER GUARD
CI CAST IRON
CIR CIRCLE
CIRC CIRCULAR
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLR CLEAR
cm CENTIMETER
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECT
CONSTR CONSTRUCTION
CONT CONTINUE
CONTR CONTRACTOR
CRCMF CIRCUMFERENCE
CSK COUNTER SUNK
CSI CONSTRUCTION SPECIFICATIONS INSTITUTE
CTR CENTER
CU YD CUBIC YARD
D
D DEPTH
DAT DATUM
DBL DOUBLE
DDS DOUBLE DISPLAY STRIP
DEG DEGREE
DEMO DEMOLISH
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIV DIVIDE
DL DEAD LOAD
DS DOWNSPOUT
DWG DRAWING
E
E EAST, MODULUS OF ELASTICITY
EA EACH
EF EACH FACE, EXTERIOR FINISH
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ENGR ENGINEER
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPANSION
EXP BT EXPANSION BOLT
EXT EXTERIOR
F
FD FLOOR DRAIN
FDTN FOUNDATION
FEB FIRE EXTINGUISHER & BRACKET
FEC FIRE EXTINGUISHER & CABINET
FF EL FINISH FLOOR ELEVATION
FIN FLR FINISH FLOOR
FIN FINISH(ED)
FOC FACE OF CONCRETE, FACE OF CURB
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FOW FACE OF WALL
FS FAR SIDE (FACE, LAYER)
FT FOOT
FTG FOOTING
FURG FURRING
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GOVT GOVERNMENT
GYP BD GYPSUM BOARD
GYP GYPSUM
H
HDBD HARDBOARD
HDWD HARDWOOD
HDW HARDWARE
HEX HEXAGON(AL)
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HEAT PUMP
HS HIGH STRENGTH
HT HEIGHT
HVAC HEATING VENTILATION AND AIR CONDITIONING
I
I MOMENT OF INERTIA
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
IF INSIDE FACE
INCL INCLUDE(D)(ING)(SIVE)
INS INSULATION
INT INTERIOR
INV INVERT(ED)
J
JAN JANITOR
L
l LITER
L ANGLE (STRUCTURAL SHAPE)
LB POUND
LH LEFT HAND
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LIGHT
LT WT LIGHT WEIGHT
M
MAU MAKE UP AIR UNIT(S)
m METER(S)
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MCJ MASONRY CONTROL JOINT
MECH MECHANIC(AL)
MFG MANUFACTURING
MFR MANUFACTURER
MIL STD MILITARY STANDARD
MIN MINIMUM
MISC MISCELLANEOUS
mm MILLIMETER
MO MASONRY OPENING
MOD MODIFY
MT METAL THRESHOLD
MTL METAL
MLWK MILLWORK
N
N NORTH
NA NOT APPLICABLE
NAT NATURAL
NBS NATIONAL BUREAU OF STANDARDS
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NS NEAR SIDE (FACE)
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFD OVER FLOW DRAIN
OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED/OWNER INSTALLED
OH DR OVERHEAD DOOR
OPNG OPENING
OPH OPPOSITE HAND
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
Oz OUNCE
P
PAR PARALLEL
PCA PORTLAND CEMENT ASSOCIATION
PCF POUNDS PER CUBIC FOOT
PCI PRESTRESSED CONCRETE INSTITUTE
PERF PERFORATE(D)
PERP PERPENDICULAR
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLF POUNDS PER LINEAL FOOT
PR PAIR
PREFAB PREFABRICATE
PREFIN PREFINISH
PRELIM PRELIMINARY
PROJ PROJECT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PBD PARTICLE BOARD
PTD PAPER TOWEL DISPENSER
PTDWR PAPER TOWEL DISPENSER & WASTE RECEPTACLE
PVC POLYVINYL CHLORIDE
PLYWD PLYWOOD
PVG PAVING
Q
QC QUALITY CONTROL
QTY QUANTITY
R
R RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFERENCE
REFL REFLECT
REINF REINFORCE
REQD REQUIRED
REV REVISION
RH RIGHT HAND(ED)
RO ROUGH OPENING
ROW RIGHT OF WAY
RTU ROOF TOP UNIT
S
S SOUTH
SBCCI SOUTHERN BUILDING CODE CONGRESS
INTERNATIONAL
SCHED SCHEDULE
SD SOAP DISPENSER
SDI STEEL DOOR INSTITUTE
SECT SECTION
SHT SHEET
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SPEC SPECIFICATION
SP SOLID PLASTIC
SST STAINLESS STEEL
STD STANDARD
STL STEEL
STRUCT STRUCTURAL
SUSP SUSPENDED
SYMM SYMMETRICAL
T
THD TREAD
TAN TANGENT
TEMP TEMPORARY
TFF TOP OF FINISH FLOOR
THK THICKNESS
TLT TOILET
TMH TOP OF MANHOLE
TOB TOP OF BEAM
TOC TOP OF CURB
TOF TOP OF FOOTING
TOG TOP OF GRADE
TOJ TOP OF JOIST
TOL TOLERANCE
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TTD TOILET TISSUE DISPENSER
TRANS TRANSPARENT
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
T&G TONGUE AND GROOVE
U
UBC UNIFORM BUILDING CODE
UL UNDERWRITERS LABORATORIES, INC.
ULT ULTIMATE
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
V
VAR VARIES
VERT VERTICAL
W
W WEST
WLD WELDED
WP WORK POINT
WWF WELDED WIRE FABRIC
W/ WITH
W/O WITHOUT
W/W WALL TO WALL
X
XFMR TRANSFORMER
DB00
A0
PLAN NORTH ARROW
PLAN NORTH
TRUE NORTH
FURNISHINGS
1/4
1
2
1/2
60" MIN
60
M
IN
30
MIN
24
MIN
12
MIN
30
MIN
12
MIN
60 MIN
48 MIN
30
MIN
FORWARD
PARALLEL
48
M
IN
30 MIN
30
M
IN
48 MIN
36 MIN
X >
2
4
60 MIN
X >
1
5
ELEVATION
TOE CLEARANCE
PLAN
CENTERED
30
M
IN
6 MAX
17-25
ELEVATION
KNEE CLEARANCE
8 MIN
9"
MIN
11 MIN
27
M
IN
4 MAX
X ≥ 80
X >
2
7
X <
8
0"
27
"
MA
X
48
M
AX
15
MIN
20
MAX
48
M
AX
44
M
AX
2O-25
MAX
10 MAX
48
M
AX
15
MIN
34
M
AX
10 MAX
48
M
AX
34
M
AX
>10-24
MAX
46
M
AX
24
MAX 48 MIN
24
MAX
32
M
IN
36
M
IN
32
M
IN
36
M
IN
Y
48
M
IN
X
42 MIN
X
42 MIN
X<48
CLEAR FLOOR AREA/ACCESSIBLE ROUTE
ALCOVE
FORWARD
ALCOVE
PARALLEL
180 DEG
TURN AROUND
NARROW
PASSAGE
SINGLE
WHEELCHAIR
T-SHAPE
TURN AROUND
CIRCLE
TURN AROUND
BEVELED TRANSITION
VERTICAL TRANSITION
PROTRUDING
OBJECT
UNDER STAIRS
FORWARD REACH RANGES SIDE REACH RANGES
PROTRUDING OBJECT PROTECTION/REACH RANGES
5 M
AX
15
M
IN
BACK WALL
BACK WALL
LENGTH
30
M
IN
30
M
IN
12 MIN
CO
NT
RO
L
EN
D W
AL
L
24
M
IN
12 MAX 24 MAX24 MIN
12
M
IN
24
M
IN
12 MAX
15 MAX
12 MAX15 MAX12 MAX
24 MAX24 MIN
REMOVABLE SEAT CONTROLS LOCATION FIXED SEAT
REMOVABLE SEAT FIXED SEAT
CO
NT
RO
L
WA
LL
BACK
SE
AT
WA
LL
36
36
36
M
IN
48 MIN
SE
AT
60 MIN
30
M
IN
30
M
IN
36
36 MIN
60 MIN60 MIN
30
M
IN
30
M
IN
6 M
AX
6 MAX6 MAX
6 M
AX
6 MAX
6 MAX
6 M
AX
6 M
AX
6 MAX
TRANSFER SHOWER ROLL-IN SHOWER ROLL-IN SHOWER
W/ SEAT ROLL-IN SHOWER
W/ SEAT
ALTERNATE
38
M
IN
48
M
AX
15 MAX
BACK
WALL
CONTROL WALL
WITHOUT SEAT
CONTROL WALL
WITH SEAT
48
M
AX
27 MAX
48
M
AX
SHOWERS
