Page 1: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite® TRX™ BDC™

User Manual–10-30kVA, 60Hz

Page 2: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous
Page 3: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

i

TABLE OF CONTENTS

IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

1.0 DUAL-LITE TRX BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61.1 Normal (UPS) Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.2 Maintenance Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.3 Locating the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

1.4 Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71.4.1 Wiring Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71.4.2 Power Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71.4.3 Input/Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81.4.4 Accessory Fuses and Back-Feed Breaker Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

1.5 Bolting Cabinets Together . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111.5.1 Floor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121.5.2 Cable Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121.5.3 Optional Cabinets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

1.6 Dual-Lite TRX UPS Bypass Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131.6.1 Dual-Lite TRX BDC Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

2.0 INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

3.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .233.1 Electrical Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

3.2 Torque Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

FIGURESFigure 1 Single input UPS with external Dual-Lite TRX BDC with optional internal

transformer—Typical configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Figure 2 Dual-Lite TRX BDC—Access plate removed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Figure 3 Accessory fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Figure 4 Dual-Lite TRX BDC wiring with transformer option, single input . . . . . . . . . . . . . . . . . . . . . . . 10Figure 5 Bolting Dual-Lite TRX UPS to a Dual-Lite TRX BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Figure 6 Cabinet arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Figure 7 Dual-Lite TRX UPS bypass assembly connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Figure 8 Input dry contacts—J26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Figure 9 Output dry contacts and EPO wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Figure 10 Dual-Lite TRX BDC with optional SKRU and transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Figure 11 Busbars—Dual-Lite TRX BDC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Figure 12 Lineup arrangement, Dual-Lite TRX with Dual-Lite TRX BDC . . . . . . . . . . . . . . . . . . . . . . . . . . 18Figure 13 Outline drawing, Dual-Lite TRX BDC for Dual-Lite TRX, 10-30kVA. . . . . . . . . . . . . . . . . . . . . . 19Figure 14 Dual-Lite TRX BDC transformer location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Figure 15 One-line diagram, 208V single input 10-30kVA UPS with three-breaker Dual-Lite TRX

BDC and input isolation transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Page 4: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

ii

TABLESTable 1 Control wiring for Dual-Lite TRX to Dual-Lite TRX BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Table 2 Dual-Lite TRX BDC interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Table 3 Output dry contact relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Table 4 Hardware torque values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Table 5 Wiring for Dual-Lite TRX to Dual-Lite TRX BDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Table 6 Physical standards and parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Table 7 Mechanical characteristics, Dual-Lite TRX BDC, 10-30kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Table 8 Dual-Lite TRX BDC heat dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Table 9 Dual-Lite TRX BDC input currents, single input, main, without transformer. . . . . . . . . . . . . . . 24Table 10 Dual-Lite TRX BDC output currents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Table 11 Recommended lug sizes (compression type) M12, 1/2" bolt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Table 12 Busbar torque for power wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Table 13 Terminal block torque with compression lugs for control wiring. . . . . . . . . . . . . . . . . . . . . . . . . . 25Table 14 Breaker torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Table 15 Electrical data—Dual-Lite TRX BDC, 480VAC input, 208VAC output, single input, with

480V:208V transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Table 16 Electrical data—Dual-Lite TRX BDC, 208VAC input, single input, with 208V:208V

transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Page 5: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

1 Dual-Lite® TRX™ BDC™

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONSThis manual contains important instructions that should be followed during installation of the Dual-Lite TRX BDC (bypass distribution cabinet).

Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel.

A properly trained and qualified electrical contractor should oversee the installation of the equipment.

The Dual-Lite TRX BDC cannot be put into operation until it is commissioned by the manufacturer or authorized engineer. Otherwise, human safety may be endangered and damage to the UPS will not be covered by the warranty.

The Dual-Lite TRX BDC is designed for commercial and industrial uses and cannot be used as life support equipment.

! WARNINGRisk of moving heavy equipment and electric shock. Can cause equipment damage, injury anddeath.

Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury topersonnel. The Dual-Lite TRX BDC’s weight ranges from 660 to 1752 lb. (300 to 794kg).

Determine the unit’s weight and locate the center of gravity symbols before handling theDual-Lite TRX BDC. Test lift and balance the cabinet before transporting it. Never tiltequipment more than 15 degrees from vertical.

In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers orthose approved for use in fighting electrical fires.

Extreme caution is required when performing maintenance.

Be constantly aware that the UPS system contains high DC as well as AC voltages.

Check for voltage with both AC and DC voltmeters prior to making contact.

! AVERTISSEMENTRisque lors du déplacement de l’équipement lourd et de décharge électrique pouvantentraîner des dommages matériels, des blessures et même la mort.

Faites preuve d’une extrême prudence lors de la manutention des armoires ASC afin d’éviterde les endommager ou de blesser le personnel. Les armoires Dual-Lite TRX BDC pèsent de660 à 1752 lb (de 300 à 794 kg).

Déterminez le poids de l’unité et trouvez les symboles de centre de gravité avant de déplacerl’armoire Dual-Lite TRX BDC. Faites des essais de levage et d’équilibre avant de transporterl’armoire. N’inclinez jamais l’équipement à plus de 15 degrés à la verticale.

En cas d’incendie associé à du matériel électrique, n’utilisez que des extincteurs à dioxyde decarbone ou homologués pour la lutte contre les incendies d’origine électrique.

Les opérations d’entretien requièrent une extrême prudence.

