dr.kulkarni
DESCRIPTION
transfrmrTRANSCRIPT
Phase Shifting Transformers
Prof. S. V. KulkarniDepartment of Electrical Engineering
Indian Institute of Technology Bombay, [email protected]
CBIP Conference, New Delhi 28-11-2013
1
IIT
Bom
bay Outline
Introduction
Applications of PSTs
Basic Concepts
Design Considerations
Other Technologies
Concluding Remarks
2
IIT
Bom
bay Need for Phase Shifting Transformers
Power systems are becoming complex
Devices useful in controlling power flow in a complex interconnected network are desirable
Power system deregulation and market mechanism
Power flow from generation centers to load centers in an efficient way
Major disturbances and system blackouts
Stability of a large interconnected system can be improved
Overloading and under-utilization of transmission lines
Lines can be optimally loaded
PSTs would be more relevant when penetration of intermittently available renewable energy sources increases in the system
4
IIT
Bom
bay Functions of Phase Shifting Transformers
Power flow control between the sending and receiving ends of a transmission line
Control of power flow between two parts of a large power system network
Improvement of system stability and reliability
Re-routing of powers through transmission lines leading to their optimum utilization/deferment of investment costs for new lines: Congestion management
Avoid/minimize loop currents and corresponding power flow
Allow efficient evacuation of new generation
5
IIT
Bom
bay Representative and Notable Applications of PSTs
i.Control and increase the power flow between two large systems: PST option was found better than HVDC and series capacitors
(Ref: Patel, B. K., Smith, H. S., Hewes, T. S., and Marsh, W. J. Application of phase shifting transformers for Daniel-Mcknight 500 KV interconnection, IEEE Transactions on Power Delivery, Vol. PWRD-1, No. 3, July 1986, pp. 167–173)
ii. Kothagudem thermal power station: - 500 MW evacuation – 220 kV lines would be overloaded- One option: 400/220 kV ICT – which would also increase the loading of
the underutilized double-circuit 400 kV line- System studies indicated reverse flow – from 400 kV to 220 kV- Hence the option chosen : ICT with a phase shifter(Information: Courtesy - BHEL)
7
IIT
Bom
bay Representative and Notable Applications of PSTs
iii. Reduction in loop flows
400 MW
300 MW 400 MW
100 MW100 MW“Loop flow”
100 MW
400 MW 300 MW
400 MWArea-1
Area-2
8
Ref: Kulkarni, A. M. Power System Operation and Control – NPTEL Web Course, Module 4 : Voltage and Power Flow Control, Lecture 19
IIT
Bom
bay Power Flow Through a Transmission Line
The real power transferred to the receiving end is proportional to the angle difference whereas the reactive power is proportional to the magnitude of the voltage drop across the line.
Gsss jQPS
SV 0RV
LoadRRR jQPS
sinS RR
V VP
X
2
cosS R RR
V V VQ
X X ( )R R
S R
V VV V V
X X
10
IIT
Bom
bay Current (and power) flows through low impedance paths,
governed by Kirchoff’s circuit laws, irrespective of line loading and thermal limits
In order to control the flow of active power and reactive power, regulating transformers can be used
Magnitude-regulating transformer:
The reactive power flowing through a line can be controlled by adjusting its tap setting
The transformer can also be used to modify the magnitudes of reactive powers flowing through two parallel transmission lines
Phase-shifting transformer
Control of active power flow between two interconnected parts
Redistribution of active powers between two parallel lines
11
IIT
Bom
bay
Source: S. V. Kulkarni and S. A. Khaparde, Transformer Engineering: Design, Technology, and Diagnostics, Second Edition, CRC Press, Taylor & Francis Group, New York, September 2012.