8-1
0
17
-1
9
8-1
0
17
-1
9
17
-1
9
SHOWER SEAT
48
M
IN
33 MIN 33 MIN
60
M
IN
33 MIN 33 MIN
BENCH SEATING
THEATER SEATING
30
M
IN
24
M
IN
BENCH SEATING
THEATER SEATING
ASSEMBLY SEATING
LINE OF SIGHT
LINE OF SIGHT
SPORTS ARENA
THEATER/PLAYHOUSE
AUDITORIUM/CONCERT HALL
LECTURE HALLS
MEETING ROOMS
OF TUB
CO
NT
RO
L E
ND
W
AL
L
HE
AD
E
ND
W
AL
L
LENGTH
OF TUB
WA
LL
/P
OS
T M
TD
CA
NT
IL
EV
ER
ED
UN
IT
FORWARD APPROACH
ACCESSIBLE UNIT
56
M
IN
59
M
IN
60 MIN60 MIN
4 MAX
42
M
IN
6 M
IN
6 MIN
42
M
IN
60
M
IN
35-37
ANY AMOUNT
X ≥ 80
X <
2
7
PROTRUDING
OBJECT
URINALS
NOTE:
WIDE SIDE
LEVER ON
36 MIN
TYPICAL WATER CLOSETS
33
-3
6
250 LBS AND BE CONTINUOUS
GRAB BARS MUST SUPPORT
EWC/DRINKING FOUNTAINS
DOWN TO 27" AFF MIN
APRON THAT EXTENDS
HIGH UNIT SHOULD HAVE
15 MIN
CL
BRACKET MOUNTED
FIRE EXTINGUISHER
48
48
* CHALKBOARD MOUNTING
* MARKERBOARD MOUNTING
36
M
AX
9
ROOM
FIRE ALARM
AUDIBLE &
ACCESSIBLE
COAT HOOKS
VISUAL SIGNAL
60
M
AX
OUTLET
15
M
IN
80
-9
6
48
M
AX
2 FROM
DOOR FRAME
48
M
AX
* TACKBOARD MOUNTING
CABINET
FIRE EXTINGUISHER
TOWELS
48
M
AX
MISC MOUNTING (DIMENSIONS SHOWN ARE TO THE HIGHEST OPERABLE PART)
STANDARD ACCESSIBLE MOUNTING HEIGHTS
TELEPHONE
THERMOSTAT
TOWELS
SWITCH
OUTLET
CUPS
SOAP
TO
P O
F E
XT
IN
GU
IS
HE
R
IN
SID
E O
F C
AB
IN
ET
TO
P O
F T
RA
Y
6
FIN CLG
IF CEILING IS BELOW 90"
MOUNT TOP OF SIGNAL DEVICE
6" BELOW FINISHED CEILING
NOTE:
17 MIN
EQUIPMENT PERMITTED
IN OUTLINED AREA
36
M
AX
28
-3
4
38
M
AX
2 M
AX
WASHING MACHINE
TOP LOAD
CONVEYOR
GROCERY
SLIDE
TRAYACCESSIBLE
COAT HOOKS
AMBULATORY ACCESSIBLE TOE CLEARANCE SIDE APPROACH WALL HUNG WATER CLOSET FLOOR MTD WATER CLOSET
TYPICAL TOILET STALLS
CL
HE
AD
E
ND
(REQUIRED) (REQUIRED)
WA
LL
TUBS
CL
PUSH SIDE
48
M
IN
NOTE:
PULL SIDE
18 MIN
60
M
IN
X
FRONT APPROACHES SWINGING DOORS
HAS BOTH A CLOSER AND A LATCH
X = 12" MIN (305mm) IF DOOR
PUSH SIDE
Y
42
M
IN
PUSH SIDE
NOTE:
A CLOSER
PULL SIDE
A CLOSER
Y = 54" MIN (1370mm) IF DOOR HAS
NOTE:
PULL SIDE
NOTE: X = 36" MIN IF Y = 60";
X = 42" MIN IF Y = 54"
X
Y
Y
42
M
IN
HINGE SIDE APPROACHES SWINGING DOORS
LATCH SIDE APPROACHES SWINGING DOORS
Y = 48" MIN (1220mm) IF DOOR
22 MIN
HAS BOTH A CLOSER AND A LATCH
Y = 48" MIN IF DOOR HAS
Y
48
M
IN
24 MIN24 MIN
NOTE:
VESTIBULE DOORS
TWO HINGED DOORS IN SERIES
NOTE:
THE CLEARANCES FOR FRONT APPROACHES
ALL DOORS IN ALCOVES SHALL COMPLY WITH
TYPICAL DOOR CLEARANCES
48 MIN
4
8
M
I
N
VESTIBULE DOORS
32 MIN
CLEAR
43
M
AX
34
M
IN
60
M
IN
18 MIN
X>
8
48
M
IN
12 MIN
X>
8
48
M
IN
RECESSED DOOR
DOOR HARDWARE DOOR LITE
CLOSER & LATCH PROVIDED
WALL
CL
14-17
20-25
18
40
LOW
HIGH
REACH RANGES
RAMPS AND STAIRS
TOP OF HANDRAIL GRIPPING SURFACE
WATER CLOSETS
GRAB BARS
DISPENSER HEIGHT
36
20
28 MAX
18-20
14
READING AND STUDY AREAS, AND
KNEE CLEARANCE
HEIGHT OF TABLES OR COUNTERS
FIXED OR BUILT-IN SEATING AND TABLES,
WORK STATIONS
24 MIN
26-30 MAX
AGES: 3 AND 4
CHILDREN'S MOUNTING
GENERAL NOTES
ACCESSIBILITY GUIDELINE SHEETS ARE BASED ON
THE 2012 TEXAS ACCESSIBILITY STANDARDS (TAS).
ACCESSIBILITY GUIDELINE SHEETS ARE FOR
INFORMATIONAL PURPOSES ONLY. AND INTENDED
TO SERVE AS A GUIDE FOR CONSTRUCTION
PROFESSIONALS AND OWNERS.
SOME OF THE INFORMATION AND PICTOGRAPHS
SHOWN MAY NOT BE APPLICABLE TO THIS PROJECT.
REFER TO PLUMBING SHEETS FOR PLUMBING
FIXTURE MOUNTING HEIGHTS.
GRAPHICS SHOWN ARE FOR ADULTS.
HEIGHTS & REACH RANGES
AGES: 5 THROUGH 8
17-19
25-27
16
44
AGES: 9 THROUGH 12
WATER CLOSET CENTERLINE 12-1512 15-18
48
M
AX
27 MAX
17-19
CL
16-18
CL
16-18
CL
16-18
CL
16-18
CL
60 MIN
CLEARANCE AT WATER CLOSET
16-18
CL
56
M
IN
LAVATORY, URINAL
OR TOILET ACCESSORIES
NOT IN A STALL
12
MIN
24 MIN
15 MIN
CL
36
36
TO
S
HO
UL
DE
R
IF Y=60 MIN, X=36 MIN
33
-3
6
LINE OF SIGHT OVER HEADS
CL
FRONT LOAD
15
-3
6
IF A WALL HUNG OR FLOOR
MOUNTED FLUSH VALVE
WATER CLOSET IS SPECIFIED,
ENSURE ALL DIMENSIONS
SHOWN ARE MET.
APPROACH ALLOWED
PARALLEL
AGES: 5 & YOUNGER AGES: 6-12
EXAMPLE SIGNAGE - SEE STANDARD ACCESSIBLE MOUNTING HEIGHT
LETTERS & BRAILLE
GRAPHIC SYMBOLS
6x8 PICTOGRAM
6 M
IN
MEN
6x8 PICTOGRAM
GRAPHIC SYMBOLS
LETTERS & BRAILLE
6 M
IN
WOMEN
& BRAILLE
ROOM NUMBER
8x6 ROOM NAME
6 M
IN
129
SUPERVISOR
MAINTENANCE
& BRAILLE
10x3 ROOM NAME
ADMINISTRATION
6x6 DIRECTIONAL
GRAPHIC SYMBOL
ONLY ONLY
GRAPHIC SYMBOL
6x6 DIRECTIONAL
6 M
IN
& BRAILLE
6x6 CHANGEABLE
MESSAGE W/ PERMANENT
ROOM NAME, NUMBER,
ITHJOHN S
OFFICE
169
REFER TO SIGNAGE PACKAGE OR DETAILS FOR ACTUAL SIGNAGE SPECIFIED
6x8 PICTOGRAM
GRAPHIC SYMBOLS
LETTERS & BRAILLE
6 M
IN
STAIR 1
6x8 PICTOGRAM
GRAPHIC SYMBOLS
LETTERS & BRAILLE
6 M
IN
STAIR 1
48
M
IN
60
M
AX
6
0 M
AX
48
M
IN
6 M
IN
6
0 M
AX
48
M
IN
60
M
AX
48
M
IN
CL
DISPENSERS
36 MAX
12
MAX
54 MIN
42 MIN
33
-3
6
TO
P O
F G
RIP
PIN
G
SU
RF
AC
E
7-9
48
M
AX
15
M
IN
100
48
M
IN
15
MIN
CL
30
MIN
X
36
MIN
IF X>24
15
MIN
CL
36
MIN
IF X>24
X
CL
LAVATORIES
36
MIN
IF X>24
X
REFER TO KNEE AND
TOE CLEARANCE GRAPHICS
CL
36 MIN
30
IF X ≤ 24
X
15
MIN
CL
NOT ASSOCIATED
24 MIN
9"
MIN
15
MIN
CL
WITH A WATER CLOSET
ONLY TOILET
ASSOCIATED WITH
WATER CLOSETS ARE
ALLOWED WITHIN
FLOOR AREA
ACCESSORIES
28 MAX 28 MAX
CHANGES IN LEVELNOTE: REFER TO "CHANGES IN LEVEL" DETAILS FOR SHOWER THRESHOLDS
THRESHOLD
SEAT
SEAT
THRESHOLD THRESHOLD
1
2
1/4
VERTICAL/BEVELED
1/4
TRANSITION
43
M
AX
43
M
AX
48
M
AX
LIT
E
OP
EN
IN
G
ACCESSIBILITYSTANDARDS
G-003
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
AMARILLO 7966.16
-
01/23/17 BID SET
THIS DOCUMENT IS RELEASED ON 1/22/2017
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
THIS DOCUMENT IS RELEASED ON 1/22/2017
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
RE
G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
S
T
A
T
E
OF
T
E
X
A
S
19104
P
A
U
L
S.
