ductgard - gilberts blackpool...bs en 1366-2 test/assessment references: 256538/cc 261450 meets the...

15
Features Certifed to Current test standards BS EN 1366-2 Fully tested and CE marked and compliant Galvanised or stainless interlocking double skin blades Stainless steel frame side seals 4 modes of operation Connections to suit most proprietary ductwork Extensive range of supporting controls DUCTGARD Duct Mounting Fire and Smoke Dampers SFB (57.9) X UDC 697.9 Dampers 1 Sep 2020

Upload: others

Post on 04-Feb-2021

9 views

Category:

Documents


0 download

TRANSCRIPT

  • Features• Certified to Current test standards BS EN 1366-2

    • Fully tested and CE marked and compliant

    • Galvanised or stainless interlocking double skin blades

    • Stainless steel frame side seals

    • 4 modes of operation

    • Connections to suit most proprietary ductwork

    • Extensive range of supporting controls

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    SFB (57.9) X

    UDC 697.9

    Dampers 1 Sep 2020

  • 2

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Introduction

    Control Mode Options

    Gilberts Ductgard presents an ‘engineered’ range of

    combined smoke and fire dampers suitable for use in all types of HVAC ductwork. Benefitting from over 50 years of engineering experience in the industry considerable

    ingenuity has been applied in the design and construction

    of this product to produce a damper of high efficiency, reliability, durability and ease of use.

    Ductgard has been tested to the latest BS-EN1366-2 fire test standard and includes mandatory CE marking.

    The Gilbert’s Ductgard presents a re-engineered range of

    combined fire and smoke dampers suitable for use in HVAC ductwork systems.

    Developed from a well proven heritage of tried and tested damper designs, considerable ingenuity and manufacturing expertise has been applied to produce a robust, effective, competitive unit that is easy to install and maintain.

    The unit is designed to fit within all types of ductwork at its junction with a fire barrier wall, where it can be fixed directly in or immediately adjacent to the building structure in both

    the horizontal and vertical positions.

    With a choice of 4 different modes of operation all units

    are fully automatic and motorised. All units comprise of an

    air-tight galvanised casing (DW144 Class C Specification) with stainless steel interlocking blades and frame side seals, which provides a four-hour fire rated assembly. Sizes range from 200 x 200 upto a maximum of 1000 x 1000 in one unit

    Dampers over this size are supplied in multiple units but are not CE compliant.

    Features• Certified to Current test standards BS EN 1366-2

    • Fully tested and CE marked and compliant

    • Galvanised or stainless interlocking double skin blades

    • Stainless steel frame side seals

    • 4 modes of operation

    • Connections to suit most proprietary ductwork

    • Extensive range of supporting controls

    Mode Description Page

    9A Fully automatic opening operating on 24v with failsafe spring return closure via 72˚c electro thermal link release

    4

    9B Fully automatic opening operating on 230v with failsafe spring return closure via 72˚c electro thermal link release

    4

    10A Fully automatic closure operating on 24v with failsafe spring return opening via 72˚c electro thermal link release

    4

    10B Fully automatic closure operating on 230v with failsafe spring return opening via 72˚c electro thermal link release

    4

  • 3

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Mode 9

    Mode 10

    DescriptionMode 9 provides a fully automatic type of smoke and fire damper that operates on the basis of fail safe closure with

    automatic reset. It has been designed to close in smoke

    and fire conditions upon a failure of the supply voltage to the motor or in the event of an electro thermal fusible link separating at a pre-determined temperature (72°C

    standard). Volt free microswitches are included as standard.

    OperationMode 9 is fitted with a spring return square drive motor which will hold the damper open for as long, as the supply voltage is available. Interruption of this supply will cause controlled damper closure by way of the motors spring

    return operation. In addition however, the damper is fitted with an electro thermal fusible link which will fail at a pre-

    determined temperature (72°C standard) and close the

    damper irrespective of the status of the motor.An integral test pushbutton on the electro thermal fuse

    housing allows for the local testing of the damper operation.

    Motor Voltage Control OptionsMode A: 24V AC or DC supply.

    Mode B: 230V AC supply.

    Note: All options include position microswitches as standard.

    Re-set ProcedureProvided the fusible link is intact the damper will automatically reset after an interruption of the supply voltage to the motor. The motor will take

    approximately 80 seconds to open the damper.

    The spring return motor and terminal box (if fitted) are mounted on the ductwork connection sleeve. Fully assembled prior to despatch they

    require only the external electrical connections to be made.