Soyez toujours conscient du fait que le système ASC contient des tensions c.c. et c.a. élevées.

Vérifiez les tensions avec des voltmètres c.a. et c.c. avant d’établir tout contact.

Page 6: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite® TRX™ BDC™ 2

! WARNINGRisk of electric shock. Can cause equipment damage, injury and death.

As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure even after input power has been disconnected. The risk of contact with these voltages is minimized as the live component parts are housed behind a metal panel. Further internal safety screens make the equipment protected to IP20 standards. Never remove panels or covers or open doors that will expose internal components to contact.

Read and follow all warnings, cautions and safety and operating instructions to avoid serious injury or death from electric shock. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures.

All equipment maintenance and servicing procedures involve internal access and should be carried out only by trained personnel.

! AVERTISSEMENTRisque de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort.

À l’instar des autres types d’équipement haute puissance, des tensions dangereuses sont présentes à l’intérieur de l’armoire ASC et du châssis de batteries même après le débranchement de l’alimentation d’entrée. Le risque de contact avec ces tensions est diminué, car les parties de composants sous tension sont abritées derrière un panneau métallique. D’autres écrans de sécurité internes protègent l’équipement en conformité avec les normes IP20. Ne retirez jamais les panneaux ou les couvercles et n’ouvrez pas les portes donnant accès aux composants internes avec lesquels vous pouvez entrer en contact.

Veuillez lire et suivre l’ensemble des avertissements, des mises en garde et des instructions de sécurité et de fonctionnement afin d’éviter des blessures graves, voire la mort, pouvant être causées par une décharge électrique. Il n’y a aucun risque pour le personnel lorsque l’équipement est utilisé normalement, en suivant les procédures de fonctionnement recommandées.

Toutes les procédures de réparation et d’entretien de l’équipement exigent un accès à l’intérieur de l’armoire et devraient être menées uniquement par du personnel compétent.

Page 7: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

3 Dual-Lite® TRX™ BDC™

Ground Leakage Currents

! WARNINGRisk of electric shock from high leakage current. Can cause injury, property damage anddeath.

EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.

Earth leakage current exceeds 3.5 mA and is less than 1000 mA.

Transient and steady-state earth leakage currents, which may occur when starting theequipment, should be taken into account when selecting instantaneous RCCB or RCD devices.

Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectionalpulses (Class A) and insensitive to transient current pulses.

Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.

This equipment must be earthed in accordance with the local electrical code of practice.

! AVERTISSEMENTRisque de décharge électrique due à un courant de fuite élevé pouvant causer des blessures,des dommages matériels et même la mort.

IL EST PRIMORDIAL D’ASSURER UNE CONNEXION DE TERRE AVANT DEBRANCHER L’ALIMENTATION D’ENTRÉE. La fuite à la terre est supérieure à 3,5 mA etinférieure à 1 000 mA.

Vous devez tenir compte des fuites de courant transitoires et permanentes à la terre,susceptibles de se produire au démarrage de l’équipement, lors de la sélection des dispositifsDDFT instantanés.

Vous devez sélectionner des disjoncteurs différentiels de fuite à la terre (DDFT) sensibles auximpulsions unidirectionnelles c.c. (classe A) et insensibles aux impulsions de couranttransitoires.

Notez également que les courants de fuite à la terre de la charge seront acheminés par cedispositif DDFT.

Cet équipement doit être mis à la terre conformément au code national de l’électricité.

! WARNINGRisk of electric shock. Can cause injury, property damage and death.Under typical operation and with all UPS doors closed, only normal safety precautions arenecessary. The area around the UPS system should be kept free of puddles of water, excessmoisture and debris.Special safety precautions are required for procedures involving handling, installation andmaintenance of the UPS system and the internal batteries (internal batteries accommodatedby the 10-30kVA frame only). Observe all safety precautions in this manual before handlingor installing the UPS system as well as during all maintenance procedures. Observe allbattery safety precautions before working on or near the battery.This equipment contains several circuits that are energized with high voltage. Onlytest equipment designed for troubleshooting should be used. This is particularly true foroscilloscopes. Always check with AC and DC voltmeters to ensure safety before makingcontact or using tools. Even when the power is turned Off, dangerously high electric chargesmay exist within the UPS.All power and control wiring should be installed by a qualified electrician. All powerand control wiring must comply with the NEC and applicable local codes.ONLY qualified service personnel should perform maintenance on the UPS system.When performing maintenance with any part of the equipment under power, servicepersonnel and test equipment should be standing on rubber mats. The service personnelshould wear insulating shoes for isolation from direct contact with the floor (earth ground).Never work alone, even if all power is removed from the equipment. A second person shouldbe standing by to assist and summon help in case an accident should occur.

Page 8: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite® TRX™ BDC™ 4

NOTICERisk of improper ground connection. Can cause equipment damage.Ground connection is essential before connecting the input supply. This equipment must be grounded in accordance with local electrical codes. Maximum load must not exceed that shown on the UPS rating label.

NOTICERisk of improper electromagnetic shielding. Can cause radio communication interference.This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the user is solely responsible for correcting.

! AVERTISSEMENTRisque de décharge électrique pouvant causer des blessures, des dommages matériels et même la mort.

Les précautions de sécurité habituelles suffisent lorsque le système ASC est en mode de fonctionnement normal et que toutes les portes sont fermées. La zone entourant le système ASC doit être exempte de flaques d’eau, d’humidité excessive et de débris.

