drywall suspension system technical guide
TRANSCRIPT
CertainTeed Ceilings
Drywall Suspension System and QuickSpan™ Locking Drywall Grid SystemTECHNICAL GUIDE
Drywall Suspension System
QuickSpan™ Locking Drywall Grid System
Locking Channel
Spanning Tee
ISO
ISO
END
SIDE
SIDE
144"
8" O.C.
Lengths Available: 72" / 96" / 120" / 144" / 168"
1/4"
END
1/4"
13/32"
1-19/32"
1-1/2"
1-3/4" 1-1/2"
1-9/16"
Other Suspension Systems Available from CertainTeed Ceilings
Installing an acoustical ceiling starts with a dependable, easy-to-use, stable suspension system. CertainTeed Ceilings provides a range of suspension systems and accessories for your next project.
• 9/16" Elite Narrow Stab System
• 9/16" Smoothline Bolt Slot System
• 15/16" Classic Hook System
• 15/16" Classic Stab System
•• 15/16" Classic Aluminum Capped Hook System
• 15/16" Classic Aluminum Capped Stab System
• 15/16" Classic Environmental Stab System
• 15/16" Cleanroom Stab System
• 15/16" FireSecure™ Stab System
• 15/16" SeismicSecure ™ Stab System
• Cloud Perimeter Trim
Drywall Suspension SystemPerformance . ............................................................................................................................................................... 2
Code Compliance ....................................................................................................................................................... 2
Components ................................................................................................................................................................. 3
Metric Components (for use with Gyptone® BIG™ Boards) ............................................................ 4
Slot Positions .............................................................................................................................................................. .5
Lighting Integration ................................................................................................................................................... 7
Type F vs. Type G Fixtures ........................................................................................................................... 7
48-inch, 50-inch and 72-inch On Center Spacing ........................................................................................... 8
UL Fire Resistive Assemblies ................................................................................................................................ 9
Load Data .................................................................................................................................................................... 11
Quantity Estimating Tables . .................................................................................................................................. 12
QuickSpan™ Locking Drywall Grid System Performance ..............................................................................................................................................................13
Code Compliance .....................................................................................................................................................13
Components ...............................................................................................................................................................14
Profile and Spacing .................................................................................................................................................15
Load Data ....................................................................................................................................................................16
Installation Method and Instructions ................................................................................................................. 17
Quantity Estimating Tables ..................................................................................................................................19
Installation Accessories ....................................................................................................................................... .20
Wire Data ....................................................................................................................................................................22
Notes Section . ...........................................................................................................................................................23
Table of Contents
Drywall and QuickSpan™ Suspension System Technical Guide
Technical Support | certainteed.com/ceilings 1-800-233-8990 1
2 Technical Support | certainteed.com/ceilings 1-800-233-8990
Drywall and QuickSpan™ Suspension System Technical Guide
Performance
• 1-1/2-inch wide face on main runners and cross tees
• Knurled and uncapped face – Allows for easy screw installation and helps to prevent screw spin off
• Heavy-duty load rating – Exceeds minimum HD load performance per ASTM C635
- 0.020-inch metal thickness on main runners and cross tees for superior strength
- Rotary stitched web for increased stability
- 1.6-inch profile height for increased load capacity
• Improved cross tee clip installs with lower insertion effort and audible click
• G40 hot dipped galvanized coating – Standard corrosion resistance for all main runners, cross tees and wall angle
• G90 hot dipped galvanized coating – Superior corrosion resistance (for severe or exterior applications) available on all main runners, cross tees and wall angle
• Fire rated – Suitable for use in the following UL/ULC Fire Resistive Assemblies: D501, D502, D503, G041, G523, G524, G526, G527, G528, G529, G553, L502, L508, L513, L515, L525, L526, L529, P506, P508, P509, P510, P513, P514, P560
• Cross tee spacing:
- Up to max. 24 inches O.C. for 1/2-inch and 5/8-inch drywall
• Main runner features 54 slots to accommodate Type F and Type G fixture integration
Code Compliance
• Meets ASTM C635
• Meets ASTM C645
• Installation per ASTM C636
• Installation per ASTM C754
• ICC Evaluation Service Report (ESR 3336)
• L.A. Research Report (LARR 25978)
• Uniform Building Code, Continuous Membrane, One Level. Per Section 25.210 single-level drywall ceilings are exempt from lateral force bracing requirements when walls are not over 50-feet apart. When walls are over 50-feet apart, the ceiling should be examined for bracing requirements.
