Download - VOLTAS JPSK
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 1
S.No ITEM DESCRIPTION Qty Unit Rate Amount
b) MEDIA CENTRE 21.00 SUB STATION SAFETY EQUIPMENT : MC 2 MISC
1.10 MC 2 MISC
MC 2 MISC
a) 1100 V grade size 1000 x 900 x 15 mm thick 15 Nos. MC 2 MISC
1.20 1 No. MC 2 MISC
1.30 ur Nos. MC 2 MISC
1.40 Providing first aid box as per IS:13115. 1 Set MC 2 MISC
MC 2 MISC
MC 2 BBT
2.0 BUS DUCT/BUS BAR TRUNKING SYSTEM : MC 2 BBT
MC 2 BBT
2.1 Bus Duct : MC 2 BBT
MC 2 BBT
MC 2 BBT
MC 2 BBT
a)
ur RM
MC 2 BBT
MC 2 BBT
b)
ur RM
MC 2 BBT
MC 2 BBT
c)
ur RM
MC 2 BBT
MC 2 BBT
2.2 Bus Bar Trunking (BBT) : MC 2 BBT
MC 2 BBT
BUILDING NAME
ITEM CODE
Supplying and fixing 1000 mm x 900 mm wide checkered rubber matting conforming to IS 15652-2006 complete as required.
Supplying & fixing standard shock treatment charts in English & Hindi / (Local Language) duly framed and covered with glass.
Providing & fixing HT danger notice plate 200 mm x 150 mm made of mild steel atleast 2mm thick & vitreous enameled white on both sides and with inscription in signal red colour with skull & bone on front side as required.
TOTAL OF SUB STATION SAFETY EQUIPMENT CARRIED OVER TO SUMMARY
Design, manufacturing, supply, installation, testing & commissioning (at site) of sheet steel enclosed 3 phase & neutral, 400V, 50 Hz., 50 KA copper conductor bus duct with insulation of thermal rating confirming to class 'H' including bends, transposition piece, expansion joint, Tees, End termination units, Feeder units, tap off unit etc. with all flexible connections as per specifications and drawings with all accessories, supports and termination of bus duct to switchgear/transformer.
3000A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 8 Nos. of Terminations and all other accessories as required as per specifications, and approved Shop Drawings.
2000A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 4 Nos. of Terminations and all other accessories as required as per specifications, and approved Shop Drawings.
2500A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 4 Nos. of Terminations and all other accessories as required as per specifications, and approved Shop Drawings.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 2
2.2.1
MC 2 BBT
MC 2 BBT
MC 2 BBT
MC 2 BBT
i)ur RM
MC 2 BBT
MC 2 BBT
ii)ur RM
MC 2 BBT
MC 2 BBT
iii)ur RM
MC 2 BBT
MC 2 BBT
iv)ur RM
MC 2 BBT
MC 2 BBT
v)ur RM
MC 2 BBT
vi)ur RM
MC 2 BBT
MC 2 BBT
vii)ur RM
MC 2 BBT
MC 2 BBT
viii)ur RM
MC 2 BBT
MC 2 BBT
ix)ur RM
MC 2 BBT
MC 2 BBT
Notes: MC 2 BBT
MC 2 BBT
a)MC 2 BBT
MC 2 BBT
b) Rates shall be inclusive of all accessories & fittings. MC 2 BBT
MC 2 BBT
Design, manufacture, assembly, supply, installation, testing and commissioning (at site) of following capacity compact, Copper Conductor, Bus Bar Trunking System including Bends, Tees, Expansion Joints, Feeder Units, Tap off Units, Transposition pieces, Flexible Connections etc. with all other Hardware/accessories required for installation of Bus Bar Trunking as per Specifications, approved Shop Drawings and instruction of Engineer-in-charge.
Shutter type spring loaded arrangements shall be provided for tap off system. The shutter shall get closed when tap off box is taken out. Tap off facilities shall be there at every 500 mm interval as per standard.
1500A, TPN+E, 400 Volt, 40 KA, compact, copper conductor BBT.
1250 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
1200 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
1000 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
800 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
630 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
400 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
250 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
200 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
The quantity mentioned above is approximate. Bidder to procure /manufacture the items as per actual site measurement & approved Shop drawings.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 3
2.2.2
MC 2 BBT
MC 2 BBT
i) 250A, TPN MCCB Tap off box. ur No. MC 2 BBT
MC 2 BBT
ii) 125A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT
iii) 100A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT
iv) 80A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT
v) 63A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT
vi) 40A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT
vii) 32A TPN MCCB Tap off box. ur Nos. MC 2 BBT
MC 2 BBT
2.2.3
MC 2 BBT
MC 2 BBT
a) 1500 Amp with 1600 Amp, TPN, 40 KA, MDO ACB. ur Nos. MC 2 BBT
MC 2 BBT
b) 1250 Amp with 1250 Amp, TPN, 40 KA, MDO ACB. ur Nos. MC 2 BBT
MC 2 BBT
c) 1200 Amp with 1200 Amp, TPN, 40 KA, MDO ACB. ur Nos. MC 2 BBT
MC 2 BBT
d) 1000 Amp with 1000 Amp, TPN, 40 KA, MDO ACB. ur Nos. MC 2 BBT
MC 2 BBT
e) 800 Amp with 800 Amp, TPN, 40 KA, MDO ACB. ur Nos. MC 2 BBT
MC 2 BBT
f) 630 Amp with 630 Amp, TPN, 40 KA, MCCB. ur Nos. MC 2 BBT
g) 400 Amp with 400 Amp, TPN, 40 KA, MCCB. ur Nos. MC 2 BBT
MC 2 BBT
h) 250 Amp with 250 Amp, TPN, 40 KA, MCCB. ur Nos. MC 2 BBT
MC 2 BBT
MC 2 BBT
2.2.4 MC 2 PANEL
Design, manufacture, assembly, supply, installation, testing and commissioning of plug-in type TPN tap off box of following capacity on the existing Bus Bar Trunking and complete with TPN MCCBs, links, interconnections, earthing etc. as required, as per specifications and as per approved Shop drawings.
Design, Manufacture, Supply, installation, testing and commissioning of End Feed Box/Bus Bar Trunking Adapter Box, of following ratings with Digital Voltmeter & Ammeter (ELF 3259 of Conzerv or Equivalent) complete with 5VA, class 1.0 CTs of required ratio and one set of phase indication lamps and back-up SPMCBs, as per approved drawing and specifications.
Design, Manufacturing, Supply, installation, testing and commissioning of Bus Coupler panels with ACB/MCCB of following ratings for Bus Duct/Bus Bar Trunking System.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 4
- MC 2 PANEL
MC 2 PANEL
- MC 2 PANEL
- MC 2 PANEL
MC 2 PANEL
a) ur Nos. MC 2 PANEL
MC 2 PANEL
b) ur Nos. MC 2 PANEL
MC 2 PANEL
c) ur Nos. MC 2 PANEL
MC 2 PANEL
Notes: MC 2 PANEL
MC 2 PANEL
i) MC 2 PANEL
MC 2 PANEL
ii) MC 2 PANEL
MC 2 PANEL
MC 2 PANEL
3.00 LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS: MC 2 PANEL
MC 2 PANEL
LV SWITCHGEAR PANELS : MC 2 PANEL
MC 2 PANEL
The Bus Coupler panel shall consist of 400V, 40 KA@ 1 Sec, 4 pole, Draw out type, Electrically operated, ACB/MCCB complete with under voltage and shunt trip release, antipumping protection, ON/OFF indication lamps etc. as required, as per specifications and approved Shop drawings.
Bus Couper Panel shall be suitable for Termination of Compact Bus Bar Trunking from Top/Bottom as per approved shop drawing.
Bus Coupler Breaker shall have suitable No. of NO/NC contacts for required interlocking with the Breakers of End feed units of Bus Bar Trunking.
Bus Coupler Panel with 1000 Amp, 400V, 40 KA @ 1 Sec, 4 Pole, EDO ACB
Bus Coupler Panel with 800 Amp, 400V, 40 KA @ 1 Sec, 4 Pole, EDO ACB
Bus Coupler Panel with 630 Amp, 400V, 40 KA @ 1 Sec, 4 Pole, Motorised MCCB
The fabrication of bus duct/Bus Bar Trunking shall be taken up only after actual measurement and site routing. Necessary bends/transposition pieces/ expansion joints etc. shall be estimated & included. Payment will be made on running meter basis.
The supply and fabrication & installation of structural steel for bus duct/Bus Bar Trunking support is included in the above items.
TOTAL OF BUS DUCT/BUS BAR TRUNKING SYSTEM CARRIED OVER TO SUMMARY
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 5
. MC 2 PANEL
MC 2 PANEL
Important Notes: Common for all Switchboard: MC 2 PANEL
MC 2 PANEL
1.00 MC 2 PANEL
MC 2 PANEL
2.00 Fault current wherever mentioned shall be Ics value. MC 2 PANEL
MC 2 PANEL
3.00 MC 2 PANEL
MC 2 PANEL
4.00 All feeder doors shall have pad locking arrangement. MC 2 PANEL
MC 2 PANEL
5.00 All TP feeders shall have solid isolable neutral link. MC 2 PANEL
MC 2 PANEL
6.00 MC 2 PANEL
MC 2 PANEL
7.00 All power contactors including NIC shall be of AC3 duty. MC 2 PANEL
MC 2 PANEL
8.00 MC 2 PANEL
MC 2 PANEL
9.00 MC 2 PANEL
Design, manufacture, supply, unloading, receiving, storing, handling, installation, testing and commissioning of following LV panels suitable for 400 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, Copper bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of as indicated elsewhere or shown in Single Line Diagrams.
The BOQ shall be read inconjunction with general notes, specification and Single Line Diagrams. Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Employer before quoting the rates, otherwise stringent condition shall be deemed to have been considered.
All MCCB shall be provided with door interlocked rotary handle with ON/OFF/TRIP position indicator, microprocessor based releases for over current, selectable short circuit and instentaneous short circuit protection (settable at site). I/C MCCB shall be provided with E/F release/ protection also.
All MCCB used in starter feeder shall be suitable for motor duty application.
All ACB's shall be with micro processor based O/C and S/C releases and Breaker Control Switch (BCS) having lost motion device. I/C ACBs shall be provided with E/F release also. Bus coupler shall be provided without releases.
Spare contacts of ACB/Relays/Contactor etc. shall be wired upto terminal block.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 6
10.00 MC 2 PANEL
MC 2 PANEL
11.00 Capacitor shall be super heavy duty type (MPP technology). MC 2 PANEL
MC 2 PANEL
12.00 MC 2 PANEL
MC 2 PANEL
13.00 MC 2 PANEL
MC 2 PANEL
14.00 MC 2 PANEL
MC 2 PANEL
15.00 All CT, PT shall be epoxy resin cast. MC 2 PANEL
MC 2 PANEL
16.00 All meters are digital type. MC 2 PANEL
MC 2 PANEL
17.00 MC 2 PANEL
MC 2 PANEL
18.00 MC 2 PANEL
MC 2 PANEL
19.00 MC 2 PANEL
MC 2 PANEL
20.00 Bus bar chamber shall be kept at top of the all panels. MC 2 PANEL
MC 2 PANEL
21.00 MC 2 PANEL
MC 2 PANEL
22.00 MC 2 PANEL
MC 2 PANEL
23.00 All indicating light shall be LED type . MC 2 PANEL
MC 2 PANEL
24.00 MC 2 PANEL
MC 2 PANEL
25.00 MC 2 PANEL
MC 2 PANEL
26.00 MC 2 PANEL
All switchgear used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to submit manufacturers type-2 co-ordination chart for the make used.
All outgoing terminals (power and control) shall be brought upto cable alley. 10% extra terminals shall be provided.
10% extra indicating lamp in loose shall be supplied along with panel.
Removable lifting hook shall be provided in all transportation section.
Panel shall be powder coated of approved shade with minimum 60 micron thickness.
ACB's/MCCB's in one particular panel shall be of one similar make.
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal shall be used in the panel.
All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB,BK as per colour code.
Internal wiring of panel shall be with size 2.5sqmm Flexible Copper Conductor for CT circuit and control wiring with 1.5 sqmm.
Each vertical section of floor mounted panel shall have independent base frame (75mm x 40mm) size made out of 3 mm sheet steel (LT Panel & DG Panel).
All the makes shall be as per Employer's approved make list only.
Wherever only voltmeter & ammeter are required, the same may be provided in combined meter suitable for both parameter.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 7
3.10 SMDB-EE-ME2.00-E2-01 : MC 2 PANEL
Location: Ground Floor : MC 2 PANEL
MC 2 PANEL
SMDB shall Comprise of the following: MC 2 PANEL
MC 2 PANEL
a) Incomings: MC 2 PANEL
MC 2 PANEL
MC 2 PANEL
MC 2 PANEL
b) Metering & indication for incoming breaker: MC 2 PANEL
MC 2 PANEL
Incoming breaker shall be provided with MC 2 PANEL
MC 2 PANEL
i) MC 2 PANEL
MC 2 PANEL
ii) MC 2 PANEL
MC 2 PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. MC 2 PANEL
MC 2 PANEL
Notes : MC 2 PANEL
MC 2 PANEL
1.00 MC 2 PANEL
MC 2 PANEL
2.00 MC 2 PANEL
MC 2 PANEL
c) BUS BARS: MC 2 PANEL
MC 2 PANEL
MC 2 PANEL
MC 2 PANEL
d) Outgoing: MC 2 PANEL
MC 2 PANEL
MC 2 PANEL
MC 2 PANEL
One (1) No. 400 Amps, 400 V, 40kA TPN MCCB with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release, microprocessor based O/C, S/C & E/F protection etc. complete as required for Incomming Supply Feeder as per SLD, (E/SP/ME2 5.S.01.01, Rev. A).
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
Operation interlocks as per specification & drawings indicating sufficient nos. of potential free contacts for interlocking/ indication annunciation/ control etc shall be provided by the bidder as required.
One (1) Sets of 500Amp., 40kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Copper Earth Bus of 40 x 6 mm.
Outgoing feeders, supplying to the pumps shall be provided with Earth leakage relay with CBCT as required and as per SLD (E/SP/ME2 5.S.01.01, Rev. A) and specifications.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 8
i) Two (2) Nos. 100 A, 40 KA, TPN MCCB. MC 2 PANEL
MC 2 PANEL
ii) One (1) No. 80 A, 40 KA, TPN MCCB. MC 2 PANEL
MC 2 PANEL
iii) Four (4) Nos. 63 A, 40 KA, TPN MCCB. MC 2 PANEL
MC 2 PANEL
iv) Three (3) Nos. 40 A, 40 KA, TPN MCCB. MC 2 PANEL
1 Set MC 2 PANEL
3.20 FINAL DISTRIBUTION BOARDS : MC 2 PANEL
MC 2 PANEL
MC 2 PANEL
MC 2 PANEL
3.2.1 DB-EE-ME2.00-E2-01 : MC 2 PANEL
MC 2 PANEL
Incomer: MC 2 PANEL
MC 2 PANEL
- 100A TP MCB Isolator. MC 2 PANEL
MC 2 PANEL
Busbar : MC 2 PANEL
MC 2 PANEL
- 150A 4P Cu. busbar MC 2 PANEL
MC 2 PANEL
Outgoing – (10KA) comprising MC 2 PANEL
MC 2 PANEL
Section-1 MC 2 PANEL
MC 2 PANEL
- One (1) no. 16A 3 phase, RCD (100 mA). MC 2 PANEL
MC 2 PANEL
- Fifteen (15) nos. 10A SP MCB. MC 2 PANEL
MC 2 PANEL
Section-2 MC 2 PANEL
MC 2 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC 2 PANEL
MC 2 PANEL
- Twenty One (21) nos. 20A SP MCB. MC 2 PANEL
MC 2 PANEL
- 1 Set MC 2 PANEL
MC 2 PANEL
3.2.2 DB-EE-ME2.00-E2-02 : MC 2 PANEL
MC 2 PANEL
Incomer: MC 2 PANEL
MC 2 PANEL
- 63A TP MCB Isolator. MC 2 PANEL
SMDB-EE-ME2.00-E2-01 described as above (from a to d) and as per Specifications and SLD.
Design, manufacture, supply, installation (recessed/ surface), testing and commissioning of following switch fuse Unit/ MCCB/MCB type distribution boards as per drawings & specifications. The surface distribution boards shall be mounted as required and as per specifications and relevant approved shop drawings.
DB-EE-ME2.00-E2-01 as described above and as per DB chart.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 9
MC 2 PANEL
Busbar : MC 2 PANEL
MC 2 PANEL
- 100A 4P Cu. busbar MC 2 PANEL
MC 2 PANEL
Outgoing – (10KA) comprising MC 2 PANEL
MC 2 PANEL
Section-1 MC 2 PANEL
MC 2 PANEL
- One (1) no. 16A, 3 Phase RCD (100 mA). MC 2 PANEL
MC 2 PANEL
- Nine (9) nos. 10A SP MCB. MC 2 PANEL
MC 2 PANEL
Section-2 MC 2 PANEL
MC 2 PANEL
- One (1) no. 32A, 3 Phase RCD (30 mA). MC 2 PANEL
MC 2 PANEL
- Twelve (12) nos. 20A SP MCB. MC 2 PANEL
MC 2 PANEL
- 1 Set MC 2 PANEL
3.2.3 DB-EE-ME2.10-D2-03 : MC 2 PANEL
MC 2 PANEL
Incomer: MC 2 PANEL
MC 2 PANEL
- 63A TP MCB Isolator. MC 2 PANEL
MC 2 PANEL
Busbar : MC 2 PANEL
MC 2 PANEL
- 100A 4P Cu. busbar MC 2 PANEL
MC 2 PANEL
Outgoing – (10KA) comprising MC 2 PANEL
MC 2 PANEL
Section-1 MC 2 PANEL
MC 2 PANEL
- One (1) no. 20A 3 Phase RCD (100 mA). MC 2 PANEL
MC 2 PANEL
- Twelve (12) nos. 10A SP MCB. MC 2 PANEL
MC 2 PANEL
Section-2 MC 2 PANEL
MC 2 PANEL
- One (1) no. 32A 3 Phase RCD (30 mA). MC 2 PANEL
MC 2 PANEL
- Twenty One (21) nos. 20A, SP MCB. MC 2 PANEL
MC 2 PANEL
- 1 Set MC 2 PANEL
MC 2 PANEL
3.2.4 DB-EE-ME2.10-D2-04 : MC 2 PANEL
DB-EE-ME2.00-E2-02 as described above and as per DB chart.
DB-EE-ME2.10-D2-03 as described above and as per DB chart
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 10
MC 2 PANEL
Incomer: MC 2 PANEL
MC 2 PANEL
- 100A TP MCB Isolator. MC 2 PANEL
MC 2 PANEL
Busbar : MC 2 PANEL
MC 2 PANEL
- 150A 4P Cu. busbar MC 2 PANEL
MC 2 PANEL
Outgoing – (10KA) comprising MC 2 PANEL
MC 2 PANEL
Section-1 MC 2 PANEL
MC 2 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC 2 PANEL
MC 2 PANEL
- Twenty One (21) nos. 20A SP MCB. MC 2 PANEL
MC 2 PANEL
Section-2 MC 2 PANEL
MC 2 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC 2 PANEL
MC 2 PANEL
- Twenty Four (24) nos. 20A SP MCB. MC 2 PANEL
MC 2 PANEL
- 1 Set MC 2 PANEL
MC 2 PANEL
3.30 MC 2 PANEL
MC 2 PANEL
a) 250 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC 2 PANEL
MC 2 PANEL
b) 200 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC 2 PANEL
MC 2 PANEL
c) 100 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC 2 PANEL
MC 2 PANEL
d) 63 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC 2 PANEL
MC 2 PANEL
e) 40 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC 2 PANEL
MC 2 PANEL
f) 32 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC 2 PANEL
MC 2 PANEL
MC 2 PANEL
4.00 CABLES, SUB MAINS & CABLE TRAYS : MC 2 CAB
MC 2 CAB
4.10 Cables in Under Ground Installations : MC 2 CAB
MC 2 CAB
DB-EE-ME2.10-D2-04 as described above and as per DB chart.
Design, Manufacturing, Supply, installation, Testing and Commissioning of Auto Transfer Switch Panel (ATS Panels) of following ratings as per specifications, SLD and approved Shop drawing :-
TOTAL OF LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS CARRIED OVER TO SUMMARY
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 11
MC 2 CAB
MC 2 CAB
4.1.1 MC 2 CAB
MC 2 CAB
a) 4 core 400 Sqmm 10 RM MC 2 CAB
b) 4 core 300 Sqmm 10 RM MC 2 CAB
c) 4 core 240 Sqmm 200 RM MC 2 CAB
d) 4 core 185 sqmm 10 RM MC 2 CAB
e) 4 core 150 sqmm 10 RM MC 2 CAB
f) 4 core 120 sqmm 10 RM MC 2 CAB
g) 4 core 95 sqmm 10 RM MC 2 CAB
h) 4 core 70 sqmm 20 RM MC 2 CAB
i) 4 core 50 sqmm 10 RM MC 2 CAB
j) 4 core 35 sqmm 50 RM MC 2 CAB
k) 4 core 25 sqmm 50 RM MC 2 CAB
l) 4 core 16 sqmm 20 RM MC 2 CAB
m) 4 core 10 sqmm 10 RM MC 2 CAB
n) 4 core 6 sqmm 10 RM MC 2 CAB
o) 4 core 4 sqmm 10 RM MC 2 CAB
p) 3 core 25 sqmm 10 RM MC 2 CAB
q) 3 core 16 sqmm 10 RM MC 2 CAB
r) 3 core 10 sqmm 10 RM MC 2 CAB
s) 3 core 6 sqmm 10 RM MC 2 CAB
t) 3 core 4 sqmm 10 RM MC 2 CAB
u) 2 core 6 sqmm 10 RM MC 2 CAB
v) 2 core 4 sqmm 10 RM MC 2 CAB
MC 2 CAB
4.20 Cables on Racks / Pipes / Ducts / Wireways/Cable Trays : MC 2 CAB
MC 2 CAB
MC 2 CAB
MC 2 CAB
4.2.1 Copper Conductor Armoured Cables : MC 2 CAB
MC 2 CAB
a) 4 core 400 Sqmm 10 RM MC 2 CAB
b) 4 core 300 Sqmm 10 RM MC 2 CAB
c) 4 core 240 Sqmm 100 RM MC 2 CAB
d) 4 core 185 sqmm 10 RM MC 2 CAB
Supply, installation, testing and commissioning of following sizes of PVC sheathed, XLPE insulated copper conductor power/multicore control, armoured, Multi-strand cable of 1.1 KV grade in ground including digging the trench, laying the cable with sand and brick covering, back filling reaming etc as required, as per specfications and as per directions of Engineer-in-charge.
Copper Conductor, Armoured XLPE Cables (PVC/SWA/XLPE) :
Supply, installation, testing and commissioning of following sizes of PVC sheathed, XLPE insulated, copper conductor, power/multicore, control, armoured, Multi-stranded cable of 1.1 KV grade on surface of wall or in existing cable tray /masonary ducts/hume pipe with fixing hardware etc as required, as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 12
e) 4 core 150 sqmm 10 RM MC 2 CAB
f) 4 core 120 sqmm 10 RM MC 2 CAB
g) 4 core 95 sqmm 10 RM MC 2 CAB
h) 4 core 70 sqmm 10 RM MC 2 CAB
i) 4 core 50 sqmm 10 RM MC 2 CAB
j) 4 core 35 sqmm 10 RM MC 2 CAB
k) 4 core 25 sqmm 200 RM MC 2 CAB
l) 4 core 16 sqmm 200 RM MC 2 CAB
m) 4 core 10 sqmm 100 RM MC 2 CAB
n) 4 core 6 sqmm 100 RM MC 2 CAB
o) 4 core 4 sqmm 100 RM MC 2 CAB
p) 3 core 25 sqmm 10 RM MC 2 CAB
q) 3 core 16 sqmm 10 RM MC 2 CAB
r) 3 core 10 sqmm 10 RM MC 2 CAB
s) 3 core 6 sqmm 10 RM MC 2 CAB
t) 3 core 4 sqmm 100 RM MC 2 CAB
u) 2 core 6 sqmm 10 RM MC 2 CAB
v) 2 core 4 sqmm 10 RM MC 2 CAB
MC 2 CAB
4.2.2 Copper Conductor Armoured Control Cables : MC 2 CAB
MC 2 CAB
a) 14 C 1.5 Sqmm PVC cable 10 RM MC 2 CAB
b) 10 C 1.5 Sqmm PVC cable 10 RM MC 2 CAB
c) 9 C 1.5 Sqmm PVC cable 10 RM MC 2 CAB
d) 7 C 1.5 Sqmm PVC cable 10 RM MC 2 CAB
e) 5 C 1.5 Sqmm PVC cable 100 RM MC 2 CAB
f) 3 C 1.5 Sqmm PVC cable 100 RM MC 2 CAB
MC 2 CAB
4.30 Cable Termination : MC 2 TERM
MC 2 TERM
MC 2 TERM
MC 2 TERM
4.3.1 Copper conductor armoured cables : MC 2 TERM
MC 2 TERM
a) 4 core 400 Sqmm 2 Nos. MC 2 TERM
b) 4 core 300 Sqmm 2 Nos. MC 2 TERM
c) 4 core 240 Sqmm 2 Nos. MC 2 TERM
d) 4 core 185 sqmm 2 Nos. MC 2 TERM
e) 4 core 150 sqmm 2 Nos. MC 2 TERM
f) 4 core 120 sqmm 2 Nos. MC 2 TERM
g) 4 core 95 sqmm 2 Nos. MC 2 TERM
h) 4 core 70 sqmm 2 Nos. MC 2 TERM
i) 4 core 50 sqmm 2 Nos. MC 2 TERM
Supply and making end termination with brass double compression glands for the following XLPE insulated PVC sheathed, 1100 V grade, Multi-strand copper conductor cable including cost of crimping lugs/ferrules, double compression glands, solder, cable sockets, insulation tap etc complete as required, as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 13
j) 4 core 35 sqmm 2 Nos. MC 2 TERM
k) 4 core 25 sqmm 10 Nos. MC 2 TERM
l) 4 core 16 sqmm 8 Nos. MC 2 TERM
m) 4 core 10 sqmm 4 Nos. MC 2 TERM
n) 4 core 6 sqmm 2 Nos. MC 2 TERM
o) 4 core 4 sqmm 2 Nos. MC 2 TERM
p) 3 core 25 sqmm 2 Nos. MC 2 TERM
q) 3 core 16 sqmm 2 Nos. MC 2 TERM
r) 3 core 10 sqmm 2 Nos. MC 2 TERM
s) 3 core 6 sqmm 2 Nos. MC 2 TERM
t) 3 core 4 sqmm 2 Nos. MC 2 TERM
u) 2 core 6 sqmm 2 Nos. MC 2 TERM
v) 2 core 4 sqmm 2 Nos. MC 2 TERM
4.3.2 Copper Conductor PVC Insulated Armoured Control Cables : MC 2 TERM
MC 2 TERM
MC 2 TERM
a) 14 C x 1.5 Sqmm 2 Nos. MC 2 TERM
b) 10 C x 1.5 Sqmm 2 Nos. MC 2 TERM
c) 9 C x 1.5 Sqmm 2 Nos. MC 2 TERM
d) 7 C x 1.5 Sqmm 2 Nos. MC 2 TERM
e) 5 C x 1.5 Sqmm 4 Nos. MC 2 TERM
f) 3 C x 1.5 Sqmm 4 Nos. MC 2 TERM
MC 2 TERM
Notes : MC 2 TERM
MC 2 TERM
4.40 MC 2 CAB
MC 2 CAB
a) 4 C x 185 Sqm, CWZ Cable 10 RM MC 2 CAB
b) 4 C x 150 Sqm, CWZ Cable 10 RM MC 2 CAB
c) 4 C x 120 Sqm, CWZ Cable 10 RM MC 2 CAB
d) 4 C x 95 Sqm, CWZ Cable 10 RM MC 2 CAB
e) 4 C x 70 Sqm, CWZ Cable 10 RM MC 2 CAB
f) 4 C x 50 Sqm, CWZ Cable 10 RM MC 2 CAB
g) 4 C x 35 Sqm, CWZ Cable 10 RM MC 2 CAB
h) 4 C x 25 Sqm, CWZ Cable 10 RM MC 2 CAB
i) 4 C x 16 Sqm, CWZ Cable 200 RM MC 2 CAB
j) 4 C x 10 Sqm, CWZ Cable 10 RM MC 2 CAB
k) 4 C x 6 Sqm, CWZ Cable 10 RM MC 2 CAB
l) 4 C x 4 Sqm, CWZ Cable 10 RM MC 2 CAB
(Single Compression Glands suitable for following armoured cables)
The cable quantities given are approximate and to cover various sizes. The contractor shall measure the cables required and procurement order shall be placed accordingly. The quantities shall be confirmed before start of work.
Supply, installation, testing and commissioning of 1.1 KV grade, Multicore, copper conductor, LSZH outer sheathed, CWZ fire resistant cable (in compliance with BS:6387) of following sizes on surfae of wall/existing cable trays/Mesonary Hume pipe/Duct/Trenches etc., with fixing hardware etc. as required as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 14
m) 4 C x 2.5 Sqm, CWZ Cable 10 RM MC 2 CAB
MC 2 CAB
4.50 Cable Trays : MC 2 TRAY
MC 2 TRAY
MC 2 TRAY
MC 2 TRAY
Notes : MC 2 TRAY
MC 2 TRAY
4.5.1 Ladder Type Cable tray : MC 2 TRAY
MC 2 TRAY
a) 900 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
b) 750 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
c) 600 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
d) 450 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
e) 300 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
f) 225 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
g) 100 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
MC 2 TRAY
4.5.2 Perforated Type Cable Tray : MC 2 TRAY
MC 2 TRAY
a) 900 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
b) 750 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
c) 600 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
d) 400 mm x 75 mm x 2.0 mm 50 RM MC 2 TRAY
e) 300 mm x 50 mm x 2.0 mm 50 RM MC 2 TRAY
f) 250 mm x 50 mm x 2.0 mm 10 RM MC 2 TRAY
g) 200 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
h) 150 mm x 75 mm x 2.0 mm 10 RM MC 2 TRAY
i) 100 mm x 75 mm x 2.0 mm 50 RM MC 2 TRAY
MC 2 TRAY
4.5.3 Fibreglass Ladder Type Cable Tray : MC 2 TRAY
MC 2 TRAY
MC 2 TRAY
a) 600 mm wide 10 RM MC 2 TRAY
b) 450 mm wide 10 RM MC 2 TRAY
Supply and installation of ladder type/perforated type cable trays of the following sizes fabricated out of perforated hot dip galvanised MS sheets of minimum 2.0 mm thick to be installed horizontally or vertically. The cable tray shall be complete including cost of supporting Steel/Hangers, bends, elbows, cross, tees, reducers etc as per drawings/site condition and rate shall include cost of anchor fasteners, screws, nuts, bolts and misc. other fixing hardware etc as required, as per specifications and approved Shop drawings.
The cable tray shall be factory built. Bidder shall include in his price, required numbers of Tees, Crosses, Bends, Elbows etc as required as per actual site conditions. Bidder may refer to the drawings for estimation purpose.
Supply & Installation of Ladder type Cable tray of following sizes. The Cable Tray shall be complete including the cost of Anchor fasteners, Hardware, supporting structure etc. as required and as per specifications and approved drawing :
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 15
c) 300 mm wide 10 RM MC 2 TRAY
d) 225 mm wide 10 RM MC 2 TRAY
e) 100 mm wide 10 RM MC 2 TRAY
MC 2 TRAY
4.60 Misc. Works Relating to Cabling: MC 2 PIPE
MC 2 PIPE
4.6.1 GI Pipe Installation : MC 2 PIPE
MC 2 PIPE
MC 2 PIPE
MC 2 PIPE
a) 25 mm dia 10 RM MC 2 PIPE
b) 32 mm dia 10 RM MC 2 PIPE
c) 40 mm dia 10 RM MC 2 PIPE
d) 50 mm dia 10 RM MC 2 PIPE
e) 80 mm dia 10 RM MC 2 PIPE
f) 100 mm dia 10 RM MC 2 PIPE
g) 150 mm dia 10 RM MC 2 PIPE
MC 2 PIPE
4.6.2 Flexible Conduits Installation : MC 2 PW
MC 2 PW
MC 2 PW
MC 2 PW
4.6.2.1 GI flexible conduits : MC 2 PW
MC 2 PW
a) 20 mm dia 100 RM MC 2 PW
b) 25 mm dia 200 RM MC 2 PW
c) 40 mm dia 50 RM MC 2 PW
d) 50 mm dia 50 RM MC 2 PW
MC 2 PW
5.00 WIRING : MC 2 PW
MC 2 PW
5.10 Point Wiring : MC 2 PW
MC 2 PW
The rates for point wiring shall include the circuit wiring. MC 2 PW
MC 2 PW
MC 2 PW
MC 2 PW
Supply and installation of following sizes of `A' class GI pipe for cable sleeves in recess/ on surface/Ground complete with all accessories pull boxes where ever required, G.I. fish wire, fixing hardware etc. including the chasing of wall/floor, and plastering the chased portion, digging the trench and back filling, making good the damages, sealing of pipe entry etc as required.
Supply and installation of following sizes of GI flexible conduits with all accessories including fixing nipples, couplings and fixing hardware etc as required and as per specifications.
TOTAL OF CABLES, SUB MAINS, CABLE TRAYS CARRIED OVER TO SUMMARY
Circuit wiring means the wiring from DB / Dimmer panel to the first point of circuit through control switch.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 16
MC 2 PW
MC 2 PW
MC 2 PW
MC 2 PW
MC 2 PW
MC 2 PW
MC 2 PW
MC 2 PW
5.1.1 Light Points controlled by switch : MC 2 PW
MC 2 PW
a) Single/ First light point con-trolled by a 5Amps switch. 29 Nos. MC 2 PW
MC 2 PW
b) Same as above but loop point 151 Nos. MC 2 PW
MC 2 PW
5.1.2 Light Points controlled directly from DB . MC 2 PW
MC 2 PW
i. Single/ First Point Controlled directly by MCB in DB 6 Nos. MC 2 PW
MC 2 PW
ii. Same as above but loop point. 50 Nos. MC 2 PW
MC 2 PW
5.1.3 Two way points : MC 2 PW
MC 2 PW
a) Light points controlled by 2 Nos 2 way switch. MC 2 PW
MC 2 PW
i) 1 No. MC 2 PW
MC 2 PW
ii) Same as above but loop point. 1 No. MC 2 PW
MC 2 PW
5.1.4 Presence Sensor : MC 2 PW
MC 2 PW
a) 5 Nos. MC 2 PW
5.1.5 6A Socket Points : MC 2 PW
Circuit wiring and subsequent looping shall be done with 2.5 Sqmm, 1100V grade LSZH insulated stranded, copper wires.
The rates of point wiring shall include supply, installation, testing & commissioning of MS conduit with accessories, GI Boxes and required GI flexible conduits with accessories up to the Point, LSZH insulated, stranded, Cu. Wire, switches and sockets (as approved by Engineer-in-charge) etc. as required and as per specification and direction of Engineer-in-charge.
Where the light points are directly controlled from DB (without any local control switches), the quoted rates shall not include the cost of MCBs etc. in the point wiring.
The rates of point wiring shall include earthing of each light, fan, switches, switch plates, boxes and other non current carrying metallic part with 2.5Sqm. Stranded copper, LSZH insulated, stranded, copper wire.
One / first light point controlled by two nos. two way 5 Amps. switch.