H
A
R
E
01/23/17
DIRECTION
HANDRAILS
LANDING
RAMP
LANDING
60 MINSLOPE 1:12 MAX
EDGE PROTECTION CURB/BARRIER OR 12" EXTENDED
HANDRAILS REQUIRED ON BOTH SIDES OF RAMP
RAMP WIDTH TO BE NO LESS THAN 36" BETWEEN
RAMP CROSS SLOPE NOT TO EXCEED 2% MAX
LANDING SLOPE NOT TO EXCEED 2% IN ANY
SURFACE REQUIRED ON BOTH SIDES OF
ACCESSIBLE RAMP
60 MIN
RAMP RUN LANDINGLANDING
LANDING
RAMP RUN
RAMP RUN
EXTENDED
SURFACE
CURB OR
BARRIER
1
1
OFF-CENTERED DOOR
RAISED OR FLUSH
1 2
ENTRY LEVEL
DOOR OPEN
ALARM
DOOR CLOSE
EMERGENCY
1 2
43
5 6
7 8
CAR FLOOR
HE
IG
HT
W
IT
HIN
RE
AC
H R
AN
GE
8
3
1
4
2
7
5
8
6
1
3
2
4
5
7
6
8
8 1
12
PUSH FOR HELP
EMERGENCY
PHONE
PLATFORM
LIF
T M
EC
HA
NIS
M
42 MIN
54
M
IN
32 MIN
32 MIN
42
M
IN
(NEW CONSTRUCTION)
60 MIN
36 MIN
60
M
IN
80 MIN
51
M
IN
54
M
IN
42 MIN
80
M
IN
36 MIN 36 MIN
54
M
IN
51
M
IN
68 MIN
54 MIN
DOOR SAFETY BEAMS HALL LANTERNS HALL CONTROLS
48
M
AX
72
29
5
INSIDE CAB
FLOOR DESIGNATION
BESIDE DOOR ABOVE DOOR EMERGENCY
COMMUNICATION
DEVICE
48
M
AX
OUTSIDE CAB
60
2
35
M
IN
3/4 MIN
2 1
/2
M
IN
2 1
/2
M
IN
CAR CONTROL DETAILS
ELEVATORS
ELEVATORS
60 MIN 60 MIN 60 MIN
60
M
IN
36 MIN
BETWEEN
HANDRAILS
36
M
IN
BE
TW
EE
N
HA
ND
RA
IL
S
12 MIN12 MIN
X<
4
27
M
AX
34
-3
8
34
-3
8
36 MIN
SECTION
TOP & BOTTOM
OF RAMP
12 MIN
MAIN
CENTERED DOOR
CL
CL
STOP
ACCESSIBLE PARKING SIGNAGE
DOMINANT DIRECTION
OF TRAVEL
LONG DIRECTION
PERPENDICULAR TO
DOMINANT DIRECTION
OF TRAVEL
1/2 MAX
80
M
IN
X>12
X>12
27
M
AX
12MAX
27
-8
0
12 MAX
20
1 1
12
ADJOINING
SURFACE
MAX SLOPE
CURB RAMP
MAX SLOPE
CURB RAMP AT ISLANDCUT THROUGH AT ISLAND
OVERHANG
POST
OVERHANG
SIGNS
GRATING
36 MIN
48
M
IN
36 MIN
60 MIN
96
M
IN
CURB OR
ROADWAY
EDGE
BUS
STOP
PAD
SHELTER
ACCESSIBLE
ROUTE
96 MIN
(8'-0")
5'-0
"
MIN
FULL LENGTH OF
VEHICLE PULL-UP SPACE
20'-0" MIN
PERPENDICULAR SIDEWALK PARALLEL SIDEWALK
W/ IN-LINE CURB RAMP W/ PARALLEL CURB RAMP
PERPENDICULAR SIDEWALK
W/ FLARED CURB RAMP
NON-WALKING
SURFACE
NON-WALKING
SURFACE
PERPENDICULAR SIDEWALK
W/ LONGITUDINAL CURB RAMP
NON-WALKING
SURFACE
NON-WALKING SURFACE
17
-1
9
20-24
42
M
IN
2 M
AX
PLAN
10
M
AX
20
M
AX
PARALLEL
APPROACH
60 MIN
(5'-0")
132 MIN
(11'-0")
FIN GRADE
5'-0" ABOVE
CAR
PARKING SPACESPASSENGER LOADING ZONE
ACCESSIBLE ROUTE FROM PARKING
CURB RAMPS AT MARKED CROSSINGS
X
ISLAND CUT THROUGH
LEVEL WITH STREET
ISLAND
CURB RAMP WITHIN
MARKED CROSSING
4
8
M
I
N
X
FLARED SIDES
1:12 MAX IF
X IS < 36"
ISLAND
X
24
MIN
STRAIGHT
SEGMENT WITHIN
CROSS WALK
24
MIN
STRAIGHT
SEGMENT
WITHIN
CROSS WALK
ISLAND
4
8
M
I
N
NON-WALKING
SURFACE
NON-WALKING
SURFACE
WELL DEFINED
EDGE
3
6
M
I
N
WITHIN CURB RAMP AND FLARES, THERE SHALL BE NO LIGHT OR SIGNAL
POLES, SIGNAL BOXES, VALVE BOX COVERS, OR THE LIKE
(A) (B)
(C) (D)
CURB RAMP AND ADJOINING SURFACE SLOPES
CURB RAMPS
PROTRUDING OBJECTS/TELEPHONES
PROTRUDING OBJECTS
PASSING
60
M
IN
36
M
IN
ACCESSIBLE PATH WIDTH
SINGLE
FORWARD
APPROACH
12 MAX
27
-8
0
OVERHANG
POST
TELEPHONES
ACCESSIBLE ROUTES
ACCESSIBLE SEATING
30 MIN
48
MIN
ACCESSIBLE PATH
OF TRAVEL
60 MIN
96
M
IN
CURB OR
ROADWAY
EDGE
BUS
STOP
PAD
48
30
36
ACCESSIBLE
ROUTE
36
BUS STOPS
36
MIN
36
MIN
36
MIN
36
MIN
36
MIN
CURB RAMP
CURB RAMP CONFIGURATION MAY VARY
36
MIN
3
6
M
I
N
3
6
M
I
N
36
MIN
60 MIN60 MIN
ACCESSIBLE ROUTE
2% MAX SLOPE
ENLARGED PLAN
ENLARGED PLAN
ENLARGED PLAN
ENLARGED PLAN
CURB RAMP WITHIN
MARKED CROSSING
CURB RAMP
MARKED
CROSSING
CURB RAMP
MARKED
CROSSING
1:12 MAX IF
X IS < 36
ISLAND CUT THROUGH
LEVEL WITH STREET
12
MAX
12
MAX
TYPICAL
FLARED SIDES
1:12 MAX IF
X IS < 36"
2 1/2
MAX
2.35
2.3
5
0.9
0.2
4
MA
X
4
MAX
4
MAX
DETAIL
36
MIN
1:1
2 S
LO
PE
M
AX
BOTTOM OF RAMP SURFACE
DETECTABLE WARNING
DEVICES SHALL COMPLY
WITH THE TEXAS
ACCESSIBILITY STANDARDS
AND BE ALIGNED IN THE
DIRECTION OF
PEDESTRIAN TRAVEL
THE SURFACE OF THE
DETECTABLE WARNING
DEVICES SHALL BE A
CONTRASTING COLOR
THAT PROVIDES A LIGHT
REFLECTIVE VALUE
SIGNIFICANTLY
CONTRASTING WITH THE
ADJACENT SURFACES
FLARED SIDES
24
MIN
1:10
MAX
SLOPE
EACH SIDE
CHANGE IN DIRECTION
SLOPED SURFACE WHERE VERT EDGE IS > 8"
AT
L
EA
ST
A
S
WID
E A
S T
HE
WID
ES
T R
AM
P R
UN
STRAIGHT
OR
18
MIN
51
M
IN
36 MIN
51 MIN
LULA LIFTS
DOOR FRAME
(ABOVE CAR CONTROL PANEL)
24
MIN
8'-0
"
MIN
VAN
PARKING SPACES AND ACCESS AISLE
SLOPE NOT TO EXCEED 2% IN ANY DIRECTION
ACCESSIBILITYSTANDARDS
G-004
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
AMARILLO 7966.16
-
01/23/17 BID SET
THIS DOCUMENT IS RELEASED ON 1/22/2017
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
THIS DOCUMENT IS RELEASED ON 1/22/2017
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
RE
G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
S
T
A
T
E
OF
T
E
X
A
S
19104
P
A
U
L
S.
H
A
R
E
01/23/17
A1
SECURITY PLAN - HIGH SCHOOL
1/16"=1'-0"
1
AS INDICATED BY: 00
KEY NOTES
1. EXISTING HIGH SCHOOL TO REMAIN.
2. NEW DOOR, ADD ACCESS CONTROL (CARD READER) TO DOOR, REFER TO
ELECTRICAL
3. REMOVE EXISTING GLAZING AND REPLACE WITH SECURITY GLAZING,
REFER TO DETAILS.
4. USE EXISTING DOOR, ADD DOOR CONTACTS, REFER TO ELECTRICAL.
VESTIBULE
101
101B101A
2
3
2
VESTIBULE
102
VESTIBULE
103
4
VESTIBULE
104
4
VESTIBULE
105
4
2
VESTIBULE
106
2
VESTIBULE
107
2
VESTIBULE
108
AL01
102
103
104
105
106
107
108
NORTH
GENERAL NOTES
A. ANY ERRORS, INCONSISTENCIES OR OMISSIONS DISCOVERED BY THE
CONTRACTOR SHALL BE REPORTED PROMPTLY TO THE ARCHITECT OR
ENGINEER AS REQUEST FOR INFORMATION.
B. CONTRACTORS SHALL NOT SCALE THESE DRAWINGS FOR CONSTRUCTION
PURPOSES. IN THE EVENT OF OMISSION OF NECESSARY DIMENSIONS, THE
CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER.
C. VERIFY ALL DIMENSIONS, CONDITIONS AND GRADES AT JOB SITE PRIOR TO
COMMENCING WORK.
D. ALL WORK SHALL COMPLY WITH FEDERAL, STATE AND LOCAL BUILDING CODES
AND REGULATIONS.
E. CONTRACTOR SHALL COORDINATE AND OBTAIN ALL BUILDING PERMITS
REQUIRED FOR CONSTRUCTION AND CERTIFICATES OF OCCUPANCY.
F. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL ASPECTS OF SAFETY
DURING BUILDING CONSTRUCTION AND SHALL PROVIDE ADEQUATE SHORING
AND BRACING TO ENSURE SUCH SAFETY.
