DRAWING LIST
A-000 GENERAL NOTES, ABBREVIATIONS, LEGENDS
A-100 EXISTING PLAN
A-140 DEMOLITION PLAN GENERAL NOTES, KEYS, LEGENDS
A-150 FLOOR PLANS GENERAL NOTES, KEYS, LEGEND
A-160 FINISH PLAN GENERAL NOTES, KEYS LEGENDS
A-170 REFLECTED CEILING GENERAL NOTES, KEYS, LEGENDS
A-180 FFE PLAN
A-210 INTERIOR ELEVATIONS GENERAL NOTES, KEYS, LEGENDS
A-710 TYPICAL PARTITION DETAILS, DOOR DETAILS, CASEWORK DETAILS
Isgenuity LLC500 Harrison Avenue, Suite 5FBoston, MA 02118Tel 617 419 4660Fax 617 419 4661 www.isgenuity.com
Architect
Project Number:
Date Issued:
NOT FOR CONSTRUCTION
R.W. Sullivan EngineeringThe Schrafft Center529 Main Street, Suite 203Boston, MA 02129Tel 617 523 8227Fax 617 523 8016
V1 6th Floor Tissue Culture Labs
179-27-00
3/13/20
Vertex Pharmaceuticals, Inc.
V1 6th Floor Tissue Culture Labs
50 Northern AveBoston, MA 02110
ISSUED FOR BID
MEP/FP Engineer
FP-001 FIRE PROTECTION LEGEND, DETAILS, SCHEDULE & GENERAL NOTESFP-101 FIRE PROTECTION LEVEL 6 DEMOLITION PLANFP-201 FIRE PROTECTION LEVEL 6 NEW WORK PLAN
H-001 HVAC LEGEND, DETAILS, SCHEDULE & GENERAL NOTESH-002 HVAC SCHEDULES & DETAILSH-101 HVAC LEVEL 6 NEW WORK PLAN
P-001 PLUMBING LEGEND, DETAILS, SCHEDULE & GENERAL NOTESP-101 PLUMBING LEVEL 6 DEMOLITION & NEW WORK PLAN
E-001 ELECTRICAL LEGEND AND GENERAL NOTESE-101 LEVEL 6 DEMOLITION PLANE-201 LEVEL 6 NEW WORK LIGHTING PLANE-301 LEVEL 6 NEW WORK POWER PLANE-401 SCHEDULES AND DETAILS
FA-001 FIRE ALARM LEGEND, GENERAL NOTES, RISER, AND DETAILSFA-101 FIRE ALARM LEVEL 6 NEW WORK PLAN
Issuance Schedule
Number Date Description
& ANDL ANGLE@ AT
CENTERLINEØ DIAMETER# POUNDA/E ARCHITECT / ENGINEERAB ANCHOR BOLTACBL ACCESSIBLE (ADA COMPLIANT)ACOUS ACOUSTICALACP ACOUSTICAL CEILING PANELAD ACCESS DOORADA THE AMERICANS WITH DISABILITIES ACTADBL ADAPTABLE (ADA COMPLIANT)ADDL ADDITIONALADH ADHESIVEADJ ADJUSTABLEADJC ADJACENTAF ACCESS FLOORAFF ABOVE FINISHED FLOORAFI AIR FLOW INDICATORAGGR AGGREGATEAL ALUMINUMALT ALTERNATEANOD ANODIZEDAP ACCESS PANELARCH ARCHITECTASC ABOVE SUSPENDED CEILINGASPH ASPHALTAVAF AUDIO/VISUAL ALARM
BD BOARDBLDG BUILDINGBLKG BLOCKINGBM BEAMBOT BOTTOMBUR BUILT-UP ROOFING
CA CARD ACCESSCAB CABINETCB CASING BEADCEM CEMENTCEMTS CEMENTITIOUSCER CERAMICCG CORNER GUARDCGE CORNER END GUARDCHAN CHANNELCHBD CHALKBOARDCHFR CHAMFERCJ CONSTRUCTION JOINTCL CENTER LINECLG CEILINGCLJ CONTROL JOINTCLO CLOSETCLR CLEARCLRM CLASSROOMCMPST COMPOSITECMU CONCRETE MASONRY UNITCNTR COUNTERCO CASED OPENINGCOL COLUMNCOMP COMPUTERCONC CONCRETECONN CONNECTIONCONSTR CONSTRUCTIONCONT CONTINUOUSCONTR CONTRACTORCORR CORRIDORCPRS COMPRESSIBLE OR COMPRESSIONCR CHAIR RAILCRS COLD ROLLED STEELCS CAST STONECSK COUNTERSUNKCSMT CASEMENTCSWK CASEWORKCYL CYLINDER
DBL DOUBLEDEMO DEMOLITIONDEPT DEPARTMENTDET DETAILDF DRINKING FOUNTAINDG DECORATIVE GLASSDIA DIAMETERDIM DIMENSIONDISP DISPENSERDIV DIVISIONDMBD DRY MARKER BOARDDMPF DAMPPROOFINGDN DOWNDO DITTODOP DOOR OPENINGDPG DECORATIVE PLASTIC GLAZINGDS DOWNSPOUTDSP DRY STANDPIPEDST DOOR STOPDWG DRAWINGDWR DRAWER
E EASTEA EACHEIFS EXTERIOR INSULATION & FINISH SYSTEMEL ELEVATIONELAST ELASTOMERICELEC ELECTRICELEV ELEVATOREMER EMERGENCYENCL ENCLOSUREENGR ENGINEERENTR ENTRANCEEO EMERGENCY POWEREP ELECTRICAL PANELEPDM ETHYLENE PROPYLENE DIENE MONOMEREPRF EXPLOSION PROOFEQ EQUALEQUIP EQUIPMENTESCAL ESCALATOREW EACH WAYEWC ELECTRIC WATER COOLEREXC EXCAVATEEXH EXHAUSTEXP EXPANSIONEXIST EXISTINGEXT EXTERIOR
F/F FACE TO FACEF/T/UC FLOOR / TABLE / UNDERCOUNTERFA FIRE ALARMFACP FIRE ALARM CONTROL PANELFB FLAT BARFCO FLOOR CLEAN OUTFD FLOOR DRAINFDC FIRE DEPARTMENT CONNECTIONFDN FOUNDATIONFEC FIRE EXTINGUISHER CABINETFE FIRE EXTINGUISHERFGL FIBERGLASSFHC FIRE HOSE CABINETFHP FULL HEIGHT PARTITIONFH FULL HEIGHTFIN FINISHFL FLASHINGFLR FLOOR OR FLOORINGFLUOR FLUORESCENT
FOC FACE OF CONCRETEFOF FACE OF FINISHFOM FACE OF MASONRYFOS FACE OF STUDFPRF FIREPROOFINGFS FULL SIZEFSH FIRE SPRINKLER HEADFSTP FIRESTOPPINGFT FOOT OR FEETFTG FOOTINGFURN FURNITUREFURR FURRINGFUT FUTURE
G GASGA GAGEGALV GALVANIZEDGB GRAB BARGEN GENERATORGFRC GLASS FIBER REINFORCED CONCRETEGFRG GLASS FIBER REINFORCED GYPSUMGL GLASSGLMU GLASS MASONRY UNITGMMU GLASS MESH MORTAR UNITGND GROUNDGR GRADEGRL GRILLEGRTG GRATINGGSKT GASKETGT GROUTGVL GRAVELGWB GYPSUM WALL BOARDGYP GYPSUM
HB HOSE BIBBHC HOLLOW COREHDBD HARDBOARDHDWD HARDWOODHDWE HARDWAREHGR HANGERHGT HEIGHTHM HOLLOW METALHMD HOLLOW METAL DOORHNDRL HANDRAILHO HOLD OPENHORIZ HORIZONTALHPT HIGH POINTHR HOURHSAFD HORIZONTAL SLIDING ACCORDION FIRE DOORHVAC HEATING, VENTILATION, AIR CONDITIONINGHYDR HYDRAULIC
ID INSIDE DIAMETERIF INSIDE FACEIN INCH OR INCHESINSUL INSULATIONINTR INTERIORIWH INSTANTANEOUS WATER HEATER
JAN JANITORJST JOISTJT JOINT
KIT KITCHENKO KNOCKOUTKOP KNOCKOUT PANELKPL KICK PLATE
L LEFTLAB LABORATORYLAD LADDERLAM LAMINATIONLAV LAVATORYLB POUNDLBL LABELLF LINEAR FOOTLG LENGTHLG LENGTHLH LEFT HANDLHR LEFT HAND REVERSELIB LIBRARYLIN LINEARLKR LOCKERLLH LONG LEG HORIZONALLLV LONG LEG VERTICALLNTL LINTELLONG LONGITUDINALLP LIGHTPROOFLPT LOW POINTLT LIGHTLTWT LIGHTWEIGHTLTG LIGHTINGLVR LEVER OR LOUVER
MACH MACHINEMAINT MAINTENANCEMAS MASONRYMATL MATERIALMAX MAXIMUMMECH MECHANICALMED MEDIUMMEMB MEMBRANEMET METALMEZZ MEZZANINEMFG MANUFACTURERMH MANHOLEMIN MINIMUMMIR MIRRORMISC MISCELLANEOUSML METAL LATHMLDG MOLDINGMLWK MILLWORKMO MASONRY OPENINGMTD MOUNTEDMTR MORTARMULL MULLIONMVBL MOVABLE
N NORTHNA NOT APPLICABLENAT NATURALNIC NOT IN CONTRACTNO NUMBERNOM NOMINALNTS NOT TO SCALE
OA OVERALLOC ON CENTEROD OUTSIDE DIAMETEROF OUTSIDE FACEOF/CI OWNER FURNISHED/CONTRACTOR INSTALLEDOFF OFFICEOPNG OPENINGOPP OPPOSITEOT ELECTRICAL OUTLETOXY OXYGEN
PB PANIC BARPERF PERFORATEDPERIM PERIMETERPERP PERPENDICULARPGBD PED BOARD
PL PLATEPLAM PLASTIC LAMINATEPLAS PLASTICPLBG PLUMBINGPLYWD PLYWOODPNEU PNEUMATICPNL PANELPNT PAINTPNTD PAINTEDPOL POLISHEDPOLY POLYETHYLENEPR PAIRPRCST PRECASTPREFAB PREFABRICATEDPREFIN PREFINISHEDPTD PAPER TOWEL DISPENSERPTN PARTITIONPTR PAPER TOWEL RECEPTACLEPVG PAVING
QT QUARRY TILEQTY QUANTITYQUAL QUALITY
R RISERRAD RADIUSRBR RUBBERRD ROOF DRAINREC RECESSEDREF REFERENCEREFR REFRIGERATORREG REGISTERREINF REINFORCED OR REINFORCINGREM REMOVEABLEREQD REQUIREDRESIL RESILIENTRFG ROOFINGRH RIGHT HANDRHR RIGHT HAND REVERSERLG RAILINGRM ROOMRO ROUGH OPENINGRV ROOF VENTRWL RAIN WATER LEADER
S SOUTHSC SOLID CORESCHED SCHEDULESCRN SCREENSD SOAP DISPENSERSECT SECTIONSGL SINGLESHR SHOWERSHT SHEETSHTHG SHEATHINGSHV SHELVINGSIM SIMILARSK SINKSLV SLEEVESM SHEET METALSND SANITARY NAPKIN DISPENSERSNR SANITARY NAPKIN RECEPTACLESPEC SPECIFICATIONSQ SQUARESSK SERVICE SINKSSP SOLID SURFACE POLYMERSST STAINLESS STEELST STREETSTA STATIONSTC SOUND TRANSMISSION CLASSSTD STANDARDSTL STEELSTOR STORAGESTRUCT STRUCTURALSUSP SUSPENDEDSYM SYMBOL
SYMM SYMMETRICALSYS SYSTEM
T THERMOSTATT&B TOP AND BOTTOMT&G TONGUE AND GROOVETB TOWEL BARTBM TOP OF BEAMTC TOP OF CONCRETETD TEL / DATATEL TELEPHONETEMP TEMPORARYTER TERRAZZOTF TOP OF FOOTINGTFF TOP OF FINISHED FLOORTHK THICKNESSTHRES THRESHOLDTHRU THROUGHTKBD TACKBOARDTMPD TEMPEREDTOL TOLERANCETP TOP OF PAVEMENTTPH TOILET PAPER HOLDERTS TACKABLE SURFACETSL TOP OF SLABTST TOP OF STEELTV TELEVISIONTW TOP OF WALLTYP TYPICAL
U/C UNDER COUNTER UNEX UNEXCAVATEDUNFIN UNFINISHEDUON UNLESS OTHERWISE NOTEDUPS UNINTERRUPTIBLE POWER SUPPLY
UR URINALUV ULTRAVIOLET
VAC VACUUMVAF VISUAL ALARM VCT VINYL COMPOSITION TILEVERT VERTICALVEST VESTIBULEVIF CONTRACTOR TO VERIFY IN FIELDVNR VENEERVR VAPOR RETARDER
W WESTW/ WITHW/O WITHOUTWC WATERCLOSETWD WOODWLD WELDEDWSCT WAINSCOTWT WEIGHTWTRPRF WATERPROOFINGWWF WELDED WIRE FABRIC
CL
1
A1.01
SIM
A1.01
1SIM
TOP OF SLABELEV = 100'-0"
WINDOW / LOUVER SYMBOL
DOOR MARK
ELEVATION /LEVEL MARKER
DATUM POINT ELEV = 100'-0"
1 View Name1/8" = 1'-0"
A
B
C
D A5.10
1
A1.01
SIM
1
A1.01
SIM
1
A1.01
SIM
ACCESSIBILITYCLEARANCES
REVISION SYMBOL
ACCESSIBILITY SYMBOL
BUILDING SECTION
WALL SECTION
DETAIL
PLAN / SECTION DETAIL
ELEVATION INTERIOR
ELEVATION EXTERIOR
SCALE:
1 View Name1/8" = 1'-0"A1.01
VIEW NAME: PLAN,SECTION, ELEVATION, DETAILS
VIEW NAME WITH REFERENCE
COLUMN GRIDS
PARTITION SYMBOL
FN-00FURNITURE SYSTEM SYMBOL
CURTAIN WALL PANEL SYMBOL
EQUIPMENT SYMBOL
#
ROOM TAG
/1 A1.01MATCH LINE
CEILING TYPE/HT.
ROOM NUMBER
APPROX ROOM AREA
SHEET REFERENCE
CEILING TYPE
CEILING HEIGHT
EQUIP. NUMBER
PARTITION TYPE
PANEL TYPE
WINDOW / LOUVER
MARK
COLUMN
NUMBER
FURNITURE
NUMBER
CASEWORK TAGCASEWORK TYPE
1
A5.01
COLUMN LETTER
R 2' - 6"
FINISH TAG
1
001M
12'-6"
TYPE
EQ-00
PL
X1
Room Name
101123 SF
WIN
X
#
1541-AROOM # - PRIMARY, SECONDARY, ECT.
OVERHEAD (OVER COUNTER AND SOFFITS)
CALLOUT
BREAK LINE
GRID LINE
BELOW OR BEYOND (UNDERCOUNTER AND FOOTINGS)
SCOPE OF WORK
CASED OPENING
PAIR
TYPICAL DOOR
DOOR WITH SIDELIGHT
VARYING LEAF
SLIDING
DOUBLE ACTING
TYPICAL WINDOW
EXISTING TO REMAIN
EXISTING TO BE REMOVED
EXISTING WALL
NEW WALL
DEMOLISHED WALL
ALUMINUM
WOOD FINISH
EXISTING BUILDINGS
STEEL
CONCRETE
EARTH
RIGID INSULATION
RUBBER
SAND
GYPSUM BOARD
INSULATION
CMU
Scale: Date Issued:
Project Number:
Isgenuity LLC500 Harrison Avenue, Suite 5FBoston, MA 02118Tel 617 419 4660Fax 617 419 4661www.isgenuity.com
Architect
NOT FOR CONSTRUCTION
R.W. Sullivan EngineeringThe Schrafft Center529 Main Street, Suite 203Boston, MA 02129Tel 617 523 8227Fax 617 523 8016
1/4" = 1'-0"
3/1
3/2
02
0 1
:49:2
8 P
M
A-000179-27-00
3/13/20
GENERAL NOTES,ABBREVIATIONS, LEGENDS
Vertex Pharmaceuticals, Inc.
V1 6th Floor Tissue CultureLabs
ISSUED FOR BID
MEP/FP Engineer
ABBREVIATIONS SYMBOLS LINE TYPES
DOORS / WINDOWS / WALLS
MATERIALS
Issuance Schedule
Number Date Description
4 5 6
D
C.5
C
SOLVENT STORAGE
6032STORAGE ROOM
6031
LAB SUPPLY ROOM
6035ELEC ROOM
6036
STAIR
S3-6
PLUMBING CLOSET
621
CORRIDOR
6037
EQUIPMENT
CORRIDOR
6030
EQUIPMENT LAB
6029MONITORING LAB
6028EQUIPMENT LAB
6027
MICROSCOPE
ROOM
6022
COLD ROOM
6017EQUIPMENT LAB
6019
EQUIPMENT
CORRIDOR
6021EQUIPMENT ROOM
6023
CORRIDOR
6020
EQUIPMENT
CORRIDOR
6018
CORRIDOR
6002
CORRIDOR
6026
SCOPE OF WORK
Scale: Date Issued:
Project Number:
Isgenuity LLC500 Harrison Avenue, Suite 5FBoston, MA 02118Tel 617 419 4660Fax 617 419 4661www.isgenuity.com
Architect
NORTH
NOT FOR CONSTRUCTION
R.W. Sullivan EngineeringThe Schrafft Center529 Main Street, Suite 203Boston, MA 02129Tel 617 523 8227Fax 617 523 8016
1/4" = 1'-0"
3/1
3/2
02
0 1
:49:2
9 P
M
A-100179-27-00
3/13/20
EXISTING PLAN
Vertex Pharmaceuticals, Inc.
V1 6th Floor Tissue CultureLabs
ISSUED FOR BID
MEP/FP Engineer
Issuance Schedule
Number Date Description
SCALE:
1/4" = 1'-0"1
LEVEL 6 EXISTING PLAN
A. SCOPE OF WORK LINE GENERALLY INDICATES THE AREA OF GREATEST IMPACT DURING RENOVATIONS. EXISTING AREAS OUTSIDE THE SCOPE OF WORK LINE THAT ARE DISTURBED IN ORDER TO COMPLETE THIS AREA ARE CONSIDERED TO BE PART OF THE SCOPE OF WORK WHETHER INDICATED SPECIFICALLY OR NOT. CONTRACTOR SHALL ALLOW FOR REMOVAL AND REPLACEMENT OF EXISTING FINISHES OUTSIDE THE SCOPE OF WORK LINE IN ORDER TO COMPLETE THE WORK.
B. SEE HOURS OF WORK REQUIREMENTS AND COORDINATE DEMOLITION ACTIVITIES ACCORDINGLY.C. REFER TO ALL OTHER CONSULTANT AND VENDOR DRAWINGS AND SPECIFICATIONS FOR EXTENT AND
REQUIREMENTS OF REMOVAL/SALVAGE/RELOCATION OF STRUCTURAL, PLUMBING/FIRE PROTECTION, MECHANICAL AND ELECTRICAL ITEMS. COORDINATE WITH ALL ASSOCIATED TRADES.
D. REFER TO DIV. 01 SECTION "CUTTING AND PATCHING" FOR REQUIREMENTS RELATED TO CUTTING AND PATCHING DUE TO DEMOLITION ACTIVITIES.
E. REFER TO DEMOLITION SPECIFICATION (DIVISION 01) FOR REQUIREMENTS RELATED TO DEMOLITION ACTIVITIES.
F. DISPOSE OF ALL DEMOLITION ITEMS IN ACCORDANCE WITH PROJECT SPECIFICATIONS. G. REMOVE ALL ITEMS SHOWN AS DASHED LINES ON THE DEMOLITION DRAWINGS, INCLUDING ALL
ASSOCIATED FITTINGS AND ACCESSORIES ASSOCIATED WITH ITEM(S) BEING REMOVED.H. DEMOLITION KEYNOTES NOT SPECIFICALLY TAGGING AN INDIVIDUAL ITEM (NO LEADER ARROW)
REFER TO ALL ITEMS WITHIN THE ROOM OR AREA IN WHICH THE NOTE IS LOCATED. I. WHERE A PARTITION IS SHOWN TO BE DEMOLISHED, CONTRACTOR TO REMOVE ALL WALL MOUNTED
FIXTURES/FITTINGS/EQUIPMENT. J. FIRE RATINGS TO BE MAINTAINED AT ALL RATED ASSEMBLIES AT ALL TIMES. K. FOR THE PURPOSES OF A COMPLETE SCOPE OF WORK THE CONTRACTOR IS TO ASSUME THAT ALL
EXISTING WALLS TO BE DEMOLISHED THAT ARE GREATER THAN 8" THICK ARE CHASE WALLS, CONTINUOUS TO ADJACENT FLOORS AND WILL REQUIRE PATCHING.
L. RELOCATION OF ALL EQUIPMENT TO BE COORDINATED WITH OWNER.M. PROVIDE TEMPORARY SUPPORTS FOR PORTION OF DEMOLISHED WALLS TO REMAIN.
4 5 6
D
C.5
C
CORRIDOR
6002
TISSUE CULTURE
LAB
6029
MONITORING LAB
6028EQUIPMENT LAB
6027
MICROSCOPE
ROOM
6022
TISSUE CULTURE
LAB
6019
COLD ROOM
6017
EQUIPMENT
CORRIDOR
6021
EQUIPMENT ROOM
6023
CORRIDOR
6020EQUIPMENT
CORRIDOR
6018
CORRIDOR
6026
EQUIPMENT
CORRIDOR
6030
STORAGE ROOM
6031SOLVENT STORAGE
6032
CORRIDOR
6037
ELEC ROOM
6036
LAB SUPPLY ROOM
6035
PLUMBING CLOSET
621
STAIR
S3-6
SCOPE OF WORK
11
45
45
08
08
16
16
17
Scale: Date Issued:
Project Number:
Isgenuity LLC500 Harrison Avenue, Suite 5FBoston, MA 02118Tel 617 419 4660Fax 617 419 4661www.isgenuity.com
Architect
NORTH
NOT FOR CONSTRUCTION
R.W. Sullivan EngineeringThe Schrafft Center529 Main Street, Suite 203Boston, MA 02129Tel 617 523 8227Fax 617 523 8016
1/4" = 1'-0"
3/1
3/2
02
0 1
:49:3
0 P
M
A-140179-27-00
3/13/20
DEMOLITION PLAN GENERALNOTES, KEYS, LEGENDS
Vertex Pharmaceuticals, Inc.
V1 6th Floor Tissue CultureLabs
ISSUED FOR BID
MEP/FP Engineer
GENERAL DEMOLITION NOTES
SPECIFIC DEMOLITION NOTES
08 REMOVE INTERIOR LAYERS OF GYPSUM BOARD IN COORDINATION WITH NEW LAYER OF 5/8" GYPSUMBOARD, EXISTING PARTITION FRAMING TO REMAIN.
11 REMOVE AND SALVAGE DOOR AND ALL ASSOCIATED FITTINGS, EXISTING FRAME TO REMAIN. RETURNDOOR TO OWNER.
16 REMOVE PROTECTIVE FILM FROM WINDOW, EXISTING GLASS AND FRAME TO REMAIN.
17 REMOVE AND SALVAGE DOOR HARDWARE FOR REUSE ON NEW DOOR PANEL.
45 REMOVE AND SALVAGE EXISTING BENCH, LAB CASEWORK, SHELVES, AND ALL ASSOCIATEDHARDWARE/FIXTURES/FITTINGS.
SCALE:
1/4" = 1'-0"1
LEVEL 6 DEMOLITION PLAN
Issuance Schedule
Number Date Description
1. ALL WORK SHALL BE PERFORMED PER APPLICABLE CODES, ORDINANCES AND PER REQUIREMENTS OF ALL APPLICABLE REGULATORY AGENCIES AND AUTHORITIES HAVING JURISDICTION.
