dynamic conditioning of stochastic fluctuating … · superior distribution grid distribution grid:...

5
DYNAMIC CONDITIONING OF STOCHASTIC FLUCTUATING ENERGY FROM WINDPARKS Prof. Dr.-Ing. C. Sourkounis, Dr.-Ing. J. Wenske*, Dipl.-Ing. F. Richter Research Group of Power Systems Technology Faculty of electronics and information technology Ruhr-University Bochum Bochum, Germany [email protected] *Schmiedekoppel 4, 21449 Radbruch Abstract – The stochastic fluctuating offer of wind energy limits the capacity of supply in electrical grids by means of technical and economical reasons. To increase the supply, a concept of dynamic conditioning with the objective to increase the quality of supply was developed. The concept envisages support and management of the electrical grid respectively through compensation of active and reactive power with static converters (“Electronic Synchronous Machine”) and short time storage. By the four-quadrant operation of the converters, short time fluctuation of the energy sources and changes of the load can be absorbed or smoothed directly on location. By the use of dynamic storage systems an intermediate storage of the stochastic offered primary energy is done. This low order energy can thereby be converted into high order recallable energy, which even can be used to satisfy peak demands. The local compensation of the fluctuation of the energy supply on the one hand and of the changes of the demand on the other hand, allows a more steady energy demand from the nation-wide electrical grid. Keywords: power conditioning, dynamic storage, renewable energy systems 1 INTRODUCTION Generally a conditioning of the energy is necessary if, due to strong fluctuation of the local power flows or non-sinusoidal currents, a rigorous reduction of the power grid quality is caused at the relevant point of common coupling. By means of energy supply from statistic fluctuating sources, the mentioned unfavourable conditions can easily occur, especially within network spurs with low short circuit power output or in isolated grids. As well the maximum allowable connection load is highly restricted. Besides the non-periodical fluctuating active power, caused by the stochastic fluctuating source, the causes of low or unsteady quality of supply in coupled grid units can be switch on/off incidents, emission of harmonics caused by systems with converters, and not appropriate adapted system control or operation. The low, respectively unsteady, quality of supply is the cause for voltage fluctuation (flicker effect) and voltage alterations (demand of reactive power) in coupled part grids. Figure 1: Basic concept for energy conditioning in dezentralized electrical energy supply systems The major tasks of the dynamic “energy conditioning” are smoothing of the long term fluctuation of the renewable energy supply, dynamic compensation of short term power variation, and filtering of harmonics (grid support) (fig. 1). t PCC t Pt Qt t Pt Pt Qt Qt fluctuating power flows power flows of the compensation smoothed power flows f 50 Hz frequency spectrum t Ueff. RMS-Value Energy conditioning: - Compensation of fundamental oscillation active and reactive power WEC WEC wind farm superior distribution grid distribution grid: consumer, self generation S S closed: grid support S open : grid control 15th PSCC, Liege, 22-26 August 2005 Session 33, Paper 2, Page 1

Upload: others

Post on 22-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DYNAMIC CONDITIONING OF STOCHASTIC FLUCTUATING … · superior distribution grid distribution grid: consumer, self generation S ... short term accumulator for the active power input

DYNAMIC CONDITIONING OF STOCHASTIC FLUCTUATING ENERGY

FROM WINDPARKS

Prof. Dr.-Ing. C. Sourkounis, Dr.-Ing. J. Wenske*, Dipl.-Ing. F. Richter Research Group of Power Systems Technology

Faculty of electronics and information technology Ruhr-University Bochum

Bochum, Germany [email protected]

*Schmiedekoppel 4, 21449 Radbruch

Abstract – The stochastic fluctuating offer of wind

energy limits the capacity of supply in electrical grids by means of technical and economical reasons. To increase the supply, a concept of dynamic conditioning with the objective to increase the quality of supply was developed. The concept envisages support and management of the electrical grid respectively through compensation of active and reactive power with static converters (“Electronic Synchronous Machine”) and short time storage. By the four-quadrant operation of the converters, short time fluctuation of the energy sources and changes of the load can be absorbed or smoothed directly on location. By the use of dynamic storage systems an intermediate storage of the stochastic offered primary energy is done. This low order energy can thereby be converted into high order recallable energy, which even can be used to satisfy peak demands. The local compensation of the fluctuation of the energy supply on the one hand and of the changes of the demand on the other hand, allows a more steady energy demand from the nation-wide electrical grid.