Wiring from Presence Sensor to the DB/SwitchBoard/Light fixtures, including providing Presence Sensor as required and as per approved shop drawing (wiring from DB to light points has already been included in subheads 1.1,1.2,1.3 above and not to be considered here).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 17
MC 2 PW
a) 23 Point MC 2 PW
MC 2 PW
5.20 Power Socket Wiring : MC 2 PW
MC 2 PW
MC 2 PW
MC 2 PW
5.2.1 4 Point MC 2 PW
MC 2 PW
5.2.2 10 Point MC 2 PW
MC 2 PW
5.2.3 3 Point MC 2 PW
MC 2 PW
5.2.4 2 Point MC 2 PW
Wiring for 6A, BS, switched socket outlet including providing 6A, BS, switched, socket outlet as per specification and approved shop drawing.
Power Socket Wiring shall include supply, installation, testing and commissioning of wiring of following points, including, providing conduits of suitable size, its accessories/Hardware, Junction Boxes, LSZH wires, termination of wires, switches, socket outlets, Plug tops etc. as required, as per specification and as approved by Engineer-in-charge.
Wiring for 1 No. BS, 16A, switched socket outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos.BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 3 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 3 Nos.BS outlet 16A switched with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 4 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 4 Nos.BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 18
5.2.5 5 Point MC 2 PW
MC 2 PW
5.2.6 1 Point MC 2 PW
MC 2 PW
5.2.7 2 Point MC 2 PW
MC 2 PW
5.2.8 1 Point MC 2 PW
MC 2 PW
5.2.9 6 Point MC 2 PW
MC 2 PW
Wiring for 1 No. BS, 16A, switched outlet in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. BS, 16A, switched outlet in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos. BS, 16A, switched outlet in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 3 Nos. BS, 16A, switched outlet in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 3 Nos. BS, 16A, switched outlet in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. BS, 16A, switched outlet & 1 No. IP-65 BS outlet 16A switched with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet & 1 No. IP-65 BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. BS, 16A, switched outlet (Spur Outlet) with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet (Spur Outlet) with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 19
5.2.10 1 Point MC 2 PW
MC 2 PW
5.2.11 6 Point MC 2 PW
MC 2 PW
5.2.12 42 Point MC 2 PW
MC 2 PW
5.2.13 5 Point MC 2 PW
MC 2 PW
Wiring for 1 No. BS, 32A, switched outlet in IP-65 enclosure for Water Heater with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 32A, switched outlet in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. Power & Data Pillar (type-1), each consisting of 2 Nos. 6A BS socket, 1 No. 15A Switch and 1 No. RJ-45 Data Outlets in IP-65 enclosure, with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos. Power & Data Pillar (type-1), each consisting of 2 Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45 Data Outlets in IP-65 enclosure, with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 4 Nos. Power & Data Pillar (type-1), each consisting of 2 Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45 Data outlet in IP-65 enclosure, with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 4 Nos. Power & Data Pillar (type-1), each consisting of 2 Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45 Data outlet in IP-65 enclosure, with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required.
Wiring for 2 Nos. Power & Data Pillar (type-2), each consisting of 1 No. 6A BS switched socket and 1 No. RJ-45 Data outlets in IP-65 enclosure, with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos. Power & Data Pillar (type-2), each consisting of 1 No. 6A BS switched socket and 1 No. RJ-45 Data outlets in IP-65 enclosure, with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 20
5.2.14 4 Nos. MC 2 PW
MC 2 PW
5.30 CEE INDUSTRIAL SWITCHED SOCKETS MC 2 PW
MC 2 PW
5.3.1 MC 2 PW
MC 2 PW
a) 16A, 2P+E, CEE, switched socket outlet with plug top (IP-44) 8 Nos. MC 2 PW
b) 1 No. MC 2 PW
c) 1 No. MC 2 PW
MC 2 PW
5.40 ISOLATORS MC 2 DB
MC 2 DB
MC 2 DB
MC 2 DB
a) 16A Double pole isolator 1 No. MC 2 DB
MC 2 DB
b) 16A Four pole isolator 1 No. MC 2 DB
MC 2 DB
c) 40A Four pole isolator 4 Nos. MC 2 DB
MC 2 DB
d) 63A Four pole isolator 1 No. MC 2 DB
MC 2 DB
5.50 M.S. Black Conduits : MC 2 PW
MC 2 PW
MC 2 PW
MC 2 PW
a) 20 mm dia 20 RM MC 2 PW
Wiring for 1 No. Floor LV tank consisting of 4 Nos. 6A BS switched socket and 2 Nos. RJ-45 Data Outlets in IP-65 enclosure, with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. Floor LV tank consisting of 4 Nos. 6A BS switched socket and 2 Nos. RJ-45 Data outlets in IP-65 enclosure, with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required.
Supply, installation, testing and commissioning of single phase/three phase, CEE, switched, industrial type plug and socket outlet in IP-65 enclosure including termination, earthing etc. in surface/recessed mounting as required, as per specifications and approved shop drawings (Cabling/Conduiting & wiring shall be paid separately under different items).
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-44)
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-65) for water heaters.
Supply, installation, testing and commissioning of isolators in IP-65 enclosures complete with termination in surface/recessed mounting as required.
Supply and installation of following size of MS conduit pipe in recess or on surface including all accessories MS/CI pull/junction boxes, GI fish wire, fixing hardware etc including chasing the walls/floor and plastering the chased portion and making good the damages etc, complete as required and as per specifications.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 21
b) 25 mm dia 20 RM MC 2 PW
c) 32 mm dia 20 RM MC 2 PW
d) 40 mm dia 20 RM MC 2 PW
e) 50 mm dia 20 RM MC 2 PW
MC 2 PW
5.60 Sub-mains Wiring : MC 2 PW
MC 2 PW
MC 2 PW
MC 2 PW
a) 2 x 1.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC 2 PW
b) 2 x 2.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC 2 PW
c) 2 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire. 20 RM MC 2 PW
d) 2 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC 2 PW
e) 4 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC 2 PW
f) 4 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC 2 PW
g) 2 x 10.0 Sqmm + 1 No. 6.0 Sqmm Copper earth wire 20 RM MC 2 PW
h) 4 x 10.0 Sqmm + 2 Nos. 6.0 Sqmm Copper earth wire 20 RM MC 2 PW
i) 4 x 16.0 Sqmm + 2 Nos. 10.0 Sqmm Copper earth wire 20 RM MC 2 PW
j) 4 x 25.0 Sqmm + 2 Nos. 16.0 Sqmm Copper earth wire 20 RM MC 2 PW
MC 2 PW
Note: MC 2 PW
MC 2 PW
1) MC 2 PW
MC 2 PW
2) MC 2 PW
MC 2 PW
TOTAL OF WIRING CARRIED OVER TO SUMMARY MC 2 PW
6.00 LIGHTING FIXTURES : MC 2 LIGHT
MC 2 LIGHT
MC 2 LIGHT
MC 2 LIGHT
i) 45 Nos. MC 2 LIGHT
MC 2 LIGHT
Supply and drawing of following sizes of LSZH insulated, stranded, copper conductor wires of 650/1100 Volts grade in existing conduit pipe /wire ways including connection /terminations etc as required.
In false ceiling areas the work is to be co-ordinated with respect to interior work and rate for point wiring shall include flexible conduit/fixing nipples/couplers etc from the junction box up to the fitting.
All wires used for circuit / point wiring shall be Low Smoke Zero Halogen (LSZH) wires.
Inspection, receiving, storing, handling, assembling, installation, testing and commissioning of wall /ceiling, surface/ recessed, suspended from down rod, in furniture, fluorescent / incandescent / Halogen lamp fixtures including making connections with PVC insulated stranded copper conductor wires complete including steel supports, suspenders, fixing screws, turn buckles, bolts, nuts (down rods ball and socket arrangement and special channel mounting for industrial fitting/chandelier) etc, as required. The mounting arrangement of lighting fixture shall be as indicated in the approved drawings.
Recessed Downlight 1 x 26 W (Thorn Chalice C 190H 1 X 26 W or Equivalent) (T13)
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 22
ii) 14 Nos. MC 2 LIGHT
MC 2 LIGHT
iii) 4 Nos. MC 2 LIGHT
MC 2 LIGHT
iv) 47 Nos. MC 2 LIGHT
MC 2 LIGHT
v) 19 Nos. MC 2 LIGHT
MC 2 LIGHT
vi) 6 Nos. MC 2 LIGHT
MC 2 LIGHT
vii) 2 Nos. MC 2 LIGHT
MC 2 LIGHT
viii) 3 Nos. MC 2 LIGHT
MC 2 LIGHT
ix) 21 Nos. MC 2 LIGHT
MC 2 LIGHT
x) 9 Nos. MC 2 LIGHT
MC 2 LIGHT
xi) 18 Nos. MC 2 LIGHT
MC 2 LIGHT
xii) 4 Nos. MC 2 LIGHT
xiii) 4 Nos. MC 2 LIGHT
MC 2 LIGHT
xiv) 4 Nos. MC 2 LIGHT
MC 2 LIGHT
xv) 5 Nos. MC 2 LIGHT
MC 2 LIGHT
Recessed Downlight 1 x 26 W (Thorn Chalice C 190H 1 X 26 W or Equivalent) (T13) complete with Emergency Lighting Units.
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp water proof IP44 (SITECO Europlex 24W IP44 or Equivalent) (T8)
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14)
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14) complete with Emergency Lighting Units.
Recessed outside Downlight IP54 (Trilux Downlight IP54 or Equivalent) (T21)
Wall mounted Luminaire with 2 x 35W Fluorescent T5 Lamps with Prismatic Diffuser (Thorn Prisma C 2 x 35 T16CL or Equivalent) (T19)
Wall mounted Luminaire with 2 x 35W Fluorescent T5 Lamps with Prismatic Diffuser (Thorn Prisma C 2 x 35 T16CL or Equivalent) (T19) complete with Emergency Lighting Units.
Recessed Outside Downlight IP44 (Thorn Chalice or Equivalent) (T22)
Recessed Outside Downlight IP44 (C190H 1 x 26W IP44 or Equivalent) (T22) complete with Emergency Lighting Units.
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp IP-65 (Thorn Dunube 2 x 28W IP65 or Equivalent) (T11)
Surface mounted Industrial Luminaire with 2 x 36W Fluorescent T5 Lamps (Thorn Indus RD 2 x 58W TW or Equivalent) (T6)
Surface mounted Industrial Luminaire with 2 x 36W Fluorescent T5 Lamps (Thorn Indus RD 2 x 58W TW or Equivalent) (T6) complete with Emergency Lighting Units.
CL 90 Bollard 18/24W IP65 Single-S (Siteco DL 102 Bollard Luminaire TC-L 1x18/24W IP67 or equivalent) (T28)
Emergency Exit down Fixture complete with Emergency Lighting Units (Cooper/Crompton or Approved Equivalent).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 23
xvi) 1 No. MC 2 LIGHT
MC 2 LIGHT
MC 2 LIGHT
7.00 EARTHING & LIGHTNING PROTECTION SYSTEM : MC 2 EARTH
7.10 Earthing System: MC 2 EARTH
7.1.1 4 Nos. MC 2 EARTH
MC 2 EARTH
7.1.2 ur Nos. MC 2 EARTH
MC 2 EARTH
7.1.3 ur Nos. MC 2 EARTH
MC 2 EARTH
7.1.4 Earthing Strip/Tape/Cables : MC 2 EARTH
MC 2 EARTH
MC 2 EARTH
MC 2 EARTH
7.1.4.1 G.I. Earthing strip/tape : MC 2 EARTH
MC 2 EARTH
a 50 x 8 mm strip 5 RM MC 2 EARTH
b 50 x 6 mm strip 5 RM MC 2 EARTH
c 40 x 6 mm strip 5 RM MC 2 EARTH
Emergency Exit Up Fixture complete with Emergency Lighting Units (Cooper/Crompton or Approved Equivalent).
TOTAL OF LIGHTING FIXTURES CARRIED OVER TO SUMMARY
Supply, installation, testing and commissioning of copper plate earthing stations making earth pits, earthing with copper earth plate 600 mm x 600 mm x 3.15 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS –3043 complete as required, as per specifications, drawings and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI plate earthing stations making earth pits, earthing with GI earth plate 600 mm x 600 mm x 6.30 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required, as per specifications, drawing and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI Pipe earthing stations making earth pits, earthing with GI pipe 4500 mm x 40 mm Dia including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required as per specifications, drawing and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of following sizes of GI/Tinned Copper strip/tape clamped to walls, cable trays, bus ducts, recess in Ground or surface etc for equipment/ System earthing complete as required including inter connection between length at joints, all fixing accessories saddles, clamps etc and other fixing hardware material as required, as per specifications, detail drawings shall be included for proper installation.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 24
d 32 x 6 mm strip 5 RM MC 2 EARTH
e 25 x 6 mm strip 5 RM MC 2 EARTH
f 25 x 3 mm strip 5 RM MC 2 EARTH
MC 2 EARTH
7.1.4.2 Tinned Copper earthing strip/tape : MC 2 EARTH
MC 2 EARTH
a) 50 x 6 mm 500 RM MC 2 EARTH
b) 32 x 6 mm 100 RM MC 2 EARTH
c) 25 x 6 mm 10 RM MC 2 EARTH
d) 25 x 3 mm 500 RM MC 2 EARTH
7.1.5 MC 2 CAB
MC 2 CAB
a) 1C x 185 Sqm 100 RM MC 2 CAB
MC 2 CAB
b) 1C x 90 Sqm 5 RM MC 2 CAB
MC 2 CAB
c) 1C x 50 Sqm 5 RM MC 2 CAB
MC 2 CAB
d) 1C x 35 Sqm 5 RM MC 2 CAB
MC 2 CAB
e) 1C x 25 Sqm 5 RM MC 2 CAB
MC 2 CAB
7.1.6 MC 2 EARTH
MC 2 EARTH
7.1.6.1 75 x 6 mm tinned, Copper, Earth Bars. MC 2 EARTH
MC 2 EARTH
a) 300 mm 1 No. MC 2 EARTH
b) 500 mm 1 No. MC 2 EARTH
c) 750 mm 1 No. MC 2 EARTH
d) 1000 mm 1 No. MC 2 EARTH
MC 2 EARTH
7.1.6.2 50 x 6 mm tinned, Copper, Earth Bars. MC 2 EARTH
MC 2 EARTH
a) 300 mm 5 Nos. MC 2 EARTH
b) 500 mm 5 Nos. MC 2 EARTH
c) 750 mm 2 Nos. MC 2 EARTH
d) 1000 mm 1 No. MC 2 EARTH
MC 2 EARTH
7.20 Lightning Protection System: MC 2 EARTH
Supply, installation, Termination, testing and commissioning of PVC insulated, stranded copper conductor cable, laid on surface/cable tray/duct/undger ground/Trench etc. as required, as per approved shop drawing, site conditions and as directed by Engineer-in-charge.
Supply, installation, Termination, testing and Commissioning of following sizes Tinned Copper Earth Bars including its supporting/fixing hardware, as per drawings, specifications and as directed by Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 25
MC 2 EARTH
7.2.1 4 Nos. MC 2 EARTH
MC 2 EARTH
7.2.2 6 Nos. MC 2 EARTH
MC 2 EARTH
7.2.3 Earthing Strip/Wires : MC 2 EARTH
MC 2 EARTH
0.00 MC 2 EARTH
MC 2 EARTH
a) 25 x 3 mm strip 500 RM MC 2 EARTH
MC 2 EARTH
b) 25 x 6 mm strip 100 RM MC 2 EARTH
MC 2 EARTH
c) 32 x 6 mm strip 10 RM MC 2 EARTH
MC 2 EARTH
7.2.4 MC 2 EARTH
MC 2 EARTH
7.2.4.1 75 x 6 mm GI Earth Bars. MC 2 EARTH
MC 2 EARTH
a) 300 mm 2 Nos. MC 2 EARTH
b) 500 mm 2 Nos. MC 2 EARTH
c) 750 mm 2 Nos. MC 2 EARTH
d) 1000 mm 2 Nos. MC 2 EARTH
Supply, installation, testing and commissioning of copper plate earthing stations making earth pits, earthing with copper earth plate 600 mm x 600 mm x 3.15 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS –3043 complete as required, as per drawings, specifications and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI Pipe earthing stations making earth pits, earthing with GI pipe 4500 mm x 40 mm Dia including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required, as per drawings, specifications and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of following sizes of GI strip/wire clamped to walls, Ductwork, pipe work, Structural steel work, cladding work etc. in recess, in Ground or surface etc for Lightning Protection System complete as required including inter connection, terminations, between length at joints, all fixing accessories saddles, plastic isolator mounting (of 50mmx80mm approx.), Sealing Collars, Sealing Strip, Squared Timber Block (80mmx100mm approx.), clamps, Lugs etc and other fixing hardware material as required for proper installation as per detail drawings, specifications and direction of Engineer-in-charge.
Supply, installation, Termination, testing and Commissioning of following sizes GI Earth Bars including in supporting/fixing hardware, as per drawings, specifications and as directed by Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 26
MC 2 EARTH
7.2.4.2 50 x 6 mm GI Earth Bars. MC 2 EARTH
MC 2 EARTH
a) 300 mm 2 Nos. MC 2 EARTH
b) 500 mm 2 Nos. MC 2 EARTH
c) 750 mm 2 Nos. MC 2 EARTH
d) 1000 mm 2 Nos. MC 2 EARTH
MC 2 EARTH
7.2.5 20 Nos. MC 2 EARTH
MC 2 EARTH
7.2.6 6 Nos. MC 2 EARTH
MC 2 EARTH
MC 2 EARTH
TEAM BUILDING T B
1.00 LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS: T B PANEL
T B PANEL
LV SWITCHGEAR PANELS : T B PANEL
T B PANEL
T B PANEL
T B PANEL
Important Notes: Common for all Switchboard: T B PANEL
T B PANEL
Supply and fixing of Lightning Arrestor Rod/Lightning Conductor finial made of 25 mm dia, 2.0 mm thick & 300 mm Long GI Tube having single prong at top with 75 mm dia, 6 mm thick Base plate, including connections with roof parapit Lightning protection Conductors, as per detailed drawings and as per direction of Engineer-in-charge.
Supply and fixing of "Earth Test Joints" encased in 200 mm (H) x 150 mm (W) x 100 mm (D) recessed in concrete with removable cover plate as per detailed drawing and as per direction of Engineer-in-charge.
TOTAL OF EARTHING & LIGHTNING PROTECTION SYSTEM CARRIED OVER TO SUMMARY
Design, manufacture, supply, unloading, receiving, storing, handling, installation, testing and commissioning of following LV panels suitable for 400 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, Copper bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of as indicated elsewhere or shown in Single Line Diagram.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 27
1.00 T B PANEL
T B PANEL
2.00 Fault current wherever mentioned shall be Ics value. T B PANEL
T B PANEL
3.00 T B PANEL
T B PANEL
4.00 All feeder doors shall have pad locking arrangement. T B PANEL
T B PANEL
5.00 All TP feeders shall have solid isolable neutral link. T B PANEL
T B PANEL
6.00 T B PANEL
T B PANEL
7.00 All power contactors including NIC shall be of AC3 duty. T B PANEL
T B PANEL
8.00 T B PANEL
9.00 T B PANEL
T B PANEL
10.00 T B PANEL
T B PANEL
11.00 Capacitor shall be super heavy duty type (MPP technology). T B PANEL
T B PANEL
12.00 T B PANEL
T B PANEL
13.00 T B PANEL
T B PANEL
14.00 T B PANEL
T B PANEL
15.00 All CT, PT shall be cast resin. T B PANEL
T B PANEL
The BOQ shall be read inconjunction with general notes, specification and Single Line Diagram. Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Employer before quoting the rates, otherwise stringent condition shall be deemed to have been considered.
All MCCB shall be provided with door interlocked rotary handle with ON/OFF/Trip position indicator, microprocessor based releases for over current, selectable short circuit and instentaneous short circuit protection (settable at site). I/C MCCB shall be provided with E/F release/ protection also.
All MCCB used in starter feeder shall be suitable for motor duty application.
All ACB's shall be with micro processor based O/C and S/C releases and Breaker Control Switch (BCS) having lost motion device. I/C ACBs shall be provided with E/F release also. Bus coupler shall be provided without releases.
Spare contacts of ACB/Relays/Contactor etc. shall be wired upto terminal block.
All switchgear used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to submit manufacturers type-2 co-ordination chart for the make used.
All outgoing terminals (power and control) shall be brought upto cable alley. 10% extra terminals shall be provided.
10% extra indicating lamp in loose shall be supplied along with panel.
Removable lifting hook shall be provided in all transportation section.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 28
16.00 All meters are digital type. T B PANEL
T B PANEL
17.00 T B PANEL
T B PANEL
18.00 T B PANEL
T B PANEL
19.00 T B PANEL
T B PANEL
20.00 Bus bar chamber shall be kept at top of the all panels. T B PANEL
T B PANEL
21.00 T B PANEL
T B PANEL
22.00 T B PANEL
T B PANEL
23.00 All indicating light shall be LED type . T B PANEL
T B PANEL
24.00 T B PANEL
T B PANEL
25.00 T B PANEL
T B PANEL
26.00 T B PANEL
T B PANEL
1.10 T B PANEL
T B PANEL
Comprisising of the following: T B PANEL
T B PANEL
a) Incomings: T B PANEL
T B PANEL
T B PANEL
T B PANEL
b) Metering & indication for incoming breakers: T B PANEL
T B PANEL
Incoming breaker shall be provided with T B PANEL
T B PANEL
Panel shall be powder coated of approved shade with minimum 60 micron thickness.
ACB's/MCCB's in one particular panel shall be of one similar make.
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal shall be used in the panel.
All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB,BK as per colour code.
Internal wiring of panel shall be with size 2.5sqmm Flexible Copper Conductor for CT circuit and control wiring with 1.5 sqmm.
Each vertical section of floor mounted panel shall have independent base frame (75mm x 40mm) size made out of 3 mm sheet steel (LT Panel & DG Panel).
All the makes shall be as per Employer's approved make list only.
Wherever only voltmeter & ammeter are required, the same may be provided in combined meter suitable for both parameter.
SDB-EE-TB-03-J06, SDB-EE-TB-04-H09, SDB-EE-TB-08-J19, SDB-EE-TB-09-H21, SDB-EE-TB10-H23, SDB-EE-TB11-J27, SDB-EE-TB15-H36, SDB-EE-TB16-J39
One (1) No.160Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP/ indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 29
i) T B PANEL
T B PANEL
ii) T B PANEL
T B PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. T B PANEL
T B PANEL
Note: T B PANEL
T B PANEL
c) BUS BARS: T B PANEL
T B PANEL
T B PANEL
T B PANEL
d) Outgoing: T B PANEL
T B PANEL
i) Three (3) Nos. 100 A, 36 KA, TPN MCCB. T B PANEL
T B PANEL
8 Set T B PANEL
T B PANEL
1.20 T B PANEL
T B PANEL
Comprisising of the following: T B PANEL
T B PANEL
a) Incomings: T B PANEL
T B PANEL
T B PANEL
T B PANEL
b) Metering & indication for incoming breakers: T B PANEL
T B PANEL
Incoming breaker shall be provided with T B PANEL
T B PANEL
i) T B PANEL
T B PANEL
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 150/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
200Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-TB-03-J06, SDB-EE-TB-04-H09, SDB-EE-TB-08-J19, SDB-EE-TB-09-H21, SDB-EE-TB10-H23, SDB-EE-TB11-J27, SDB-EE-TB15-H36, SDB-EE-TB16-J39 described as above (from a to d) and as per SLD
SDB-EE-TB-01-H01, SDB-EE-TB-02-G04, SDB-EE-TB-05-G13, SDB-EE-TB-06-J13, SDB-EE-TB07-G16, SDB-EE-TB12-G29, SDB-EE-TB13-J32, SDB-EE-TB14-G32, SDB-EE-TB17-G41, SDB-EE-TB18-G44
One (1) No.100Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP/ indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 30
ii) T B PANEL
T B PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. T B PANEL
T B PANEL
Note: T B PANEL
T B PANEL
c) BUS BARS: T B PANEL
T B PANEL
T B PANEL
T B PANEL
d) Outgoing: T B PANEL
T B PANEL
i) Three (3) Nos. 100 A, 36 KA, TPN MCCB. T B PANEL
T B PANEL
10 Set T B PANEL
T B PANEL
1.30 FINAL DISTRIBUTION BOARDS T B PANEL
T B PANEL
T B PANEL
T B PANEL
1.3.1 DB-EE-TB01-G01, DB-EE-TB18-G44 : T B PANEL
T B PANEL
Incomer: T B PANEL
- 125A TPN MCCB. T B PANEL
T B PANEL
Busbar : T B PANEL
- 150A 4P Cu. Busbar T B PANEL
T B PANEL
Outgoing – (10KA) comprising T B PANEL
T B PANEL
Section-1 T B PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). T B PANEL
T B PANEL
One (1) set 3 Nos. CTs of ratio 100/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
200Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-TB-01-H01, SDB-EE-TB-02-G04, SDB-EE-TB-05-G13, SDB-EE-TB-06-J13, SDB-EE-TB07-G16, SDB-EE-TB12-G29, SDB-EE-TB13-J32, SDB-EE-TB14-G32, SDB-EE-TB17-G41, SDB-EE-TB18-G44 described as above (from a to d) and as per SLD
Design, manufacture, supply, installation (recessed/ surface), testing and commissioning of following switch fuse Unit/ MCCB/MCB type distribution boards as per drawings & specifications fabricated out of 14 SWG, CRCA sheet steel in compartmentalised design as per specification and drawings. The surface distribution boards shall be mounted on 50 x 50 x 6 MS angle frame work grounted to floor/ walls. The rate includes the angle iron frame, support, painting, numbering, earthing etc as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 31
- Twenty Four (24) nos. 10A SP MCB. T B PANEL
T B PANEL
Section-2 Part-1 T B PANEL
T B PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Four (4) nos. 6A SP MCB. T B PANEL
T B PANEL
- Eight (8) nos. 16A SP MCB. T B PANEL
T B PANEL
- Three (3) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) nos. 32A TPN MCB. T B PANEL
T B PANEL
Section-2 Part-2 T B PANEL
T B PANEL
- One (1) no. 32A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Nine (9) nos. 6A SP MCB. T B PANEL
T B PANEL
- Six (6) nos. 16A SP MCB. T B PANEL
T B PANEL
- Two (2) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) nos. 32A TPN MCB. T B PANEL
T B PANEL
- 2 Set T B PANEL
T B PANEL
T B PANEL
Incomer: T B PANEL
- 125A TPN MCCB. T B PANEL
T B PANEL
Busbar : T B PANEL
- 150A 4P Cu. Busbar T B PANEL
T B PANEL
Outgoing – (10KA) comprising T B PANEL
T B PANEL
Section-1 T B PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). T B PANEL
T B PANEL
- Twenty Four (24) nos. 10A SP MCB. T B PANEL
T B PANEL
Section-2 Part-1 T B PANEL
T B PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Four (4) nos. 6A SP MCB. T B PANEL
DB-EE-TB01-G01, DB-EE-TB18-G44 as described above and as per DB chart.
DB-EE-TB02-G05, DB-EE-TB07-G17, DB-EE-TB12-G28, DB-EE-TB17-G40 :
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 32
T B PANEL
- Eight (8) nos. 16A SP MCB. T B PANEL
T B PANEL
- Three (3) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) no. 32A TPN MCB. T B PANEL
T B PANEL
Section-2 Part-2 T B PANEL
T B PANEL
- One (1) no. 32A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Eight (8) nos. 6A SP MCB. T B PANEL
T B PANEL
- Seven (7) nos. 16A SP MCB. T B PANEL
T B PANEL
- Two (2) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) no. 32A TPN MCB. T B PANEL
T B PANEL
- 4 Set T B PANEL
T B PANEL
1.3.3 DB-EE-TB03-J07 : T B PANEL
T B PANEL
Incomer: T B PANEL
T B PANEL
- 125A TPN MCCB. T B PANEL
T B PANEL
Busbar : T B PANEL
T B PANEL
- 150A 4P Cu. Busbar T B PANEL
T B PANEL
Outgoing – (10KA) comprising T B PANEL
T B PANEL
Section-1 T B PANEL
T B PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). T B PANEL
T B PANEL
- Twenty Four (24) nos. 10A SP MCB. T B PANEL
T B PANEL
Section-2 Part-1 T B PANEL
T B PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Five (5) nos. 6A SP MCB. T B PANEL
T B PANEL
- Seven (7) nos. 16A SP MCB. T B PANEL
T B PANEL
DB-EE-TB02-G05, DB-EE-TB07-G17, DB-EE-TB12-G28, DB-EE-TB17-G40 as described above and as per DB chart.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 33
- Three (3) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) no. 32A TPN MCB. T B PANEL
T B PANEL
Section-2 Part-2 T B PANEL
T B PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Eleven (11) nos. 6A SP MCB. T B PANEL
T B PANEL
- Thirteen (13) nos. 16A SP MCB. T B PANEL
T B PANEL
- Two (2) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) no. 32A TPN MCB. T B PANEL
T B PANEL
- DB-EE-TB03-J07 as described above and as per DB chart. 1 Set T B PANEL
T B PANEL
1.3.4 DB-EE-TB04-H10, DB-EE-TB015-H35 : T B PANEL
T B PANEL
Incomer: T B PANEL
T B PANEL
- 125A TPN MCB. T B PANEL
T B PANEL
Busbar : T B PANEL
T B PANEL
- 150A 4P Cu. Busbar T B PANEL
T B PANEL
Outgoing – (10KA) comprising T B PANEL
T B PANEL
Section-1 T B PANEL
T B PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). T B PANEL
T B PANEL
- Twenty Four (24) nos. 10A SP MCB. T B PANEL
T B PANEL
Section-2 Part-1 T B PANEL
T B PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Three (3) nos. 6A SP MCB. T B PANEL
T B PANEL
- Nine (9) nos. 16A SP MCB. T B PANEL
T B PANEL
- Three (3) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) no. 32A TPN MCB. T B PANEL
T B PANEL
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 34
Section-2 Part-2 T B PANEL
T B PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Thirteen (13) nos. 6A SP MCB. T B PANEL
T B PANEL
- Fourteen (14) nos. 16A SP MCB. T B PANEL
T B PANEL
- Two (2) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) no. 32A TPN MCB. T B PANEL
T B PANEL
- 2 Set T B PANEL
T B PANEL
1.3.5 DB-EE-TB05-G12, DB-EE-TB14-G33 : T B PANEL
T B PANEL
Incomer: T B PANEL
T B PANEL
- 125A TP MCCB. T B PANEL
T B PANEL
Busbar : T B PANEL
T B PANEL
- 150A 4P Cu. Busbar T B PANEL
T B PANEL
Outgoing – (10KA) comprising T B PANEL
T B PANEL
Section-1 T B PANEL
T B PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). T B PANEL
T B PANEL
- Twenty Four (24) nos. 10A SP MCB. T B PANEL
T B PANEL
Section-2 Part-1 T B PANEL
T B PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Four (4) nos. 6A SP MCB. T B PANEL
T B PANEL
- Eight (8) nos. 16A SP MCB. T B PANEL
T B PANEL
- Three (3) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) no. 32A TPN MCB. T B PANEL
T B PANEL
Section-2 Part-2 T B PANEL
T B PANEL
- One (1) no. 32A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
DB-EE-TB04-H10, DB-EE-TB015-H35 as described above and as per DB chart.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 35
- Four (4) nos. 6A SP MCB. T B PANEL
T B PANEL
- Seven (7) nos. 16A SP MCB. T B PANEL
T B PANEL
- One (1) no. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) no. 32A TPN MCB. T B PANEL
T B PANEL
- 2 Set T B PANEL
T B PANEL
1.3.6 DB-EE-TB06-J14, DB-EE-TB13-J31 : T B PANEL
T B PANEL
Incomer: T B PANEL
T B PANEL
- 125A TPN MCCB. T B PANEL
T B PANEL
Busbar : T B PANEL
T B PANEL
- 150A 4P Cu. Busbar T B PANEL
T B PANEL
Outgoing – (10KA) comprising T B PANEL
T B PANEL
Section-1 T B PANEL
T B PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). T B PANEL
T B PANEL
- Twenty Seven (27) nos. 10A SP MCB. T B PANEL
T B PANEL
Section-2 Part-1 T B PANEL
T B PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Four (4) nos. 6A SP MCB. T B PANEL
T B PANEL
- Eight (8) nos. 16A SP MCB. T B PANEL
T B PANEL
- Four (4) nos. 16A TPN MCB. T B PANEL
T B PANEL
Section-2 Part-2 T B PANEL
T B PANEL
- One (1) no. 40A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Eleven (11) nos. 6A SP MCB. T B PANEL
T B PANEL
- Seven (7) nos. 16A SP MCB. T B PANEL
T B PANEL
Two (2) nos. 32A TPN MCB. T B PANEL
T B PANEL
DB-EE-TB05-G12, DB-EE-TB14-G33 as described above and as per DB chart.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 36
- 2 Set T B PANEL
1.3.7 DB-EE-TB08-J18, DB-EE-TB11-J27, DB-EE-TB16-J38 : T B PANEL
T B PANEL
Incomer: T B PANEL
- 160A TPN MCCB. T B PANEL
T B PANEL
Busbar : T B PANEL
- 200A 4P Cu. Busbar T B PANEL
T B PANEL
Outgoing – (10KA) comprising T B PANEL
T B PANEL
Section-1 T B PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). T B PANEL
T B PANEL
- Twenty Four (24) nos. 10A SP MCB. T B PANEL
T B PANEL
Section-2 Part-1 T B PANEL
T B PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Five (5) nos. 6A SP MCB. T B PANEL
T B PANEL
- Seven (7) nos. 16A SP MCB. T B PANEL
T B PANEL
- Three (3) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) nos. 32A TPN MCB. T B PANEL
T B PANEL
Section-2 Part-2 T B PANEL
T B PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Eleven (11) nos. 6A SP MCB. T B PANEL
T B PANEL
- Thirteen (13) nos. 16A SP MCB. T B PANEL
T B PANEL
- Two (2) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) nos. 32A TPN MCB. T B PANEL
T B PANEL
- 3 Set T B PANEL
T B PANEL
1.3.8 DB-EE-TB09-H22, DB-EE-TB10-H23, DB-EE-TB12-G28 : T B PANEL
T B PANEL
Incomer: T B PANEL
- 125A TPN MCCB. T B PANEL
T B PANEL
DB-EE-TB06-J14, DB-EE-TB13-J31 as described above and as per DB chart.
DB-EE-TB08-J18, DB-EE-TB11-J27, DB-EE-TB16-J38 as described above and as per DB chart.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 37
Busbar : T B PANEL
- 150A 4P Cu. Busbar T B PANEL
T B PANEL
Outgoing – (10KA) comprising T B PANEL
T B PANEL
Section-1 T B PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). T B PANEL
T B PANEL
- Twenty Four (24) nos. 10A SP MCB. T B PANEL
T B PANEL
Section-2 Part-1 T B PANEL
T B PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). T B PANEL
T B PANEL
- Three (3) nos. 6A SP MCB. T B PANEL
T B PANEL
- Nine (9) nos. 16A SP MCB. T B PANEL
T B PANEL
- Three (3) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) no. 32A TPN MCB. T B PANEL
T B PANEL
Section-2 Part-2 T B PANEL
T B PANEL
- Twelve (12) nos. 6A SP MCB. T B PANEL
T B PANEL
- Twelve (12) nos. 16A SP MCB. T B PANEL
T B PANEL
- Two (2) nos. 16A TPN MCB. T B PANEL
T B PANEL
- One (1) no. 32A TPN MCB. T B PANEL
T B PANEL
- 3 Set T B PANEL
T B PANEL
T B PANEL
2.00 CABLES, SUB MAINS & CABLE TRAYS : T B CAB
T B CAB
2.10 Cables in Under Ground Installations : T B CAB
T B CAB
T B CAB
T B CAB
DB-EE-TB09-H22, DB-EE-TB10-H23, DB-EE-TB12-G28 as described above and as per DB chart.