2. ALTERATIONS/RENOVATIONS ON THIS AND OTHER FLOORS NOT SPECIFICALLY CALLED OUT AS RENOVATION AREAS ARE TO BE DONE AS NECESSARY TO COMPLETE WORK SHOWN ON THE CONTRACT DOCUMENTS. REFER TO ENGINEER CONSULTANT AND VENDOR DRAWINGS TO IDENTIFY THE SCOPE OF WORK IN AREAS IDENTIFIED OUTSIDE THE ARCHITECTURAL DOCUMENTS. THE G.C. SHALL BE RESPONSIBLE FOR THE REMOVAL AND RESTORATION OF ALL EXISTING FINISHES DISTURBED BY THE WORK. WHERE TEMPORARY M.E.P. CONNECTIONS ARE REQUIRED, ALL FINISHES SHALL BE RESTORED IMMEDIATELY TO MAINTAIN OPERATION OF THE FACILITY, EVEN IF THE WORK WILL REQUIRE TO BE REMOVED AGAIN DURING THIS PROJECT.
3. ALL OPENINGS, IN EXISTING FLOORS AND WALLS ABOVE AND BELOW THE CEILING PLENUM, BOTH EXISTING AND AS A RESULT OF DEMOLITION ACTIVITIES SHALL BE PATCHED TO COMPLETE AND FINISH EXISTING WALLS AND FLOORS CONSISTENT WITH NEW WORK. ALL PATCHES SHALL BE MADE WITH MATERIALS CONSISTENT WITH THE WALL IN WHICH THE PATCH WILL BE LOCATED.
4. THE G.C. SHALL COORDINATE AND SCHEDULE ALL WORK WITH THE CLIENT AND/OR CLIENTS AUTHORIZED REPRESENTATIVE/PROJECT MANAGER. WORK SCHEDULED IN OCCUPIED AREAS SHALL BE UNDERTAKEN IN A MANNER SO AS NOT TO DISTURB THE OPERATION OF THE FACILITY.
5. WHERE A NEW SERVICE PENETRATES AN EXISTING WALL WHICH EXTENDS TO THE UNDERSIDE OF THE STRUCTURE, THE G.C. WILL BE RESPONSIBLE FOR PATCHING AND FIRE SAFING THE WALL AND FOR PROVIDING THE REQUIRED FIRE RATING AND FINISH.
6. PROVIDE BLOCKING IN WALL THROUGHOUT AS INDICATED ON DRAWINGS FOR ALL WALL MOUNTED ITEMS, INCLUDING ITEMS FURNISHED BY OWNER.
7. ITEMS IDENTIFIED AS NOT IN CONTRACT (NIC) ARE TO BE PURCHASED AND INSTALLED BY THE OWNER. THE G.C. SHALL COORDINATE INSTALLATION OF ALL ITEMS NIC WITH THE OWNER.
8. PROVIDE ALL HEADERS, LINTELS AND SUPPORTS AS NECESSARY FOR ALL WALLS AND PARTS OF WALLS SHOWN TO BE REMOVED. ALL NEW MEMBERS SHALL BE IN CONFORMANCE WITH THE MASSACHUSETTS STATE BUILDING CODE, 9TH EDITION. THE GC IS RESPONSIBLE FOR IDENTIFYING ANY STRUCTURAL BEARING CONDITIONS THAT BECOME APPARENT DURING DEMOLITION. ANY FOUND STRUCTURAL CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO REMOVAL OF STRUCTURAL MEMBERS.
9. IT IS THE INTENT OF THIS DOCUMENT THAT ALL NEW WIRING, PIPING FIXTURES, FITTINGS AND DEVICES BE RECESSED INTO EXISTING WALLS. THE CONTRACTOR IS RESPONSIBLE FOR ALL CUTTING, PATCHING, REPAIRING, ETC. AS REQUIRED TO RECESS ITEMS IDENTIFIED ABOVE.
10. WHERE WALL MOUNTED ITEMS HAVE BEEN REMOVED, PATCH AND REPAIR EXISTING WALL.
1. ALL WALL PARTITIONS TO BE TYPE "B" UNLESS OTHERWISE NOTED.2. WHERE NEW WALL IS NOT DIMENSIONED LAYOUT TO ASSUME NEW WALL IS ALIGNED WITH
ADJACENT WALL.3. ALL PARTITIONS ARE TO EXTEND TO THE UNDERSIDE OF THE EXISTING DECK AND TO BE SEALED
ON BOTH SIDES.4. ALL PENETRATIONS IN SMOKE AND FIRE RATED PARTITIONS ABOVE CEILING TO BE FIRE
STOPPED.5. ALL PENETRATIONS IN NON-RATED PARTITIONS ABOVE CEILING TO BE SEALED.
4 5 6
D
C.5
C
SCOPE OF WORK
A-210
20A
20B
20C
20D
A-210
10A
10B
10C
10D
A-210
30A
30B30C
TISSUE CULTURE
LAB
6029
TISSUE CULTURE
LAB
6019
MONITORING LAB
6028
EQUIPMENT LAB
6027
CORRIDOR
6002
EQUIPMENT
CORRIDOR
6030
STORAGE ROOM
6031SOLVENT STORAGE
6032
CORRIDOR
6037
LAB SUPPLY ROOM
6035ELEC ROOM
6036
PLUMBING CLOSET
621COLD ROOM
6017
MICROSCOPE
ROOM
6022
EQUIPMENT
CORRIDOR
6021
EQUIPMENT ROOM
6023
EQUIPMENT
CORRIDOR
6018
CORRIDOR
6020
CORRIDOR
6026
V
V
V
V
19'-3" +/-
20'-4
" +/
-21'-4" +/-
19'-7
" +/
-
6019
-A
V
V
1'-0"5'
-11"
5'-1
1"12'-0"
2'-6
"
12'-0"
2'-6
"
12'-0
"
2'-6" 2'-6"
12'-0
"
4'-0" TYP.
6'-0" TYP.
4'-0
" T
YP
.
6'-0
" T
YP
.
G
G
G
G
G
G
G
G
PATCH DRYWALL AT BENCHES
1. LAB CASEWORK WILL BE FURNISHED BY OWNER GC TO COORDINATE WITH OWNER TO BRING CASEWORK IN STORAGE UP TO CONSTRUCTION SITE. G TO INSTALL ALL LAB CASEWORK. REFER TO DRAWINGS FOR LOCATION AND SPECIFIC SIZES.
2. 75% OF EPOXY TOPS WILL BE FURNISHED BY OWNER. GC TO OWN REMAINING 25% TO MATCH EXISTING 1" BLACK EPOXY.
3. ALL CASEWORK TO BE 34 3/4" HEIGHT UNLESS OTHERWISE NOTED.
Scale: Date Issued:
Project Number:
Isgenuity LLC500 Harrison Avenue, Suite 5FBoston, MA 02118Tel 617 419 4660Fax 617 419 4661www.isgenuity.com
Architect
NORTH
NOT FOR CONSTRUCTION
R.W. Sullivan EngineeringThe Schrafft Center529 Main Street, Suite 203Boston, MA 02129Tel 617 523 8227Fax 617 523 8016
1/4" = 1'-0"
3/1
3/2
02
0 1
:49:3
1 P
M
A-150179-27-00
3/13/20
FLOOR PLANS GENERALNOTES, KEYS, LEGEND
Vertex Pharmaceuticals, Inc.
V1 6th Floor Tissue CultureLabs
ISSUED FOR BID
MEP/FP Engineer
GENERAL NOTES
PARTITION NOTES
SCALE:
1/4" = 1'-0"1
LEVEL 6 NEW WORK PLAN
Issuance Schedule
Number Date Description
LAB CASEWORK NOTES
1. ALL WALLS AND SOFFITS TO BE PAINTED PT-1, UNLESS OTHERWISE NOTED.2. PROVIDE TRANSITION STRIPS AT ALL CHANGE IN FLOORING MATERIAL INTERSECTIONS.3. STRAIGHT BASE AT CARPET. COVE BASE AT ALL OTHER FLOORING.4. ALL FLOORING TO CONTINUE UNDER MILLWORK/CASEWORK UNLESS OTHERWISE NOTED.5. FINISH TAGS NOT SPECIFICALLY TAGGING AN INDIVIDUAL ITEM (NO LEADER ARROW) OR NOT
ASSOCIATED WITH A HATCH, REFER TO ALL ITEMS WITHIN THE ROOM OR AREA IN WHICH THE NOTE IS LOCATED.
EP EPOXY SURFACEMT METALPL PLASTIC LAMINATEPT PAINTRB RESILIENT BASEVCT VINYL COMPOSITION TILE
PAINT THRESHOLDS
4 5 6
D
C.5
C
EQUIPMENT
CORRIDOR
6018
CORRIDOR
6020
COLD ROOM
6017
TISSUE CULTURE
LAB
6019
EQUIPMENT
CORRIDOR
6021EQUIPMENT ROOM
6023
MICROSCOPE
ROOM
6022
CORRIDOR
6026
EQUIPMENT LAB
6027MONITORING LAB
6028
TISSUE CULTURE
LAB
6029EQUIPMENT
CORRIDOR
6030
STORAGE ROOM
6031SOLVENT STORAGE
6032
CORRIDOR
6037
ELEC ROOM
6036LAB SUPPLY ROOM
6035
STAIR
S3-6
CORRIDOR
6002
PLUMBING CLOSET
621
SCOPE OF WORK
PT-1RB-1
VCT-1
PT-1RB-1
VCT-1
EP-1EP-1
EP-1
EP-1MT-1 MT-1
MT-1 MT-1
MT-1
MT-1
MT-1
MT-1
EP-1
RB-2
RB-2
RB-2 RB-2
MT-1RB-2
MT-1
RB-2
MT-1
RB-2
ACT-1
ACT-1
PT-1
Scale: Date Issued:
Project Number:
Isgenuity LLC500 Harrison Avenue, Suite 5FBoston, MA 02118Tel 617 419 4660Fax 617 419 4661www.isgenuity.com
Architect
NORTH
NOT FOR CONSTRUCTION
R.W. Sullivan EngineeringThe Schrafft Center529 Main Street, Suite 203Boston, MA 02129Tel 617 523 8227Fax 617 523 8016
1/4" = 1'-0"
3/1
3/2
02
0 1
:49:3
2 P
M
A-160179-27-00
3/13/20
FINISH PLAN GENERALNOTES, KEYS LEGENDS
Vertex Pharmaceuticals, Inc.
V1 6th Floor Tissue CultureLabs
ISSUED FOR BID
MEP/FP Engineer
FINISH NOTES
ABBREVIATIONS - FINISHES
FINISH FLOOR PATTERN KEY
FINISH SCHEDULE
FINISH MANUFACTURER STYLE/NUMBER COLOR NOTES
ACT-1 ARMSTRONG OPTIMA 3251 WHITE BUILDING STANDARD CEILING TILE
EP-1 EPOXY BENCH FURNISHED BY OWNER
MT-1 METAL SHELVES AND CASEWORK FURNISHED BY OWNER; INSTALLED BY GC
PT-1 SHERWIN WILLIAMS OC-122 COTTON BALLS BUILDING STANDARD FIELD PAINT
RB-1 JOHNSONITE 4" HIGH 01 SNOW WHITE COVED; COLOR TO MATCH EXISTING
RB-2 JOHNSONITE 4" HIGH BLACK BLACK COVED AT LAB CABINET LOCATIONS; COLOR TO MATCH EXISTING
VCT-1 MANNINGTON SOLIDPOINT 317 COOL BEIGE BUILDING STANDARD FIELD VCT
Issuance Schedule
Number Date Description
SCALE:
1/4" = 1'-0"1
LEVEL 6 - FINISH PLAN
1. ALL TYPICAL ACT CEILING HEIGHTS 9'-0" UNLESS OTHERWISE NOTED.2. CEILINGS SHALL NOT BE INSTALLED WITHOUT REVIEWED MEP COORDINATION DRAWINGS AS
REQUIRED BY THE PROJECT SPECIFICATIONS.3. AT NO TIME SHALL THE CONTRACTOR ADJUST THE CEILING HEIGHT AS INDICATED ON
DOCUMENTS WITHOUT REVIEW WITH ARCHITECT. ARCHITECT SHALL BE INFORMED OF ALL CEILING HEIGHT CONFLICTS WHEN DISCOVERED FOR REVIEW.
4. COORDINATE ALL SOFFITS ABOVE CABINETS WITH INTERIOR ELEVATIONS AND CASEWORK DETAILS.
5. ALL DEVICES SHALL BE ALIGNED AND CENTERED WITHIN GRID UNLESS OTHERWISE NOTED. 6. REFER TO ALL ENGINEERING CONSULTANT AND VENDOR DRAWINGS FOR ALL RELATED SCOPE
FOR COORDINATION.
2'x2' SUPPLY DIFFUSER
NEW CEILING GRID WITH NEW 2'x2' ACOUSTICAL PANEL CEILING
NEW SOFFIT
1'x1' SUPPLY DIFFUSER
2'x2' RETURN REGISTER
1'x1' RETURN REGISTER
EXIT SIGN
SMOKE DETECTOR RECESSED DOWN LIGHT
2'x2' RECESSED LIGHT FIXTURE
SPRINKLER
EXISTING CEILING GRID WITH EXISTING 2'x2' ACOUSTICAL PANEL CEILING
EXISTING SOFFIT
RECESSED LIGHT FIXTURE
MOTION SENSOR WIRELESS ACCESS POINT
4 5 6
D
C.5
C
TISSUE CULTURE
LAB
6029
MONITORING LAB
6028
TISSUE CULTURE
LAB
6019
EQUIPMENT LAB
6027
MICROSCOPE
ROOM
6022
EQUIPMENT
CORRIDOR
6021
EQUIPMENT ROOM
6023
EQUIPMENT
CORRIDOR
6018
COLD ROOM
6017PLUMBING CLOSET
621
EQUIPMENT
CORRIDOR
6030STORAGE ROOM
6031
SOLVENT STORAGE
6032
CORRIDOR
6002
CORRIDOR
6026
STAIR
S3-6ELEC ROOM
6036LAB SUPPLY ROOM
6035
CORRIDOR
6037
SCOPE OF WORK
9' - 0"
ACT
9' - 0"
ACT
POWER FROM CEILING; SEE ELEC DRAWINGS
POWER FROM CEILING; SEE ELEC DRAWINGS
Scale: Date Issued:
Project Number:
Isgenuity LLC500 Harrison Avenue, Suite 5FBoston, MA 02118Tel 617 419 4660Fax 617 419 4661www.isgenuity.com
Architect
NORTH
NOT FOR CONSTRUCTION
R.W. Sullivan EngineeringThe Schrafft Center529 Main Street, Suite 203Boston, MA 02129Tel 617 523 8227Fax 617 523 8016
1/4" = 1'-0"
3/1
3/2
02
0 1
:49:3
3 P
M
A-170179-27-00
3/13/20
REFLECTED CEILINGGENERAL NOTES, KEYS,LEGENDS
Vertex Pharmaceuticals, Inc.
V1 6th Floor Tissue CultureLabs
ISSUED FOR BID
MEP/FP Engineer
GENERAL CEILING NOTES
CEILING PLAN KEY
SCALE:
1/4" = 1'-0"1
LEVEL 6 REFLECTED CEILING PLAN
Issuance Schedule
Number Date Description
4 5 6
C.5
C
EQ-1
EQ-3
EQ-3
EQ-1EQ-1
EQ-1
EQ-2
EQ-2
EQ-2
EQ-2
EQ-1 EQ-1
EQ-1EQ-1
EQ-2
EQ-2
EQ-2EQ-2
EQ-3EQ-3
8"6"
6"
8"
6"
6"
Scale: Date Issued:
Project Number:
Isgenuity LLC500 Harrison Avenue, Suite 5FBoston, MA 02118Tel 617 419 4660Fax 617 419 4661www.isgenuity.com
Architect
NORTH
NOT FOR CONSTRUCTION
R.W. Sullivan EngineeringThe Schrafft Center529 Main Street, Suite 203Boston, MA 02129Tel 617 523 8227Fax 617 523 8016
1/4" = 1'-0"
3/1
3/2
02
0 1
:49:3
4 P
M
A-180179-27-00
3/13/20
FFE PLAN
Vertex Pharmaceuticals, Inc.
V1 6th Floor Tissue CultureLabs
ISSUED FOR BID
MEP/FP Engineer
EQUIPMENT SCHEDULE
TYPE
MARK TYPE WIDTH HEIGHT DEPTH
PURCHASED
BY
INSTALLED
BY COMMENTS
EQ-1 BIOSAFETY CABINET 6' - 5 1/2" 6' - 0" 2' - 6 3/8" OWNER CONTRACTOR
EQ-2 INCUBATOR 2' - 3" 3' - 6" 2' - 3" OWNER CONTRACTOR
EQ-3 U/C REFRIGERATOR 1' - 11" 2' - 9" 1' - 11" OWNER CONTRACTOR
Issuance Schedule
Number Date Description
SCALE:
1/4" = 1'-0"1
LEVEL 6 - FFE
BIOSAFETY CABINET
V
WALL BASE, TYP.
OT
CL
5'-0"
2'-0
"
CL
5'-6"
INCUBATOR
CO2
OT
UNDERCOUNTER FRIDGE
CL
6'-0
"
5'-0"
EO
CL
EO
CL
5'-6" 1'-6"
V
4'-0
"
2'-0" 2'-0" 2'-0" 1'-6"
EXISTING WINDOW
INCUBATOR
CL
5"
OT
LS
TST
INCUBATOR
V
CO2 CO2 CO2
RO/DI
METAL PAPER TOWEL DISP; MANUFACTURER TO MATCH PTD IN ROOM 6027
OPEN
EYEWASH
OT OT OT
6'-0
"
2'-0" 2'-6" 2'-6"
1'-7
"
CL CL CL
CL
4'-0
"
7'-0"
4'-0" 1'-6" 1'-6" 1'-6"
MOTT 30" X 30" PEGBOARD WITH TRAY; MANUFACTURER TO MATCH
PEGBOARD IN ROOM 6027
INCUBATORS
CO2 CO2
INC INC
UNDERCOUNTER FRIDGE
CL CL
2'-6"
6'-0
"
2'-6"
V
CL CL
EOEO
1'-6"5'-6"
4'-0
"
2'-0" 2'-0" 2'-0" 2'-0" INCUBATORS
EXISTING WINDOW
WALL BASE, TYP.
CO2
INC
CL
4'-0"
6'-0
"
OT
LS
6"
CL
TST
INCUBATOR
V
CO2
MOTT 30" X 30" PEGBOARD WITH TRAY; MANUFACTURER TO MATCH
PEGBOARD IN ROOM 6027
OPEN
RO/DIEYEWASH
INC
5'-0"
CL
6'-0
"
CL
1'-7
"
4'-0
"
5'-6"
4'-0" 1'-6" 2'-0" 2'-0"
METAL PAPER TOWEL DISP; MANUFACTURER TO MATCH PTD IN ROOM 6027
BIOSAFETY CABINET
V
OT
CL
5'-6"
CL
4'-9"
2'-0
"
OPEN
3'-7
"
CL
1'-6" 1'-6"
OPEN
3'-7
"
CL
1'-6" 1'-6"
OPEN
3'-7
"
CL
1'-6"END PANEL
TYP. VOICE / DATA OUTLETS
CL
CL
2' -
10"
3' -
4"
3' -
6"
4"
3' -
2"
COUNTER - DESK (WITH BACKSPLASH)
3' -
8"
COUNTER - STANDING (WITH BACKSPLASH)
4' -
2"
CL
CLCL
CL
COUNTER - STANDING (HIGH)(WITH BACKSPLASH)
5' -
0"
4' -
0"
1' -
6"
ELECTRICAL OUTLET
ELECTRICAL OUTLET ELECTRICAL OUTLET
5' -
6"
CL
HOOK STRIPADA ROBE HOOK
CL
VARIES
VARIOUS LENGTHS
CL
4' -
8"
THERMOSTAT
WALL PHONE
LIGHT SWITCH PLATE
AFI
XR-L
7' -
8"
NC
AIR FLOW INDICATOR
NURSE CALL LIGHT
X-RAY IN USE LIGHT
AUDIO / VISUALALARM
6' -
8"
4' -
0"
FIRE ALARM PULL STATION
CLCL
4' -
0"
LS
TYP. LIGHT SWITCH
CL
4' -
0"
SLC
TYP. LIGHTING CONTROL SENSOR
4' -
6"
TELEPHONE OUTLET THERMOSTAT
5' -
0"
TO
TST
AP
4' -
0"
ANNUNCIATION PANEL
TYP. ELECTRICALOUTLETS
CL
1' -
6"
1' -
6"
CL
CARD ACCESS
CL
4' -
0"
1' - 0"
4' -
6"
CL
GENERAL NOTE: HEIGHTS INDICATED ARE FOR GENERAL CONDITIONS, UNLESS OTHERWISE NOTED. REFER TO INTERIOR ELEVATIONS FOR SPECIFIC MOUNTING HEIGHTS.
TYP. EMERGENCYELECTRICAL
OUTLETS
CL
1' -
6"
3' -
0"
4"
2' -
6"
4"
EOOT
Scale: Date Issued:
Project Number:
Isgenuity LLC500 Harrison Avenue, Suite 5FBoston, MA 02118Tel 617 419 4660Fax 617 419 4661www.isgenuity.com
Architect
NOT FOR CONSTRUCTION
R.W. Sullivan EngineeringThe Schrafft Center529 Main Street, Suite 203Boston, MA 02129Tel 617 523 8227Fax 617 523 8016
1/4" = 1'-0"
3/1
3/2
02
0 1
:49:3
4 P
M
A-210179-27-00
3/13/20
INTERIOR ELEVATIONSGENERAL NOTES, KEYS,LEGENDS
Vertex Pharmaceuticals, Inc.
V1 6th Floor Tissue CultureLabs
ISSUED FOR BID
MEP/FP Engineer
1/4" = 1'-0"10ATISSUE LAB 6019 - A
10B 10C 10D
1/4" = 1'-0"20ATISSUE LAB 6029 - A
20B 20C 20D
Issuance Schedule
Number Date Description
1/4" = 1'-0"30AMONITORING LAB 6028 - A
30B 30C
TYPICAL MOUNTING HEIGHTS
MULTIPLE LAYERS OF GYPSUM BOARD (WHERE INDICATED)
MULTIPLE LAYERS OF JOINT SEALER AND BACKING WHERE MULTIPLE LAYERS OF GYPSUM BOARD ARE SHOWN
FLOOR RUNNER
3/8"
TY
PIC
AL
JOINT SEALER AND BACKING
-PROVIDE FIRE STOPPING AT FIRE RATED PARTITIONS
- PROVIDE SMOKE STOPPING AT SMOKE PARTITIONS
- PROVIDE ACOUSTICAL SEALANT AT ACOUSTICAL PARTITIONS
GYPSUM BOARD
SCHEDULED BASE
3/8"
PA
RT
ITIO
N A
S S
CH
ED
ULE
D
ADJACENT MATERIALS
JOINT SEALER AND BACKING
5" UNLESS OTHERWISE NOTED
BOOKENDS WHERE REQUIRED
METAL SHELF
SCHEDULED SHELVING BRACKET, TYP.
LOCATER CLIP ATTACHED TO SHELF (TYP.)
48" SCHEDULED SHELVING STANDARD - CUT TO SUIT FIELD CONDITIONS IF REQUIRED
CLEAR HEIGHT BETWEEN SHELVES
1' -
1"
TY
P.
1' - 0" TYP.
6" T
YP
.