Des précautions de sécurité spéciales sont requises pour les procédures associées à la manutention, à l’installation et à l’entretien du système ASC. Observez toutes les précautions de sécurité décrites dans le présent manuel avant de manipuler ou d’installer le système ASC, ainsi que pendant toutes les procédures d’entretien.

Cet équipement comporte plusieurs circuits à haute tension. Seuls des équipements d’essai conçus pour le dépannage doivent être utilisés. Cette mise en garde couvre notamment les oscilloscopes. Utilisez toujours des voltmètres c.a. et c.c. pour vérifier les tensions avant d’établir un contact ou d’utiliser des outils. Des tensions dangereusement élevées peuvent demeurer dans le système ASC même une fois l’alimentation coupée.

Tous les câbles d’alimentation et de contrôle doivent être installés par un électricien qualifié. Tous les câbles d’alimentation et de contrôle doivent être conformes au Code national de l’électricité des États-Unis (NEC) et celui du Canada, ainsi qu’aux codes locaux en vigueur.

L’entretien du système ASC ne doit être confié qu’à des professionnels qualifiés.

Les responsables de l’entretien et l’équipement d’essai doivent reposer sur des tapis de caoutchouc lors de toute intervention sur une pièce d’équipement sous tension. Les responsables de l’entretien doivent porter des chaussures isolantes pour prévenir tout contact direct avec le plancher.

Ne travaillez jamais seul, même si toute l’alimentation d’entrée est coupée de l’équipement. Une seconde personne devrait toujours être présente pour porter assistance ou chercher de l’aide en cas d’accident.

Page 9: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

5 Dual-Lite® TRX™ BDC™

GLOSSARY OF SYMBOLS

Risk of electrical shock

Indicates caution followed by important instructions

AC input

AC output

Requests the user to consult the manual

Indicates the unit contains a valve-regulated lead acid battery

Recycle

DC voltage

AC voltage

Equipment grounding conductor

Bonded to ground

!

i

PbH2SO4

- +

R

Page 10: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite TRX BDC

Dual-Lite® TRX™ BDC™ 6

1.0 DUAL-LITE TRX BDC

The Dual-Lite TRX BDC is designed to operate in UPS normal mode, static bypass mode and maintenance mode. The Dual-Lite TRX BDC offers 10-30kVA capacity to match the associated Dual-Lite TRX frame offerings. Each of the Dual-Lite TRX BDC capacities offer optional input 208V and 480V internal transformers.

Figure 1 Single input UPS with external Dual-Lite TRX BDC with optional internal transformer—Typical configuration

1.1 Normal (UPS) Mode

While the Dual-Lite TRX BDC is in Normal mode (MBB open; BIB/MIB closed), the UPS is supplying the connected load with continuous, high-quality AC power. In this mode of operation, the load is protected by the UPS.

1.2 Maintenance Mode

When the Dual-Lite TRX BDC is in Maintenance mode (MBB closed; BIB/MIB open), it provides an alternate path for power to the connected equipment should the UPS need to be taken out of service for limited maintenance or repair. In this mode of operation, no power is supplied to the UPS and the load is NOT protected by the UPS.

MBB

BIB MIB

BYPASS DISTRIBUTION CABINET

STATIC BYPASS

UPS CABINET

BIB - Bypass Isolation BreakerMBB - Maintenance Bypass BreakerMIB - Maintenance Isolation Breaker* External Overcurrent Protection by Others

AC Output208V

4 Wire + GND

Local GroundingElectrode

See Note 1

* SystemAC Input

3 Wire + GND

BATTERY

NOTES 1. Install in accordance with national and local electrical codes.2. Input and bypass must share the same single source.3. UPS system input and output cables must be run

in separate conduits.4. Control wiring must be run in separate conduits.5. Transformer available: 208, 480 input.

Field-Supplied Wiring

Page 11: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite TRX BDC

7 Dual-Lite® TRX™ BDC™

1.3 Locating the Cabinet

This Dual-Lite TRX BDC may be mounted to the right of the UPS. Ensure that the unit is in a well-ventilated area and that there is clearance for access to the switches and cable connections as required by national and local codes.

1.4 Cable Installation

1.4.1 Wiring Preparation

Be sure that the unit is not connected to any AC utility power source or UPS before installing any wiring to this unit. This Dual-Lite TRX BDC should be installed by a qualified / certified electrician.

Removing the Cover Plates

Plates cover the input and output terminals on the front of the Dual-Lite TRX BDC (see Figure 2). Remove these and keep the screws and plates for reinstallation.

Figure 2 Dual-Lite TRX BDC—Access plate removed

1.4.2 Power Cable InstallationRefer to Table 42 when selecting cables.

! WARNINGRisk of electrical shock and arc flash. Can cause property damage, injury and death.

Read this section thoroughly before attempting to install wiring to this unit. Read andcomply with all warnings and cautions in this manual.

NOTETransient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground current detection devices because these will carry the earth leakage currents of both the UPS equipment and the load.

Page 12: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite TRX BDC

Dual-Lite® TRX™ BDC™ 8

1.4.3 Input/Output WiringFollow the steps below to connect the input wiring:

1. Locate the input wiring access (top or bottom access), remove the conduit landing plate and punchthe appropriate size hole for the size conduit being used. Pull the three/four input wires throughit, allowing some slack for installation. For cabinets that are located to the immediate left of theUPS, the access plate is on the lower right of the cabinet. Remove the access plate and verify thatthe edge guarding is installed and intact.