TOTAL OF LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS CARRIED OVER TO SUMMARY
Supply, installation, testing and commissioning of following sizes of PVC sheathed, XLPE insulated copper conductor power/multicore control, armoured, Multi-strand cable of 1.1 KV grade in ground including digging the trench, laying the cable with sand and brick covering, back filling reaming etc as required, as per specfications and as per directions of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 38
2.1.1 T B CAB
T B CAB
a) 4 core 150 sqmm 10 RM T B CAB
b) 4 core 120 sqmm 10 RM T B CAB
c) 4 core 95 sqmm 10 RM T B CAB
d) 4 core 70 sqmm 10 RM T B CAB
e) 4 core 50 sqmm 10 RM T B CAB
f) 4 core 35 sqmm 10 RM T B CAB
g) 4 core 25 sqmm 10 RM T B CAB
T B CAB
2.20 Cables on Racks / Pipes / Ducts / Wireways/Cable Trays : T B CAB
T B CAB
T B CAB
T B CAB
2.2.1 Copper Conductor Armoured Cables : T B CAB
T B CAB
a) 4 core 150 sqmm 10 RM T B CAB
b) 4 core 120 sqmm 50 RM T B CAB
c) 4 core 95 sqmm 10 RM T B CAB
d) 4 core 70 sqmm 10 RM T B CAB
e) 4 core 50 sqmm 10 RM T B CAB
f) 4 core 35 sqmm 10 RM T B CAB
g) 4 core 25 sqmm 100 RM T B CAB
h) 4 core 16 sqmm 250 RM T B CAB
i) 4 core 10 sqmm 900 RM T B CAB
j) 4 core 6 sqmm 450 RM T B CAB
k) 4 core 4 sqmm 1,600 RM T B CAB
l) 3 core 25 sqmm 10 RM T B CAB
m) 3 core 16 sqmm 10 RM T B CAB
n) 3 core 10 sqmm 10 RM T B CAB
o) 3 core 6 sqmm 10 RM T B CAB
p) 3 core 4 sqmm 10 RM T B CAB
q) 2 core 6 sqmm 10 RM T B CAB
r) 2 core 4 sqmm 10 RM T B CAB
2.2.2 Copper Conductor Armoured Control Cables : T B CAB
T B CAB
a) 14 C 1.5 Sqmm PVC cable 10 RM T B CAB
b) 10 C 1.5 Sqmm PVC cable 10 RM T B CAB
c) 9 C 1.5 Sqmm PVC cable 10 RM T B CAB
d) 7 C 1.5 Sqmm PVC cable 10 RM T B CAB
e) 5 C 1.5 Sqmm PVC cable 10 RM T B CAB
f) 3 C 1.5 Sqmm PVC cable 10 RM T B CAB
Copper Conductor, Armoured XLPE Cables (PVC/SWA/XLPE) :
Supply, installation, testing and commissioning of following sizes of PVC sheathed, XLPE insulated, copper conductor, power/multicore, control, armoured, Multi-stranded cable of 1.1 KV grade on surface of wall or in existing cable tray /masonary ducts/hume pipe with fixing hardware etc as required, as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 39
T B CAB
2.30 Cable Termination : T B TERM
T B TERM
T B TERM
T B TERM
2.3.1 Copper conductor armoured cables : T B TERM
T B TERM
a) 4 core 150 sqmm 2 Nos. T B TERM
b) 4 core 120 sqmm 2 Nos. T B TERM
c) 4 core 95 sqmm 2 Nos. T B TERM
d) 4 core 70 sqmm 2 Nos. T B TERM
e) 4 core 50 sqmm 2 Nos. T B TERM
f) 4 core 35 sqmm 2 Nos. T B TERM
g) 4 core 25 sqmm 6 Nos. T B TERM
h) 4 core 16 sqmm 30 Nos. T B TERM
i) 4 core 10 sqmm 84 Nos. T B TERM
j) 4 core 6 sqmm 60 Nos. T B TERM
k) 4 core 4 sqmm 156 Nos. T B TERM
l) 3 core 25 sqmm 2 Nos. T B TERM
m) 3 core 16 sqmm 2 Nos. T B TERM
n) 3 core 10 sqmm 2 Nos. T B TERM
o) 3 core 6 sqmm 2 Nos. T B TERM
p) 3 core 4 sqmm 2 Nos. T B TERM
q) 2 core 6 sqmm 2 Nos. T B TERM
r) 2 core 4 sqmm 2 Nos. T B TERM
T B TERM
2.3.2 Copper Conductor PVC Insulated Armoured Control Cables : T B TERM
T B TERM
T B TERM
a) 14 C x 1.5 Sqmm 2 Nos. T B TERM
b) 10 C x 1.5 Sqmm 2 Nos. T B TERM
c) 9 C x 1.5 Sqmm 2 Nos. T B TERM
d) 7 C x 1.5 Sqmm 2 Nos. T B TERM
e) 5 C x 1.5 Sqmm 2 Nos. T B TERM
f) 3 C x 1.5 Sqmm 2 Nos. T B TERM
T B TERM
Notes: T B TERM
T B CAB
Supply and making end termination with brass double compression glands for the following XLPE insulated PVC sheathed, 1100 V grade, Multi-strand copper conductor cable including cost of crimping lugs/ferrules, double compression glands, solder, cable sockets, insulation tap etc complete as required, as per specifications and as per direction of Engineer-in-charge.
(Single Compression Glands suitable for following armoured cables)
The cable quantities given are approximate and to cover various sizes. The contractor shall measure the cables required and procurement order shall be placed accordingly. The quantities shall be confirmed before start of work.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 40
2.40 T B CAB
T B CAB
a) 4 C x 185 Sqm, CWZ Cable 5 RM T B CAB
b) 4 C x 150 Sqm, CWZ Cable 5 RM T B CAB
c) 4 C x 120 Sqm, CWZ Cable 5 RM T B CAB
d) 4 C x 95 Sqm, CWZ Cable 5 RM T B CAB
e) 4 C x 70 Sqm, CWZ Cable 5 RM T B CAB
f) 4 C x 50 Sqm, CWZ Cable 5 RM T B CAB
g) 4 C x 35 Sqm, CWZ Cable 5 RM T B CAB
h) 4 C x 25 Sqm, CWZ Cable 5 RM T B CAB
i) 4 C x 16 Sqm, CWZ Cable 5 RM T B CAB
j) 4 C x 10 Sqm, CWZ Cable 5 RM T B CAB
k) 4 C x 6 Sqm, CWZ Cable 5 RM T B CAB
l) 4 C x 4 Sqm, CWZ Cable 5 RM T B CAB
m) 4 C x 2.5 Sqm, CWZ Cable 5 RM T B CAB
T B CAB
2.50 Cable Trays : T B TRAY
T B TRAY
T B TRAY
T B TRAY
Notes: T B TRAY
T B TRAY
2.5.1 Ladder Type Cable tray : T B TRAY
T B TRAY
a) 900 mm x 75 mm x 2.0 mm 5 RM T B TRAY
b) 750 mm x 75 mm x 2.0 mm 5 RM T B TRAY
c) 600 mm x 75 mm x 2.0 mm 5 RM T B TRAY
d) 450 mm x 75 mm x 2.0 mm 5 RM T B TRAY
e) 300 mm x 75 mm x 2.0 mm 5 RM T B TRAY
f) 225 mm x 75 mm x 2.0 mm 5 RM T B TRAY
g) 100 mm x 75 mm x 2.0 mm 5 RM T B TRAY
T B TRAY
2.5.2 Perforated Type Cable Tray : T B TRAY
Supply, installation, testing and commissioning of 1.1 KV grade, Multicore, copper conductor, LSZH outer sheathed, CWZ fire resistant cable (in compliance with BS : 6387) of following sizes on surfae of wall/existing cable trays/Mesonary Hume pipe/Duct/Trenches etc., with fixing hardware etc. as required as per specifications and as per direction of Engineer-in-charge.
Supply and installation of ladder type/perforated type cable trays of the following sizes fabricated out of perforated hot dip galvanised MS sheets of minimum 2.0 mm thick to be installed horizontally or vertically. The cable tray shall be complete including cost of supporting Steel/Hangers, bends, elbows, cross, tees, reducers etc as per drawings/site condition and rate shall include cost of anchor fasteners, screws, nuts, bolts and misc. other fixing hardware etc as required, as per specifications and approved Shop drawings.
The cable tray shall be factory built. Bidder shall include in his price, required numbers of Tees, Crosses, Bends, Elbows etc as required as per actual site conditions. Bidder may refer to the drawings for estimation purpose.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 41
T B TRAY
a) 750 mm x 75 mm x 2.0 mm 10 RM T B TRAY
b) 600 mm x 75 mm x 2.0 mm 10 RM T B TRAY
c) 500 mm x 75 mm x 2.0 mm 10 RM T B TRAY
d) 400 mm x 75 mm x 2.0 mm 10 RM T B TRAY
e) 300 mm x 50 mm x 2.0 mm 10 RM T B TRAY
f) 250 mm x 50 mm x 2.0 mm 10 RM T B TRAY
g) 200 mm x 75 mm x 2.0 mm 800 RM T B TRAY
h) 150 mm x 75 mm x 2.0 mm 10 RM T B TRAY
i) 100 mm x 75 mm x 2.0 mm 10 RM T B TRAY
T B TRAY
2.5.3 Fibreglass Ladder Type Cable Tray : T B TRAY
T B TRAY
T B TRAY
a) 600 mm wide 5 RM T B TRAY
b) 450 mm wide 5 RM T B TRAY
c) 300 mm wide 5 RM T B TRAY
d) 225 mm wide 5 RM T B TRAY
e) 100 mm wide 5 RM T B TRAY
T B TRAY
2.60 Misc. Works Relating to Cabling: T B PIPE
T B PIPE
2.6.1 GI Pipe Installation : T B PIPE
T B PIPE
T B PIPE
T B PIPE
a) 25 mm dia 10 RM T B PIPE
b) 32 mm dia 10 RM T B PIPE
c) 40 mm dia 10 RM T B PIPE
d) 50 mm dia 10 RM T B PIPE
e) 80 mm dia 10 RM T B PIPE
f) 100 mm dia 10 RM T B PIPE
g) 150 mm dia 10 RM T B PIPE
T B PIPE
2.6.2 Flexible Conduits Installation : T B PW
T B PW
T B PW
T B PW
Supply & Installation of Ladder type Cable tray of following sizes. The Cable Tray shall be complete including the cost of Anchor fasteners, Hardware, supporting structure etc. as required and as per specifications and approved drawing :
Supply and installation of following sizes of `A' class GI pipe for cable sleeves in recess/ on surface/Ground complete with all accessories pull boxes where ever required, G.I. fish wire, fixing hardware etc. including the chasing of wall/floor, and plastering the chased portion, digging the trench and back filling, making good the damages, sealing of pipe entry etc as required.
Supply and installation of following sizes of GI flexible conduits with all accessories including fixing nipples, couplings and fixing hardware etc as required and as per specifications.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 42
2.6.2.1 GI flexible conduits : T B PW
a) 20 mm dia 100 RM T B PW
b) 25 mm dia 100 RM T B PW
c) 40 mm dia 100 RM T B PW
d) 50 mm dia 100 RM T B PW
T B PW
3.00 WIRING : T B PW
T B PW
3.10 Point Wiring : T B PW
T B PW
The rates for point wiring shall include the circuit wiring. T B PW
T B PW
T B PW
T B PW
T B PW
T B PW
T B PW
T B PW
T B PW
T B PW
T B PW
T B PW
3.1.1 Light Points controlled by switch : T B PW
T B PW
a) Single/ First light point con-trolled by a 5Amps switch. 341 No. T B PW
T B PW
b) Same as above but loop point 979 No. T B PW
T B PW
3.1.2 Light Points controlled directly from DB T B PW
T B PW
i. Single/ First Point Controlled directly by MCB in DB 4 Nos. T B PW
T B PW
ii. Same as above but loop point. 35 Nos. T B PW
T B PW
3.1.3 Light points controlled by Two Way Switch : T B PW
TOTAL OF CABLES, SUB MAINS, CABLE TRAYS CARRIED OVER TO SUMMARY
Circuit wiring means the wiring from DB / Dimmer panel to the first point of circuit through control switch.
Circuit wiring and subsequent looping shall be done with 2.5 Sqmm, 1100V grade LSZH insulated stranded, copper wires.
The rates of point wiring shall include supply, installation, testing & commissioning of MS conduit with accessories, GI Boxes and required GI flexible conduits with accessories up to the Point, LSZH insulated, stranded, Cu. Wire etc. as required and as per specification, Tender Drawing and direction of Engineer-in-charge.
Where the light points are directly controlled from DB (without any local control switches), the quoted rates shall not include the cost of MCBs etc. in the point wiring.
The rates of point wiring shall include earthing of each light, fan, switches, switch plates, boxes and other non current carrying metallic part with 2.5 Sqm. Stranded copper, LSZH insulated, stranded, copper wire.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 43
T B PW
i) 86 Nos. T B PW
T B PW
ii) Same as above but loop point. 277 Nos. T B PW
T B PW
3.1.4 Light points controlled by Twilight Switch : T B PW
T B PW
i) One / first light point controlled by Twilight switch. 18 Nos. T B PW
T B PW
ii) Same as above but loop point. 154 Nos. T B PW
T B PW
3.1.5 Light points controlled by Push Buttons : T B PW
T B PW
i) Three light points controlled by One Push Button. 1 Nos. T B PW
T B PW
ii) Four light points controlled by One Push Button. 2 Nos. T B PW
T B PW
iii) Five light points controlled by One Push Button. 2 Nos. T B PW
T B PW
iv) Six light points controlled by One Push Button. 6 Nos. T B PW
T B PW
v) Eight light points controlled by One Push Button. 4 Nos. T B PW
T B PW
vi) Five light points controlled by Two Push Buttons. 3 Nos. T B PW
T B PW
vii) Five light points controlled by Three Push Buttons. 4 Nos. T B PW
T B PW
viii) Fifteen light points controlled by Three Push Buttons. 4 Nos. T B PW
T B PW
ix) Sixteen light points controlled by Three Push Buttons. 4 Nos. T B PW
T B PW
ix) Twenty light points controlled by Three Push Buttons. 4 Nos. T B PW
T B PW
3.1.6 Presence Sensor : T B PW
T B PW
a) 4 Nos. T B PW
T B PW
3.1.7 6A Socket Points : T B PW
T B PW
a) 323 Point T B PW
T B PW
3.1.8 FCU Points controlled by 6A Switch : T B PW
One / first light point controlled by two nos. two way 5 Amps. switch.
Wiring from Presence Sensor to the DB/SwitchBoard/Light fixtures, including providing Presence Sensor as required and as per approved shop drawing (wiring from DB to light points has already been included in subheads 8.1.1, 8.1.2, 8.1.3, 8.1.4, 8.1.5 above and not to be considered here).
Wiring for 6A, BS, switched socket outlet including providing 6A, BS, switched, socket outlet as per specification and approved shop drawing.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 44
T B PW
i) 94 Nos. T B PW
T B PW
ii) Same as above but loop point. 50 Nos. T B PW
T B PW
3.20 Power Socket Wiring : T B PW
T B PW
0.00 T B PW
T B PW
3.2.1 1 Point T B PW
T B PW
3.2.2 6 Point T B PW
3.2.3 83 Point T B PW
T B PW
3.2.4 11 Point T B PW
T B PW
One / first light point controlled by 6A, BS, switched socket outlet including providing 6A, BS, switched, socket outlet.
Power Socket Wiring shall include supply, installation, testing and commissioning of wiring of following points, including, providing conduits of suitable size, its accessories/Hardware, Junction Boxes, LSZH wires, termination of wires, switches, socket outlets, Plug tops etc. as required and as per specification.
Wiring for 1 No. BS, 16A, switched socket outlet with 4.0 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. BS, 16A, switched outlet with 4.0 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 4 Nos. BS, 16A, switched outlet with 4.0 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 4 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 5 Nos. BS, 16A, switched outlet with 4.0 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 5 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 45
3.2.5 1 Point T B PW
T B PW
3.2.6 5 Point T B PW
T B PW
3.2.7 5 Point T B PW
T B PW
3.2.8 18 Point T B PW
T B PW
3.2.9 20 Point T B PW
T B PW
Wiring for 2 Nos. BS, 16A, switched outlets and 1 No. 16A DP Isolators in IP-65 enclosure with 4.0 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 No. BS, 16A, switched outlets and 1 No. 16A DP Isolator in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. BS, 16A, switched outlets and 2 Nos. 16A DP Isolators in IP-65 enclosure with 4.0 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos. BS, 16A, switched outlets and 2 Nos. 16A DP Isolators in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 4 Nos. BS, 16A, switched outlets and 1 No. 16A DP Isolator in IP-65 enclosure with 4.0 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 4 Nos. BS, 16A, switched outlets and 1 No. 16A DP Isolator in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. 16A DP Isolators in IP-65 enclosure with 4.0 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos. 16A DP Isolator in IP-65 enclosure with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 3 Nos. 16A DP Isolators in IP-65 enclosure with 4.0 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 3 Nos. 16A DP Isolator in IP-65 enclosure with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 46
3.2.10 4 Point T B PW
T B PW
3.2.11 14 Point T B PW
T B PW
3.2.12 206 Nos. T B PW
3.30 CEE INDUSTRIAL SWITCHED SOCKETS T B PW
T B PW
3.3.1 T B PW
T B PW
a) 18 No. T B PW
T B PW
3.40 ISOLATORS T B DB
T B DB
Wiring for 5 Nos. 16A DP Isolators in IP-65 enclosure with 4.0 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 5 Nos. 16A DP Isolator in IP-65 enclosure with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. Power & Data Pillar (consisting of 1 No. 6A BS socket with 1 No. 6A Switch and 1 No. RJ-45 Data outlet in IP-65 enclosure) and 1 No. Power & TV Pillar (consisting of 1 No. 6A BS socket with 1 No. 6A Switch and 1 No. RJ-11 TV outlet in IP-65 enclosure) with 2.5 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. 6A BS socket with 1 No. 6A Switch and 1 No. RJ-45 Data outlet in IP-65 enclosure and 1 No. Power & TV Pillar, consisting of 1 No. 6A BS socket with 1 No. 6A Switch and 1 No. RJ-11 TV outlet in IP-65 enclosure, with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required.
Wiring for 1 No. Floor LV tank consisting of 4 Nos. 6A BS switched socket and 2 Nos. RJ-45 Data Outlets in IP-65 enclosure, with 2.5 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. Floor LV tank consisting of 4 Nos. 6A BS switched socket and 2 Nos. RJ-45 Data outlets in IP-65 enclosure, with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required.
Supply, installation, testing and commissioning of single phase/three phase, CEE, switched, industrial type plug and socket outlet in IP-44 enclosure including termination, earthing etc. in surface/recessed mounting as required, as per specifications and approved shop drawings (Cabling/Conduiting & wiring shall be paid separately under different items).
32A, 3P+N+E, CEE, switched socket outlet with plug top (IP-44).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 47
T B DB
T B DB
a) 16A Four pole isolator 78 Nos. T B DB
T B DB
b) 32A Four pole isolator 18 Nos. T B DB
T B DB
3.50 M.S. Black Conduits : T B PW
T B PW
. T B PW
T B PW
a) 20 mm dia 20 RM T B PW
b) 25 mm dia 20 RM T B PW
c) 32 mm dia 20 RM T B PW
d) 40 mm dia 20 RM T B PW
e) 50 mm dia 20 RM T B PW
T B PW
3.60 Sub-mains Wiring : T B PW
T B PW
T B PW
T B PW
a) 2 x 1.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM T B PW
b) 2 x 2.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM T B PW
c) 2 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire. 20 RM T B PW
d) 2 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM T B PW
e) 4 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM T B PW
f) 4 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM T B PW
g) 2 x 10.0 Sqmm + 1 No. 6.0 Sqmm Copper earth wire 20 RM T B PW
h) 4 x 10.0 Sqmm + 2 Nos. 6.0 Sqmm Copper earth wire 20 RM T B PW
i) 4 x 16.0 Sqmm + 2 Nos. 10.0 Sqmm Copper earth wire 20 RM T B PW
j) 4 x 25.0 Sqmm + 2 Nos. 16.0 Sqmm Copper earth wire 20 RM T B PW
Note: T B PW
T B PW
1) T B PW
T B PW
2) T B PW
T B PW
TOTAL OF WIRING CARRIED OVER TO SUMMARY T B PW
Supply, installation, testing and commissioning of isolators in IP-65 enclosures complete with termination in surface/recessed mounting as required.
Supply and installation of following size of MS conduit pipe in recess or on surface including all accessories MS/CI pull/junction boxes, GI fish wire, fixing hardware etc including chasing the walls/floor and plastering the chased portion and making good the damages etc, complete as required and as per specifications.
Supply and drawing of following sizes of LSZH insulated, stranded, copper conductor wires of 650/1100 Volts grade in existing conduit pipe /wire ways including connection /terminations etc as required.
In false ceiling areas the work is to be co-ordinated with respect to interior work and rate for point wiring shall include flexible conduit/fixing nipples/couplers etc from the junction box up to the fitting.
All wires used for circuit / point wiring shall be Low Smoke Zero Halogen (LSZH) wires.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 48
4.00 LIGHTING FIXTURES : T B LIGHT
T B LIGHT
T B LIGHT
T B LIGHT
1.00 87 Set T B LIGHT
T B LIGHT
2.00 19 Set T B LIGHT
T B LIGHT
3.00 ur Set T B LIGHT
T B LIGHT
4.00 6 Set T B LIGHT
T B LIGHT
5.00 88 Set T B LIGHT
T B LIGHT
6.00 8 Set T B LIGHT
T B LIGHT
7.00 860 Set T B LIGHT
T B LIGHT
8.00 226 Set T B LIGHT
T B LIGHT
9.00 416 Set T B LIGHT
T B LIGHT
10.00 70 Set T B LIGHT
T B LIGHT
Inspection, receiving, storing, handling, assembling, installation, testing and commissioning of wall /ceiling, surface/ recessed, suspended from down rod, in furniture, fluorescent / incandescent / Halogen lamp fixtures including making connections with PVC insulated stranded copper conductor wires complete including steel supports, suspenders, fixing screws, turn buckles, bolts, nuts (down rods ball and socket arrangement and special channel mounting for industrial fitting/chandelier) etc, as required. The mounting arrangement of lighting fixture shall be as indicated in the approved drawings.
Surface mounted Industrial Luminaire with 1x36W Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or Equivalent) (T5).
Surface mounted Industrial Luminaire with 1x36W Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or Equivalent) (T5) complete with emergency lighting units.
Surface mounted Industrial Luminaire with 2x36W Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or Equivalent) (T6).
Surface mounted Industrial Luminaire with 2x36W Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or Equivalent) (T6) complete with emergency lighting units.
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp waterproof IP44 (Siteco Europlex 24W IP44 or Equivalent) (T8).
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp waterproof IP44 (Siteco Europlex 24W IP44 or Equivalent) (T8) complete with emergency lighting units.
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W or Equivalent) (T13)
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W or Equivalent) (T13) complete with emergency lighting units.
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14)
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14) complete with emergency lighting units.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 49
11.00 226 Set T B LIGHT
T B LIGHT
12.00 33 Set T B LIGHT
T B LIGHT
13.00 96 Set T B LIGHT
T B LIGHT
14.00 22 Set T B LIGHT
T B LIGHT
15.00 29 Set T B LIGHT
T B LIGHT
16.00 47 Set T B LIGHT
T B LIGHT
17.00 9 Set T B LIGHT
T B LIGHT
18.00 9 Set T B LIGHT
T B LIGHT
T B LIGHT
5.00 EARTHING & LIGHTNING PROTECTION SYSTEM : T B EARTH
T B EARTH
5.10 Earthing System: T B EARTH
T B EARTH
5.1.1 2 Nos. T B EARTH
T B EARTH
5.1.2 42 Nos. T B EARTH
T B EARTH
Recessed outside Downlight IP54 (Trilux Downlight IP54 or Equivalent) (T21)
Recessed outside Downlight IP54 (Trilux Downlight IP54 or Equivalent) (T21) complete with emergency lighting units.
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W T26 H2F or Equivalent) (T23).
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W T26 H2F or Equivalent) (T23) complete with emergency lighting units.
Emergency Exit Up Fixture (Cooper/Crompton or Equivalent) complete with emergency lighting units.
Emergency Exit Down Fixture (Cooper/Crompton or Equivalent) complete with emergency lighting units.
Emergency Exit Left Fixture (Cooper/Crompton or Equivalent) complete with emergency lighting units.
Emergency Exit Right Fixture (Cooper/Crompton or Equivalent) complete with emergency lighting units.
TOTAL OF LIGHTING FIXTURES CARRIED OVER TO SUMMARY
Supply, installation, testing and commissioning of copper plate earthing stations making earth pits, earthing with copper earth plate 600 mm x 600 mm x 3.15 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS –3043 complete as required, as per specifications, drawings and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI plate earthing stations making earth pits, earthing with GI earth plate 600 mm x 600 mm x 6.30 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required, as per specifications, drawing and direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 50
5.1.3 2 Nos. T B EARTH
T B EARTH
5.1.4 Earthing Strip/Tape/Cables : T B EARTH
T B EARTH
0.00 T B EARTH
T B EARTH
5.1.4.1 G.I. Earthing strip/tape : T B EARTH
T B EARTH
a 75 x 6 mm strip 10 RM T B EARTH
b 50 x 6 mm strip 10 RM T B EARTH
c 40 x 6 mm strip 100 RM T B EARTH
d 32 x 6 mm strip 100 RM T B EARTH
e 25 x 6 mm strip 100 RM T B EARTH
f 25 x 3 mm strip 1,500 RM T B EARTH
T B EARTH
5.1.4.2 Tinned Copper earthing strip/tape : T B EARTH
T B EARTH
a) 50 x 6 mm 10 RM T B EARTH
b) 32 x 6 mm 10 RM T B EARTH
c) 25 x 6 mm 10 RM T B EARTH
d) 25 x 3 mm 10 RM T B EARTH
T B EARTH
5.1.5 T B CAB
T B CAB
a) 1C x 240 Sqm 10 RM T B CAB
T B CAB
b) 1C x 185 Sqm 10 RM T B CAB
T B CAB
c) 1C x 90 Sqm 100 RM T B CAB
Supply, installation, testing and commissioning of GI Pipe earthing stations making earth pits, earthing with GI pipe 4500 mm x 40 mm Dia including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required as per specifications, drawing and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of following sizes of GI/Tinned Copper strip/tape clamped to walls, cable trays, bus ducts, recess in Ground or surface etc for equipment/ System earthing complete as required including inter connection between length at joints, all fixing accessories saddles, clamps etc and other fixing hardware material as required, as per specifications, detail drawings shall be included for proper installation.
Supply, installation, Termination, testing and commissioning of PVC insulated, stranded copper conductor cable, laid on surface/cable tray/duct/undger ground/Trench etc. as required, as per approved shop drawing, site conditions and as directed by Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 51
T B CAB
d) 1C x 50 Sqm 100 RM T B CAB
T B CAB
5.1.6 T B EARTH
T B EARTH
5.1.6.1 75 x 6 mm GI Earth Bars. T B EARTH
T B EARTH
a) 300 mm 1 No. T B EARTH
b) 500 mm 1 Nos. T B EARTH
c) 750 mm 1 Nos. T B EARTH
d) 1000 mm 1 No. T B EARTH
T B EARTH
5.1.6.2 50 x 6 mm GI Earth Bars. T B EARTH
T B EARTH
a) 300 mm 2 Nos. T B EARTH
b) 500 mm 7 Nos. T B EARTH
c) 750 mm 7 Nos. T B EARTH
d) 1000 mm 2 Nos. T B EARTH
T B EARTH
5.20 Lightning Protection System: T B EARTH
T B EARTH
5.2.1 2 Nos. T B EARTH
T B EARTH
5.2.2 110 Nos. T B EARTH
T B EARTH
5.2.3 Earthing Strip/Wires : T B EARTH
T B EARTH
Supply, installation, Termination, testing and Commissioning of following sizes GI Earth Bars including its supporting/fixing hardware, as per drawings, specifications and as directed by Engineer-in-charge.
Supply, installation, testing and commissioning of copper plate earthing stations making earth pits, earthing with copper earth plate 600 mm x 600 mm x 3.15 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS –3043 complete as required, as per drawings, specifications and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI Pipe earthing stations making earth pits, earthing with GI pipe 4500 mm x 40 mm Dia including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required, as per drawings, specifications and direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 52
T B EARTH
T B EARTH
a) 25 x 3 mm strip 2,400 RM T B EARTH
T B EARTH
b) 25 x 6 mm strip 1,000 RM T B EARTH
T B EARTH
c) 32 x 6 mm strip 10 RM T B EARTH
T B EARTH
5.2.4 T B EARTH
T B EARTH
5.2.4.1 75 x 6 mm GI Earth Bars. T B EARTH
T B EARTH
a) 300 mm 2 Nos. T B EARTH
b) 500 mm 2 Nos. T B EARTH
c) 750 mm 2 Nos. T B EARTH
d) 1000 mm 2 Nos. T B EARTH
T B EARTH
5.2.4.2 50 x 6 mm GI Earth Bars. T B EARTH
T B EARTH
a) 300 mm 2 Nos. T B EARTH
b) 500 mm 2 Nos. T B EARTH
c) 750 mm 2 Nos. T B EARTH
d) 1000 mm 2 Nos. T B EARTH
T B EARTH
5.2.5 110 Nos. T B EARTH
T B EARTH
5.2.6 110 Nos. T B EARTH
T B EARTH
Supply, installation, testing and commissioning of following sizes of GI strip/wire clamped to walls, Ductwork, pipe work, Structural steel work, cladding work etc. in recess, in Ground or surface etc for Lightning Protection System complete as required including inter connection, terminations, between length at joints, all fixing accessories saddles, plastic isolator mounting (of 50mmx80mm approx.), Sealing Collars, Sealing Strip, Squared Timber Block (80mmx100mm approx.), clamps, Lugs etc and other fixing hardware material as required for proper installation as per detail drawings, specifications and direction of Engineer-in-charge.
Supply, installation, Termination, testing and Commissioning of following sizes GI Earth Bars including in supporting/fixing hardware, as per drawings, specifications and as directed by Engineer-in-charge.
Supply and fixing of Lightning Arrestor Rod/Lightning Conductor finial made of 25 mm dia, 2.0 mm thick & 300 mm Long GI Tube having single prong at top with 75 mm dia, 6 mm thick Base plate, including connections with roof parapit Lightning protection Conductors, as per detailed drawings and as per direction of Engineer-in-charge.
Supply and fixing of "Earth Test Joints" encased in 200 mm (H) x 150 mm (W) x 100 mm (D) recessed in concrete with removable cover plate as per detailed drawing and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 53
T B EARTH
MEDICAL CENTER MC
1.00 FINAL DISTRIBUTION BOARDS MC PANEL
MC PANEL
MC PANEL
MC PANEL
1.10 SDB-MC00-D01 : MC PANEL
MC PANEL
Incomer: MC PANEL
MC PANEL
- 100A TPN MCB Isolator. MC PANEL
MC PANEL
Busbar : MC PANEL
MC PANEL
- 150A 4P Cu. Busbar MC PANEL
MC PANEL
Outgoing – (10KA) comprising MC PANEL
MC PANEL
Section-1 MC PANEL
MC PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC PANEL
MC PANEL
- Twelve (12) nos. 10A SP MCB. MC PANEL
MC PANEL
Section-2 MC PANEL
MC PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC PANEL
MC PANEL
- Three (3) nos. 16A SP MCB. MC PANEL
MC PANEL
- Thirteen (13) nos. 16A TPN MCB. MC PANEL
MC PANEL
- Six (6) nos. 32A TPN MCB. MC PANEL
MC PANEL
SDB-MC00-D01 as described above and as per DB chart. 1 Set MC PANEL
MC PANEL
1.20 DB-EE-MC00-B04 : MC PANEL
MC PANEL
Incomer: MC PANEL
MC PANEL
TOTAL OF EARTHING & LIGHTNING PROTECTION SYSTEM CARRIED OVER TO SUMMARY
Design, manufacture, supply, installation (recessed/ surface), testing and commissioning of following switch fuse Unit/ MCCB/MCB type distribution boards as per drawings & specifications fabricated out of 14 SWG, CRCA sheet steel in compartmentalised design as per specification and drawings. The surface distribution boards shall be mounted on 50 x 50 x 6 MS angle frame work grounted to floor/ walls. The rate includes the angle iron frame, support, painting, numbering, earthing etc as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 54
- 100A TPN MCB Isolator. MC PANEL
MC PANEL
Busbar : MC PANEL
MC PANEL
- 150A 4P Cu. Busbar MC PANEL
MC PANEL
Outgoing – (10KA) comprising MC PANEL
MC PANEL
Section-1 MC PANEL
MC PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC PANEL
MC PANEL
- Eighteen (18) nos. 10A SP MCB. MC PANEL
MC PANEL
- Space for installation of three(3) Nos. SP MCB MC PANEL
MC PANEL
Section-2 MC PANEL
MC PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC PANEL
MC PANEL
- Thirteen (13) nos. 16A SP MCB. MC PANEL
MC PANEL
- Two (2) nos. 16A TPN MCB. MC PANEL
MC PANEL
- Space for installation of eight (8) Nos. SP MCB MC PANEL
MC PANEL
DB-EE-MC00-B04 as described above and as per DB chart. 1 Set MC PANEL
MC PANEL
MC PANEL
2.00 CABLES, SUB MAINS & CABLE TRAYS : MC CAB
MC CAB
2.10 Cables in Under Ground Installations : MC CAB
MC CAB
MC CAB
MC CAB
2.1.1 MC CAB
MC CAB
a) 4 core 150 sqmm 10 RM MC CAB
b) 4 core 120 sqmm 10 RM MC CAB
c) 4 core 95 sqmm 10 RM MC CAB
d) 4 core 70 sqmm 10 RM MC CAB
TOTAL OF FINAL DISTRIBUTION BOARDS CARRIED OVER TO SUMMARY
Supply, installation, testing and commissioning of following sizes of PVC sheathed, XLPE insulated copper conductor power/multicore control, armoured, Multi-strand cable of 1.1 KV grade in ground including digging the trench, laying the cable with sand and brick covering, back filling reaming etc as required, as per specfications and as per directions of Engineer-in-charge.
Copper Conductor, Armoured XLPE Cables (PVC/SWA/XLPE) :
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 55
e) 4 core 50 sqmm 10 RM MC CAB
f) 4 core 35 sqmm 10 RM MC CAB
g) 4 core 25 sqmm 10 RM MC CAB
MC CAB
2.20 Cables on Racks / Pipes / Ducts / Wireways/Cable Trays : MC CAB
MC CAB
MC CAB
MC CAB
2.2.1 Copper Conductor Armoured Cables : MC CAB
MC CAB
a) 3.5 core 50 sqmm 10 RM MC CAB
b) 3.5 core 35 sqmm 10 RM MC CAB
c) 4 core 25 sqmm 10 RM MC CAB
d) 4 core 16 sqmm 10 RM MC CAB
e) 4 core 10 sqmm 50 RM MC CAB
f) 4 core 6 sqmm 50 RM MC CAB
g) 4 core 4 sqmm 600 RM MC CAB
h) 3 core 25 sqmm 10 RM MC CAB
i) 3 core 16 sqmm 10 RM MC CAB
j) 3 core 10 sqmm 10 RM MC CAB
k) 3 core 6 sqmm 10 RM MC CAB
l) 3 core 4 sqmm 300 RM MC CAB
m) 2 core 6 sqmm 10 RM MC CAB
n) 2 core 4 sqmm 10 RM MC CAB
MC CAB
2.2.2 Copper Conductor Armoured Control Cables : MC CAB
MC CAB
a) 14 C 1.5 Sqmm PVC cable 10 RM MC CAB
b) 10 C 1.5 Sqmm PVC cable 10 RM MC CAB
c) 9 C 1.5 Sqmm PVC cable 10 RM MC CAB
d) 7 C 1.5 Sqmm PVC cable 10 RM MC CAB
e) 5 C 1.5 Sqmm PVC cable 10 RM MC CAB
f) 3 C 1.5 Sqmm PVC cable 10 RM MC CAB
MC CAB
2.30 Cable Termination : MC TERM
MC TERM
MC TERM
MC TERM
Supply, installation, testing and commissioning of following sizes of PVC sheathed, XLPE insulated, copper conductor, power/multicore, control, armoured, Multi-stranded cable of 1.1 KV grade on surface of wall or in existing cable tray /masonary ducts/hume pipe with fixing hardware etc as required, as per specifications and as per direction of Engineer-in-charge.