• IBC categories D, E and F single layer drywall ceilings are exempt from lateral force bracing requirements, regardless of room size
• Consult local authorities having jurisdiction for local code requirements
Drywall Suspension System
Technical Support | certainteed.com/ceilings 1-800-233-8990 3
Drywall and QuickSpan™ Suspension System Technical Guide
Components
Main RunnersDescription ItemNumber Dimensions SlotSpacing ASTMC635 Fire Recycled Recycled Recycled PCs Feet (in) (in) Rating Rated Content Content Content per per Total Pre Post carton carton
54 slots, starting 2-1/4 from each end
HD FR Main Runner G40 DWS12-13-20 144 x 1.6 x 1.5 Heavy Duty Yes 88% 19% 69% 16 192
HD FR Main Runner G90 DWS12-13-20 G90 144 x 1.6 x 1.5 Heavy Duty Yes 88% 19% 69% 16 192
G40 Galvanization
G90 Galvanization
Wall Angle Description ItemNumber Dimensions RecycledContent RecycledContent RecycledContent PCsper Feetper (in) Total Pre Post carton carton
1.5" WA G40 DWA1.5-1.5 144 x 1.5 x 1.5 88% 19% 69% 20 240
2" WA G40 DWA2-2 144 x 2 x 2 88% 19% 69% 20 240
1.5" WA G90 DWA1.5-1.5 G90 144 x 1.5 x 1.5 88% 19% 69% 20 240
2" WA G90 DWA 2-2 G90 144 x 2 x 2 88% 19% 69% 20 240
Cross TeesDescription ItemNumber Dimensions SlotSpacing Fire Recycled Recycled Recycled PCs Feet (in) (in) Rated Content Content Content per per Total Pre Post carton carton
14" Cross Tee G40 DWS1.16-13-20 14 x 1.6 x 1.5 No slots Yes 87% 19% 68% 48 56
24" Cross Tee G40 DWS2-13-20 24 x 1.6 x 1.5 10, 12, 14 Yes 87% 19% 68% 48 96
26" Cross Tee G40 DWS2.16-13-20 26 x 1.6 x 1.5 12, 14 Yes 87% 19% 68% 48 104
36" Cross Tee G40 DWS3-13-20 36 x 1.6 x 1.5 No slots Yes 87% 19% 68% 48 144
48" Cross Tee G40 DWS4-13-20 48 x 1.6 x 1.5 10, 12, 14, 22, 24, 26, Yes 87% 19% 68% 48 192 34, 36, 38
50" Cross Tee G40 DWS4.16-13-20 50 x 1.6 x 1.5 10, 12, 14, 24, 26, 36, Yes 87% 19% 68% 48 200 38, 40
72" Cross Tee G40 DWS6-13-20 72 x 1.6 x 1.5 22, 24, 26, 46, 48, 50 Yes 87% 19% 68% 36 216
14" Cross Tee G90 DWS1.16-13-20 G90 14 x 1.6 x 1.5 No slots Yes 87% 19% 68% 48 56
24" Cross Tee G90 DWS2-13-20 G90 24 x 1.6 x 1.5 10, 12, 14 Yes 87% 19% 68% 48 96
26" Cross Tee G90 DWS2.16-13-20 G90 26 x 1.6 x 1.5 12, 14 Yes 87% 19% 68% 48 104
36" Cross Tee G90 DWS3-13-20 G90 36 x 1.6 x 1.5 No slots Yes 87% 19% 68% 48 144
48" Cross Tee G90 DWS4-13-20 G90 48 x 1.6 x 1.5 10, 12, 14, 22, 24, 26, Yes 87% 19% 68% 48 192 34, 36, 38
50" Cross Tee G90 DWS4.16-13-20 G90 50 x 1.6 x 1.5 10, 12, 14, 24, 26, 36, Yes 87% 19% 68% 48 200 38, 40
72" Cross Tee G90 DWS6-13-20 G90 72 x 1.6 x 1.5 22, 24, 26, 46, 48, 50 Yes 87% 19% 68% 36 216
4 Technical Support | certainteed.com/ceilings 1-800-233-8990
Drywall and QuickSpan™ Suspension System Technical Guide
Main RunnersDescription ItemNumber Dimensions
(mm)SlotSpacing(mm)
ASTM FireRated
RecycledContentTotal
RecycledContentPre
RecycledContentPost
PCsPerCarton
MetersPerCarton
HD FR Main Runner DWS3600MM-13-20 3600 x 41 x 38 150 Heavy Duty
Yes 88% 19% 69% 16 57.6
Cross TeesDescription ItemNumber Dimensions
(mm)SlotSpacing(mm)
FireRated
RecycledContentTotal
RecycledContentPre
RecycledContentPost
PCsPerCarton
MetersPerCarton
1500 mm Cross Tee DWS1500MM-13-20 1500 x 41 x 38 150, 350, 250,
250, 350, 150
Yes 87% 19% 68% 36 54
1200 mm Cross Tee DWS1200MM-13-20 1200 x 41 x 38 300 Yes 87% 19% 68% 48 57.6
900 mm Cross Tee DWS900MM-13-20 900 x 41 x 38 None Yes 87% 19% 68% 48 43.2
750 mm Cross Tee DWS750MM-13-20 750 x 41 x 38 None Yes 87% 19% 68% 48 36
600 mm Cross Tee DWS600MM-13-20 600 x 41 x 38 None Yes 87% 19% 68% 48 29
Metric Drywall Components (for use with Gyptone® BIG™ Boards – Quattro 41, Quattro 46, Sixto 63, Sixto 65 and Line 6)
Technical Support | certainteed.com/ceilings 1-800-233-8990 5
Drywall and QuickSpan™ Suspension System Technical Guide
Slot Positions
Main Runner DWS12-13-20 / DWS12-13-20 G90
72" Cross Tee DWS6-13-20 / DWS6-13-20 G90
50" Cross Tee DWS4.16-30-20
48" Cross Tee DWS4-13-20
1.75"
.743"- 6 Places
12"12"
12"
1.75"1.75"1.75"
.875".875"- 6 Places
1.75"1.75"
24"24"
1.75" .743"- 8 Places1.75"
.875".875"- 8 Places
1.75"1.75"
12" 12"
50"
1.75"
1.75"
1.75" 1.75"1.75"
144"
1.75"
8" 128"
1.75"
16"
1.75"1.75"
.25 (54x)
2.25" 1.75"1.75"
72"
48"
6 Technical Support | certainteed.com/ceilings 1-800-233-8990
Drywall and QuickSpan™ Suspension System Technical Guide
Slot Positions
36" Cross Tee DWS3-13-20 / DWS3-13-20 G90
26" Cross Tee DWS2. 16-13-20
24" Cross Tee DWS2-13-20
14" Cross Tee DWS1.16-13-20
14"
1.75"12"
1.75"
.875".875"
24"
12"
.875" .875"
1.75"
26"
36"
Technical Support | certainteed.com/ceilings 1-800-233-8990 7
Drywall and QuickSpan™ Suspension System Technical Guide
CertainTeed Ceilings Drywall Suspension System main runners feature slots 8-inches on center. Each slot has two additional offset slots; each is 1-3/4-inches from the center slot. These additional offset slots allow for integration with Type F fixtures. Use the center slot for typical cross tee installation.