    DescriptionMode 10 performs in exactly the same manner as the Mode

    9 except that the operation is reversed and the units are fail safe open. The motor sets the unit in the full closed position

    and the unit will only open in the event of an interruption of the supply voltage to the motor or separation of the thermal fusible link.

  • 4

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Dimensional Data Square/Rectangular Spigot Connection

    * Allow extra 50mm for cables

    Circular Spigot Connection * Allow extra 50mm for cables

    B Dimension Up to 350mm dia = 41mm

    Over 350mm dia = 55mm

    39 120 39

    VARYING LENGTHS OF OPTIONAL STUB DUCT AVAILABLE210MM TO 450MM. PLEASE REFER TO SALES OFFICE

    90 40DUCT WIDTH - 4mm

    (100 to 1000) 40

    40

    DU

    CT

    HE

    IGH

    T -

    4m

    m(1

    00

    to

    10

    00

    )4

    0

    194

    19

    8*

    19

    8*

    336*

    Dim

    en

    sio

    n ‘A’

    Se

    e T

    ab

    le

    AL

    LO

    W F

    OR

    AC

    TU

    AT

    OR

    RE

    MO

    VA

    L

    50

    25

    39

    DUCT DIAMETER - 3mm(100 to 1000)B 41 120

    194

    39

    DU

    CT

    DIA

    ME

    TE

    R -

    3m

    m(1

    00

    to

    10

    00

    )3

    9

    41 B

    336*

    19

    8*

    19

    8*

    Dim

    en

    sio

    n ‘A’

    Se

    e T

    ab

    le

    1616

    38

    90 39

    AL

    LO

    W F

    OR

    AC

    TU

    AT

    OR

    RE

    MO

    VA

    L

    50

    16 16

    16

    Dimension ADuct Height/Dia. 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000

    Dimensio’A’ 84 109 84 159 184 159 184 259 284 259 284 359 384 359 384 459 484 459 484

    Damper Handing

    Right hand motor

    positioning (as shown)

    as standard

  • 5

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Installation Dimensional Data

    InstallationFrame(HEVAC)Ref. IF

    Sleeve with AngleRef. SF* Suitable for walls

    up to 200mm.

    Above this thickness refer to our technical

    sales office.

    Drop RodCleats

    Ref. DF

    Angle FrameRef. AF

    3413134 DUCT WIDTH OR DIA. + 136mm

    DU

    CT

    HE

    IGH

    T O

    R D

    IA. +

    136m

    m

    285

    DU

    CT

    HE

    IGH

    T O

    R D

    IA. +

    81m

    m

    DU

    CT

    HE

    IGH

    T O

    R D

    IA. +

    161m

    m

    DUCT WIDTH OR DIA. + 189

    DUCT WIDTH OR DIA. + 109

    DIMENSION = X + 25mm DIMENSION = X

    CENTRE LINE OF DUCT

    *

    CONNECTING DUCTWORK BY OTHERS

    CONNECTING

    DUCTWORK

    BY OTHERS

    50 50

    50

    50

    40 40 40O 12mm HOLE FOR DROP RODS

    1818

    DUCT WIDTH or DIA. + 225

    DU

    CT

    HE

    IGH

    T O

    R D

    IA. +

    198m

    m

    35

    120

    60

    60

    DIMENSION = X + 25mm DIMENSION = X

    CENTRE LINE OF DUCT

    6085

  • 6

    Dry Wall

    with sleeve & angles (Ref...SF)Single section sizes (mm):

    100 x 100 to 1000 x 1000

    Tested to BS EN 1366-2 for 4 hours

    Equivalent to BS EN 13501-3 classification: ES240 (E240S)BS EN 1366-2 test/assessment references: 256538/CC 261450Meets the requirements of bs 476-20/22 - refer bs 476-10.6.6.3

    ALL R

    OU

    ND

    GA

    P 5

    MM

    TYPE 5 PLASTERBOARD

    STONE WOOL

    SLEEVE

    ANGLES

    OPENING LINED WITH

    TRACK AND BOARD

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Installation MethodsDuctgard can be installed in a wide variety of approved ways using the different installation options detailed on page 6.

    Please remember that only the installation methods detailed

    are tested and approved to EN1366-2.

    If your installation varies from these options you will need to confirm approval with Building Control. Manufacturers are not able to approve alternative installation methods.