Supply and making end termination with brass double compression glands for the following XLPE insulated PVC sheathed, 1100 V grade, Multi-strand copper conductor cable including cost of crimping lugs/ferrules, double compression glands, solder, cable sockets, insulation tap etc complete as required, as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 56
2.3.1 Copper conductor armoured cables : MC TERM
MC TERM
a) 3.5 core 50 sqmm 2 Nos. MC TERM
b) 3.5 core 35 sqmm 2 Nos. MC TERM
c) 4 core 25 sqmm 2 Nos. MC TERM
d) 4 core 16 sqmm 2 Nos. MC TERM
e) 4 core 10 sqmm 4 Nos. MC TERM
f) 4 core 6 sqmm 4 Nos. MC TERM
g) 4 core 4 sqmm 42 Nos. MC TERM
h) 3 core 25 sqmm 2 Nos. MC TERM
i) 3 core 16 sqmm 2 Nos. MC TERM
j) 3 core 10 sqmm 2 Nos. MC TERM
k) 3 core 6 sqmm 2 Nos. MC TERM
l) 3 core 4 sqmm 20 Nos. MC TERM
m) 2 core 6 sqmm 2 Nos. MC TERM
n) 2 core 4 sqmm 2 Nos. MC TERM
MC TERM
2.3.2 Copper Conductor PVC Insulated Armoured Control Cables : MC TERM
MC TERM
MC TERM
a) 14 C x 1.5 Sqmm 2 Nos. MC TERM
b) 10 C x 1.5 Sqmm 2 Nos. MC TERM
c) 9 C x 1.5 Sqmm 2 Nos. MC TERM
d) 7 C x 1.5 Sqmm 2 Nos. MC TERM
e) 5 C x 1.5 Sqmm 2 Nos. MC TERM
f) 3 C x 1.5 Sqmm 2 Nos. MC TERM
MC TERM
Notes: MC TERM
MC TERM
2.40 MC CAB
MC CAB
a) 4 C x 185 Sqm, CWZ Cable 5 RM MC CAB
b) 4 C x 150 Sqm, CWZ Cable 5 RM MC CAB
c) 4 C x 120 Sqm, CWZ Cable 5 RM MC CAB
d) 4 C x 95 Sqm, CWZ Cable 5 RM MC CAB
e) 4 C x 70 Sqm, CWZ Cable 5 RM MC CAB
f) 4 C x 50 Sqm, CWZ Cable 5 RM MC CAB
g) 4 C x 35 Sqm, CWZ Cable 5 RM MC CAB
h) 4 C x 25 Sqm, CWZ Cable 5 RM MC CAB
(Single Compression Glands suitable for following armoured cables)
The cable quantities given are approximate and to cover various sizes. The contractor shall measure the cables required and procurement order shall be placed accordingly. The quantities shall be confirmed before start of work.
Supply, installation, testing and commissioning of 1.1 KV grade, Multicore, copper conductor, LSZH outer sheathed, CWZ fire resistant cable (in compliance with BS : 6387) of following sizes on surfae of wall/existing cable trays/Mesonary Hume pipe/Duct/Trenches etc., with fixing hardware etc. as required as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 57
i) 4 C x 16 Sqm, CWZ Cable 5 RM MC CAB
j) 4 C x 10 Sqm, CWZ Cable 5 RM MC CAB
k) 4 C x 6 Sqm, CWZ Cable 5 RM MC CAB
l) 4 C x 4 Sqm, CWZ Cable 5 RM MC CAB
m) 4 C x 2.5 Sqm, CWZ Cable 5 RM MC CAB
MC CAB
2.50 Cable Trays : MC TRAY
MC TRAY
MC TRAY
MC TRAY
Notes: MC TRAY
MC TRAY
2.5.1 Ladder Type Cable tray : MC TRAY
MC TRAY
a) 900 mm x 75 mm x 2.0 mm 5 RM MC TRAY
b) 750 mm x 75 mm x 2.0 mm 5 RM MC TRAY
c) 600 mm x 75 mm x 2.0 mm 5 RM MC TRAY
d) 450 mm x 75 mm x 2.0 mm 5 RM MC TRAY
e) 300 mm x 75 mm x 2.0 mm 5 RM MC TRAY
f) 250 mm x 75 mm x 2.0 mm 5 RM MC TRAY
g) 200 mm x 75 mm x 2.0 mm 5 RM MC TRAY
g) 150 mm x 75 mm x 2.0 mm 5 RM MC TRAY
g) 100 mm x 75 mm x 2.0 mm 5 RM MC TRAY
MC TRAY
2.52 Perforated Type Cable Tray : MC TRAY
MC TRAY
a) 750 mm x 75 mm x 2.0 mm 10 RM MC TRAY
b) 600 mm x 75 mm x 2.0 mm 10 RM MC TRAY
c) 450 mm x 75 mm x 2.0 mm 10 RM MC TRAY
d) 300 mm x 50 mm x 2.0 mm 10 RM MC TRAY
e) 200 mm x 75 mm x 2.0 mm 100 RM MC TRAY
f) 150 mm x 75 mm x 2.0 mm 10 RM MC TRAY
g) 100 mm x 75 mm x 2.0 mm 10 RM MC TRAY
MC TRAY
2.5.3 Fibreglass Ladder Type Cable Tray : MC TRAY
MC TRAY
Supply and installation of ladder type/perforated type cable trays of the following sizes fabricated out of perforated hot dip galvanised MS sheets of minimum 2.0 mm thick to be installed horizontally or vertically. The cable tray shall be complete including cost of supporting Steel/Hangers, bends, elbows, cross, tees, reducers etc as per drawings/site condition and rate shall include cost of anchor fasteners, screws, nuts, bolts and misc. other fixing hardware etc as required, as per specifications and approved Shop drawings.
The cable tray shall be factory built. Bidder shall include in his price, required numbers of Tees, Crosses, Bends, Elbows etc as required as per actual site conditions. Bidder may refer to the drawings for estimation purpose.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 58
MC TRAY
MC TRAY
a) 600 mm wide 5 RM MC TRAY
b) 450 mm wide 5 RM MC TRAY
c) 300 mm wide 5 RM MC TRAY
d) 225 mm wide 5 RM MC TRAY
e) 100 mm wide 5 RM MC TRAY
MC TRAY
2.60 Misc. Works Relating to Cabling: MC PIPE
MC PIPE
2.6.1 GI Pipe Installation : MC PIPE
MC PIPE
MC PIPE
MC PIPE
a) 25 mm dia 10 RM MC PIPE
b) 32 mm dia 10 RM MC PIPE
c) 40 mm dia 10 RM MC PIPE
d) 50 mm dia 10 RM MC PIPE
e) 80 mm dia 10 RM MC PIPE
f) 100 mm dia 10 RM MC PIPE
g) 150 mm dia 10 RM MC PIPE
MC PIPE
2.6.2 Flexible Conduits Installation : MC PW
MC PW
MC PW
2.6.2.1 GI flexible conduits : MC PW
MC PW
a) 20 mm dia 50 RM MC PW
b) 25 mm dia 50 RM MC PW
c) 40 mm dia 10 RM MC PW
d) 50 mm dia 10 RM MC PW
MC PW
MC PW
3.00 WIRING : MC PW
MC PW
3.10 Point Wiring : MC PW
Supply & Installation of Ladder type Cable tray of following sizes. The Cable Tray shall be complete including the cost of Anchor fasteners, Hardware, supporting structure etc. as required and as per specifications and approved drawing :
Supply and installation of following sizes of `A' class GI pipe for cable sleeves in recess/ on surface/Ground complete with all accessories pull boxes where ever required, G.I. fish wire, fixing hardware etc. including the chasing of wall/floor, and plastering the chased portion, digging the trench and back filling, making good the damages, sealing of pipe entry etc as required.
Supply and installation of following sizes of GI flexible conduits with all accessories including fixing nipples, couplings and fixing hardware etc as required and as per specifications.
TOTAL OF CABLES, SUB MAINS, CABLE TRAYS CARRIED OVER TO SUMMARY
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 59
MC PW
The rates for point wiring shall include the circuit wiring. MC PW
MC PW
MC PW
MC PW
MC PW
MC PW
MC PW
MC PW
MC PW
MC PW
MC PW
MC PW
3.1.1 Light Points controlled by switch : MC PW
MC PW
i. Single/ First light point con-trolled by a 5Amps switch. 24 Nos. MC PW
MC PW
ii. Same as above but loop point 44 Nos. MC PW
MC PW
3.1.2 Light Points controlled directly from DB . MC PW
MC PW
i. Single/ First Point Controlled directly by MCB in DB 1 Nos. MC PW
MC PW
ii. Same as above but loop point. 5 Nos. MC PW
MC PW
3.1.3 Light points controlled by Two Way Switch : MC PW
MC PW
i) 2 Nos. MC PW
MC PW
ii) Same as above but loop point. 9 Nos. MC PW
MC PW
3.1.4 Light Points controlled by Twilight switch : MC PW
MC PW
i. Single/ First light point con-trolled by a Twilight switch. 24 Nos. MC PW
MC PW
ii. Same as above but loop point 44 Nos. MC PW
Circuit wiring means the wiring from DB / Dimmer panel to the first point of circuit through control switch.
Circuit wiring and subsequent looping shall be done with 2.5 Sqmm, 1100V grade LSZH insulated stranded, copper wires.
The rates of point wiring shall include supply, installation, testing & commissioning of MS conduit with accessories, GI Boxes and required GI flexible conduits with accessories up to the Point, LSZH insulated, stranded, Cu. Wire etc. as required and as per specification, Tender Drawing and direction of Engineer-in-charge.
Where the light points are directly controlled from DB (without any local control switches), the quoted rates shall not include the cost of MCBs etc. in the point wiring.
The rates of point wiring shall include earthing of each light, fan, switches, switch plates, boxes and other non current carrying metallic part with 2.5 Sqm. Stranded copper, LSZH insulated, stranded, copper wire.
One / first light point controlled by two nos. two way 5 Amps. switch.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 60
MC PW
3.1.5 Light points controlled by Push Buttons : MC PW
MC PW
i) Five light points controlled by Two Push Buttons. 1 Nos. MC PW
MC PW
ii) Eleven light points controlled by Two Push Buttons. 1 Nos. MC PW
MC PW
iii) Ten light points controlled by Four Push Buttons. 1 Nos. MC PW
MC PW
iv) Twelve light points controlled by Four Push Buttons. 1 Nos. MC PW
MC PW
v) Ten light points controlled by Six Push Buttons. 1 Nos. MC PW
MC PW
3.1.6 Presence Sensor : MC PW
MC PW
a) 1 Nos. MC PW
MC PW
3.1.7 6A Socket Points : MC PW
MC PW
a) 12 Point MC PW
MC PW
3.1.8 FCU Points controlled by 6A Switch : MC PW
MC PW
i) 2 Nos. MC PW
MC PW
ii) Same as above but loop point. 9 Nos. MC PW
MC PW
3.20 Power Socket Wiring : MC PW
MC PW
MC PW
MC PW
Wiring from Presence Sensor to the DB/SwitchBoard/Light fixtures, including providing Presence Sensor as required and as per approved shop drawing (wiring from DB to light points has already been included in subheads 3.1.1, 3.1.2, 3.1.3, 3.1.4, 3.1.5 above and not to be considered here).
Wiring for 6A, BS, switched socket outlet including providing 6A, BS, switched, socket outlet as per specification and approved shop drawing.
One / first light point controlled by 6A, BS, switched socket outlet including providing 6A, BS, switched, socket outlet.
Power Socket Wiring shall include supply, installation, testing and commissioning of wiring of following points, including, providing conduits of suitable size, its accessories/Hardware, Junction Boxes, LSZH wires, termination of wires, switches, socket outlets, Plug tops etc. as required and as per specification.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 61
3.2.1 4 Point MC PW
MC PW
3.2.2 1 Point MC PW
MC PW
3.2.3 7 Point MC PW
MC PW
3.2.4 10 Point MC PW
MC PW
3.2.5 1 Point MC PW
MC PW
Wiring for 1 No. BS, 16A, switched socket outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 3 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 3 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 4 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 4 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. BS, 16A, switched outlet in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 62
3.2.6 1 Point MC PW
MC PW
3.2.7 1 Point MC PW
MC PW
3.2.8 1 Point MC PW
MC PW
3.30 CEE INDUSTRIAL SWITCHED SOCKETS MC PW
MC PW
3.3.1 MC PW
MC PW
a) 16A, 2P+E, CEE, switched socket outlet with plug top (IP-44) 1 Nos. MC PW
MC PW
b) 8 Nos. MC PW
MC PW
c) 4 No. MC PW
MC PW
d) 3 No. MC PW
Wiring for 3 Nos. BS, 16A, switched outlets and 1 No. 16A DP Isolator in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 3 Nos. BS, 16A, switched outlets and 1 No. 16A DP Isolator in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. 16A DP Isolators in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. 16A DP Isolator in IP-65 enclosure with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. Disabled Alarm Device with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. Disabled Alarm Device, Single phase motor of required capacity (As approved by the Engineer-in-charge) with internal wiring in G.I. box, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Supply, installation, testing and commissioning of single phase/three phase, CEE, switched, industrial type plug and socket outlet in IP-44 enclosure including termination, earthing etc. in surface/recessed mounting as required, as per specifications and approved shop drawings (Cabling/Conduiting & wiring shall be paid separately under different items).
32A, 2P+E, CEE, switched socket outlet with plug top (IP-44) (for single phase motors)
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-44)
32A, 3P+N+E, CEE, switched socket outlet with plug top (IP-44).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 63
MC PW
e) 1 No. MC PW
MC PW
b) 2 Nos. MC PW
MC PW
3.40 ISOLATORS MC DB
MC DB
MC DB
MC DB
a) 16A Double pole isolator 10 Nos. MC DB
MC DB
b) 16A Four pole isolator 2 Nos. MC DB
MC DB
c) 32A Four pole isolator 1 Nos. MC DB
MC DB
3.50 M.S. Black Conduits : MC PW
MC PW
MC PW
MC PW
a) 20 mm dia 20 RM MC PW
MC PW
b) 25 mm dia 20 RM MC PW
MC PW
c) 32 mm dia 20 RM MC PW
MC PW
d) 40 mm dia 20 RM MC PW
MC PW
e) 50 mm dia 20 RM MC PW
MC PW
3.60 Sub-mains Wiring : MC PW
MC PW
MC PW
MC PW
a) 2 x 1.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC PW
MC PW
b) 2 x 2.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC PW
MC PW
c) 2 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire. 20 RM MC PW
MC PW
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-65) for water heaters.
32A, 3P+N+E, CEE, switched socket outlet with plug top (IP-44) (for three phase motors)
Supply, installation, testing and commissioning of isolators in IP-65 enclosures complete with termination in surface/recessed mounting as required.
Supply and installation of following size of MS conduit pipe in recess or on surface including all accessories MS/CI pull/junction boxes, GI fish wire, fixing hardware etc including chasing the walls/floor and plastering the chased portion and making good the damages etc, complete as required and as per specifications.
Supply and drawing of following sizes of LSZH insulated, stranded, copper conductor wires of 650/1100 Volts grade in existing conduit pipe /wire ways including connection /terminations etc as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 64
d) 2 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC PW
MC PW
e) 4 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC PW
MC PW
f) 4 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC PW
MC PW
g) 2 x 10.0 Sqmm + 1 No. 6.0 Sqmm Copper earth wire 20 RM MC PW
MC PW
h) 4 x 10.0 Sqmm + 2 Nos. 6.0 Sqmm Copper earth wire 20 RM MC PW
MC PW
i) 4 x 16.0 Sqmm + 2 Nos. 10.0 Sqmm Copper earth wire 20 RM MC PW
MC PW
j) 4 x 25.0 Sqmm + 2 Nos. 16.0 Sqmm Copper earth wire 20 RM MC PW
MC PW
Note: MC PW
MC PW
1) MC PW
MC PW
2) MC PW
MC PW
TOTAL OF WIRING CARRIED OVER TO SUMMARY MC PW
4.00 LIGHTING FIXTURES : MC LIGHT
MC LIGHT
MC LIGHT
MC LIGHT
1.00 2 Set MC LIGHT
MC LIGHT
2.00 2 Set MC LIGHT
MC LIGHT
3.00 10 Set MC LIGHT
MC LIGHT
In false ceiling areas the work is to be co-ordinated with respect to interior work and rate for point wiring shall include flexible conduit/fixing nipples/couplers etc from the junction box up to the fitting.
All wires used for circuit / point wiring shall be Low Smoke Zero Halogen (LSZH) wires.
Inspection, receiving, storing, handling, assembling, installation, testing and commissioning of wall /ceiling, surface/ recessed, suspended from down rod, in furniture, fluorescent / incandescent / Halogen lamp fixtures including making connections with PVC insulated stranded copper conductor wires complete including steel supports, suspenders, fixing screws, turn buckles, bolts, nuts (down rods ball and socket arrangement and special channel mounting for industrial fitting/chandelier) etc, as required. The mounting arrangement of lighting fixture shall be as indicated in the approved drawings.
Recessed Grid Luminaire 2x36W (Thorn Specalph BS/SB 2x36W or Equivalent) (T2).
Recessed Grid Luminaire 2x36W (Thorn Specalph BS/SB 2x36W or Equivalent) (T2) complete with emergency lighting units.
Recessed Grid Luminaire 2x58W (Thorn Specalph BS/SB 2x58W or Equivalent) (T4).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 65
4.00 6 Set MC LIGHT
MC LIGHT
5.00 24 Set MC LIGHT
MC LIGHT
6.00 5 Set MC LIGHT
MC LIGHT
7.00 11 Set MC LIGHT
MC LIGHT
8.00 3 Set MC LIGHT
MC LIGHT
9.00 9 Set MC LIGHT
MC LIGHT
10.00 1 Set MC LIGHT
MC LIGHT
11.00 1 Set MC LIGHT
MC LIGHT
12.00 8 Set MC LIGHT
MC LIGHT
13.00 14 Set MC LIGHT
MC LIGHT
14.00 7 Set MC LIGHT
MC LIGHT
15.00 20 Set MC LIGHT
MC LIGHT
16.00 4 Set MC LIGHT
MC LIGHT
17.00 5 Set MC LIGHT
MC LIGHT
18.00 10 Set MC LIGHT
MC LIGHT
Recessed Grid Luminaire 2x58W (Thorn Specalph BS/SB 2x58W or Equivalent) (T4) complete with emergency lighting units.
Surface mounted Industrial Luminaire with 1x36W Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or Equivalent) (T5).
Surface mounted Industrial Luminaire with 1x36W Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or Equivalent) (T5) complete with emergency lighting units.
Surface mounted Industrial Luminaire with 2x36W Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or Equivalent) (T6).
Surface mounted Industrial Luminaire with 2x36W Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or Equivalent) (T6) complete with emergency lighting units.
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp waterproof IP44 (Siteco Europlex 24W IP44 or Equivalent) (T8).
Surfaced Luminaire 2x58W IP65 (Thorn AQUAF2 2x58W IP65 or Equivalent) (T9)
Surfaced Luminaire 2x58W IP65 (Thorn AQUAF2 2x58W IP65 or Equivalent) (T9) complete with emergency lighting units.
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp IP 65 (Thorn Danube 2x28W IP65 or Equivalent) (T11).
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W or Equivalent) (T13)
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W or Equivalent) (T13) complete with emergency lighting units.
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or Equivalent) (T15)
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or Equivalent) (T15) complete with emergency lighting units.
Recessed outside Downlight IP54 (Trilux Downlight IP54 or Equivalent) (T21)
Emergency Exit Up Fixture (Cooper/Crompton or Equivalent) complete with emergency lighting units.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 66
19.00 4 Set MC LIGHT
MC LIGHT
20.00 3 Set MC LIGHT
MC LIGHT
MC LIGHT
5.00 EARTHING & LIGHTNING PROTECTION SYSTEM : MC EARTH
MC EARTH
5.10 Earthing System: MC EARTH
MC EARTH
5.1.1 5 Nos. MC EARTH
MC EARTH
5.1.2 5 Nos. MC EARTH
MC EARTH
5.1.3 1 Nos. MC EARTH
MC EARTH
5.1.4 Earthing Strip/Tape/Cables : MC EARTH
MC EARTH
MC EARTH
MC EARTH
Emergency Exit Down Fixture (Cooper/Crompton or Equivalent) complete with emergency lighting units.
Emergency Exit Left & Right Fixture (Cooper/Crompton or Equivalent) complete with emergency lighting units.
TOTAL OF LIGHTING FIXTURES CARRIED OVER TO SUMMARY
Supply, installation, testing and commissioning of copper plate earthing stations making earth pits, earthing with copper earth plate 600 mm x 600 mm x 3.15 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS –3043 complete as required, as per specifications, drawings and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI plate earthing stations making earth pits, earthing with GI earth plate 600 mm x 600 mm x 6.30 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required, as per specifications, drawing and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI Pipe earthing stations making earth pits, earthing with GI pipe 4500 mm x 40 mm Dia including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required as per specifications, drawing and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of following sizes of GI/Tinned Copper strip/tape clamped to walls, cable trays, bus ducts, recess in Ground or surface etc for equipment/ System earthing complete as required including inter connection between length at joints, all fixing accessories saddles, clamps etc and other fixing hardware material as required, as per specifications, detail drawings shall be included for proper installation.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 67
5.1.4.1 G.I. Earthing strip/tape : MC EARTH
MC EARTH
a 75 x 8 mm strip 10 RM MC EARTH
b 75 x 6 mm strip 10 RM MC EARTH
c 50 x 6 mm strip 10 RM MC EARTH
d 40 x 6 mm strip 10 RM MC EARTH
e 32 x 6 mm strip 10 RM MC EARTH
f 25 x 6 mm strip 10 RM MC EARTH
g 25 x 3 mm strip 250 RM MC EARTH
MC EARTH
5.1.4.2 Tinned Copper earthing strip/tape : MC EARTH
MC EARTH
a) 50 x 6 mm 10 RM MC EARTH
b) 32 x 6 mm 10 RM MC EARTH
c) 25 x 6 mm 10 RM MC EARTH
d) 25 x 3 mm 10 RM MC EARTH
MC EARTH
5.1.5 MC CAB
MC CAB
a) 1C x 240 Sqm 100 RM MC CAB
MC CAB
b) 1C x 185 Sqm 100 RM MC CAB
MC CAB
c) 1C x 90 Sqm 10 RM MC CAB
MC CAB
d) 1C x 50 Sqm 10 RM MC CAB
MC CAB
5.1.6 MC EARTH
MC EARTH
5.1.6.1 75 x 6 mm GI Earth Bars. MC EARTH
MC EARTH
a) 300 mm 1 No. MC EARTH
b) 500 mm 1 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 No. MC EARTH
MC EARTH
5.1.6.2 50 x 6 mm GI Earth Bars. MC EARTH
MC EARTH
Supply, installation, Termination, testing and commissioning of PVC insulated, stranded copper conductor cable, laid on surface/cable tray/duct/undger ground/Trench etc. as required, as per approved shop drawing, site conditions and as directed by Engineer-in-charge.
Supply, installation, Termination, testing and Commissioning of following sizes tinned Cu/GI Earth Bars including its supporting/fixing hardware, as per drawings, specifications and as directed by Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 68
a) 300 mm 1 Nos. MC EARTH
b) 500 mm 1 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 Nos. MC EARTH
MC EARTH
5.1.6.3 75 x 6 mm tinnned Cu Earth Bars. MC EARTH
MC EARTH
a) 300 mm 1 No. MC EARTH
b) 500 mm 2 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 No. MC EARTH
MC EARTH
5.1.6.4 50 x 6 mm tinned Cu Earth Bars. MC EARTH
MC EARTH
a) 300 mm 1 Nos. MC EARTH
b) 500 mm 1 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 Nos. MC EARTH
5.20 Lightning Protection System: MC EARTH
MC EARTH
5.2.1 1 Nos. MC EARTH
MC EARTH
5.2.2 6 Nos. MC EARTH
MC EARTH
5.2.3 Earthing Strip/Wires : MC EARTH
MC EARTH
Supply, installation, testing and commissioning of copper plate earthing stations making earth pits, earthing with copper earth plate 600 mm x 600 mm x 3.15 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required, as per drawings, specifications and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI Pipe earthing stations making earth pits, earthing with GI pipe 4500 mm x 40 mm Dia including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required, as per drawings, specifications and direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 69
MC EARTH
MC EARTH
a) 25 x 3 mm strip 250 RM MC EARTH
MC EARTH
b) 25 x 6 mm strip 100 RM MC EARTH
MC EARTH
5.2.4 MC EARTH
MC EARTH
5.2.4.1 75 x 6 mm GI Earth Bars. MC EARTH
MC EARTH
a) 300 mm 1 Nos. MC EARTH
b) 500 mm 1 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 Nos. MC EARTH
MC EARTH
5.2.4.2 50 x 6 mm GI Earth Bars. MC EARTH
MC EARTH
a) 300 mm 1 Nos. MC EARTH
b) 500 mm 1 Nos. MC EARTH
c) 750 mm 1 Nos. MC EARTH
d) 1000 mm 1 Nos. MC EARTH
10.2.5 15 Nos. MC EARTH
MC EARTH
10.2.6 6 Nos. MC EARTH
MC EARTH
MC EARTH
PIT BUILDING PB HTO
Supply, installation, testing and commissioning of following sizes of GI strip/wire clamped to walls, Ductwork, pipe work, Structural steel work, cladding work etc. in recess or surface etc for Lightning Protection System complete as required including inter connection, terminations, between length at joints, all fixing accessories saddles, plastic isolator mounting (of 50mmx80mm approx.), Sealing Collars, Sealing Strip, Squared Timber Block (80mmx100mm approx.), clamps, Lugs etc and other fixing hardware material as required for proper installation as per detail drawings, specifications and direction of Engineer-in-charge.
Supply, installation, Termination, testing and Commissioning of following sizes GI Earth Bars including in supporting/fixing hardware, as per drawings, specifications and as directed by Engineer-in-charge.
Supply and fixing of Lightning Arrestor Rod/Lightning Conductor finial made of 25 mm dia, 2.0 mm thick & 300 mm Long GI Tube having single prong at top with 75 mm dia, 6 mm thick Base plate, including connections with roof parapit Lightning protection Conductors, as per detailed drawings and as per direction of Engineer-in-charge.
Supply and fixing of "Earth Test Joints" encased in 200 mm (H) x 150 mm (W) x 100 mm (D) recessed in concrete with removable cover plate as per detailed drawing and as per direction of Engineer-in-charge.
TOTAL OF EARTHING & LIGHTNING PROTECTION SYSTEM CARRIED OVER TO SUMMARY
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 70
PB HTO
1.00 11 KV, GAS INSULATED, RING MAIN UNITS: PB HTO
PB HTO
1.10 PB HTO
PB HTO
a) PB HTO
PB HTO
b) 2 Set PB HTO
PB HTO
Notes : PB HTO
PB HTO
i) PB HTO
PB HTO
ii) PB HTO
PB HTO
1.30 Battery & Battery Charger : PB BATT
PB BATT
a) PB BATT
PB BATT
i) for 24V DC System ur Set PB BATT
PB BATT
ii) for 110V DC System 2 Set PB BATT
PB BATT
b) PB BATT
PB BATT
i) for 24V DC System ur Set PB BATT
PB BATT
ii) for 110V DC System 2 Set PB BATT
PB BATT
Unloading,Receiving, storing, checking, handling, installation, testing and commissioning of 350 MVA, 11 KV indoor 4 way, SF6 insulated, Extensible Ring Main Breaker Unit consisting of following :-
Two (2) Nos. 630 Amp, TP VCB with disconnector and Earth Switch as Incommers, with required Indication, Metering and Protection System.
Two (2) Nos. 630 Amp, TP VCB with disconnector and Earth Switch as Outgoings, with required Indication, Metering & Protection System.
Installation shall include supply of all Hardware material (excluding civil work) as required and as per Approved Shop Drawings.
Necessary Co-ordination with client and manufacturer to be done by the contractor for successful installation, Testing and Commissioning.
Supply, installation, testing & commissioning of 200 AH capacity, Ni-Cd maintenance free batteries, duly charged, complete with seasoned teak wood stand, connecting lead as required for 11 KV RMU boards and some other control loads. (AH calculation to be submitted by successful bidder in co-ordination with the client and 11 KV, RMU Vendor).
Supply, installation, testing & commissioning of suitable float cum boost battery charger and necessary distribution board with 12 Nos. 16A outgoing feeders, instrument panel, Amp, Volts meter, interconnections etc. power supply 240 V, 1 phase, 50 Hz ± 10%. Charger trouble annunciation shall be provided through potential free contacts.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 71
PB BATT
2.00 H T CABLING : PB CAB
PB CAB
2.10 11kV Cable laying : PB CAB
PB CAB
PB CAB
PB CAB
2.1.1 Underground: PB CAB
PB CAB
PB CAB
PB CAB
a) 3C x 400 Sqmm, 11KV XLPE 10 Mtr PB CAB
PB CAB
b) 3C x 300 Sqmm, 11KV XLPE 10 Mtr PB CAB
PB CAB
c) 3C x 240 Sqmm, 11KV XLPE 10 Mtr PB CAB
PB CAB
2.1.2 In hume pipe/trays/trenches : PB CAB
PB CAB
PB CAB
PB CAB
a) 3C x 400 Sqmm, 11KV XLPE 20 Mtr. PB CAB
PB CAB
b) 3C x 300 Sqmm, 11KV XLPE 20 Mtr PB CAB
PB CAB
c) 3C x 240 Sqmm, 11KV XLPE 100 Mtr PB CAB
PB CAB
2.20 End Termination (HT) : PB TERM
PB TERM
PB TERM
PB TERM
a) 3C x 400 Sqmm, 11KV XLPE 1 Set PB TERM
PB TERM
b) 3C x 300 Sqmm, 11KV XLPE 1 Set PB TERM
PB TERM
TOTAL OF 11 KV, GAS INSULATED, RING MAIN UNITS CARRIED OVER TO SUMMARY
Supplying, laying, testing and commissioning of 11 KV grade copper conductor, cross linked polyethylene (XLPE) insulated, individual core screened, extruded inner sheath, flat steel/strip armoured PVC sheathed cable and suitable for (E) system complete as required and as per specification, as follows:
Supply and laying of following size of 11 KV cables in earth as per drawing, specifications and direction of engineer in charge.
Supply and laying of following sizes of 11 KV cables on already laid trays/hume pipes/walls/ trench etc, as required, as per drawing, specifications and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of Cable joints of 11 KV grade, XLPE insulated, armoured, Copper Conductor cable with suitable cable termination KITS including all accessories i.e. Sockets, lugs, gland etc as required, as per drawings, specifications and direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 72
c) 3C x 240 Sqmm, 11KV XLPE 8 Set PB TERM
PB TERM
2.30 End Termination (HT) : PB TERM
PB TERM
PB TERM
PB TERM
a) 3C x 400 Sqmm, 11KV XLPE 4 Set PB TERM
PB TERM
b) 3C x 300 Sqmm, 11KV XLPE 1 Set PB TERM
PB TERM
c) 3C x 240 Sqmm, 11KV XLPE 1 Set PB TERM
PB TERM
Notes : PB TERM
PB TERM
1.00 PB TERM
PB TERM
2.00 PB TERM
PB TERM
TOTAL OF H.T CABLING CARRIED OVER TO SUMMARY PB TERM
3.00 SUB STATION SAFETY EQUIPMENT : PB MISC
PB MISC
3.10 PB MISC
PB MISC
a) 11 KV grade size 1000 x 900 mm of suitable thickness 12 Nos. PB MISC
PB MISC
b) 1100 V grade size 1000 x 900 mm of suitable thickness 40 Nos. PB MISC
PB MISC
3.20 3 Nos. PB MISC
PB MISC
3.30 4 Nos. PB MISC
PB MISC
3.40 Providing 11 KV tested hand gloves. 2 Pair PB MISC
PB MISC
3.50 Providing 11 KV insulated grounding rod. 2 Nos. PB MISC
Cable jointing of 11 KV grade, XLPE insulated, armoured, Aluminium Conductor cable with suitable cable termination KITS including all accessories i.e. Sockets, lugs, gland etc as required, as per drawings, specifications and direction of Engineer-in-charge.
The cable and cable terminations quantities given above, are approximate. The contractor shall measure the cables required at site and procurement order shall be place accrodingly.
Wherever copper cable to be connected to Aluminium Bus Bar or vis-à-vis., Bimetalic lugs to be used for terminations.
Supplying and fixing 1000 mm x 900 mm wide checkered rubber matting conforming to IS 15652-2006 complete as required.
Supplying & fixing standard shock treatment charts in English & Hindi / (Local Language) duly framed and covered with glass.
Providing & fixing HT danger notice plate 200 mm x 150 mm made of mild steel atleast 2mm thick & vitreous enameled white on both sides and with inscription in signal red colour with skull & bone on front side as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 73
PB MISC
3.60 Providing first aid box as per IS:13115. 2 Set PB MISC
PB MISC
PB MISC
4.00 TRANSFORMER: PB TRAFO
PB TRAFO
PB TRAFO
PB TRAFO
a) 1600 KVA 4 Set PB TRAFO
PB TRAFO
PB TRAFO
Notes : PB TRAFO
PB TRAFO
i) PB TRAFO
PB TRAFO
ii) PB TRAFO
PB TRAFO
PB TRAFO
PB BBT
5.0 BUS DUCT/BUS BAR TRUNKING SYSTEM : PB BBT
PB BBT
5.1 Bus Duct : PB BBT
PB BBT
PB BBT
PB BBT
TOTAL OF SUB STATION SAFETY EQUIPMENT CARRIED OVER TO SUMMARY
Unloading,Receiving, storing, handling, installation, testing and commissioning of 11 kV/ 400V (terminal voltage), 3 phase, 50 Hz delta/star connected, copper winding. indoor type, natural air cooled, dry type, cast resin transformer of following ratings, complete with all fittings such as thermometer, off circuit tap changer with + 5 % to –15%, tapping at the step of 2.5% bi-directional roller, diagrams & rating plate & Winding temperature indicator, lifting lugs, H. T. cable box/ LT Terminal Box suitable for bus duct / Cable termination etc. complete as per relevant specifications, drawings and direction of Engineer-in-charge.
Installation rate shall include unloading, receiving including storage at site,assembly, erection, testing and commissioning etc. as required, as per approved Shop Drawing and as per direction of Engineer-in-charge..
Necessary co-ordination with the manufacturer and client shall be done by the contractor without extra cost.
TOTAL OF TRANSFORMER CARRIED OVER TO SUMMARY
Design, manufacturing, supply, installation, testing & commissioning (at site) of sheet steel enclosed 3 phase & neutral (100% neutral), 400V, 50 Hz., 65 KA copper conductor bus duct with insulation of thermal rating confirming to class 'F', including bends, transposition piece, expansion joint, Tees, End termination units, Feeder units, tap off unit etc. with all flexible connections as per specifications and drawings with all accessories, supports and termination of bus duct to switchgear/transformer.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 74
a)
80 RM
PB BBT
PB BBT
b)
120 RM
PB BBT
PB BBT
5.2 Bus Bar Trunking (BBT) : PB BBT
PB BBT
5.2.1
PB BBT
PB BBT
PB BBT
PB BBT
i)40 RM
PB BBT
PB BBT
ii)180 RM
PB BBT
PB BBT
iii)565 RM
PB BBT
PB BBT
iv)ur RM
PB BBT
PB BBT
v)15 RM
PB BBT
PB BBT
vi)ur RM
PB BBT
PB BBT
vii)ur RM
PB BBT
PB BBT
Notes: PB BBT
PB BBT
a)PB BBT
PB BBT
2500A, 65kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 4 Nos. of Terminations and all other accessories as required as per specifications, and approved Shop Drawings.