2. Secure the conduit to the access plate of the Dual-Lite TRX BDC.3. Input power cables connect to the system input bus.4. Connect the ground (earth) wire to the earth busbar and tighten it to 428 lb-in (48Nm) for M12

bolt.5. Locate UPS input and output cables and access panel to UPS on lower right side.

6. Connect the system ground cable between the Dual-Lite TRX BDC and UPS and tighten theconnections to 428 lb-in (48Nm) for M12 bolt.

7. Connect the system input cables between the Dual-Lite TRX BDC “UPS Input” Busbars (A-B-C Nterminals) and UPS input busbars (A-B-C N terminals) and tighten the connections to 428 lb-in(48Nm) for M12 bolt.

8. Connect the system output cables between the Dual-Lite TRX BDC “UPS Output” Busbars (A-B-CN terminals) and UPS output busbars (A-B-C N terminals) and tighten the connections to 428 lb-in (48Nm) for M12 bolt.

9. Connect TB1 from the Dual-Lite TRX BDC to J23, J24 and J26 on the Dual-Lite TRX.

NOTICERisk of improper wiring connection. Can cause equipment damage.The control wire must be installed to ensure proper operation of the system and fully protect the load when switching between bypass cabinet and UPS.

NOTEInput wiring must be installed using conduit if cabinet is not mounted to the immediate right of the UPS.

NOTEIf the Dual-Lite TRX BDC is not to be bolted to the UPS, use either top or bottom access plate.

Page 13: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite TRX BDC

9 Dual-Lite® TRX™ BDC™

NOTES1. All interconnection hardware supplied by Dual-Lite.2. AC connections must be made to the UPS module before attaching Dual-Lite TRX BDC to UPS

module.3. All cabling will be field-supplied when a Dual-Lite TRX BDC is configured as a stand-alone

cabinet.4. Dual-Lite TRX BDC’s must attach to the right side only of the Dual-Lite TRX UPS.5. Refer to the individual drawing of each piece of equipment for additional details.

1.4.4 Accessory Fuses and Back-Feed Breaker Wiring

The back-feed breaker fuse block provides power to trip the BIB breaker. It is at the lower right of the input/output panel on the front of the Dual-Lite TRX UPS. See Figure 3 for fuse block locations.

Figure 3 Accessory fuses

The back-feed breaker fuse block provides 120V and is connected to the UPS output (L-N). The fuse is rated for 8A. Figure 4 show the back-feed breaker wiring; the connections are made to the static bypass assembly as shown in Table 1.

For additional details about the FH1 fuse block refer to the Dual-Lite TRX UPS manuals, SL-25648 and SL-25650. The manuals ship with the UPS and are available from Dual-Lite.

Table 1 Control wiring for Dual-Lite TRX to Dual-Lite TRX BDC

From To

Dual-Lite TRX UPS BypassModule (X9 J23, J24 and J26)

Dual-Lite TRX BDCTerminal Strip (TB1)

J24-3 TB1-7

FH1-B TB1-8

J26-15 TB1-6

J26-13 TB1-5

J26-11 TB1-4

J26-9 TB1-3

J23-4 TB1-11

J23-6 TB1-12

FH1-N J24-1

Refer to Figure 3 for the location of fuse block FH1 and to Figure 7 for the location of J23, J24 and J26

Back-Feed Breaker Fuse Block, FH1

Fuse Blocks areon the front of the Dual-Lite TRX UPS.

Page 14: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite TRX BDC

Dual-Lite® TRX™ BDC™ 10

Figure 4 Dual-Lite TRX BDC wiring with transformer option, single input

NO

TES

1. W

iring

furn

ishe

d by

fact

ory.

2. C

usto

mer

-furn

ishe

d gr

ound

ing

elec

trode

cond

ucto

r to

be in

stal

led

in a

ccor

danc

ew

ith N

atio

nal E

lect

ric C

ode

Arti

cle

250-

26.

WIR

ING

LE

GE

ND

Fact

ory-

Sup

plie

d W

iring

Fact

ory

- or F

ield

-Sup

plie

d

Cus

tom

erIn

put N

eutra

l

Cus

tom

er M

ain

Gro

und

Bus

bar

Gro

und

Ele

ctro

deS

ee N

ote

2

Isol

atio

nTr

ansf

orm

er

BIB

W07

W08

W09

W04 W

05 W06

Det

ail A

Det

ail B

To P

anel

boar

dor

Sub

feed

DE

TAIL

A

DE

TAIL

B

6075

09P

g. 2

, Rev

. 3

W88

W89

W90

AC

Out

put

AC

Inpu

t

Gro

und

toU

nit F

ram

e

Gro

und

toU

nit F

ram

e

Util

ityIn

put

MB

B

Out

put N

eutra

l

W85 W

83

W10

W84

W86 W

87

MIB

AU

X.

T

H1

W01

W02

W03

H2

H3

X-A

X-B X-C

X0

A B C

A B C mN

PE

C

N/ON/C

AU

X.

C

N/ON/C

UP

S

Fuse

G15

, G61

, G71

, G81

G91

, G93

, G10

1 O

nly

Ref

er t

o

Tab

le1

Ref

er t

o

Tab

le1

Page 15: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite TRX BDC

11 Dual-Lite® TRX™ BDC™

1.5 Bolting Cabinets Together

1. Line up cabinets so that mounting holes are aligned.

Figure 5 Bolting Dual-Lite TRX UPS to a Dual-Lite TRX BDC

2. Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either theUPS side or from the Dual-Lite TRX BDC side, whichever is more convenient.