1 Install from below the grid
2 Fixture has integral flange (or separate flange kit) to finish the drywall board
3 Fixture rests on bulb of grid and/or is suspended from flange kit
4 Fixture is level with drywall
5 Requires actual 48-inch opening
1 Install from above the grid
2 Fixture trim is required for finishing drywall
3 Fixture rests on flange of grid
4 Fixture is recessed the thickness of the drywall
5 Requires nominal 48-inch opening
Lighting Integration – Offset Slots
Type F Fixtures
Type F vs. Type G Fixtures
Type G Fixtures
8 Technical Support | certainteed.com/ceilings 1-800-233-8990
Drywall and QuickSpan™ Suspension System Technical Guide
48-inch, 50-inch and 72-inch On Center Spacing
Type F fixtures, air diffusers and access hatches require actual 12-inch, 24-inch and 48-inch openings in the suspension system. Type F fixtures can be installed both parallel and perpendicular to the main runners using 48-inch, 50-inch or 72-inch cross tees. The additional slots in the main runners and cross tees allow for integration with type F fixtures, while the availability of seven different cross tee sizes allows for framing without cutting and field modifications.
The combination of CertainTeed Ceilings offset main runner slots and availability of 48-inch, 50-inch and 72-inch cross tees allows for type F fixture installations on 48-inch, 50-inch and 72-inch centers.
48" On Center 50" On Center
AccessOpening
Type “F”Fixture2' x 4'
Type “F”Fixture
1'x 4'
50"Cross
Tee
Main Runner48" O.C.
26"CrossTee
50"CrossTee
Cross Tee24" O.C.
Grid for 48" Type F Fixture
48"
Access Opening
Type “F”Fixture2'x 4'
Type “F”Fixture
2'x 4'
Type “F”Fixture1'x 4'
Main Runner50" O.C.
26"CrossTee
50"
Cross Tee24"
50"CrossTee
Grid for 50" Type F Fixture
50"Cross
Tee
There are a multitude of fixture placement options when installing type F fixtures 72-inches on center and perpendicular to the main runners. Cut the clips off the 26-inch cross tee and use the CertainTeed L-bracket (LBRC) to fasten the tee in place.
Type G fixtures can also be installed by cutting cross tee clips and using the LRBC to create the module size required instead of 15/16-inches wide face tees.
Technical Support | certainteed.com/ceilings 1-800-233-8990 9
Drywall and QuickSpan™ Suspension System Technical Guide
UL Fire Resistive Assemblies (Drywall Suspension System Only)
Floor / Ceiling Drywall Assemblies
Fire Ratings specified in this section pertain to UL Classifications, which are based on standard test method ANSI / UL263, ASTM E119, UBC 7-1, NFPA 251, CAN / ULC-S101M.