2500A, 65kA @ 1 Sec., TP+N, Bus Duct (IP.68) with 4 Nos. of Terminations and all other accessories as required as per specifications, and approved Shop Drawings.
Design, manufacture, assembly, supply, installation, testing and commissioning (at site) of following capacity compact, Copper Conductor, Bus Bar Trunking System including Bends, Tees, Expansion Joints, Feeder Units, Tap off Units, Transposition pieces, Flexible Connections etc. with all other Hardware/accessories required for installation of Bus Bar Trunking as per Specifications, approved Shop Drawings and instruction of Engineer-in-charge.
Shutter type spring loaded arrangements shall be provided for tap off system. The shutter shall get closed when tap off box is taken out. Tap off facilities shall be there at every 500 mm interval as per standard.
1600A, TPN+E, 400 Volt, 65 KA, compact, copper conductor BBT.
1250 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor BBT.
1000 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor BBT.
800 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor BBT.
630 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor BBT.
400 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor BBT.
250 A, TPN+E, 400 Volt, 65 KA, compact, copper Conductor BBT.
The quantity mentioned above is approximate. Bidder to procure /manufacture the items as per actual site measurement & approved Shop drawings.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 75
b) Rates shall be inclusive of all accessories & fittings. PB BBT
PB BBT
5.2.2
PB BBT
PB BBT
i) 630A, TPN MCCB, 65 kA Tap off box. 1 No. PB BBT
PB BBT
ii) 400A TPN MCCB, 65 kA Tap off box. 2 Nos. PB BBT
PB BBT
iii) 315A TPN MCCB, 65 kA Tap off box. 4 Nos. PB BBT
PB BBT
iv) 250A TPN MCCB, 65 kA Tap off box. 1 Nos. PB BBT
PB BBT
v) 160A TPN MCCB, 65 kA Tap off box. 40 Nos. PB BBT
PB BBT
vi) 100A TPN MCCB, 65 kA Tap off box. 2 Nos. PB BBT
PB BBT
vii) 63A TPN MCCB, 65 kA Tap off box. 2 Nos. PB BBT
PB BBT
vi) 50A TPN MCCB, 65 kA Tap off box. 2 Nos. PB BBT
PB BBT
5.2.3
PB BBT
PB BBT
a) 1600 Amp with 1600 Amp, TPN, 65 kA, MDO ACB. 1 Nos. PB BBT
PB BBT
b) 1250 Amp with 1250 Amp, TPN, 65 kA, MDO ACB. 1 Nos. PB BBT
PB BBT
c) 1000 Amp with 1000 Amp, TPN, 65 kA, MDO ACB. 3 Nos. PB BBT
PB BBT
d) 800 Amp with 800 Amp, TPN, 65 kA, MDO ACB. ur Nos. PB BBT
PB BBT
e) 630 Amp with 630 Amp, TPN, 65 kA, MCCB. 1 Nos. PB BBT
PB BBT
f) 400 Amp with 400 Amp, TPN, 65 kA, MCCB. ur Nos. PB BBT
PB BBT
g) 250 Amp with 250 Amp, TPN, 65 kA, MCCB. ur No. PB BBT
PB BBT
PB BBT
Design, manufacture, assembly, supply, installation, testing and commissioning of plug-in type TPN tap off box of following capacity on the existing Bus Bar Trunking and complete with TPN MCCBs, links, interconnections, earthing etc. as required, as per specifications and as per approved Shop drawings.
Design, Manufacture, Supply, installation, testing and commissioning of End Feed Box/Bus Bar Trunking Adapter Box, of following ratings with Digital Voltmeter & Ammeter (ELF 3259 of Conzerv or Equivalent) complete with 5VA, class 1.0 CTs of required ratio and one set of phase indication lamps and back-up SPMCBs, as per approved drawing and specifications.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 76
5.2.4 PB PANEL
PB PANEL
- PB PANEL
- PB PANEL
PB PANEL
- PB PANEL
PB PANEL
a) ur Nos. PB PANEL
PB PANEL
b) ur Nos. PB PANEL
PB PANEL
c) ur Nos. PB PANEL
PB PANEL
Notes: PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
PB PANEL
6.00 LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS: PB PANEL
PB PANEL
LV SWITCHGEAR PANELS : PB PANEL
PB PANEL
Design, Manufacturing, Supply, installation, testing and commissioning of Bus Coupler panels with ACB/MCCB of following ratings for Bus Duct/Bus Bar Trunking System.
The Bus Coupler panel shall consist of 400V, 65 KA@ 1 Sec, 4 pole, Draw out type, Electrically operated, ACB/MCCB complete with under voltage and shunt trip release, antipumping protection, ON/OFF indication lamps etc. as required, as per specifications and approved Shop drawings.
Bus Couper Panel shall be suitable for Termination of Compact Bus Bar Trunking from Top/Bottom as per approved shop drawing.
Bus Coupler Breaker shall have suitable No. of NO/NC contacts for required interlocking with the Breakers of End feed units of Bus Bar Trunking.
Bus Coupler Panel with 1600 Amp, 400V, 65 kA @ 1 Sec, 4 Pole, EDO ACB
Bus Coupler Panel with 1250 Amp, 400V, 65 kA @ 1 Sec, 4 Pole, EDO ACB
Bus Coupler Panel with 1000 Amp, 400V, 65 kA @ 1 Sec, 4 Pole, MCCB
The fabrication of bus duct/Bus Bar Trunking shall be taken up only after actual measurement and site routing. Necessary bends/transposition pieces/ expansion joints etc. shall be estimated & included. Payment will be made on running meter basis.
The supply and fabrication & installation of structural steel for bus duct/Bus Bar Trunking support is included in the above items.
TOTAL OF BUS DUCT/BUS BAR TRUNKING SYSTEM CARRIED OVER TO SUMMARY
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 77
PB PANEL
PB PANEL
Important Notes: Common for all Switchboard: PB PANEL
PB PANEL
1.00 PB PANEL
PB PANEL
2.00 Fault current wherever mentioned shall be Ics value. PB PANEL
PB PANEL
3.00 PB PANEL
PB PANEL
4.00 All feeder doors shall have pad locking arrangement. PB PANEL
PB PANEL
5.00 All TP feeders shall have solid isolable neutral link. PB PANEL
PB PANEL
6.00 PB PANEL
PB PANEL
7.00 All power contactors including NIC shall be of AC3 duty. PB PANEL
PB PANEL
8.00 PB PANEL
PB PANEL
9.00 PB PANEL
Design, manufacture, supply, unloading, receiving, storing, handling, installation, testing and commissioning of following LV panels suitable for 400 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, Copper bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of as indicated elsewhere or shown in Single Line Diagram.
The BOQ shall be read inconjunction with general notes, specification and Single Line Diagram. Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Employer before quoting the rates, otherwise stringent condition shall be deemed to have been considered.
All MCCB shall be provided with door interlocked rotary handle with ON/OFF/Trip position indicator, microprocessor based releases for over current, selectable short circuit and instentaneous short circuit protection (settable at site). I/C MCCB shall be provided with E/F release/ protection also.
All MCCB used in starter feeder shall be suitable for motor duty application.
All ACB's shall be with micro processor based O/C and S/C releases and Breaker Control Switch (BCS) having lost motion device. I/C ACBs shall be provided with E/F release also. Bus coupler shall be provided without releases.
Spare contacts of ACB/Relays/Contactor etc. shall be wired upto terminal block.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 78
PB PANEL
10.00 PB PANEL
11.00 Capacitor shall be super heavy duty type (MPP technology). PB PANEL
PB PANEL
12.00 PB PANEL
PB PANEL
13.00 PB PANEL
PB PANEL
14.00 PB PANEL
PB PANEL
15.00 All CT, PT shall be cast resin. PB PANEL
PB PANEL
16.00 All meters are digital type. PB PANEL
PB PANEL
17.00 PB PANEL
PB PANEL
18.00 PB PANEL
PB PANEL
19.00 PB PANEL
PB PANEL
20.00 Bus bar chamber shall be kept at top of the all panels. PB PANEL
PB PANEL
21.00 PB PANEL
PB PANEL
22.00 PB PANEL
PB PANEL
23.00 All indicating light shall be LED type . PB PANEL
PB PANEL
24.00 PB PANEL
PB PANEL
25.00 PB PANEL
PB PANEL
26.00 PB PANEL
All switchgear used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to submit manufacturers type-2 co-ordination chart for the make used.
All outgoing terminals (power and control) shall be brought upto cable alley. 10% extra terminals shall be provided.
10% extra indicating lamp in loose shall be supplied along with panel.
Removable lifting hook shall be provided in all transportation section.
Panel shall be powder coated of approved shade with minimum 60 micron thickness.
ACB's/MCCB's in one particular panel shall be of one similar make.
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal shall be used in the panel.
All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB,BK as per colour code.
Internal wiring of panel shall be with size 2.5sqmm Flexible Copper Conductor for CT circuit and control wiring with 1.5 sqmm.
Each vertical section of floor mounted panel shall have independent base frame (75mm x 40mm) size made out of 3 mm sheet steel (LT Panel & DG Panel).
All the makes shall be as per Employer's approved make list only.
Wherever only voltmeter & ammeter are required, the same may be provided in combined meter suitable for both parameter.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 79
PB PANEL
6.10 MDB-EE-PB00-C3 : PB PANEL
Location: Ground Floor Electrical Room : PB PANEL
PB PANEL
MDB-EE-PB00-C3 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) PB PANEL
PB PANEL
Each incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
iii) PB PANEL
PB PANEL
iv) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
v) PB PANEL
PB PANEL
1.00 WTI Alarm PB PANEL
2.00 WTI Trip PB PANEL
3.00 REF Trip PB PANEL
4.00 HT Breaker Trip PB PANEL
PB PANEL
c) PB PANEL
PB PANEL
Two (2) Nos. 2500 Amps, 400 V, 65kA, TPN draw out, Electrically operated ACB, with ON/OFF/TRIP/Trip circuit healthy indication lamp and TNC control switch, under voltage & shunt trip release, anti pumping protection microprocessor based O/C, S/C & E/F protection etc. complete as required for Transformer Supply Feeder.
One (1) no. 1600 Amps, 400 V, 50KA, four pole EDO ACB Bus coupler breaker complete with under voltage and shunt trip release, anti pumping protection, ON/OFF/ indication etc. to be Electrically and mechanically interlocked with the incommers so that necessary interlocking can be achieved as per approved SLD, (E/MP/PB 5.S.02.01A,02A,03A,04A,05A,06A).
Metering & indication for Transformer Supply incoming breakers:
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents, Power Factor, Frequency,Power , Energy, harmonics and hours run (EM6400 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 2500/5A,15VA, Class 1.0 as required.
One (1) set of 2500/5 A, C.L 1.0 CTs for input to APFC relay.
One (1) No. 4 Window Audi/visual annunciator system complete with hooter, Ack, test & reset PBs for annunciation of Alarm and Trip for following :-
Protection Relays for Transformer Supply incoming breakers:
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 80
Each Transformer breaker to be provided with : PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
iii) PB PANEL
PB PANEL
Notes : PB PANEL
PB PANEL
1.00 PB PANEL
PB PANEL
2.00 PB PANEL
d) BUS BARS: PB PANEL
PB PANEL
PB PANEL
PB PANEL
e) Outgoing: PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
i) One (1) No. 1250A, 65 KA, 4P ACB. PB PANEL
PB PANEL
ii) One (1) No. 630 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
iii) One (1) No. 400 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
i) One (1) No. 1000A, 65 KA, TPN ACB. PB PANEL
PB PANEL
ii) Four (4) Nos. 400 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
iii) Two (2) Nos. 100A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
1 Set PB PANEL
PB PANEL
6.20 MDB-EE-PB10-D51 : PB PANEL
Location: Ground Floor Electrical Room : PB PANEL
One (1) no. SIPROTEC compact 7SJ80 Multifunction Protection Relay of Siemens make or equivalent.
One(1) set of CTs of ratio 2500/5A with core for protection of 5VA and class 5P10.
One (1) Set, 4 Nos. CTs of ratio 2500/1A, Class PS shall be provided for REF Protection.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
Operation interlocks as per specification & drawings indicating sufficient nos. of potential free contacts for interlocking/ indication annunciation/control etc shall be provided by the bidder as required.
Two (2) Sets of 3000Amp.,65kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Seperate Earth Bus Bar of Copper Conductor of 65 x 6 mm.
MDB-EE-PB00-C3 described as above (from a to e) and as per Specifications and SLD.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 81
PB PANEL
MDB-EE-PB10-D51 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) PB PANEL
PB PANEL
Each incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
iii) PB PANEL
iv) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
v) PB PANEL
PB PANEL
1.00 WTI Alarm PB PANEL
2.00 WTI Trip PB PANEL
3.00 REF Trip PB PANEL
4.00 HT Breaker Trip PB PANEL
PB PANEL
c) PB PANEL
PB PANEL
Each Transformer breaker to be provided with : PB PANEL
PB PANEL
i) PB PANEL
Two (2) Nos. 2500 Amps, 400 V, 65kA, TPN draw out, Electrically operated ACB, with ON/OFF/TRIP/Trip circuit healthy indication lamp and TNC control switch, under voltage & shunt trip release, anti pumping protection microprocessor based O/C, S/C & E/F protection etc. complete as required for Transformer Supply Feeder.
One (1) no. 1600 Amps, 400 V, 50KA, four pole EDO ACB Bus coupler breaker complete with under voltage and shunt trip release, anti pumping protection, ON/OFF/ indication etc. to be Electrically and mechanically interlocked with the incommers so that necessary interlocking can be achieved as per approved SLD.
Metering & indication for Transformer Supply incoming breakers:
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents, Power Factor, Frequency, Power, Energy, harmonics and hours run (EM6400 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 2500/5A,15VA, Class 1.0 as required.
One (1) set of 2500/5 A, C.L 1.0 CTs for input to APFC relay.
One (1) No. 4 Window Audi/visual annunciator system complete with hooter, Ack, test & reset PBs for annunciation of Alarm and Trip for following :-
Protection Relays for Transformer Supply incoming breakers:
One (1) no. SIPROTEC compact 7SJ80 Multifunction Protection Relay of Siemens make or equivalent.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 82
PB PANEL
ii) PB PANEL
PB PANEL
iii) PB PANEL
PB PANEL
Notes : PB PANEL
PB PANEL
1.00 PB PANEL
PB PANEL
2.00 PB PANEL
PB PANEL
d) BUS BARS: PB PANEL
PB PANEL
PB PANEL
PB PANEL
e) Outgoing: PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
i) One (1) No. 1600A, 65 KA, TPN ACB. PB PANEL
PB PANEL
One (1) No. 1000A, 65 KA, TPN ACB. PB PANEL
PB PANEL
ii) One (1) No. 400 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
iii) One (1) No. 250A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
i) One (1) No. 1000A, 65 KA, TPN ACB. PB PANEL
PB PANEL
ii) One (1) No. 630 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
iii) Five (5) Nos. 400 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
iv) Two (2) Nos. 250A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
1 Set PB PANEL
6.30 CAPACITOR PANELS (250 kVAR) : PB PANEL
PB PANEL
One(1) set of CTs of ratio 2500/5A with core for protection of 5VA and class 5P10.
One (1) Set, 4 Nos. CTs of ratio 2500/1A, Class PS shall be provided for REF Protection.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
Operation interlocks as per specification & drawings indicating sufficient nos. of potential free contacts for interlocking/ indication annunciation/control etc shall be provided by the bidder as required.
Two (2) Sets of 3000Amp.,65kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Seperate Earth Bus Bar of Copper Conductor of 65 x 6 mm.
MDB-EE-PB10-D51 described as above (from a to e) and as per Specifications and SLD.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 83
a) Incoming : PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) Metering, Indication and Protection : PB PANEL
PB PANEL
- PB PANEL
PB PANEL
- PB PANEL
PB PANEL
c) Busbar : PB PANEL
PB PANEL
- PB PANEL
PB PANEL
d) Outgoings : PB PANEL
PB PANEL
- 4 Set PB PANEL
PB PANEL
Notes: PB PANEL
PB PANEL
1.00 PB PANEL
PB PANEL
2.00 PB PANEL
PB PANEL
3.00 PB PANEL
PB PANEL
6.40 SDB-EE-PB00-D24 PB PANEL
PB PANEL
SDB-EE-PB00-D24 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
One (1) No. 400A, 36KA, TPN MCCB, incomer with 10 step APFC relay with Auto/Manual selector switch, timer, aux. Contactor, louvers, Exhaust fan etc.
One (1) No. digital multifunction meter for measurement of voltage and currents with selector push buttons and one set of CTs of ratio 400A /5A, CL 1.0, 15 VA.
One (1) set of RYB phase indication lamps with control SP MCB.
500A TPN+E, Cu. Busbar insulated with heat shrinkable sleeves and shall be color coded. Copper Earth Bus of 50 x 6 mm.
250 KVAR Capacitor Panel in steps of 10 Nos. of 1 x 25 kVAR banks.
Each capacitor bank should have its individual MCCB & Contactor suitable for capacitor duty including fuses for each capacitor unit as per specifications and approved SLD.
Enclosure of capacitor panel shall be liberally designed to take care of internal heat emission by capacitor unit without forced cooling and to limit the temperature rise with in permissible limit. However, louvers are allowed to facilitate extra cooling.
Enclosure of capacitor panel shall be designed so that detuned reactors can be installed in the same panel for harmonics reduction, in future.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 84
PB PANEL
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
ii) PB PANEL
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Note: PB PANEL
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
PB PANEL
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 250 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) One (1) No. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
1 Set PB PANEL
PB PANEL
6.50 SDB-EE-PB10-D2 PB PANEL
PB PANEL
SDB-EE-PB00-D24 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP/ indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-PB00-D24 described as above (from a to d) and as per SLD
One (1) No. 250Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 85
Incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Note: PB PANEL
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
PB PANEL
d) Outgoing: PB PANEL
i) One (1) No. 250 A, 36 KA, TPN MCCB. PB PANEL
ii) One (1) No. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
1 Set PB PANEL
6.60 PB PANEL
PB PANEL
PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 250/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
300Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-PB10-D24 described as above (from a to d) and as per SLD
SDB-EE-PB20-E8, SDB-EE-PB10-E15, SDB-EE-PB10-E22, SDB-EE-PB50-E47, SDB-EE-PB10-E47
SDB-EE-PB20-E8, SDB-EE-PB10-E15, SDB-EE-PB10-E22, SDB-EE-PB50-E47, SDB-EE-PB10-E47 shall Comprise of the following:
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 86
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Note: PB PANEL
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
PB PANEL
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) Two (2) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
5 Set PB PANEL
PB PANEL
6.70 SDB-EE-PB10-E08 PB PANEL
PB PANEL
SDB-EE-PB10-E08 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Note: PB PANEL
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-PB20-E8, SDB-EE-PB10-E15, SDB-EE-PB10-E22, SDB-EE-PB50-E47, SDB-EE-PB10-E47 described as above (from a to d) and as per SLD
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 87
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
PB PANEL
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 160 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Two (2) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
1 Set PB PANEL
PB PANEL
6.80 SDB-EE-PB20-E47, SDB-EE-PB30-E47 PB PANEL
PB PANEL
PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Note: PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-PB10-E08 described as above (from a to d) and as per SLD
SDB-EE-PB20-E47, SDB-EE-PB30-E47 shall Comprise of the following:
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 88
PB PANEL
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
2 Set PB PANEL
PB PANEL
6.90 SDB-EE-PB50-D54 PB PANEL
PB PANEL
SDB-EE-PB50-D54 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Note: PB PANEL
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
PB PANEL
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 250 A, 36 KA, TPN MCCB. PB PANEL
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-PB20-E47, SDB-EE-PB30-E47 described as above (from a to d) and as per SLD
One (1) No. 630Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 600/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
700Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 89
PB PANEL
ii) Three (3) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
1 Set PB PANEL
6.10 SDB-EE-PB2M-D54 PB PANEL
PB PANEL
SDB-EE-PB2M-D54 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Note: PB PANEL
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
PB PANEL
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) Two (2) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
1 Set PB PANEL
PB PANEL
6.11 SDB-EE-PB40-E47, SDB-EE-PB10-E26 PB PANEL
PB PANEL
PB PANEL
SDB-EE-PB50-D54 described as above (from a to d) and as per SLD
One (1) No. 100Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 100/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
150Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-PB2M-D54 described as above (from a to d) and as per SLD
SDB-EE-PB40-E47, SDB-EE-PB10-E26 shall Comprise of the following:
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 90
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Note: PB PANEL
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
PB PANEL
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) Three (3) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
2 Set PB PANEL
PB PANEL
6.12 SDB-EE-PB10-E33 PB PANEL
PB PANEL
SDB-EE-PB10-E33 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-PB40-E47, SDB-EE-PB10-E26 described as above (from a to d) and as per SLD
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 91
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Note: PB PANEL
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
PB PANEL
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 160 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) One (1) No. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
1 Set PB PANEL
6.13 SDB-EE-PB10-E40 PB PANEL
PB PANEL
SDB-EE-PB10-E40 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-PB10-E33 described as above (from a to d) and as per SLD
One (1) No. 630Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 92
i) PB PANEL
PB PANEL
ii) PB PANEL
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Note: PB PANEL
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
PB PANEL
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 160 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Three (3) Nos. 100 A, 25 KA, TPN MCCB. PB PANEL
PB PANEL
1 Set PB PANEL
PB PANEL
6.13 SDB-EE-PB10-D52 PB PANEL
PB PANEL
SDB-EE-PB10-D52 shall Comprise of the following: PB PANEL
PB PANEL
a) Incomings: PB PANEL
PB PANEL
PB PANEL
PB PANEL
b) Metering & indication for incoming breakers: PB PANEL
PB PANEL
Incoming breaker shall be provided with PB PANEL
PB PANEL
i) PB PANEL
ii) PB PANEL
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 600/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
700Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-PB10-E40 described as above (from a to d) and as per SLD
One (1) No. 400Amps, 400 V, 36kA TPN MCCB, with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD.
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 93
PB PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. PB PANEL
PB PANEL
Note: PB PANEL
PB PANEL
c) BUS BARS: PB PANEL
PB PANEL
PB PANEL
PB PANEL
d) Outgoing: PB PANEL
PB PANEL
i) One (1) No. 160 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
ii) Six (6) Nos. 100 A, 36 KA, TPN MCCB. PB PANEL
PB PANEL
1 Set PB PANEL
PB PANEL
6.60 FINAL DISTRIBUTION BOARDS PB PANEL
PB PANEL
PB PANEL
PB PANEL
6.6.1 DB-EE-PB00-D10 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
500Amp., 36kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 32 x 6 mm copper.
SDB-EE-PB10-D52 described as above (from a to d) and as per SLD
Design, manufacture, supply, installation (recessed/ surface), testing and commissioning of following switch fuse Unit/ MCCB/MCB type distribution boards as per drawings & specifications fabricated out of 14 SWG, CRCA sheet steel in compartmentalised design as per specification and drawings. The surface distribution boards shall be mounted on 50 x 50 x 6 MS angle frame work grounted to floor/ walls. The rate includes the angle iron frame, support, painting, numbering, earthing etc as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 94
PB PANEL
- Nine (9) nos. 10A SP MCB. PB PANEL
PB PANEL
- Six (6) nos. 16A SP MCB. PB PANEL
PB PANEL
- Three (3) nos. 32A TPN MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Twenty Two (22) nos. 16A SP MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D10 as described above and as per DB chart. 1 Set PB PANEL
6.6.2 DB-EE-PB00-D16 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Nine (9) nos. 10A SP MCB. PB PANEL
PB PANEL
- Nine (9) nos. 16A SP MCB. PB PANEL
PB PANEL
- Two (2) nos. 32A TPN MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Twenty Two (22) nos. 16A SP MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D16 as described above and as per DB chart. 1 Set PB PANEL
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 95
PB PANEL
6.6.3 DB-EE-PB00-D31 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Twenty One (21) nos. 10A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Three (3) nos. 10A SP MCB. PB PANEL
PB PANEL
- Nineteen (19) nos. 16A SP MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D31 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.4 DB-EE-PB00-D39 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 96
- Six (6) nos. 10A SP MCB. PB PANEL
PB PANEL
- Fifteen (15) nos. 16A SP MCB. PB PANEL
PB PANEL
One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
- Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Twenty Two (22) nos. 16A SP MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D39 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.5 DB-EE-PB00-D46 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Six (6) nos. 10A SP MCB. PB PANEL
PB PANEL
- Six (6) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
- Space for installation of Nine (9) Nos. SP MCB PB PANEL
PB PANEL
- Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Twenty Two (22) nos. 16A SP MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 97
DB-EE-PB00-D46 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.6 DB-EE-PB00-D52 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- One (1) no. 6A SP MCB. PB PANEL
- Eighteen (18) nos. 10A SP MCB. PB PANEL
PB PANEL
- Five (5) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 16A TPN MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Three (3) nos. 6A SP MCB. PB PANEL
PB PANEL
- Nineteen (19) nos. 16A SP MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D52 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.7 DB-EE-PB00-D54 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 98
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Five (5) nos. 6A SP MCB. PB PANEL
PB PANEL
- Twelve (12) nos. 10A SP MCB. PB PANEL
PB PANEL
- Four (4) nos. 16A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- One (1) no. 6A SP MCB. PB PANEL
PB PANEL
- Fifteen (15) nos. 16A SP MCB. PB PANEL
PB PANEL
- Two (2) nos. 32A TPN MCB. PB PANEL
PB PANEL
- Space for installation of five (5) Nos. SP MCB PB PANEL
PB PANEL
DB-EE-PB00-D54 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.8 DB-EE-PB20-E8 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
- Thirty (30) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 99
PB PANEL
- Nine (9) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB20-E8 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.9 DB-EE-PB20-E47 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Twelve (12) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Five (5) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB20-E47 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.10 DB-EE-PB2M-D54 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 100
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Thirty Three (23) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Twenty Seven (27) nos. 16A SP MCB. PB PANEL
PB PANEL
- Four (4) nos. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB2M-D54 as described above and as per DB chart. 1 Set PB PANEL
6.6.11 DB-EE-PB3M-D2 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Twenty One (21) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Sixteen (16) nos. 16A SP MCB. PB PANEL
PB PANEL
- Two (2) nos. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB3M-D2 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.12 DB-EE-PB30-E8 : PB PANEL
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 101
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Fourty Five (45) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Fifteen (15) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB30-E8 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.13 DB-EE-PB30-E47 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
- Fourty Two (42) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 102
- Thirteen (13) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB30-E47 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.14 DB-EE-PB40-E47 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Thirty Three (33) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
- Twelve (12) nos. 16A SP MCB. PB PANEL
PB PANEL
- One (1) no. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB40-E47 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
6.6.15 DB-EE-PB50-D54 : PB PANEL
PB PANEL
Incomer: PB PANEL
PB PANEL
- 100A TP MCB Isolator. PB PANEL
PB PANEL
Busbar : PB PANEL
PB PANEL
- 150A 4P Cu. Busbar PB PANEL
PB PANEL
Outgoing – (10KA) comprising PB PANEL
PB PANEL
Section-1 PB PANEL
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 103
PB PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). PB PANEL
PB PANEL
- Fifteen (15) nos. 10A SP MCB. PB PANEL
PB PANEL
Section-2 PB PANEL
PB PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). PB PANEL
PB PANEL
- Nine (9) nos. 16A SP MCB. PB PANEL
PB PANEL
- Four (4) nos. 32A TPN MCB. PB PANEL
PB PANEL
DB-EE-PB50-D54 as described above and as per DB chart. 1 Set PB PANEL
PB PANEL
7.00 CABLES, SUB MAINS & CABLE TRAYS : PB CAB
PB CAB
7.10 Cables in Under Ground Installations : PB CAB
PB CAB
PB CAB
PB CAB
7.1.1 PB CAB
PB CAB
a) 4 core 150 sqmm 10 RM PB CAB
b) 4 core 120 sqmm 10 RM PB CAB
c) 4 core 95 sqmm 10 RM PB CAB
d) 4 core 70 sqmm 10 RM PB CAB
e) 4 core 50 sqmm 10 RM PB CAB
f) 4 core 35 sqmm 10 RM PB CAB
g) 4 core 25 sqmm 10 RM PB CAB
PB CAB
7.20 Cables on Racks / Pipes / Ducts / Wireways/Cable Trays : PB CAB
PB CAB
PB CAB
PB CAB
TOTAL OF LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS CARRIED OVER TO SUMMARY
Supply, installation, testing and commissioning of following sizes of PVC sheathed, XLPE insulated copper conductor power/multicore control, armoured, Multi-strand cable of 1.1 KV grade in ground including digging the trench, laying the cable with sand and brick covering, back filling reaming etc as required, as per specfications and as per directions of Engineer-in-charge.
Copper Conductor, Armoured XLPE Cables (PVC/SWA/XLPE) :
Supply, installation, testing and commissioning of following sizes of PVC sheathed, XLPE insulated, copper conductor, power/multicore, control, armoured, Multi-stranded cable of 1.1 KV grade on surface of wall or in existing cable tray /masonary ducts/hume pipe with fixing hardware etc as required, as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 104
7.2.1 Copper Conductor Armoured Cables : PB CAB
PB CAB
a) 3.5 core 300 sqmm 50 RM PB CAB
b) 3.5 core 240 sqmm 200 RM PB CAB
c) 3.5 core 185 sqmm 50 RM PB CAB
d) 3.5 core 150 sqmm 370 RM PB CAB
e) 3.5 core 120 sqmm 10 RM PB CAB
f) 3.5 core 95 sqmm 160 RM PB CAB
g) 3.5 core 70 sqmm 50 RM PB CAB
h) 3.5 core 50 sqmm 680 RM PB CAB
i) 3.5 core 35 sqmm 650 RM PB CAB
j) 4 core 25 sqmm 1250 RM PB CAB
k) 4 core 16 sqmm 900 RM PB CAB
l) 4 core 10 sqmm 2900 RM PB CAB
m) 4 core 6 sqmm 40 RM PB CAB
n) 4 core 4 sqmm 10 RM PB CAB
o) 3 core 25 sqmm 10 RM PB CAB
p) 3 core 16 sqmm 10 RM PB CAB
q) 3 core 10 sqmm 10 RM PB CAB
r) 3 core 6 sqmm 10 RM PB CAB
s) 3 core 4 sqmm 1600 RM PB CAB
t) 2 core 6 sqmm 10 RM PB CAB
u) 2 core 4 sqmm 10 RM PB CAB
PB CAB
7.2.2 Copper Conductor Armoured Control Cables : PB CAB
PB CAB
a) 14 C 1.5 Sqmm PVC cable 10 RM PB CAB
b) 10 C 1.5 Sqmm PVC cable 10 RM PB CAB
c) 9 C 1.5 Sqmm PVC cable 10 RM PB CAB
d) 7 C 1.5 Sqmm PVC cable 10 RM PB CAB
e) 5 C 1.5 Sqmm PVC cable 10 RM PB CAB
f) 3 C 1.5 Sqmm PVC cable 10 RM PB CAB
PB CAB
7.30 Cable Termination : PB TERM
PB TERM
PB TERM
PB TERM
7.3.1 Copper conductor armoured cables : PB TERM
PB TERM
a) 3.5 core 300 sqmm 2 Nos. PB TERM
b) 3.5 core 240 sqmm 12 Nos. PB TERM
c) 3.5 core 185 sqmm 4 Nos. PB TERM
d) 3.5 core 150 sqmm 16 Nos. PB TERM
Supply and making end termination with brass double compression glands for the following XLPE insulated PVC sheathed, 1100 V grade, Multi-strand copper conductor cable including cost of crimping lugs/ferrules, double compression glands, solder, cable sockets, insulation tap etc complete as required, as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 105
e) 3.5 core 120 sqmm 2 Nos. PB TERM
f) 3.5 core 95 sqmm 16 Nos. PB TERM
g) 3.5 core 70 sqmm 20 Nos. PB TERM
h) 3.5 core 50 sqmm 46 Nos. PB TERM
i) 3.5 core 35 sqmm 44 Nos. PB TERM
j) 4 core 25 sqmm 92 Nos. PB TERM
k) 4 core 16 sqmm 46 Nos. PB TERM
l) 4 core 10 sqmm 268 Nos. PB TERM
m) 4 core 6 sqmm 4 Nos. PB TERM
n) 4 core 4 sqmm 2 Nos. PB TERM
o) 3 core 25 sqmm 2 Nos. PB TERM
p) 3 core 16 sqmm 2 Nos. PB TERM
q) 3 core 10 sqmm 2 Nos. PB TERM
r) 3 core 6 sqmm 2 Nos. PB TERM
s) 3 core 4 sqmm 164 Nos. PB TERM
t) 2 core 6 sqmm 2 Nos. PB TERM
u) 2 core 4 sqmm 2 Nos. PB TERM
PB TERM
7.3.2 Copper Conductor PVC Insulated Armoured Control Cables : PB TERM
PB TERM
PB TERM
a) 14 C x 1.5 Sqmm 2 Nos. PB TERM
b) 10 C x 1.5 Sqmm 2 Nos. PB TERM
c) 9 C x 1.5 Sqmm 2 Nos. PB TERM
d) 7 C x 1.5 Sqmm 2 Nos. PB TERM
e) 5 C x 1.5 Sqmm 2 Nos. PB TERM
f) 3 C x 1.5 Sqmm 2 Nos. PB TERM
PB TERM
Notes: PB TERM
PB TERM
7.40 PB CAB
PB CAB
a) 4 C x 185 Sqm, CWZ Cable 5 RM PB CAB
b) 4 C x 150 Sqm, CWZ Cable 5 RM PB CAB
c) 4 C x 120 Sqm, CWZ Cable 5 RM PB CAB
d) 4 C x 95 Sqm, CWZ Cable 5 RM PB CAB
e) 4 C x 70 Sqm, CWZ Cable 5 RM PB CAB
f) 4 C x 50 Sqm, CWZ Cable 5 RM PB CAB
g) 4 C x 35 Sqm, CWZ Cable 5 RM PB CAB
(Single Compression Glands suitable for following armoured cables)
The cable quantities given are approximate and to cover various sizes. The contractor shall measure the cables required and procurement order shall be placed accordingly. The quantities shall be confirmed before start of work.