PROVIDE BLOCKING IN WALL
CONFIRM DIMENSIONS MATCHES SHELVES IN ROOM 6027
MARINE EDGE WITH EASED EDGES
4"
3"
TOE KICK HEIGHT
TOE KICK DEPTH
FACE OF CASEWORK BELOW
2' - 6" BACKSPLASH
JOINT SEALANT
SCHEDULED WALL BASE
4"
SIDESPLASH
1"
3' -
0"
EPOXY
FILLER PANEL
1" EPOXY
DOOR AND WINDOW CONSTRUCTION:
ACOUS ACOUSTICAL CORE WOODAC ALUMINUM CLAD WOODAL ALUMINUM HC HOLLOW CORE WOODHM HOLLOW METALLL LEAD LINED FRAME SC SOLID CORE WOODSS STAINLESS STEELTG TEMPERED SAFETY GLASS
DOOR GLASS TYPE:
-- NO GLASS REQUIREDCR CLEAR WIREDFR FIRE RATED PER SPECIFICATIONSIG INSULATING GLASSLG LAMINATED GLASSTF CLEAR TEMPERED FLOATTI TEMPERED INSULATINGLE LEAD GLASS
FRAME CONSTRUCTION:
AC ALUMINUM CLAD WOODAL ALUMINUMPS PRESSED STEELSS STAINLESS STEELWD WOOD
DOOR FACING AND FINISH:
AF ALUMINUM FACTORY FINISHCC COPPER CLADDINGCL HARDWOOD, TRANSPARENT FINISHMF METAL FACTORY FINISHMP METAL PAINTEDWD WOOD PAINTED
FIRE RATING:
BLANK NO FIRE RATING REQUIREDA180 3 HOUR RATING ('A' LABEL REQUIRED)B60 1 HOUR RATING (B LABEL REQUIRED)B90 1- 1/2 HOUR RATING ('B' LABEL REQUIRED)C45 3/4 HOUR ('C' LABEL REQUIRED)20 1/3 HOUR RATING 30 1/2 HOUR RATING
REMARKS:
1. TRANSOM OR SIDELIGHT ADJACENT2. SPECIAL HEIGHT DOOR3. SPECIAL ALUMINUM DOOR AND FRAME4. SECURITY TIE IN REQUIREMENTS5. SPECIAL WOOD DOOR AND FRAME6. SOUND GASKETING7. WEATHERING STRIP8. MAGNETIC HOLD OPENS9. LIGHT GASKET10. FIELD MEASUREMENT REQUIRED11. DOUBLE ACTING REMOVE FRAME STOP12. LEAD LINING REQUIRED13. AUTOMATIC DOORS14. CODE ACCESS HARDWARE15. EXISTING DOOR16. STAINLESS STEEL KICK PLATE17. ROTON HINGE
SE
E S
CH
ED
ULE
SEE SCHEDULE
A SINGLEG HALF GLAZED
TEMPERED GLAZING
SEE SCHEDULE
6"4'
- 0
"
6" 6"
SE
E S
CH
ED
ULE
UNDERSIDE OF STRUCTURE
JOINT SEALER AND BACKING
PROVIDE CASING BEAD WHERE EXPOSED TO VIEW
SOUND ATTENUATION INSULATION
SUSPENDED CEILINGWHERE SCHEDULED
5/8" GYPSUM BOARD
SCHEDULED BASE
JOINT SEALER AND BACKING
TOP OF SLAB
BA
SE
PLA
NC
EIL
ING
HE
AD
G NO FIRE RESISTANCE RATINGNO ACOUSTICAL RATING
EXISTING PARTITION W/ NEW GWB
EXISTING WALL ASSEMBLY TO REMAIN
1/8" EASED EDGES
3/4" MARINE GRADE PLYWOOD SUBSTRATE
1" x 4" INTEGRAL BACK AND SIDE SPLASHES WITH EASED EDGE
PROVIDE BLOCKING
INTEGRAL SINK
4"EASED EDGE
1" EPOXY WITH MARINE GRADE PLYWOOD SUBSTRATE
2' - 6"
MARINE EDGE
TOE KICK HEIGHT
TOE KICK DEPTH
FACE OF CASEWORK BELOW
SCHEDULED WALL BASE
3"
4"
1"
3' -
0"
1 SINGLE DOOR 6019 (SALVAGED EXISTING):
4 HINGES TCA3786 5 X 4 1/2 26D MC1 LOCKSET 60 DG1 8237 LNW 1 1/4" CTE WBS RH 32D SA1 CYLINDER CORE DG1 6300 DO NOT DUPLICATE MK X 3 KEYS 15 SA1 DOOR STOP 446 US26D RO3 DOOR SILENCERS 608 GREY RO
Scale: Date Issued:
Project Number:
Isgenuity LLC500 Harrison Avenue, Suite 5FBoston, MA 02118Tel 617 419 4660Fax 617 419 4661www.isgenuity.com
Architect
NOT FOR CONSTRUCTION
R.W. Sullivan EngineeringThe Schrafft Center529 Main Street, Suite 203Boston, MA 02129Tel 617 523 8227Fax 617 523 8016
As indicated
3/1
3/2
02
0 1
:49:3
5 P
M
A-710179-27-00
3/13/20
TYPICAL PARTITIONDETAILS, DOOR DETAILS,CASEWORK DETAILS
Vertex Pharmaceuticals, Inc.
V1 6th Floor Tissue CultureLabs
ISSUED FOR BID
MEP/FP Engineer
SCALE:
SECTION DETAIL
3" = 1'-0"11 TYPICAL PARTITION AT BASE DETAIL
SCALE:
SECTION DETAIL
3" = 1'-0"12 TYPICAL GYPSUM BOARD PARTITION / ADJACENT MATERIAL
SCALE:
PLAN DETAIL
3/4" = 1'-0"13 DOOR FRAME LOCATION
Issuance Schedule
Number Date Description
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"14 ADJUSTABLE SHELVES- SECTION
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"20 STRAIGHT BENCH COUNTERTOP ABOVE CABINETS
DOOR ABBREVIATIONSDOOR FRAME TYPESDOOR PANEL TYPES
LOCATION DOOR FRAME
RATING HDWR COMMENTSMARK ROOM NAME
OPENING PANEL
TYPE MATLWIDTH HEIGHT TYPE MATL THICK
6019-A TISSUE CULTURE LAB 3' - 6" 8' - 0" G MP 1 3/4" EXISTING EXISTING REUSE SALVAGED
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"10 PARTITION TYPE G
SCALE:
SECTION DETAIL
1 1/2" = 1'-0"21 TYPICAL LAB SINK
DOOR HARDWARE
1. ALL WORK TO OCCUR AT OWNER'S CONVENIENCE. NOTIFY OWNER WELL IN ADVANCE OF
BEGINNING ANY PHASE OF WORK.
2. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND SYSTEMS TO WHICH NEW
CONNECTIONS ARE MADE. LOCATIONS OF PIPING, ELEVATIONS, SIZES, ETC. HAVE BEEN
OBTAINED FROM THE BEST SOURCES AVAILABLE AND MUST BE FIELD VERIFIED PRIOR TO
COMMENCING WORK IN AREAS WHERE RENOVATIONS ARE TO TAKE PLACE. NOTIFY THE
ARCHITECT FOR DIRECTION IF ANY DIFFERENCES ARISE BETWEEN ON-SITE CONDITIONS AND
CONDITIONS SHOWN ON THE DRAWINGS AS EXISTING.
3. NEW WORK IS DRAWN IN HEAVILY OR IS NOTED ON PLANS. REFER TO ARCHITECTURAL
DETAILED PLANS FOR ADDITIONAL INFORMATION.
4. EXISTING FIRE PROTECTION PIPING AND EQUIPMENT ARE DRAWN LIGHTLY OR ARE NOTED ON
PLANS.
5. EXISTING SPRINKLER PIPING, HEADS AND DEVICES TO BE REMOVED ARE DRAWN
CROSSHATCHED OR ARE NOTED ON PLANS.
6. INCLUDE THE COST OF ALL ALARM SHUTDOWNS & FIRE WATCHES IN THE BID FOR THIS WORK.
NOTIFY OWNER'S ALARM COMPANY SUFFICIENTLY IN ADVANCE OF SHUTDOWNS TO PERMIT
ALARM COMPANY TO PERFORM THE SHUTDOWN ON SCHEDULE.
7. COORDINATE SPRINKLER SYSTEM SHUTDOWN WITH OWNER AND GENERAL CONTRACTOR,
PERFORM SHUTDOWNS ON PREMIUM TIME IF NECESSARY.
NOTIFY OWNER AT LEAST (1) WEEK PRIOR TO ANY SHUTDOWN.
8. AFTER ANY SHUTDOWN, RETURN REMAINING SYSTEM TO ACTIVE CONDITION AS SOON AS
POSSIBLE.
9. IN NO CASE SHALL THE SPRINKLER SYSTEM BE INACTIVE AFTER WORKING HOURS.
10. IT SHALL BE THE RESPONSIBILITY OF THE FIRE PROTECTION SUBCONTRACTOR DURING
DEMOLITION TO SUPPORT AND PROTECT FROM DAMAGE ALL FIRE PROTECTION SYSTEMS
WHICH ARE EXISTING TO REMAIN. FIRE PROTECTION SYSTEMS SHALL BE SUPPORTED IN
ACCORDANCE WITH NFPA 13.
11. IN AREAS WITH FINISHED CEILING, CONCEALED SPRINKLER HEADS SHALL BE USED UNLESS
OTHERWISE NOTED.
12. IN AREAS WITHOUT FINISHED CEILING, UPRIGHT SPRINKLER HEADS SHALL BE USED UNLESS
OTHERWISE NOTED.
13. PROVIDE HEAD GUARDS IN ALL ANY POSSIBLE MECHANICAL & STORAGE ROOMS.
14. THE FIRE PROTECTION SUBCONTRACTOR SHALL REFER TO ALL ARCHITECTURAL DRAWINGS
FOR COMPLETE COORDINATION OF SPRINKLER SYSTEM WITH ALL WALLS, SOFFITS, CEILING
TYPES AND CEILING HEIGHTS.
15. ALL SPRINKLER HEAD TEMPERATURE RATINGS SHALL BE COORDINATED BY THE FIRE
PROTECTION SUBCONTRACTOR BASED ON THE INTENDED USE OF EACH ROOM/AREA IN WHICH
THE SPRINKLER HEAD(S) IS LOCATED.
16. FIRESTOP ALL RESULTING PENETRATIONS IN RATED AND ANY FULL HEIGHT PARTITIONS.
17. SPRINKLER HEADS SUPPLIED BY FLEXIBLE HOSES TO MAY BE CAREFULLY REMOVED AND
RELOCATED.
18. SPRINKLER HEADS MUST BE COMPLETELY COORDINATED WITH FINAL LIGHTING LAYOUTS AND
DIFFUSER LOCATIONS TO ARRIVE AT A SUITABLE PATTERN CONSISTENT WITH PROPER
SPRINKLER HEAD COVERAGE. SPRINKLER HEADS TO BE LOCATED IN CENTER OF CEILING TILE.
19. PRIOR TO THE START OF CORING ANY STRUCTURAL MEMBER, IF ANY, THE FIRE PROTECTION
SUBCONTRACTOR SHALL COORDINATE LOCATION OF PENETRATION WITH STRUCTURAL
ENGINEER AND GENERAL CONTRACTOR. THE FIRE PROTECTION SUBCONTRACTOR SHALL
PREPARE AND SUBMIT TO STRUCTURAL ENGINEER AND ARCHITECT A SET OF PENETRATION
DRAWINGS DURING COORDINATION DRAWING REVIEW PERIOD.
20. SPRINKLER SYSTEM AND ALL COMPONENTS, DESIGNED IN ACCORDANCE WITH NFPA 13, STATE
BUILDING CODE, CITY OF BOSTON REQUIREMENTS, BUILDING OWNER'S INSURANCE COMPANY
AND OTHER APPLICABLE NFPA STANDARDS GOVERNING THE INSTALLATION OF SPRINKLER
SYSTEMS, SYSTEM DRAINS, ETC. THE FIRE PROTECTION SUBCONTRACTOR SHALL SUBMIT HIS
SHOP DRAWINGS TO LOCAL FIRE DEPARTMENT, BUILDING DEPARTMENT AND OWNER'S
INSURANCE COMPANY FOR APPROVAL.
21. ALL MATERIALS & COMPONENTS SHALL BE UL LISTED AND APPROVED BY OWNER'S INSURANCE
COMPANY.
22. ALL PIPING, VALVES AND FITTINGS NECESSARY TO COORDINATE THIS SYSTEM WITH NEW DUCT
WORK, LIGHTING, ARCHITECTURAL FINISHES AND STRUCTURAL MEMBERS SHALL BE PROVIDED
BY THE FIRE PROTECTION CONTRACTOR.
23. THE FIRE PROTECTION SYSTEM SHALL BE COMPLETELY COORDINATED WITH ALL OTHER
TRADES BEFORE INSTALLATION BEGINS.
24. DO NOT RUN ANY PIPING WITHIN 3'-0" ABOVE OR IN FRONT OF ABOVE-CEILING HVAC BOXES.
PROVIDE PIPE FITTINGS, OFFSETS ETC AS REQUIRED.
25. SPRINKLER PIPING SHALL NOT RUN ABOVE ANY ELECTRICAL, TELEPHONE, IT PANELS OR GEAR
ROOMS.
26. PROVIDE-WRAP-AROUND-TYPE PIPE LABELING ON ALL EXISTING TO REMAIN PIPING IN ALL
SCOPE OF WORK AREAS.
27. PROVIDE FULL SPRINKLER PROTECTION DURING CONSTRUCTION.
IN AREAS WHERE SEVERAL DIFFERENT OCCUPANCIES EXIST, THE SPRINKLER SYSTEMS SHALL BE DESIGNED TO MEET THE MOST
HYDRAULICALLY DEMANDING DENSITY AND AREA REQUIREMENTS. PROVIDE A MINIMUM 10 PSI CUSHION FOR ALL HYDRAULIC
CALCULATIONS.
PROVIDE AUTOMATIC SPRINKLER SYSTEMS OVER ENTIRE FLOOR AND CEILING WITHIN THE SCOPE OF WORK. SYSTEM SHALL
BE BASED ON NFPA STANDARDS AND OWNER'S INSURANCE COMPANY COVERAGE REQUIREMENTS AND ACCORDING TO THE
FOLLOWING GENERAL GUIDELINES:
LOCATION DENSITY AND AREA
1. OPEN OFFICE SPACE, CONFERENCE ROOM, BATHROOMS,
ETC. (LIGHT HAZARD)
0.10 GPM/FT² OVER 1500 FT²
WITH A 100 GPM HOSE ALLOWANCE
2. LABORATORY SPACE (ORDINARY HAZARD GROUP I)
0.15 GPM/FT² OVER 1500 FT²
WITH A 250 GPM HOSE ALLOWANCE
FIRE PROTECTION GENERAL NOTES
SPR SPRINKLER PIPING
PIPE CAP
PIPE CONTINUATION
PIPE UP THRU SLAB OF FLOOR ABOVE
PIPE DROP OR RISE
VIF VERIFY IN FIELD
NTS NOT TO SCALE
PIPE DOWN THRU FLOOR SHOWN
ETBR EXISTING TO BE REMOVED PIPE
ETR EXISTING TO REMAIN PIPE
CTECONNECT TO EXISTING
SPR
FIRE PROTECTION LEGEND
SYMBOL ABBR DESCRIPTION
B.O.B. BOTTOM OF BEAM
B.O.P. BOTTOM OF PIPE
ETR EXISTING TO REMAIN
ETBR EXISTING TO BE REMOVED
CTE CONNECT TO EXISTING
SPR
NEW EXISTING
SPRINKLER HEAD SCHEDULE
SYMBOL
RESPONSE
TYPE
DESCRIPTION MANUFACTURER TEMPERATURE MODEL # K-FACTOR LOCATION COMMENTS
QUICK
RESPONSE
CONCEALED SPRINKLER RELIABLE
135°F COVER
165°F HEAD
G5-56 5.6
ALL AREAS WITH FINISHED CEILINGS UNLESS
NOTED OTHERWISE
1. WHITE COVER PLATE IN ALL AREAS2)
2. PROVIDE AQUAFLEX STAINLESS STEEL SPRINKLER
HOSE AND FITTING WITH CEILING GRID MOUNT BRACKET
- EXISTING TO BE REMOVED - - - - - -
- EXISTING TO REMAIN SPRINKLER - - - - - -
THE FIRE PROTECTION SUBCONTRACTOR SHALL COORDINATE THE FINISHES OF ALL SPRINKLER HEADS WITH THE ARCHITECT PRIOR TO THE START OF WORK.
NTS1
4" MIN
18
" M
IN
STORAGE
STORAGE
SPRINKLER HEAD
4" MIN
SHELVING
SPRINKLER HEAD
4" MIN
CEILING
WALL
WALL
CEILING
SPRINKLER HEAD
C
D
A
A ≥ 3*C or 3*D
WHICHEVER IS LARGER
JOIST
B
A
OBSTRUCTION
CEILING
CEILING
SPRINKLER HEAD
SPRINKLER HEAD
B
A
CEILING
OBSTRUCTION
SPRINKLER HEAD
WALL
A ≥ (D - 8") + B
WHERE: D ≤ 30"
D
18" Minimum
(No Max)
CEILING
OBSTRUCTION
SPRINKLER HEAD
WALL
24" Max
NO ADDITIONAL
PROTECTION IS
REQUIRED
1. SPRINKLER IN CLOSET
8.6.3.3 Minimum Distances from Walls. Sprinklers shall be located
a minimum of 4 in. (102 mm) from a wall.
2. Ceiling Mounted Obstructions
8.6.5.1.2* Sprinklers shall be arranged to comply with on of the
following arrangements:
1) Subsection 8.5.5.2, Table 8.6.5.1.2, and Figure 8.6.5.1.2(a)
shall be followed.
2) Sprinklers shall be permitted to be spaced on opposite sides
of obstructions not exceeding 4 ft (1.2 m) in width, provided
the distance from the centerline of the obstruction to the
sprinklers does not exceed one-half the allowable distance
permitted between sprinklers.
3) Obstructions located against the wall and that are not over
30 in. (762 mm) in width shall be permitted to be protected in
accordance with Figure 8.6.5.1.2(b) below.
4) Obstructions located against the wall and that are not over
24 in. (610 mm) in width shall be permitted to be protected in
accordance with Figure 8.6.5.1.2(c) below. The maximum
distance between the sprinkler and the wall shall be
measured from the sprinkler to the wall behind the
obstruction and not to the face of the obstruction.
A.8.6.5.1.2 The intent of 8.6.5.1.2(3) is to apply to soffits that are
located within the 18 in. (457 mm) plane from the sprinkler
deflector. A soffit or other obstruction (i.e., Shelf) located
against a wall that is located entirely below the 18 in. (457
mm) plane from the sprinkler deflector should be in
accordance with 8.6.5.3.3. (See Figure A.8.6.5.1.2)
3. The Three Times Rule
A.8.6.5.2.1.3 The rules of 8.6.5.2.1.3 (known as the "Three Times
Rule") have been written to apply to obstructions where
the sprinkler can be expected to get water to both sides of
the obstruction without allowing a significant dry shadow
on the other side of the obstruction. This works for small
non-continuous obstructions and for continuous
obstructions where the sprinkler can throw water over and
under the obstruction, such as the bottom chord of an
open truss or joist. For solid continuous obstructions, such
as a beam, the Three Times Rule is ineffective since the
sprinkler cannot throw water over and under the
obstruction. Sufficient water must be thrown under the
obstruction to adequately cover the floor area on the other
side of the obstruction. To ensure this, compliance with the
rules of 8.6.5.1.2 is necessary.
A.8.6.5.3.3 When obstructions are located more than 18 in. (457
mm) below the sprinkler deflector, an adequate spray
pattern develops and obstructions up to and including 4 ft
(1.2 m) wide do not require additional protection
underneath. examples are ducts, decks, open grate
flooring, catwalks, cutting tables, overhead doors, soffits,
ceiling panels, and other similar obstructions. The width of
an object is the lesser of the two horizontal dimensions
(with the length being the longer horizontal dimension).
Sprinkler protection is not required under objects where
the length is greater than 4 ft (1.2 m) and the width is 4 ft
(1.2 m) or less.
4. Clearance to Storage
8.6.6 Clearance to Storage (Standard Pendent and Upright Spray
Sprinklers)
8.6.6.1 The clearance between the deflector and the top of the
storage shall be 18 in. (457 mm) or greater.
8.6.6.2 The 18 in. (457 mm) dimension shall not limit the height of
shelving on a wall or shelving against a wall in accordance
with 8.6.6, 8.7.6, 8.8.6 and Section 8.9.
8.6.6.2.1 Where shelving is installed on a wall and is not directly
below sprinklers, the shelves, including storage thereon,
shall extend above the level of a plane located 18 in. (457
mm) below ceiling sprinkler deflectors.
8,6,6,2,2 Shelving and any storage thereon, directly below the
sprinklers shall not extend above a plane located 18 in.
(457 mm) below the ceiling sprinkler deflectors.
8.6.6.3 Where other standards specify greater clearance to
storage minimums, they shall be followed.
Note: Maintain Clearances as indicated by Rule #4 - Clearance to Storage
Distance from Sprinklers to Side of
Obstruction (A)
Maximum Allowable
Distance of Deflector
Above Bottom of
Obstruction (B)
(in.)
Less than 1 ft 0
1 ft to less than 1 ft 6 in. 2
1
2
1 ft 6 in. to less than 2 ft 3
1
2
2 ft to less than 2 ft 6 in. 5
1
2
2 ft 6 in. to less than 3 ft 7
1
2
3 ft to less than 3 ft 6 in. 9
1
2
3 ft 6 in. to less than 4 ft 12
4 ft to less than 4 ft 6 in. 14
4 ft 6 in. to less than 5 ft 16
1
2
5 ft to less than 5 ft 6 in. 18
5 ft 6 in. to less than 6 ft 20
6 ft to less than 6 ft 6 in. 24
6 ft 6 in. to less than 7 ft 30
7 ft to less than 7 ft 6 in. 35
For S.I. Units, 1 in. = 25.4 mm; 1 ft = 0.3048 m
Note: For A and B, refer to Figure 8.6.5.1.2(a).
Table 8.6.5.1.2
Figure 8.6.5.1.2(a)
Figure 8.6.5.1.2(b)
Figure 8.6.5.1.2(c)
NFPA 13 - SPRINKLER OBSTRUCTION GUIDELINES
NOTES:
1. REFER TO CUT SHEET FOR MAXIMUM TOTAL BENDS FOR ASSOCIATED HOSE LENGTH
BRAIDED FLEXIBLE SPRINKLER CONNECTION
2 NTS
END BRACKET ASSEMBLY
SPRINKLER HEAD
RELIABLE MODEL G5-56
REDUCING OUTLET
NUT
VICTAULIC AQUAFLEX
STAINLESS STEEL FLEXIBLE
BRAIDED HOSE
REFER TO CUT SHEET FOR
MAXIMUM TOTAL BENDS
1"NPT THREADS
HANGER SUPPORT FROM BUILDING
STRUCTURES WITH SURGE
RESTRAINT PER NFPA ON ALL ARM
OVERS GREATER THAN 12" AND WITH
SYSTEM PRESSURE OVER 100 PSI.
NIPPLE UP
BRANCH OR MAIN
PIPE HANGERS
NOTE:
ALL HANGERS, HARDWARE, AND RODS SHALL BE ELECTRO GALVANIZED
NTS
THE EXISTING SPRINKLER SYSTEM SHALL REMAIN ACTIVE
DURING CONSTRUCTION. UPRIGHT SPRINKLER HEADS SHALL BE
INSTALLED AT THE START OF DEMOLITION, PROVIDED IN
ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13, AND BE
MAINTAINED THROUGHOUT CONSTRUCTION. IT IS THE GENERAL
CONTRACTOR'S RESPONSIBILITY TO MAINTAIN/RE-WORK THE
FIRE SPRINKLER SYSTEM LAYOUT THROUGHOUT ALL PHASES OF
CONSTRUCTION AS NEW WALLS ARE ERECTED AND EGRESS
PATTERNS ARE REVISED.
