Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylorengineering.com ASHRAE Golden Gate Chapter November 13, 2014

Upload: others

Post on 05-Feb-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

  • Dual Maximum VAV Box Controls

    Steven T. Taylor, PE FASHRAETaylor Engineering LLCstaylor@taylor‐engineering.com

    ASHRAE Golden Gate ChapterNovember 13, 2014

  • Agenda

    VAV Box basics• Sizing VAV Boxes• How low can you go?

    VAV Box control logic• Conventional VAV box control logic• “Dual Maximum” control logic• Non-complying dual maximum control logic• Determining setpoints

    How well does “Dual Maximum” logic work?• ASHRAE RP-1515 Results

  • VAV Box Sizing

    Oversized box• Less pressure drop• Less noise• Higher box min → more reheat, higher fan energy• Cost more

    Undersized box• Higher pressure drop• More noise• Lower box min → less reheat, lower fan energy

  • VAV Box Sizing: LCC Analysis

    Compared ∆TP from 0.3” to 0.8” Low rise office building Sensitivity Analysis

    • Climate• Loads• operating schedules• Utility rates• Load calc’ (aggressive, conservative)• 8 bit versus 10 bit A/D converter• SAT (50°F-60°F), SAT reset, SP reset

    RESULT: Size VAV Boxes for ~0.5” ∆TP

    VPSPTP

  • VAV Box Sizing: Sample Calc.

    Nominal size

    Inlet dia. (in.)

    Outlet width (in.)

    Outlet height

    (in.)

    ∆SP(in.

    w.g.)*

    ∆VP (in.

    w.g.)

    ∆TP(in.

    w.g.)

    Max CFM

    Radiated NC*

    4 4 12 8 0.08 0.42 0.50 230 21 5 5 12 8 0.15 0.35 0.50 333 20 6 6 12 8 0.24 0.25 0.49 425 21 7 7 12 10 0.25 0.25 0.50 580 20 8 8 12 10 0.33 0.17 0.50 675 22 9 9 14 13 0.27 0.23 0.50 930 17 10 10 14 13 0.32 0.18 0.50 1100 19 12 12 16 15 0.32 0.17 0.49 1560 19 14 14 20 18 0.31 0.19 0.50 2130 18 16 16 24 18 0.32 0.18 0.50 2730 22

    *From selection software using ARI 885-95 and assuming inlet SP = 1.5 and outlet SP = 0.25

  • What is the lowest minimum?

    • Function of–DDC Controller: What’s the lowest

    controllable velocity pressure (VP) signal?• DDC velocity pressure transducer accuracy• A/D converter resolution (bits)

    –VAV Box: • Amplification factor, F • Inlet size, D

    4

    2

    minminDFPMCFM

    FVPFPM minmin 4005

  • Why Not Just Look in the VAV Box Catalog?

    Equates to ~0.03” minimum VP and about 30% of design CFM for typical box selections

  • Why Not Just Look in the VAV Box Catalog?Still too high

    Good Advice! NEVER use Box manufacturer’s minimums!

  • Controllable VP Minimum

    Some manufacturers list the range in catalog

    Some you have to ask Most available from ASHRAE RP 1353 and PG&E

    research projects (see references)• Almost all controllers ± 10% at 0.003”

    Specify allowable setpoint ≤ 0.004”

  • Typical DDC Performance

    Highly accurate down to about 50 CFM (0.003”)

    -40

    -30

    -20

    -10

    0

    10

    20

    30

    0 100 200 300 400 500 600 700 800Reference Flow [cfm]

    Flo

    w E

    rror

    [cfm

    ]

    Nailor VAV BoxTitus VAV Box“A”“B”

  • Flow Probe Amplification

    229

    358

    515

    70291611601432

    2062

    3665

    7000

    2806

    4 inch

    5 inch

    6 inch

    7 inch8 inch9 inch

    10 inch

    12 inch

    14 inch16 inch

    22 inch

    10

    100

    1000

    10000

    0.01 0.1 1Flow Probe Velocity Pressure Signal (Inches W.G.)