Supply, installation, testing and commissioning of 1.1 KV grade, Multicore, copper conductor, LSZH outer sheathed, CWZ fire resistant cable (in compliance with BS : 6387) of following sizes on surfae of wall/existing cable trays/Mesonary Hume pipe/Duct/Trenches etc., with fixing hardware etc. as required as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 106
h) 4 C x 25 Sqm, CWZ Cable 5 RM PB CAB
i) 4 C x 16 Sqm, CWZ Cable 5 RM PB CAB
j) 4 C x 10 Sqm, CWZ Cable 5 RM PB CAB
k) 4 C x 6 Sqm, CWZ Cable 5 RM PB CAB
l) 4 C x 4 Sqm, CWZ Cable 5 RM PB CAB
m) 4 C x 2.5 Sqm, CWZ Cable 5 RM PB CAB
PB CAB
7.50 Cable Trays : PB TRAY
PB TRAY
PB TRAY
PB TRAY
Notes: PB TRAY
PB TRAY
7.5.1 Ladder Type Cable tray : PB TRAY
PB TRAY
a) 900 mm x 75 mm x 2.0 mm 5 RM PB TRAY
b) 750 mm x 75 mm x 2.0 mm 5 RM PB TRAY
c) 600 mm x 75 mm x 2.0 mm 5 RM PB TRAY
d) 450 mm x 75 mm x 2.0 mm 5 RM PB TRAY
e) 300 mm x 75 mm x 2.0 mm 5 RM PB TRAY
f) 250 mm x 75 mm x 2.0 mm 5 RM PB TRAY
g) 200 mm x 75 mm x 2.0 mm 5 RM PB TRAY
g) 150 mm x 75 mm x 2.0 mm 5 RM PB TRAY
g) 100 mm x 75 mm x 2.0 mm 5 RM PB TRAY
PB TRAY
7.5.2 Perforated Type Cable Tray : PB TRAY
PB TRAY
a) 750 mm x 75 mm x 2.0 mm 10 RM PB TRAY
b) 600 mm x 75 mm x 2.0 mm 10 RM PB TRAY
c) 500 mm x 75 mm x 2.0 mm 10 RM PB TRAY
d) 400 mm x 75 mm x 2.0 mm 10 RM PB TRAY
e) 300 mm x 50 mm x 2.0 mm 50 RM PB TRAY
f) 250 mm x 50 mm x 2.0 mm 970 RM PB TRAY
g) 200 mm x 75 mm x 2.0 mm 610 RM PB TRAY
h) 150 mm x 75 mm x 2.0 mm 1590 RM PB TRAY
i) 100 mm x 75 mm x 2.0 mm 350 RM PB TRAY
PB TRAY
7.5.3 Fibreglass Ladder Type Cable Tray : PB TRAY
Supply and installation of ladder type/perforated type cable trays of the following sizes fabricated out of perforated hot dip galvanised MS sheets of minimum 2.0 mm thick to be installed horizontally or vertically. The cable tray shall be complete including cost of supporting Steel/Hangers, bends, elbows, cross, tees, reducers etc as per drawings/site condition and rate shall include cost of anchor fasteners, screws, nuts, bolts and misc. other fixing hardware etc as required, as per specifications and approved Shop drawings.
The cable tray shall be factory built. Bidder shall include in his price, required numbers of Tees, Crosses, Bends, Elbows etc as required as per actual site conditions. Bidder may refer to the drawings for estimation purpose.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 107
PB TRAY
PB TRAY
PB TRAY
a) 600 mm wide 5 RM PB TRAY
b) 450 mm wide 5 RM PB TRAY
c) 300 mm wide 5 RM PB TRAY
d) 225 mm wide 5 RM PB TRAY
e) 100 mm wide 5 RM PB TRAY
PB TRAY
7.60 Misc. Works Relating to Cabling: PB PIPE
PB PIPE
7.6.1 GI Pipe Installation : PB PIPE
PB PIPE
PB PIPE
PB PIPE
a) 25 mm dia 10 RM PB PIPE
b) 32 mm dia 10 RM PB PIPE
c) 40 mm dia 10 RM PB PIPE
d) 50 mm dia 10 RM PB PIPE
e) 80 mm dia 10 RM PB PIPE
f) 100 mm dia 10 RM PB PIPE
g) 150 mm dia 10 RM PB PIPE
7.6.2 Flexible Conduits Installation : PB PW
PB PW
PB PW
7.6.2.1 GI flexible conduits : PB PW
PB PW
a) 20 mm dia 100 RM PB PW
b) 25 mm dia 100 RM PB PW
c) 40 mm dia 100 RM PB PW
d) 50 mm dia 100 RM PB PW
PB PW
PB PW
8.00 WIRING : PB PW
PB PW
8.10 Point Wiring : PB PW
Supply & Installation of Ladder type Cable tray of following sizes. The Cable Tray shall be complete including the cost of Anchor fasteners, Hardware, supporting structure etc. as required and as per specifications and approved drawing :
Supply and installation of following sizes of `A' class GI pipe for cable sleeves in recess/ on surface/Ground complete with all accessories pull boxes where ever required, G.I. fish wire, fixing hardware etc. including the chasing of wall/floor, and plastering the chased portion, digging the trench and back filling, making good the damages, sealing of pipe entry etc as required.
Supply and installation of following sizes of GI flexible conduits with all accessories including fixing nipples, couplings and fixing hardware etc as required and as per specifications.
TOTAL OF CABLES, SUB MAINS, CABLE TRAYS CARRIED OVER TO SUMMARY
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 108
PB PW
The rates for point wiring shall include the circuit wiring. PB PW
PB PW
PB PW
PB PW
PB PW
PB PW
PB PW
PB PW
PB PW
PB PW
PB PW
PB PW
8.1.1 Light Points controlled by switch : PB PW
PB PW
a) Single/ First light point con-trolled by a 5Amps switch. 103 No. PB PW
PB PW
b) Same as above but loop point 322 No. PB PW
PB PW
8.1.2 Light Points controlled directly from DB . PB PW
PB PW
i. Single/ First Point Controlled directly by MCB in DB 419 Nos. PB PW
PB PW
ii. Same as above but loop point. 3780 Nos. PB PW
PB PW
8.1.3 Light points controlled by Two Way Switch : PB PW
PB PW
i) 41 Nos. PB PW
PB PW
ii) Same as above but loop point. 256 Nos. PB PW
PB PW
8.1.5 Light points controlled by Push Buttons : PB PW
PB PW
i) One light points controlled by One Push Button. 1 Nos. PB PW
PB PW
ii) Two light points controlled by One Push Button. 41 Nos. PB PW
Circuit wiring means the wiring from DB / Dimmer panel to the first point of circuit through control switch.
Circuit wiring and subsequent looping shall be done with 2.5 Sqmm, 1100V grade LSZH insulated stranded, copper wires.
The rates of point wiring shall include supply, installation, testing & commissioning of MS conduit with accessories, GI Boxes and required GI flexible conduits with accessories up to the Point, LSZH insulated, stranded, Cu. Wire etc. as required and as per specification, Tender Drawing and direction of Engineer-in-charge.
Where the light points are directly controlled from DB (without any local control switches), the quoted rates shall not include the cost of MCBs etc. in the point wiring.
The rates of point wiring shall include earthing of each light, fan, switches, switch plates, boxes and other non current carrying metallic part with 2.5 Sqm. Stranded copper, LSZH insulated, stranded, copper wire.
One / first light point controlled by two nos. two way 5 Amps. switch.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 109
PB PW
iii) Three light points controlled by One Push Button. 45 Nos. PB PW
PB PW
iv) Six light points controlled by Two Push Buttons. 39 Nos. PB PW
PB PW
v) Seven light points controlled by Two Push Buttons. 39 Nos. PB PW
PB PW
vi) Nine light points controlled by Two Push Buttons. 1 Nos. PB PW
8.1.6 Presence Sensor : PB PW
PB PW
a) 208 Nos. PB PW
PB PW
8.1.7 6A Socket Points : PB PW
PB PW
a) 215 Point PB PW
PB PW
8.1.8 FCU Points controlled by 6A Switch : PB PW
PB PW
i) 21 Nos. PB PW
PB PW
ii) Same as above but loop point. 38 Nos. PB PW
PB PW
8.20 Power Socket Wiring : PB PW
PB PW
PB PW
PB PW
8.2.1 43 Point PB PW
PB PW
Wiring from Presence Sensor to the DB/SwitchBoard/Light fixtures, including providing Presence Sensor as required and as per approved shop drawing (wiring from DB to light points has already been included in subheads 8.1.1, 8.1.2, 8.1.3, 8.1.4, 8.1.5 above and not to be considered here).
Wiring for 6A, BS, switched socket outlet including providing 6A, BS, switched, socket outlet as per specification and approved shop drawing.
One / first light point controlled by 6A, BS, switched socket outlet including providing 6A, BS, switched, socket outlet.
Power Socket Wiring shall include supply, installation, testing and commissioning of wiring of following points, including, providing conduits of suitable size, its accessories/Hardware, Junction Boxes, LSZH wires, termination of wires, switches, socket outlets, Plug tops etc. as required and as per specification.
Wiring for 1 No. BS, 16A, switched socket outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 110
8.2.2 10 Point PB PW
PB PW
8.2.3 26 Point PB PW
8.2.4 77 Point PB PW
PB PW
8.2.5 29 Point PB PW
PB PW
8.2.6 19 Point PB PW
PB PW
Wiring for 2 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 3 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 3 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 4 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 4 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 5 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 5 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 6 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 6 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 111
8.2.7 12 Point PB PW
PB PW
8.2.8 1 Point PB PW
8.2.9 41 Point PB PW
PB PW
8.2.10 1 Point PB PW
PB PW
8.2.11 2 Point PB PW
Wiring for 7 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 7 Nos. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 3 Nos. BS, 16A, switched outlet & 2 Nos. BS 16A switched outlet in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of Wiring for 3 Nos. BS, 16A, switched outlet & 2 Nos. BS 16A switched outlet in IP-65 enclosure with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. BS, 16A, switched outlets in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 No. BS, 16A, switched outlets in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. BS, 16A, switched outlets and 1 No. 16A DP Isolators in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 No. BS, 16A, switched outlets and 1 No. 16A DP Isolator in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 3 Nos. BS, 16A, switched outlets and 1 No. 16A DP Isolator in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 3 Nos. BS, 16A, switched outlets and 1 No. 16A DP Isolator in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 112
PB PW
8.2.12 43 Point PB PW
PB PW
8.2.13 12 Point PB PW
8.2.14 20 Point PB PW
PB PW
8.2.15 7 Nos. PB PW
PB PW
Wiring for 1 No. BS, 16A, switched outlet (Spur Outlet) for Hand Dryer with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet (Spur Outlet) with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. Disabled Alarm Device with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. Disabled Alarm Device, Single phase motor of required capacity (As approved by the Engineer-in-charge) with internal wiring in G.I. box, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. 16A DP Isolators in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. 16A DP Isolator in IP-65 enclosure with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. Floor LV tank consisting of 4 Nos. 6A BS switched socket and 2 Nos. RJ-45 Data Outlets in IP-65 enclosure, with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. Floor LV tank consisting of 4 Nos. 6A BS switched socket and 2 Nos. RJ-45 Data outlets in IP-65 enclosure, with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 113
8.2.2 41 Point PB PW
PB PW
8.30 CEE INDUSTRIAL SWITCHED SOCKETS PB PW
PB PW
8.3.1 PB PW
PB PW
a) 16A, 2P+E, CEE, switched socket outlet with plug top (IP-44) 82 Nos. PB PW
PB PW
b) 1 No. PB PW
PB PW
c) 40 No. PB PW
PB PW
d) 4 No. PB PW
PB PW
d) 36 No. PB PW
8.3.2 Socket Combination A PB PW
PB PW
PB PW
PB PW
- PB PW
PB PW
- PB PW
PB PW
- PB PW
Wiring for 2 Nos. 16A 2P+E CEE, switched, industrial type plug and socket outlet in IP-44 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos. 16A 2P+E CEE, switched, industrial type plug and socket outlet in IP-44 enclosure with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Supply, installation, testing and commissioning of single phase/three phase, CEE, switched, industrial type plug and socket outlet in IP-44 enclosure including termination, earthing etc. in surface/recessed mounting as required, as per specifications and approved shop drawings (Cabling/Conduiting & wiring shall be paid separately under different items).
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-44)
32A, 3P+N+E, CEE, switched socket outlet with plug top (IP-44).
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-65) for water heaters.
125A, 3P+N+E, CEE, switched socket outlet with plug top (IP-44)
Supply, installation, testing and commissioning of following Single Phase/3 phase, CEE, switched, Industrial type Plug and socket Combination Outlet in single enclosure (IP-44) including termination, Earthing etc. in surface/recess mounting as required. (Conduiting/wiring/cabling for the same shall be paid seperately under different item).
One no. 16A, 2P+E, CEE, switched socket outlets with plug (IP-44) with 16A TPN MCB,10kA.
One no. 16A, 3P+N+E, CEE, switched socket outlets with plug (IP-44) with 16A TPN MCB,10kA.
One no. 32A, 3P+N+E, CEE, switched socket outlets with plug (IP-44) with 32A TPN MCB,10kA.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 114
PB PW
- One no. 13A, BS switched socket outlet 39 Set PB PW
PB PW
8.3.3 Socket Combination B PB PW
PB PW
PB PW
PB PW
- PB PW
PB PW
- PB PW
PB PW
- PB PW
PB PW
- Two nos. 13A, BS switched socket outlet 122 Set PB PW
PB PW
8.3.4 Socket Combination C PB PW
PB PW
PB PW
PB PW
- PB PW
PB PW
- PB PW
PB PW
- PB PW
PB PW
- PB PW
PB PW
- One no. 13A, BS switched socket outlet 1 Set PB PW
8.40 ISOLATORS PB PW
PB PW
PB PW
PB PW
Supply, installation, testing and commissioning of following Single Phase/3 phase, CEE, switched, Industrial type Plug and socket Combination Outlet in single enclosure (IP-44) including termination, Earthing etc. in surface/recess mounting as required. (Conduiting/wiring/cabling for the same shall be paid seperately under different item).
Two nos. 16A, 2P+E, CEE, switched socket outlets with plug (IP-44) with 16A TPN MCB,10kA.
One no. 16A, 3P+N+E, CEE, switched socket outlets with plug (IP-44) with 16A TPN MCB,10kA.
One no. 32A, 3P+N+E, CEE, switched socket outlets with plug (IP-44) with 32A TPN MCB,10kA.
Supply, installation, testing and commissioning of following Single Phase/3 phase, CEE, switched, Industrial type Plug and socket Combination Outlet in single enclosure (IP-44) including termination, Earthing etc. in surface/recess mounting as required. (Conduiting/wiring/cabling for the same shall be paid seperately under different item).
One no. 16A, 2P+E, CEE, switched socket outlets with plug (IP-44) with 16A TPN MCB,10kA.
One no. 16A, 3P+N+E, CEE, switched socket outlets with plug (IP-44) with 16A TPN MCB,10kA.
One no. 32A, 3P+N+E, CEE, switched socket outlets with plug (IP-44) with 32A TPN MCB,10kA.
One no. 63A, 3P+N+E, CEE, switched socket outlets with plug (IP-44) with 63A TPN MCB,10kA.
Supply, installation, testing and commissioning of isolators in IP-65 enclosures complete with termination in surface/recessed mounting as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 115
a) 16A Four pole isolator 3 Nos. PB PW
PB PW
b) 63A Four pole isolator 19 Nos. PB PW
PB PW
c) 125A Four pole isolator 2 Nos. PB PW
PB PW
8.50 M.S. Black Conduits : PB PW
PB PW
PB PW
PB PW
a) 20 mm dia 20 RM PB PW
b) 25 mm dia 20 RM PB PW
c) 32 mm dia 20 RM PB PW
d) 40 mm dia 20 RM PB PW
e) 50 mm dia 20 RM PB PW
PB PW
8.60 Sub-mains Wiring : PB PW
PB PW
PB PW
PB PW
a) 2 x 1.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM PB PW
b) 2 x 2.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM PB PW
c) 2 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire. 20 RM PB PW
d) 2 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM PB PW
e) 4 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM PB PW
f) 4 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM PB PW
g) 2 x 10.0 Sqmm + 1 No. 6.0 Sqmm Copper earth wire 20 RM PB PW
h) 4 x 10.0 Sqmm + 2 Nos. 6.0 Sqmm Copper earth wire 20 RM PB PW
i) 4 x 16.0 Sqmm + 2 Nos. 10.0 Sqmm Copper earth wire 20 RM PB PW
j) 4 x 25.0 Sqmm + 2 Nos. 16.0 Sqmm Copper earth wire 20 RM PB PW
PB PW
Note: PB PW
PB PW
1) PB PW
PB PW
2) PB PW
PB PW
TOTAL OF WIRING CARRIED OVER TO SUMMARY PB PW
9.00 LIGHTING FIXTURES : PB LIGHT
Supply and installation of following size of MS conduit pipe in recess or on surface including all accessories MS/CI pull/junction boxes, GI fish wire, fixing hardware etc including chasing the walls/floor and plastering the chased portion and making good the damages etc, complete as required and as per specifications.
Supply and drawing of following sizes of LSZH insulated, stranded, copper conductor wires of 650/1100 Volts grade in existing conduit pipe /wire ways including connection /terminations etc as required.
In false ceiling areas the work is to be co-ordinated with respect to interior work and rate for point wiring shall include flexible conduit/fixing nipples/couplers etc from the junction box up to the fitting.
All wires used for circuit / point wiring shall be Low Smoke Zero Halogen (LSZH) wires.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 116
PB LIGHT
PB LIGHT
PB LIGHT
1.00 87 Set PB LIGHT
PB LIGHT
2.00 25 Set PB LIGHT
PB LIGHT
3.00 2 Set PB LIGHT
PB LIGHT
4.00 2 Set PB LIGHT
PB LIGHT
5.00 5 Set PB LIGHT
PB LIGHT
6.00 1 Set PB LIGHT
PB LIGHT
7.00 154 Set PB LIGHT
PB LIGHT
8.00 46 Set PB LIGHT
PB LIGHT
9.00 92 Set PB LIGHT
PB LIGHT
10.00 15 Set PB LIGHT
PB LIGHT
11.00 441 Set PB LIGHT
PB LIGHT
Inspection, receiving, storing, handling, assembling, installation, testing and commissioning of wall /ceiling, surface/ recessed, suspended from down rod, in furniture, fluorescent / incandescent / Halogen lamp fixtures including making connections with PVC insulated stranded copper conductor wires complete including steel supports, suspenders, fixing screws, turn buckles, bolts, nuts (down rods ball and socket arrangement and special channel mounting for industrial fitting/chandelier) etc, as required. The mounting arrangement of lighting fixture shall be as indicated in the approved drawings.
Recessed Grid Luminaire 1x36W (Thorn Specalph BS/SB 1x36W or Equivalent) (T1).
Recessed Grid Luminaire 1x36W (Thorn Specalph BS/SB 1x36W or Equivalent) (T1) complete with emergency lighting units.
Recessed Grid Luminaire 2x36W (Thorn Specalph BS/SB 2x36W or Equivalent) (T2).
Recessed Grid Luminaire 2x36W (Thorn Specalph BS/SB 2x36W or Equivalent) (T2) complete with emergency lighting units.
Recessed Grid Luminaire 1x58W (Thorn Specalph BS/SB 1x58W or Equivalent) (T3).
Recessed Grid Luminaire 1x58W (Thorn Specalph BS/SB 1x58W or Equivalent) (T3) complete with emergency lighting units.
Surface mounted Industrial Luminaire with 1x36W Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or Equivalent) (T5).
Surface mounted Industrial Luminaire with 1x36W Fluorescent T5 Lamps (Thorn Indus RD 1x36W TW or Equivalent) (T5) complete with emergency lighting units.
Surface mounted Industrial Luminaire with 2x36W Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or Equivalent) (T6).
Surface mounted Industrial Luminaire with 2x36W Fluorescent T5 Lamps (Thorn Indus RD 2x36W TW or Equivalent) (T6) complete with emergency lighting units.
Surface mounted Industrial Luminaire with 2x58W Fluorescent T5 Lamps (Thorn Indus RD 2x58W TW or Equivalent) (T7).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 117
12.00 39 Set PB LIGHT
PB LIGHT
13.00 184 Set PB LIGHT
PB LIGHT
14.00 30 Set PB LIGHT
PB LIGHT
15.00 165 Set PB LIGHT
PB LIGHT
16.00 60 Set PB LIGHT
PB LIGHT
17.00 2524 Set PB LIGHT
PB LIGHT
18.00 234 Set PB LIGHT
PB LIGHT
19.00 96 Set PB LIGHT
PB LIGHT
20.00 10 Set PB LIGHT
PB LIGHT
21.00 35 Set PB LIGHT
PB LIGHT
22.00 3 Set PB LIGHT
PB LIGHT
23.00 760 Set PB LIGHT
PB LIGHT
24.00 36 Set PB LIGHT
PB LIGHT
25.00 311 Set PB LIGHT
PB LIGHT
26.00 9 Set PB LIGHT
PB LIGHT
Surface mounted Industrial Luminaire with 2x58W Fluorescent T5 Lamps (Thorn Indus RD 2x58W TW or Equivalent) (T7) complete with emergency lighting units.
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp waterproof IP44 (Siteco Europlex 24W IP44 or Equivalent) (T8).
Floodlight 400W (Siteco A2 Midi 400W IP65 asym or Equivalent) (T10)
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp IP 65 (Thorn Danube 2x28W IP65 or Equivalent) (T11).
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp IP 65 (Thorn Danube 2x28W IP65 or Equivalent) (T11) complete with emergency lighting units.
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W or Equivalent) (T13)
Recessed Downlight 1x26W (Thorn Chalice C 190H 1x26W or Equivalent) (T13) complete with emergency lighting units.
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14)
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14) complete with emergency lighting units.
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or Equivalent) (T15)
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or Equivalent) (T15) complete with emergency lighting units.
Recessed outside Downlight IP54 (Trilux Downlight IP54 or Equivalent) (T21)
Recessed outside Downlight IP54 (Trilux Downlight IP54 or Equivalent) (T21) complete with emergency lighting units.
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W T26 H2F or Equivalent) (T23).
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W T26 H2F or Equivalent) (T23) complete with emergency lighting units.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 118
27.00 29 Set PB LIGHT
PB LIGHT
28.00 200 Set PB LIGHT
PB LIGHT
29.00 58 Set PB LIGHT
PB LIGHT
30.00 46 Set PB LIGHT
PB LIGHT
31.00 22 Set PB LIGHT
PB LIGHT
PB LIGHT
10.00 EARTHING & LIGHTNING PROTECTION SYSTEM : PB EARTH
PB EARTH
10.10 Earthing System: PB EARTH
PB EARTH
10.1.1 8 Nos. PB EARTH
PB EARTH
10.1.2 21 Nos. PB EARTH
PB EARTH
10.1.3 2 Nos. PB EARTH
PB EARTH
10.1.4 Earthing Strip/Tape/Cables : PB EARTH
PB EARTH
Wall Luminaire 2x36W IP44 (Bega 4422-2 TC-L 2x36W IP44 or Equivalent) (T30)
Emergency Exit Up Fixture (Cooper/Crompton or Equivalent) complete with emergency lighting units.
Emergency Exit Down Fixture (Cooper/Crompton or Equivalent) complete with emergency lighting units.
Emergency Exit Left Fixture (Cooper/Crompton or Equivalent) complete with emergency lighting units.
Emergency Exit Right Fixture (Cooper/Crompton or Equivalent) complete with emergency lighting units.
TOTAL OF LIGHTING FIXTURES CARRIED OVER TO SUMMARY
Supply, installation, testing and commissioning of copper plate earthing stations making earth pits, earthing with copper earth plate 600 mm x 600 mm x 3.15 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS –3043 complete as required, as per specifications, drawings and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI plate earthing stations making earth pits, earthing with GI earth plate 600 mm x 600 mm x 6.30 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required, as per specifications, drawing and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI Pipe earthing stations making earth pits, earthing with GI pipe 4500 mm x 40 mm Dia including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required as per specifications, drawing and direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 119
PB EARTH
PB EARTH
G.I. Earthing strip/tape : PB EARTH
PB EARTH
a 75 x 8 mm strip 50 RM PB EARTH
b 75 x 6 mm strip 50 RM PB EARTH
c 50 x 6 mm strip 10 RM PB EARTH
d 40 x 6 mm strip 50 RM PB EARTH
e 32 x 6 mm strip 10 RM PB EARTH
f 25 x 6 mm strip 50 RM PB EARTH
g 25 x 3 mm strip 1100 RM PB EARTH
PB EARTH
Tinned Copper earthing strip/tape : PB EARTH
PB EARTH
a) 50 x 6 mm 10 RM PB EARTH
b) 32 x 6 mm 10 RM PB EARTH
c) 25 x 6 mm 10 RM PB EARTH
d) 25 x 3 mm 10 RM PB EARTH
PB EARTH
10.1.5 PB CAB
PB CAB
a) 1C x 240 Sqm 200 RM PB CAB
PB CAB
b) 1C x 185 Sqm 300 RM PB CAB
PB CAB
c) 1C x 90 Sqm 500 RM PB CAB
PB CAB
d) 1C x 50 Sqm 2000 RM PB CAB
PB CAB
10.1.6 PB EARTH
PB EARTH
75 x 6 mm GI Earth Bars. PB EARTH
Supply, installation, testing and commissioning of following sizes of GI/Tinned Copper strip/tape clamped to walls, cable trays, bus ducts, recess in Ground or surface etc for equipment/ System earthing complete as required including inter connection between length at joints, all fixing accessories saddles, clamps etc and other fixing hardware material as required, as per specifications, detail drawings shall be included for proper installation.
10.1.4.1
10.1.4.2
Supply, installation, Termination, testing and commissioning of PVC insulated, stranded copper conductor cable, laid on surface/cable tray/duct/undger ground/Trench etc. as required, as per approved shop drawing, site conditions and as directed by Engineer-in-charge.
Supply, installation, Termination, testing and Commissioning of following sizes tinned Cu/GI Earth Bars including its supporting/fixing hardware, as per drawings, specifications and as directed by Engineer-in-charge.
10.1.6.1
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 120
PB EARTH
a) 300 mm 1 No. PB EARTH
b) 500 mm 1 Nos. PB EARTH
c) 750 mm 1 Nos. PB EARTH
d) 1000 mm 1 No. PB EARTH
PB EARTH
50 x 6 mm GI Earth Bars. PB EARTH
PB EARTH
a) 300 mm 1 Nos. PB EARTH
b) 500 mm 1 Nos. PB EARTH
c) 750 mm 1 Nos. PB EARTH
d) 1000 mm 1 Nos. PB EARTH
PB EARTH
75 x 6 mm tinnned Cu Earth Bars. PB EARTH
PB EARTH
a) 300 mm 1 No. PB EARTH
b) 500 mm 3 Nos. PB EARTH
c) 750 mm 3 Nos. PB EARTH
d) 1000 mm 1 No. PB EARTH
PB EARTH
50 x 6 mm tinned Cu Earth Bars. PB EARTH
PB EARTH
a) 300 mm 25 Nos. PB EARTH
b) 500 mm 30 Nos. PB EARTH
c) 750 mm 30 Nos. PB EARTH
d) 1000 mm 10 Nos. PB EARTH
10.20 Lightning Protection System: PB EARTH
PB EARTH
10.2.1 2 Nos. PB EARTH
PB EARTH
10.2.2 44 Nos. PB EARTH
PB EARTH
10.1.6.2
10.1.6.3
10.1.6.4
Supply, installation, testing and commissioning of copper plate earthing stations making earth pits, earthing with copper earth plate 600 mm x 600 mm x 3.15 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS –3043 complete as required, as per drawings, specifications and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI Pipe earthing stations making earth pits, earthing with GI pipe 4500 mm x 40 mm Dia including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required, as per drawings, specifications and direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 121
10.2.3 Earthing Strip/Wires : PB EARTH
PB EARTH
PB EARTH
PB EARTH
a) 25 x 3 mm strip 1100 RM PB EARTH
PB EARTH
b) 25 x 6 mm strip 2400 RM PB EARTH
PB EARTH
10.2.4 PB EARTH
PB EARTH
75 x 6 mm GI Earth Bars. PB EARTH
PB EARTH
a) 300 mm 2 Nos. PB EARTH
b) 500 mm 2 Nos. PB EARTH
c) 750 mm 2 Nos. PB EARTH
d) 1000 mm 2 Nos. PB EARTH
PB EARTH
50 x 6 mm GI Earth Bars. PB EARTH
PB EARTH
a) 300 mm 2 Nos. PB EARTH
b) 500 mm 2 Nos. PB EARTH
c) 750 mm 2 Nos. PB EARTH
d) 1000 mm 2 Nos. PB EARTH
10.2.5 130 Nos. PB EARTH
PB EARTH
10.2.6 44 Nos. PB EARTH
PB EARTH
Supply, installation, testing and commissioning of following sizes of GI strip/wire clamped to walls, Ductwork, pipe work, Structural steel work, cladding work etc. in recess or surface etc for Lightning Protection System complete as required including inter connection, terminations, between length at joints, all fixing accessories saddles, plastic isolator mounting (of 50mmx80mm approx.), Sealing Collars, Sealing Strip, Squared Timber Block (80mmx100mm approx.), clamps, Lugs etc and other fixing hardware material as required for proper installation as per detail drawings, specifications and direction of Engineer-in-charge.
Supply, installation, Termination, testing and Commissioning of following sizes GI Earth Bars including in supporting/fixing hardware, as per drawings, specifications and as directed by Engineer-in-charge.
10.2.4.1
10.2.4.2
Supply and fixing of Lightning Arrestor Rod/Lightning Conductor finial made of 25 mm dia, 2.0 mm thick & 300 mm Long GI Tube having single prong at top with 75 mm dia, 6 mm thick Base plate, including connections with roof parapit Lightning protection Conductors, as per detailed drawings and as per direction of Engineer-in-charge.
Supply and fixing of "Earth Test Joints" encased in 200 mm (H) x 150 mm (W) x 100 mm (D) recessed in concrete with removable cover plate as per detailed drawing and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 122
PB EARTH
MC-1 EARTH
MC-1 MC-1 EARTH
1.00 11 KV, GAS INSULATED, RING MAIN UNITS: MC-1 HTO
MC-1 HTO
1.10 MC-1 HTO
MC-1 HTO
a) MC-1 HTO
MC-1 HTO
b) 1 Set MC-1 HTO
MC-1 HTO
Notes : MC-1 HTO
MC-1 HTO
i) MC-1 HTO
MC-1 HTO
ii) MC-1 HTO
MC-1 HTO
1.20 Battery & Battery Charger : MC-1 BATT
MC-1 BATT
a) MC-1 BATT
MC-1 BATT
i) for 24V DC System ur Set MC-1 BATT
MC-1 BATT
ii) for 110V DC System 1 Set MC-1 BATT
MC-1 BATT
b) MC-1 BATT
MC-1 BATT
i) for 24V DC System ur Set MC-1 BATT
MC-1 BATT
TOTAL OF EARTHING & LIGHTNING PROTECTION SYSTEM CARRIED OVER TO SUMMARY
Safe Unloading, Receiving, storing, checking, handling, installation, testing and commissioning of 350 MVA, 11 KV indoor 4 way, SF6 insulated, Extensible Ring Main Breaker Unit consisting of following :-
Two (2) Nos. 630 Amp, TP VCB with disconnector and Earth Switch as Incommers, with required Indication, Metering and Protection System.
Two (2) Nos. 630 Amp, TP VCB with disconnector and Earth Switch as Outgoings, with required Indication, Metering & Protection System.
Installation shall include supply of all Hardware material (excluding civil work) as required and as per Approved Shop Drawings.
Necessary Co-ordination with client and manufacturer to be done by the contractor for successful installation, Testing and Commissioning.
Supply, installation, testing & commissioning of 200 AH capacity, Ni-cd maintenance free batteries, duly charged, complete with seasoned teak wood stand, connecting lead as required for 11 KV RMU boards and some other control loads. (AH calculation to be submitted by successful bidder in co-ordination with the client and 11 KV, RMU Vendor).
Supply, installation, testing & commissioning of suitable float cum boost battery charger and necessary distribution board with 12 Nos. 16A outgoing feeders, instrument panel, Amp, Volts meter, interconnections etc. power supply 240 V, 1 phase, 50 Hz ± 10%. Charger trouble annunciation shall be provided through potential free contacts.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 123
ii) for 110V DC System 1 Set MC-1 BATT
MC-1 BATT
2.00 H T CABLING : MC-1 CAB
MC-1 CAB
2.10 11kV Cable laying : MC-1 CAB
MC-1 CAB
MC-1 CAB
MC-1 CAB
2.1.1 Underground: MC-1 CAB
MC-1 CAB
MC-1 CAB
MC-1 CAB
a) 3C x 400 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
b) 3C x 300 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
c) 3C x 240 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
d) 3C x 185 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
e) 3C x 150 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
f) 3C x 120 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
g) 3C x 95 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
h) 3C x 70 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
i) 3C x 50 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
2.1.2 In hume pipe/trays/trenches : MC-1 CAB
MC-1 CAB
MC-1 CAB
MC-1 CAB
a) 3C x 400 Sqmm, 11KV XLPE 10 Mtr. MC-1 CAB
MC-1 CAB
b) 3C x 300 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
c) 3C x 240 Sqmm, 11KV XLPE 50 Mtr MC-1 CAB
MC-1 CAB
TOTAL OF 11 KV, GAS INSULATED, RING MAIN UNITS CARRIED OVER TO SUMMARY
Supplying, laying, testing and commissioning of 11 KV grade copper conductor, cross linked polyethylene (XLPE) insulated individual core screened extruded inner sheath, flat steel/strip armoured PVC sheathed cable and suitable for (E) system complete as required and as per specification, as follows:
Supply and laying of following size of 11 KV cables in earth as per drawing, specifications and direction of engineer in charge.
Supply and laying of following sizes of 11KV cables on already laid trays/hume pipes/walls/ trench etc, as required, as per drawing, specifications and direction of Engineer-in-charge..
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 124
d) 3C x 185 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
e) 3C x 150 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
f) 3C x 120 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
g) 3C x 95 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
h) 3C x 70 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
i) 3C x 50 Sqmm, 11KV XLPE 10 Mtr MC-1 CAB
MC-1 CAB
2.20 End Termination (HT) : MC-1 TERM
MC-1 TERM
MC-1 TERM
MC-1 TERM
a) 3C x 400 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
b) 3C x 300 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
c) 3C x 240 Sqmm, 11KV XLPE 4 Set MC-1 TERM
MC-1 TERM
d) 3C x 185 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
e) 3C x 150 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
f) 3C x 120 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
g) 3C x 95 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
h) 3C x 70 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
i) 3C x 50 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
2.30 End Termination (HT) : MC-1 TERM
MC-1 TERM
MC-1 TERM
MC-1 TERM
a) 3C x 400 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
b) 3C x 300 Sqmm, 11KV XLPE 2 Set MC-1 TERM
MC-1 TERM
Cable jointing of 11 KV grade, XLPE insulated, armoured, Copper Conductor cable with suitable cable termination KITS including all accessories i.e. Sockets, lugs, gland etc as required, as per drawings, specifications and direction of Engineer-in-charge.
Cable jointing of 11 KV grade, XLPE insulated, armoured, Aluminium Conductor cable with suitable cable termination KITS including all accessories i.e. Sockets, lugs, gland etc as required, as per drawings, specifications and direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 125
c) 3C x 240 Sqmm, 11KV XLPE 2 Set MC-1 TERM
MC-1 TERM
d) 3C x 185 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
e) 3C x 150 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
f) 3C x 120 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
g) 3C x 95 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
h) 3C x 70 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
i) 3C x 50 Sqmm, 11KV XLPE 1 Set MC-1 TERM
MC-1 TERM
Notes : MC-1 TERM
MC-1 TERM
1.00 MC-1 TERM
MC-1 TERM
2.00 MC-1 TERM
MC-1 TERM
TOTAL OF H.T CABLING CARRIED OVER TO SUMMARY MC-1 TERM
3.00 SUB STATION SAFETY EQUIPMENT : MC-1 MISC
MC-1 MISC
3.10 MC-1 MISC
MC-1 MISC
a) 11 KV grade size 1000 x 900 x 25 mm thick 5 Nos. MC-1 MISC
MC-1 MISC
b) 1100 V grade size 1000 x 900 x 15 mm thick 5 Nos. MC-1 MISC
MC-1 MISC
3.20 1 No. MC-1 MISC
MC-1 MISC
3.30 5 Nos. MC-1 MISC
MC-1 MISC
3.40 Providing 11 KV tested hand gloves. 1 Pair MC-1 MISC
MC-1 MISC
3.50 Providing 11 KV insulated grounding rod. 1 No. MC-1 MISC
MC-1 MISC
The cable and cable terminations quantities given above, are approximate. The contractor shall measure the cables required at site and procurement order shall be place accrodingly.
Wherever copper cable to be connected to Aluminium Bus Bar or vis-à-vis., Bimetalic lugs to be used for terminations.