NOTEUPS wiring must be completed before the cabinets are bolted together.

! WARNINGRisk of heavy units tipping over while being moved. Can cause property damage, injury anddeath.

The Dual-Lite TRX BDC and battery cabinets must be properly prepared and secured forlifting. Improper lifting may cause the cabinets to fall, causing equipment damage, personalinjury and death.

Dual-Lite recommends lifting the units with one of the following methods:

• Installing four eyebolts in the factory-fabricated holes, one at each corner of the unit,attaching cables or similar strapping to the eyebolts and lifting with a suitable mechanism.

• Placing suitable straps on the Dual-Lite TRX BDC or battery cabinet. The straps must gounder the unit to be lifted.

A

DETAIL A

WasherFlat, M10

WasherSplit, M10

Hex Head Bolt,M10 x 30mm

Place cabinets so mounting holes are aligned.A bolt from the adjacent cabinet may be screwed into the threaded top hole, or a bolt may be inserted through the lower hole and screwed into the threaded hole in the adjacent cabinet.

Page 16: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite TRX BDC

Dual-Lite® TRX™ BDC™ 12

1.5.1 Floor Installation

If the Dual-Lite TRX BDC is to be placed on a raised floor, the UPS should be mounted on a pedestal that will support the equipment point loading. Refer to the Dual-Lite TRX UPS manual, SL-25648 or SL-25650, to design this pedestal.

1.5.2 Cable Entry

Cables can enter the Dual-Lite TRX BDC from the top or bottom through removable metal plates.

Some plates have factory-punched holes and others are designed to allow personnel to punch holes for fitting and securing the conduit. Once the conduit holes are punched, these plates should be reattached to the UPS. The conduit size and wiring method must be in accordance with all local, regional and national codes and regulations, including NEC ANSI/NFPA 70.

1.5.3 Optional Cabinets

The Dual-Lite TRX BDC must be bolted to right side of the Dual-Lite TRX (see Figure 6).

The Dual-Lite TRX BDC must be cabled and bolted to the Dual-Lite TRX before the UPS and bypass distribution cabinet are moved into their final position. Connect input wiring to the Dual-Lite TRX BDC ONLY after the units are internally cabled and positioned.

Battery cabinets may be bolted only to the left side of the Dual-Lite TRX; see Figure 6.

Figure 6 Cabinet arrangement

! AVERTISSEMENTLe centre de gravité élevé des appareils présente un risque de renversement lors desdéplacements, pouvant entraîner des dommages matériels, des blessures et même la mort.

Les armoires Dual-Lite TRX BDC et de batterie doivent être correctement préparées etsécurisées avant d’être levées. Un mauvais levage peut faire tomber les armoires, causant desdommages à l’équipement, des blessures, voire la mort.

Dual-Lite recommande de soulever les unités en suivant l’une des méthodes suivantes :

• En installant quatre anneaux de levage dans les ouvertures fabriquées en usine, avec unanneau dans chaque coin de l’appareil, pour ensuite fixer les câbles ou sangles aux anneauxafin d’effectuer le levage à l’aide d’un mécanisme approprié.

• En plaçant des sangles convenables sur l’armoire Dual-Lite ou de batterie. Les sanglesdoivent passer sous l’unité à soulever.

NOTEWhen installing the UPS, the customer must provide a disconnect with overcurrent protection at the output of the UPS.

Dual-Lite TRX UPS connected onlyto Dual-Lite TRX BDC

(The Dual-Lite TRX BDC must be on right side of the Dual-Lite TRX UPS)

Dual-Lite TRX UPS connected to Dual-Lite TRX BDC and Battery Cabinets

(BDC must be on right side of the Dual-Lite TRX)(Battery Cabinets must be on the left side of the Dual-

Lite TRX UPS)

ALL UNITS VIEWED FROM ABOVE

Dual-Lite TRX UPS

Dual-Lite TRX

Bypass Distribution

Cabinet

Dual-Lite TRX

Bypass Distribution

Cabinet

Dual-Lite TRX UPS

Battery Cabinet

Battery Cabinet

Page 17: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite TRX BDC

13 Dual-Lite® TRX™ BDC™

1.6 Dual-Lite TRX UPS Bypass Assembly

Figure 7 Dual-Lite TRX UPS bypass assembly connections

The Static bypass assembly has three intel slot interface card bays and connections for ancillary cabinets (Dual-Lite TRX BDC and battery) and for options.

1.6.1 Dual-Lite TRX BDC Interface

The Dual-Lite TRX BDC interface is on the Auxiliary Terminal Block at J26. Refer to Figure 8 for circuit details.

Table 2 Dual-Lite TRX BDC interface

Position Name Description

J26.1 Q1 STA Main input switch status signal

J26.5 Q2 STA Bypass input switch status signal

J26.9 Q3 STA External maintenance switch status signal

J26, 3, 7, 9 GND Ground for dry contacts

These contacts cannot be active unless they are set via software.

Dual-Lite Intel Slot Bays 1, 2, 3

Ready Switch

J1 J19 J20 J21 J22 J26 J23 J24 J25

Page 18: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite TRX BDC

Dual-Lite® TRX™ BDC™ 14

Figure 8 Input dry contacts—J26

Figure 9 Output dry contacts and EPO wiring

NOTEAll auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 80 and 200 feet (25-60m), respectively.

NOTERefer to Table 1 for the Dual-Lite TRX BDC wiring.