2 3
ELECTRO
GALVANIZED CARBON
STEEL SWIVEL RING
STRAP HANGER
ELECTRO
GALVANIZED
THREADED ROD
ELECTRO GALVANIZED
STEEL REVERSIBLE
BEAM CLAMP
-TYPE 23
LOCK NUT
BEAM, PURLIN OR TRUSS
HANGER (TYP)
SINGLE NUT
(TYP)
DOUBLE NUT (TYP)
ELECTRO
GALVANIZED
THREADED ROD
ANCHOR SECURELY TO
BUILDING STRUCTURE
FP-001
FIRE PROTECTION
LEGEND, DETAILS,
SCHEDULE &
GENERAL NOTES
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
NORTH
ISSUED FOR BID
3/2/20NONE
Drawn By: JES Checked By: WMN
V1 6th Floor Tissue CultureLabs
:3/13/20
4 5 6
D
C.5
C
SCOPE OF WORK
TISSUE CULTURELAB6029
TISSUE CULTURELAB6019
MONITORING LAB6028
EQUIPMENT LAB6027
CORRIDOR6002
EQUIPMENTCORRIDOR
6030
STORAGE ROOM6031
SOLVENT STORAGE6032
CORRIDOR6037
LAB SUPPLY ROOM6035
ELEC ROOM6036
PLUMBING CLOSET621
COLD ROOM6017
MICROSCOPEROOM6022
EQUIPMENTCORRIDOR
6021
EQUIPMENT ROOM6023
EQUIPMENTCORRIDOR
6018
CORRIDOR6020
CORRIDOR6026
BIOSAFETY CABINET
BIOSAFETY CABINET
STACKED INCUBATOR
STACKED INCUBATORS
STACKED INCUBATOR
BIOSAFETY CABINET
BIOSAFETY CABINET
STACKED INCUBATOR
V
V
V
V
6019
-A
V
V
3"
SPR
SP
R
SP
R
SP
R
SP
R
SP
R
SP
R
SPR
SP
R
SCOPE OF
WORK.
3"
SP
RS
PR
SP
R
EXISTING UPRIGHT SPRINKLER HEAD AND ASSOCIATED
RISE NIPPLE SHALL BE REMOVED & CAPPED.
1
FIRE PROTECTION DEMOLITION NOTES
EXISTING UPRIGHT SPRINKLER HEAD BELOW DUCTWORK AND
ASSOCIATED RISE NIPPLE SHALL BE REMOVED BACK TO
1"SPR BRANCH LINE OUTLET. RESULTING 1"SPR THE OUTLET
WILL BE USED FOR NEW WORK CONNECTION.
3
EXISTING SPRINKLER HEAD AND ASSOCIATED FLEX HOSE,
CEILING TILE MOUNT BRACKET, AND COUPLING SHALL
REMAIN (TYPICAL)
4
EXISTING COLD ROOM DRY SPRINKLER HEADS AND
ASSOCIATED PIPING SHALL REMAIN.
5
EXISTING UPRIGHT SPRINKLER HEAD AND ASSOCIATED
RISE NIPPLE SHALL BE REMOVED, RESULTING 1"SPR
BRANCH OUTLET WILL BE USED FOR NEW WORK
CONNECTION.
2
1
3
2
1
3
ETR
ETR
ETR
ETR
2
2
1
2
1
2
2
44
4
4
5
5
ETR
ETR
ETR
1"
1"
1"
1"
1"
3"
3"
3"3"
3"
3"
SP
R
SP
R
SP
R
SP
R
SPR
SP
R
SP
R
SP
R
SPR
SP
R
SP
R
SP
R
SPR
SP
R
SP
R
SP
R
SP
R
SPR
SPR
SP
R
SPR
SP
R
SP
R
SP
R
SP
R
SPR
SP
R
SP
R
1
3
4
5
2
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
FIRE PROTECTION
LEVEL 6
DEMOLITION PLAN
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
KEY PLAN
1 2 3 5 7
8
A.7
B
C
C.5
E
F
G
OFFICE6010
OFFICE6011
OFFICE6012
DSELAB6016
6019
MICROSCOPEROOM6022
EQUIPMENTLAB6027
MONITORINGLAB6028
EQUIPMENTLAB6029
STORAGEROOM6031
SOLVENTSTORAGE6032
GLASSWASH6069
OPENOFFICEAREA6063
CELLCULTURE6058
MASSSPEC6057
OPEN LAB6056
EQUIPMENTCORRIDOR
6053
DNAROOM6055
TISSUECULTURE6054
6050
EQUIPMENT6048
STORAGE/FREEZERROOM6045
HUMANBIOLOGY
LABORATORY6046
OFFICE6042
OFFICE6043
EQUIPMENTROOM6039
STABILITYCHAMBER
6040
MASSSPEC6038
MASSSPEC6025
ELECROOM6036
LABSUPPLYROOM6035
BIOREPOSITORYROOM6068
SAMPLERECEIVING
ROOM6074
CONFERENCE6067
CONFERENCE6003
CONFERENCE6004
CONFERENCE6005
VIPERLAB6014
EQUIPMENTCORRIDOR
6021
EQUIPMENTROOM6023
COLDROOM6047
COLDROOM6052
MEETINGAREA6059
OPENOFFICEAREA6007
INNOVATIONBAR6008
COPY6009
OPENOFFICEAREA6013
EQUIPMENTCORRIDOR
6018
DSE LAB6015
COLDROOM6017
EQUIPMENTCORRIDOR
6030
CORRIDOR6002
CORRIDOR6001
CORRIDOR6075
CORRIDOR6073
CORRIDOR6006
OPENOFFICEAREA6041
TEL/DATAIDF6072
CORRIDOR6071
CORRIDOR6037
D
E5
E6
E3
4
STORAGE6060
STORAGE6064
KITCHEN6065
BREAKRM6066
MEDIAPREPROOM6062
POD6033
POD6034
COPY/MAIL6044
CORRIDOR6026
CORRIDOR6020
CONFERENCE6061
6
STAIR 1S1-6
SERVICEELEVATOR
LOBBY602
STAIR 2S2-6
STAIR 3S3-6
ELEV #2
ELEV #3
ELEV #4
ELEV #8
ELEV #7
ELEV #6
ELEV #5
MECH.PIPING606
NORMALELECTRICAL
ROOM604
PLUMB.CLOSET621
LIFESAFETY605
PLUMB.CLOSET620
JANITOR607
MEN610
WOMEN609
SHOWER608
BIOWASTESTORAGE
651
EQUIPMENTLAB
CLINICALBIOMARKERS
OPEN LAB
ELEVATORLOBBY601
CORRIDOR6049
IMPORTANT NOTE:
SCOPE OF WORK
NORTH
ISSUED FOR BID
3/2/20
1
4
" = 1'-0"
FP-101
SCALE:
1/4" = 1'-0"1 FIRE PROTECTION LEVEL 6 DEMOLITION PLAN
Drawn By: JES Checked By: WMN
V1 6th Floor Tissue CultureLabs
:3/13/20
4 5 6
D
C.5
C
TISSUE CULTURELAB6029
TISSUE CULTURELAB6019
MONITORING LAB6028
EQUIPMENT LAB6027
CORRIDOR6002
EQUIPMENTCORRIDOR
6030
STORAGE ROOM6031
SOLVENT STORAGE6032
CORRIDOR6037
LAB SUPPLY ROOM6035
ELEC ROOM6036
PLUMBING CLOSET621
COLD ROOM6017
MICROSCOPEROOM6022
EQUIPMENTCORRIDOR
6021
EQUIPMENT ROOM6023
EQUIPMENTCORRIDOR
6018
CORRIDOR6020
CORRIDOR6026
6019
-A
3"
SPR
3"
3"
3"3"
3"
3"
SP
R
SP
R
SP
R
SP
R
SP
R
SPR
SP
R
SP
R
SP
R
SP
R
SP
R
SP
R
SP
R
SPR
SP
R
SPR
SP
R
SP
R
SP
R
SPR
SP
R
SP
R
SP
R
SP
R
SPR
SPR
SP
R
SPR
SP
R
SP
R
SP
R
SP
R
SPR
SP
R
SP
R
SP
R
SCOPE OF
WORK.
3"
SP
RS
PR
SP
R
CAP 1"SPR BRANCH OUTLET.1
FIRE PROTECTION DEMOLITION NOTES
CONNECT TO 1"SPR BRANCH OUTLET BELOW DUCTWORK
WITH NEW SPR FLEX HOSE AND INSTALL NEW FLEX
CONCEALED SPR HEAD AND CEILING TILE MOUNT BRACKET.
3
EXISTING SPRINKLER HEAD AND ASSOCIATED FLEX HOSE,
BRACKET, AND COUPLING SHALL REMAIN (TYPICAL)
4
EXISTING DRY SPRINKLER HEAD AND ASSOCIATED PIPING
SHALL REMAIN.
5
CONNECT TO 1"SPR BRANCH OUTLET, PROVIDE ARM
OVER AND EXTEND TO NEW LOCATION, INSTALL NEW
FLEX CONCEALED SPR HEAD WITH FLEX HOSE AND
CEILING TILE MOUNT BRACKET.
2
3
2
3
ETR
ETR
ETR
ETR
2
2
1
2
2
2
44
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5
5
4
4
4
4
4
4
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
ETR
1"
1"
1"
1"
1"
1
1
1
4 5 6
D
C.5
C
9' - 0"ACT
9' - 0"ACT
EXISTING TO REMAIN
UNLESS OTHERWISE
NOTED
FIRE PROTECTION
LEVEL 6
NEW WORK PLAN
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
KEY PLAN
1 2 3 5 7
8
A.7
B
C
C.5
E
F
G
OFFICE6010
OFFICE6011
OFFICE6012
DSELAB6016
6019
MICROSCOPEROOM6022
EQUIPMENTLAB6027
MONITORINGLAB6028
EQUIPMENTLAB6029
STORAGEROOM6031
SOLVENTSTORAGE6032
GLASSWASH6069
OPENOFFICEAREA6063
CELLCULTURE6058
MASSSPEC6057
OPEN LAB6056
EQUIPMENTCORRIDOR
6053
DNAROOM6055
TISSUECULTURE6054
6050
EQUIPMENT6048
STORAGE/FREEZERROOM6045
HUMANBIOLOGY
LABORATORY6046
OFFICE6042
OFFICE6043
EQUIPMENTROOM6039
STABILITYCHAMBER
6040
MASSSPEC6038
MASSSPEC6025
ELECROOM6036
LABSUPPLYROOM6035
BIOREPOSITORYROOM6068
SAMPLERECEIVING
ROOM6074
CONFERENCE6067
CONFERENCE6003
CONFERENCE6004
CONFERENCE6005
VIPERLAB6014
EQUIPMENTCORRIDOR
6021
EQUIPMENTROOM6023
COLDROOM6047
COLDROOM6052
MEETINGAREA6059
OPENOFFICEAREA6007
INNOVATIONBAR6008
COPY6009
OPENOFFICEAREA6013
EQUIPMENTCORRIDOR
6018
DSE LAB6015
COLDROOM6017
EQUIPMENTCORRIDOR
6030
CORRIDOR6002
CORRIDOR6001
CORRIDOR6075
CORRIDOR6073
CORRIDOR6006
OPENOFFICEAREA6041
TEL/DATAIDF6072
CORRIDOR6071
CORRIDOR6037
D
E5
E6
E3
4
STORAGE6060
STORAGE6064
KITCHEN6065
BREAKRM6066
MEDIAPREPROOM6062
POD6033
POD6034
COPY/MAIL6044
CORRIDOR6026
CORRIDOR6020
CONFERENCE6061
6
STAIR 1S1-6
SERVICEELEVATOR
LOBBY602
STAIR 2S2-6
STAIR 3S3-6
ELEV #2
ELEV #3
ELEV #4
ELEV #8
ELEV #7
ELEV #6
ELEV #5
MECH.PIPING606
NORMALELECTRICAL
ROOM604
PLUMB.CLOSET621
LIFESAFETY605
PLUMB.CLOSET620
JANITOR607
MEN610
WOMEN609
SHOWER608
BIOWASTESTORAGE
651
EQUIPMENTLAB
CLINICALBIOMARKERS
OPEN LAB
ELEVATORLOBBY601
CORRIDOR6049
IMPORTANT NOTE:
SCOPE OF WORK
NORTH
ISSUED FOR BID
3/2/20
1
4
" = 1'-0"
FP-201
SCALE:
1/4" = 1'-0"1 FIRE PROTECTION LEVEL 6 NEW WORK PLAN
Drawn By: JES Checked By: WMN
V1 6th Floor Tissue CultureLabs
:3/13/20
BALL VALVE W/HOSE
BIBB END, BRONZE
CAP AND CHAIN
SUPPLY PIPING (TYP.)
RETURN PIPING (TYP.)
BALL VALVE
GLOBE VALVE
BALANCING VALVE
ANGLE GLOBE VALVE
PRESSURE REDUCING
VALVE
HORIZONTAL CHECK
VALVE
2-WAY CONTROL
VALVE
3-WAY CONTROL
VALVE
BUTTERFLY VALVE
QUICK CLOSING VALVE
W/ FUSIBLE LINK
SELF CONTAINED
RADIATION VALVE
"Y" STRAINER
"Y" STRAINER W/ BLOW
DOWN
GATE VALVE
GATE VALVE W/ HOSE
BIBB END, BRONZE
CAP & CHAIN
PRESSURE REDUCING
VALVE
EXPANSION JOINT
PRESSURE RELIEF
VALVE
DIRECTION OF FLOW
PIPE DROP
PIPE RISE/DROP
PIPE RISE/DROP
PENETRATION
BRANCH CONNECTION
BOTTOM CONNECTION
45° OR 90°
CAPPED PIPE
GRAPHIC BREAK &/OR
CONTINUATION
UNION
FLEX PIPE
CONNECTOR
AIR VENT (AUTOMATIC)
AIR VENT (MANUAL)
FLOW SWITCH
PRESSURE SWITCH
THERMOMETER
THERMOMETER WELL
PRESS./ TEMP.
TAP(PETE'S PLUG)
PRESSURE GAUGE
PRESSURE GAUGE W/
COIL SYPHON
PRESSURE GAUGE W/
DAMPENER
IN LINE PUMP
BASKET STRAINER
BUCKET TRAP
THERMOSTATIC TRAP
FLOAT &
THERMOSTATIC TRAP
& VALVE TRAIN
DIRT LEG
PITCH UP/DOWN IN
DIRECTION OF ARROW
PIPE GUIDE
PIPE ANCHOR
FLANGES
REDUCED PRESSURE
BACKFLOW PREVENTER
CLEAN-OUT FOR
CONDENSATE
DRAIN
MV
PT
TW
UP
xxx
xxx
xxx
X
X
X
X
X
DESIGNATION
NUMBER
MAXIMUM CFM
MINIMUM CFM
ELECTRIC kW
VAV BOX
DENOTES EQUIPMENT
NOT REQUIRING
ELECTRICAL INPUT
DENOTES EQUIPMENT
REQUIRING ELECTRICAL
INPUT
DENOTES EQUIPMENT
REQUIRING ELECTRICAL
INPUT
DENOTES HVAC
DUCTWORK RISER
DENOTES CONTROL
DEVICES
AIR DISTRIBUTION
DEVICE
NECK SIZE
FLOW RATE (CFM)
GENERAL SYMBOLS
REVISION NUMBER
THERMOSTAT
HUMIDISTAT (MOUNT 54"
AFF)
SPEED SWITCH
SMOKE DETECTOR
REMOTE SENSOR
CONNECT TO EXISTING
EXTENT OF REMOVAL
SUPPLY AIR ARROW
RETURN/EXHAUST AIR
ARROW
UNDERCUT DOOR
DOOR LOUVER
UC
DL
CARBON MONOXIDE
SENSOR
(QUANTITY) TYPE
xxx
XXX
SUPPLY AIR DUCT TURN
90° UP
SUPPLY AIR DUCT TURN
90° DOWN
RETURN AIR DUCT TURN
90° UP
RETURN AIR DUCT TURN
90° DOWN
ROUND DUCT TURN 90°
UP
ROUND DUCT TURN 90°
DOWN
SUPPLY AIR DUCT UP &
PENETRATING FLOOR
ABOVE
RETURN AIR DUCT UP
& PENETRATING
FLOOR ABOVE
ROUND DUCT UP &
PENETRATING FLOOR
ABOVE
VOLUME DAMPER
COMBINATION FIRE AND
SMOKE DAMPER
BACKDRAFT DAMPER
FIRE DAMPER
SMOKE DAMPER
AUTOMATIC CONTROL
DAMPER (ELECTRIC OR
PNEUMATIC)
DUCT MOUNTED
HUMIDIFIER
DOUBLE LINE SINGLE LINE
FLEXIBLE DUCT
FLEXIBLE CONNECTION
(RECT.) BREAK &/OR
CONTINUATION (ROUND)
EXISTING DUCTWORK AND
EQUIPMENT TO REMAIN
EXISTING DUCTWORK
AND/OR EQUIP. TO BE
REMOVED
CONCENTRIC REDUCER
ECCENTRIC REDUCER
RECTANGULAR TO
ROUND TRANSITION
DUCT W/ 1" ACOUSTICAL
LINER
(RECT.)
VERTICAL OFFSET UP OR
DOWN (ARROW INDICATES
DIRECTION OF FLOW)
(ROUND)
DUCT REMOVED AND HOLE
CAPPED/BLANKED OFF
HORIZONTAL OFFSET
SMOOTH RADIUS ELBOW
ELBOW W/ TURNING VANES
TRUNK TEE
SQUARE BULLHEAD TEE
W/TURNING VANES
90° BRANCH
TAKE-OFF
90° BRANCH
TAKE-OFF
(RECT. TO
ROUND)
90° BRANCH
TAKE-OFF
(BELLMOUTH)
45° BRANCH
TAKE-OFF
(RECTANGULAR)
45° BRANCH TAKE-OFF
(ROUND)
LINEAR SIDEWALL
DIFFUSER (W/SHEET METAL
CONNECTION PLENUM W/1"
LINING & BRANCH FOR
EVERY 4' OF LINEAR.)
LINEAR SIDEWALL
DIFFUSER (W/SHEET
METAL CONNECTION
PLENUM W/1" LINING &
BRANCH FOR EVERY 4' OF
LINEAR.)
SIDEWALL DUCT MTD.
REG./GRILLE
EXHAUST AIR DUCT
TURN 90° UP
EXHUAST AIR DUCT
TURN 90° DOWN
EXHAUST AIR DUCT UP
& PENETRATING FLOOR
ABOVE
SUPPLY AIR DUCT DOWN
& PENETRATING FLOOR
ABOVE
RETURN AIR DUCT
DOWN & PENETRATING
FLOOR BELOW
EXHAUST AIR DUCT
DOWN & PENETRATING
FLOOR BELOW
VD
VD
FSD
FSD
BDD
BDD
FD
FD
SD
SD
ACD
ACD
MD
MD
UP
DN
UP
DN
BOOT BY LD MFG'R
DOUBLE LINE SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE SINGLE LINE
PIPING SYMBOLS
SHEETMETAL SYMBOLS
MOTORIZED
DAMPER
AV
FS
PS
NOT USED
S / E / R FOR SUPPLY, EXHAUST OR RETURN
FLOOR / LEVEL
UNIT NUMBER
(WHERE SMOOTH RADIUS
ELBOWS CANNOT BE
INSTALLED)
GENERAL ABBREVIATIONS
ABREV DESCRIPTION
A COMPRESSED AIR
AC AIR CONDITIONING UNIT
ACCU AIR COOLED CONDENSING UNIT
ACD AUTOMATIC CONTROL DAMPER
AD ACCESS DOOR
AHU AIR HANDLING UNIT
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AFR ABOVE FINISHED ROOF
AP ACCESS PANEL
APD
AIR PRESSURE DROP (INCHES OF
WATER)
AS AIR SEPARATOR
ATC
AUTOMATIC TEMPERATURE
CONTROL
AV
AIR VENT (AUTOMATIC)
B BOILER
BDD BACKDRAFT DAMPER
BHP BRAKE HORSE POWER
BTUH BRITISH THERMAL UNITS PER HOUR
C CONTRACTOR
CRAC COMPUTER ROOM A.C. UNIT
CC COOLING COIL
CD CONDENSATE DRAIN
CF CHEMICAL FEED
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CM CONSTRUCTION MANAGER
CNR CONDENSER WATER RETURN
CNS CONDENSER WATER SUPPLY
CO CLEAN OUT
COND CONDENSATE
CP CONDENSATE PUMP
CT COOLING TOWER
CTR COOLING TOWER RETURN
CTS COOLING TOWER SUPPLY
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CW CITY WATER
D DRAIN
DBT DRY BULB TEMP °F
DIA DIAMETER
DOV DRAIN OFF VALVE
DTR
DUAL TEMPERATURE WATER
RETURN
DTS DUAL TEMPERATURE WATER SUPPLY
DX DIRECT EXPANSION
E
EXISTING (BEFORE SYMBOL)
EA EXHAUST AIR
EHC ELECTRIC HEATING COIL
EAT ENTERING AIR TEMPERATURE
EBB ELECTRIC BASE BOARD
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ERV
ENERGY RECOVERY VENTILATION
UNIT
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETBR EXISTING TO BE REMOVED
ETR EXISTING TO REMAIN
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXP EXPANSION
F FILL
FA FRESH AIR
FCU FAN COIL UNIT
FD FIRE DAMPER
FF FINAL FILTER
FLA FULL LOAD AMPS
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPT FAN POWERED TERMINAL BOX
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOW SWITCH
FSD FIRE & SMOKE DAMPER
FT FINNED TUBE RADIATION
G NATURAL GAS
GA GAUGE
GAL GALLONS
GC GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GLYCOL RETURN
GS GLYCOL SUPPLY
GUH GAS UNIT HEATER
H HUMIDIFIER
HG HOT GAS
HP HORSE POWER OR HEAT PUMP
HPR
HIGH PRESSURE CONDENSATE
RETURN
HPS
HIGH PRESSURE STEAM (60# & UP)
HTHW HIGH TEMPERATURE HOT WATER
HV HEATING VENTILATING
HVAC
HEATING, VENTILATING & AIR
CONDITIONING
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
HX HEAT EXCHANGER
ID INSIDE DIAMETER
IU INDUCTION UNIT
KW KILOWATT
KWH
KILOWATT-HOUR(S)
LAT LEAVING AIR TEMPREATURE
LBS / HR POUNDS PER HOUR
LPR
LOW PRESSURE CONDENSATE
RETURN
LPS
LOW PRESSURE STEAM (2# TO 15#)
LRA LOCKED ROTOR AMPS
LTHW LOW TEMPERATURE HOT WATER
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH1,000 BTU/HOUR
MD MOTORIZED DAMPER
MFG'R MANUFACTURER
MIN MINIMUM
MPR
MEDIUM PRESSURE CONDENSATE
RETURN
MPS
MEDIUM PRESSURE STEAM (16# TO
50#)
MTD MOUNTED
MTHW MEDIUM TEMPERATURE HOT WATER
MUA MAKE UP AIR
MV
AIR VENT (MANUAL)
NA NOT APPLICABLE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
OD OUTSIDE DIAMETER
OED OPEN ENDED DUCT
P PUMP
PC PLUMBING CONTRACTOR
PCHWR PROCESS CHILLED WATER RETURN
PCHWS PROCESS CHILLED WATER SUPPLY
PD
PRESSURE DROP (FEET OF WATER )
PF PRE FILTER
PH PRE HEAT COIL
PRV PRESSURE REDUCING VALVE
PS PRESSURE SWITCH
PSIA
POUNDS PER SQUARE INCH
ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
PTAC
PACKAGED TERMINAL AIR
CONDITIONER
PTHP PACKAGED TERMINAL HEAT PUMP
RA RETURN AIR
RAF RETURN AIR FAN
RHC REHEAT COIL
RH RELATIVE HUMIDITY
RL REFRIGERANT LIQUID
RP RADIANT PANEL
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RVD REMOTE VOLUME DAMPER
S SUPPLY AIR DEVICE
SA SUPPLY AIR
SATT SOUND ATTENUATING UNIT
SD
SMOKE DAMPER OR SMOKE
DETECTOR
SF SUPPLY AIR FAN
SG SPECIFIC GRAVITY
SP
STATIC PRESSURE (INCHES OF
WATER )
SPC STATIC PRESSURE CONTROLLER
SS STAINLESS STEEL
TA TRANSFER AIR
TAC THRU WALL AIR CONDITIONER
TB TERMINAL BOX
TEMP TEMPERATURE
TSP TOTAL STATIC PRESSURE
TW THERMOMETER WELL
TYP TYPICAL
UC UNDERCUT
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UV UNIT VENTILATOR
V VOLTS
VAV
VARIABLE AIR VOLUME TERMINAL
BOX
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
VP VACUUM PUMP
VTR VENTED THROUGH ROOF
W WATTS
WAC WINDOW AIR CONDITIONER
WBT WET BULB TEMPERATURE °F
WH WALL HEATER
WMS WIRE MESH SCREEN
WPD
WATER PRESSURE DROP (FEET)
GENERAL NOTES
1. THE HEATING, VENTILATING AND AIR CONDITIONING (HVAC)
CONTRACTOR SHALL VISIT THE SITE TO DETERMINE ALL
PRE-EXISTING CONDITIONS AND WORK NECESSARY PRIOR
TO SUBMISSION OF BID PRICE.
