XEKAMAN 3 HPP PROJECT
UNIT 01
SCALA250 FUNCTION TEST REPORT
Prepared by:
Ma Yongkuan
Checked by:
Liu Chunlong
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-04-27 Page 2 of 23
Checked by: Liu Chunlong Date: 2013-04-27 Report No. AHCN-4R_003
TABLE OF CONTENTS
Page
1. CONTROL SYSTEM TOPOLGOY AND DIAGNOSTIC INFORMATION ........................................ 2
2. SCALA 250 CURVE AND REPORT FUNCTION ............................................................................. 4
3. SCALA 250 ALARM LIST FUNCTION ............................................................................................. 7
4. SCALA 250 EVENT LIST FUNCTION .............................................................................................. 8
5. SCALA 250 UNIT CONTROL FUNCTION........................................................................................ 9
6. SCALA 250 SEQUENCE CONTROL FUNCTION.......................................................................... 10
7. SCALA 250 GENERATOR BRAKE/LIGTING/RTD ....................................................................... 11
8. SCALA 250 UNIT01 GENERATOR LUBRICATION...................................................................... 12
9. SCALA 250 GOVERNOR OIL SYSTEM......................................................................................... 13
10. SCALA 250 TURBINE & MAIN INLET VLAVE............................................................................ 14
11. SCALA 250 UNIT01 MAIN TRANSFORMER .............................................................................. 15
12. SCALA 250 UNIT01 VIBRATION ................................................................................................. 16
13. SCALA 250 UNIT01 TEMPERATURE ......................................................................................... 17
14. SCALA 250 COMMON I-AIR SYSTEM ........................................................................................ 18
15. SCALA 250 COMMON II – COOLING WATER SYSTEM ........................................................... 19
16. SCALA 250 COMMON III – AC STATION SERVICE .................................................................. 20
17. CONCLUSIONS OF ACTIONS AND TESTS ............................................................................... 21
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 2 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
1. CONTROL SYSTEM TOPOLGOY AND DIAGNOSTIC INFORMATION
All devices for the control system specified by the client, they are installed, inspected and tested, and now are normally working forthe run of the Unit01 and Unit02.
Pic 001 SCALA250 CSCS Topology
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 3 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
Upon the Diagnostic function test and implementation, the following pic will show you the status of the LCU01 working status..
Pic 002 SCALA 250 Diagnostics Information
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 4 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
2. SCALA 250 CURVE AND REPORT FUNCTION
As for the standard function configuration of SCALA 250, running in the Center Control Room, the curve and report function had been tested andimplemented .Further, the XKM3 site operators had used them in the early half of the last year for the Unit dry and wet test.
Pic 003 SCALA250 Curve and Report
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 5 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
The following is the Curve Picture.
Pic 004 SCALA 250 Curve
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 6 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
The following is the Report Picture.
. Pic 005 SCALA 250 Report
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 7 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
3. SCALA 250 ALARM LIST FUNCTION
Pic 006 SCALA 250 Alarm List
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 8 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
4. SCALA 250 EVENT LIST FUNCTION
Pic 007 SCALA 250 Event List
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 9 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
5. SCALA 250 UNIT CONTROL FUNCTION
Pic 008 SCALA 250 Unit01 Control
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 10 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
6. SCALA 250 SEQUENCE CONTROL FUNCTION
Pic 009 SCALA 250 Unit01 Sequence Control
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 11 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
7. SCALA 250 GENERATOR BRAKE/LIGTING/RTD
Pic 010 SCALA 250 Unit01 Generator (AUX)
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 12 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
8. SCALA 250 UNIT01 GENERATOR LUBRICATION
Pic 011 SCALA 250 LCU01 Generator Lubrication
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 13 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
9. SCALA 250 GOVERNOR OIL SYSTEM
Pic 012 SCALA 250 LCU01 Governor Oil System
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 14 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
10. SCALA 250 TURBINE & MAIN INLET VLAVE
Pic 013 SCALA 250 Turbine and Main Inlet Valve
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 15 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
11. SCALA 250 UNIT01 MAIN TRANSFORMER
Pic 014 SCALA 250 Unit01 Main Transformer
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 16 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
12. SCALA 250 UNIT01 VIBRATION
Pic 015 SCALA 250 Unit01 Vibration
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 17 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
13. SCALA 250 UNIT01 TEMPERATURE
Pic 016 SCALA 250 Unit01 Temperature
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 18 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
14. SCALA 250 COMMON I-AIR SYSTEM
Pic 017 SCALA 250 Common I-Air System
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 19 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
15. SCALA 250 COMMON II – COOLING WATER SYSTEM
Pic 018 SCALA 250 Common II-Cooling Water System
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 20 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
16. SCALA 250 COMMON III – AC STATION SERVICE
Pic 019 SCALA 250 Common III-AC Station Service
SCALA 250 Function Test Report
U01
Client : XPC Project: XEKAMAN 3 HPP Code: XKM-HAH
Prepared by: Ma Yongkuan Date: 2013-07-16 Page 21 of 23
Checked by: Liu Chunlong Date: 2013-07-20 Report No. AHCN-XKM3-U01
17. CONCLUSIONS OF ACTIONS AND TESTS
The actions and measures are specified in the meeting memo .The test are executed and witnessed by the K-WATER/AH/LS/ENC engineers inthe Sangju power house. The result is Okay.