J26

24

68

1012

1416

1820

2224

2628

3032

GEN MODE

+12V_DRY

GND_DRY

GND_DRY

TMP BATT IN_

RESERVED

ENV_DET

GND_DRY

CHG SHUT

GND_DRY

RESV1

UT2 485+

UT2 485-

GND_DRY

NC

NC

13

57

911

1315

1719

2123

2527

2931

Q1 STATUS

GND_DRY

Q2 STATUS

GND_DRY

Q3 STATUS

GND_DRY

Q5 STATUS

GND_DRY

GND_DRY

RESV2

RESV3

GND_DRY

UT1 485+

GND_MON

UT1 485-

NC

BFP_O

J23J25

J24

BFP_S

BFP_C

INV_O

INV_S

INV_C

MAIN_O

MAIN_S

MAIN_C

MFP_O

MFP_S

MFP_C

RESV_O

RESV_S

RESV_C

RESV_O

RESV_S

RESV_C

13

51

35

13

5

24

62

46

24

6

Page 19: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Dual-Lite TRX BDC

15 Dual-Lite® TRX™ BDC™

Table 3 Output dry contact relays

Port Pin Name Description

J24

1 MFP_O Rectifier back-feed normally open contact. Open when there is no back-feed.

3 MFP_S Rectifier back-feed common contact.

5 MFP_C Rectifier back-feed normally closed contact. Closed when there is no back-feed.

J23

2 INV_O Inverter state normally open contact. Open when the inverter is abnormal.

4 INV_S Inverter state common contact.

6 INV_C Inverter state normally open contact. Closed when the inverter is normal.

J23

1 BFP_O Bypass back-feed normally open contact. Open when there is no back-feed.

3 BFP_S Bypass back-feed common contact.

5 BFP_C Bypass back-feed normally closed contact. Closed when there is no back-feed.

J24

2 MAIN_O Rectifier input state normally open contact. Open when the rectifier is abnormal.

4 MAIN_S Rectifier input state common contact.

6 MAIN_C Rectifier input state normally closed contact. Closed when the rectifier is normal.

Page 20: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Installation Drawings

Dual-Lite® TRX™ BDC™ 16

2.0 INSTALLATION DRAWINGS

Figure 10 Dual-Lite TRX BDC with optional SKRU and transformer

KeyOperator

Lamp

KirkKeys MBB

BIB MIB

SystemInputBus

TransformerOption for 208Vor 480V Input

Neutral BusGround Bus

FRONT VIEWDoor Removed

FRONT VIEWWith Covers

RIGHT SIDE VIEWPanel Removed

Page 21: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Installation Drawings

17 Dual-Lite® TRX™ BDC™

Figure 11 Busbars—Dual-Lite TRX BDC

1.38"(35mm)

1.38" (35mm)

1.38" (35mm)

1.38" (35mm)

2.44" (62mm)

2.44" (62mm)

UPS BusØ 0.44"(11mm)Typical

Ø 0.44"(11mm)Typical

Shown withOptional SKRU

Ø 0.44"(11mm)Typical

1.75"(44.5mm)TypicalAll Busbars

Ø 0.56"(14mm)Typical

Ø 0.56"(14mm)Typical

Ø 0.56"(14mm)Typical

System Input BusSee Detail B

DETAIL A

DETAIL BIso-View Front Left

Corner Post Removed

Input/OutputBus, Typical

1.5" x 8.9" (38mm x 227mm)

InputBreaker

InputGround

Bus

Ground Bus5" x 4" (127mm x 102mm)

Neutral Bus5" x 8.9" (127mm x 227mm)

SystemInput

Busbarat Rear, Typical

SystemInput

Connections

NeutralInput/OutputConnections

Page 22: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Installation Drawings

Dual-Lite® TRX™ BDC™ 18

Figure 12 Lineup arrangement, Dual-Lite TRX with Dual-Lite TRX BDC

47.6" (1208mm)23.6"

(600mm)23.6"

(600mm)

78.7"(2000mm)

UPS BDCFRONT VIEW

NOTES1. Dimensions are in inches (mm).2. 24" (610mm) minimum clearance above unit.

36" (914mm) front access required for service.For seismic mounting only 5" (102mm) in rearfor mounting brackets

3. Keep cabinet within 15 degrees of vertical.4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.5. Unit bottom is structurally adequate for forklift handling.6. Control wiring and power wiring must be run in

separate conduits.7. All wiring is to be in accordance with national and

local electrical codes.8. Bypass distribution cabinet must be positioned on the right

side of the UPS.

Page 23: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Installation Drawings

19 Dual-Lite® TRX™ BDC™

Figure 13 Outline drawing, Dual-Lite TRX BDC for Dual-Lite TRX, 10-30kVA

1. All dimensions are in inches (mm). 2. 24" (610) minimum clearance above unit; 36" (914) front access required for service. 3. Keep cabinet within 15 degrees of vertical. 4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace. 5. Control wiring and power wiring must be run in separate conduits. 6. All wiring is to be in accordance with national and local electrical codes.

Cable Entry Area11.4" x 13.2"(290 x 335mm)

Cable Entry Area6.2" x 13.2"(57 x 335mm)

6.5" (164mm)Outside Panel

6.5" (164mm)Outside Panel

11.5" (292mm)Outside Panel

5.5"(140mm)

34.6"(870mm)

23.7"(602mm)

23.6"(600mm) 39.5" (1000mm)

78.7"(2000mm)

28.3"(719mm)BracketCenters

6.4" (162mm)Outside Panel

24"(609mm)FRONT

RIGHT SIDE

UAM06008Rev. 5

LevelingFeet

BOTTOM VIEW

TOP VIEWMaximum

Door Swing - 120°

Page 24: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Installation Drawings

Dual-Lite® TRX™ BDC™ 20

Figure 14 Dual-Lite TRX BDC transformer location

Transformer

REAR OF CABINETRIGHT SIDE

Page 25: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Installation Drawings

21 Dual-Lite® TRX™ BDC™

See Table 1 for additional details.