    Tested to BS EN 1366-2 for 4 hours

    Equivalent to BS EN 13501-3 classification: ES240 (E240S)BS EN 1366-2 test/assessment references: 256538/CC 261450Meets the requirements of bs 476-20/22 - refer bs 476-10.6.6.3

    Block/Masonry Wall with sleeve & angles (Ref...SF)Single section sizes (mm):

    100 x 100 to 1000 x 1000

    Block/Masonary Wall/Concrete Floorwith HEVAC frame (Ref...IF)Single section sizes (mm):

    100 x 100 to 1000 x 1000

    Tested to BS EN 1366-2 for 4 hours

    Equivalent to BS EN 13501-3 classification: ES120 (E12 0S)BS EN 1366-2 test/assessment references: 256538/CC 261450Meets the requirements of bs 476-20/22 - refer bs 476-10.6.6.3

    ALL R

    OU

    ND

    GA

    P 5

    MMBLOCK WALL

    BUILDING TIES

    MORTAR OR CONCRETE BACK FILL

    FRAME POSITIONED CENTRALLY OR

    THE CENTRE TO BE AT LEAST

    50MM AWAY FROM NEAREST WALL FACE

    SLEEVE

    ANGLES

    MIN.

    150MM

    Dry Wall

    with drop rod cleats (Ref...DF)Single section sizes (mm):

    100 x 100 to 1000 x 1000

    Tested to BS EN 1366-2 for 4 hours

    Equivalent to BS EN 13501-3 classification: ES120 (ES120)BS EN 1366-2 test/assessment references: 256538/CC 261450Meets the requirements of bs 476-20/22 - refer bs 476-10.6.6.3

    M10 DROP RODS

    STONE WOOL

    TYPE 5 PLASTERBOARD

    OPENING LINED WITH

    TRACK AND BOARD

  • 7

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Tested to bs en 1366-2 for 4 hours

    Equivalent to bs en 13501-3 classification: es240 (e240s)bs en 1366-2 test/assessment references: 216413/cc 254958/cc 261450Meets the requirements of bs 476-20/22 - refer bs 476-10.6.6.3

    Dry Wall, Masonary or Concrete Floor - with angle frame (Ref...AF)Single section sizes (mm):-

    100 x 100 to 1000 x 1000

    MIN. 100MM

    MAX. 200MMSTONE WOOL

    OPENING LINED WITH TRACK

    AND BOARD

    TYPE 5 PLASTERBOARD

    FLANGE SCREWED

    TO TRACK

  • 8

    CLAMPBRACKET

    REVERSE MOUNTEDTRANSFER DRIVE

    M6 BOLTS & WASHERS (X4)

    ACTUATOR WITH FIXINGBRACKET SUB ASSEMBLY

    Reverse Mounted

    Actuator Clamping

    Kit

    439.5

    195.5 145

    50MM FORCABLE

    268

    40 DUCT WIDTH - 4MM 40

    40

    40

    DU

    CT

    HE

    IGH

    T -

    4M

    M

    25.5

    105

    565

    195.5 270.5

    Standard Position

    Alternative

    Position 1

    Alternative

    Position 2

    145

    198

    50MM FORCABLE

    268

    439.5

    195.5 145

    19

    8

    50MM FORCABLE

    268

    19

    8

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Actuator - Inboard Mounting OptionThe actuator is normally fitted to the outside face of the motor mounting bracket. Where limited clearence or other

    factors dictate it is posible to move the motor to an inboard position.

    The motor can also be rotated into three alternative positions either on site or in the factory.

  • 9

    1 2

    - +

    M

    Control Option A

    S1 S2 S3 S4 S5 S6

    5° 80°

    L N E

    M

    N L 1 2 3 4 5 6 + + - - S S

    1 2 3 4 5 6

    2 Core ScreenedCommunication Cable

    Belimo Damper Motor

    DCM Damper Control Module

    240V 50HZFused Spur(option 24V DC)

    1 2

    - +

    M

    Control Option B

    S1 S2 S3 S4 S5 S6

    5° 80°

    Control Option A

    Control Option B

    24 V WIRING DIAGRAM

    Power Supply 24V AC +-20%

    50/60 Hz 24V DC +-20%

    Current Rating 380mA AC max

    POWER CONSUMPTION

    Opening 5 watts

    Holding 2.5 watts

    240V WIRING DIAGRAM

    Power Supply 240V AC +15% -10%

    50/60 Hz 240V AC +10% 50Hz

    Current Rating 200mA AC max

    POWER CONSUMPTION

    Opening approx 6 watts

    Holding approx 3 watts

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Wiring Diagrams

    All ModesAddressable

    Mode 9 and 10 Ductgards are normally controlled, by a remote switch on the Motor Supply.