G. DURING CONSTRUCTION, AND PRIOR TO THE INCORPORATION OF ANY
CHANGES, REVISIONS, MODIFICATIONS AND/OR DEVIATIONS FROM THE
CONSTRUCTION DOCUMENTS, CONTRACTOR SHALL BRING TO THE ATTENTION
OF THE ARCHITECT AND OBTAIN APPROVAL FROM THE GOVERNING BUILDING
OFFICIAL BEFORE PROCEEDING WITH THE WORK.
H. ALL MATERIALS SHALL BE INSTALLED PER MANUFACTURER'S
INSTRUCTIONS/SPECIFICATIONS.
I. CONTRACTOR SHALL COORDINATE AND SCHEDULE WITH OWNER ALL WORK.
2
VESTIBULE
109
102
* = SIMILAR
X=EXISTING
7
M1, M2, G22
6
-
SILL
REMARKS
-
5
-
HEAD
4
FRAME
3
EXISTING
CONST
EXISTING
SIZE
-
JAMB
DETAILS
2
D
TYPE
1
PR SIZE
DOOR
1
FLR
101A
MARK
DOOR SCHEDULE
CONST
FOOTNOTES
REMOVE EXISTING GLAZING AND REPLACE WITH SECURITY GLAZING=M2
= VERIFY EXISTING OPENINGM1
MISCELLANEOUS (GENERAL NOTES)
=
=HM
ALUM
1
HOLLOW METAL FRAME PROFILE & ADDITIONAL INFORMATION.
IHMPF = INSULATED HOLLOW METAL, PAINT FINISH
DOOR SIZE INDICATED IS NOMINAL. REDUCTION SHALL BE MADE FOR
ALUMINUM
OPENING SIZE (INDICATED IN FT-IN, WxH)
THRESHOLD & EDGE CLEARANCES. ALL DOORS ARE 1 3/4" THICK,
REFER TO STANDARD DOOR DETAILS (THIS SHEET) FOR TYPICAL
SIZE INDICATED IS OVERALL FRAME DEPTH.
5 FRAME SIZE (INDICATED IN INCHES)
3 CONSTRUCTION/VENEER
2 DOOR TYPE
REFER TO DOOR TYPE SCHEDULE (THIS SHEET)
FRAME TYPE4
HOLLOW METAL, PAINT FINISH
DETAILS6
EXAMPLE:
DETAIL # A1/A-501 SHEET #
7 REMARKS
UNLESS INDICATED OTHERWISE.
3-0x7-0
00A
HM02HM01
NOTE: FRAME FACES ARE 2" UNO
RE
F D
OO
R S
CH
ED
RE
F D
OO
R S
CH
ED
RE
F D
OO
R S
CH
ED
RE
F D
OO
R S
CH
ED
REF DOOR
SCHED
DC
REF DOOR
SCHED
3'-6"
AF
F
2'-8
"
10" 10"10"9"
2'-8
"3'-6"
AF
F
REF DOOR
SCHED
BA
RE
F D
OO
R S
CH
ED
REF DOOR
SCHED
DOOR TYPE SCHEDULE
4"
REF DOOR
SCHED
REF DOOR
SCHED
RE
F D
OO
R S
CH
ED
HOLLOW METAL FRAME SCHEDULE
LF
LF
HM00
10
"
M1, M2, G22
---
EXISTING EXISTING
-
D1 101B 3-0x7-0
M1, M3
---
IHMPF EXISTING
-
D1 102 3-0x7-0
6'-0" FIELD VERIFY 6'-0" FIELD VERIFY 6'-0" FIELD VERIFY
7'-0
" F
ILE
D V
ER
IF
Y
EXISTING
GLAZING TO
REMAIN
EXISTING
GLAZING TO
REMAIN
EXISTING
GLAZING TO
REMAIN
2'-10
"1'-10
"1'-10
"
ADD ACCESS CONTROLS, REFER TO ELECTRICAL=M3
M1, M4
---
EXISTING EXISTING
-
D1 103 3-0x7-0
PROVIDE NEW DOOR WITH DOOR CONTACTS, REFER TO ELECTRICAL=M4
M1, M4
---
EXISTING EXISTING
-
D1 104 3-0x7-0
M1, M4
---
EXISTING EXISTING
-
D1 105 3-0x7-0
M1, M3
---
IHMPF EXISTING
-
D1 106 3-0x7-0
----
M1, M3
---
IHMPF EXISTING
-
D1 107 3-0x7-0
----
M1, M3, G18
---
IHMPF EXISTING
-
C1 108 3-0x7-0
----
MARK TYPE
G18 LOW-E COATED, TEMPERED INSULATING GLASS UNITS
G22
CLEAR FULLY TEMPERED GLASSG07
GLAZING SCHEDULE
SECURITY GLASS
----
M1, M3, G18
---
IHMPF EXISTING
-
B1 109 3-0x7-0
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
AMARILLO 7966.16
-
01/23/17 BID SET
THIS DOCUMENT IS RELEASED ON 12/23/2016
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
THIS DOCUMENT IS RELEASED ON 12/23/2016
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
RE
G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
S
T
A
T
E
OF
T
E
X
A
S
19104
P
A
U
L
S.
H
A
R
E
01/23/17
SECURITY PLANHIGH SCHOOL
A-101
A1
SECURITY PLAN - MIDDLE SCHOOL
1/16"=1'-0"
1
AS INDICATED BY: 00
KEY NOTES
1. EXISTING MIDDLE SCHOOL TO REMAIN.
2. NEW DOOR, ADD ACCESS CONTROL (CARD READER) TO DOOR, REFER TO
ELECTRICAL
3. USE EXISTING DOOR, ADD DOOR CONTACTS, REFER TO ELECTRICAL.
VESTIBULE
101
101B
101A
AL01
NORTH
GENERAL NOTES
A. ANY ERRORS, INCONSISTENCIES OR OMISSIONS DISCOVERED BY THE
CONTRACTOR SHALL BE REPORTED PROMPTLY TO THE ARCHITECT OR
ENGINEER AS REQUEST FOR INFORMATION.
B. CONTRACTORS SHALL NOT SCALE THESE DRAWINGS FOR CONSTRUCTION
PURPOSES. IN THE EVENT OF OMISSION OF NECESSARY DIMENSIONS, THE
CONTRACTOR SHALL NOTIFY THE ARCHITECT OR ENGINEER.
C. VERIFY ALL DIMENSIONS, CONDITIONS AND GRADES AT JOB SITE PRIOR TO
COMMENCING WORK.
D. ALL WORK SHALL COMPLY WITH FEDERAL, STATE AND LOCAL BUILDING CODES
AND REGULATIONS.
E. CONTRACTOR SHALL COORDINATE AND OBTAIN ALL BUILDING PERMITS
REQUIRED FOR CONSTRUCTION AND CERTIFICATES OF OCCUPANCY.
F. CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL ASPECTS OF SAFETY
DURING BUILDING CONSTRUCTION AND SHALL PROVIDE ADEQUATE SHORING
AND BRACING TO ENSURE SUCH SAFETY.
G. DURING CONSTRUCTION, AND PRIOR TO THE INCORPORATION OF ANY
CHANGES, REVISIONS, MODIFICATIONS AND/OR DEVIATIONS FROM THE
CONSTRUCTION DOCUMENTS, CONTRACTOR SHALL BRING TO THE ATTENTION
OF THE ARCHITECT AND OBTAIN APPROVAL FROM THE GOVERNING BUILDING
OFFICIAL BEFORE PROCEEDING WITH THE WORK.
H. ALL MATERIALS SHALL BE INSTALLED PER MANUFACTURER'S
INSTRUCTIONS/SPECIFICATIONS.
I. CONTRACTOR SHALL COORDINATE AND SCHEDULE WITH OWNER ALL WORK.
101C
101D
102
103
WAIT
102
PRINC
103
OFFICE
104
VESTIBULE
105
105
3
106
106A
ENTRY
106
GYM
107
107A3
107B 2
108A 2
109A 3
ENTRY
108
CAFETERIA
109
109B3
108B
110 2
KITCHEN
110
ENTRY
112
112 2
LIBRARY
111
1113
ENTRY
113
113
2
CHOIR
114
114
3
115
3
BAND
115
ENTRY
116
116
3
ENTRY
117
117
2
104
2
DOOR NOTES
A. CONTRACTOR SHALL FIELD VERIFY ALL DOOR AND FRAME SIZES PRIOR TO
ORDERING OR INSTALLATION. ANY ERRORS, INCONSTANCIES OR OMISSIONS
DISCOVERED BY THE CONTRACTOR SHALL BE REPORTED PROMPTLY TO THE
ARCHITECT AS A REQUEST FOR INFORMATION. ERRORS AND/OR OMISSIONS IN
DOOR SCHEDULES DO NOT RELIEVE THE CONTRACTOR FROM EXECUTING
WORK SHOWN ON DRAWINGS OR DESCRIBED IN SPECIFICATIONS.
B. DOOR AND FRAME SUPPLIER SHALL COORDINATE INSTALLATION WITH
CONTRACTOR. SUPPLIER SHALL VERIFY DEPTHS OF FRAMES PER
INSTALLATION TECHNIQUE (BEFORE OR AFTER DRYWALL).
C. ALL HARDWARE SHALL COMPLY WITH ALL APPLICABLE CODE REQUIREMENTS
AND ADA ACCESSIBILITY REQUIREMENTS PER LOCAL, STATE & FEDERAL
REGULATIONS. REFER TO SPECIFICATIONS FOR HARDWARE ALLOWANCE AND
REQUIREMENTS.
D. EXTERIOR DOORS TO HAVE A MAXIMUM OF 8.5 LBS. 'PUSH/PULL' PRESSURE.
E. INTERIOR DOORS TO HAVE MAXIMUM OF 5.0 LBS. 'PUSH/PULL' PRESSURE.
F. ALL STEEL DOORS, DOOR FRAMES SHALL BE RATED ACCORDINGLY TO WALL
OR DOOR RATINGS (VERIFY WITH CONSTRUCTION DOCUMENTS).