2. THE HVAC CONTRACTOR SHALL BE FAMILIAR WITH ALL
CONTRACT DOCUMENTS FOR ALL TRADES AND
COORDINATE WITH OTHER CONTRACTORS.
3. DRAWINGS ARE DIAGRAMMATIC ONLY, FINAL ROUTING OF
DUCTWORK, PIPING AND EQUIPMENT LOCATIONS SHALL
BE DETERMINED IN THE FIELD. ADDITIONAL OFFSETS,
ELBOWS, ETC., SHALL BE PROVIDED AND INSTALLED
WITHOUT ADDITIONAL COST TO THE OWNER.
4. ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED
IN ACCORDANCE WITH THE LATEST EDITION OF SMACNA
STANDARDS.
5. SUPPLY AND RETURN DUCT MAINS FROM AIR HANDLING
EQUIPMENT SHALL BE INTERNALLY LINED AS PER
SPECIFICATIONS A MINIMUM OF 15'-0" FROM THE UNIT
UNLESS OTHERWISE NOTED. ALL DUCTWORK DIMENSIONS
INDICATED ARE CLEAR INSIDE DIMENSIONS.
6. VOLUME DAMPERS SHALL BE INSTALLED AT BRANCHES,
SPLITS, AND TAKE-OFFS. ALL LOW PRESSURE SUPPLY,
RETURN AND EXHAUST DUCTWORK.
7. MINIMUM SIZE OF ALL HVAC PIPING SHALL BE 3/4" UNLESS
OTHERWISE NOTED.
8. INSTALL SMOKE DETECTORS IN DUCT SYSTEMS IN
ACCORDANCE WITH NFPA.
9. THE HVAC CONTRACTOR SHALL COORDINATE ALL
ELECTRICAL AND PLUMBING REQUIREMENTS WITH THE
ELECTRICAL AND PLUMBING CONTRACTORS.
10. THE HVAC CONTRACTOR SHALL FIELD MEASURE EXACT
SIZES AND VERIFY ALL OPENINGS FOR SHAFTS AND
LOUVERS PRIOR TO SUBMISSION OF SHOP DRAWINGS AND
INSTALLATION.
11. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR
FINAL LOCATIONS OF DIFFUSERS, REGISTER, GRILLES,
THERMOSTATS, ETC.
12. THE HVAC CONTRACTOR SHALL FURNISH AND INSTALL ALL
INCIDENTAL ACCESSORIES NECESSARY TO MAKE THE
HVAC WORK COMPLETE AND READY FOR OPERATION.
13. ALL HVAC WORK SHALL BE IN ACCORDANCE WITH
APPLICABLE FEDERAL, STATE AND LOCAL CODES.
14. ALL HVAC EQUIPMENT SHALL BE INSTALLED IN
ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
15. FIRE DAMPERS AND ACCESS PANELS SHALL BE INSTALLED
AT ALL 2-HOUR RATED PARTITIONS AND FLOOR
PENETRATIONS. IN ADDITION COMBINATION FIRE/SMOKE
DAMPERS AND ACCESS PANELS SHALL BE INSTALLED AT
PENETRATIONS OF ALL RATED SHAFT ENCLOSURES
CONNECTING THREE STORIES OR MORE. REFER TO
ARCHITECTURAL DRAWINGS FOR PARTITION LOCATIONS.
16. TRANSFER DUCTS IN RATED PARTITIONS SHALL BE
INSTALLED WITH FIRE DAMPERS.
17. ISOLATION VALVES SHALL BE INSTALLED IN SUPPLY AND
RETURN PIPING ON EACH FLOOR AT EACH MAIN BRANCH
AND AT EACH BRANCH OR RUN-OUT SERVING MORE THAN
ONE PIECE OF EQUIPMENT.
18. SHUTOFF VALVES SHALL BE INSTALLED IN THE SUPPLY
AND RETURN PIPING TO ALL EQUIPMENT TO ALLOW FOR
SERVICING. UNIONS OR FLANGES SHALL BE ARRANGED
SUCH THAT EQUIPMENT CAN BE SERVICED WITHOUT
CUTTING, AND WITH MINIMAL DISRUPTION OF PIPING
SERVING THE EQUIPMENT.
19. THE HVAC CONTRACTOR SHALL FURNISH TO THE GENERAL
CONTRACTOR ALL INFORMATION REQUIRED FOR SETTING
OF WALL, ROOF AND PARTITION OPENINGS FOR HVAC
WORK. THIS INFORMATION SHALL BE FURNISHED IN A
TIMELY MANNER SUCH THAT CONSTRUCTION SCHEDULE IS
NOT JEOPARDIZED.
20. THE HVAC CONTRACTOR SHALL INFORM AND COORDINATE
WITH THE OWNER ALL NECESSARY INTERRUPTIONS TO
EXISTING BUILDING SYSTEMS AND SERVICE THAT MAY
AFFECT THE NORMAL OPERATION OF OCCUPIED
PORTIONS OF THE BUILDING. THE OWNER SHALL BE
INFORMED OF ANY INTERRUPTIONS AT LEAST TWO (2)
WEEKS IN ADVANCE.
21. THE HVAC CONTRACTOR SHALL COORDINATE ANY
PREMIUM WORK REQUIRED FOR THIS PROJECT WITH THE
GENERAL CONTRACTOR.
22. THE HVAC CONTRACTOR SHALL COORDINATE WITH THE
GENERAL CONTRACTOR PHASING REQUIREMENTS OF THE
PROJECT.
23. THE AUTOMATIC TEMPERATURE CONTROL (ATC)
CONTRACTOR SHALL COORDINATE THERMOSTAT
LOCATIONS WITH ARCHITECTURAL FURNITURE PLANS.
THERMOSTATS SHALL BE INSTALLED 54" ABOVE FINISHED
FLOOR UNLESS OTHERWISE NOTED.
24. EXISTING FIBEROUS DUCT LINERS WHICH ARE CUT DURING
RENOVATION SHALL BE RE-SEALED SO THAT NO FIBEROUS
LINER MEDIA IS EXPOSED TO THE AIRSTREAM.
VD
VD
VD
VD
VD
VD
VD
VD
VDVD
VD
VD
VD VD
VD VD
VAV-X-X
XXX
XXX
X.X
X.X
DESIGNATION
NUMBER
MAXIMUM CFM
MINIMUM CFM
WATER
FLOW RATE
MBH
VAV WITH
HYDRONIC HEAT
VAV WITH
ELECTRIC HEAT
CARBON DIOXIDE
SENSOR
FPT BOX
SERVICE
CLEARANCE
H
H
UNIT
#
X-X
#
DP
HI
LO
0.02"
HIGH PRESSURE SIDE
DIFF. PRESSURE SENSOR
DESIGN PRESSURE
DIFFERENTIAL (IN. H2O)
LOW PRESSURE SIDE
T
H
S
RS
CO₂
SD
CO
H-001
HVAC LEGEND,
DETAILS, SCHEDULE
& GENERAL NOTES
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
NORTH
ISSUED FOR BID
3/2/20NONE
Drawn By: DO Checked By: EJE
V1 6th Floor Tissue CultureLabs
:3/13/20
AIR DISTRIBUTION DEVICE SCHEDULE
ITEM SERVICE TYPE NECK SIZE AIR PATTERN MATERIAL
MANUFACTURER / MODEL
NUMBER
REMARKS
A RADIAL SUPPLY CEILING DIFFUSER
(SEE DRAWINGS)
RADIAL 2-WAY ALUMINUM PRICE / FRFD1,2,3,4,5
B RETURN/EXHAUST LOUVERED GRILLE
(SEE DRAWINGS)
45 DEG. DEFLECTION STEEL PRICE / 5301,2,3,4
NOTES:
1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR MOUNTING TYPE.
2. DEVICES IN GRID CEILINGS SHALL BE LAY-IN TYPE UNLESS OTHERWISE NOTED.
3. DEVICES IN SHEETROCK AND PLASTER CEILINGS SHALL BE SURFACE MOUNTED.
4. ALL COLOR AND FINISHES TO BE APPROVED BY ARCHITECT.
5. DIFFUSERS TO BE 24"x24" FACE
VARIABLE & CONSTANT VOLUME BOX SCHEDULE
ITEM TYPE MAX CFM MIN CFM
Δ PRESSURE
IN. H₂O (MAX)
HOT WATER COIL
INLET STATIC
PRESSURE
(IN.)
INLET
CONNECTION
SIZE (IN.)
MAX BOX
DEPTH (IN.)
SILENCER
LINING
THICKNESS
LINING
HOSPITAL
GRADE
ACCESS
DOOR
BEFORE
COIL
ACCESS
DOOR
AFTER
COIL
MANUFACTURER /
MODEL NUMBER
REMARKS
AIR WATER
INTEGRAL
EXTERNAL
SEE
SCHEDULE
MBH EWT °F LWT °F EAT °F
LAT °F
(MIN)
GPM
AIR Δ
PRESSURE
(IN H₂O)
FPI MAX.
MAX Δ
PRESSURE
(FT. H₂O)
MIN NO.
ROWS
VAV-S-6019 VARIABLE VOLUME 800 400 0.7 18 150 120 55 95 1.3 0.5 10 8 2 1.5 10Ø 13 NO NO 1" YES YES BY HVAC PRICE / SDV
VAV-R-6019 VARIABLE VOLUME 920 460 0.7 - - - - - - - - - - 1.5 12Ø 13 NO NO 1" YES YES BY HVAC PRICE / SDE
VAV-S-6029 VARIABLE VOLUME 800 400 0.7 18 150 120 55 95 1.3 0.5 10 8 2 1.5 10Ø 13 NO NO 1" YES YES BY HVAC PRICE / SDV
VAV-R-6029 VARIABLE VOLUME 920 460 0.7 - - - - - - - - - - 1.5 12Ø 13 NO NO 1" YES YES BY HVAC PRICE / SDE
NOTES
MATERIAL
TO MATCH
DUCT
MATERIAL
DAMPER
STIFFENING
OUTSIDE END
BEARING
INSIDE END
BEARING
RECTANGULAR DAMPER
FOR DUCTS 19" TO 48"x12"
TWO BLADE DAMPER
ARRANGEMENT
DUCT
EXTENSION FOR WRAPPED
DUCT
WING NUT & ARM (TYP)
ROUND DAMPER
3/8" QUADRANT
DUCT
1/2" QUADRANT
DUCT
3/8"Ø ROD PIN
16 GA. BLADE
RECTANGULAR
DAMPER FOR DUCTS
UP TO 18"x12"
22 GA. BLADE
3/8"Ø ROD PIN
NOTES:
1. FOR DUCTS OVER 12" HIGH USE MULTIPLE BLADES.
2. ALL BRANCH DUCTS (SUPPLY, RETURN & EXHAUST) SHALL HAVE VOLUME
DAMPERS, INCLUDING RUNOUTS TO DIFFUSERS (MANDATORY).
DUCT SIDE ELEVATION
1/8" ALL AROUND 1/8" ALL AROUND
DUCT DEPTH
NTSVOLUME DAMPER (SINGLE BLADE)
NTS
NOTES:
1. FOR STRAP AND TRAPEZE HANGER SIZE, REFER TO SMACNA DUCT STANDARDS.
2. NO POP RIVETS ALLOWED; USE SELF-TAPPING SHEET METAL SCREWS ONLY.
3. COORDINATE WITH STRUCTURAL.
4. REVIEW SEISMIC SECTION OF SPECS FOR ATTACHMENT.
C-CLAMP
(TYP.)
STRUCTURAL STEEL OR
BUILDING STRUCTURE
HANGER
STRAPS
ANGLES
SPOT WELD ANGLE TO
STRUCTURAL STEEL
1/2"Ø MIN
HANGER ROD
(TYP.)
BAND
STRAP HANGER TRAPEZE HANGER
HANGER STRAP
3/8" BOLT (MIN)
41" MAX.
BAND OF SAME SIZE
AS HANGER STRAP.
RECTANGULAR & ROUND DUCT HANGER DETAIL (LOW VELOCITY)
DOUBLE THICKNESS TURNING
VANES (SEE TURNING VANE
DETAIL)
FULL RADIUS
WHERE POSSIBLE
(R=W)
RECTANGULAR ELBOW
RADIUS ELBOW
LOW VELOCITY
ELBOWS
LOW VELOCITY
TRANSITIONS
AIR FLOW
DIVERGING FLOW
R
R
LOW VELOCITY
OFFSETS
30° ELBOWS 45°
MAX.
AIR FLOW
CONTRACTION FLOW
W
W
W
20° MAX.
30° MAX.
R=1-1/2W
NTSLOW VELOCITY TRANSITION TAKEOFFS & ELBOWS
NTS
STANDARD FEATURES:
1. NEOPRENE GASKET
TO MINIMIZE AIR
LEAKAGE.
2. PRE-DRILLED HOLES
FOR QUICK
MOUNTING.
3. CONSTRUCTED OF
HEAVY DUTY
GALVANIZED STEEL.
OPTIONAL FEATURES:
1. 26 GAUGE GALV. QUANDRANT
VOLUME DAMPER W/TIGHT
FITTING GASKETING TO
MINIMIZE LEAKAGE AT
DAMPER PIVOT POINTS.
2. HEAVY DUTY HARDWARE IS
AVAILABLE FOR
APPLICATIONS WITH
INCREASED STATIC
PRESSURE.
NOTES:
ALL ROUND AND RECTANGULAR BELLMOUTH FITTINGS
SHALL BE INCLUDED WITH THE FOLLOWING FEATURES:
45° RECTANGULAR
TAKE-OFF
RECTANGULAR
BELL MOUTH
FITTING
MODEL RBMD
PREFERED
TAKE-OFF FITTING
ALTERNATE
TAKE-OFF FITTING
RECTANGULAR BRANCH DUCT TAKE-OFFS
BELLMOUTH
CONNECTION
MODEL BMD
BELLMOUTH
MODEL BMD
W/ END FLAPS
BENT OVER
MINI-BELLMOUTH
CONNECTION
MODEL MBMD
OVAL-BELLMOUTH
CONNECTION
MODEL OVBMD
STANDARD 45°
REGULAR TO ROUND
BOOT CONNECTION
MODEL 33000
ROUND BRANCH DUCT TAKE-OFFS
PREFERED ALTERNATE ALTERNATE ALTERNATE ALTERNATE
TAKE-OFF FITTING TAKE-OFF FITTING TAKE-OFF FITTING TAKE-OFF FITTING TAKE-OFF FITTING
VD VD
VD VD
VD
AIR FLOW
AIR FLOW
VDVD
BELL MOUTH CONNECTION DETAIL
NTS
INSULATION
PROVIDE VIBRATION ISOLATOR ON
PIPING LOCATED IN MECHANICAL
EQUIPMENT ROOMS.
LOCK NUTS
PIPE ROLL
INSULATION
PROTECTION
SADDLE WELDED TO
PIPE
BOLT (TYP.)
ANGLE IRON
SUPPORT BY HVAC
INSULATION AS
SPECIFIED
INSULATION PROTECTION
SHIELD
NOTES:
1. FOR TYPE OF HANGER AND INSULATION REQUIREMENTS REFER TO SPECIFICATIONS.
2. SERVICE PIPING AS INDICATED IN SPECIFICATIONS SHALL BE INSTALLED ON ROLLER HANGERS.
3. COORDINATE WITH STRUCTURAL.
PIPE HANGER AND PIPE ROLLER
A B
PROVIDE ACCESS TO CONTROLS AS
PER MANUFACTURER'S
RECOMENDATIONS
CD
AIR FLOW
EXHAUST BOX
TRANSITION
A. SCHEDULED INLET DUCT SIZE UNLESS OTHERWISE NOTED
B. BOX OUTLET SIZE
C. BOX INLET SIZE
D. SCHELUDED INLET DUCT SIZE UNLESS OTHERWISE NOTED
NOTES:
NTSEXHAUST BOX
NTS
ACCESS PANEL BY
HVAC CONTRACTOR
ACCESS PANEL BY
BOX MANUFACTURER
TRANSITION BY
CONTRACTOR
PROVIDE ACCESS TO CONTROLS AS PER
MANUFACTURER'S RECOMENDATIONS
TRANSITION
NOTES:
A. SCHEDULED INLET DUCT SIZE UNLESS OTHERWISE NOTED
B. BOX INLET SIZE
C. BOX OUTLET SIZE
D. COIL OUTLET SIZE
E. SCHEDULED DISCHARGE DUCT SIZE UNLESS OTHERWISE NOTED
AB
COIL
C D
E
SUPPLY BOX WITH COIL
18" MIN.
36" MAX.
HWS
HWR
NTS
PRESSURE AND TEMPERATURE TAPS
BALL VALVE WITH CAPPED
HOSE ADAPTOR (TYP.)
HOT WATER COIL
PER SPECIFICATIONS
SEE A.T.C. SPECIFICATIONS
CONTROL VALVE
SEPARATE BALANCING
VALVE WITH GAUGE PORTS
REFER TO DWG
FOR PIPE SIZES
STRAINER
BALL VALVE (TYP.)
OR BUTTERFLY
VALVE WHEN
LARGER THAN 2".
BALL VALVE WITH CAPPED
HOSE ADAPTOR (TYPICAL)
NOTE:
COIL FLANGES, READY FOR BOLTING TO DUCTWORK FLANGES.
TYPICAL FOR IN-DUCT COIL AND TERMINAL BOX COIL.
TYPICAL VAV REHEAT/DUCT-MOUNTED
HOT WATER COIL PIPING
H-002
HVAC SCHEDULES &
DETAILS
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
NORTH
ISSUED FOR BID
3/2/20NONE
Drawn By: DO Checked By: EJE
V1 6th Floor Tissue CultureLabs
:3/13/20
4 5 6
D
C.5
C
SCOPE OF WORK
TISSUE CULTURELAB6029
TISSUE CULTURELAB6019
MONITORING LAB6028
EQUIPMENT LAB6027
CORRIDOR6002
EQUIPMENTCORRIDOR
6030
STORAGE ROOM6031
SOLVENT STORAGE6032
CORRIDOR6037
LAB SUPPLY ROOM6035
ELEC ROOM6036
PLUMBING CLOSET621
COLD ROOM6017
MICROSCOPEROOM6022
EQUIPMENTCORRIDOR
6021
EQUIPMENT ROOM6023
EQUIPMENTCORRIDOR
6018
CORRIDOR6020
CORRIDOR6026
BIOSAFETY CABINET
BIOSAFETY CABINET
STACKED INCUBATOR
STACKED INCUBATORS
STACKED INCUBATOR
BIOSAFETY CABINET
BIOSAFETY CABINET
STACKED INCUBATOR
V
V
V
V
6019
-A
V
V
56x1456x14
56x14
56x14
60x16
60x16
56
x1
4
10Ø
12Ø
40x18
56x12
14x12
14x1210x12
8Ø
8Ø
8Ø
8Ø
VD
VD
VD
VD
VAV-S
6019
A-8"Ø
200
(TYP.4)
B-16x16
460
(TYP.2)
10
Ø1
4x12
14x1210x12
8Ø
8Ø
8Ø
8Ø
VD
VD
VD
VD
VAV-S
6029
VAV-E
6019
VAV-E
6029
A-8"Ø
200
(TYP.4)
B-16x16
460
(TYP.2)
20x12
20x12
3/4"
HW
S
HW
R
3/4"
EXISTING HWS&R
1
1 1
1
2
2
2
2
T
T
16x12
16x1
2
VD
VD
16x12
VD
VD
NEW WORK NOTES:
EXISTING CONTROL ALARM DROPS (4) ON WALL SHALL BE REUSED
FOR INCUBATORS IN T.C. LAB 6029 (THERE ARE 4 DOUBLE
STACKED INCUBATORS) PROVIDE ADDITIONAL AS REQUIRED
PROVIDE ALARMS AT INCUBATORS IN ROOM 6019 (THERE ARE 4
DOUBLE STACKED INCUBATORS)
1
2
HVAC LEVEL 6
NEW WORK PLAN
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
KEY PLAN
1 2 3 5 7
8
A.7
B
C
C.5
E
F
G
OFFICE6010
OFFICE6011
OFFICE6012
DSELAB6016
6019
MICROSCOPEROOM6022
EQUIPMENTLAB6027
MONITORINGLAB6028
EQUIPMENTLAB6029
STORAGEROOM6031
SOLVENTSTORAGE6032
GLASSWASH6069
OPENOFFICEAREA6063
CELLCULTURE6058
MASSSPEC6057
OPEN LAB6056
EQUIPMENTCORRIDOR
6053
DNAROOM6055
TISSUECULTURE6054
6050
EQUIPMENT6048
STORAGE/FREEZERROOM6045
HUMANBIOLOGY
LABORATORY6046
OFFICE6042
OFFICE6043
EQUIPMENTROOM6039
STABILITYCHAMBER
6040
MASSSPEC6038
MASSSPEC6025
ELECROOM6036
LABSUPPLYROOM6035
BIOREPOSITORYROOM6068
SAMPLERECEIVING
ROOM6074
CONFERENCE6067
CONFERENCE6003
CONFERENCE6004
CONFERENCE6005
VIPERLAB6014
EQUIPMENTCORRIDOR
6021
EQUIPMENTROOM6023
COLDROOM6047
COLDROOM6052
MEETINGAREA6059
OPENOFFICEAREA6007
INNOVATIONBAR6008
COPY6009
OPENOFFICEAREA6013
EQUIPMENTCORRIDOR
6018
DSE LAB6015
COLDROOM6017
EQUIPMENTCORRIDOR
6030
CORRIDOR6002
CORRIDOR6001
CORRIDOR6075
CORRIDOR6073
CORRIDOR6006
OPENOFFICEAREA6041
TEL/DATAIDF6072
CORRIDOR6071
CORRIDOR6037
D
E5
E6
E3
4
STORAGE6060
STORAGE6064
KITCHEN6065
BREAKRM6066
MEDIAPREPROOM6062
POD6033
POD6034
COPY/MAIL6044
CORRIDOR6026
CORRIDOR6020
CONFERENCE6061
6
STAIR 1S1-6
SERVICEELEVATOR
LOBBY602
STAIR 2S2-6
STAIR 3S3-6
ELEV #2
ELEV #3
ELEV #4
ELEV #8
ELEV #7
ELEV #6
ELEV #5
MECH.PIPING606
NORMALELECTRICAL
ROOM604
PLUMB.CLOSET621
LIFESAFETY605
PLUMB.CLOSET620
JANITOR607
MEN610
WOMEN609
SHOWER608
BIOWASTESTORAGE
651
EQUIPMENTLAB
CLINICALBIOMARKERS
OPEN LAB
ELEVATORLOBBY601
CORRIDOR6049
IMPORTANT NOTE:
SCOPE OF WORK
NORTH
ISSUED FOR BID
3/2/20
1
4
" = 1'-0"
H-101
SCALE : 1/4" = 1'-0"1 HVAC LEVEL 6 NEW WORK PLAN
Drawn By: DO Checked By: EJE
V1 6th Floor Tissue CultureLabs
:3/13/20
PLUMBING FIXTURE SCHEDULE
DESIGNATION DESCRIPTION MANUFACTURER MODEL# TYPE
FAUCET
MANUFACTURER
FAUCET / TRIM/ MODEL SUPPLIES TRAP / WASTE LAB WASTE
LAB
VENT
CW TW HW RO NDCW NDHW ADA CARRIER COMMENTS / DESCRIPTION
LSK-1
EPOXY
LABORATORY
SINK
BY OTHERS -
BENCH INTEGRAL
SINK
CHICAGO
A) # 930-GN8BVB-317-XKCP-HW/CW
B) # 828-RO
PROVIDE CHICAGO
1016 1/2"SUPPLIES W/
LOOSE KEY HANDLE
FOR NDHW, NDCW
PROVIDE 2"ACID RESISTING P-TRAP W/ CO
PLUG.PROVIDE ACID RESISTING GRID
STRAINER AND TAILPIECE. PROVIDE ACID
RESISTING OVERFLOW DRAIN FOR SINK,
TIE-IN TO TAIL PIECE.