    Note: To interface with Gilberts remote indicators it is easier

    to switch the negative rather than the positive.

    Mode 9 and 10 Ductgards in this option are interfaced with

    our Gardex Controller as described on Page 11. Motorised

    dampers are fitted with the Belimo BLF-T range as standard. Other actuators are available upon request.

  • 10

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Control Systems

    Bespoke Control Panels

    Gilberts offer a wide choice of hard wired and multiplex

    controlled systems to meet the challenge of effective fire and smoke control monitoring.

    Available as stand alone, or suitable for interfacing or incorporating with building management or fire/smoke control systems designs, the range includes four simple off the shelf packages through to bespoke designs to satisfy the most

    demanding criteria.

    The Gardex system has been designed to reduce the cost of

    electrical wiring installations and satisfy the most complex of

    control changes. Up to 126 dampers can share the same 2

    wire communication line to transmit information to and from

    the central controller.

    Features

    Housing - Metal wall mounted enclosure complete with a

    clear hinged lockable front cover and lower cabling chamber. Protection rating IP55

    Keyboard and Display - Directory command programming

    via arrow keys and 2 line x 40 character LCD display are provided as an operator interface.

    Fault reporting - Faults are identified on the LCD display and the controller can be interrogated to determine the

    nature of the fault and its location.

    Gardex (Modes 9/10 Options Only) Multiplex System

    GardexController

    DamperIndicator

    DamperIndicatorExpander

    400mm

    500m

    m

    Bottom Entry GlandPlate 300x90mm (approx)

    CENTRAL CONTROLLER

    PROGRAMRESET

    ACKNOWLEDGE

    POWER ON

    SYSTEM FAULT

    LAMP TEST

    FIRE COMMAND

    FAULTACKNOWLEDGED

    SMOKE DAMPER STATUS INDICATION

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

    SMOKE DAMPER STATUS INDICATION

    21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

    SMOKE DAMPER STATUS INDICATION

    41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60

    SMOKE DAMPER STATUS INDICATION

    61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80

    TYPICAL OPTIONAL FEATURES• MIMIC AND DAMPER STATUS INDICATOR LIGHTS• INTEGRAL FIREMANS INTERFACE SWITCH• MECHANICAL FAN CONTROL• LINE ISOLATION• REMOTE ALARM INTERFACE

    Field Stations (DCM)

    Available as an integral part of the damper, or as a separate enclosure, the addressable module has been designed to provide independent operation of individual or groups of dampers in accordance with a pre-programmed logic

    sequence of events.

    Individual dampers are controlled and have there status constantly monitored by the module in response to signals

    from the pre-programmed controller. Maximum length of

    communications 2km. In the event of communications failure dampers assume failsafe position.

    These are available in a number of configurations and are designed and manufactured to suit individual specific requirements. The electro-mechanical control/monitoring panels are based on IP55 wall mounting enclosures, which can be provided to include such features as:

    • FIREMANS/BMS INTERFACE• MULTI ZONE CONTROL & DAMPER STATUS

    INDICATIONS

    • UPS• VOLT FREE CONTROLS FOR REMOTE INDICATION

    OR ALARM

    Please contact Head Office to discuss specific requirements.

  • 11

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Ancillary Items

    Gilberts range of ancillary Items have been designed for use in conjunction with both the Ductgard and Smokegard models. Purpose built for straightforward connection and compatibility they offer a number of useful services.

    Remote Indicators/Master Monitors

    Gilberts remote indicator panels can be

    linked to damper Modes 5 and 6 and

    will provide remote indication of the status of one or more dampers.

    Ref:

    • RT1 (1 damper)• MM1-12 (upto 12 dampers)

    Larger Panels available upon request

    Master Monitor

    A more advanced form of remote indication is available with a master monitor. This unit provides remote indication for the status of up to 12

    individual dampers.

    Ref:

    • MM1-12*

    * dependant on number of dampers on

    the system

    Standard Power Supply

    Standard power supplies are available in two sizes to suit up to 6 or up to 12

    dampers. They provide conversion from 240v AC input to a smooth and stabilised 24v DC output.