Supplying and fixing 1000 mm x 900 mm wide checkered rubber matting conforming to IS 15652-2006 complete as required.
Supplying & fixing standard shock treatment charts in English & Hindi / (Local Language) duly framed and covered with glass.
Providing & fixing HT danger notice plate 200 mm x 150 mm made of mild steel atleast 2mm thick & vitreous enameled white on both sides and with inscription in signal red colour with skull & bone on front side as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 126
3.60 Providing first aid box as per IS:13115. 1 Set MC-1 MISC
MC-1 MISC
MC-1 MISC
4.00 TRANSFORMER: MC-1 TRAFO
MC-1 TRAFO
MC-1 TRAFO
MC-1 TRAFO
a) 2000 KVA ur Set MC-1 TRAFO
b) 1600 KVA 2 Set MC-1 TRAFO
c) 1250 KVA ur Set MC-1 TRAFO
d) 1000 KVA ur Set MC-1 TRAFO
e) 800 KVA ur Set MC-1 TRAFO
f) 630 KVA ur Set MC-1 TRAFO
g) 500 KVA ur Set MC-1 TRAFO
h) 315 KVA ur Set MC-1 TRAFO
MC-1 TRAFO
Notes : MC-1 TRAFO
MC-1 TRAFO
i) MC-1 TRAFO
MC-1 TRAFO
ii) MC-1 TRAFO
MC-1 TRAFO
MC-1 TRAFO
MC-1 BBT
5.0 BUS DUCT/BUS BAR TRUNKING SYSTEM : MC-1 BBT
MC-1 BBT
5.1 Bus Duct : MC-1 BBT
MC-1 BBT
TOTAL OF SUB STATION SAFETY EQUIPMENT CARRIED OVER TO SUMMARY
Unloading,Receiving, storing, handling, installation, testing and commissioning of 11 kV/ 400V (terminal voltage), 3 phase, 50 Hz delta/star connected, copper winding. indoor type, natural air cooled, dry type, cast resin transformer of following ratings, complete with all fittings such as thermometer, off circuit tap changer with + 5 % to –15%, tapping at the step of 2.5% bi-directional roller, diagrams & rating plate & Winding temperature indicator, lifting lugs, H. T. cable box/ LT Terminal Box suitable for bus duct / Cable termination etc. complete as per relevant specifications, drawings and direction of Engineer-in-charge.
Installation rate shall include unloading, receiving including storage at site,assembly, erection, testing and commissioning etc. as required, as per approved Shop Drawing and as per direction of Engineer-in-charge..
Necessary co-ordination with the manufacturer and client shall be done by the contractor without extra cost.
TOTAL OF TRANSFORMER CARRIED OVER TO SUMMARY
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 127
MC-1 BBT
MC-1 BBT
a)
RM R.O.
MC-1 BBT
MC-1 BBT
b)
RM R.O.
MC-1 BBT
MC-1 BBT
c)
RM 55
MC-1 BBT
MC-1 BBT
5.2 Bus Bar Trunking (BBT) : MC-1 BBT
MC-1 BBT
5.2.1
MC-1 BBT
MC-1 BBT
MC-1 BBT
MC-1 BBT
i)RM R.O.
MC-1 BBT
MC-1 BBT
ii)RM R.O.
MC-1 BBT
MC-1 BBT
iii)RM R.O.
MC-1 BBT
MC-1 BBT
iv)RM R.O.
MC-1 BBT
MC-1 BBT
Design, manufacturing, supply, installation, testing & commissioning (at site) of sheet steel enclosed 3 phase & neutral, 400V, 50 Hz., 50 KA copper conductor bus duct with insulation of thermal rating confirming to class 'H' including bends, transposition piece, expansion joint, Tees, End termination units, Feeder units, tap off unit etc. with all flexible connections as per specifications and drawings with all accessories, supports and termination of bus duct to switchgear/transformer.
3000A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 8 Nos. of Terminations and all other accessories as required as per specifications, and approved Shop Drawings.
2000A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 4 Nos. of Terminations and all other accessories as required as per specifications, and approved Shop Drawings.
2500A, 50kA @ 1 Sec., TP+N, Bus Duct (IP.55) with 4 Nos. of Terminations and all other accessories as required as per specifications, and approved Shop Drawings.
Design, manufacture, assembly, supply, installation, testing and commissioning (at site) of following capacity compact, Copper Conductor, Bus Bar Trunking System including Bends, Tees, Expansion Joints, Feeder Units, Tap off Units, Transposition pieces, Flexible Connections etc. with all other Hardware/accessories required for installation of Bus Bar Trunking as per Specifications, approved Shop Drawings and instruction of Engineer-in-charge.
Shutter type spring loaded arrangements shall be provided for tap off system. The shutter shall get closed when tap off box is taken out. Tap off facilities shall be there at every 500 mm interval as per standard.
1500A, TPN+E, 400 Volt, 40 KA, compact, copper conductor BBT.
1250 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
1200 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
1000 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 128
v)RM R.O.
MC-1 BBT
vi)RM 10
MC-1 BBT
MC-1 BBT
vii)RM 10
MC-1 BBT
MC-1 BBT
viii)RM 10
MC-1 BBT
MC-1 BBT
ix)RM 10
MC-1 BBT
MC-1 BBT
Notes: MC-1 BBT
MC-1 BBT
a)MC-1 BBT
MC-1 BBT
b) Rates shall be inclusive of all accessories & fittings. MC-1 BBT
MC-1 BBT
5.2.2
MC-1 BBT
MC-1 BBT
i) 250A, TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
ii) 125A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
iii) 100A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
iv) 80A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
v) 63A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
vi) 40A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
vii) 32A TPN MCCB Tap off box. No. 1 MC-1 BBT
MC-1 BBT
5.2.3
MC-1 BBT
MC-1 BBT
a) 1500 Amp with 1600 Amp, TPN, 40 KA, MDO ACB. Nos. R.O. MC-1 BBT
800 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
630 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
400 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
250 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
200 A, TPN+E, 400 Volt, 40 KA, compact, copper Conductor BBT.
The quantity mentioned above is approximate. Bidder to procure /manufacture the items as per actual site measurement & approved Shop drawings.
Design, manufacture, assembly, supply, installation, testing and commissioning of plug-in type TPN tap off box of following capacity on the existing Bus Bar Trunking and complete with TPN MCCBs, links, interconnections, earthing etc. as required, as per specifications and as per approved Shop drawings.
Design, Manufacture, Supply, installation, testing and commissioning of End Feed Box/Bus Bar Trunking Adapter Box, of following ratings with Digital Voltmeter & Ammeter (ELF 3259 of Conzerv or Equivalent) complete with 5VA, class 1.0 CTs of required ratio and one set of phase indication lamps and back-up SPMCBs, as per approved drawing and specifications.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 129
MC-1 BBT
b) 1250 Amp with 1250 Amp, TPN, 40 KA, MDO ACB. Nos. R.O. MC-1 BBT
MC-1 BBT
c) 1200 Amp with 1200 Amp, TPN, 40 KA, MDO ACB. Nos. R.O. MC-1 BBT
MC-1 BBT
d) 1000 Amp with 1000 Amp, TPN, 40 KA, MDO ACB. Nos. R.O. MC-1 BBT
MC-1 BBT
e) 800 Amp with 800 Amp, TPN, 40 KA, MDO ACB. No. 1 MC-1 BBT
MC-1 BBT
f) 630 Amp with 630 Amp, TPN, 40 KA, MCCB. No. 1 MC-1 BBT
g) 400 Amp with 400 Amp, TPN, 40 KA, MCCB. No. 1 MC-1 BBT
MC-1 BBT
h) 250 Amp with 250 Amp, TPN, 40 KA, MCCB. No. 1 MC-1 BBT
MC-1 BBT
MC-1 BBT
5.2.4 MC-1 PANEL
MC-1 PANEL
- MC-1 PANEL
MC-1 PANEL
- MC-1 PANEL
MC-1 PANEL
- MC-1 PANEL
MC-1 PANEL
a) ur Nos. MC-1 PANEL
MC-1 PANEL
b) ur Nos. MC-1 PANEL
MC-1 PANEL
c) ur Nos. MC-1 PANEL
MC-1 PANEL
Notes: MC-1 PANEL
MC-1 PANEL
i) MC-1 PANEL
MC-1 PANEL
Design, Manufacturing, Supply, installation, testing and commissioning of Bus Coupler panels with ACB/MCCB of following ratings for Bus Duct/Bus Bar Trunking System.
The Bus Coupler panel shall consist of 400V, 40 KA@ 1 Sec, 4 pole, Draw out type, Electrically operated, ACB/MCCB complete with under voltage and shunt trip release, antipumping protection, ON/OFF indication lamps etc. as required, as per specifications and approved Shop drawings.
Bus Couper Panel shall be suitable for Termination of Compact Bus Bar Trunking from Top/Bottom as per approved shop drawing.
Bus Coupler Breaker shall have suitable No. of NO/NC contacts for required interlocking with the Breakers of End feed units of Bus Bar Trunking.
Bus Coupler Panel with 1000 Amp, 400V, 40 KA @ 1 Sec, 4 Pole, EDO ACB
Bus Coupler Panel with 800 Amp, 400V, 40 KA @ 1 Sec, 4 Pole, EDO ACB
Bus Coupler Panel with 630 Amp, 400V, 40 KA @ 1 Sec, 4 Pole, Motorised MCCB
The fabrication of bus duct/Bus Bar Trunking shall be taken up only after actual measurement and site routing. Necessary bends/transposition pieces/ expansion joints etc. shall be estimated & included. Payment will be made on running meter basis.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 130
ii) MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
6.000 LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS: MC-1 PANEL
MC-1 PANEL
LV SWITCHGEAR PANELS : MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
Important Notes: Common for all Switchboard: MC-1 PANEL
MC-1 PANEL
1.000 MC-1 PANEL
MC-1 PANEL
2.000 Fault current wherever mentioned shall be Ics value. MC-1 PANEL
MC-1 PANEL
3.000 MC-1 PANEL
MC-1 PANEL
4.000 All feeder doors shall have pad locking arrangement. MC-1 PANEL
MC-1 PANEL
5.000 All TP feeders shall have solid isolable neutral link. MC-1 PANEL
MC-1 PANEL
The supply and fabrication & installation of structural steel for bus duct/Bus Bar Trunking support is included in the above items.
TOTAL OF BUS DUCT/BUS BAR TRUNKING SYSTEM CARRIED OVER TO SUMMARY
Design, manufacture, supply, unloading, receiving, storing, handling, installation, testing and commissioning of following LV panels suitable for 400 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, Copper bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as required and as per specifications and drawings. The panel shall withstand the fault level of as indicated elsewhere or shown in Single Line Diagram (Dwg No. E/SP/ME1 5.S.01.01.REV. B).
The BOQ shall be read inconjunction with general notes, specification and Single Line Diagram (Dwg. No. E/SP/ME1 5.S.01.01.REV B). Incase of any discrepancy between specification, BOQ and SLD, the same shall be brought to the notice of Employer before quoting the rates, otherwise stringent condition shall be deemed to have been considered.
All MCCB shall be provided with door interlocked rotary handle with ON/OFF/Trip position indicator, microprocessor based releases for over current, selectable short circuit and instentaneous short circuit protection (settable at site). I/C MCCB shall be provided with E/F release/ protection also.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 131
6.000 MC-1 PANEL
MC-1 PANEL
7.000 All power contactors including NIC shall be of AC3 duty. MC-1 PANEL
MC-1 PANEL
8.000 MC-1 PANEL
MC-1 PANEL
9.000 MC-1 PANEL
10.000 MC-1 PANEL
MC-1 PANEL
11.000 Capacitor shall be super heavy duty type (MPP technology). MC-1 PANEL
MC-1 PANEL
12.000 MC-1 PANEL
MC-1 PANEL
13.000 MC-1 PANEL
MC-1 PANEL
14.000 MC-1 PANEL
MC-1 PANEL
15.000 All CT, PT shall be epoxy resin cast. MC-1 PANEL
MC-1 PANEL
16.000 All meters are digital type. MC-1 PANEL
MC-1 PANEL
17.000 MC-1 PANEL
MC-1 PANEL
18.000 MC-1 PANEL
MC-1 PANEL
19.000 MC-1 PANEL
MC-1 PANEL
20.000 Bus bar chamber shall be kept at top of the all panels. MC-1 PANEL
MC-1 PANEL
21.000 MC-1 PANEL
MC-1 PANEL
22.000 MC-1 PANEL
All MCCB used in starter feeder shall be suitable for motor duty application.
All ACB's shall be with micro processor based O/C and S/C releases and Breaker Control Switch (BCS) having lost motion device. I/C ACBs shall be provided with E/F release also. Bus coupler shall be provided without releases.
Spare contacts of ACB/Relays/Contactor etc. shall be wired upto terminal block.
All switchgear used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to submit manufacturers type-2 co-ordination chart for the make used.
All outgoing terminals (power and control) shall be brought upto cable alley. 10% extra terminals shall be provided.
10% extra indicating lamp in loose shall be supplied along with panel.
Removable lifting hook shall be provided in all transportation section.
Panel shall be powder coated of approved shade with minimum 60 micron thickness.
ACB's/MCCB's in one particular panel shall be of one similar make.
Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal shall be used in the panel.
All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB,BK as per colour code.
Internal wiring of panel shall be with size 2.5sqmm Flexible Copper Conductor for CT circuit and control wiring with 1.5 sqmm.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 132
MC-1 PANEL
23.000 All indicating light shall be LED type . MC-1 PANEL
MC-1 PANEL
24.000 MC-1 PANEL
MC-1 PANEL
25.000 MC-1 PANEL
MC-1 PANEL
26.000 MC-1 PANEL
MC-1 PANEL
6.100 LV PANEL 1 & 2. MC-1 PANEL
Location: Ground Floor MC-1 PANEL
MC-1 PANEL
LV PANEL 1 & 2 shall Comprise of the following: MC-1 PANEL
MC-1 PANEL
a) Incomings: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
b) MC-1 PANEL
MC-1 PANEL
Each incoming breaker shall be provided with MC-1 PANEL
MC-1 PANEL
i) MC-1 PANEL
MC-1 PANEL
ii) MC-1 PANEL
MC-1 PANEL
iii) MC-1 PANEL
MC-1 PANEL
iv) One set (3 Nos) phase indication lamp with backup SP MCB. MC-1 PANEL
Each vertical section of floor mounted panel shall have independent base frame (75mm x 40mm) size made out of 3 mm sheet steel (LT Panel & DG Panel).
All the makes shall be as per Employer's approved make list only.
Wherever only voltmeter & ammeter are required, the same may be provided in combined meter suitable for both parameter.
Two (2) Nos. 2500 Amps, 400 V, 50kA TPN draw out, Electrically operated ACB, with ON/OFF/TRIP/Trip circuit healthy indication lamp and TNC control switch, under voltage & shunt trip release, anti pumping protection microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD for Transformer Supply Feeder.
One (1) no. 3000 Amps, 400 V, 50KA four pole EDO ACB Bus coupler breaker complete with under voltage and shunt trip release, anti pumping protection, ON/OFF/ indication etc. to be electrically and mechanically interlocked with the incommers so that necessary interlocking can be achieved as per approved SLD.
Metering & indication for Transformer Supply incoming breakers:
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents, Power Factor, Frequency,Power , Energy, harmonics and hours run (EM6400 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 2500/5A,15VA, Class 1.0 as required.
One (1) set of 2500/5 A, C.L 1.0 CTs for input to APFC relay.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 133
MC-1 PANEL
v) MC-1 PANEL
MC-1 PANEL
1.000 WTI Alarm MC-1 PANEL
2.000 WTI Trip MC-1 PANEL
3.000 REF Trip MC-1 PANEL
4.000 HT Breaker Trip MC-1 PANEL
MC-1 PANEL
c) MC-1 PANEL
MC-1 PANEL
Each Transformer breaker to be provided with : MC-1 PANEL
MC-1 PANEL
i) MC-1 PANEL
MC-1 PANEL
ii) MC-1 PANEL
MC-1 PANEL
iii) MC-1 PANEL
MC-1 PANEL
Notes : MC-1 PANEL
MC-1 PANEL
1.000 MC-1 PANEL
MC-1 PANEL
2.000 MC-1 PANEL
MC-1 PANEL
d) BUS BARS: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
e) Outgoing: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
i) Two (2) Nos. 800 A, 50 KA, TPN MDO ACB. MC-1 PANEL
MC-1 PANEL
ii) One (1) No. 630 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
One (1) No. 4 Window Audi/visual annunciator system complete with hooter, Ack, test & reset PBs for annunciation of Alarm and Trip for following :-
Protection Relays for Transformer Supply incoming breakers:
One (1) no. SIPROTEC compact 7SJ80 Multifunction Protection Relay of Siemens make or equivalent.
One(1) set of CTs of ratio 2500/5A with core for protection of 5VA and class 5P10.
One (1) Set, 4 Nos. CTs of ratio 2500/1A, Class PS shall be provided for REF Protection.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
Operation interlocks as per specification & drawings indicating sufficient nos. of potential free contacts for interlocking/ indication annunciation/ control etc shall be provided by the bidder as required.
Two (2) Sets of 3000Amp.,50kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 50 x 6 mm copper.
Some of the outgoing feeders shall be provided with earth leakage relays with CBCT of suitable size as per SLD, (E/SP/ME1 5.S.01.01 Rev. B).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 134
iii) One (1) No. 400 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iv) Two (2) Nos. 200 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
v) Five (5) Nos. 100 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
vi) Five (5) Nos. 63 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
vii) Eight (8) Nos. 40 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
viii) Four (4) Nos. 32 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
i) One (1) No. 800 A, 50 KA, TP MDO ACB. MC-1 PANEL
MC-1 PANEL
ii) One (1) No. 400 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iii) Six (6) Nos. 250 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iv) One (1) No. 200 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
v) Two (2) Nos. 160 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
vi) Six (6) Nos. 125 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
vii) One (1) No. 100 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
viii) Two (2) Nos. 63 A, 50 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
1 Set MC-1 PANEL
MC-1 PANEL
6.200 Capacitor Panels (400 kVAR) MC-1 PANEL
MC-1 PANEL
a) Incoming : MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
b) Metering, Indication and Protection : MC-1 PANEL
MC-1 PANEL
- MC-1 PANEL
MC-1 PANEL
- MC-1 PANEL
MC-1 PANEL
LV Panel 1 & 2 described as above (from a to e) and as per SLD
One (1) No. 800A, 50KA, TPN MDO ACB, incomer with 10 step APFC relay with Auto/Manual selector switch, timer, aux. Contactor, louvers, Exhaust fan etc.
One (1) No. digital multifunction meter for measurement of voltage and currents with selector push buttons and one set of CTs of ratio 800A /5A, CL 1.0, 15 VA.
One (1) set of RYB phase indication lamps with control SP MCB.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 135
c) Busbar : MC-1 PANEL
MC-1 PANEL
- MC-1 PANEL
MC-1 PANEL
d) Outgoings : MC-1 PANEL
- 2 Set MC-1 PANEL
MC-1 PANEL
Notes: MC-1 PANEL
MC-1 PANEL
1.000 MC-1 PANEL
2.000 MC-1 PANEL
MC-1 PANEL
3.000 MC-1 PANEL
MC-1 PANEL
6.300 GENERATOR PANEL MC-1 PANEL
MC-1 PANEL
Generator Panel shall Comprise of the following: MC-1 PANEL
MC-1 PANEL
a) Incomings: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
b) Metering & indication for incoming breakers: MC-1 PANEL
MC-1 PANEL
Incoming breaker shall be provided with MC-1 PANEL
MC-1 PANEL
i) MC-1 PANEL
MC-1 PANEL
ii) MC-1 PANEL
MC-1 PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. MC-1 PANEL
MC-1 PANEL
1000A, TPN+E, Cu. Busbar insulated with heat shrinkable sleeves and shall be color coded. Earth Bus of 50 x 6 mm copper shall be provided.
400 KVAR Capacitor Panel in steps of 6 nos. of 2 x 25 kVAR banks, 4 Nos. of 1 x 25 kVAR banks.
Each capacitor bank should have its individual MCCB & Contactor suitable for capacitor duty including fuses for each capacitor unit as per specifications and approved SLD.
Enclosure of capacitor panel shall be liberally designed to take care of internal heat emission by capacitor unit without forced cooling and to limit the temperature rise with in permissible limit. However, louvers are allowed to facilitate extra cooling.
Enclosure of capacitor panel shall be designed so that detuned reactors can be installed in the same panel for harmonics reduction, in future.
One (1) No. 630 Amps, 400 V, 40kA TPN MCCB, with ON/OFF/TRIP and TNC control switch, under voltage & shunt trip release, microprocessor based O/C, S/C & E/F protection releases etc. complete as required for DG Supply Feeder.
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents, Power Factor, Frequency,Power, Energy, harmonics and hours run (EM6400 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 600/5A,15VA, Class 1.0 as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 136
Note: MC-1 PANEL
MC-1 PANEL
c) BUS BARS: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
d) Outgoing: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
i) One (1) No. 630 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
ii) Two (2) Nos. 100 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iii) Two (2) Nos. 63 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iv) One (1) No. 40 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
v) One (1) No. 32 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
1 Set MC-1 PANEL
6.400 SMDB-EE-ME1.30-C8-TR1.01 MC-1 PANEL
MC-1 PANEL
SMDB shall Comprise of the following: MC-1 PANEL
MC-1 PANEL
a) Incomings: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
b) Metering & indication for incoming breakers: MC-1 PANEL
MC-1 PANEL
Incoming breaker shall be provided with MC-1 PANEL
MC-1 PANEL
i) MC-1 PANEL
MC-1 PANEL
ii) MC-1 PANEL
MC-1 PANEL
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
800Amp., 40kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus Bar of 40 x 6 mm Copper shall be provided.
Each outgoing feeder shall be provided with Earth leakage relay and CBCT of suitable size as per SLD (E/SP/ME1 5.S.01.01, Rev. B)
Generator Panel described as above (from a to d) and as per SLD (E/SP/ME1 5.S.01.01 Rev. B)
One (1) No. 800 Amps, 400 V, 40kA TPN draw out, Electrically operated ACB, with ON/OFF/TRIP/Trip circuit healthy indication lamp and TNC control switch, under voltage & shunt trip release, anti pumping protection microprocessor based O/C, S/C & E/F protection etc. complete as required.
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 800/5A,15VA, Class 1.0 as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 137
iii) One set (3 Nos) phase indication lamp with backup SP MCB. MC-1 PANEL
MC-1 PANEL
Note: MC-1 PANEL
MC-1 PANEL
c) BUS BARS: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
d) Outgoing: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
i) Twelve (12) Nos. 100 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
ii) One (1) No. 80 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iii) Six (6) Nos. 63 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iv) Two (2) Nos. 40 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
v) Five (5) Nos. 32 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
vi) Three (3) Nos. 16 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
1 Set MC-1 PANEL
MC-1 PANEL
6.500 SMDB-EE-ME1-OM-C4-TR1.01 MC-1 PANEL
MC-1 PANEL
SMDB shall Comprise of the following: MC-1 PANEL
MC-1 PANEL
a) Incomings: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
b) Metering & indication for incoming breakers: MC-1 PANEL
MC-1 PANEL
Incoming breaker shall be provided with MC-1 PANEL
MC-1 PANEL
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
1000Amp., 40kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 40 x 6 mm copper.
Some of the outgoing feeders shall be provided with Earth leakage relay with CBCT of suitable size as per SLD (E/SP/ME1 5.S.01.01, Rev. B).
SMDB-EE-ME1.30-C8-TR1.01 described as above (from a to d) and as per SLD
One (1) No. 400 Amps, 400 V, 40kA TPN MCCB, with ON/OFF/TRIP indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD (E/SP/ME1 5.S.01.01 Rev. B).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 138
i) MC-1 PANEL
MC-1 PANEL
ii) MC-1 PANEL
MC-1 PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. MC-1 PANEL
MC-1 PANEL
Note: MC-1 PANEL
MC-1 PANEL
c) BUS BARS: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
d) Outgoing: MC-1 PANEL
MC-1 PANEL
i) Three (3) Nos. 100 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
ii) Two (2) Nos. 63 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iii) Two (2) Nos. 40 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
iv) Four (4) Nos. 16 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
1 Set MC-1 PANEL
MC-1 PANEL
6.600 SMDB-EE-ME1.O1-E1-TR1.01 MC-1 PANEL
MC-1 PANEL
SMDB shall Comprise of the following: MC-1 PANEL
MC-1 PANEL
a) Incomings: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
b) Metering & indication for incoming breaker: MC-1 PANEL
MC-1 PANEL
Incoming breaker shall be provided with MC-1 PANEL
MC-1 PANEL
i) MC-1 PANEL
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
One (1) set 3 Nos. CTs of ratio 400/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
500Amp., 40kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 40 x 6 mm copper.
SMDB-EE-ME1,OM-C4-TR1.01 described as above (from a to d) and as per SLD
One (1) No. 630Amps, 400 V, 40kA TPN MCCB, with ON/OFF/TRIP/ indication lamp and TNC control switch, under voltage & shunt trip release with microprocessor based O/C, S/C & E/F protection etc. complete as required and as per SLD (E/SP/ME1 5.S.01.01, Rev. B).
One (1) No. Digital Multifunction meter with RS-485 port suitable for measurement of voltage, currents and Frequency (ELF 3259 of 'Conzerv' make or equivalent).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 139
MC-1 PANEL
ii) MC-1 PANEL
MC-1 PANEL
iii) One set (3 Nos) phase indication lamp with backup SP MCB. MC-1 PANEL
MC-1 PANEL
Note: MC-1 PANEL
MC-1 PANEL
c) BUS BARS: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
d) Outgoing: MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
i) Three (3) Nos. 250 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
ii) Two (2) Nos. 32 A, 40 KA, TPN MCCB. MC-1 PANEL
MC-1 PANEL
1 Set MC-1 PANEL
MC-1 PANEL
6.700 FINAL DISTRIBUTION BOARDS MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
MC-1 PANEL
6.7.1 DB-EE-ME1.00-E2-TR1.01 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
One (1) set 3 Nos. CTs of ratio 600/5A,15VA, Class 1.0 as required.
Sufficient No. of contacts terminals shall be provided in the panel as required for necessary remote operation and indications etc.
800Amp., 40kA, TPN+E, Copper Bus bar with colour coded, heat shrinkable sleeves (with 100% neutral). Earth Bus shall be of 40 x 6 copper.
Each outgoing feeder shall be provided with earth leakage relay with CBCT of suitable size as per SLD (E/SP/ME1 5.S.01.01, Rev. B).
SMDB-EE-ME1.01-E1-TR1.01 described as above (from a to e) and as per SLD
Design, manufacture, supply, installation (recessed/ surface), testing and commissioning of following switch fuse Unit/ MCCB/MCB type distribution boards as per drawings & specifications. The surface distribution boards shall be mounted on 50 x 50 x 6 MS angle frame work grounted to floor/ walls. The rate includes the angle iron frame, support, painting, numbering, earthing etc as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 140
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 16A 3 Phase RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 10A SP MCB. MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Three (3) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- One (1) no. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
Section-3 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
- Two (2) nos. 20A, TP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
MC-1 PANEL
6.7.2 DB-EE-ME1.00-D1TR1.02 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 63A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 32A, 3 Phase RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) Nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 40A, 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.00-E2-TR1.01 as described above and as per DB chart
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 141
- Two (2) nos. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
MC-1 PANEL
6.7.3 ME1.00-E2-TR1.03 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty Seven (27) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- ME1.00-E2-TR1.03 as described above and as per DB chart 1 Set MC-1 PANEL
MC-1 PANEL
6.7.4 DB-EE-ME1.00-E2-TR1.04 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 40A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Eighteen (18) nos. 10A, SP MCB. MC-1 PANEL
DB-EE-ME1.00-D1TR1.02 as described above and as per DB chart.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 142
MC-1 PANEL
- 1 Set MC-1 PANEL
MC-1 PANEL
6.7.5 DB-EE-ME1.00-D2-TR1.05 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty Seven (27) no. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
MC-1 PANEL
6.7.6 DB-EE-ME1.00-D2-TR1.06 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 40A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Eighteen (18) nos. 10A, SP MCB. MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.00-E2-TR1.04 as described above and as per DB chart
DB-EE-ME1.00-D2-TR1.05 as described above and as per DB chart
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 143
- 1 Set MC-1 PANEL
6.7.7 DB-EE-ME1.00-B2-TR1.07 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty Seven (27) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
MC-1 PANEL
6.7.8 DB-EE-ME1.00-B2-TR1.08 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
- 40A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Eighteen (18) nos. 10A, SP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
MC-1 PANEL
6.7.9 DB-EE-ME1.00-E4-TR1.09 MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.00-D2-TR1.06 as described above and as per DB chart
DB-EE-ME1.00-B2-TR1.07 as described above and as per DB chart
DB-EE-ME1.00-B2-TR1.08 as described above and as per DB chart
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 144
Incomer: MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Twelve (12) nos. 10A, SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
- One (1) no. 63A, 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Thirty (30) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
6.7.10 DB-EE-ME1.00-D4-TR1.10 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 40A 3 Phase RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Twenty Seven (27) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Seventeen (17) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- One (1) no. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
Section-3 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
DB-EE-ME1.00-E4-TR1.09 as described above and as per DB chart
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 145
MC-1 PANEL
- Fourteen (14) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- One (1) no. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
MC-1 PANEL
6.7.11 DB-EE-ME1.0M-E2-TR1.01 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 63A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 16A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Nine (9) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 40A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- Two (2) nos. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
6.7.12 DB-EE-ME1.10-D3-TR1.01 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
- 40A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Nine (9) nos. 10A SP MCB. MC-1 PANEL
DB-EE-ME1.00-D4-TR1.10 as described above and as per DB chart
DB-EE-ME1.0M-E2-TR1.01 as described above and as per DB chart
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 146
MC-1 PANEL
Section-2 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twelve (12) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
MC-1 PANEL
6.7.13 DB-EE-ME1.10-D3-TR1.02 MC-1 PANEL
Incomer: MC-1 PANEL
- 40A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
MC-1 PANEL
6.7.14 DB-EE-ME1.20-C4-TR2.01 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
- 63A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC-1 PANEL
- Twenty One (21) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
- One (1) no. 40A 3 Phase RCD (30 mA). MC-1 PANEL
- Fifteen (15) nos. 20A SP MCB. MC-1 PANEL
Section-3 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC-1 PANEL
- Twelve (12) nos. 10A SP MCB. MC-1 PANEL
Section-4 MC-1 PANEL
- One (1) no. 32A 3 Phase RCD (100 mA). MC-1 PANEL
- Six (6) nos. 20A SP MCB. MC-1 PANEL
- 1 Set MC-1 PANEL
6.7.16 DB-EE-ME1.20-C5-TR2.02 MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.10-D3-TR1.01 as described above and as per DB chart
DB-EE-ME1.10-D3-TR1.02 as described above and as per DB chart
DB-EE-ME1.20-C4-TR2.01 as described above and as per DB chart
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 147
Incomer: MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 16A 3 Phase RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A 3 Phase RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- One (1) no. 20A TP MCB. MC-1 PANEL
MC-1 PANEL
Section-3 MC-1 PANEL
MC-1 PANEL
- One (1) no. 63A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Nine (9) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
- One (1) no. 20A, TP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
MC-1 PANEL
6.7.17 DB-EE-ME1.20-C8-TR2.03 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
- 100A TP MCB Isolator. MC-1 PANEL
Busbar : MC-1 PANEL
- 150A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
- One (1) no. 16A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Twenty One (21) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
- One (1) no. 40A, 3 Phase, RCD (30 mA). MC-1 PANEL
DB-EE-ME1.20-C5-TR2.02 as described above and as per DB chart
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 148
MC-1 PANEL
- Nine (9) nos. 20A, SP MCB. MC-1 PANEL
MC-1 PANEL
Section-3 MC-1 PANEL
- One (1) no. 40A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Twelve (12) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-4 MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Twelve (12) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-5 MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Six (6) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
6.7.18 DB-EE-ME1.30-C8-TR2.01 MC-1 PANEL
MC-1 PANEL
Incomer: MC-1 PANEL
MC-1 PANEL
- 63A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
MC-1 PANEL
- 100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
MC-1 PANEL
- One (1) no. 32A, 3 Phase, RCD (100 mA). MC-1 PANEL
MC-1 PANEL
- Nine (9) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
MC-1 PANEL
- One (1) no. 40A, 3 Phase, RCD (30 mA). MC-1 PANEL
MC-1 PANEL
- Fifteen (15) nos. 20A SP MCB. MC-1 PANEL
MC-1 PANEL
- 1 Set MC-1 PANEL
MC-1 PANEL
6.7.19 DB-EE-ME1.01-F1-TR1.01 MC-1 PANEL
MC-1 PANEL
DB-EE-ME1.20-C8-TR2.03 as described above and as per DB chart
DB-EE-ME1.30-C8-TR2.01 as described above and as per DB chart
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 149
Incomer: MC-1 PANEL
- 63A TP MCB Isolator. MC-1 PANEL
MC-1 PANEL
Busbar : MC-1 PANEL
100A 4P Cu. busbar MC-1 PANEL
MC-1 PANEL
Outgoing – (10KA) comprising MC-1 PANEL
MC-1 PANEL
Section-1 MC-1 PANEL
- MC-1 PANEL
One (1) no. 16A, 3 Phase, RCD (100 mA). MC-1 PANEL
- MC-1 PANEL
Six (6) nos. 10A SP MCB. MC-1 PANEL
MC-1 PANEL
Section-2 MC-1 PANEL
- MC-1 PANEL
One (1) no. 40A, 3 Phase, RCD (30 mA). MC-1 PANEL
- MC-1 PANEL
Six (6) nos. 20A SP MCB. MC-1 PANEL
- MC-1 PANEL
1 Set MC-1 PANEL
MC-1 PANEL
6.800 MC-1 PANEL
MC-1 PANEL
a) 630 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
b) 250 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
c) 200 Amp, 4 pole, 400V, 40 KA @ 1 Sec. ur Nos. MC-1 PANEL
d) 100 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
e) 63 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
f) 40 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
g) 32 Amp, 4 pole, 400V, 40 KA @ 1 Sec. 1 No. MC-1 PANEL
MC-1 PANEL
7.00 CABLES, SUB MAINS & CABLE TRAYS : MC-1 CAB
MC-1 CAB
7.10 Cables in Under Ground Installations : MC-1 CAB
MC-1 CAB
MC-1 CAB
MC-1 CAB
DB-EE-ME1.01-F1-TR1.01 as described above and as per DB chart
Design, Manufacturing, Supply, installation, Testing and Commissioning of Auto Transfer Switch Panel (ATS Panels) of following ratings as per specifications, SLD and approved Shop drawing :-
TOTAL OF LV SWITCHGEAR PANELS & DISTRIBUTION BOARDS CARRIED OVER TO SUMMARY
Supply, installation, testing and commissioning of following sizes of PVC sheathed, XLPE insulated copper conductor power/multicore control, armoured, Multi-strand cable of 1.1 KV grade in ground including digging the trench, laying the cable with sand and brick covering, back filling reaming etc as required, as per specfications and as per directions of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 150
7.1.1 MC-1 CAB
MC-1 CAB
a) 4 core 400 Sqmm 10 RM MC-1 CAB
b) 4 core 300 Sqmm 10 RM MC-1 CAB
c) 4 core 240 Sqmm 10 RM MC-1 CAB
d) 4 core 185 sqmm 10 RM MC-1 CAB
e) 4 core 150 sqmm 100 RM MC-1 CAB
f) 4 core 120 sqmm 10 RM MC-1 CAB
g) 4 core 95 sqmm 50 RM MC-1 CAB
h) 4 core 70 sqmm 100 RM MC-1 CAB
i) 4 core 50 sqmm 100 RM MC-1 CAB
j) 4 core 35 sqmm 500 RM MC-1 CAB
k) 4 core 25 sqmm 500 RM MC-1 CAB
l) 4 core 16 sqmm 100 RM MC-1 CAB
m) 4 core 10 sqmm 10 RM MC-1 CAB
n) 4 core 6 sqmm 10 RM MC-1 CAB
o) 4 core 4 sqmm 10 RM MC-1 CAB
p) 3 core 25 sqmm 10 RM MC-1 CAB
q) 3 core 16 sqmm 10 RM MC-1 CAB
r) 3 core 10 sqmm 10 RM MC-1 CAB
s) 3 core 6 sqmm 10 RM MC-1 CAB
t) 3 core 4 sqmm 10 RM MC-1 CAB
u) 2 core 6 sqmm 10 RM MC-1 CAB
v) 2 core 4 sqmm 10 RM MC-1 CAB
MC-1 CAB
7.20 Cables on Racks / Pipes / Ducts / Wireways/Cable Trays : MC-1 CAB
MC-1 CAB
MC-1 CAB
MC-1 CAB
7.2.1 Copper Conductor Armoured Cables : MC-1 CAB
MC-1 CAB
a) 4 core 400 Sqmm 100 RM MC-1 CAB
b) 4 core 300 Sqmm 400 RM MC-1 CAB
c) 4 core 240 Sqmm 300 RM MC-1 CAB
d) 4 core 185 sqmm 150 RM MC-1 CAB
e) 4 core 150 sqmm 300 RM MC-1 CAB
f) 4 core 120 sqmm 1700 RM MC-1 CAB
g) 4 core 95 sqmm 10 RM MC-1 CAB
h) 4 core 70 sqmm 10 RM MC-1 CAB
i) 4 core 50 sqmm 1500 RM MC-1 CAB
j) 4 core 35 sqmm 200 RM MC-1 CAB
k) 4 core 25 sqmm 700 RM MC-1 CAB
Copper Conductor, Armoured XLPE Cables (PVC/SWA/XLPE) :
Supply, installation, testing and commissioning of following sizes of PVC sheathed, XLPE insulated, copper conductor, power/multicore, control, armoured, Multi-stranded cable of 1.1 KV grade on surface of wall or in existing cable tray /masonary ducts/hume pipe with fixing hardware etc as required, as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 151
l) 4 core 16 sqmm 600 RM MC-1 CAB
m) 4 core 10 sqmm 700 RM MC-1 CAB
n) 4 core 6 sqmm 1500 RM MC-1 CAB
o) 4 core 4 sqmm 1200 RM MC-1 CAB
p) 3 core 25 sqmm 10 RM MC-1 CAB
q) 3 core 16 sqmm 10 RM MC-1 CAB
r) 3 core 10 sqmm 10 RM MC-1 CAB
s) 3 core 6 sqmm 10 RM MC-1 CAB
t) 3 core 4 sqmm 1700 RM MC-1 CAB
u) 2 core 6 sqmm 300 RM MC-1 CAB
v) 2 core 4 sqmm 10 RM MC-1 CAB
MC-1 CAB
7.2.2 Copper Conductor Armoured Control Cables : MC-1 CAB
MC-1 CAB
a) 14 C 1.5 Sqmm PVC cable 50 RM MC-1 CAB
b) 10 C 1.5 Sqmm PVC cable 50 RM MC-1 CAB
c) 9 C 1.5 Sqmm PVC cable 100 RM MC-1 CAB
d) 7 C 1.5 Sqmm PVC cable 200 RM MC-1 CAB
e) 5 C 1.5 Sqmm PVC cable 200 RM MC-1 CAB
f) 3 C 1.5 Sqmm PVC cable 200 RM MC-1 CAB
MC-1 CAB
7.30 Cable Termination : MC-1 TERM
MC-1 TERM
MC-1 TERM
MC-1 TERM
7.3.1 Copper conductor armoured cables : MC-1 TERM
MC-1 TERM
a) 4 core 400 Sqmm 2 Nos. MC-1 TERM
b) 4 core 300 Sqmm 8 Nos. MC-1 TERM
c) 4 core 240 Sqmm 4 Nos. MC-1 TERM
d) 4 core 185 sqmm 12 Nos. MC-1 TERM
e) 4 core 150 sqmm 20 Nos. MC-1 TERM
f) 4 core 120 sqmm 20 Nos. MC-1 TERM
g) 4 core 95 sqmm 2 Nos. MC-1 TERM
h) 4 core 70 sqmm 2 Nos. MC-1 TERM
i) 4 core 50 sqmm 16 Nos. MC-1 TERM
j) 4 core 35 sqmm 10 Nos. MC-1 TERM
k) 4 core 25 sqmm 42 Nos. MC-1 TERM
l) 4 core 16 sqmm 30 Nos. MC-1 TERM
m) 4 core 10 sqmm 26 Nos. MC-1 TERM
n) 4 core 6 sqmm 44 Nos. MC-1 TERM
o) 4 core 4 sqmm 100 Nos. MC-1 TERM
p) 3 core 25 sqmm 2 Nos. MC-1 TERM
Supply and making end termination with brass double compression glands for the following XLPE insulated PVC sheathed, 1100 V grade, Multi-strand copper conductor cable including cost of crimping lugs/ferrules, double compression glands, solder, cable sockets, insulation tap etc complete as required, as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 152
q) 3 core 16 sqmm 2 Nos. MC-1 TERM
r) 3 core 10 sqmm 2 Nos. MC-1 TERM
s) 3 core 6 sqmm 2 Nos. MC-1 TERM
t) 3 core 4 sqmm 114 Nos. MC-1 TERM
u) 2 core 6 sqmm 2 Nos. MC-1 TERM
v) 2 core 4 sqmm 2 Nos. MC-1 TERM
MC-1 TERM
7.3.2 Copper Conductor PVC Insulated Armoured Control Cables : MC-1 TERM
MC-1 TERM
MC-1 TERM
a) 14 C x 1.5 Sqmm 2 Nos. MC-1 TERM
b) 10 C x 1.5 Sqmm 2 Nos. MC-1 TERM
c) 9 C x 1.5 Sqmm 2 Nos. MC-1 TERM
d) 7 C x 1.5 Sqmm 4 Nos. MC-1 TERM
e) 5 C x 1.5 Sqmm 4 Nos. MC-1 TERM
f) 3 C x 1.5 Sqmm 2 Nos. MC-1 TERM
MC-1 TERM
Notes : MC-1 TERM
MC-1 TERM
7.40 MC-1 cab
MC-1 cab
a) 4 C x 185 Sqm, CWZ Cable 150 RM MC-1 cab
b) 4 C x 150 Sqm, CWZ Cable 10 RM MC-1 cab
c) 4 C x 120 Sqm, CWZ Cable 10 RM MC-1 cab
d) 4 C x 95 Sqm, CWZ Cable 10 RM MC-1 cab
e) 4 C x 70 Sqm, CWZ Cable 10 RM MC-1 cab
f) 4 C x 50 Sqm, CWZ Cable 10 RM MC-1 cab
g) 4 C x 35 Sqm, CWZ Cable 10 RM MC-1 cab
h) 4 C x 25 Sqm, CWZ Cable 400 RM MC-1 cab
i) 4 C x 16 Sqm, CWZ Cable 250 RM MC-1 cab
j) 4 C x 10 Sqm, CWZ Cable 200 RM MC-1 cab
k) 4 C x 6 Sqm, CWZ Cable 10 RM MC-1 cab
l) 4 C x 4 Sqm, CWZ Cable 10 RM MC-1 cab
m) 4 C x 2.5 Sqm, CWZ Cable 10 RM MC-1 cab
MC-1 cab
7.50 Cable Trays : MC-1 tray
MC-1 tray
(Single Compression Glands suitable for following armoured cables)
The cable quantities given are approximate and to cover various sizes. The contractor shall measure the cables required and procurement order shall be placed accordingly. The quantities shall be confirmed before start of work.