2" 2" - - -
1
2
"
1
2
"
1
2
" - N/A
1. PROVIDED & INSTALL BELOW DECK NDCW, NDHW, RO SHUT-OFF
VALVES AND CONNECT TO FAUCETS INLET WATER SUPPLIES.
EW-1
EMERGENCY
EYEWASH
GUARDIAN G5022-HG-VB
DECK MOUNT
POINT OF USE
EYEWASH/DRENCH
HOSE UNIT
- -
1
2
"SHUT OFF VALVE - - - -
1
2
" - - - - - N/A
1. PROVIDE BELOW DECK SHUT-OFF VALVE AND CONNECT TO
EYEWASH WATER INLET.
2. PROVIDE WITH INTEGRAL VACUUM BREAKER & HOSE GUIDE
EXISTING TO REMAIN
CONNECT TO EXISTING
ETR
CTE
AFFABOVE FINISHED FLOOR
GENERAL CONTRACTOR
PLUMBING GENERAL NOTES
1. PLUMBING SUBCONTRACTOR SHALL REFER TO THE ARCHITECTURAL DETAILED PLANS AND LABORATORY
PLANNING DRAWINGS FOR EXACT LOCATIONS OF ALL ELEVATIONS, FIXTURES, AND LABORATORY GAS
OUTLETS.
2. PLUMBING SUBCONTRACTOR SHALL REFER TO ARCHITECTURAL AND LABORATORY PLANNING DRAWINGS,
INCLUDING THESE DOCUMENTS, FOR EXACT LOCATIONS OF EQUIPMENT TO BE PIPED UNDER THE
PLUMBING SCOPE OF WORK.
3. PLUMBING SUBCONTRACTOR SHALL REFER TO THE ARCHITECTURAL LABORATORY PLANNING DRAWINGS
FOR ALL ELEVATIONS, LAB BENCH AND CASEWORK DETAILS.
4. COORDINATE PIPING DEMOLITION WITH OWNER TURN OVER ALL DEMOLISHED COPPER PIPE, VALVES AND
FITTINGS TO OWNER.
5. ALL NEW WORK IS DRAWN HEAVY.
6. EXISTING PIPING AND FIXTURES TO REMAIN ARE DRAWN LIGHT.
7. ALL HATCHED OR SHADED IN FIXTURES AND ASSOCIATED FIXTURE PIPING SHALL BE DISCONNECTED AND
REMOVED BACK TO NEAREST STACK, MAIN OR RISER. NO DEAD END PIPING PERMITTED.
8. THE LOCATIONS OF PIPING, FIXTURES, ELEVATIONS, ETC. HAVE BEEN TAKEN FROM THE BEST SOURCES
AVAILABLE AND MUST BE VERIFIED IN THE FIELD PRIOR TO COMMENCING WORK IN RENOVATED AREAS.
9. SINCE PORTIONS OF THE EXISTING BUILDING SHALL REMAIN IN OPERATION DURING CONSTRUCTION, THE
PHASING REQUIREMENTS SHALL BE MET BY THIS SUB-CONTRACTOR AND ALL REQUIRED PIPES, VALVES,
AND FITTINGS NECESSARY TO ACCOMPLISH SAME SHALL BE PROVIDED. COORDINATION OF THIS IS VERY
IMPORTANT.
10. DEBRIS REMOVAL FROM THE CONSTRUCTION SITE WILL BE COMPLETED BY A PREDETERMINED ROUTE AT
PREDETERMINED TIMES. COORDINATE WITH THE HOSPITAL.
11. DURING DEMOLITION WORK THIS SUBCONTRACTOR SHALL COORDINATE WITH THE OWNER'S SAFETY
OFFICER REGARDING REMOVAL OF PIPE AND PLUMBING IN HAZARDOUS AREAS. FLUSHING OR
DECONTAMINATION OF SYSTEMS MAY BE REQUIRED PRIOR TO THE START OF DEMOLITION.
12. PLUMBING SUB-CONTRACTOR IS REQUIRED TO GIVE MINIMUM 5 DAYS NOTICE FOR ANY PLUMBING SYSTEM
SHUT-DOWNS THAT ARE REQUIRED. THESE SHUT-DOWNS MUST BE COORDINATED WITH CHILDREN'S
HOSPITAL ENGINEERING AND MAINTENANCE OFFICES.
13. ALL NEW PIPE PENETRATIONS & SLEEVES SHALL BE FIRE STOPPED & SMOKE STOPPED, SEE SPECIFICATION
FOR REQUIREMENTS AND DIGITALLY PICTURES OF FINISH WORK SHALL BE PROVIDED TO OWNER, AND
ENGINEER PRIOR TO CLOSE-OUT
GC
FUME HOODFH
CAP EXISTING PIPECEP
BUILDING AUTOMATION SYSTEMBAS
PIPING IDENTIFICATION SCHEDULE (PLUMBING)
SYSTEM TAG PLAN TAG
PIPE JACKETING PIPE IDENTIFICATION VALVE TAGS
JACKET COLOR
MANUFACTURER
MATERIAL
BACKGROUND LETTERING BACKGROUND LETTERING
MANUFACTURER
MATERIAL
NON-DOMESTIC COLD WATER NDCW TAN 42438-R1 LIGHT GREY GREEN LIGHT GREY WHITE ROWMARK 2XX-322
NON-DOMESTIC HOT WATER NDHW BROWN 41079-R2 LIGHT GREY RED LIGHT GREY RED ROWMARK 2XX-326
NON-DOMESTIC HOT WATER CIRCULATION NDHC GREY L7-1228V LIGHT GREY YELLOW LIGHT GREY RED ROWMARK 2XX-326
REVERSE OSMOSIS/ DE-IONIZED WATER RODI - - - - - - - - - - - - - - - - WHITE BLACK ROWMARK 2XX-204
CARBON DIOXIDE CO2 - - - - - - - - GREY WHITE GREY WHITE ROWMARK 2XX-312
LABORATORY COMPRESSED AIR CA - - - - - - - - YELLOW BLACK BLACK YELLOW ROWMARK 3XX-407
LABORATORY VACUUM LVAC - - - - - - - - YELLOW BLACK BLACK YELLOW ROWMARK 3XX-407
LABORATORY WASTE LW - - - - - - - - GREEN WHITE - - - - - - - - - - - -
LABORATORY VENT LV - - - - - - - - GREEN WHITE - - - - - - - - - - - -
SPRINKLER SPR - - - - - - - - RED WHITE - - - - - - - - - - - -
REMOVE TO THIS POINTRTTP
BIO SAFETY CABINETBSC
EXISTING TO BE REMOVED & RELOCATEDETBR&R
PRESSURE GAUGE
BV BALL VALVE
NORMALLY CLOSED VALVE
ETBR EXISTING TO BE REMOVED
ETR EXISTING TO REMAIN
PRV PRESSURE REDUCING VALVE
VIV VALVE IN VERTICAL
TMV THERMOSTATIC MIXING VALVE
PIPE UNION
PIPE CONNECT TO EXISTING
PIPE RISER
PIPE CAP OR PLUG
PIPE CONTINUATION
PIPE UP THROUGH SLAB ABOVE
PIPE DOWN THROUGH FLOOR SHOWN
PIPE RISE/DROP
W&T WASTE AND TRAP
CO CLEANOUT
CA COMPRESSED AIR PIPING
N NITROGEN PIPING
CO2 HIGH PRESSURE CARBON DIOXIDE PIPING
LW LAB WASTE PIPING
LV LAB VENT PIPING
ROS REVERSE OSMOSIS WATER SUPPLY PIPING
TWS TEMPERED WATER SUPPLY PIPING
TWR TEMPERED WATER RETURN PIPING
NDCW NON-DOMESTIC COLD WATER PIPING
NDHW NON-DOMESTIC HOT WATER PIPING
NDHC NON-DOMESTIC HOT WATER CIRCULATION PIPING
CTE
PLUMBING LEGEND
EMERGENCY SHOWER STATION (DEMO/NEW)
ESS
EMERGENCY EYEWASHEW
CA
N
CO2
LW
LV
NDCW
NDHW
NDHC
TWS
TWR
ROS
LABORATORY GAS TURRET BALL VALVE
LW&LV LABORATORY WASTE & VENT PIPING
SYMBOL ABBR DESCRIPTION
CA
N
CO2
LW
LV
NDCW
NDHW
NDHC
TWS
TWR
ROS
EXISTING NEW
LVAC LABORATORY VACUUM PIPING
SW SOLVENT WASTE PIPINGSWSW
BVNC
PGPG
REGULATOR
4 PIPE HANGERS FROM BOTTOM OF SLAB
UNINSULATED PIPEINSULATED PIPE
POLYPROPYLENE PIPE
METAL "V" CHANNEL
W/ CLEVIS HANGER
HANGER (TYP)
INSULATION
SHIELD
INSULATION
ELECTRO
GALVANIZED
THREADED ROD
ELECTRO
GALVANIZED
THREADED ROD
ELECTRO
GALVANIZED
THREADED ROD
NOTE:
1.ALL HANGERS, HARDWARE, AND RODS SHALL BE ELECTRO GALVANIZED
2. ALL MISCELLANEOUS IRON & STEEL SHALL BE FURNISHED UNDER THIS CONTRACT AS REQUIRED FOR PROPER
SUPPORT OF ALL SYSTEMS INSTALLED UNDER DIV. 22
NTS
DOUBLE NUT
SINGLE NUT
DOUBLE NUT
SINGLE NUT
DOUBLE NUT
SINGLE NUT
ELECTRO GALVANIZEDTHREADED ROD
ALL PIPE SIZES
ANCHOR SECURELY TOBUILDING STRUCTURE
DOUBLE NUT
CLEVIS HANGER
SINGLE NUT
NUT & WASHER
12"
6" 6"
3
NOTES:
1. PROVIDE NON-COMPRESSIBLE INSULATION SECTION WITH SHIELD AT
EACH SUPPORT POINT FOR INSULATED PIPING.
2. PROVIDE "UNICUSHION" OR OTHER APPROVED RESILIENT WRAPPING
AROUND ALL UNINSULATED PIPING AT EACH SUPPORT POINT.
3. ALL HANGERS, HARDWARE, AND RODS SHALL BE ELECTRO GALVANIZED
4. REFER TO DRAWINGS FOR PIPE SIZES
TRAPEZE HANGER
DOUBLE LOCK
NUTS &
WASHERS
PIPE RACK
CHANNEL
(UNISTRUT OR
EQUAL P1000) 48"
LONG
PIPE CLIPS
(TYPICAL)
LV
AC
TW
S
CO₂
RO
S
RO
S
ND
CW
ND
HW
1
2
" ALL THREAD ROD
SUPPORT FROM BUILDING STRUCTURE
SEGMENT OF NON-
COMPRESSIBLE INSULATION
EXTEND BEYOND INSULATION
SHIELD IN BOTH DIRECTIONS
A
A
SECTION 'A-A'
PIPING INSULATION
18 GAUGE ELECTRO
GALVANIZED STEEL INSULATION
SHIELD
PIPE CLIP
NTS
ANCHOR SECURELY TO
BUILDING STRUCTURE
ANCHOR SECURELY
TO BUILDING
STRUCTURE
PROVIDE
PIPE SADDLE
(TYPICAL)
LVACLVAC
LAB TURRET SCHEDULE
SYMBOL MANUFACTURER OUTLET MODEL TYPE REMARK
T-1CHICAGO
LAB VACUUM BALL VALVE
(SINGLE)
986-909-VCP WALL MONTED 1. INDEXED FOR VACUUM.
DETAIL OF LAB VACUUM CONNECTION AT BIO SAFETY CABINETNTS
1
CEILING
NOTES:
1. REFER TO PLUMBING DRAWINGS FOR PIPING & SERVICES REQUIRED AT EACH BSC.
2. THE LOCATION OF LAB VAC PIPE DROP, IN THE WALL, SHALL BE COORDINATED IN THE FIELD IN ACCORDANCE WITH
BIO SAFETY CABINET INTEGRAL TURRET LOCATION.
3. PLUMBING SUBCONTRACTOR SHALL INSTALL ALL LOOSE TRIM & TURRETS IN THE BSC.
4. DETAIL NOTED IS BASED ON A LESS THAN 6'-0" WIDE BSC & PLUMBING SUBCONTRACTOR SHALL PROVIDE ADDITIONAL
CONNECTION FOR BSC 6'-0" OR LONGER. REFER TO THE BSC SCHEDULE FOR ADDITIONAL INFORMATION.
FLOOR
VACUUM & AIR TURRETS TO BE
PROVIDED BY BIO SAFETY CABINET
VENDOR AND TO BE INSTALLED BY
PLUMBING CONTRACTOR
BSC
NEW
3
4
"VACUUM PIPING ABOVE
CEILING TO VACUUM SYSTEM
PROVIDE SHUT-OFF VALVE
VALVE MUST BE ACCESSIBLE,
COORDINATE LOCATION
IN FIELD
PROVIDE WALL ESCUTCHEONS
NTS2
CO2 PIPING AT INCUBATORS
INCUBATOR
ELEVATION
CEILING
INCUBATOR
VERIFY ELEVATION/LOCATION OF CO2 SET-UP WITH
VERTEX PRIOR TO INSTALLATION
FLOOR
NEW
1
2
" CO2 OR HIGH PRESSURE
NIT PIPING ABOVE CEILING NEW
1
2
"CO2
PIPING DROP IN WALL
TYGON TUBING PROVIDED BY OWNER
(INSTALLED BY MOVE-IN CREW
NOT PLUMBER)
PROVIDE CO2 APOLLO SHUT-OFF BALL VALVE TO
MATCH EXISTING IN ROOM 6027 WITH
CONNECTION ADAPTER FOR PRESSURE
REGULATOR PROVIDED BY OTHER
SHUT-OFF VALVE TO BE INSTALLED AT 7'-6" ABOVE
FINISH FLOOR IN ACCESSIBLE LOCATION TO THE
SIDE OF THE STACKED INCUBATORS.
NEW
3
4
"VACUUM PIPE
IN WALL
BSC
TW
S
PROVIDED & INSTALLED BY OWNER
P-001
PLUMBING
LEGEND, DETAILS,
SCHEDULE &
GENERAL NOTES
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
NORTH
ISSUED FOR BID
3/2/20NONE
Drawn By: JES Checked By: WMN
V1 6th Floor Tissue CultureLabs
:3/13/20
4 5 6
D
C.5
C
SCOPE OF WORK
TISSUE CULTURELAB6029
TISSUE CULTURELAB6019
MONITORING LAB6028
EQUIPMENT LAB6027
CORRIDOR6002
EQUIPMENTCORRIDOR
6030
STORAGE ROOM6031
SOLVENT STORAGE6032
CORRIDOR6037
LAB SUPPLY ROOM6035
ELEC ROOM6036
PLUMBING CLOSET621
COLD ROOM6017
MICROSCOPEROOM6022
EQUIPMENTCORRIDOR
6021
EQUIPMENT ROOM6023
EQUIPMENTCORRIDOR
6018
CORRIDOR6020
CORRIDOR6026
BIOSAFETY CABINET
BIOSAFETY CABINET
STACKED INCUBATOR
STACKED INCUBATORS
STACKED INCUBATOR
BIOSAFETY CABINET
BIOSAFETY CABINET
STACKED INCUBATOR
V
V
V
V
6019
-A
V
V
NEW
1
2
"NDCW,
1
2
"NDHW DROPS & 2"LW&V
IN WALL PARTITION TO NEW LAB SINK LSK-1
CONNECT TO EXISTING LAB WASTE PIPE IN WALL
1
PLUMBING DMOLITION AND NEW WORK NOTES
NEW 1
1
2
"ROS DROP & RISE IN WALL PARTITION TO FEED THE NEW
RO FAUCET. PROVIDE
1
2
"RO SHUT-OFF VALVE IN CASEWORK .
3
NEW
3
4
"LAVC SHUT-OFF BALL VALVE EXPOSED ALONG THE BSC .
PROVIDE PIPE REDUCER AND CONNECTION ADAPTORS TO BSC
PRE-PIPED PIPING.
7
REMOVE PORTION OF THE 1
1
2
"TWS AND CONNECT ON BOTH ENDS
WITH NEW 1
1
2
"TWS LOOP AND EXTEND TO NEW EMERGENCY EYE
WASH LOCATIONS.
8
CONNECT TO EXISTING 2"NDCW AND 1
1
2
"NDHW MAINS WITH NEW
1
2
"NDCW &
1
2
"NDHW PIPING, PROVIDE SHUT-OFF VALVES AND
EXTEND TO NEW LAB SINK LOCATIONS.
9
NEW 1"LVAC DROP IN WALL TO APPROXIMATELY 2 FEET ABOVE
FINISH FLOOR TO
3
4
"LAVC SHUT-OFF BALL VALVE EXPOSED
ALONG WALL TO SERVE THE BSC'S.
6
REMOVE PORTION OF THE 1
1
2
"ROS AND CONNECT ON BOTH ENDS
WITH NEW 1
1
2
"ROS LOOP AND EXTEND TO NEW RO FAUCET
LOCATIONS.
10
NEW (2) 1
1
2
"TWS DROP & RISE IN WALL PARTITION TO
FEED THE NEW EMERGENCY EYE WASH EW-1. PROVIDE
1
2
" TW
SHUT-OFF VALVE IN CASEWORK SERVING EW-1.
2
NEW
3
4
"LVAC DROP IN WALL TO WALL MOUNTED VACUUM
TURRET (T-1)
5
CONNECT TO EXISTING 3"LVAC MAIN WITH NEW 1
1
2
"LVAC PIPING,
PROVIDE SHUT-OFF VALVE AND EXTEND TO LAB VACUUM TURRETS
AND BIO SAFETY CABINETS
11
NEW
1
2
"CO2 DROP IN WALL TO SHUT-OFF BALL VALVE
LOCATED ALONG WALL AT 7'-6" OF FINISH FLOOR. LOCATE
THE VALVE TO THE SIDE OF THE STACKED INCUBATORS AND
PROVIDE CONNECTION ADAPTOR TO PRESSURE REGULATOR
AND SERRATION CONNECTION TO TYGON TUBING PROVIDED
AND INSTALLED BY OWNER TO SERVE STAKED INCUBATOR.
REFER TO DETAIL NO: #2 ON DRAWING P.001
4
NDHW
CA
ROS
NDHC
NDCW
LVAC
N
CO2
1"
1
1
2
"
3"2"2"
1
1
2
"
3
4
"
TWR
TWS
1"
1
1
2
"1
1
2
"
ND
HW
CA
RO
S
ND
HC
ND
CW
LV
AC
N
CO
2
TW
R
TW
S
TWR
NDHW
CA
TWS
NDHC
NDCW
LVAC
N
CO2
ROS
1"
1
1
2
"
3"2"2"
1
1
2
"
3
4
"
1"
1
1
2
"1
1
2
"
LV
LV
LV
2"
2"
2"
CO
2
CO2
TWR
NDHW
CA
ROS
TWS
NDHC
NDCW
LVAC
N
CO2
ND
CW
ND
HW
CA
LV
AC
RO
S
RO
S
CO
2
TW
S
TW
S
ND
CW
ND
HW
LV
AC
RO
S
RO
S
TW
R
ND
HW
CA
TW
S
ND
HC
ND
CW
LV
AC
N
CO
2
RO
S
ND
CW
ND
HW
CO
2
TW
TW
LV
LV
AC
LV
AC
LVAC
LVAC
LV
AC
CO2
NDHW
NDCW
LVAC
NDHW
NDCW
LVAC
TWR
NDHW
CA
ROS
TWS
NDHC
NDCW
LVAC
N
CO2
CO2
CO2
ND
CW
ND
HW
CO
2
TW
TW
LV
TW
RO
S
RO
S
RO
S
RO
S
TW
ROS
ROS
ND
CW
ND
HW
RO
S
CO
2
CO
2
TW
TW
LV
AC
RO
S
LV
T-1
T-1
T-1
T-1
INC'S
INC'S
INC'S
BSC
BSC
BSC
BSC
BSC
BSC
BSC
BSC
LVAC
LVACLVAC
LVAC
LVAC
LV
AC
LV
AC
LV
AC
LV
AC
LV
AC
ETR
ETR
ETR
ETR
ETR
LSK-1
EW-1
EW-1 LSk-1
1
2
"
3
4
"
1"
3
4
"
3
4
"
LV
AC
1
2
4
4
6
9
8
10
12
3
5
7
5 4
4
4
11
5
6
7
5
4
7
7
13
AP
1
2
3
CONNECT TO NEW
1
2
"CO2 EXISTING
1
2
"CO2 PIPE, PROVIDE
SHUT-OFF BALL VALVE AND EXTEND TO NEW INCUBATORS . ALSO
ADD AN ISOLATION VALVE ON EXISTING PIPE TO ROOM 6027
12
INSTALL A 12"x12" WALL ACCESS PANEL AT EXISTING OPEN END
CONDENSATE DRAIN LOCATION. COORDINATE COLOR WITH
ARCHITECT.
