Ducted HEPA filter units Content overview Leaflet F3 / 2 / 2 / EN Duct casing for installation into ductwork Fitting of filter elements for the separation of suspended particles » » .................................................................. .................................................................. 2 3 General information Technical data Specification text

Upload: kalmech2003

Post on 30-Oct-2014

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Ducted HEPA Filter

Ducted HEPA filter units

Content overview

Leaflet F3 / 2 / 2 / EN

Duct casing for installation into ductworkFitting of filter elements for the separation of suspended particles

»»

..................................................................

.................................................................. 23

General informationTechnical data ∙ Specification text

Page 2: Ducted HEPA Filter

Ducted HEPA filter units - Leaflet F3/2/2/EN2

General information

Ducted HEPA filter unit

Detail

Suitable filterelements

»

»

»

»

»

»

»

Type F353

Turnbuckles for secure sealing between ca sing and filter element.Cover plate with profiled gasket and fourclamping screws with star grips.Pressure measuring points for each filter unit are part of the supply package but mustbe set up on site by others.

Type F780 (E11), Type F781 (H13), Type F782 (H14).Construction: Frame made of MDF, galvanisedsheet steel, or stainless sheet steel.

Type F770 (E11), Type F771 (H13).Construction: Frame made of MDF, galvanised sheet steel, or stainless sheet steel.

Duct casing for installation into ductwork. Fit ting of filter elements for the separation ofsu spended particles such as aerosols, toxicdusts, viruses, and bacteria from the supply or extract air.

Duct casing made of sheet steel with decon taminable powder coating RAL 9010.

Type F352

Duct casing with rigid connecting flanges.

High-efficiency filters for the most critical re quirements of air purity and sterility.

Main or final filter for the most critical re quirements of air purity and sterility.

Upon request.

Application

Material

Construction

Equipment

Minipleat filter cells or minipleat filter pa nels as HEPA filters (F7/7/../.. and F7/9/../..)

HEPA filter cells (F7/12/../..)

Other filter elements

»

»

»

»

With sealing integrity test facility for HEPA fil ter elements.

Associated filters must be ordered separately.

»

»

»»

Construction

Associated TROX filter elements

»

»

Page 3: Ducted HEPA Filter

T 30

H

B

3Ducted HEPA filter units - Leaflet F3/2/2/EN

Technical data ∙ Specification text

Ducted HEPA filter units F352, F353:»»

»

»

»

Technical data:Nominal volume flow rate ____________l/s (m3/h)Dimensions of ducted HEPA filter unit ________________mmNet weight ____________________________kgOrder no. _______________________________Make: TROX

Duct casing for installation into ductworkFitting of filter elements for the separation of su spended particlesDuct casing made of sheet steel with deconta minable powder coating RAL 9010Turnbuckles for secure sealing between casing and filter elementCover plate with profiled gasket and four clam ping screws with star grips

Dimensions of ducted HEPA filter unit F352

Dimensions of ducted HEPA filter unit F353

Table 1: Technical data for F352

Table 2: Technical data for F353

1) HEPA filter elements H13 with various nominal volume flow rates depending on construction.

1) HEPA filter elements H13 with various nominal volume flow rates depending on construction.

Technical data

Filter casing withperipheral connectingflanges, width 42.5 mm.

Individual units to beinstalled either asshown or after a 90°rotation.

Specification text

All weights are net,without packaging.

Detail drawing 1: Ducted HEPA filter unit

HEPA filter elements H13, the lowest and highest volume flow rates are shown.

≈ kg

≈ kg

Weight

Weight

B H T

B H T

F352A01F352B01F352C01F352D01F352E01

F353A01F353B01F353C01F353D01F353E01

1619192427

1821212830

Order no.

Order no.

Nominal volume flow rate 1)

Nominal volume flow rate 1)

Dimensions of unit mm

Dimensions of unit mm

l/s m3/h

l/s m3/h

Filter size mm

Filter size mm

305 305 150305 610 150305 610 150610 610 150762 610 150

305 305 292305 610 292305 610 292610 610 292762 610 292

130 460270 980270 980585 2100740 2660

150 545325/470 1165/1700325/470 1165/1700695/945 2500/3400

880/1180 3160/4250

B H T

B H T

405 378 405405 378 710710 378 405710 378 710710 378 862

405 520 405405 520 710710 520 405710 520 710710 520 862