1 1 1
2 2 2
1 1 1
2 2 2
o1 1 1
2 2 2
0.425 0.3 1.000.425 0.3
0.4354 0.1525 1.050.4146 0.4475
0.1817 0.3148 1.0 40.6683 0.2852
S P jQ j aS P jQ j
S P jQ j aS P jQ j
S P jQ j aS P jQ j
G
SourceBus
LoadBus
1I
2
Load
0.15
LI
j
0.15
V
I1
I2
j
=1.0 0
I
LVS
|
|
2
1:1
1:a
1
12
IIT
Bom
bay Improvement in Stability
Equal area criterion for assessment of stability Without PST Accelerating area: abcda, Decelerating area: defgd, Margin: fghf With PST When the power angle is α + β while swinging, a phase-shift of α is
introduced Accelerating area: mnopm, Decelerating area: pqrstup, Margin: tuvt (> fghf)
Source: S. V. Kulkarni and S. A. Khaparde, Transformer Engineering: Design, Technology, and Diagnostics, Second Edition, CRC Press, Taylor & Francis Group, New York, September 2012.
PSafety margin
c
ePmech
a
b
d g h
f
0 0
Safety margin
m
n
r
su
v
o
p
q
P
t
Pmech
Without PST With PST
13
IIT
Bom
bay Power Flow with Regulating Transformers
Source: S. V. Kulkarni and S. A. Khaparde, Transformer Engineering: Design, Technology, and Diagnostics, Second Edition, CRC Press, Taylor & Francis Group, New York, September 2012.
Ideal Transformer
Inm mI
SSm
nZ1
Y=
1: a
VV a nm nVm
14
IIT
Bom
bay
Off-nominal tap ratio, a may be real (e.g., 1.04) or imaginary (ejπ/60 or 3о shift).
Lossless transformer:
or
Now,
Multiplying both sides by
m n
m m m n
m n m n
n n m m n
S S
V I aV I
I aI I a II V aV Y aY V Y V
a
,m m m n n nS V I S V I
15
IIT
Bom
bay
If a is a real number, and we can draw an equivalent πcircuit for this case:
a a
But if a is imaginary (as in a phase shifting transformer), the Y bus is not symmetrical, and we can’t draw a π equivalent circuit.
m a Y n
(a a )1 Y Vn
m ( 1 a ) YV
22 *Now,
n m m n
m m mm mn m
n n nm nn n
a I I a a Y V a Y V
V I Y Y Va Y a Ya a aV I Y Y VaY Y
16
IIT
Bom
bay Design of PSTs
V L V S V SV L
V V
S
PST
L
phase rotation
Phase-advanceA leading quadraturevoltage drop is added to the source voltage
Phase-retardA lagging quadraturevoltage drop is added to the source voltage
Phase-advance and phase-retard modes
Source: S. V. Kulkarni and S. A. Khaparde, Transformer Engineering: Design, Technology, and Diagnostics, Second Edition, CRC Press, Taylor & Francis Group, New York, September 2012.
18
IIT
Bom
bay
PSTs are manufactured in different ways depending on the power output, the rated voltage, and the amount of required phase shift. Single-core design: for smaller voltage and power ratings
Disadvantages: taps at line ends – tap changer cost increases, vulnerability to system transients
Phase-advance mode (OLTC without reversing switch)
Source: S. V. Kulkarni and S. A. Khaparde, Transformer Engineering: Design, Technology, and Diagnostics, Second Edition, CRC Press, Taylor & Francis Group, New York, September 2012.
Ve
VSRVLR
VRR2
R1 R2S L
L
LS
S
VR1R
R
R
Y
B B
R
Y
19
IIT
Bom
bay Two-core design: larger ratings
Source: S. V. Kulkarni and S. A. Khaparde, Transformer Engineering: Design, Technology, and Diagnostics, Second Edition, CRC Press, Taylor & Francis Group, New York, September 2012.
