dt seet prosec ii+ features - raycap · prosec ii+ the prosec ii+ is a surge counter with...

1
ProSEC II+ The ProSEC II+ is a surge counter with additional functionality. Besides counting the number of surges, it also logs the hour and date of each surge counted. This additional time and date logging function makes it is possible to pinpoint the exact time of every surge and correlate it with equipment and power supply problems inside of a facility or structure. Features LCD screen displays number of surges, hour, minute and date of surge event Buttons for TIME/DATE setting and log viewing Replaceable battery, lifetime up to two years Easy to install, snap-on surge current sensor Complies with: IEC/EN 62561-6 Technical Data Electrical ProSEC II+ Order Code 130 100 Threshold Current (8/20 µs) [l tc ] 50 A Maximum Counting Discharge Current (8/20 µs) [I mcw ] 50 kA Power Supply Replaceable CR17335 lithium battery Lifetime up to two years Maximum Events Logged 999 Mechanical Mounting Method EN 60715 35 mm DIN rail Maximum Wired Diameter through Current Sensor 0.55" [14 mm] Sensor Cable 19.7" [0.5 m] Temperature Range -4 °F to +158 °F [-20 °C to +70 °C] Environmental Ingress Protection (IP) Rating IP 20 Enclosure Material Thermoplastic; Extinguishing degree UL 94 V-0 Enclosure Dimension (L × W × D) 3.54" × 1.42" × 2.64" [90 × 36 × 67 mm] Dimensions DIN 43880 2 TE Packaging Dimensions (L × W × D) 4.33" × 1.65" × 3.27" [110 × 42 × 83 mm] Weight .33 lbs [150 g] Standards Compliance & Certifications Standards IEC 62561-6 Certification RoHS, CE Product Diagram Typical Installation [36.0] 1.42 [67.0] 2.64 [90.0] 3.54 L1 L2 L3 N 10 cm minimum surge current sensor Set OK IP20 I=50A (8/20) I=50kA (8/20) ProSEC II+ Surge Counter www.raycap.com DATA SHEET [mm] inches © 2017 Raycap All rights reserved. G29-00-152 17041

Upload: others

Post on 27-Apr-2020

18 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DT SEET ProSEC II+ Features - Raycap · ProSEC II+ The ProSEC II+ is a surge counter with additional functionality. Besides counting the number of surges, it also logs the hour and

ProSEC II+

The ProSEC II+ is a surge counter with additional functionality. Besides counting the number of surges, it also logs the hour and date of each surge counted. This additional time and date logging function makes it is possible to pinpoint the exact time of every surge and correlate it with equipment and power supply problems inside of a facility or structure.

Features

• LCD screen displays number of surges, hour, minute and date of surge event• Buttons for TIME/DATE setting and log viewing• Replaceable battery, lifetime up to two years• Easy to install, snap-on surge current sensor• Complies with: IEC/EN 62561-6

Technical Data

Electrical

ProSEC II+ Order Code 130 100

Threshold Current (8/20 µs) [ltc] 50 A

Maximum Counting Discharge Current (8/20 µs) [Imcw] 50 kA

Power Supply Replaceable CR17335 lithium battery Lifetime up to two years

Maximum Events Logged 999

Mechanical

Mounting Method EN 60715 35 mm DIN rail

Maximum Wired Diameter through Current Sensor 0.55" [14 mm]

Sensor Cable 19.7" [0.5 m]

Temperature Range -4 °F to +158 °F [-20 °C to +70 °C]

Environmental Ingress Protection (IP) Rating IP 20

Enclosure Material Thermoplastic;Extinguishing degree UL 94 V-0

Enclosure Dimension (L × W × D) 3.54" × 1.42" × 2.64"[90 × 36 × 67 mm]

Dimensions DIN 43880 2 TE

Packaging Dimensions (L × W × D) 4.33" × 1.65" × 3.27"[110 × 42 × 83 mm]

Weight .33 lbs [150 g]

Standards Compliance & Certifications

Standards IEC 62561-6

Certification RoHS, CE

Product Diagram

Typical Installation

[36.0]1.42

[67.0]2.64

[90.0]

3.5

4

L1L2L3N

PROTEC C PROTUBE CPROTEC CPROTEC C

10 cmminimum

surgecurrentsensor

Set OK

IP20Itc =50A (8/20)Imcw=50kA (8/20)

ProSEC II+

Surge Counter

www.raycap.com

DATA SHEET

[mm]inches

�© 2017 Raycap All rights reserved.

G29-00-152 17041