    Ref:-

    • G6 = 6 UNIT OUTPUT• G12 = 12 UNIT OUTPUT• G6R = 6 UNIT OUTPUT + RELAY• G12R = 12 UNIT OUTPUT + RELAY

    Uninterruptible Power Supply

    Uninterruptible power supplies

    operating on a 240v AC input provide a smooth 24v DC output to power up to 12 dampers. Unlike standard

    power supplies however, in the event of a power failure, there will be an automatic changeover to in-built batteries without tripping the dampers

    providing continued power for a period of up to 1 hour.

    Ref:-

    • UPS6 = 6 UNIT OUTPUT• UPS12 = 12 UNIT OUTPUT• UPS6R = 6 UNIT OUTPUT + RELAY• UPS12R = 12 UNIT OUTPUT + RELAY

    RED LIGHT

    SYSTEM TRIPPED

    GREEN LIGHT

    SYSTEM SET

    UNIT No.

    AIIFA No.

    OUTLINE OF PCB

    NOTE: When damper is open yellow is +VE

    When damper is closed blue is +VE

    O

    R

    G

    YE

    LL

    OW

    BL

    UE -V

    E D

    C

    FROM

    DUCTGARD

    10

    0m

    m

    76mm 35mm

    Master Monitor

    UP TO 12 PCBs IN 1

    MASTER MONITOR

    NOTE: When damper is open yellow is +VE

    When damper is closed blue is +VE

    FROM

    DUCTGARD

    YE

    LL

    OW

    BL

    UE -V

    E D

    C

    O

    R

    G

    O

    R

    G

    240mm

    24

    0m

    m

    87mm

    240mm

    24

    0m

    m

    87mm

    POWER SUPPLY

    UNITTYPE G12

    MAINS INPUT 240 V.A.C.l

    OUTPUT TO DAMPER 24 V.A.C.l

    WARNING - ISOLATE

    MAINS SUPPLY BEFORE

    ENTERING

    E

    N

    L

    MAIN POWER SUPPLY

    240v AC

    24v DC POWER OUT

    240mm

    35

    0m

    m

    87mm

    UNINTERUPTABLE

    POWER SUPPLY

    CELLS:- 27.6v DC MAX: TEST YEARLY

    MAINS INPUT: 240v AC

    OUTPUT TO DAMPERS 24v DC

    ON

    ON

    THIS UNIT IS DESIGNED TO SUPPLY UP

    TO 12 DAMPERS FOR UP TO 1 HOUR

    THE INTERNAL DRY-FIT CELLS DO NOT REQUIRE SERVICE OR

    ELECTROLYTE LEVEL TOPPING-UP. WARNING: TAKE CARE WHEN

    INSIDE THIS UNIT CELLS GIVE 100+ AMPS IF SHORTED OUT

    E

    N

    L

    MAIN POWER SUPPLY

    240v AC

    24v DC POWER OUT

    Smoke Detectors

    Smoke Detectors are available for in duct or ceiling mounting and can link directly into Modes 5 & 6 or the output relay of the Power Supply units. Detectors are 24v DC Ionisation type

    Ref:

    • In-duct 4 wire - SD3• 4 wire - SD2

  • 12

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Test Data

    Pressure Drop BSRIA Report 15633/1Calculated performance at various damper settingsSize tested: 500mm x 600mm

    Blade Leakage

    ------- 100mm x 100mm (smallest) unit as tested to BS EN 1366-2

    ------- 1000mm x 1000mm (largest) unit as tested to BS EN 1366-2

    Casing Leakage

    Ductgard was tested and found to meet Class ‘C’

    Classification BS EN 1751:1999. Leakage recorded at less than 0.1l/s/m² at 2000 Pa

    Blade Leakage for a 500mm square Damper------- 500mm x 500mm unit as tested to BS EN 1366-2

    Width (mm)