13
1"
1
1
2
"
INCS
1
2
"
1
1
2
"
3
4
"
1
2
"
1
2
"
1
1
2
"
1
2
"
1
1
2
"
2"
2"
1
1
2
"
1
1
4
"
1
1
2
"
3
4
"
PLUMBING
LEVEL 6
DEMOLITION &
NEW WORK PLAN
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
KEY PLAN
1 2 3 5 7
8
A.7
B
C
C.5
E
F
G
OFFICE6010
OFFICE6011
OFFICE6012
DSELAB6016
6019
MICROSCOPEROOM6022
EQUIPMENTLAB6027
MONITORINGLAB6028
EQUIPMENTLAB6029
STORAGEROOM6031
SOLVENTSTORAGE6032
GLASSWASH6069
OPENOFFICEAREA6063
CELLCULTURE6058
MASSSPEC6057
OPEN LAB6056
EQUIPMENTCORRIDOR
6053
DNAROOM6055
TISSUECULTURE6054
6050
EQUIPMENT6048
STORAGE/FREEZERROOM6045
HUMANBIOLOGY
LABORATORY6046
OFFICE6042
OFFICE6043
EQUIPMENTROOM6039
STABILITYCHAMBER
6040
MASSSPEC6038
MASSSPEC6025
ELECROOM6036
LABSUPPLYROOM6035
BIOREPOSITORYROOM6068
SAMPLERECEIVING
ROOM6074
CONFERENCE6067
CONFERENCE6003
CONFERENCE6004
CONFERENCE6005
VIPERLAB6014
EQUIPMENTCORRIDOR
6021
EQUIPMENTROOM6023
COLDROOM6047
COLDROOM6052
MEETINGAREA6059
OPENOFFICEAREA6007
INNOVATIONBAR6008
COPY6009
OPENOFFICEAREA6013
EQUIPMENTCORRIDOR
6018
DSE LAB6015
COLDROOM6017
EQUIPMENTCORRIDOR
6030
CORRIDOR6002
CORRIDOR6001
CORRIDOR6075
CORRIDOR6073
CORRIDOR6006
OPENOFFICEAREA6041
TEL/DATAIDF6072
CORRIDOR6071
CORRIDOR6037
D
E5
E6
E3
4
STORAGE6060
STORAGE6064
KITCHEN6065
BREAKRM6066
MEDIAPREPROOM6062
POD6033
POD6034
COPY/MAIL6044
CORRIDOR6026
CORRIDOR6020
CONFERENCE6061
6
STAIR 1S1-6
SERVICEELEVATOR
LOBBY602
STAIR 2S2-6
STAIR 3S3-6
ELEV #2
ELEV #3
ELEV #4
ELEV #8
ELEV #7
ELEV #6
ELEV #5
MECH.PIPING606
NORMALELECTRICAL
ROOM604
PLUMB.CLOSET621
LIFESAFETY605
PLUMB.CLOSET620
JANITOR607
MEN610
WOMEN609
SHOWER608
BIOWASTESTORAGE
651
EQUIPMENTLAB
CLINICALBIOMARKERS
OPEN LAB
ELEVATORLOBBY601
CORRIDOR6049
IMPORTANT NOTE:
SCOPE OF WORK
NORTH
ISSUED FOR BID
3/2/20
1
4
" = 1'-0"
P-101
SCALE:
1/4" = 1'-0"1 PLUMBING - LEVEL 6 DEMOLITION & NEW WORK PLAN
Drawn By: JES Checked By: WMN
V1 6th Floor Tissue CultureLabs
:3/13/20
CONTACTOR, RATING AND TYPE AS NOTED ON DRAWINGS
"EWC" - INDICATES CONNECTION TO ELECTRIC WATER COOLER
"ATC" - INDICATES CONNECTION TO AUTOMATIC TEMPERATURE
CONTROL PANEL
"DDC" - INDICATES CONNECTION TO DIRECT DIGITAL CONTROL PANEL
"FSD" - INDICATES CONNECTION TO FREE/SMOKE DAMPER
"MD" - INDICATES CONNECTION TO MOTORIZED DAMPER
"P" - INDICATES POWER CONNECTION
"T" - INDICATES TEL/DATA CONNECTION
DISCONNECT SWITCH (FUSED), "AS" INDICATES AMPERE SWITCH RATING,
"AF" INDICATES AMPERE FUSE RATING.
HOME RUN, 3/4"C. WITH 2#12 AND 1#12 GND. CONNECTED TO A 20A-1P
CIRCUIT BREAKER. "N22A" REPRESENTS PANEL NAME AND "2" INDICATES
CIRCUIT NUMBER IN PANEL. WHEN MULTIPLE CIRCUITS ARE SHOWN,
HASH MARKS INDICATE NUMBER OF PHASE AND NEUTRAL CONDUCTORS
(GROUND CONDUCTOR IS NOT INDICATED IN HASH MARKS).
JUNCTION BOX, 4 11/16" SQUARE (UNLESS OTHERWISE NOTED)
JUNCTION BOX, FLUSH MOUNT IN FLOOR, REFER TO SPECIFICATIONS FOR
TYPE
30AS
30AF
"C" - INDICATES DEVICE TO BE MOUNTED ABOVE COUNTER SURFACE
"INC" - INDICATES DEVICE FOR AN INCUBATOR MOUNTED AT 7'-6" A.F.F.
"GFCI" - INDICATES RECEPTACLE FED FROM GFCI TYPE CIRCUIT BREAKER
"WP" - INDICATES RECEPTACLE MOUNTED IN A WEATHERPROOF
ENCLOSURE
DUPLEX RECEPTACLE - "2" INDICATES CIRCUIT NUMBER
EXISTING SPECIAL PURPOSE RECEPTACLE - FIELD CONFIRM EXACT NEMA
CONFIGURATION
WALL MOUNTED, SINGLE OR DOUBLE FACE ILLUMINATED EXIT SIGN,
FED FROM LIFE SAFETY BRANCH WITH FACES AND ARROWS AS
INDICATED ON DRAWINGS.
UNIVERSAL MOUNT SINGLE OR DOUBLE FACE ILLUMINATED EXIT SIGN,
FED FROM LIFE SAFETY BRANCH WITH FACES AND ARROWS AS
INDICATED ON DRAWINGS.
SINGLE POLE TOGGLE SWITCH, WALL MOUNTED AT 48" UNLESS
OTHERWISE NOTED. "a" INDICATES LIGHT FIXTURE CONTROL
DETAIL IDENTIFIER
"1" INDICATES DETAIL NUMBER
"E0.0" INDICATES SHEET NUMBER
DRAWING REVISION MARKER
DRAWING REVISION CLOUD
LIGHT FIXTURE NOTES
(TYPICAL FOR ALL LIGHT FIXTURES):
"FR1" INDICATES FIXTURE TYPE AS
SPECIFIED ON THE LIGHTING FIXTURE
SCHEDULE.
"2,a" INDICATES FIXTURE IS
CONNECTED TO CIRCUIT #2 AND
CONTROLLED BY SWITCH "a"
THREE-WAY TOGGLE SWITCH, WALL MOUNTED AT 48" UNLESS OTHERWISE
NOTED. - "a" INDICATES LIGHT FIXTURE CONTROL
FOUR-WAY TOGGLE SWITCH, WALL MOUNTED AT 48" UNLESS OTHERWISE
NOTED. - "a" INDICATES LIGHT FIXTURE CONTROL
MANUAL MOTOR STARTER W/THERMAL OVERLOAD PROTECTION & PILOT
LIGHT
DISCONNECT SWITCH (UNFUSED).
CIRCUIT BREAKER IN NEMA 1 ENCLOSURE
120/208V,3Ø,4W SURFACE MOUNTED PANEL, "CR2W4A" INDICATES PANEL
DESIGNATION
FLEXIBLE POWER CONNECTION TO EQUIPMENT AS NOTED
QUAD RECEPTACLE
DUPLEX RECEPTACLE WITH INTEGRAL GROUND FAULT CIRCUIT
INTERRUPTER
POWER POLE - PROVIDE AS SPECIFIED ON DRAWINGS
HOME RUN, 3/4"C. WITH 4#10 AND 1#10 GND. CONNECTED TO A 30A-3P
CIRCUIT BREAKER-REFER TO THE BRANCH CIRCUIT SCHEDULE FOR
CONDUCTOR SIZES AND QUANTITIES. . "N22A" REPRESENTS PANEL
NAME AND "2,4,6" INDICATES CIRCUIT NUMBERS IN PANEL.
N22A-2,4,6
30A-3P+
"C" - INDICATES MOUNTED ABOVE COUNTER HEIGHT
CEILING MOUNTED LOW VOLTAGE OCCUPANCY SENSOR. MATCH
EXISTING BUILDING STANDARDS. "a,b" - INDICATES DEVICE CONTROLLING
MULTIPLE POLE SWITCHING
N22A-2,4
EXISTING DEVICE, EQUIPMENT OR WIRING TO BE REMOVED
EXISTING DEVICE, EQUIPMENT OR WIRING TO REMAIN
NEW DEVICE, EQUIPMENT OR WIRING
VARIABLE FREQUENCY DRIVE
ELECTRIC TRAP PRIMER
MAGNETIC MOTOR STARTER
TIME CLOCK/SWITCH, RATING AND TYPE AS NOTED ON DRAWINGS
CONTROL PANEL
FLEXIBLE POWER CONNECTION NOTES:
PULL BOX, SIZED AS REQUIRED PER THE NATIONAL ELECTRIC CODE
MOTOR ("NUMBER" INDICATES HORSE POWER - 5 HORSEPOWER)
CONDUIT TURNING UP
CONDUIT TURNING DOWN
COMMUNICATION DEVICE NOTES:
WALL PHONE WORK AREA OUTLET DEVICE
RECEPTACLE NOTES:
2'X2' LIGHT FIXTURE
2'X4' LIGHT FIXTURE
ELECTRICAL LEVEL 6 DEMOLITION PLAN
ELECTRICAL LEGEND AND GENERAL NOTES
DESCRIPTION
E-101
E-001
DRAWING No
PROJECT GENERAL NOTES
TP
J
J
PB
5
N22A-2
2
EMERGENCY DUPLEX RECEPTACLE
C
CP
CB
TC
VFD
PP
1X4' LIGHT FIXTURE
DOWN LIGHT
WALL WASHER
WALL MOUNTED LIGHT
1
E0.0
1
ELECTRICAL DRAWING LIST
DRAWING NOTES AND DESIGNATIONS
EXISTING CONDITIONS DESIGNATIONS
LINE TYPE LEGEND
POWER DEVICES LEGEND
POWER DISTRIBUTION EQUIPMENT LIGHTING CONTROL LEGEND
LIGHTING LEGEND
TELECOMMUNICATIONS LEGEND
WALL MOUNTED LOW VOLTAGE OCCUPANCY SENSOR, WALL MOUNTED AT
48" UNLESS OTHERWISE NOTED. MATCH EXISTING BUILDING STANDARDS.
1. THE CONTRACTOR SHALL FURNISH LABOR, MATERIALS, TOOLS AND OTHER
EQUIPMENT REQUIRED TO INSTALL THE WORK SHOWN AND SPECIFIED. THE
CONTRACTOR SHALL FURNISH AND INSTALL ITEMS NECESSARY FOR A COMPLETE
ELECTRICAL SYSTEM. MATERIALS SHALL BE NEW AND SHALL BEAR THE REGISTERED
UL MARK. WORK SHALL CONFORM WITH THE NATIONAL FIRE PROTECTION
ASSOCIATION STANDARD 70 (NEC), THE NATIONAL ELECTRICAL CODE (NEC), AND
APPLICABLE FEDERAL, STATE AND LOCAL CODES. CONTRACTOR SHALL SECURE
PERMITS AND PAY THE FEES REQUIRED TO CARRY OUT HIS WORK. THE CONTRACTOR
SHALL FURNISH COPIES OF CERTIFICATES AND PERMITS TO THE ARCHITECT.
2. THE DRAWINGS AND SPECIFICATIONS INDICATE THE INTENT OF THE DESIGN AND
SHALL BE CONSIDERED AS DIAGRAMMATIC ONLY. EXACT LOCATIONS FOR OUTLETS
AND EQUIPMENT SHALL BE DETERMINED AT THE SITE, AS WORK PROGRESSES
DIMENSIONS AND CONDITIONS SHALL BE CHECKED AND VERIFIED BY THE
CONTRACTOR AT THE SITE. FINAL WORK SHALL BE DOCUMENTED ON AS BUILT
RECORD DRAWINGS.
3. PIPING, CONDUITS AND EQUIPMENT OF ALL TRADES SHALL BE PROPERLY
COORDINATED AND SET TO MAINTAIN THE CLEARANCES REQUIRED BY APPLICABLE
FEDERAL, STATE AND LOCAL CODES.
4. CONDUIT RUNS CROSSING EXPANSION JOINTS SHALL HAVE EXPANSION OR
EXPANSION DEFLECTION TYPE FITTINGS, AS REQUIRED VERIFY EXISTING JOINTS BY
FIELD MEASUREMENTS.
5. OUTDOOR ELECTRICAL EQUIPMENT SHALL BE NEMA 3R TYPE, UNLESS OTHERWISE
NOTED.
6. RACEWAYS AND CABLE SHALL BE RUN CONCEALED IN FINISHED SPACES UNLESS
OTHERWISE NOTED.
7. WIRING DEVICES SHALL BE MOUNTED IN ACCORDANCE WITH THE LATEST
REQUIREMENTS OF THE ACCESSIBILITY CODE.
8. EXIT SIGNS AND EMERGENCY BATTERY UNITS AND LIGHTING FIXTURES DESIGNATED
AS NIGHT LIGHTS SHALL BE UNSWITCHED.
9. ALL BRANCH CIRCUITS, (LIGHTING AND POWER) SHALL HAVE A DEDICATED NEUTRAL
CONDUCTOR. COMMON OR SHARING OF NEUTRALS WILL NOT BE ALLOWED. NO MORE
THAN (3) CIRCUITS (SIX CURRENT CARRYING CONDUCTORS) SHALL BE RUN IN A
SINGLE CONDUIT.
10.RECEPTACLES, SWITCHES, LIGHTING FIXTURES, SMOKE DETECTORS, ETC INDICATE
QUANTITY, EXACT LOCATIONS OF DEVICES SHALL BE DETERMINED IN THE FIELD AND
COORDINATED WITH ARCHITECTURAL DRAWINGS
11.THIS IS A STANDARD SYMBOL LIST. ALL DEVICE SYMBOLS AND ABBREVIATIONS MAY
NOT NECESSARILY APPEAR ON THE FLOOR PLANS OR DETAIL SHEET. ONLY THOSE
SYMBOLS INDICATED ON THE FLOORS PLANS ARE USED AND OTHERS SHOULD BE
DISREGARDED.
12.MOUNTING HEIGHTS SHALL BE AS INDICATED ON ARCHITECTURAL DRAWINGS. THE
MOUNTING HEIGHT DETAIL SHALL BE USED AS A GUIDE IN THE ABSENCE OF THE
ARCHITECTURAL DRAWINGS.
13.CONTRACTOR SHALL VERIFY ALL DOORS SWINGS BEFORE INSTALLING SWITCH BOXES.
14.FOR EXACT LOCATION OF LIGHTING FIXTURES, SEE REFLECTED CEILING PLAN
DRAWINGS. FOR MOUNTING HEIGHT OF UNDERCABINET LIGHTING FIXTURES AND
OTHER TASK LIGHTING, REFER TO ARCHITECTURAL ELEVATION DRAWINGS.
15.ELECTRICAL CONTRACTOR IS TO COORDINATE THE EXACT LOCATION OF LIGHTING
FIXTURES IN MECHANICAL AND STORAGE AREAS WITH OTHER TRADES.
16.FOR EXACT LOCATION OF MECHANICAL EQUIPMENT, (AC UNITS, FANS, PUMPS, ETC)
REFER TO RESPECTIVE TRADES DRAWINGS.
17.CURRENT CARRYING MATERIAL USED SHALL BE COPPER, INCLUDING PANELBOARD
BUS MATERIALS AND TRANSFORMER WINDINGS.
18.FURNISH GROUNDING/ BONDING BUSHINGS ONTO ALL CONDUIT ENTERING/ LEAVING
BOXES.
19. ALL GROUND CONDUCTORS SHALL BE GREEN, ISOLATED GROUND CONDUCTORS
SHALL BE GREEN/ YELLOW STRIPED, AND NEUTRAL CONDUCTORS SHALL BE WHITE.
20.WHERE EXISTING BRANCH CIRCUITS ARE REUSED TO FEED NEW CIRCUITS FED FROM
GFCI OR AFCI CIRCUIT BREAKERS OR WHICH FEED NEW GFCI RECEPTACLES, THE
CONTRACTOR SHALL FIELD VERIFY IF EACH CIRCUIT CONTAINS A DEDICATED
NEUTRAL WHICH IS REQUIRED FOR PROPER OPERATION OF GFCI AND AFCI CIRCUIT
BREAKERS AND RECEPTACLES. IF A DEDICATED NEUTRAL IS NOT PRESENT,
CONTRACTOR SHALL INFORM ARCHITECT AND ENGINEER IN WRITING VIA RFI.
21.ALL TELECOMMUNICATIONS CABLING SHALL BE PLENUM RATED.
22.THE CONTRACTOR SHALL CARRY ALL PREMIUM TIME COSTS ASSOCIATED WITH
CABLING REQUIRED IN OCCUPIED TENANT AREAS.
FR1
2,a
2,a
FR1
FR1
2,a
VOLUME CONTROL SWITCH
SPEAKER (FLUSH CEILING MOUNTED)
PUBLIC ADDRESS/PAGING LEGEND
NOTES:
1. REFER TO MECHANICAL AND PLUMBING PLANS AND SCHEDULES
FOR ACTUAL EQUIPMENT NAME AND ASSOCIATED DESCRIPTION.
MECHANICAL EQUIPMENT TAG "EF"
INDICATES EQUIPMENT TYPE (EXHAUST
FAN) "1" INDICATES EQUIPMENT NUMBER
EF
1
MECHANICAL EQUIPMENT IDENTIFIER LEGEND
W
2,a
R1
2,a
WW1
2,a
W1
EMERGENCY QUAD RECEPTACLE
EMERGENCY DUPLEX RECEPTACLE WITH INTEGRAL GROUND FAULT
CIRCUIT INTERRUPTER
480/277V,3Ø,4W SURFACE MOUNTED PANEL, "L45" INDICATES PANEL
DESIGNATION
S251
L45
SPSP
VV
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION
DIGITAL PROXIMITY CARD READER
ELECTRIC STRIKE PROVIDED BY DOOR HARDWARE MANUFACTURER,
WIRED BY SECURITY CONTRACTOR
DEMOLITION GENERAL NOTES
WIRING METHODS
SECURITY DEVICES LEGEND
1. REFER TO THE ARCHITECTURAL DRAWINGS FOR THE FULL EXTENT OF THE SCOPE OF
DEMOLITION. DISCONNECT AND MAKE SAFE ALL ELECTRICAL EQUIPMENT IDENTIFIED
FOR REMOVAL ON THE ARCHITECTURAL, HVAC, PLUMBING AND FIRE PROTECTION
PLANS. THE ELECTRICAL SCOPE MAY EXTEND BEYOND THE AREA DEFINED BY THE
ARCHITECTURAL DEMOLITION LIMITS TO FULLY COMPLY WITH THE VARIOUS
REQUIREMENTS DEFINED BY THESE NOTES.
2. THE ELECTRICAL DEMOLITION PLANS INDICATE GENERAL INTENT AND ARE NOT
INTENDED TO SHOW ALL COMPONENTS AND ITEMS TO BE REMOVED OR RETAINED.
THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMISSION OF
THEIR BID TO BECOME FAMILIAR WITH THE ACTUAL WORKING CONDITIONS AND
EXTENT OF WORK. DEVICES AND EQUIPMENT LOCATED ON WALLS AND/OR CEILINGS
DESIGNATED TO BE REMOVED SHALL BE DISCONNECTED AND MADE SAFE. THE
ELECTRICAL CONTRACTOR SHALL IMMEDIATELY NOTIFY THE OWNER'S
REPRESENTATIVE AND ARCHITECT OF ANY UNANTICIPATED OR HIDDEN CONDITIONS
ENCOUNTERED DURING DEMOLITION.
3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ALL
SYSTEMS OR BUILDING COMPONENTS DAMAGED DURING EXECUTION OF THE WORK.
DAMAGE SHALL INCLUDE, BUT NOT BE LIMITED TO, THE DESTRUCTION OR DISPOSAL
OF ITEMS INTENDED TO REMAIN OR BE SALVAGED.
4. THE ELECTRICAL CONTRACTOR SHALL CIRCUIT TRACE AND LABEL ALL EXISTING
BRANCH CIRCUITS AND FEEDERS WITHIN OR ASSOCIATED WITH THE DEMOLITION
SCOPE, PRIOR TO DE-ENERGIZING AND DISCONNECTION. ALL CIRCUITS WITHIN
PANELBOARDS, LOAD CENTERS, MOTOR CONTROL CENTERS, AND SWITCHBOARDS
IDENTIFIED FOR REMOVAL, SHALL BE TRACED AND FIELD LABELED TO ENSURE THAT
NO AREA OUTSIDE THE DEMOLITION SCOPE LIMIT IS AFFECTED.
5. IN ANY AREA REQUIRING THE PERFORMANCE OF ANY TRADE'S WORK, THE
ELECTRICAL CONTRACTOR SHALL CAREFULLY REMOVE AND STORE ANY OR ALL
ELECTRICAL ITEMS IN PATH OF WORK, REINSTALLING AND RECONNECTING SAME AS
REQUIRED, IN ACCORDANCE WITH THE PLANS AND/OR AS DIRECTED AFTER
COMPLETION OF OTHER TRADES WORK IN THAT AREA.
6. THE ELECTRICAL CONTRACTOR SHALL IDENTIFY ALL BRANCH CIRCUITS, FEEDERS AND
SYSTEM COMPONENTS WHICH ARE TO REMAIN WITHIN THE AREA OF DEMOLITION
SCOPE. THERE SHALL BE NO INTERRUPTION OF SERVICE TO ANY AREA OUTSIDE THE
SCOPE LIMITS WITHOUT WRITTEN APPROVAL FROM THE OWNER'S REPRESENTATIVE.
EXISTING EQUIPMENT TO REMAIN SHALL BE LEFT IN A CODE COMPLIANT CONDITION.
7. THE ELECTRICAL CONTRACTOR SHALL TAKE INVENTORY OF ELECTRICAL ITEMS THAT
ARE REMOVED AND PROVIDE A LIST TO THE OWNER FOR THEIR SELECTION OF ITEMS
TO BE RETAINED. ALL ITEMS REJECTED BY THE OWNER SHALL BECOME THE
PROPERTY OF THE CONTRACTOR, AND SHALL BE REMOVED FROM THE SITE AND
DISPOSED OF LEGALLY.
8. THE ELECTRICAL CONTRACTOR SHALL DE-ENERGIZE AND REMOVE ALL CONDUCTORS
AND RACEWAYS WITHIN THE AREA OF DEMOLITION SCOPE TO THEIR POINT OF ORIGIN.
ITEMS IDENTIFIED FOR DEMOLITION SHALL NOT BE ABANDONED IN PLACE. RACEWAYS
THAT ENTER MASONRY WALLS AND FLOORS SHALL BE CUT FLUSH AT THE SURFACE
FOR PATCHING BY OTHERS. ALL CIRCUIT BREAKERS ASSOCIATED WITH THE
DEMOLITION SHALL BE DE-ENERGIZED, TRIPPED TO THE "OFF" POSITION AND
RE-LABELLED AS "SPARE". NEW TYPED UPDATED CIRCUIT DIRECTORIES SHALL ALSO
BE PROVIDED.
9. THE ELECTRICAL CONTRACTOR SHALL TEMPORARILY SUPPORT ALL ITEMS TO REMAIN
THAT ARE AFFECTED BY THE DEMOLITION OF BUILDING STRUCTURAL COMPONENTS
(WALLS, CEILINGS, PARTITIONS, ETC). CONTRACTOR SHALL TEMPORARILY SUPPORT
ITEMS AND SHALL PROVIDE PERMANENT SUPPORTS WHEN FINALIZED STRUCTURES
ARE IN PLACE.
10. ALL EXISTING ELECTRICAL EQUIPMENT THAT ARE TO BE RELOCATED SHALL BE
STORED IN A SAFE MANNER UNTIL SUCH TIME AS TO BE REINSTALLED. ANY DAMAGE
INCURRED TO EQUIPMENT SHALL BE RECTIFIED BY THE ELECTRICAL CONTRACTOR.