Keywords: power conditioning, dynamic storage, renewable energy systems

1 INTRODUCTION Generally a conditioning of the energy is necessary

if, due to strong fluctuation of the local power flows or non-sinusoidal currents, a rigorous reduction of the power grid quality is caused at the relevant point of common coupling.

By means of energy supply from statistic fluctuating sources, the mentioned unfavourable conditions can easily occur, especially within network spurs with low short circuit power output or in isolated grids. As well the maximum allowable connection load is highly restricted. Besides the non-periodical fluctuating active power, caused by the stochastic fluctuating source, the causes of low or unsteady quality of supply in coupled grid units can be switch on/off incidents, emission of harmonics caused by systems with converters, and not appropriate adapted system control or operation. The low, respectively unsteady, quality of supply is the cause for voltage fluctuation (flicker effect) and voltage alterations (demand of reactive power) in coupled part grids.

Figure 1: Basic concept for energy conditioning in

dezentralized electrical energy supply systems

The major tasks of the dynamic “energy conditioning” are smoothing of the long term fluctuation of the renewable energy supply, dynamic compensation of short term power variation, and filtering of harmonics (grid support) (fig. 1).

t PC

C

tPt Q

t

t

Pt

Pt

Qt

Qt

fluct

uatin

gpo

wer

flow

s

pow

er fl

ows

of th

e co

mpe

nsat

ion

smoo

thed

pow

er fl

ows

f50

Hz

frequ

ency

spe

ctru

mt

Uef

f. RM

S-V

alue

Ener

gy c

ondi

tioni

ng:

- Com

pens

atio

n of

fund

amen

tal o

scill

atio

n ac

tive

and

reac

tive

pow

er

WE

C

WE

C

win

d fa

rm

supe

rior

dist

ribut

ion

grid

dist

ribut

ion

grid

:co

nsum

er, s

elf g

ener

atio

n

S

S c

lose

d: g

rid s

uppo

rtS

open

: g

rid c

ontro

l

15th PSCC, Liege, 22-26 August 2005 Session 33, Paper 2, Page 1

Page 2: DYNAMIC CONDITIONING OF STOCHASTIC FLUCTUATING … · superior distribution grid distribution grid: consumer, self generation S ... short term accumulator for the active power input

2 FUNCTION PRINCIPLE OF ENERGY CONDITIONING

The synchronous machine can basically be used for energy conditioning, because of the special subtransient and transient behavior as well as the possibility to adjust the stator current versus the stator voltage by alternating the synchronous internal voltage over the excitation voltage and the load angle over the drive torque in all four electric quadrants during grid parallel operation. Therefore disadvantageous for active power smoothing are the fixed rotation-torque characteristic, the poor control dynamic of the synchronous internal voltage, and the rotor displacement angle at the range from 100ms to several seconds, and phase swinging.

Using the simplified model of the rotating synchronous machine with damper cage, it can be seen as a real voltage source with frequency-dependent operator impedance X(p) and variable (amplitude, phase angle) source voltage. With increasing frequency the reactance decreases until the subtransient reactance xd´´ is reached and operates as a harmonics drain. In case of transient behavior caused by switching operations in the grid, the effect of grid support results in means of dynamic increase of the grids short-circuits power at the PCC. Therefore voltage drops are reduced without intervention of the control.

3~

3~

2-

2-

digi

tal

cont

rol

syst

emH

ost-

PC

PC

C

part

grid

1

part

grid

2

i N1 i N2N

Nu P

CC

u WR

CF

CD

dyn.

sto

rage

u D

i S

i TL D

F

L F

"prim

ary

side

""s

econ

dary

sid

e of

ELS

AD"

"act

ive

dam

ping

circ

uit"

stat

e va

riabl

es o

f the

ele

ctric

al g

rid

A WRw

wD

fD

f WR

WR

AD

visu

alis

atio

nsy

stem

man

agem

ent

ui

Bat

Bat

Figure 2: Electronic Synchronous Machine with active

damping circuit for energy conditioning

At stationary operation, X(p) of the synchronous ma-chine equals the synchronous reactance at fundamental oscillation mode (e.g. for reference value of the con-trolled system). The characteristics during this period

are only determined by the dynamic of the superior control loop (e.g. for the terminal voltage).