Table 4 Wiring for Dual-Lite TRX to Dual-Lite TRX BDC

Run From To Conductors

A Utility AC source BDC System Input Bus Phase A, B, C

B Utility AC Source BDC System Input Bus Neutral

C BDC Bypass Isolation Breaker UPS Main Input Phase A, B, C

D BDC Bypass Isolation Breaker UPS Main Input Neutral

E UPS Output Dual-Lite TRX BDC Maintenance Isolation Breaker

Phase A, B, C

F UPS Output Dual-Lite TRX BDC Maintenance Isolation Breaker Neutral

G BDC Panelboard Load AC Connection Phase A, B, C

H BDC Panelboard Load AC Connection Neutral

I Utility AC Source All Ground Connections Ground

J BDC Terminal Block TB1 UPS Static Bypass Module J23, J24 and J26Wiring for KO on Dual-Lite TRX BDC

NOTEInterconnection wiring between the UPS and bypass distribution cabinet is supplied by Dual-Lite when the Dual-Lite TRX BDC and Dual-Lite TRX UPS are ordered as a system.

Table 5 Hardware torque values

Hardware Two Belleville Washers

M10 (3/8") 240 lb-in. (27 Nm)

M12 (1/2") 428 lb-in. (48Nm)

Page 26: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Installation Drawings

Dual-Lite® TRX™ BDC™ 22

Figure 15 One-line diagram, 208V single input 10-30kVA UPS with three-breaker Dual-Lite TRX BDC and input isolation transformer

MBB

BIB MIB

BYPASS DISTRIBUTION CABINET

STATIC BYPASS

UPS CABINET

BIB - Bypass Isolation BreakerMBB - Maintenance Bypass BreakerMIB - Maintenance Isolation Breaker* External Overcurrent Protection by Others

AC Output208V

4 Wire + GND

Local GroundingElectrode

See Note 1

* SystemAC Input

3 Wire + GND

BATTERY

NOTES 1. Install in accordance with national and local electrical codes.2. Input and bypass must share the same single source.3. UPS system input and output cables must be run

in separate conduits.4. Control wiring must be run in separate conduits.5. Transformer available: 208, 480 input.

Field-Supplied Wiring

Page 27: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Specifications

23 Dual-Lite® TRX™ BDC™

3.0 SPECIFICATIONS

The following are approved branch breakers for the panel boards used in the Dual-Lite TRX BDC.

Listed (DIVQ), Schneider Electric Square D branch circuit breakers:

• Type QOB, rated 22 kA, 150 A maximum• Type QO, rated 22 kA, rated 100 A maximum• Type QOB, rated 10 kA, rated 100 A maximum• Type QO, rated 10 kA, rated 100 A maximum

Table 6 Physical standards and parameters

Bypass Distribution Cabinet Parameters Values

Standard Color Black (ZP-7021)

Front Door Opening (for serviceability) More than 180°

Degree of Protection for UPS Enclosure IP 20 (with and without front door open)

Minimum Clearance, Top 24" (610mm)

Minimum Clearance, Back 0" (5" [127mm] when seismic brackets are used)

Minimum Clearance, Sides 0"

Cable Entrance Top or Bottom

Standards & Conformities UL 71778 5th Ed.; CSA 22.2 107.3-14

FCC Part 15, Class A; ISTA Procedure 1H; WEEE;IBC 2012/CBC 2010

Environmental

Storage Temperature Range, °F (°C) -13°F to 158°F (-25°C to 70°C)

Operating Temperature Range, °F (°C) 32°F to 104°F (0 to 40°C)32°F to 86°F (0-30°C) when seismic brackets are used

Relative Humidity up to 95% Non-Condensing (Operating and Non-Operating)

Maximum Altitude Above MSL, ft (m) 4920 (1500) (as per IEC 62040/3) -

1% Maximum kW derate / 100m rise between 1500-3000m

Table 7 Mechanical characteristics, Dual-Lite TRX BDC, 10-30kVA

Dimensions, W x D x H, in (mm) 23.625 x 39.375 x 78.73

Frame Sizemm

RatingkVA

Weight, lb. (kg)

No TransformerNo Distribution

No Transformer WithPanel Board or

Subfeed BreakerWith Transformer

No Distribution

With Transformerand Panel Board or

Subfeed Breaker

600 10-30 525 (238) 625 (283) 914 (415) 1014 (460)

Add 27 lb. (12 kg) for monitoring.

Table 8 Dual-Lite TRX BDC heat dissipation

Dual-Lite TRXBDC Rating, kVA

Dual-Lite TRX BDCHeat Dissipation

208:208 TransformerBTU/Hr (kW)

10 1966 (0.576)

15 2504 (0.734)

20 2938 (0.861)

30 4847 (1.421)

Page 28: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Specifications

Dual-Lite® TRX™ BDC™ 24

3.1 Electrical Characteristics

NOTEThe breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect breaker must be provided for AC input, Bypass and AC output. Recommended cable sizes are suitable for operation at a maximum temperature of 104°F (40°C).