TypeofConstruction Maximum UL Concrete Numberof MinimumDrywall MaximumFixture MaximumDuct DrywallGrid TimeRating Design Thickness Drywall Thickness Penetration Penetration System (hrs) Number (in) Layers (in) (ft2/100ft2) (in2/100ft2)
Concrete on metal lath or corrugated 2 D501 2-1/2 1 1/2 N/A N/A CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Concrete on metal lath or corrugated 2 D502 2-1/2 1 1/2 24 144 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Concrete on metal lath or corrugated 2 D503 2-1/2 1 1/2 One 6" diameter N/A CertainTeed DWSsteel deck, steel joists fixture per 25ft2 (max. 50" cross tee)
Concrete on metal lath or corrugated 2 G041 2-1/2 1 1/2 15.3 54 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Concrete on metal lath or corrugated 1 G041 2-1/2 1 1/2 15.3 54 CertainTeed DWSsteel deck, steel joists (max. 72" cross tee)
Concrete on metal lath or corrugated 2 G523 2-1/2 1 1/2 24 144 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Concrete on metal lath or corrugated 2 G524 2-1/2 1 1/2 One fixture 144 CertainTeed DWSsteel deck, steel joists per 100 ft2 (max. 50" cross tee)
Concrete on metal lath or corrugated 2 G526 2-1/2 1 1/2 24 56.5 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Concrete on metal lath or corrugated 2 G527 2-1/2 1 1/2 N/A N/A CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Concrete on metal lath or corrugated 1-1/2 G528 2-1/2 1 1/2 N/A N/A CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Concrete on metal lath or corrugated 2 G529 2-1/2 1 1/2 24 57 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Concrete on metal lath or corrugated 2 G553 2-1/2 1 1/2 N/A N/A CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Wood deck 1 L502 - 1 1/2 N/A 99 CertainTeed DWS (max. 50" cross tee)
Wood deck 1 L508 - 1 1/2 N/A 99 CertainTeed DWS (max. 50" cross tee)
Wood deck 1 L513 - 1 1/2 N/A 99 CertainTeed DWS (max. 50" cross tee)
Wood deck 1 L515 - 1 1/2 N/A 99 CertainTeed DWS (max. 50" cross tee)
Wood deck 1 L525 - 1 1/2 24 113 CertainTeed DWS (max. 50" cross tee)
Wood deck 1 L526 - 1 1/2 24 100 CertainTeed DWS (max. 50" cross tee)
Wood deck 1 L529 - 1 1/2 24 113 CertainTeed DWS (max. 50" cross tee)
10 Technical Support | certainteed.com/ceilings 1-800-233-8990
Drywall and QuickSpan™ Suspension System Technical Guide
UL Fire Resistive Assemblies (Drywall Suspension System Only)
Roof / Ceiling Drywall Assemblies
Fire ratings specified in this section pertain to UL Classifications, which are based on standard test method ANSI / UL263, ASTM E119, UBC 7-1, NFPA 251, CAN / ULC-S101M.
TypeofConstruction Maximum UL Concrete Numberof MinimumDrywall MaximumFixture MaximumDuct DrywallGrid TimeRating Design Thickness Drywall Thickness Penetration Penetration System (hrs) Number (in) Layers (in) (ft2/100ft2) (in2/100ft2)
BUR, modified or single-ply over 1-1/2 P506 - 1 5/8 24 113 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
BUR, modified or single-ply over 1 P508 - 1 5/8 24 144 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
BUR, modified or single-ply over 1 P509 - 1 5/8 24 144 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
BUR, modified or single-ply over 1-1/2 P510 - 1 5/8 24 113 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
BUR, modified or single-ply over 1-1/2 P513 - 1 5/8 24 144 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
BUR, modified or single-ply over 2 P514 - 1 5/8 24 255 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
BUR, modified or single-ply over 2 P560 - 1 5/8 15.3 54 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Floor / Ceiling Drywall AssembliesFire ratings specified in this section pertain to ULC Classifications, which are based on standard test method ANSI/UL263, ASTM E119, UBC 7-1, NFPA 251, CAN/ULC - S101M.
TypeofConstruction Maximum ULC Concrete Numberof MinimumDrywall MaximumFixture MaximumDuct DrywallGrid TimeRating Design Thickness Drywall Thickness Penetration Penetration System (hrs) Number (in) Layers (in) (ft2/100ft2) (in2/100ft2)
Concrete on metal lath or corrugated 2 G021 2.5 1 1/2 15.3 54 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Concrete on metal lath or corrugated 1 G021 2.5 1 1/2 15.3 54 CertainTeed DWSsteel deck, steel joists (max. 72" cross tee)
Roof / Ceiling Drywall Assemblies
TypeofConstruction Maximum ULC Concrete Numberof MinimumDrywall MaximumFixture MaximumDuct DrywallGrid TimeRating Design Thickness Drywall Thickness Penetration Penetration System (hrs) Number (in) Layers (in) (ft2/100ft2) (in2/100ft2)
BUR, modified or single-ply over 2 R503 - 1 5/8 15.3 54 CertainTeed DWSsteel deck, steel joists (max. 50" cross tee)
Technical Support | certainteed.com/ceilings 1-800-233-8990 11
Drywall and QuickSpan™ Suspension System Technical Guide
Load Data (Drywall Suspension System Only)
Cross Tees
ProductNumber Dimensions(length/height)(in)
Dimensions(face)(in)
MetalThickness(in)
SimpleSpan(poundsperlf)
14-in 2-ft 26-in 3-ft 4-ft 50-in 6-ft
L /360 L/240 L/360 L/240 L/360 L/240 L/360 L/240 L/360 L/240 L/360 L/240 L/360 L/240
14" Cross Tee (G40/G90) DWS1.16-13-20 14 x 1.6 1.5 0.020 199* 199*
24" Cross Tee (G40/G90) DWS2-13-20 24 x 1.6 1.5 0.020 147
26" Cross Tee (G40/G90) DWS2.16-13-20 26 x 1.6 1.5 0.020 199* 115 180
36" Cross Tee (G40/G90) DWS3-13-20 36 x 1.6 1.5 0.020 43 68
48" Cross Tee (G40/G90) DWS4-13-20 48 x 1.6 1.5 0.020 18 28
50" Cross Tee (G40/G90) DWS4.16-13-20 50 x 1.6 1.5 0.020 16 25
72" Cross Tee (G40/G90) DWS6-13-20 72 x 1.6 1.5 0.020 5 8
*Failurelimited
NOTE:AllowableloadstestedperASTMC635fordeflectionlimitedtoL/360andcomplieswithASTMC645fordeflectionlimitedtoL/240.