The behavior of the synchronous machine is simulated within the energy conditioner. By the use of a short term accumulator for the active power input and output, the system becomes a static energy conditioner (fig. 2). Additional requirements are short-circuit proof operation and application in a large range of performance.

The introduced system, in the following known as Electronic Synchronous Machine with Active Damping circuit (ELSAD), is able to control the active and reactive power at the PCC. Therefore it can increase the energy quality to the demanded degree at this point.

3 CONTROL STRUCTURE The concept of a cascaded PI-state control, pictured

out in this paper (fig. 3), establishes among the known advantages of a PI-state control the possibility to ac-complish detaching control circuits by cascading state control circuits with given limits for the setpoint values.

e-jv3

2

++

++

phiA R

Kurz

VKu

rz-

AWAW

-

R L

R Sp

g

part

grid

1

part

grid

2

--

--

i N1 i N2i S u PC

C

u PC

C

i Pd i Pq i N1d

i N1q

i N2d

i N2q

coor

dina

te tr

ansf

orm

atio

n

u PC

C d

u PC

C q

cons

umer

cur

rent

setp

oint

proc

esso

r

fund

atm

enta

l os

cila

tion

pow

er fl

ow re

quire

men

tsi

, iN

1d

N2d

i, i

N1q

N

2q

ri,ri 9

10co

nver

ter c

urre

nt

c

ontro

l

PCC

-vol

tage

con

trol

cons

umer

cur

rent

con

trol

(VT)

AWAW

PCC

8x

6x8x

cont

rol o

fse

cond

ary

side

con

ver-

ters

vect

ortra

nsfo

r.

P tQ

tso

llso

ll

Gru

ndsc

hwin

gung

sreg

elun

g de

r ELS

AD a

m P

CC

sym

bol f

or E

LSAD

ris

ris

rii rixrs

x

gene

ratio

n of

the

coor

dina

te s

yste

m:

- rat

ed fr

eque

ncy

(50

Hz)

- f

requ

ency

lock

ed- g

rid lo

cked

Figure 3: Diagrammed illustration of the fundamental oscillations control

15th PSCC, Liege, 22-26 August 2005 Session 33, Paper 2, Page 2

Page 3: DYNAMIC CONDITIONING OF STOCHASTIC FLUCTUATING … · superior distribution grid distribution grid: consumer, self generation S ... short term accumulator for the active power input

The trait of the controller changes through structure modification, depending on the active limits, by seizing of determined control circuits through the limitation. Thereby the operating behavior is collected by the sub-ordinated control circuits.

The inverter current, control with limitation of the absolute value of the current, establishes the innermost control loop of the dynamic compensator. It is, provided that it has a adequate design, used to limit the current in case of a short circuit. The controller is based on a state control parameterized on the short circuit impedance of the inverter. This impedance depends, unlike to the impedance of electrical grids coupled at the PCC, on time. As a result of this, the parameters of the control circuit don’t have to change with the charge states.

The actual voltage value at the PCC is kept in a small range of tolerance at a adjustable setpoint by a superior voltage control circuit. Due to the special control structure the voltage control circuit is only active in case of a actual voltage value outside of the range of tolerance and therefore only then impresses a voltage source like behavior to the system.

The consumer current control is superior to the PCC-voltage control. If this control circuit is active, the dynamic conditioner behaves like a controlled current source at the PCC. Such a mode of operation has advantages at a coupling on a rigid net. This means the nominal power of the dynamic conditioner is slender compared to the coupled grid. In this case there can be no noteworthy impact on the working voltage at the PCC, neither by the load, nor by the dynamic conditioner.

If the setpoint values of the voltage control are in their range of tolerance, the consumer current control should impress its behavior on the system and compensate the subordinated control circuits. To avoid stationary control deviation this outer control circuit is also a PI-state control circuit.

The calculation of the setpoint values of the current control circuit is based on orthogonal active and reactive power components. Hereunto a consumer current setpoint processor is heterodyned on the consumer current control circuit, which calculates the consumer current setpoint value from the power setpoint values forced by the operating control and from the actual voltage value at the PCC.