VAA’VLRVSR
Series unit
Exciting unit (Main unit)
a’a
A’AS L LS S L
R R Y Y B B
B’
B
VBB’
Advantages:The series and exciting units can be independently designed, reduced tap changer cost
20
IIT
Bom
bay
Mechanical: Low cost, slow, wear and tear, step-control
Solid-state: Smooth variation, fast acting, high cost,
complex control
Hybrid: Cost-effective
OLTC based PST: –150 to + 150 (coarse in step of 50)
and Power Electronics based PST –50 to +50 (smooth)
Overall –200 to +200 variation
Mechanical, Solid-State and Hybrid Phase-Shifters22
IIT
Bom
bay
Reduction in line reactance through a series compensator
(capacitor):
Thyristor Controlled Series Compensator (TCSC)
Voltage Source Converter (VSC) based series compensator
High Voltage DC Transmission
Other Means of Power Flow Control
VSC
+_
23
IIT
Bom
bay Challenges
Need for co-ordinated PSTs
Issue: “You work, I enjoy” – PST deployed in one region may benefit an adjacent region
Optimized location is valid for a given operating point
As the base case changes the location of PST changes – use truck mounted PSTs
Expansion of network – optimum location will change
PST design and control strategies can be site-specific – detailed systems studies are necessary
25
IIT
Bom
bay Conclusions
PST – a cost-effective option with conventional technology
Advantages: optimal line loading, stability improvement, elimination of loop flows, deferment of investment in transmission infrastructure, damping of low frequency oscillations
Potential of PSTs is unexploited in India
Relevance of PSTs is more now in the context of deregulation and penetration of intermittent renewable energy sources
26
IIT
Bom
bay References
Reddy, T., Gulati, A., Khan, M. I., and Koul, R. Application of Phase Shifting Transformer in Indian Power System, International Journal of Computer and Electrical Engineering, Vol.4, No.2, April 2012.
Belivanis, M., and Bell, K. R. W. Coordination of Phase-Shifting Transformers to Improve Transmission Network Utilisation, Innovative Smart Grid Technologies Conference Europe (ISGT Europe), 2010 IEEE PES.
IEEE Standard C57.135-2001TM, IEEE guide for the application, specification, and testing of phase-shifting transformers.
Kramer, A. and Ruff, J. Transformers for phase angle regulation considering the selection of on-load tap changers, IEEE Transactions on Power Delivery, Vol. 13, No. 2, April 1998, pp. 518–525.
Iravani, M. R. and Mathur, R. M. Damping subsynchronous oscillations in power systems using a static phase shifter, IEEE Transactions on Power Systems, Vol. PWRS-1, No. 2, May 1986, pp. 76–83.
Iravani, M. R., Dandeno, P. L., Nguyen, K. H., Zhu, D., and Maratukulam, D. Applications of static phase shifters in power systems, IEEE Transactions on Power Delivery, Vol. 9, No. 3, July 1994, pp. 1600–1608.
Del Vecchio, R. M., Poulin, B., Feghali, P. T., Shah, D. M., and Ahuja R. Power transformer design principles: with applications to core-form power transformers, Gordon and Breach Science Publishers, Canada, 2001, pp. 499–542.
27
IIT
Bom
bay
O’ Kelly, D., and Musgrave, G. Improvement of power-system transient stability by phase-shift insertion, Proceedings IEE, Vol. 120, No. 2, February 1973, pp. 247–252.
Hertem, D. V., Verboomen, J., Cole, S., and Belmans, R. Influence of phase shifting transformers and HVDC on power system losses, IEEE Power Engineering Society General Meeting, 2007, pp. 1-8.
Kulkarni, A. M. Power System Operation and Control – NPTEL Course, Module 4 : Voltage and Power Flow Control, Lecture 19.
Sweeney, B. Application of phase-shifting transformers for the enhanced interconnection between Northern Ireland and the Republic of Ireland, Power Engineering Journal, June 2002, pp. 161-167
Verboomen, J., Hertem, D. V., Schavemaker, P.H., Kling, W.L., and Belmans, R. Phase Shifting Transformers: Principles and Applications, International Conference on Future Power Systems, Nov. 2005 , Vol. 6. Belivanis, M. , and Bell, K.R.W. Use of Phase-Shifting Transformers on the
Transmission Network in Great Britain 45th International Universities Power Engineering Conference (UPEC), 2010, pp.1-5.
28