Main Runners
ProductNumber Dimensions(length/height)(in)
Dimensions(face)(in)
MetalThickness(in)
SimpleSpan(poundsperlf)
4-ft 3-ft 2-ft
L /360 L/240 L/360 L/240 L/360 L/240
Main Runner / G40 DWS12-13-20 144 x 1.6 1.5 0.020 19.21 27.36 45.53 64.85 153.68 198.60*
Main Runner / G90 DWS12-13-20 G90 144 x 1.6 1.5 0.020 19.21 27.36 45.53 64.85 153.68 198.60*
System Load Value
AllowableLoadinlbs/SF(psf)atMainRunnerHangerWireSpacing
HangerWireSpacing(ft) 4 3 2
CrossTeeLength(in) L/360 L/240 L/360 L/240 L/360 L/240
14 16.47 23.45 39.03 55.59 131.73 170.23
24 9.61 13.68 22.77 32.43 76.84 99.30
26 8.87 12.63 21.01 29.93 70.93 91.66
36 6.40 9.12 15.18 21.62 51.23 66.20
48 4.80 6.84 11.38 16.21 38.42 49.65
50 4.61 6.57 10.93 15.56 36.88 47.66
72 3.20 4.56 7.59 10.81 25.61 33.10
12 Technical Support | certainteed.com/ceilings 1-800-233-8990
Drywall and QuickSpan™ Suspension System Technical Guide
Quantity Estimating Tables (Drywall Suspension System Only)
Main RunnersProductNumber PerBundle Areaofceilingcompletebyonecarton(ft2)
Dimensions(length)(in)
PCs Lf Lbs 8"O.C. 16"O.C. 24"O.C. 36"O.C. 48"O.C. 50"O.C. 72"O.C.
Main runner / G40 DWS12-13-20 144 16 192 61 — — 384 576 768 800 1152
Main runner / G90 DWS12-13-20 G90 144 16 192 61 — — 384 576 768 800 1152
Cross TeesProductNumber PerBundle Areaofceilingcompletebyonecarton(ft2)
Dimensions(length)(in)
PCs Lf Lbs 8"O.C. 16"O.C. 24"O.C.
14" Cross Tee (G40/G90) DWS1.16-13-20 14 48 56 18 — — —
24" Cross Tee (G40/G90) DWS2-13-20 24 48 96 31 64 — —
26" Cross Tee (G40/G90) DWS2.16-13-20 26 48 104 33 — — —
36" Cross Tee (G40/G90) DWS3-13-20 36 48 144 46 96 192 288
48" Cross Tee (G40/G90) DWS4-13-20 48 48 192 61 128 256 384
50" Cross Tee (G40/G90) DWS4.16-13-20 50 48 200 64 133.33 267 400
72" Cross Tee (G40/G90) DWS6-13-20 72 36 216 72 144 288 432
Wall AngleProductNumber PerBundle
Dimensions(length)(in)
PCs Lf Lbs
1.5" WA (G40/G90) DWA1.5-1.5 144 20 192 45
2" WA (G40/G90) DWA2-2 144 20 192 59
Estimating Lineal Feet of Grid Based on Square Footage of Ceiling
On Center Spacing Percent of Square Footage
8" 108%
12" 100%
16" 76%
20" 60%
24" 50%
30" 40%
36" 33%
48" 25%
60" 20%
Example calculation:
Main Runners at 48" O.C.
6,400ft2x.25=1,600lf
1,600lf÷192lf/ctn=9cartonsrequired
48" Cross Tees at 24" O.C.
6,400ft2x.50=3,200lf
3,200lf÷192lf/ctn=17cartonsrequired
48" Cross Tees at 16" O.C.
6,400ft2x.76=4,864lf
4,864lf÷192lf/ctn=26cartonsrequired
Technical Support | certainteed.com/ceilings 1-800-233-8990 13
Drywall and QuickSpan™ Suspension System Technical Guide
Performance
QuickSpan™ Locking Channel
• 1-9/16-inches wide bottom flange
• 0.020-inch metal thickness allows for superior rigidity and maximum screw retention
• Tees quickly twist into place for fast installation
• Knurled pattern on back and bottom of flange for easy screw insertion
• No need for screws, pop rivets or crimpers
• Pre-engineered locking tabs punched every 8-inches on center
• G40 hot dipped galvanized coating for corrosion resistance
QuickSpan™ Cross Tees
• 1-1/2-inches wide face with knurled and uncapped face for easy screw installation and helps to prevent screw spin off
• Unsupported spans – Up to 10 feet 6 inches for 1/2-inch drywall and 10 feet 4 inches for 5/8-inch drywall
• Heavy duty material – 0.020-inches metal thickness for maximum rigidity and screw grip
• Double-stitched web for added strength
• Sizes – standard and custom lengths available
Code Compliance
• Meets ASTM C635
• Meets ASTM C645
• Installation per ASTM C636
• Installation per ASTM C754
• ICC Evaluation Service Report (ESR 3941)
• Uniform Building Code, Continuous Membrane, One Level. Per Section 25.210 single-level drywall ceilings are exempt from lateral force bracing requirements when walls are not over 50-feet apart. When walls are over 50-feet apart, the ceiling should be examined for bracing requirements.