G. TEMPERED GLAZING AND IDENTIFICATION SHALL BE PROVIDED BY GLAZING
SUPPLIER AND TO MEET ALL LOCAL, STATE AND FEDERAL REGULATIONS.
* = SIMILAR
X=EXISTING
7
M1, M5, G22
6
-
SILL
REMARKS
-
5
-
HEAD
4
FRAME
3
ALUM
CONST
AL01
SIZE
-
JAMB
DETAILS
2
E
TYPE
1
PR SIZE
DOOR
1
FLR
101A
MARK
DOOR SCHEDULE
CONST
FOOTNOTES
PROVIDE HINGES, SILENCERS AND LOCKSET=M2
= VERIFY EXISTING OPENINGM1
MISCELLANEOUS (GENERAL NOTES)
=
=HM
ALUM
1
HOLLOW METAL FRAME PROFILE & ADDITIONAL INFORMATION.
IHMPF = INSULATED HOLLOW METAL, PAINT FINISH
DOOR SIZE INDICATED IS NOMINAL. REDUCTION SHALL BE MADE FOR
ALUMINUM
OPENING SIZE (INDICATED IN FT-IN, WxH)
THRESHOLD & EDGE CLEARANCES. ALL DOORS ARE 1 3/4" THICK,
REFER TO STANDARD DOOR DETAILS (THIS SHEET) FOR TYPICAL
SIZE INDICATED IS OVERALL FRAME DEPTH.
5 FRAME SIZE (INDICATED IN INCHES)
3 CONSTRUCTION/VENEER
2 DOOR TYPE
REFER TO DOOR TYPE SCHEDULE (THIS SHEET)
FRAME TYPE4
HOLLOW METAL, PAINT FINISH
DETAILS6
EXAMPLE:
DETAIL # A1/A-501 SHEET #
7 REMARKS
UNLESS INDICATED OTHERWISE.
3-0x7-0
00A
HM02HM01
NOTE: FRAME FACES ARE 2" UNO
RE
F D
OO
R S
CH
ED
4"
REF DOOR
SCHED
REF DOOR
SCHED
RE
F D
OO
R S
CH
ED
HOLLOW METAL FRAME SCHEDULE
HM00
M1, M5, G22
---
ALUM AL01
-
E1 101B 3-0x7-0
PROVIDE NEW DOOR, ADD ACCESS CONTROLS, REFER TO ELECTRICAL=M3
M1, M4
---
EXISTING EXISTING
-
A1 105 3-0x7-0
USE EXISTING DOOR, ADD DOOR CONTACTS, REFER TO ELECTRICAL=M4
MARK TYPE
G18 LOW-E COATED, TEMPERED INSULATING GLASS UNITS
G22
CLEAR FULLY TEMPERED GLASSG07
GLAZING SCHEDULE
SECURITY GLASS
M1, M5, G22
---
ALUM AL01
-
E1 101C 3-0x7-0
M1, M5, G22
-
D4/A-401E4/A-401ALUM HM02 F.V.E1 101D 3-0x7-0
EXISTING TO REMAIN
---
EXISTING EXISTING
-
EXISTING1 102
-
EXISTING TO REMAIN
---
EXISTING EXISTING
-
EXISTING1 104
-
M2
-
D6/A-401E6/A-401SCPL HM 5 7/8"A1 103 3-0x7-0
=SCPL SOLID CORE, PLASTIC LAMINATED
M1, M3, G18
---
IHMPF EXISTING
-
E1 106 3-0x7-0
M1
---- - -
F1 106A
-
M1, M4
---
EXISTING EXISTING
-
A1 107A 3-0x7-0
M1, M3
---
IHMPF EXISTING
-
A1 107B 3-0x7-0
M1, M3, G18
---
IHMPF EXISTING
-
E1 108A 3-0x7-0
M1
---- - -
F108B
-
1
M1, M4
---
EXISTING EXISTING
-
E1 109A 4-0x7-0
M1, M3, G18
---
IHMPF EXISTING
-
C1 110 3-6x7-0
M1, M4
---
EXISITNG EXISTING
-
D1 109B 3-0x7-0
M1, M4
---
EXISTING EXISTING
-
A1 111 3-0x7-0
M1, M3, G18
---
IHMPF EXISTING
-
E1 112 3-0x7-0
M1, M3, G18
---
IHMPF EXISTING
-
E1 113 3-0x7-0
M1, M4
---
EXISTING EXISTING
-
A1 114 3-0x7-0
M1, M4
---
EXISTING EXISTING
-
A1 115 3-0x7-0
M1, M4
---
EXISTING EXISTING
-
A1 116 3-0x7-0
M1, M3, G18
---
ALUM EXISTING
-
D1 117 3-0x7-0
2"
6'-10"
2"
1'-8"
2"
9'-0" V
ER
IF
Y - M
AT
CH
E
XIS
TIN
G
HE
AD
ER
W
ALL
51'-5 3/8" FIELD VERIFY
2" 3'-7 3/8" 2" 6'-0" 2" 2" 6'-0" 2" 2" 6'-0" 2" 3'-0" 2"4'-0" 2" 4'-0" 2" 4'-0" 4'-3" 2" 4'-4" 2" 4'-3"
7'-0"
4"
7'-4"
2" 3'-0" 2"
3'-4"
RE
F D
OO
R S
CH
ED
RE
F D
OO
R S
CH
ED
RE
F D
OO
R S
CH
ED
REF DOOR
SCHED
DC
REF DOOR
SCHED
3'-6"
AF
F
2'-8"
10" 10"10"9"
2'-8"
3'-6"
AF
F
REF DOOR
SCHED
BA
RE
F D
OO
R S
CH
ED
REF DOOR
SCHED
DOOR TYPE SCHEDULE
LF
LF
OH COILING GATE
F
REF DOOR SCHED
RE
F D
OO
R S
CH
ED
HOOD
A6/A-401
B6
/A
-4
01
C6/A
-401
A6/A-401
C6/A
-401
BASIS OF DESING: KAWNEER 451,
COLOR: TO MATCH EXISTING
C6
/A
-4
01 S
IM
.
C6
/A
-4
01 S
IM
.
7'-0" F
IE
LD
V
ER
IF
Y
REF DOOR
SCHED
E
1'-6
"
1'-4
"6"
1'-4
"6"
1'-4
"6
"
6" 2'-0" 6"
NOTE: FIELD VERIFY ALL DOOR OPENING SIZES.
DOOR AND FRAME COLOR TO MATCH EXISTING=M5
1'-6
"
1'-4
"6"
3'-2"
6"
6" 2'-0" 6"
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
AMARILLO 7966.16
-
01/23/17 BID SET
THIS DOCUMENT IS RELEASED ON 12/23/2016
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
THIS DOCUMENT IS RELEASED ON 12/23/2016
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
RE
G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
S
T
A
T
E
OF
T
E
X
A
S
19104
P
A
U
L
S.
H
A
R
E
01/23/17
SECURITY PLANMIDDLE SCHOOL
A-102
A1
MIDDLE SCHOOL - DEMOLITION FLOOR PLAN
1/8"=1'-0"
AS INDICATED BY:
DEMOLITION KEY NOTES
1. DOOR AND FRAME.
2. WALL PARTITION.
3. MILLWORK.
4. CMU PARTITION.
5. CEILING GRID AND TILES.
6. FLOORING.
NORTH
1
0
DEMOLITION GENERAL NOTES
A. CONTRACTOR SHALL PATCH ALL SURFACES AFFECTED BY THIS WORK.
PATCH AND FINISH TO MATCH ADJACENT SURFACES WHICH REMAIN. ALL
ABANDONED MECHANICAL, ELECTRICAL OR PLUMBING WORK SHALL BE
REMOVED AND PATCHED.
B. THE GENERAL CONTRACTOR IS NOT RESPONSIBLE FOR REMOVAL OF
HAZARDOUS MATERIAL (I.E. ASBESTOS). IF ANY HAZARDOUS MATERIALS
ARE DISCOVERED, STOP WORK AND NOTIFY THE OWNER IMMEDIATELY.
C. ALL WORK SHALL CONFORM TO THE CODES AND REQUIREMENTS OF
EVERY REGULATORY AGENCY HAVING JURISDICTIONS OVER THE
PROJECT.
D. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME COMPLETELY
FAMILIAR WITH ALL EXISTING CONDITIONS IN THE AREA OF CONSTRUCTION
PRIOR TO SUBMITTING PRICES AND STARTING WORK. ALL ELEVATIONS,
DIMENSIONS, EXISTING SERVICES SHALL BE FIELD VERIFIED. IN THE
EVENT OF CONFLICT, CONTACT THE ARCHTIECT/OWNER AND OBTAIN
INSTRUCTIONS BEFORE PROCEEDING WITH THE WORK.
E. NEITHER THE OWNER, ARCHITECT OR THE ENGINEER OF RECORD WILL
ENFORCE SAFETY MEASURES OR REGULATION. THE CONTRACTOR SHALL
DESIGN, CONSTRUCT AND MAINTAIN ALL SAFETY DEVICES, INCLUDING
SHORING, AND SHALL BE SOLELY RESPONSIBLE FOR CONFIRMING TO ALL
LOCAL, STATE AND FEDERAL SAFETY AND HEALTH STANDARDS, LAW AND
REGULATION.
F. ALL EXISTING CONSTRUCTION TO BE REMOVED SHOWN DASHED (TYPICAL).
G. CONTRACTOR TO TEMPORARILY REMOVE ALL LIGHTING, MECHANICAL
EQUIPMENT, DUCT WORK, REGISTERS, GRILLES AND OTHER PLENUM OR
CEILING MOUNTED FIXTURES AND EQUIPMENT DURING CONSTRUCTION.
RELOCATE ITEMS AFTER NEW CEILING GRID AND TILES ARE INSTALLED.