Supply, installation, testing and commissioning of 1.1 KV grade, Multicore, copper conductor, LSZH outer sheathed, CWZ fire resistant cable (in compliance with BS : 6387) of following sizes on surfae of wall/existing cable trays/Mesonary Hume pipe/Duct/Trenches etc., with fixing hardware etc. as required as per specifications and as per direction of Engineer-in-charge.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 153
MC-1 tray
MC-1 tray
Notes : MC-1 tray
MC-1 tray
7.5.1 Ladder Type Cable tray : MC-1 tray
MC-1 tray
a) 900 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
b) 750 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
c) 600 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
d) 450 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
e) 300 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
f) 225 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
g) 100 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
MC-1 tray
7.5.2 Perforated Type Cable Tray : MC-1 tray
MC-1 tray
a) 750 mm x 75 mm x 2.0 mm 10 RM MC-1 tray
b) 600 mm x 75 mm x 2.0 mm 50 RM MC-1 tray
c) 500 mm x 75 mm x 2.0 mm 300 RM MC-1 tray
d) 400 mm x 75 mm x 2.0 mm 100 RM MC-1 tray
e) 300 mm x 50 mm x 2.0 mm 300 RM MC-1 tray
f) 250 mm x 50 mm x 2.0 mm 100 RM MC-1 tray
g) 200 mm x 75 mm x 2.0 mm 200 RM MC-1 tray
h) 150 mm x 75 mm x 2.0 mm 500 RM MC-1 tray
i) 100 mm x 75 mm x 2.0 mm 150 RM MC-1 tray
MC-1 tray
7.5.3 Fibreglass Ladder Type Cable Tray : MC-1 tray
MC-1 tray
MC-1 tray
a) 600 mm wide 10 RM MC-1 tray
b) 450 mm wide 10 RM MC-1 tray
c) 300 mm wide 10 RM MC-1 tray
d) 225 mm wide 10 RM MC-1 tray
e) 100 mm wide 10 RM MC-1 tray
MC-1 tray
Supply and installation of ladder type/perforated type cable trays of the following sizes fabricated out of perforated hot dip galvanised MS sheets of minimum 2.0 mm thick to be installed horizontally or vertically. The cable tray shall be complete including cost of supporting Steel/Hangers, bends, elbows, cross, tees, reducers etc as per drawings/site condition and rate shall include cost of anchor fasteners, screws, nuts, bolts and misc. other fixing hardware etc as required, as per specifications and approved Shop drawings.
The cable tray shall be factory built. Bidder shall include in his price, required numbers of Tees, Crosses, Bends, Elbows etc as required as per actual site conditions. Bidder may refer to the drawings for estimation purpose.
Supply & Installation of Ladder type Cable tray of following sizes. The Cable Tray shall be complete including the cost of Anchor fasteners, Hardware, supporting structure etc. as required and as per specifications and approved drawing :
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 154
7.60 Misc. Works Relating to Cabling: MC-1 pipe
MC-1 pipe
7.6.1 GI Pipe Installation : MC-1 pipe
MC-1 pipe
MC-1 pipe
MC-1 pipe
a) 25 mm dia 10 RM MC-1 pipe
b) 32 mm dia 10 RM MC-1 pipe
c) 40 mm dia 10 RM MC-1 pipe
d) 50 mm dia 10 RM MC-1 pipe
e) 80 mm dia 10 RM MC-1 pipe
f) 100 mm dia 10 RM MC-1 pipe
g) 150 mm dia 10 RM MC-1 pipe
MC-1 pipe
7.6.2 Flexible Conduits Installation : MC-1 pw
MC-1 pw
MC-1 pw
7.6.2.1 GI flexible conduits : MC-1 pw
MC-1 pw
a) 20 mm dia 200 RM MC-1 pw
b) 25 mm dia 100 RM MC-1 pw
c) 40 mm dia 100 RM MC-1 pw
d) 50 mm dia 100 RM MC-1 pw
MC-1 pw
8.00 WIRING : MC-1 pw
MC-1 pw
8.10 Point Wiring : MC-1 pw
MC-1 pw
The rates for point wiring shall include the circuit wiring. MC-1 pw
MC-1 pw
MC-1 pw
MC-1 pw
MC-1 pw
MC-1 pw
Supply and installation of following sizes of `A' class GI pipe for cable sleeves in recess/ on surface/Ground complete with all accessories pull boxes where ever required, G.I. fish wire, fixing hardware etc. including the chasing of wall/floor, and plastering the chased portion, digging the trench and back filling, making good the damages, sealing of pipe entry etc as required.
Supply and installation of following sizes of GI flexible conduits with all accessories including fixing nipples, couplings and fixing hardware etc as required and as per specifications.
TOTAL OF CABLES, SUB MAINS, CABLE TRAYS CARRIED OVER TO SUMMARY
Circuit wiring means the wiring from DB / Dimmer panel to the first point of circuit through control switch.
Circuit wiring and subsequent looping shall be done with 2.5 Sqmm, 1100V grade LSZH insulated stranded, copper wires.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 155
MC-1 pw
MC-1 pw
MC-1 pw
MC-1 pw
MC-1 pw
MC-1 pw
8.1.1 Light Points controlled by switch : MC-1 pw
MC-1 pw
a) Single/ First light point con-trolled by a 5Amps switch. 52 Nos. MC-1 pw
MC-1 pw
b) Same as above but loop point 172 Nos. MC-1 pw
MC-1 pw
8.1.2 Light Points controlled directly from DB . MC-1 pw
MC-1 pw
i. Single/ First Point Controlled directly by MCB in DB 108 Nos. MC-1 pw
MC-1 pw
ii. Same as above but loop point. 699 Nos. MC-1 pw
MC-1 pw
8.1.3 Two way points : MC-1 pw
MC-1 pw
a) Light points controlled by 2 Nos 2 way switch. MC-1 pw
MC-1 pw
i) 2 Nos. MC-1 pw
MC-1 pw
ii) Same as above but loop point. 11 Nos. MC-1 pw
MC-1 pw
8.1.4 Presence Sensor : MC-1 pw
MC-1 pw
a) 25 Nos. MC-1 pw
MC-1 pw
8.1.5 6A Socket Points : MC-1 pw
MC-1 pw
The rates of point wiring shall include supply, installation, testing & commissioning of MS conduit with accessories, GI Boxes and required GI flexible conduits with accessories up to the Point, LSZH insulated, stranded, Cu. Wire, switches and sockets (as approved by Engineer-in-charge) etc. as required and as per specification and direction of Engineer-in-charge.
Where the light points are directly controlled from DB (without any local control switches), the quoted rates shall not include the cost of MCBs etc. in the point wiring.
The rates of point wiring shall include earthing of each light, fan, switches, switch plates, boxes and other non current carrying metallic part with 2.5Sqm. Stranded copper, LSZH insulated, stranded, copper wire.
One / first light point controlled by two nos. two way 5 Amps. switch.
Wiring from Presence Sensor to the DB/SwitchBoard/Light fixtures, including providing Presence Sensor as required and as per approved shop drawing (wiring from DB to light points has already been included in subheads 1.1,1.2,1.3 above and not to be considered here).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 156
a) 40 Point MC-1 pw
8.20 Power Socket Wiring : MC-1 pw
MC-1 pw
MC-1 pw
MC-1 pw
8.2.1 11 Point MC-1 pw
MC-1 pw
8.2.2 15 Point MC-1 pw
MC-1 pw
8.2.3 7 Point MC-1 pw
MC-1 pw
8.2.4 9 Point MC-1 pw
MC-1 pw
Wiring for 6A, BS, switched socket outlet including providing 6A, BS, switched, socket outlet as per specification and approved shop drawing.
Power Socket Wiring shall include supply, installation, testing and commissioning of wiring of following points, including, providing conduits of suitable size, its accessories/Hardware, Junction Boxes, LSZH wires, termination of wires, switches, socket outlets, Plug tops etc. as required, as per specification and as approved by Engineer-in-charge.
Wiring for 1 No. BS, 16A, switched socket outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos.BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 3 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 3 Nos.BS outlet 16A switched with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 4 Nos. BS, 16A, switched outlet with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 4 Nos.BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 157
8.2.5 1 Point MC-1 pw
MC-1 pw
8.2.6 10 Point MC-1 pw
MC-1 pw
8.2.7 1 Point MC-1 pw
MC-1 pw
8.2.8 40 Point MC-1 pw
MC-1 pw
8.2.9 4 Point MC-1 pw
MC-1 pw
Wiring for 1 No. BS, 16A, switched outlet in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. BS, 16A, switched outlet in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos. BS, 16A, switched outlet in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. BS, 16A, switched outlet & 1 No. BS 16A switched outlet in IP-65 enclosure with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet & 1 No. IP-65 BS, 16A, switched outlet with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. BS, 16A, switched outlet (Spur Outlet) with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 16A, switched outlet (Spur Outlet) with internal wiring in G.I. box, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 1 No. BS, 32A, switched outlet in IP-65 enclosure for Water Heater with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. BS, 32A, switched outlet in IP-65 enclosure with internal wiring, earthing of 3rd pin with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 158
8.2.10 3 Point MC-1 pw
MC-1 pw
8.2.11 2 Point MC-1 pw
MC-1 pw
8.2.12 2 Point MC-1 pw
MC-1 pw
8.2.13 120 Point MC-1 pw
MC-1 pw
8.30 CEE INDUSTRIAL SWITCHED SOCKETS MC-1 pw
MC-1 pw
Wiring for 1 No. Disabled Alarm Device with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 1 No. Disabled Alarm Device (As approved by the Engineer-in-charge) with internal wiring in G.I. box, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 2 Nos. Power & Data Pillar, each consisting of 2 Nos. 6A BS socket, 1 No. 15A Switch and 1 No. RJ-45 Data Outlets in IP-65 enclosure, with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 2 Nos. Power & Data Pillar, each consisting of 2 Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45 Data Outlets in IP-65 enclosure, with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required and as per approved shop drawing.
Wiring for 3 Nos. Power & Data Pillar, each consisting of 2 Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45 Data outlet in IP-65 enclosure, with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 3 Nos. Power & Data Pillar, each consisting of 2 Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45 Data outlet in IP-65 enclosure, with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required.
Wiring for 4 Nos. Power & Data Pillar, each consisting of 2 Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45 Data outlets in IP-65 enclosure, with 4 Sqmm LSZH insulated stranded copper conductor wires in recessed/surface black enameled MS conduit including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing of 4 Nos. Power & Data Pillar, each consisting of 2 Nos. 6A BS socket with 1 No. 15A Switch and 1 No. RJ-45 Data outlets in IP-65 enclosure, with internal wiring, earthing with LSZH insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 159
8.3.1 MC-1 pw
MC-1 pw
a) 16A, 2P+E, CEE, switched socket outlet with plug top (IP-44) 47 Nos. MC-1 pw
b) 15 Nos. MC-1 pw
c) 4 Nos. MC-1 pw
MC-1 pw
8.3.2 MC-1 pw
MC-1 pw
a) 16A BS switched socket outlet. 12 Nos. MC-1 pw
MC-1 pw
b) 15 Nos. MC-1 pw
MC-1 pw
8.3.3 MC-1 pw
MC-1 pw
- MC-1 pw
MC-1 pw
- MC-1 pw
MC-1 pw
- 7 Nos. MC-1 pw
MC-1 pw
8.40 ISOLATORS MC-1 pw
MC-1 db
MC-1 db
MC-1 db
a) 16A Four pole isolator 7 Nos. MC-1 db
MC-1 db
b) 32A Four pole isolator 6 Nos. MC-1 db
MC-1 db
c) 63A Four pole isolator 2 Nos. MC-1 db
Supply, installation, testing and commissioning of single phase/three phase, CEE, switched, industrial type plug and socket outlet in IP-65 enclosure including termination, earthing etc. in surface/recessed mounting as required, as per specifications and approved shop drawings (Cabling/Conduiting & wiring shall be paid separately under different items).
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-44)
16A, 3P+N+E, CEE, switched socket outlet with plug top (IP-65) for water heaters.
Supply, installation, testing and commissioning of following BS switched socket outlets including termination, earthing etc. in surface/recessed mounting as required. (Cabling/conduiting & wiring shall be paid seperately under different item).
16A weatherproof BS switched socket outlet in IP-65 enclosure.
Supply, installation, testing and commissioning of following Single Phase/3 phase, CEE, switched, Industrial type Plug and socket Combination Outlet in single enclosure (IP-65) consisting of including termination, Earthing etc. in surface/recess mounting as required. (Conduiting/wiring/cabling for the same shall be paid seperately under different item).
16A, 3P+N+E, CEE, switched socket outlets with plug (IP-44) with 16A TPN MCB,10kA.
32A, 3P+N+E, CEE, switched socket outlets with plug (IP-44) with 32A TPN MCB,10kA.
63A, 3P+N+E, CEE, switched socket outlets with plug (IP-44) with 63A TPN MCB,10kA.
Supply, installation, testing and commissioning of isolators in IP-65 enclosures complete with termination in surface/recessed mounting as required.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 160
MC-1 db
d) 100A Four pole isolator 2 Nos. MC-1 db
MC-1 db
e) 200A Four pole isolator 1 No. MC-1 db
MC-1 db
f) 250A Four pole isolator 2 Nos. MC-1 db
MC-1 db
8.50 M.S. Black Conduits : MC-1 pw
MC-1 pw
. MC-1 pw
MC-1 pw
a) 20 mm dia 20 RM MC-1 pw
b) 25 mm dia 20 RM MC-1 pw
c) 32 mm dia 20 RM MC-1 pw
d) 40 mm dia 20 RM MC-1 pw
e) 50 mm dia 20 RM MC-1 pw
8.60 Sub-mains Wiring : MC-1 pw
MC-1 pw
MC-1 pw
MC-1 pw
a) 2 x 1.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC-1 pw
b) 2 x 2.5 Sqmm + 1 No. 1.5 Sqmm Copper earth wire 20 RM MC-1 pw
c) 2 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire. 20 RM MC-1 pw
d) 2 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC-1 pw
e) 4 x 4.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC-1 pw
f) 4 x 6.0 Sqmm + 1 No. 2.5 Sqmm Copper earth wire 20 RM MC-1 pw
g) 2 x 10.0 Sqmm + 1 No. 6.0 Sqmm Copper earth wire 20 RM MC-1 pw
h) 4 x 10.0 Sqmm + 2 Nos. 6.0 Sqmm Copper earth wire 20 RM MC-1 pw
i) 4 x 16.0 Sqmm + 2 Nos. 10.0 Sqmm Copper earth wire 20 RM MC-1 pw
j) 4 x 25.0 Sqmm + 2 Nos. 16.0 Sqmm Copper earth wire 20 RM MC-1 pw
MC-1 pw
Note: MC-1 pw
MC-1 pw
1) MC-1 pw
MC-1 pw
2) MC-1 pw
MC-1 pw
TOTAL OF WIRING CARRIED OVER TO SUMMARY MC-1 pw
9.00 LIGHTING FIXTURES : MC-1 light
Supply and installation of following size of MS conduit pipe in recess or on surface including all accessories MS/CI pull/junction boxes, GI fish wire, fixing hardware etc including chasing the walls/floor and plastering the chased portion and making good the damages etc, complete as required and as per specifications.
Supply and drawing of following sizes of LSZH insulated, stranded, copper conductor wires of 650/1100 Volts grade in existing conduit pipe /wire ways including connection /terminations etc as required.
In false ceiling areas the work is to be co-ordinated with respect to interior work and rate for point wiring shall include flexible conduit/fixing nipples/couplers etc from the junction box up to the fitting.
All wires used for circuit / point wiring shall be Low Smoke Zero Halogen (LSZH) wires.
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 161
MC-1 light
MC-1 light
MC-1 light
i) 21 Nos. MC-1 light
MC-1 light
ii) 7 Nos. MC-1 light
MC-1 light
iii) 3 Nos. MC-1 light
MC-1 light
iv) 303 Nos. MC-1 light
MC-1 light
v) 84 Nos. MC-1 light
MC-1 light
vi) 45 Nos. MC-1 light
MC-1 light
vii) 22 Nos. MC-1 light
MC-1 light
viii) 7 Nos. MC-1 light
MC-1 light
ix) 162 Nos. MC-1 light
MC-1 light
x) 34 Nos. MC-1 light
MC-1 light
xi) 13 Nos. MC-1 light
MC-1 light
Inspection, receiving, storing, handling, assembling, installation, testing and commissioning of wall /ceiling, surface/ recessed, suspended from down rod, in furniture, fluorescent / incandescent / Halogen lamp fixtures including making connections with PVC insulated stranded copper conductor wires complete including steel supports, suspenders, fixing screws, turn buckles, bolts, nuts (down rods ball and socket arrangement and special channel mounting for industrial fitting/chandelier) etc, as required. The mounting arrangement of lighting fixture shall be as indicated in the approved drawings.
Pole Light with 70W Lamp, Pole Height 4.2 m (SIMES Minislot Disk S.3982 with S.2846 Pole or Equivalent) (F11)
Surfaced Downlight 1 x 26 W (Thorn Chalice C 190H 1 X 26 W or Equivalent) (T12)
Surfaced Downlight 1 x 26 W (Thorn Chalice C 190H 1 X 26 W or Equivalent) (T2) complete with Emergency Lighting Units.
Recessed Downlight 1 x 26W (Thorn Chalice C 190H 1 x 26W or Equivalent) (T13)
Recessed Downlight 1 x 26W (Thorn Chalice C 190H 1 x 26W or Equivalent) (T13) complete with Emergency Lighting Units.
Wall mounted Luminaire with 1 x 28W Fluorescent T5 Lamp water proof IP44 (SITECO Europlex 24W IP44 or Equivalent) (T8)
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or Equivalent) (T15)
Recessed Quad 2 x 18W (Thorn Matrix 300 2 x 18W or Equivalent) (T15) complete with Emergency Lighting Units.
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14)
Recessed Luminaire with 4 x 18W T5 Lamps with Parabolic Louvre (Thorn Omega BS/SB 4 x 18W or Equivalent) (T14) complete with Emergency Lighting Units.
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W T26 H2F or Equivalent) (T23).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 162
xii) 5 Nos. MC-1 light
MC-1 light
xiii) 8 Nos. MC-1 light
MC-1 light
xiv) 5 Nos. MC-1 light
MC-1 light
xv) 156 Nos. MC-1 light
MC-1 light
xvi) 29 Nos. MC-1 light
MC-1 light
xvii) 10 Nos. MC-1 light
MC-1 light
xviii) 4 Nos. MC-1 light
MC-1 light
xix) 40 Nos. MC-1 light
MC-1 light
xx) 4 Nos. MC-1 light
MC-1 light
xxi) 75 Nos. MC-1 light
MC-1 light
xxii) 32 Nos. MC-1 light
MC-1 light
xxiii) 9 Nos. MC-1 light
MC-1 light
xxiv) 11 Nos. MC-1 light
MC-1 light
xxv) 1 No. MC-1 light
MC-1 light
Recessed Luminaire 2 x 58W IP65 (Thorn Duopre 2 x 58W T26 H2F or Equivalent) (T23) complete with Emergency Lighting Units.
Recessed outside Downlight IP54 (Trilux Downlight IP54 or Equivalent) (T21)
Recessed outside Downlight IP54 (Trilux Downlight IP54 or Equivalent) (T21) complete with Emergency Lighting Units.
Step Light recessed in stairs with 11W LED Lamp diffusers with pressure formed glass IP64 (Bega Step Light TC-S 2191 or Iguzzini Step Light Vision SP50 or Equivalent) (T26).
Wall mounted Luminaire with 2 x 35W Fluorescent T5 Lamps with Prismatic Diffuser (Thorn Prisma C 2 x 35 T16CL or Equivalent) (T19)
Wall mounted Luminaire with 2 x 35W Fluorescent T5 Lamps with Prismatic Diffuser (Thorn Prisma C 2 x 35 T16CL or Equivalent) (T19) complete with Emergency Lighting Units.
Recessed Outside Downlight IP44 (Thorn Chalice C 190H 1 x 26W IP44) (T22)
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp IP-65 (Thorn Dunube 1 x 28W IP65 or Equivalent) (T11)
Bulk Head Light Wall Mounted with 2 x 28W TC-DEL Lamp IP-65 (Thorn Dunube 1 x 28W IP65 or Equivalent) (T11) complete with Emergency Lighting Units.
Surface mounted Industrial Luminaire with 2 x 36W Fluorescent T5 Lamps (Thorn Indus RD 2 x 58W TW or Equivalent) (T6)
Surface mounted Industrial Luminaire with 2 x 36W Fluorescent T5 Lamps (Thorn Indus RD 2 x 58W TW or Equivalent) (T6) complete with Emergency Lighting Units.
Emergency Exit Up Fixture complete with Emergency Lighting Unit (Cooper/Crompton or Approved Equivalent).
Emergency Exit Down Fixture complete with Emergency Lighting Unit (Cooper/Crompton or Approved Equivalent).
Emergency Exit Right Fixture complete with Emergency Lighting Units (Cooper/Crompton or Approved Equivalent).
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 163
MC-1 light
10.00 EARTHING & LIGHTNING PROTECTION SYSTEM : MC-1 earth
MC-1 earth
10.10 Earthing System: MC-1 earth
MC-1 earth
10.1.1 14 Nos. MC-1 earth
MC-1 earth
10.1.2 2 Nos. MC-1 earth
MC-1 earth
10.1.3 2 Nos. MC-1 earth
MC-1 earth
10.1.4 Earthing Strip/Tape/Cables : MC-1 earth
MC-1 earth
MC-1 earth
MC-1 earth
G.I. Earthing strip/tape : MC-1 earth
MC-1 earth
a 50 x 8 mm strip 10 RM MC-1 earth
b 50 x 6 mm strip 10 RM MC-1 earth
c 40 x 6 mm strip 10 RM MC-1 earth
TOTAL OF LIGHTING FIXTURES CARRIED OVER TO SUMMARY
Supply, installation, testing and commissioning of copper plate earthing stations making earth pits, earthing with copper earth plate 600 mm x 600 mm x 3.15 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS –3043 complete as required, as per specifications, drawings and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI plate earthing stations making earth pits, earthing with GI earth plate 600 mm x 600 mm x 6.30 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required, as per specifications, drawing and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI Pipe earthing stations making earth pits, earthing with GI pipe 4500 mm x 40 mm Dia including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required as per specifications, drawing and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of following sizes of GI/Tinned Copper strip/tape clamped to walls, cable trays, bus ducts, recess in Ground or surface etc for equipment/ System earthing complete as required including inter connection between length at joints, all fixing accessories saddles, clamps etc and other fixing hardware material as required, as per specifications, detail drawings shall be included for proper installation.
10.1.4.1
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 164
d 32 x 6 mm strip 10 RM MC-1 earth
e 25 x 6 mm strip 10 RM MC-1 earth
f 25 x 3 mm strip 10 RM MC-1 earth
MC-1 earth
Tinned Copper earthing strip/tape : MC-1 earth
MC-1 earth
a) 50 x 6 mm 100 RM MC-1 earth
b) 32 x 6 mm 50 RM MC-1 earth
c) 25 x 6 mm 10 RM MC-1 earth
d) 25 x 3 mm 2100 RM MC-1 earth
10.1.5 MC-1 cab
MC-1 cab
a) 1C x 185 Sqm 400 RM MC-1 cab
MC-1 cab
b) 1C x 90 Sqm 10 RM MC-1 cab
MC-1 cab
c) 1C x 50 Sqm 10 RM MC-1 cab
MC-1 cab
d) 1C x 35 Sqm 10 RM MC-1 cab
MC-1 cab
e) 1C x 25 Sqm 10 RM MC-1 cab
MC-1 cab
10.1.6 MC-1 earth
MC-1 earth
75 x 6 mm tinned, Copper, Earth Bars. MC-1 earth
MC-1 earth
a) 300 mm 1 No. MC-1 earth
b) 500 mm 2 Nos. MC-1 earth
c) 750 mm 3 Nos. MC-1 earth
d) 1000 mm 1 No. MC-1 earth
MC-1 earth
50 x 6 mm tinned, Copper, Earth Bars. MC-1 earth
MC-1 earth
a) 300 mm 5 Nos. MC-1 earth
b) 500 mm 5 Nos. MC-1 earth
c) 750 mm 10 Nos. MC-1 earth
d) 1000 mm 5 Nos. MC-1 earth
MC-1 earth
10.20 Lightning Protection System: MC-1 earth
10.1.4.2
Supply, installation, Termination, testing and commissioning of PVC insulated, stranded copper conductor cable, laid on surface/cable tray/duct/undger ground/Trench etc. as required, as per approved shop drawing, site conditions and as directed by Engineer-in-charge.
Supply, installation, Termination, testing and Commissioning of following sizes Tinned Copper Earth Bars including its supporting/fixing hardware, as per drawings, specifications and as directed by Engineer-in-charge.
10.1.6.1
10.1.6.2
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 165
MC-1 earth
10.2.1 2 Nos. MC-1 earth
MC-1 earth
10.2.2 10 Nos. MC-1 earth
MC-1 earth
10.2.3 Earthing Strip/Wires : MC-1 earth
MC-1 earth
MC-1 earth
MC-1 earth
a) 25 x 3 mm strip 500 RM MC-1 earth
MC-1 earth
b) 25 x 6 mm strip 200 RM MC-1 earth
MC-1 earth
c) 32 x 6 mm strip 10 RM MC-1 earth
MC-1 earth
10.2.4 MC-1 earth
MC-1 earth
75 x 6 mm GI Earth Bars. MC-1 earth
MC-1 earth
a) 300 mm 2 Nos. MC-1 earth
b) 500 mm 2 Nos. MC-1 earth
c) 750 mm 2 Nos. MC-1 earth
d) 1000 mm 2 Nos. MC-1 earth
Supply, installation, testing and commissioning of copper plate earthing stations making earth pits, earthing with copper earth plate 600 mm x 600 mm x 3.15 mm thick including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS –3043 complete as required, as per drawings, specifications and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of GI Pipe earthing stations making earth pits, earthing with GI pipe 4500 mm x 40 mm Dia including funnel, charcoal/coke, salt, all earth work. Providing masonry enclosure with 10 mm thick C.I. cover plate having locking arrangement and watering pipe, disconnecting/ testing links etc as per IS–3043 complete as required, as per drawings, specifications and direction of Engineer-in-charge.
Supply, installation, testing and commissioning of following sizes of GI strip/wire clamped to walls, Ductwork, pipe work, Structural steel work, cladding work etc. in recess, in Ground or surface etc for Lightning Protection System complete as required including inter connection, terminations, between length at joints, all fixing accessories saddles, plastic isolator mounting (of 50mmx80mm approx.), Sealing Collars, Sealing Strip, Squared Timber Block (80mmx100mm approx.), clamps, Lugs etc and other fixing hardware material as required for proper installation as per detail drawings, specifications and direction of Engineer-in-charge.
Supply, installation, Termination, testing and Commissioning of following sizes GI Earth Bars including in supporting/fixing hardware, as per drawings, specifications and as directed by Engineer-in-charge.
10.2.4.1
LABOUR RATE
VOLTEC ENERGY SYSTEMS Page 166
MC-1 earth
50 x 6 mm GI Earth Bars. MC-1 earth
MC-1 earth
a) 300 mm 2 Nos. MC-1 earth
b) 500 mm 2 Nos. MC-1 earth
c) 750 mm 2 Nos. MC-1 earth
d) 1000 mm 2 Nos. MC-1 earth
MC-1 earth
10.2.5 40 Nos. MC-1 earth
MC-1 earth
10.2.6 10 Nos. MC-1 earth
MC-1 earth
MC-1 earth
MC-1 earth
GRAND TOTAL
10.2.4.2
Supply and fixing of Lightning Arrestor Rod/Lightning Conductor finial made of 25 mm dia, 2.0 mm thick & 300 mm Long GI Tube having single prong at top with 75 mm dia, 6 mm thick Base plate, including connections with roof parapit Lightning protection Conductors, as per detailed drawings and as per direction of Engineer-in-charge.
Supply and fixing of "Earth Test Joints" encased in 200 mm (H) x 150 mm (W) x 100 mm (D) recessed in concrete with removable cover plate as per detailed drawing and as per direction of Engineer-in-charge.
TOTAL OF EARTHING & LIGHTNING PROTECTION SYSTEM CARRIED OVER TO SUMMARY