• IBC categories D, E and F single layer drywall ceilings are exempt from lateral force bracing requirements, regardless of room size
• Consult local authorities having jurisdiction for local code requirements
QuickSpan™ Locking Drywall Grid System
14 Technical Support | certainteed.com/ceilings 1-800-233-8990
Drywall and QuickSpan™ Suspension System Technical Guide
Components
QuickSpan™ Tees
Description Dimensions(in)LxHxW
Hanger/LockSpacing RecycledContentTotal LbsperBundle LfperBundle PieceperBundle
QST6-13-20 6' QuickSpan™
Cross Tee G40
72 x 1-9/16 x 1-1/2 2 hole grouping,
every 8" O.C.
87% 25 72 12
QST8-13-20 8' QuickSpan™
Cross Tee G40
96 x 1-9/16 x 1-1/2 2 hole grouping,
every 8" O.C.
87% 34 96 12
QST10-13-20 10' QuickSpan™
Cross Tee G40
120 x 1-9/16 x 1-1/2 2 hole grouping,
every 8" O.C.
87% 42 120 12
QST12-13-20 12' QuickSpan™
Cross Tee G40
144 x 1-9/16 x 1-1/2 2 hole grouping,
every 8" O.C.
87% 50 144 12
QST14-13-20 14' QuickSpan™
Cross Tee G40
168 x 1-9/16 x 1-1/2 2 hole grouping,
every 8" O.C.
87% 59 168 12
CUSTOM Custom Length TBD x 1-9/16 x 1-1/2 2 hole grouping,
every 8" O.C. / TBD
87% — — —
QuickSpan™ Locking Channel
Description Dimensions(in)LxHxW
Hanger/LockSpacing RecycledContentTotal LbsperBundle LfperBundle PieceperBundle
QSLC12-14-20 12" QuickSpan™
Locking Channel
144 x 1-3/4 x 1-9/16 8" O.C. 87% 40 144 12
Wall AngleDescription Dimensions(in)
LxHxWHanger/LockSpacing RecycledContentTotal LbsperBundle LfperBundle PieceperBundle
DWA1.5–1.5 1-1/2" Knurled Wall
Angle G40
144 x 1-1/2 x 1-1/2 — 88% 45 240 20
DWA2–2 2" Knurled Wall
Angle G40
144 x 2 x 2 — 88% 59 240 20
Technical Support | certainteed.com/ceilings 1-800-233-8990 15
Drywall and QuickSpan™ Suspension System Technical Guide
Profile and Spacing
Locking Channel QSLC12-14-20
Spanning Tees QST6-13-20 / QST8-13-20 / QST10-13-20 / QST12-13-20 / QST14-13-20
Spacing (side view)
Spacing (side view)
Profile (end view)
Profile (end view)
144"
8"O.C.
1/4"
13/32"
1-19/32"
1-1/2"
1-3/4"
1-9/16"
1-1/2"
1/4"
LengthsAvailable:72"/96"/120"/144"/168"
16 Technical Support | certainteed.com/ceilings 1-800-233-8990
Drywall and QuickSpan™ Suspension System Technical Guide
Load Test Data
Clear Span L/240 No Hangers (lbs/lf)
Span Length 4' (48") 5' (60") 6' (72") 7' (84") 8' (96") 9' (107.7")
Load (lbs./ft) 33.9 17.5 10.1 6.4 4.3 3.3
Span Load Test Data
Max. Clear Span Load for 2.5 lbs/ft2 (5/8" board)
8" O.C. 11' 3" (135.6")
16" O.C. 9' (107.7")
24" O.C. 7' 7" (91.1")
Max. Clear Span Load for 2.0 lbs/ft2 (1/2" board)
8" O.C. 12' (144")
16" O.C. 9' 8" (116")
24" O.C. 8' 2" (98.2")
Max. Clear Span Load for 1.4 lbs/ft2 (Lightweight 1/2" board*)
8" O.C. 12' (144")
16" O.C. 10' 10" (130.6")
24" O.C. 9' 6" (114.1")
* CertainTeed Easi-Lite™ Drywall boards weigh between 1.2 and 1.4 lbs/ft2
Load Data (QuickSpan™ System Only)
No additional screws required for seismic areas
NOTE:
1. Loadtestdatashowsuniformloadinlbs/lfbasedonclearspantestsinaccordancewithASTMdeflectionlimitonL/240
2. Spangreaterthan14feetrequiresuseofSpliceClip(DWSC)
3. InstallationperASTMC636
4. InstallationperASTMC754
5. ESR3941
Installation:
MustbeinstalledincompliancewithASTMC636.ASTME580,CISCAandstandardandindustrypracticeswithinallapplicablecoderequirements.Alternativeassembliesandinstallationmethodsmaybeutilizedwhenapprovedbytheauthorityhavingjurisdiction.CertainTeedCeilingsrecommendscheckingwiththeauthorityhavingjurisdictionpriortodesigningandinstallingasuspendedceilingsystem.
Code Compliance:
Theinformationiscorrecttothebestofourknowledgeatthedateofissuance.Becausecodescontinuetoevolve,checkwithlocalofficialspriortodesigningandinstallingaceilingsystem.Otherrestrictionsandexemptionsmayapply.