    CFM

    CFM

    @ One Inch Signal

    Inlet Size

    24005

    KAF

    F = amplification factorK = actual flow in CFM at flow probeoutput of 1.0” w.c.A = is the nominal inlet area in ft2

    K

  • Typical Flow Probe PerformanceV

    elo

    city

    [fp

    m]

    Flow Grid Pressure [iwc]1.5.1.05.01.005.001

    50

    100

    200

    500

    1000

    2000

    6.2~slopeF Specify ≥2.0

  • Sample Controllable Minimum

    FVPFPM minmin 4005 3.2

    004.04005170

    Box Inlet Diameter

    Maximum CFM at 0.5 in.w.g. 

    pressure drop

    Minimum CFM at 0.004 in.w.g. sensor 

    reading

    Minimum Ratio at Highest 

    Maximum, %

    Minimum Ratio at lowest 

    Maximum, %6 425 33 7.8% ‐8 715 58 8.1% 13.6%10 1,100 91 8.3% 12.7%12 1,560 130 8.3% 11.8%14 2,130 177 8.3% 11.3%16 2,730 232 8.5% 10.9%

    4

    2

    minminDFPMCFM

  • VAV Reheat Control

  • Q: Why do some buildings use 3 -5 times as much energy as others?

    0

    500

    1,000

    1,500

    2,000

    2,500

    Mar-02 Apr-02 May-02 Jun-02 Jul-02

    Boi

    ler I

    nput

    (Btu

    /sf) Site #1

    Site #2

    A: Reheat

  • Conventional VAV Control

  • Conventional VAV Box Minimum Setpoint

    No less than larger of:• Minimum ventilation rate

    Per Title 24• Controller minimum

    Not an issue for conventional logic – see discussion above• Limit “dumping”

    Not an issue – see RP-1515 results below• Limit stratification

    No more than 20°F above space temperature (~≤95°F) per Standard 90.1

    No more than larger of:• 30% of cooling maximum

    Per Title 24/Standard 90.1. Now only allowed for non-DDC controls

    • Minimum ventilation rate

  • Title 24 VAV Control Requirementfor zones with DDC

  • Dual Maximum Controlper Title 24 and Standard 90.1 for DDC

  • Dual Maximum Logic in Action

    Start heating, increase DAT setpoint

    At 50% Heat, start increasing airflow

  • Sort of Dual Maximum Control (Found in some configurable controllers)

    T-24

  • Sort of Dual Maximum Control (Found in some configurable controllers)

    Title 24

  • VAV Box Dual Maximum Control Setpoints per Title 24 and Standard 90.1

    Minimum: 1. No less than larger of:

    Minimum ventilation rate for the zone Controller minimum

    2. No more than 20% of cooling maximum

    Heating Maximum:1. No less than larger of:

    Minimum Limit stratification - ≤20°F SAT above space temperature (≤~90°F to 95°F)

    2. No more than 50% of cooling maximum Always use Option 1 above

    • Do not use code maximum just because it’s legal!• Avoid using %-of-cooling-maximum setpoints – boxes are

    usually oversized!

    COOL MIN  HEATVR‐101 12 1035 135 260VR‐102 10 810 90 230VR‐103 6 210 50 50

    MARK INLET SIZE

    DESIGN CFM

  • What about Standard 62.1 Multiple Spaces compliance?

    Oakland Office - VAV System with Outdoor Air Economizer

  • How Well Does “Dual Max” Logic Actually Work?

    RP-1515 results…

  • RP 1515, "Thermal and Air Quality Acceptability in Buildings that Reduce Energy by Reducing Minimum Airflow from Overhead Diffusers"

    Objectives Measure energy savings & validate simulations Identify comfort issues that may occur at low flowFunding California Energy Commission - PIER ASHRAE UC Berkeley - Center for the Built EnvironmentResearch Team UC Berkeley Taylor Engineering Price Industries

    Method Field Study in 7 buildings Background survey “Right now” survey matched to zone trends Energy monitoring

    Laboratory Study Air distribution for various diffuser types

  • Yahoo! Sunnyvale Campus

    1073 Zones 3700 Occupants Plaque face diffusers

  • 800 Ferry Building

    22 Zones Perforated Diffuser

    with blades in face

  • Measured flow fractions: Yahoo campus

    0 20 40 60 80 100

    0.00

    0.05

    0.10

    0.15

    Warm Season All Occupied Hours

    Flow Fraction [%]

    Den

    sity

    Low Minimum30% Minimum

    0 20 40 60 80 100

    0.00

    0.05

    0.10

    0.15

    Cool Season All Occupied Hours

    Flow Fraction [%]

    Den

    sity

    Low Minimum30% Minimum

  • Total Electricity Usage

  • Energy Savings

  • Occupant Comfort Survey

    Questions• When the logic changed from conventional

    (High minimum) to Dual Maximum (Low minimum): Did occupants become less comfortable? Was their sense of air movement stronger due to

    “dumping”?