4 STORAGE TYPES To be considered as dynamic storage for energy

conditioning are:

- accumulators (chemical energy)

- flywheels (kinetic energy)

- compressed-air storage (potential energy)

- pumped storage (potential energy)

Storage Type Energy density Dynamic Max. capacity

[kWh/m³] [kWh/kg] [kWh] accumulator

200…500 0,02…5 High < 50.000

Flywheel 1…8 0,006 High < 100 compressed-air storage

1…2 0,003 … 0,06 Middle

pumped storage

0,3 0,0003 middle to low

Table 1: Storage types and their specifications

The accumulator is the most known and used system for the storage of electrical energy (in electrochemical form) by far. It features the possibility of latching bigger amounts of energy at exquisite dynamics. From the technically restricted realizable capacity an application arises in compensating short and medium term fluctuations of the energy demand or supply. Depending on the design of the accumulator there are some disadvantages. The charge/discharge cycle rate and the depth of the discharge have a direct impact on the lifetime of a battery system. These effects are appearing particularly with the, for reasons of economy, most common lead-acid accumulators. By selective structuring of the electrodes (by additives and design) special lead-acid accumulators for the use in decentralized energy supply systems has been developed with charge/discharge cycle rates above 1500 and only a small loss of high current capacity. Another development in this regard is the lead-gel accumulator. It is maintenance free for the whole life cycle and provides flexible installation possibilities.

High energy density has been realized with Ni-Cd and Li-Ion accumulators. Because of their high own consumption (e.g. Li-Ion accumulators), the memory-effect (Ni-Cd accumulators) and the high actual costs, these accumulators are only used in applications with a big need of reduction in weight.

Another alternative for the use as a high dynamic storage system are high-speed flywheels. Unfortunately the realizable capacity is today still 10-times smaller than the capacity of lead-acid accumulators. In contrast to electrochemical storage systems flywheels don’t show a memory-effect. Just as little as there is an impact of the charge/discharge cycles or the depth of the dis-charge on the lifetime of the flywheel. The fundamental disadvantages are based on the fact, that they have a high own consumption, caused by the bearings and the air friction, despite an operation at low pressure (Pabs. ¡ 2 … 10 mbar). Furthermore the flywheel systems are subject to abrasion as the case may be lifetime reduction even in “stand-by-mode”.

By compressed-air storage, in combination with sub-terranean caverns, storage depth are realizable which allow the compensation of long term fluctuations in the

15th PSCC, Liege, 22-26 August 2005 Session 33, Paper 2, Page 3

Page 4: DYNAMIC CONDITIONING OF STOCHASTIC FLUCTUATING … · superior distribution grid distribution grid: consumer, self generation S ... short term accumulator for the active power input

energy offer of renewable energy sources and the en-ergy demand. An enhancement of the energy density aspired by nearly adiabatic compression and expansion of the gas.

Equivalent to the storage pressure of compressed-air storages, the height of fall determines the energy den-sity and the storage depth of pumped storage systems. The topology of the surrounding defines, besides other factors, the realizable storage depth and energy density. This stands in conflict with a use in combination with renewable energy sources (e.g. the wind energy), be-cause regions with good wind speed rates normally have a physiography which doesn’t allow the construc-tion of pumped storage systems.

From today’s point of view lead accumulators and flywheels can cover the task of energy storage in decentralized energy supply systems. Above that it is possible to reach a higher level of utilization of the renewable energy sources on location by a middle and long term application optimization through a combination with compressed-air systems or pumped storage systems.

5 MEASUREMENTS AT THE TEST BAY The ELSAD was put to test in a test bay.

Measurements were made under grid parallel and isolated operation conditions. With a computer controlled wind energy converter-test bench, including a asynchronous generator, the characteristic of the active and reactive power curve, as shown in fig. 4, were reproduced. A 60kVA ELSAD-test plant was then used to condition and smooth the energy that was supplied to the public power grid.

The influence of the simulated gusts and tower effects could be decreased by more than the factor of 10 and the reactive power consumption from the supply grid was completely compensated.