LEGEND
NOT IN SCOPE OF WORK
2
2
3
4
1'-4"
3'-4"
5
6
5
6
5
6
1
B1
MIDDLE SCHOOL - FLOOR PLAN
1/8"=1'-0"
NORTH
VESTIBULE
101
WAIT
102
PRINC
103
OFFICE
104
AS INDICATED BY: 00
FLOOR PLAN KEY NOTES
1. INTERIOR WALL PARTITION.
2. DOOR AS SCHEDULED.
3. MILLWORK, REFER TO DETAILS.
4. CORNER GUARD, REFER TO DETAILS.
ALIGN
FLOOR PLAN GENERAL NOTES
A. INTERIOR WALL PARTITIONS SHALL BE 3 5/8" METAL STUDS WITH 5/8"
GYPSUM BOARD ON BOTH SIDES. TERMINATE STUDS 12" ABOVE FINISHED
CEILING (BRACE TO STRUCTURE AS REQUIRED) AND GYPSUM BOARD 6"
ABOVE FINISHED CEILING. CAVITY SHALL BE FILLED WITH SOUND BATT
INSULATION.
B. VERIFY ALL INTERIOR FINISHES, COLORS, ETC. WITH OWNER.
1
1
2
3
17'-0" 4 7/8" 9'-10 7/16" F.V.
11'-7 1/2"
4 7/8"
A5/A
-401
B5/A
-401
51'-5 3/8" FIELD VERIFY
7'-8"± F.V.
25'-9 1/2" F
.V
.
30'-4 3/16" F.V.
10'-9"
4
C1
MIDDLE SCHOOL - REFLECTED CEILING PLAN
1/8"=1'-0"
NORTH
FINISHED CEILING
108'-0"
FINISHED CEILING
108'-0"
AS INDICATED BY: 00
CEILING PLAN KEY NOTES
1. 2 X2 CEILING TILES IN NEW GRID.
2. HEADER WALL, REFER TO DETAILS.
3. EXISTING CEILING TO REMAIN. PATCH EXISTING CEILING AS REQUIRED.
2
1
1
3
3
3
3
3
3
3 3
CEILING PLAN GENERAL NOTES
A. CONTRACTOR TO NOTIFY ARCHITECT IMMEDIATELY OF FIELD CONFLICTS
BETWEEN CEILING MOUNTED ITEMS.
B. REFLECTED CEILING PLAN DEFINES TYPES OF CEILING AND SOFFIT
PATTERNS, REFERENCE ELECTRICAL DRAWINGS FOR QUANTITIES AND
TYPES OF LIGHT FIXTURES.
C. REFER TO FLOOR PLAN FOR ROOM DIMENSIONS AND FINISHES.
A5
INTERIOR ELEVATION
1/4"=1'-0"
B5
INTERIOR ELEVATION
1/4"=1'-0"
E1
/A
-4
01
E1
/A
-4
01
E2
/A
-4
01
E2
/A
-4
01
E3
/A
-4
01
3'-6
"
2'-6
"
2'-6
"
3'-6
"
2'-0" 5'-3 3/4" 2'-0"
KNEE
SPACE
E3
/A
-4
01
5'-0"
5'-0"
D6
JAMB DETAIL -
INTERIOR DOOR (3 5/8" STUD)
1 1/2"=1'-0"
5/8"3 5/8" 5/8"
4 7/8"
5 7/8"
5/8" GYP. BD. (BOTH SIDES)
DOOR PER SCHEDULE
STEEL FRAME (TYPICAL)
DOUBLE 3 5/8" METAL STUDS
(TYPICAL)
METAL STUD ANCHORS AS
REQUIRED (TYPICAL)
E6
HEAD DETAIL -
INTERIOR DOOR (3 5/8" STUD)
1 1/2"=1'-0"
5/8"3 5/8"
5/8"
4 7/8"
5 7/8"
5/8" GYP. BD. (BOTH SIDES)
DOOR PER SCHEDULE
STEEL FRAME (TYPICAL)
3 5/8" METAL STUDS (TYPICAL)
T.O. FRAME
PER SCHEDULE
NOTE:
CONTRACTOR SHALL PROVIDE
'FIXED FLOOR ANCHORS' AT ALL
INTERIOR DOOR JAMBS.
DOUBLE BOX HEADER
B6
SILL DETAIL - GLAZING
1 1/2"=1'-0" EXISTING FOUNDATION
4 1/2"
GLASS AS SCHEDULED
ALUMINUM FRAME
BACKER ROD AND SEALANT,
BOTH SIDES OF FRAME
SHIM AS REQUIRED
A6
JAMB DETAIL - GLAZING
1 1/2"=1'-0" EXISTING WALL
EXISTING WALL
4 1/2"
GLASS AS SCHEDULED
ALUMINUM FRAME
BACKER ROD AND SEALANT,
BOTH SIDES OF FRAME
SHIM AS REQUIRED
EXISTING FOUNDATION
3 1/2"
CEILING
FLOOR
BA
SE
H
T.
OV
ER
AL
L H
T. - R
EF
ER
T
O D
RA
WIN
GS
E5
CORNER GUARD - STAINLESS STEEL
1 1/2"=1'-0"
ELEVATION
COVER AS
SPECIFIED
GYP. BD.METAL STUD
MOUNTING
SCREWS (IF
PROVIDED)
PLAN
NOTE: REFER TO SPECIFICATIONS
FOR INSTALLATION METHOD:
CEMENT-ON OR SCREW-ON.
NOTE: PATCH FLOOR AS REQUIRED.
4 1/2"
GLASS AS SCHEDULED
ALUMINUM FRAME
BACKER ROD AND SEALANT,
BOTH SIDES OF FRAME
SHIM AS REQUIRED
C6
HEAD DETAIL - GLAZING
1 1/2"=1'-0"
5/8"3 5/8"
5/8"
4 7/8"
5/8" GYP. BD. (BOTH SIDES)
3 5/8" METAL STUDS (TYPICAL)
DOUBLE BOX HEADER
NOTE:
EXTEND HEADER WALL TO
BOTTOM OF STRUCTURE
(BRACE AS REQUIRED).
EXISTING MASONRY WALL
EXISTING
F.V.
STEEL FRAME, ANCHOR TO
EXISTING WALL
CONT. CAULK (BOTH SIDES)
D4
JAMB DETAIL - DOOR (MASONRY)
1 1/2"=1'-0"
E4
HEAD DETAIL - DOOR (MASONRY)
1 1/2"=1'-0"
DOOR PER SCHEDULE
NOTE:
CONTRACTOR SHALL PROVIDE
'FIXED FLOOR ANCHORS' AT ALL
DOOR JAMBS.
1/2" 1/2"
EXISTING MASONRY WALL
EXISTING
F.V.
STEEL FRAME, ANCHOR TO
EXISTING WALL
CONT. CAULK (BOTH SIDES)
DOOR PER SCHEDULE
1/2" 1/2"
C5
WALL SECTION
3/4"=1'-0"
EXISTING FOUNDATION
5/8" GYPSUM BOARD (BOTH SIDES)
BATT INSULATION
3 5/8" METAL STUDS AT 16" O.C.
FINISHED CEILING
108'-0"
FIN FL
100'-0"
EXISTING STRUCTURE
PROVIDE 1" SLIP TRACK AT
BOTTOM OF STRUCTURE
TERMINATE GYPSUM BOARD 6"
MINIMUM ABOVE FINISHED
CEILING
2'-6"
1'-0
"
4"
3'-0
1/2"
1 3
/4"
1'-0"
GROMMET
SCHEDULED BASE
3 5/8" METAL STUD FRAMING
3/4" PLYWOOD SUBSTRATE
COVERED WITH TYPE I (1/16")
LAMINATED
3'-6"
2'-1 1/2"
1 3
/4"
SUPPORT BRACKET EQ
TO RAKKS EH-1824
2X6 WOOD BLOCKING
3/4" PARTICLE BOARD COVERED
W/ TYPE I (1/16") LAMINATED
PLASTIC (TOP)
HARDWOOD EDGE
(TYPICAL)
5/8" GYP. BD.
2'-6"
4"
1 3/4
"
SCHEDULED BASE
3 5/8" METAL STUD FRAMING
3/4" PLYWOOD SUBSTRATE
COVERED WITH TYPE I (1/16")
LAMINATED
2'-9"
SUPPORT BRACKET EQ
TO RAKKS EH-1824
2X6 WOOD BLOCKING
3/4" PARTICLE BOARD COVERED
W/ TYPE I (1/16") LAMINATED
PLASTIC (TOP)
HARDWOOD EDGE
(TYPICAL ON EDGES)
5/8" GYP. BD.
4"
1 3/4"
2'-9"
3/4" PARTICLE BOARD COVERED
W/ TYPE I (1/16") LAMINATED
PLASTIC (TOP)
HARDWOOD EDGE
(TYPICAL ON EDGES)
4"
2'-0
1/4
"
2x BLOCKING
2'-6"
2'-0 1/4"
1'-8 1/2" 3"
1X4 FURRING STRIPS AT 24" ON
CENTER EACH WAY (BY
MILLWORKS)
1X4 FRAMING
SCHEDULED BASE
K-V #255 STANDARDS SURFACE
MOUNTED & #256R SUPPORTS
(TYPICAL)
1X4 FRAMING
3/4" PARTICLE BOARD COVERED
W/ TYPE I (1/16") LAMINATED
PLASTIC (TOP)
3/4" PLYWOOD SUBSTRATE
ADJ. SHELF W/ TYPE I (1/16")
LAMINATED & HARDWOOD
EDGES
1/4" PLYWOOD BACK
3/4" PLYWOOD SUBSTRATE
COVERED WITH TYPE I (1/16")
LAMINATED W/ HARDWOOD
EDGES (DOORS, SIDES &
BOTTOM)
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
AMARILLO 7966.16
-
01/23/17 BID SET
THIS DOCUMENT IS RELEASED ON 12/23/2016
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
THIS DOCUMENT IS RELEASED ON 12/23/2016
FOR THE PURPOSE OF INTERIM REVIEW
UNDER THE AUTHORITY OF PAUL S. HARE,
R.A., TEXAS LICENSE #19104. IT IS NOT TO BE
USED FOR REGULATORY APPROVAL,
CONSTRUCTION, BIDDING OR PERMIT
PARKHILL, SMITH & COOPER, INC.
