     HAZARD U AREACLASSIFICATIONDS/EN 60079-10-1 & UK

     

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    2/29

    BACKGROUND – DS/EN 60079-10-1

     –

    • rec ve ore o e rec ve o s ore

    • Danish Regulations (BEK 1480 + Guideline to that)

    • Norway: PSA Facilities Regulation (Guideline) points towards IEC

    61872-7 – which points towards IEC/EN 60079-10-1-

     •

    • Classify for flammable gasses, vapours and mists

    • Flammability: Dependent on flash point and design/service

    temperature

    Probability for fire/explosion:

    P(Release) x P(Ignition)

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    3/29

    AREA CLASSIFICATION – ZONING

    EN 60079-10-1 / IP 15

    Zone 0: The part of a hazardous area in which aflammable atmosphere is continuously present orpresent for long periods

    Zone 1: That part of a hazardous area in which aflammable atmosphere is likely to occur in normal

    Zone 2: That part of a hazardous area in which aflammable atmos here is not likel to occur in normaloperation, and if it occurs, it will only exist for a shortperiod

    Non-hazardous: areas that do not fall into any ofthe above (IS NOT ‘SAFE AREA’)

    3

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    4/29

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    5/29

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    6/29

    Definitions – EN 60079-10-1

    • Source of Release: A point of location from which a gas, vapour,

    mist or liquid may be released into the atmosphere so that an

    explosive gas atmosphere could be formed.

    • Grades of release: There are three basic grades of release, as

    explosive gas atmosphere being present:

    • Continous grade

    • Primary Grade

    • Secondary Grade

    • Degree of ventilation (natural / artificial):

    • Hi h ventilation VH 

    • Medium ventilation (VM)

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    7/29

    HAZARDOUS AREA CLASSIFICATION –

    GRADE OF RELEASE – IP 15 DEFINITIONS

    Continuous gra e re ease: A re ease t at is continuous or near y so, orthat occurs frequently and for short periods

    If it is likel to be resent for more than 1000 hours er ear.

    Primary grade release: a release that is likely to occur periodically oroccasionally in normal operations, i.e. a release which, in operating

    procedures is anticipated to occurIf it is likely to be present for between 10 to 1000 hours per year.

    Secondary grade release: A release that is unlikely to occur innormal operation and, in any event, will do so only infrequently and

    . .anticipated to occur. Such release may be of unknown size e.g.fracture of a drain or unknown size e.g. corrosion hole.

     

    7

      .

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    8/29

    ZONE – VENTILATION – GRADE OF RELEASE

    8

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    9/29

    Hazardous Area Classification Data Sheets

    Part I: Flammable Material List and data

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    10/29

    Hazardous Area Classification Data Sheets

    Part II: List of sources of release

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    11/29

    Hazardous Area Classification Drawings

    EN 60079-10-1, SEC 7.2

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    12/29

    WHY COMBINE EN 60079-10-1 WITH IP15

    • For continous & primary grades of release, the leak size is

    typically known.

    • We need some advise regarding size and types of leak sources for

    secondary grade of release – EN 60079-10-1 is very open on the.

     • e . to - - , . cope:

    For detailed recommendations regarding the extent of thehazardous areas in specific industries or applications, reference

    may be made to national or industry codes relating to thoseapplications.

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    13/29

    HAZARDOUS AREA CLASSIFICATION – IP 15

    Risk Target is 10-5 year

    For most offshore plants, where there is control of ignition sources

    outside the hazardous areas, IP 15’s LEVEL I is applied

    Does not concern major releases (spread of flamables morethan 30 m). These shall be minimised by design and operation

    .

    IP 15, sec. 5.4.5.1: “ As a guide, when there are more than 10 leak. .

    overlap), the area should be classified as zone 2” 

     deg. C to the handling/ambient temperature in the area.

    Followin : O en field naturall ventilated wind s eed 0.5 – 2.0 m s

    13

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    14/29

    POINT SOURCE

    14

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    15/29

    FLUID CATEGORY / CLASS

    Fluid

    Category

    Description

    A A flammable liquid that, on release, would vaporise rapidly and

    substantially.