Span Load Test Data
Main Runner Spacing (lbs/ft2)
4'
(48")
5'
(60")
6'
(72")
7'
(84")
7' 7"
(91")
8'
(96")
9
(107.7")
10'
(120")
11' 3"
(135")
12'
(144")
14'
(168")
16'
(192")
18'
(216")
8" O.C. 50.5 26.2 15.2 9.6 7.5 6.4 5.0 3.6 2.6 15.2* 9.6* 6.4* 5.0*
16" O.C. 25.5 13.2 7.6 4.8 3.8 3.2 2.5 13.2* 9.2* 7.6* 4.8* 3.2* 2.5*
24" O.C. 16.9 8.8 5.1 3.2 2.5 16.9* 12.0* 8.8* 6.2* 5.1* 3.2* 7.2** 5.1**
No hangers required. * Mid-span support required. ** Two verticle supports at 1/3 points required. Note: 5/8" drywall weighs approx. 2.4 lbs/sf2 1/2" drywall weighs approx. 2 lbs/sf2
X
Technical Support | certainteed.com/ceilings 1-800-233-8990 17
Drywall and QuickSpan™ Suspension System Technical Guide
Installing the QuickSpan™ Locking Channel
1. Establish the ceiling level and drywall board thickness to be used.
2. Place the bottom of the QuickSpan Locking Channel (QSLC) at the appropriate level.
3. Decide upon a location for your first QuickSpan™ tee. The locking tabs on the QSLC are spaced every 8-inches on center and can be cut to the desired spacing from the abutting wall.
a. To cut the QSLC, choose the desired slot, measure from the wall and cut through the top and bottom flanges first. Finish by folding the scored piece back and cut through the rest of the channel.
4. Attach the QSLC with the appropriate fasteners. Use number 8, 1-1/4-inches long (32 mm), steel-framing, self-drilling tapping screws complying with SAE J78 and ASTM C1002.
5. On short walls where locking channel and/or tees are NOT needed; drywall wall angle can be used.
a. 1-1/2-inches (DWA1.5-1.5) or 2-inches (DWA2-2) wide pieces available
Installing the QuickSpan™ Tees
1. Measure across the hallway from inside of QSLC to inside of QSLC. Find a measurement that provides no more than a 1/4 inch gap and no less than a 1/8 inch gap between the insides of the channel.
a. For example, if the walls are 8-feet (96-inches) apart, you will want to cut your tees to 95-3/4 inches to allow the proper gap between the wall channel and tee. You can use a hot saw, band saw or tin snips to cut the cross tees down to size.
2. Start at one end of the ceiling and place a QuickSpan tee into the QSLC on both sides. Make sure that the tee is lying at an angle and moves freely in the channel.
a. Place all of the tees into the channel or do one at a time, it does not matter to the system.
3. Find the next slot on the QSLC that corresponds to the chosen spacing pattern and place the bulb (top) of the tee into the upper locator slot in the V of the QSLC.
4. Rotate the bottom of the tee into position. You will hear an audible click as the tee engages in the bottom locking tab of the QSLC. This will tell you that the tee is in place and locked.
a. Extra screws are NOT required, but a pilot hole is provided in the event that you find it necessary to apply a screw.
5. Proceed to the other end of the QuickSpan tee and follow the same process. Notice that the QuickSpan tee is snapped in the locking tabs on alternate sides of the QSLC. The system is designed this way to provide added rotational strength.
6. Note that there are hanger hole groupings provided every 8 inches across the tees. This allows the installer to provide a hanger where an excessive load is going to be placed on the system.
7. In the event that you want to create an opening for a device, simply cut a QuickSpan tee and screw it to the other tees in the appropriate location. a. Standard accessories are available to attach cross tees for device openings (L-Bracket LBRC,
Splice Clip DWSP and Direct Fixing Bracket DFB)
Installation Method and Instructions for QuickSpan™
Step-by-step illustrations - Assembly of Spanning Tee and Locking Channel
18 Technical Support | certainteed.com/ceilings 1-800-233-8990
Drywall and QuickSpan™ Suspension System Technical Guide
Installing Gypsum Board to the QuickSpan™ System
In non-fire rated ceiling assemblies, it is the contractor's discretion as to the orientation of the gypsum board, whether it is applied parallel or perpendicular to the supporting structure. The long, tapered edges of the board should be installed parallel to the QuickSpan tees. Some gypsum product manufacturers will require their product to be installed with the long, tapered edges perpendicular to ceiling framing members. Refer to their product data pages for specific information concerning product installation.
Maximum 5/8-inch thick gypsum board must be installed and fastened to the QuickSpan Locking Drywall System in accordance with IBC Section2508, ASTM C840, and Gypsum Association GA-216.
Change in Direction, Intersections, Bump-Outs and Coves
Change in Direction / Intersections 1. Apply a cross tee to the area just before the intersection or corner, making sure to completely engage both
wall channels.
2. Install a channel onto the adjacent wall, making sure to locate the locking tabs where they will function best.
3. Lock a tee into the new channel in the new corridor and set it on the flange of the last tee in the first corridor. Adjust the tee until it is square with the first corridor and screw the tees together or use an L-bracket (LBRC) to connect them.
4. Cut a piece of channel at a locking tab location and set that channel against the new cross tee. Fasten the tee to the wall and continue.
Coves / Recesses 1. When the ceiling condition includes a cove or recess in the hallway, span the channel across the opening and
continue along the wall.
2. Fasten the channel to the wall and cut the channel at the first available locking slot. This will allow use of QuickSpan as a guide for placing the channel in the correct position against the back wall of the cove or recess.
