ds244_e_200ka_clamps.pdf
TRANSCRIPT
-
200 kA clampsFor classes of LPS I and II
According to the IEC 62561-x standard series, connection compo-nents must meet certain mechanical and electrical requirements. In tests according to IEC 62561-1, they are subjected to ageing and an electrical test with three lightning current impulses of 10/350 s wave form each*. Depending on the lightning current carrying capability, a distinction is made between Class N: 50 kA (normal duty) and Class H: 100 kA (high duty).
Connection components tested according to this standard can be used for class III/VI lightning protection systems and if the lightning current is distributed in a meshed lightning protection system.
In case of class I/II lightning protection systems, the lightning current is poorly distributed or not distributed at all if air-termination rods are connected to existing mesh systems. If an air-termination rod is con-nected to a mesh/roof parapet by means of a single conductor, 100% QHVJGNKIJVPKPIEWTTGPVYKNNQYHTQOVJGCKTVGTOKPCVKQPTQFXKCVJGconnection components. The case is similar for HVIConductors or HVIpower Conductors without current distribution used for class I/II lightning protection systems. When conducting the lightning current from the high-voltage-resistant, insulated down conductor to the existing lightning protection system, the clamps/connectors are exposed to 100% of the lightning current. This would be 150 kA in case of a class II lightning protection system and 200 kA in case of a class I lightning protection system.
www.dehn-international.com
The new 200 kA clamps from DEHN meet high requirements.
+'%.KIJVPKPI2TQVGEVKQP5[UVGO%QORQPGPVU.25%|2CTV|4GSWKTGOGPVUHQTEQPPGEVKQPEQORQPGPVU** DIN EN 62305-3 Bbl2 (VDE 0185-305-3 Bbl 2):2012-10 Protection against lightning Part 3: Physical damage to structures and life hazard Supplement 2: Additional information for special structures
The 200 kA imprint is characteristic of the new components.
6JGM#EQORQPGPVUCTGVVGFYKVJCURTKPIYCUJGTHQTWUGKPEx zone 2/22**. The manufacturers test reports and installation instructions for the individual components are available at www.dehn-international.com.
DEHN offers connection components with a lightning current carrying capability of 200 kA (10/350 s) based on the IEC 62561-1 standard*.
-
200 kA clampsFor classes of LPS I and II
www.dehn-international.com
The components are tested with a lightning current of 200 kA (10/350 s) based on the IEC 62561-1 standard.
DS244/E/1114 Copyright 2014 DEHN + SHNE
DEHN + SHNEGmbH + Co.KG.
Tel.: +49 9181 906-0 [email protected]
DEHN, DEHN logo and DEHN schtzt are protected by German Trademark and / or are registered trademarks in other EQWPVTKGU+NNWUVTCVKQPUCTGPQVDKPFKPI9GCEEGRVPQNKCDKNKV[HQTVGEJPKECNOQFKECVKQPUOKURTKPVUCPFGTTQTU
MV clamp
Allows two round wires to be connected.
Technical data Part No. 390 209
Material Stainless steel
Clamping range Rd / Rd 8-10 mm
Packing unit 1 piece
Disconnecting clamp
Allows HVIpower Conductors to be con-nected with the earth entry and the air-termi-nation rod with round wires.
Technical data Part No. 392 209
Material Stainless steel
Clamping range Rd/Rd 8-10 / 16 mm
Packing unit 1 piece
Clamping piece
#NNQYUVJGFQYPEQPFWEVQTCVUVTKRVQDGconnected with an isolated air-termination system and can also be used for connection to other structural parts (M10 screws).
Technical data Part No. 380 209
Material Stainless steel
Clamping range Fl 30 x 4 mm
Packing unit 1 piece
KS connector
Allows connection to building elements.
Technical data Part No. 301 209
Material Stainless steel
Clamping range Rd 10 mm
Packing unit 1 piece
Disconnecting clamp
Allows HVIpower Conductors/round conduc-tors to be connected with the earth entry.
Technical data Part No. 459 219
Material Stainless steel
Clamping range Rd / Rd 8-10 / 16 mm
Packing unit 1 piece
UNI disconnecting clamp
Allows two round wires to be connected.
Technical data Part No. 459 200
Clamp material Stainless steel
Clamping range Rd / Rd 10 / 10 mm
Clamping range Fl / Fl 10 / 30 mm
Packing unit 1 piece
Manufacturers test report available