RE
G
I
S
T
E
R
E
D A
R
C
H
I
T
E
C
T
S
T
A
T
E
OF
T
E
X
A
S
19104
P
A
U
L
S.
H
A
R
E
01/23/17
SECURITY PLANMIDDLE SCHOOLENLARGED PLANS
AND DETAILS
A-401
24x14
18x18
1
2
2
3
3
3
3 3
24x14
18x18
12"∅/S1
400 CFM
12"∅/S1
400 CFM
12"∅/S1
400 CFM
12"∅
12"∅
12x12/R1
12x12
12"∅
12"∅
12x12/R1
12"∅
12"∅/S1
400 CFM
12"∅/S1
400 CFM
VESTIBULE
101
WAIT
102
PRINC
103
OFFICE
104
DEMOLITION NOTESAS INDICATED BY: 00
1. EXISTING FURNACE TO REMAIN.
2. EXISTING MAIN DUCT RUN TO REMAIN.
3. REMOVE EXISTING SUPPLY GRILLE AND DUCT BACK TO MAIN AND CAP.
AIR DISTRIBUTION SCHEDULESYMBOL TYPE DESCRIPTION INSTALLATION MANUFACTURER
TYPE MODEL
S1 CEILING ALL STEEL, THREE STEP SQUARE CONE, NOMINAL 24" x 24" FACE, ROUND NECK SIZE AS SHOWN ON
DRAWINGS, 360 DEGREE THROW UNLESS SPECIFIED OTHERWISE.
LAY-IN / NAILOR
SUPPLY SURFACE RNS
R1 CEILING ALL STEEL, NOMINAL 24" x 24" FULL FACE EGG GRATE GRILLE, TRANSITION TO NECK SIZE AS SHOWN ON
DRAWINGS.
LAY-IN / NAILOR
RETURN SURFACE 61EC
NOTES:
1. AIR DEVICES SCHEDULED TO BE MANUFACTURED BY NAILOR. TITUS, AND PRICE ARE CONSIDERED EQUIVALENT MANUFACTURERS.
2. ALL VISIBLE SPACE ABOVE OPEN RETURN DEVICES SHALL BE PAINTED FLAT BLACK.
3. PROVIDE MANUAL BALANCING DAMPERS AT EACH SUPPLY AIR DUCT TAP, INSTALL MBD AT MAIN DUCT TAP.
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
AMARILLO 7966.16
- 01/23/17 BID SET
PR
OF
ESS I ONA L ENG
I NE
ER
BRADLEY BLOUNT
L
IC E N S
E
D
115111
STATE OF TEXAS
PA
RK
HIL
L S
MI TH & COOPER
, I NC
. F
-5
60
1/23/17
MIDDLE SCHOOL
MECHANICAL PLANS
M-101
A1MIDDLE SCHOOL MECHANICAL DEMOLITION PLAN1/4"=1'-0"
A2MIDDLE SCHOOL MECHANICAL PLAN1/4"=1'-0"
NORTH
NORTH
VISITORS MUST
REPORT TO
MAIN OFFICE
24 HOUR VIDEO
SURVEILLANCE
DOORS LOCKED
FOR SECURITY
NTS
SIGN DETAIL
PROVIDE SIGN
MANUFACTURE'S
STANDARD VIDEO
CAMERA GRAPHIC
APPROXIMATELY 4" x 4".
PROVIDE TEXT AS
SHOWN. TEXT SHALL BE
NO SMALLER THAN 5/8".
MOUNT ON SOLID WALL
ADJACENT TO ENTRANCE
60" ABOVE WALKING
SURFACE. SHALL NOT BE
LOCATED ADJACENT TO
MAIN ENTRANCE.
COORDINATE EXACT
MOUNTING LOCATION
WITH AUTHORIZED LISD
REPRESENTATIVE.
PROVIDE PREDRILLED
HOLES SIZED AS NEEDED
FOR FASTENERS.
TEXT AND GRAPHICS
SHALL BE RED.
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
AMARILLO 7966.16
- 01/23/17 BID SET
PR
OF
ESS I ONA L ENG
I NE
ER
JONATHAN LEE HARTMAN
L
I C E N SE
D
114868
STATE OF TEXAS
PA
RK
HI L
L S
MI TH & COOPER
, I NC
. F
-5
60
01/23/17
ELECTRICAL
LEGEND
AND ABBREVIATIONS
E-001
NOTE:ITEMS SHOWN AS DASHED INDICATE ITEMS WHICH ARE TO BE REMOVED.
DESCRIPTIONSYMBOL
ELECTRICAL LEGENDSYMBOL DESCRIPTION
SECURITY CAMERA OUTLET.CR SECURITY CARD READER.
DOOR CONTACT.
ELECTRIC STRIKE.
ELECTRICAL ABBREVIATIONSABOVE COUNTER ACABOVE FINISHED FLOOR AFFALARM ALMALARM ANNUNCIATOR PANEL AAPALTERNATING CURRENT ACAMERICAN NATIONAL STANDARDS INSTITUTE ANSIAMERICAN SOCIETY FOR TESTING AND MATERIALS ASTMAMERICAN STEEL WIRE GAUGE ASWG
AMPEREAWG
AMPHOURAMP
AMPERE INTERRUPTING CAPACITYAH
AMPLIFIERAIC
AMPS SHORT CIRCUITAMPL
ANNUNCIATORASC
ANTENNAANN
ARCHITECTANT
ARMORED CABLEARCH
AUDIO FREQUENCYARMC
AUDIO VISUALAF
AUTHORITY HAVING JURISDICTIONAV
AUTO TRANSFORMERAHJ
AUTOMATIC CONTROL PANELAUTO XFMR
AUTOMATIC DOOR CLOSERACP
AUTOMATIC FREQUENCY CONTROLADC
AUTOMATIC TRANSFER SWITCHAFC
AUXILIARYATS
AUXILIARY POWER UNITAUXAPU
AMERICAN WIRE GAUGE
BACKBOARD BKBDBALLAST BLSTBATTERY BATBRAKE HORSEPOWER BHPBUCK-BOOST TRANSFORMER BB XFMRBUILDING AUTOMATION SYSTEM BAS
CABLE TELEVISION CTVCANDLE POWERCAPACITORCIRCUITCIRCUIT BREAKERCLOSED CIRCUIT TELEVISIONCOAXIAL CABLECOEFFICIENT OF UTILIZATIONCOLOR RENDERING INDEXCOMMON GROUNDCOMMUNICATIONSCONDUITCONTROLCONTROL CONTRACTORCONTROL PANELCONTROL POWER TRANSFORMERCONTROL RELAYCONTROL SWITCHCOORDINATECOPPERCOVER PLATECURRENTCURRENT LIMITING FUSECURRENT TRANSFORMER.
CPCAPCKTCBCCTVCOAXCUCRICGCOMMCCTRLCCCPCPTCRCSCOORDCUCOV PLCURCLFCT
DECIBEL dBDEMOLITION DEMODETAIL DETDIRECT CURRENT DCDISCONNECT SWITCH DSDOUBLE POLE, DOUBLE THROW DPDTDOUBLE POLE, SINGLE THROW DPST
EACH EAEASEMENT ESMTELECTRIC ELECELECTRICAL METALLIC TUBING EMTELECTRICAL NONMETALLIC TUBING ENTENCLOSURE ENCL
FIRE ALARM FAFIRE ALARM ANNUNCIATOR PANEL FAAPFIRE ALARM CONTROL PANEL FACPFIXTURE FIXTFLEXIBLE METALLIC CONDUIT FMCFLUORESCENT FLUORFLUORESCENT FIXTURE FLUOR FIXTFLUORESCENT LIGHTING FLUOR LGHTFOOTCANDLE FCFREQUENCY FREQFULL LOAD AMPS FLA
GAUGE GAGENERATOR GEN
GROUND FAULT CIRCUIT INTERRUPTER GFCI
HEAVY DUTY HDHIGH OUTPUT HOHIGH VOLTAGE HVHORSEPOWER HP
ILLUMINATION ENGINEERING SOCIETY OF NORTH AMERICA IESNAINTERMEDIATE METAL CONDUIT IMC
KILOVOLT kVKILOVOLT AMP kVAKILOWATT kWKILOWATT HOUR kWH
LIQUIDTIGHT FLEXIBLE METAL CONDUIT LFMCLIQUIDTIGHT FLEXIBLE NONMETALLIC CONDUIT LFNCLOW VOLTAGE LVLUMEN LMLUMENS PER WATT LPW
MAIN CIRCUIT BREAKER MCBMAIN LUGS ONLY MLOMANUFACTURER MFRMINIMUM MINMINIMUM CIRCUIT AMPS MCAMOTOR CONTROL CENTER MCCMOTOR STARTER MS
NATIONAL ELECTRICAL CODE NECNATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NEMANATIONAL FIRE CODE NFCNATIONAL FIRE PROTECTION ASSOCIATION NFPANIGHT LIGHT NLNORMALLY CLOSED NCNORMALLY OPEN NONOTIFICATION APPLIANCE CIRCUIT NAC
PANELBOARD PBPHASE PHPHOTOELECTRIC PEPHOTOELECTRIC CELL PECPOLY VINYL CHLORIDE PVCPOWER PWRPOWER AMPLIFIER PAPOWER FACTOR PF
RECEPTACLE RECEPTRIGID GALVANIZED STEEL RGSRIGID NONMETALLIC CONDUIT RNC
SCHEDULE SCHSERVICE ENTRANCE SESINGLE PHASE 1ØSINGLE POLE, DOUBLE THROW SPDTSINGLE POLE, SINGLE THROW SPSTSWITCHBOARD SWBD
THREE PHASE 3ØTWISTED SHIELDED PAIR TSP
UNINTERRUPTIBLE POWER SUPPLY UPSUNLESS NOTED OTHERWISE UNO
VARIABLE FREQUENCY DRIVE VFDVERY HIGH OUTPUT VHOVOLT, VOLTS, VOLTAGE VVOLT AMPERE VAVOLTAGE DROP VD
WEATHERPROOF WPWIREWAY WW
GROUND GND
GENERAL NOTESA. IF UNABLE TO CONCEAL WIRING SYSTEM IN WALL OR CEILING, THEN USE WIREMOLD
500 SERIES STEEL SURFACE MOUNTED RACEWAY SYSTEM ON INTERIOR WALLS, HARDCEILINGS, DOOR FRAMES. IN BUILDINGS WITH HARD CEILINGS (GYP, PLASTER,...ETC)
INSTALL WIREMOLD RACEWAY SYSTEM ON WALL AT CEILING HEIGHT. CONTRACTOR
SHALL COORDINATE EXACT ROUTING OF RACEWAY SYSTEM WITH OWNER'S
PERSONNEL. CONTRACTOR SHALL PROVIDE ALL BOXES, COVER PLATES, ELBOWS,TRANSITIONS, CONNECTORS, AND END PLATES AS REQUIRED.