    Approach• 3 surveys:

    Yahoo warm and cool seasons 800 Ferry building warm season

    • 3 – 4 weeks of surveying each season• Switched between high and low minimum

    operation in the middle of each survey period

    • Surveys administered 3 times/day About 10,000 responses received

  • % Dissatisfied peopleHIGH

    ConventionalLOW

    Dual Maximum

    800 Ferry Building 27.3% 12.5%

    Yahoo! cool season 8.7% 9.4%

    Yahoo! warm season 20.1% 10.3%

    249

    1408

    681

    463

    1793 766

    0.0%

    5.0%

    10.0%

    15.0%

    20.0%

    25.0%

    30.0%

    800 Ferry Building Yahoo! Cool season Yahoo! Warm season

    % dissatisfie

    d of peo

    ple

    "How satisfied are you with the temperature in your workspace?“

    HIGH min flow rate LOW min flow rate

  • Thermal sensation distribution (Yahoo! warm season)

  • Loads are very low!

    0.2 0.5 1 CFM/FT2 at 20˚F ∆T

    140 Zones, 2 buildings, 1 warm month (Sept)

  • What happens when load is less than airflow minimum?

    Actual Required CFM

    Conventional Logic

    Dual Max Logic

  • Air temperature(800 Ferry building)

    09/

    22

    09/

    23

    09/

    26

    09/

    27

    09/

    28

    09/

    29

    09/

    30

    10/

    03

    10/

    04

    10/

    05

    10/

    06

    10/

    07

    10/

    10

    10/

    11

    10/

    12

    10/

    13

    10/

    14

    10/

    17

    10/

    18

    10/

    19

    10/

    20

    60

    65

    70

    75

    80

    85

    Dates

    zone

    tem

    pera

    ture

    [F]

    1.4 2 1.8 1.5 1.6 1.5 1.4 1.8 1.6 1.5 2 0.89 1.6 1.5 1.1 1.9 1.1 1.4 1.3 1.2 2.172 72 71 71 72 71 71 71 70 71 71 72 73 74 74 73 74 74 75 75 7314 27 23 35 45 36 35 41 47 34 65 23 30 51 45 64 25 37 67 27 48

    sdMean

    N

    HIGH minimum flow rateLOW minimum flow rate

    High flow: average Tair = 71.2ºF Low flow: average Tair = 73.3ºF

  • How about Drafts?(800 Ferry building)

  • Perceived air quality

  • CBE background survey results

  • Price Lab Tests

    Perforated diffusers with blades in the neck, Cooling Mode.

    Results:• Negligible impact on ADPI – all near 1• Negligible impact on ACE – all near 1

  • Dual Maximum VAV Box Logic Summary

    Title 24 requires Dual Maximum logic for VAV zones with DDC Setpoints

    • Set minimum and heating-maximum setpoints as low as possible Minimum allowed by controls is seldom a factor if box properly sized Do not use maximum allowed by T-24 just because it is legal

    Cost impact• Requires discharge temperature sensor

    This is nice for diagnostics anyway• Usually requires programmable zone controller

    Configurable controller programming should soon catch up

    Performance• Thermal comfort improves with low flow operation• Dumping & draft are not an issue at low flow• Energy savings are significant and similar to simulation predictions

  • Bibliography

    Taylor S., Stein J.; “Sizing VAV Boxes”, ASHRAE Journal, March 2004

    Dickerhoff D., Stein J.; “Stability and Accuracy of VAV Terminal Units at Low Flow”, PG&E 0514, http://www.etcc-ca.com/reports/stability-and-accuracy-vav-terminal-units-low-flow

    Lui R., Wen J.; Stability and Accuracy of VAV Box Control at Low Flows”, ASHRAE 1353-RP

    Taylor S. “Dual Maximum VAV Box Logic”, ASHRAE Journal, December 2012