3. After the channel is installed along the long walls, either install the QuickSpan locking channel along the short walls or use Certainteed 1-1/2 inch or 2 inch drywall wall angle along the short walls.
Bump-Out / Columns 1. If the condition is a bump-out or column application, cut the locking channel into the obstruction.
2. To continue onto the outer face of the column or bump out, cut a channel at any upper locking slot and butt the channel up to the last tee before the column. This again will provide the proper module size down the wall.
3. Install the channel past the opposing corner of the bump out and cut it at the first available locking slot.
As with the cove condition, use the last tee as a guide for placing the channel against the back wall of the corridor. Apply drywall wall angle where applicable along the short edges to secure the board.
Installation Method and Instructions for QuickSpan™
Technical Support | certainteed.com/ceilings 1-800-233-8990 19
Drywall and QuickSpan™ Suspension System Technical Guide
Locking Channel
ProductNumber Dimensions(length)(in) PerBundle Lengthofhallwaycompletebyonecarton–2sides(Lf)
PCs Lf Lbs
QSLC12-14-20 144 12 144 40 71
Cross TeesProductNumber Dimensions(length)(in) PerBundle Lengthofhallwaycompletebyonecarton(lf)
Widthnotfactored–willvarybyselectedcrosstee
PCs Lf Lbs 8"O.C. 16"O.C. 24"O.C.
QST6-13-20 72 12 72 25
96 192 288
QST8-13-20 96 12 96 34
QST10-13-20 120 12 120 42
QST12-13-20 144 12 144 50
QST14-13-20 168 12 168 59
Custom TBD — — — — — —
Wall AngleProductNumber Dimensions(length)(in) PerBundle
PCs Lf Lbs
1.5" WA (G40/G90) DWA1.5-1.5 144 20 192 45
2" WA (G40/G90) DWA2-2 144 20 192 59
Quantity Esimating Tables (QuickSpan™ Locking Drywall Grid System Only)
No Cardboard Cartons Reducedwaste/EasyopenX
20 Technical Support | certainteed.com/ceilings 1-800-233-8990
Drywall and QuickSpan™ Suspension System Technical Guide
Installation Accessories
Description ItemNumber PCsperCarton Application
90-Degree Angle Bracket B90 250
The90,45,30and60-degreeAngleBracketsareusedtocreateangledwallsandceilings.Featuresholesforscrewsandhangerwire.
60-Degree Angle Bracket B60 250
45-Degree Angle Bracket B45 250
30-Degree Angle Bracket B30 250
Splice Clip DWSC 200
TheSpliceClipisusedtoconnectcutendsofgridcomponents.Itcanalsobeusedtocreatearadius.
Direct Load Clip DLC 150
For15/16"flangewidthgrid.TheDirectLoadClipisusedtohangdrywallgridbelowacousticalceilings.
Slot Punch (Rout Punch) Slotter1 1
TheSlotPunchisusedtoaddaroutholewhereveroneisneededonamainrunnerorcrosstee.CompatiblewithClassicStab,EliteNarrowStabandDrywallGrid.
Hanger Wire
Tee Exposed TeeGrid System
Drywall Grid System
Gypsum Board
90° Bracket
Technical Support | certainteed.com/ceilings 1-800-233-8990 21
Drywall and QuickSpan™ Suspension System Technical Guide
Installation Accessories
Description ItemNumber PCsperCarton Application
2-Layer Drywall Clip 2LC 150
The2-LayerDrywallClipisusedtosuspendagridsystembelowanexistingceiling.Itisdesignedtotransfertheloadfromthegriddirectlytotheclip.
Drywall Fastener Clip DFC 150
TheDrywallFastenerClipisscrew-attachedthroughanexistingdrywallceilingtotheframingmemberinordertosuspendasecondceilingbelow.
L-Bracket LBRC 200
TheL-Bracketisusedtoscrew-attachcutcrossteestomainrunners.
Direct Fixing Bracket DFB 75
TheDirectFixingBracketisusedtoattachthemainrunnerstothestructureinapplicationwithshallowplenums.
Hanger Wire
22 Technical Support | certainteed.com/ceilings 1-800-233-8990
Drywall and QuickSpan™ Suspension System Technical Guide
Wire Data (9-Gauge and 12-Gauge)
9-Gauge Wire Breaking Strength and Technical Data
12-Gauge Wire Breaking Strength and Technical Data
9-GaugeWireDiameter,0.114-inchGalvanizedSteel
645lbsMin.SafeWireLoad/9-Gauge
12-GaugeWireDiameter,0.081-inchGalvanizedSteel
275lbsMin.SafeWireLoad/12-Gauge
3Turnsin3-inchesperASTMC636
450lbs.Pullout/HangerWireHole/9-Gauge
3Turnsin3-inchesperASTMC636
500lbsPullout–HangerWireHole/12-Gauge
NOTE:CertainTeedDrywallGridSystemcanbeusedwitheither9-gaugeor12-gaugehangerwire.Consultlocalauthoritieshavingjurisdictionforlocalcoderequirements.
Technical Support | certainteed.com/ceilings 1-800-233-8990 23
Drywall and QuickSpan™ Suspension System Technical Guide
Notes
DECOUSTICS®ECOPHON®GYPTONE®PERFORMA®
You can Be Certain™ that CertainTeed Ceilings is your source for complete ceiling solutions.