-10

-5

0

5

10

15

20

actic

ve p

ower

[kW

]

activ

e po

wer

[kW

]

activ

e po

wer

[kW

]

activ

e po

wer

[kW

]

0 10 20 30 40 50-10

-5

0

5

10

15

20

t[s]

reac

tive

pow

er [k

Var]

reac

tive

pow

er [k

Var]

5

10

15

23 24 25 26 275

10

15

t[s]

power flows of the sources

conditioned power flows to the grid

Pwind park

Qwind park

Pwind park

Pgrid

Qgrid

Pgrid

Figure 4: Smoothing of wind caused power fluctuations and

compensation of tower effects

Figure 5 shows the voltage curves at the PCC when an asynchronous machine (ASM, 10 kVA) at a grid short-circuit power of 150 kVA is engage (motor start-up) at the time t1 with and without the ELSAD system. The measurement results show the effect of the dynamic increasing of the short-circuit power by means of the subtransient and transient system characteristics of the ELSAD. The relative voltage drop at the PCC during engaging was decreased from 20% to 7% and was com-pletely compensated after 50 ms.

In addition, the energy conditioning system with a limited power compared to the nominal power of the wind energy converter was applied for mid and long term smoothing of wind caused power peaks. The installed power of the energy conditioner represents 20% of the nominal power of the connected wind energy converters. The accumulation depth, defined by

[ ][ ]sP

WsETWEC,N

SPSP = ,

of the test facility was set up with 8.3 s in respect to the nominal power of the wind energy converter.

-140

-70

eff

at PCC

ELSAD-currentON

curr

ent [

A]

volta

ge [V

]

Figure 5: Start-up process of a 10 kW asynchrounous

machine in a network spur with low short circuit power (ca. 50 kVA)

0,0

0,2

0,4

0,6

0,8

1,0

1,2

0,00 0,02 0,04 0,20 0,22 0,24 0,26

allocation of delivered power P(t) WEC

allocation of smoothed power at PCC

stan

dard

ised

am

plitu

de

relative frequency

~~ ~ ~

Figure 6: Comparison of frequency distribution of the

output power of the WEC with the smoothed power at the PCC

15th PSCC, Liege, 22-26 August 2005 Session 33, Paper 2, Page 4

Page 5: DYNAMIC CONDITIONING OF STOCHASTIC FLUCTUATING … · superior distribution grid distribution grid: consumer, self generation S ... short term accumulator for the active power input

The test results, as shown in figure 6, were evaluated using the classification method. It is obvious visible, that the fluctuation of the supplied electrical power at the PCC could be limited to the designated tolerant band of Pmean ± 0.2 * PN, using the energy conditioner. The distribution of the electrical power provided by the WEC shows values that noteworthy differ from the mean value.

6 RÉSUMÉ Within the scope of the presented study it was dem-

onstrated, that it is possible, to smooth short term fluc-tuations in the energy supply of renewable energy sources (e.g. wind power) by the use of a dynamic en-ergy conditioner in combination with dynamic storage. Above that a limitation of the middle and long term changes in power output relating to the average value has been realized. This limitation of the middle and long term gradient of the output power allows long term predictions about the availability of energy from renew-able energy sources in electrical public power supplies. Thereby the share of electrical power generated by wind energy converters to cover the basic energy demand can be increased.

REFERENCES [1] J. Wenske, Elektronische Synchronmaschine mit

aktivem Dämpferkreis zur Energiekonditionierung in elektrischen Versorgungssystemen, Dissertation 1999, TU Clausthal

[2] H.-P. Beck, C. Sourkounis, J. Wenske, Statischer Synchronkonverter mit aktiver Dämpfungsein-richtung zur Energiekonditionierung, Archiv für E-lektrotechnik Volume 81: Number 6 April 1999

[3] C. Sourkounis, H.-P. Beck, J. Wenske, Gesamtkonzept zur Konditionierung elektrischer Energie aus fluktuierenden Quellen in dezentralen Netzen am Beispiel der Windenergie, DEWEK ´98 Tagungsband

[4] C. Sourkounis, Windenergiekonverter mit maxima-ler Energieausbeute am leistungsschwachen Netz, Dissertation 1994, TU Clausthal

[5] H.-P. Beck, C. Sourkounis, Autonomes, modulares Energieversorgungssystem für Inselnetze, Patent-Nr.: 4232516

[6] H.-P. Beck, C. Sourkounis, J.Wenske, Electronic synchronous-machine for the power conditioning in distribution-networks with high wind-energy share, 5th International Conference Electrical Power Qualitiy and Utilisation, Sept. 15 – 17, 1999, Cra-cow, Poland, Pages 371-377

15th PSCC, Liege, 22-26 August 2005 Session 33, Paper 2, Page 5