B. IF UNABLE TO CONCEAL WIRING SYSTEM IN WALL OR CEILING, THEN ALL VERTICAL
COMMUNICATION CABLING SHALL BE IN RACEWAY SYSTEM.
C. IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE 120V AND 208V POWER FORUPS'S, SERVERS, SECURITY EQUIPMENT, EXTERIOR CAMERA HEATERS/FANS,
MONITORS AND SECURITY LIGHTS AS REQUIRED. PROVIDE CIRCUIT BREAKER(MATCH
EXISTING), RECEPTACLE, WIRE AND CONDUIT.
D. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF WALL MOUNTED SECURITYMONITORS, COMMUNICATION OUTLETS, AND 120V OUTLETS WITH OWNER.
E. ALL SECURITY EQUIPMENT SHALL BE RATED FOR THE ENVIRONMENTAL CONDITION IN
WHICH IT IS LOCATED (AMBIENT TEMPERATURE AND RELATIVE HUMIDITY).F. CONTRACTOR SHALL PROVIDE PROGRAMMING AND COORDINATE REQUIREMENTS TO
INCORPORATE OWNER'S HUMAN RESOURCES DIRECTORY WITH OWNER'S
INFORMATION TECHNOLOGY AND HR PERSONNEL.
G. CONTRACTOR SHALL COORDINATE CONNECTION TO THE EXISTING OWNER'S MAINSERVER AT EACH SCHOOL WITH OWNER'S INFORMATION TECHNOLOGY PERSONNEL.
H. CONTRACTOR SHALL PROVIDE CONDUIT SLEEVES (WITH BUSHING AT EACH END) FOR
ALL COMMUNICATION WIRING PENETRATING THROUGH A WALL OR SURFACE.
I. CONTRACTOR SHALL SUPPORT COMMUNICATION CABLES ABOVE CEILING USING A JHOOK SYSTEM OR APPROVED EQUAL SYSTEM. CABLE SUPPORT SYSTEM SHALL BE
INSTALLED MEETING REQUIREMENTS OF COMMUNICATION CABLE MANUFACTURER
AND WEIGHT REQUIREMENTS. THIS WILL INCLUDE SPACING AND SIZE OF CABLE
SUPPORTS. CABLE SUPPORT SYSTEM SHALL BE INSTALLED PER MANUFACTURERSWRITTEN INSTRUCTIONS.
J. THE PLANS AND SPECIFICATIONS FOR THIS PROJECT REPRESENT A PERFORMANCE
SPECIFICATION FOR A SECURITY AND ACCESS CONTROL. IT WILL BE THE
RESPONSIBILITY OF THE SUCCESSFUL CONTRACTOR TO PROVIDE FOR ANY DESIGNAND SYSTEM COMPONENTS TO PROVIDE FOR AN INTEGRATED AND FULLY
FUNCTIONAL SYSTEM. THIS SHALL INCLUDE, BUT NOT LIMITED TO, POWER, HARDWARE,
CONDUIT, CABLING, SUPPORTS, AND ALL NECESSARY PROGRAMMING INCLUDING
INTERFACE WITH OWNER'S EQUIPMENT AND INTERCONNECTIONS TO PROVIDEREMOTE TRANSMISSION OF DATA.
K. CAMERA MOUNTING HEIGHTS SHALL BE FIELD DETERMINED AND APPROVED TO
PROVIDE FOR MAXIMUM FIELD OF VIEW.
L. CONTRACTOR SHALL COORDINATE LOCATION OF SECURITY EQUIPMENT, RACKS,PANELS WITH OWNER'S IT PERSONNEL. CONTRACTOR SHALL NOT INSTALL NEW
SECURITY EQUIPMENT IN OWNER'S EQUIPMENT RACKS UNLESS AUTHORIZED BY
OWNER'S I.T. DEPARTMENT.
M. ALL PENETRATIONS THROUGH RATED FIRE WALLS SHALL BE SEALED WITH FIRECAULK, SEALANT OR FIRE SAFE INSULATION TO MAINTAIN RATING OF WALL.
N. CONTRACTOR SHALL PROVIDE SECURITY DOOR CONTACTS FOR EXTERIOR DOORS AS
SHOWN ON PLANS.
O. PROVIDE PANIC/DISTRESS BUTTON FOR SECURITY SYSTEM TO INITIATE DOOR LOCKDOWN. COORDINATE LOCATION OF BUTTON WITH SCHOOL PERSONNEL.
KEY PAD.
PANIC/DISTRESS BUTTON.
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
AMARILLO 7966.16
- 01/23/17 BID SET
PR
OF
ESS I ONA L ENG
I NE
ER
JONATHAN LEE HARTMAN
L
IC E N S
E
D
114868
STATE OF TEXAS
PA
RK
HIL
L S
MI TH & COOPER
, I NC
. F
-5
60
01/23/17
SECURITY PLAN
HIGH SCHOOL
E-101
A1SECURITY PLAN - HIGH SCHOOL1/16"=1'-0"
AS INDICATED BY: 00
KEY NOTES
1. NEW CEILING MOUNTED IP CAMERA. EXTEND AND CONNECT TO
SECURITY/LAN EQUIPMENT.
2. NEW WEATHERPROOF IP CAMERA. EXTEND AND CONNECT TO
SECURITY/LAN EQUIPMENT. COORDINATE EXACT MOUNTING HEIGHT WITH
OWNER.
3. NEW ACCESS CONTROL DOOR WITH INTEGRAL DOOR ELECTRONIC LOCK,
CARD READER, DOOR CONTACT AND ELECTRIFIED HINGE. PROVIDE
CONNECTION TO DOOR FOR ACCESS CONTROL. PROVIDE CONDUIT
RACEWAY AS REQUIRED TO ACCOMMODATE NEW DOOR.
4. DOOR CONTACT. PROVIDE NEW DOOR CONTACT ON EXISTING DOOR
EXTEND AND CONNECT TO ACCESS CONTROL SYSTEM.
5. ALARM KEYPAD.
NORTH
1
2
2
2 2
3
3
3
3
3
4
4
4
5
2
ISSUING OFFICE:
NO DESCRIPTIONDATE
PROJECT NO:
KEY PLAN
654321
654321
A
B
C
D
E
AMARILLO 7966.16
- 01/23/17 BID SET
PR
OF
ESS I ONA L ENG
I NE
ER
JONATHAN LEE HARTMAN
L
IC E N S
E
D
114868
STATE OF TEXAS
PA
RK
HIL
L S
MI TH & COOPER
, I NC
. F
-5
60
01/23/17
SECURITY PLAN
MIDDLE SCHOOL
E-102
A1SECURITY PLAN - MIDDLE SCHOOL1/16"=1'-0"
AS INDICATED BY: 00
KEY NOTES
1. NEW CEILING MOUNTED IP CAMERA. EXTEND AND CONNECT TO
SECURITY/LAN EQUIPMENT.
2. NEW WEATHERPROOF IP CAMERA. EXTEND AND CONNECT TO
SECURITY/LAN EQUIPMENT. COORDINATE EXACT MOUNTING HEIGHT WITH
OWNER.
3. NEW ACCESS CONTROL DOOR WITH INTEGRAL DOOR ELECTRONIC LOCK,
CARD READER, DOOR CONTACT AND ELECTRIFIED HINGE. PROVIDE
CONNECTION TO DOOR FOR ACCESS CONTROL. PROVIDE CONDUIT
RACEWAY AS REQUIRED TO ACCOMMODATE NEW DOOR.
4. DOOR CONTACT. PROVIDE NEW DOOR CONTACT ON EXISTING DOOR
EXTEND AND CONNECT TO ACCESS CONTROL SYSTEM.
5. NEW DOOR WIT INTEGRAL ELECTRONIC DOOR LOCK. DOOR TO BE
CONTROLLED BY ACCESS CONTROL SYSTEM AS WELL AS PUSHBUTTON AT
RECEPTION DESK.
6. NEW PUSH BUTTON TO CONTROL ELECTRONIC DOOR HARDWARE TO
ALLOW ENTRANCE TO LOBBY AND CORRIDOR.
7. PANIC/DISTRESS BUTTON SHALL BE INTERLOCKED WITH DOORS WITH
ELECTRIC DOOR LOCK. COORDINATE MOUNTING LOCATION WITH OWNER.
8. LOCATION OF EXISTING S2 ACCESS CONTROL/VIDEO SURVEILLANCE
SYSTEM AND I.T. EQUIPMENT. COORDINATE ANY EXPANSION REQUIRED TO
EXISTING EQUIPMENT TO ACCOMMODATE NEW DOOR CONTROL AND
ADDITIONAL CAMERAS.
NORTH
1
2
2
2
2
2
2
1
3
3
3
3
3
3
3
2
4
3
4
4
4
4
4
4
4
5 5
7
6