Table 9 Dual-Lite TRX BDC input currents, single input, main, without transformer

Voltage3-Ph, 60 Hz

BDCRating,

kVA

SystemInput

CurrentA, Max Phase

RecommendedUpstream

Protection, A

75°CWire

CurrentA, Total

CopperWire

AluminumWire

BoltSize

208/120 10 34 3W + N + G 45 65 (1) #6 (1) #4 M12

208/120 15 51 3W + N + G 70 85 (1) #4 (1) #2 M12

208/120 20 68 3W + N + G 90 115 (1) #2 (1) 1/0 M12

208/120 30 102 3W + N + G 150 175 (1) 2/0 (1) 4/0 M12

Table 10 Dual-Lite TRX BDC output currents

Voltage3-Ph, 60Hz)

BDCRating, kVA

SystemOutputCurrentA, Max Phase

RecommendedUpstream

Protection, A

75°CWire

CurrentA, Total

CopperWire

AluminumWire

BoltSize

208/120 10 28 3W + N + G 40 50 (1) #6 (1) #4 M12

208/120 15 42 3W + N + G 60 85 (1) #4 (1) #2 M12

208/120 20 56 3W + N + G 70 115 (1) #2 (1) #2 M12

208/120 30 83 3W + N + G 110 130 (1) 1/0 (1) 2/0 M12

Table 11 Recommended lug sizes (compression type) M12, 1/2" bolt

Cable SizeT&B Copper

Two HoleT&B Aluminum

Two Hole

#6AWG 256-030695-868 —

#4AWG 256-030695-733 —

#2-3AWG 54811BE —

#1AWG 54857BE —

#1/0AWG 256-30695-593 —

#2/0AWG 54862BE 60238

#3/0AWG 54864BE 60244

#4/0AWG 54866BE 60250

250kcmil 54868BE 60256

300kcmil 54870BE 60262

350kcmil 54872BE 60267

400kcmil 54874BE 60269

500kcmil 54876BE 60273

600kcmil 54878BE 60275

700kcmil 54879BE 60277

750kcmil 54880BE 60278

Page 29: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Specifications

25 Dual-Lite® TRX™ BDC™

3.2 Torque Requirements

All electrical connections must be tight.

Tables 12 and 13 provide the torque values for the connections to the Dual-Lite TRX BDC. Use these values unless the equipment is labeled otherwise.

Table 12 Busbar torque for power wiring

Bolt Shaft SizeTorque

Lb-in (Nm)

3/8" (M10) 192 (22)

1/2" (M12) 428 (48)

Table 13 Terminal block torque with compression lugs for control wiring

AWG Wire Sizeor Range

TorqueLb-in (Nm)

#22 - #14 3.5 to 5.3 (0.4 to 0.6)

NOTERefer to the manufacturer’s data for proper torque for circuit breaker power connections.

Table 14 Breaker torque

ABB Nm Siemens Nm

Tmax2 7.0 D Frame 5.5

Tmax3 8.0 F Frame 22.0

Tmax5 25.0 J Frame 31.0

Table 15 Electrical data—Dual-Lite TRX BDC, 480VAC input, 208VAC output, single input, with 480V:208V transformer

Dual-LiteTRX BDC

RatingkVA

MaximumSystem Input

Current, A Phase

RecommendedUpstream

Protection, A

75°C WireCurrent A

TotalCopper

WireAluminum

Wire Bolt Size

10 15 3W + G 20 40 (1) #8 (1) #8 M12

15 23 3W + G 30 40 (1) #8 (1) #8 M12

20 31 3W + G 40 40 (1) #8 (1) #8 M12

30 46 3W + G 60 65 (1) #6 (1) #4 M12

See Notes on Tables on page 26.

Table 16 Electrical data—Dual-Lite TRX BDC, 208VAC input, single input, with 208V:208V transformer

Dual-LiteTRX BDC

RatingkVA

MaximumSystem Input

Current, A Phase

RecommendedUpstream

Protection, A

75°C WireCurrent A

TotalCopper

WireAluminum

WireBoltSize

10 36 3W + G 45 65 (1) #6 (1) #4 M12

15 53 3W + G 70 85 (1) #4 (1) #2 M12

20 71 3W + G 90 100 (1) #3 (1) #1 M12

30 107 3W + G 150 175 (1) 2/0 (1) 4/0 M12

See Notes on Tables on page 26.

Page 30: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

Specifications

Dual-Lite® TRX™ BDC™ 26

Notes on Tables

Notes apply to Tables 15 and 16.

1. Nominal input current (considered continuous) is based on full rated output load maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous). Continuous and noncontinuous current are defined in NEC 100. Recommended overcurrent protection is based on 80% rated devices.*The recommended overcurrent protection represents 125% of nominal full load current (continuous) per NEC 215.

2. Maximum input current is controlled by the current limit setting.3. Recommended AC input external overcurrent protection is based on 80% rated devices and

maximum input current limit setting.4. Recommended AC output external overcurrent protection is based on 80% rated devices and full

rated output current.5. Nominal battery voltage is shown at 2 volts per cell.6. Input power factor of 0.99 is used for the calculations.

Page 31: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous
Page 32: Dual-Lite TRX BDC · Dual-Lite® TRX™ BDC™ 2 WARNING Risk of electric shock. Can cause equipment damage, injury and death. As with other types of high power equipment, dangerous

DL-25653_REV0_03-16

Dual-Lite® TRX™ UPSUser Manual–10-30kVA, 50/60Hz