    B A flammable liquid, not in Category A, but at a temperature

    sufficient for boiling to occur on release.

    C A flammable liquid, not in Categories A or B, but which can, onrelease be at a tem erature above its flash oint or form a

    flammable mist or spray.

    G(i) A typical methane-rich natural gas.

    G(ii) Refinery hydrogen.

    15

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    16/29

    FLUID CATEGORY - EXAMPLES

    Fluid Category

    Condensate / LPG: A

    Crude / unstabilized: BCrude / stabilized: C

    Wet/dry gas: G(i)

    Diesel: C

    Helifuel: C

    Hydraulic oil: C

    16

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    17/29

    RELATIONSHIP – CLASS & CATEGORY

    17

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    18/29

    IP 15 PROCEDURE – SECONDARY GRADE

    RELEASE

    18

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    19/29

    IP 15 – LEVEL I, II & III – FLANGES & VALVES

    For offshore oil/gas installations, where there is a strong control of

    ,

    selected.

    19

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    20/29

    CLASSIFICATION AT SPECIFIC EQUIPMENT

    Fig 1A. Pump mounted on plated deck – high integrity pump (typically double mechanical seals)

    HOLEDIA

    FLUIDCAT.

    PRESSUREBARG

    RADIUSR1 R2

    2 B 10

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    21/29

    CLASSIFICATION AT SPECIFIC EQUIPMENT

    Fig. 1B, Pump mounted on grated deck – high integrity pump (typically double mechanical seals)

    HOLE FLUID PRESSURE RADIUSDIA CAT. BARG R1 R2

    2 B P

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    22/29

    CLASSIFICATION AT SPECIFIC EQUIPMENT

    Fi . 2A Flan e valve installed over rated deck

    HOLE

    DIA

    FLUID

    CAT.

    PRESSURE

    BARG

    RADIUS

    R1 R2

    1 A / C P

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    23/29

    CLASSIFICATION AT SPECIFIC EQUIPMENT

    Control valves, often used block valves and valves not well maintained: A zone 1=

    A specific evaluation shall be made to decide if there is a further zone 2 around thezone 1.

    23

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    24/29

    CLASSIFICATION AT SPECIFIC EQUIPMENT

    24

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    25/29

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    26/29

    CLASSIFICATION AT SPECIFIC EQUIPMENT

    EN 1127-1, ANNEX BDefines equipment which are ”durably technically tight”,

    • Canned motor pumps

    examples:

    • Magnetic coupled sealless pumps

    • Ton ue roove flan es EN 1092-1 T e C & D

    • If rarely detached: NPT connections (up to DN 50)

    Should normally not cause classified areas.

    26

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    27/29

    CLASSIFICATION AT SPECIFIC EQUIPMENT

    Seal Sealing Arrangement DescriptionMax. Release Flow Rate

    (kg/s)

    Hazard Radius R1/R2

    (m)

    John Crane recommendations for mechanical seal Maximum release flowrates for pumps in all fluid categories and process pressuresITA / Appendix 5:

     Single

    Single seal ( without fixed throttle

    bushing, in a pump with no wear

    rings). This may be a component or

    cartridge, general-purpose seal

    Use IP-15 calculation ( Hole

    size. 0,23xshaft dia.)*See IP-15

    Single

    Single seal with a fixed throttle

    bushing or a single seal in an API

    610 pump. This may be acomponent or cartridge, general-

    0,0003

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    28/29

    HAZARDOUS AREA DOSSIER 

    28

  • 8/9/2019 DSEN 60079-10-1 & UK.pdf

    29/29

    ENCLOSED AREAS

    • Minimum 12 ACH (IP 15), no stagnant zones to ensure area

    classification will correspond to grade of release.

    • Pressurisation to safe a room adjacent to classified area: Min. 5

    mm WG overpressure (IP 15)

    29