    Height (mm) 100 200 300 400 500 600 700 800 900 1000

    100 7.8 9.0 9.8 10.8 11.9 13.2 14.3 15.4 16.5 17.7

    200 9.0 10.5 11.3 12.4 13.6 15.4 16.7 18.1 19.4 20.7

    300 10.3 11.9 12.8 14.1 15.4 17.7 19.3 20.8 22.4 23.9

    400 11.6 13.4 14.4 15.8 17.3 20.0 21.8 23.6 25.4 27.2

    500 12.9 14.9 16.0 17.6 19.1 22.3 24.3 26.4 28.4 30.4

    600 14.2 16.3 17.6 19.3 21.0 24.6 26.9 29.1 31.4 33.6

    700 15.5 17.8 19.1 21.0 22.8 26.9 29.4 31.9 34.3 36.8

    800 16.8 19.3 20.7 22.7 24.6 29.3 31.9 34.6 37.3 40.0

    900 18.1 20.8 22.3 24.4 26.5 31.6 34.5 37.4 40.3 43.2

    1000 19.4 22.3 23.9 26.1 28.3 33.9 37.0 40.2 43.3 46.4

    Pre

    ssure

    Dro

    p (

    Pa)

    Pre

    ssure

    Dro

    p (

    Pa)

    Pre

    ssure

    Dro

    p (

    Pa)

    1000

    25%

    OP

    EN

    75%

    OP

    EN

    50%

    OP

    EN

    100%

    OP

    EN

    100

    500 1000

    10

    300 100

    10

    1

    100 0

    Class C

    (BS EN

    1751)

    0.01100

    10 5 50

    0.1

    50

    1

    100

    Velocity (m/s)

    Leakage (m3/hr/m2) Leakage (l/s/m2)

    10

    10 1000200

    EN17

    51 C

    lass 3

    EN17

    51 C

    lass 2

    EN17

    51 C

    lass 1

    Teste

    d Res

    ult

    Weight Chart (kg approx.)Square/Rectangular Spigot

    Weight Chart (kg approx.)Circular Spigot

    To include a HEVAC/ HVCA Installation Frame, apply the following multiplier: 1.4

    Dia.(mm) Weight (kg)

    100 8.4

    150 9.8

    200 11.8

    250 13.4

    300 15.1

    350 17.2

    400 19.1

    450 21.3

    500 23.4

    550 25.8

    Dia.(mm) Weight (kg)

    600 30.0

    650 33.2

    700 36.0

    750 39.5

    800 42.5

    850 46.3

    900 49.6

    950 53.6

    1000 57.1

  • 13

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Operation & MaintenanceInstructions

    Trouble-Shooting

    Gilberts Damper, Smoke and Fire Control Range

    Operating and Maintenance Instructions

    All Ductgard units are tested before leaving the factory but should be test operated prior to commissioning to

    ensure correct operation. Quick and easy testing and reset

    procedures for each operational mode are detailed on their

    respective data pages in this brochure. In addition to their initial test however, being a fire safety product, it is also recommended that the units are test operated regularly

    thereafter . Test frequency will depend upon the damper environment but, in the absence of any other information, a maximum interval of 6 months is recommended. In addition an annual visual inspection is also advisable to permit cleaning and removal of any airborne contaminants which may affect the dampers operation.

    Note

    For safety the damper blades should be closed on modes 9

    and open on modes 10, before personally approaching them for inspection/cleaning.

    Since the drive, linkage, motors and electronic components on the ductgard units are ‘sealed for life’ there should be

    no requirement for periodic maintenance and spares are not normally required. Items such as reset levers and test keys however can be misplaced over time. In this event replacements are readily available from Head Office.

    All Ductgard units are both inspected and tested before

    leaving our premises. Manufactured using maintenance free ‘sealed for life’ components there is no reason why they

    should not reach site in full working order and continue to

    function when installed providing that our fitting and wiring instructions have been adhered to.

    In the event of operational difficulties please contact our Head Office for on-line guidance and advice.

    Telephone: (01253) 766911

    Ductgard units carry a full 1 year warranty from the date of

    delivery for all parts and labour.

    Series 60

    Smoke Evacuation DamperFiregard

    Curtain Fire Dampers

    Airgard

    Volume Control Dampers

  • 14

    DUCTGARDDuct Mounting Fire and Smoke Dampers

    Declaration of Performance: Ductgard Range

    1. Unique identification code of the product-type:

    DUCTGARD fire damper (see table below for specific damper installation type) To be used in conjunction with walls/partitions/floors to maintain fire compartments in heating, ventilating and air conditioning Installations

    2. Name, registered trade name or registered trade mark and contact address of the manufacturer as required under Article 11(5):

    Gilberts (Blackpool) Ltd, Clifton Road, Blackpool, FY4 4QT

    3. System or systems of assessment and verification of constancy of performance of the construction product as set out in CPR, Annex V:

    System 1

    4. In case of the declaration of performance concerning a construction product covered by a harmonized standard:

    BRE Global Ltd (notified body 2831) performed the determination of the product type on the basis of type testing (including sampling), type calculation, tabulated values or descriptive documentation of the product, the initial inspection of the manufacturing plant and of factory production control and continuous surveillance, assessment and evaluation of factory production control under system 1 and issued the certificate of constancy of performance of the factory production control (no. CPR-P0007-certificate number-CPR-P0010).

    5. Declared performance according to:

    EN 15650 (Ventilation for Buildings — Fire Dampers)

    Fire resistance according to EN 1366-2 and Classification according to EN 13501.3 and Harmonised Technical specification to EN 15650:2010:

    Range Type Supporting Construction Document Ref Classification

    100x100mm - 1000x1000mm DUC/IF Concrete Floor P100960 - 1006B/4 E120 (ho i 70) S

    100x100mm - 1000x1000mm DUC/IF Blockwork Wall 287719F/2 E120 (ve i o) S

    100x100mm - 1000x1000mm DUC/SF Dry Wall & Blockwork 287719A/1 E120 (ve i o) S

    100x100mm - 1000x1000mm DUC/DF Dry Wall 287719B/2 E120 (ve i o) S

    100x100mm - 1000x1000mm DUC/AF Dry Wall 287719C/2 E120 (ve i o) S

    100x100mm - 1000x1000mm DUC (No Frame) Dry Wall & Blockwork 287719E/2 E120 (ve i o) S

    100x100mm - 1000x1000mm DUC/AF Blockwork 287719B/2 E120 (ve i o) S

    100x100mm - 1000x1000mm DUC/AF Concrete Floor 287719G/2 E120 (ho i 70) S

    Nominal activation conditions/sensitivity according to ISO 10294-4:

    • sensing element load bearing capacity• sensing element response temperature

    Pass

    Pass

    Response delay (response time)

    • closure time Pass

    Operational reliability

    • cycling 50 cycles

    Durability of response delay according to EN 1366-2:

    • sensing element response to temperature and load bearing capacity Pass

    Durability of operational reliability according to EN 15650:

    • open and closing cycle 10.000 cycles Pass

  • OrderingSpecification

    GILBERTSHead Office and WorksGILBERTS (BLACKPOOL) LTD

    Gilair Works, Clifton Road,Blackpool, Lancashire FY4 4QT.

    Telephone: (01253) 766911

    Fax: (01253) 767941

    e-mail: [email protected]

    Web: www.gilbertsblackpool.com

    Specification Fire and smoke dampers shall be LPCB certificated and pass the test requirements stated in EN 1366-2 with an ES classi-fication to EN 13501-3. Dampers to be fitted with an actuator that can respond to a smoke alarm signal to ensure closure

    at the first sign of smoke.

    Motors Dampers to be motor operated with a failsafe thermal fuse

    set to operate at 72°C. The damper will close (or open) in

    less than 30 seconds.

    Damper Blades & Linkage Dampers to have opposed blade operation with interlocking double skinned blades on robust 19mm spindles for both re-

    sistance to fire and daily airflow exposure. The drive linkage shall be fully enclosed and set outside of the air stream for

    protection against damage and air contamination.

    Casing Stainless steel gaskets shall be provided at the top, bottom and sides to reduce casing leakage to below the levels stated in EN 1366-2. Damper casings shall be fully welded to meet

    the air tightness test requirements of HVCA specification DW144 to classes A, B and C at up to 1500Pa.

    Approvals The fire and smoke damper shall have a tested or assessed installation method that matches the requirement of the sup-porting construction into which it is built.

    Gilberts (Blackpool) Ltd reserve the right to alter the specification without notice. For our latest product data please visit www.gilbertsblackpool.com. All images and drawings are for illustrational purposes only and are not intended to deliver an exact visual representation. Minor variations can be expected due to the different manufacturing processes The information contained in this brochure is correct at time of going to press © 2019.

    SERIES:

    SIZE (mm width x Height or Dia)

    FIXING OPTION

    Installation Frame (HEVAC)....IF

    Sleeve and Angle...SF

    Drop Rod...DF

    Angle Frame...AF

    Frameless ... NF

    TYPE:

    Square/Rectangular:..............S

    Circular...................................C

    CONTROL OPTION

    A or B

    MODE

    9 or 10

    NUMBER REQUIRED

    DUC 450 x 200 A 159 FC/NCS

    DUCTGARDDuct Mounting Fire and Smoke Dampers