11. ALL REMOVED ITEMS SHALL BE LEGALLY DISPOSED OF UNLESS IDENTIFIED FOR
REUSE. THE OWNER'S REPRESENTATIVE SHALL INSPECT ALL RETAINED ITEMS, PRIOR
TO PLACEMENT IN THE IDENTIFIED STORAGE LOCATION BY THE ELECTRICAL
CONTRACTOR.
12.THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN FULLY FUNCTIONAL DURING THE
ENTIRE DEMOLITION AND CONSTRUCTION PERIOD. REUSE OF EXISTING FIRE ALARM
RACEWAYS SHALL NOT BE ALLOWED. ALL REQUIRED SYSTEM SHUTDOWNS SHALL BE
COORDINATED WITH AND APPROVED BY THE OWNER'S REPRESENTATIVE AND THE
AUTHORITY HAVING JURISDICTION. DEMOLITION OF THE EXISTING SYSTEM SHALL NOT
COMMENCE UNTIL THE NEW SYSTEM HAS BEEN COMPLETELY INSTALLED, TESTED AND
APPROVED BY THE AUTHORITY HAVING JURISDICTION.
13. ALL DEMOLITION SCOPE ASSOCIATED WITH LOW VOLTAGE SYSTEMS, INCLUDING BUT
NOT LIMITED TO, TELEPHONE, DATA, SECURITY, PAGING, CCTV, ETC SHALL BE
INCLUDED IN THIS CONTRACT.
14.REMOVED FLUORESCENT AND HID LAMPS AND BATTERIES SHALL BE RECYCLED BY A
FACILITY APPROVED BY THE OWNER'S REPRESENTATIVE. A UNIFORM HAZARDOUS
WASTE MANIFEST SHALL BE PREPARED FOR ALL DISPOSALS AND RETURNED WITH ALL
APPLICABLE SIGN-OFFS PRIOR TO APPLICATION FOR FINAL PAYMENT.
15. ALL BALLASTS IN LIGHTING FIXTURES TO BE DISPOSED SHALL BE VERIFIED TO BE PCB
FREE. ALL BALLASTS MANUFACTURED PRIOR TO 1979 AND NOT LABELED AS PCB FREE
SHALL BE CONSIDERED TO CONTAIN PCB's. PROVIDE WRITTEN REPRESENTATION TO
THE OWNER'S REPRESENTATIVE THAT CONFIRMS PCB FREE WASTE, WHERE PCB FREE
WASTE CANNOT BE VERIFIED. BALLASTS SHALL BE RECYCLED BY A FACILITY
APPROVED BY THE OWNER'S REPRESENTATIVE, WITH PCB COMPONENTS ELIMINATED
BY A HIGH TEMPERATURE INCINERATION. A UNIFORM HAZARDOUS WASTE MANIFEST
SHALL BE PREPARED FOR ALL DISPOSALS AND RETURNED WITH ALL APPLICABLE
SIGN-OFFS, PRIOR TO APPLICATION FOR FINAL PAYMENT. ALL HANDLING SHALL
CONFORM TO EPA REQUIREMENTS PROVIDE BREAKOUT COST FOR THIS SCOPE.
NORMAL SYSTEM FEEDERS
NORMAL BRANCH CIRCUITS
LOW VOLTAGE SYSTEM (TELEPHONE,
DATA, AND CATV) WIRING
EMERGENCY SYSTEM BRANCH CIRCUITS
XHHW/XHHW-2 CONDUCTORS IN EMT
THHN/THWN/XHHW/XHHW-2 CONDUCTORS IN
EMT OR MC CABLE
TYPE CMR, CM, MPR AND MP CABLES
THHN/THWN/XHHW/XHHW-2 CONDUCTORS IN
EMT
CR
ES
DRY TYPE TRANSFORMER, "T2" INDICATES SIZE AS PER TRANSFORMER
SCHEDULE. REFER TO 'DRY TYPE TRANSFORMER SCHEDULE' FOR FEEDER
AND CIRCUIT BREAKER SIZES
T2
KVA 15
LOW VOLTAGE SWITCH, WALL MOUNTED AT 48" UNLESS OTHERWISE
NOTED. FINISH SELECTED BY OWNER. LOW VOLTAGE SWITCH SHALL
BE COMPLETELY COMPATIBLE WITH LOW VOLTAGE VACANCY SENSOR
BEING CONTROLLED. 'D' - DENOTES DIMMER TYPE
LIGHT FIXTURE FED FROM EMERGENCY BRANCH
DOWN FED FROM LIGHT LIFE SAFETY BRANCH
QUAD RECEPTACLE WITH INTEGRAL GROUND FAULT CIRCUIT
INTERRUPTER
ELECTROMECHANICAL LOCKSET. PROVIDED BY DOOR HARDWARE
MANUFACTURER, WIRED BY SECURITY CONTRACTOR
EL
DOOR POSITION SWITCH CONTACTDPS
REQUEST TO EXIT DEVICEREX
TELECOMMUNICATIONS WORK AREA OUTLET DEVICE
AS A MINIMUM, FOR EACH SECURITY DEVICE PROVIDE A 4-11/16" x 2" DEEP
SQUARE BACK BOX AND SINGLE GANG MUD RING WITH (1) 1-1/4" CONDUIT
STUBBED UP TO ACCESSIBLE CEILING. REFER TO DETAIL 6/E401 AND
SPECIFICATIONS FOR ADDITIONAL ACCESS CONTROL REQUIREMENTS.
WIRELESS ACCESS POINT DEVICE
WAP
TP
FIELD WIRED, UL LISTED, MULTI-OUTLET RACEWAY WITH DEVICES, AS
INDICATED, MOUNTED 2'-0" ON CENTER. FOR ALL LOCATIONS PROVIDE
WIREMOLD V4000 BASE, COVER, AND DIVIDER. PROVIDE ALL REQUIRED
ACCESSORIES FOR A COMPLETE AND OPERABLE SYSTEM.
NEW SPECIAL PURPOSE RECEPTACLE - REFER TO 'SPECIAL PURPOSE
RECEPTACLE SCHEDULE' FOR NEMA CONFIGURATION AND ADDITIONAL
INFORMATION
1
1
480/277V,3Ø,4W FLUSH MOUNTED PANEL, "L45" INDICATES PANEL
DESIGNATION
L45
120/208V,3Ø,4W FLUSH MOUNTED PANEL, "CR2W4A" INDICATES PANEL
DESIGNATION
S251
CEILING MOUNTED LOW VOLTAGE VACANCY SENSOR. MATCH EXISTING
BUILDING STANDARD. "a,b" - INDICATES DEVICE CONTROLLING MULTIPLE
POLE SWITCHING
a
3
a
4
a
OC
SLIDE TO OFF DIMMER SWITCH, WALL MOUNTED AT 48" UNLESS
OTHERWISE NOTED. "a" INDICATES LIGHT FIXTURE CONTROL
D
a
a,b
OC
a,b
VC
Da
LV
ELECTRICAL LEVEL 6 NEW WORK LIGHTING PLANE-201
ELECTRICAL LEVEL 6 NEW WORK POWER PLANE-301
ELECTRICAL SCHEDULES AND DETAILSE-401
SPEAKER (WALL MOUNTED)SPSP
MAG LOCKSET. PROVIDED BY DOOR HARDWARE MANUFACTURER,
WIRED BY SECURITY CONTRACTOR
ML
POKE THROUGH TYPE FLOOR BOX. PROVIDE THOMAS & BETTS FLUSH
MOUNTED POKE THROUGH FLOOR BOX MODEL #FPT4-2P-6C-* AND COVER
MODEL #FPT4-CVR-*; COORDINATE FINISH COLOR WITH ARCHITECT.
PROVIDE WITH (1) DUPLEX RECEPTACLE AND PROVISIONS FOR TEL/DATA
FLUSH CEILING MOUNTED DUPLEX RECEPTACLE
FIRE ALARM LEGEND, GENERAL NOTES, RISER, AND DETAILSFA-001
FIRE ALARM LEVEL 6 NEW WORK PLANFA-101
NOTES:
1.
AS A MINIMUM, FOR EACH TELECOMMUNICATION DEVICE PROVIDE A 4-11/16" x 2"
DEEP SQUARE BACK BOX AND SINGLE GANG MUD RING WITH (1) 1-1/4" CONDUIT
STUBBED UP TO ACCESSIBLE CEILING.
NOTES:
1.
EXISTING DEVICE SHALL BE REMOVED INCLUDING ALL ASSOCIATED RACEWAYS
AND CIRCUITRY BACK TO ITS SOURCE
EXISTING DEVICE SHALL REMAIN AND SHALL BE MAINTAINED
EXISTING DEVICE SHALL BE RELOCATED
NEW LOCATION OF EXISTING TO BE RELOCATED DEVICE. EXTEND AND MODIFY
EXISTING WIRING AS REQUIRED TO NEW DEVICE LOCATION. MATCH EXISTING
WIRING
EXISTING DEVICE TO BE REPLACED WITH NEW. NEW DEVICE SHALL HAVE THE
SAME ELECTRICAL CHARACTERISTICS AS EXISTING DEVICE BEING REPLACED,
UNLESS INDICATED OTHERWISE
X
XM
XR
XL
XN
FLUSH CEILING MOUNTED TELECOMMUNICATIONS WORK AREA
OUTLET DEVICE
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
NORTH
ISSUED FOR BID
3/2/20
ELECTRICAL
LEGEND AND
GENERAL NOTES
N.T.S.
E-001
Drawn By: DM Checked By: AJR
V1 6th Floor Tissue CultureLabs
:3/13/20
DSELAB6016
6019
MICROSCOPEROOM6022
EQUIPMENTLAB6027
MONITORINGLAB6028
EQUIPMENTLAB6029
VIPERLAB6014
EQUIPMENTCORRIDOR
6021
EQUIPMENTROOM6023
EQUIPMENTCORRIDOR
6018
DSE LAB6015
COLDROOM6017
EQUIPMENTCORRIDOR
6030
CORRIDOR6020
STAIR 3S3-6
MECH.PIPING606
PLUMB.CLOSET621
LIFESAFETY605
EQUIPMENTLAB
D
LV
F
F
D
LV
D
LV
F
'0262' (XM)
'LB263' (XM)
X
X
XR
XR
XR
XR
XR
XR
XR
XR
XR
XR
X
X
XM XM
XMXM
XM XM
XMXM
XM
XMXM
XM
XM
XM
XM
XM
XM
XM
XM
XM
XM
XM
XM
AREA OF RENOVATION
ELECTRICAL
LEVEL 6
DEMOLITION PLAN
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
KEY PLAN
1 2 3 5 7
8
A.7
B
C
C.5
E
F
G
OFFICE6010
OFFICE6011
OFFICE6012
DSELAB6016
6019
MICROSCOPEROOM6022
EQUIPMENTLAB6027
MONITORINGLAB6028
EQUIPMENTLAB6029
STORAGEROOM6031
SOLVENTSTORAGE6032
GLASSWASH6069
OPENOFFICEAREA6063
CELLCULTURE6058
MASSSPEC6057
OPEN LAB6056
EQUIPMENTCORRIDOR
6053
DNAROOM6055
TISSUECULTURE6054
6050
EQUIPMENT6048
STORAGE/FREEZERROOM6045
HUMANBIOLOGY
LABORATORY6046
OFFICE6042
OFFICE6043
EQUIPMENTROOM6039
STABILITYCHAMBER
6040
MASSSPEC6038
MASSSPEC6025
ELECROOM6036
LABSUPPLYROOM6035
BIOREPOSITORYROOM6068
SAMPLERECEIVING
ROOM6074
CONFERENCE6067
CONFERENCE6003
CONFERENCE6004
CONFERENCE6005
VIPERLAB6014
EQUIPMENTCORRIDOR
6021
EQUIPMENTROOM6023
COLDROOM6047
COLDROOM6052
MEETINGAREA6059
OPENOFFICEAREA6007
INNOVATIONBAR6008
COPY6009
OPENOFFICEAREA6013
EQUIPMENTCORRIDOR
6018
DSE LAB6015
COLDROOM6017
EQUIPMENTCORRIDOR
6030
CORRIDOR6002
CORRIDOR6001
CORRIDOR6075
CORRIDOR6073
CORRIDOR6006
OPENOFFICEAREA6041
TEL/DATAIDF6072
CORRIDOR6071
CORRIDOR6037
D
E5
E6
E3
4
STORAGE6060
STORAGE6064
KITCHEN6065
BREAKRM6066
MEDIAPREPROOM6062
POD6033
POD6034
COPY/MAIL6044
CORRIDOR6026
CORRIDOR6020
CONFERENCE6061
6
STAIR 1S1-6
SERVICEELEVATOR
LOBBY602
STAIR 2S2-6
STAIR 3S3-6
ELEV #2
ELEV #3
ELEV #4
ELEV #8
ELEV #7
ELEV #6
ELEV #5
MECH.PIPING606
NORMALELECTRICAL
ROOM604
PLUMB.CLOSET621
LIFESAFETY605
PLUMB.CLOSET620
JANITOR607
MEN610
WOMEN609
SHOWER608
BIOWASTESTORAGE
651
EQUIPMENTLAB
CLINICALBIOMARKERS
OPEN LAB
ELEVATORLOBBY601
CORRIDOR6049
IMPORTANT NOTE:
SCOPE OF WORK
NORTH
ISSUED FOR BID
3/2/20
1
4
" = 1'-0"
E-101
1
ELECTRICAL DEMOLITION PLAN
1/4"=1'-0"
DEMOLITION PLAN GENERAL NOTES:
1. REFER TO GENERAL DEMOLITION NOTES ON DRAWING E-001 FOR ADDITIONAL
REQUIREMENTS.
2. WORK MAY BE REQUIRED OUTSIDE OF THE PROJECT'S AREA OF RENOVATION. CONTRACTOR
SHALL NOT ASSUME THAT AREA OF RENOVATION IS CONSIDERED THE SCOPE OF WORK AREA.
3. EXISTING LIGHTING BRANCH CIRCUIT SHALL BE INTERCEPTED IN A NEW JUNCTION BOX AND
MADE SAFE FOR EXTENSION TO NEW FIXTURES BEING PROVIDED FOR THE PROJECT. REFER
TO NEW WORK PLAN FOR EXTENT OF WORK.
Drawn By: DM Checked By: AJR
V1 6th Floor Tissue CultureLabs
:3/13/20
5 6
6019
-A
VIPERLAB6014
DSE LAB6015DSE
LAB6016
MECH.PIPING606
LIFESAFETY605
D
LV
D
LV
D
LV
'0262' (XM)
'LB263' (XM)
XM XM
XMXM
XM XM
XM
AREA OF RENOVATION
5 6
TISSUE CULTURELAB6029
MONITORING LAB6028
TISSUE CULTURELAB6019
EQUIPMENT LAB6027
MICROSCOPEROOM6022
EQUIPMENTCORRIDOR
6021
EQUIPMENT ROOM6023
EQUIPMENTCORRIDOR
6018
COLD ROOM6017PLUMBING CLOSET
621
EQUIPMENTCORRIDOR
6030
CORRIDOR6002
STAIR
XL
XL
L1
L1
L1
L1
L1L1
1
1
1
1
1
1
2
2
ELECTRICAL
LEVEL 6
NEW WORK LIGHTING PLAN
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
KEY PLAN
1 2 3 5 7
8
A.7
B
C
C.5
E
F
G
OFFICE6010
OFFICE6011
OFFICE6012
DSELAB6016
6019
MICROSCOPEROOM6022
EQUIPMENTLAB6027
MONITORINGLAB6028
EQUIPMENTLAB6029
STORAGEROOM6031
SOLVENTSTORAGE6032
GLASSWASH6069
OPENOFFICEAREA6063
CELLCULTURE6058
MASSSPEC6057
OPEN LAB6056
EQUIPMENTCORRIDOR
6053
DNAROOM6055
TISSUECULTURE6054
6050
EQUIPMENT6048
STORAGE/FREEZERROOM6045
HUMANBIOLOGY
LABORATORY6046
OFFICE6042
OFFICE6043
EQUIPMENTROOM6039
STABILITYCHAMBER
6040
MASSSPEC6038
MASSSPEC6025
ELECROOM6036
LABSUPPLYROOM6035
BIOREPOSITORYROOM6068
SAMPLERECEIVING
ROOM6074
CONFERENCE6067
CONFERENCE6003
CONFERENCE6004
CONFERENCE6005
VIPERLAB6014
EQUIPMENTCORRIDOR
6021
EQUIPMENTROOM6023
COLDROOM6047
COLDROOM6052
MEETINGAREA6059
OPENOFFICEAREA6007
INNOVATIONBAR6008
COPY6009
OPENOFFICEAREA6013
EQUIPMENTCORRIDOR
6018
DSE LAB6015
COLDROOM6017
EQUIPMENTCORRIDOR
6030
CORRIDOR6002
CORRIDOR6001
CORRIDOR6075
CORRIDOR6073
CORRIDOR6006
OPENOFFICEAREA6041
TEL/DATAIDF6072
CORRIDOR6071
CORRIDOR6037
D
E5
E6
E3
4
STORAGE6060
STORAGE6064
KITCHEN6065
BREAKRM6066
MEDIAPREPROOM6062
POD6033
POD6034
COPY/MAIL6044
CORRIDOR6026
CORRIDOR6020
CONFERENCE6061
6
STAIR 1S1-6
SERVICEELEVATOR
LOBBY602
STAIR 2S2-6
STAIR 3S3-6
ELEV #2
ELEV #3
ELEV #4
ELEV #8
ELEV #7
ELEV #6
ELEV #5
MECH.PIPING606
NORMALELECTRICAL
ROOM604
PLUMB.CLOSET621
LIFESAFETY605
PLUMB.CLOSET620
JANITOR607
MEN610
WOMEN609
SHOWER608
BIOWASTESTORAGE
651
EQUIPMENTLAB
CLINICALBIOMARKERS
OPEN LAB
ELEVATORLOBBY601
CORRIDOR6049
IMPORTANT NOTE:
SCOPE OF WORK
NORTH
ISSUED FOR BID
3/2/20
1
4
" = 1'-0"
E-201
1
ELECTRICAL LIGHTING NEW WORK PLAN
1/4"=1'-0"
LIGHTING PLAN GENERAL NOTES:
1. REFER TO DRAWING E-001 FOR LEGEND AND GENERAL NOTES.
2. LIGHT FIXTURES SHALL BE INSTALLED AT MOUNTING HEIGHTS AND LOCATIONS AS
INDICATED ON THE ARCHITECTURAL REFLECTED CEILING PLANS, ELEVATIONS, PART
PLANS AND DETAILS. CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR
INFORMATION.
4. EDGE-LIT TYPE EXIT SIGNS SHALL BE PROVIDED WITH MIRROR-BACKING AS REQUIRED TO
SUIT FIELD CONDITIONS AND SPECIFIC INSTALLED LOCATIONS.
5. CIRCUIT NUMBERS ARE SHOWN FOR DESCRIPTIVE PURPOSES ONLY. EXACT NUMBERS
SHALL BE DETERMINED IN FIELD AND SHALL BE NOTED ON THE CONTRACTORS' AS-BUILT
DRAWINGS.
6. EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS AND EMERGENCY BATTERY UNITS
SHALL BE CONNECTED TO AN UNSWITCHED, CONSTANT "ON" SOURCE AS INDICATED. THE
ASSOCIATED CIRCUIT BREAKER SHALL BE PROVIDED WITH A HANDLE LOCK.
7. BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND INSTALLED FOR A MAXIMUM
VOLTAGE DROP OF 3%. CONTRACTOR SHALL PROVIDE #10AWG CONDUCTORS FOR ALL
120V CIRCUITS GREATER THAN 60 FEET IN LENGTH AND #10AWG CONDUCTORS FOR ALL
277V CIRCUITS GREATER THAN 140 FEET IN LENGTH. CONTRACTOR SHALL PROVIDE
#8AWG CONDUCTORS FOR ALL 120V CIRCUITS GREATER THAN 100 FEET IN LENGTH, BUT
LESS THAN 160 FEET IN LENGTH AND #8AWG CONDUCTORS FOR ALL 277V CIRCUITS
GREATER THAN 225 FEET, BUT LESS THAN 350 FEET IN LENGTH. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS AND OPTIONS.
LIGHTING PLAN TAGGED NOTES:
CONNECT TO EXISTING LIGHTING BRANCH CIRCUIT MAINTAINED FROM THE DEMOLITION
PHASE OF THE PROJECT VIA EXISTING/RELOCATED CONTROL DEVICE. EXTEND AND
MODIFY EXISTING WIRING AS REQUIRED; MATCH EXISTING WIRING.
LIGHTING CONTROL SYSTEM MANUFACTURER (LUTRON) SHALL PROVIDE ON SITE
RE-PROGRAMMING AND COMMISSIONING OF ALL LIGHTING CONTROL SYSTEM
COMPONENTS WITH THE AREA OF RENOVATION.
1
Drawn By: DM Checked By: AJR
2
V1 6th Floor Tissue CultureLabs
:3/13/20
5 6
SCOPE OF WORK
TISSUE CULTURELAB6029
TISSUE CULTURELAB6019
MONITORING LAB6028
EQUIPMENT LAB6027
CORRIDOR6002
EQUIPMENTCORRIDOR
6030
PLUMBING CLOSET621
COLD ROOM6017
MICROSCOPEROOM6022
EQUIPMENTCORRIDOR
6021
EQUIPMENT ROOM6023
EQUIPMENTCORRIDOR
6018
CORRIDOR6020
BIOSAFETY CABINET
BIOSAFETY CABINET
STACKED INCUBATOR
STACKED INCUBATORS
STACKED INCUBATOR
BIOSAFETY CABINET
BIOSAFETY CABINET
STACKED INCUBATOR
V
V
V
V
6019
-A
V
V
VIPERLAB6014
DSE LAB6015DSE
LAB6016
MECH.PIPING606
LIFESAFETY605
XL
XL
XL
XL
XL
XL
XMXM
XM
XMXM
XM
XM
XM
XM
XM
XM
XM
XM
XM
XM
INC
INC
INC
INC
CEILING MTD
UTILITY PANEL
INC
CEILING MTD
UTILITY PANEL
INC
INC
AREA OF RENOVATION
'0262' (XM)
'LB263' (XM)
O262-331
O262-341
O262-351
O262-361
O262-371
O262-381
O262-391
O262-401
O262-411
O262-421
O262-451
O262-471
LB263-331
LB263-341
LB263-351 LB263-36
1
LB263-37,391
37 39 37 39 37 39
LB263-38,401
3840
38
4038
40
LB263-411
41
41
41
41
LB263-54,561
LB263-421
54
56
54
54
56
56
LB263-58,601
58
58
58
60
60
60
LB263-611
LB263-621
LB263-631
U.C. REF/FREEZ
U..C REF/FREEZ
ELECTRICAL
LEVEL 6
NEW WORK POWER PLAN
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
KEY PLAN
1 2 3 5 7
8
A.7
B
C
C.5
E
F
G
OFFICE6010
OFFICE6011
OFFICE6012
DSELAB6016
6019
MICROSCOPEROOM6022
EQUIPMENTLAB6027
MONITORINGLAB6028
EQUIPMENTLAB6029
STORAGEROOM6031
SOLVENTSTORAGE6032
GLASSWASH6069
OPENOFFICEAREA6063
CELLCULTURE6058
MASSSPEC6057
OPEN LAB6056
EQUIPMENTCORRIDOR
6053
DNAROOM6055
TISSUECULTURE6054
6050
EQUIPMENT6048
STORAGE/FREEZERROOM6045
HUMANBIOLOGY
LABORATORY6046
OFFICE6042
OFFICE6043
EQUIPMENTROOM6039
STABILITYCHAMBER
6040
MASSSPEC6038
MASSSPEC6025
ELECROOM6036
LABSUPPLYROOM6035
BIOREPOSITORYROOM6068
SAMPLERECEIVING
ROOM6074
CONFERENCE6067
CONFERENCE6003
CONFERENCE6004
CONFERENCE6005
VIPERLAB6014
EQUIPMENTCORRIDOR
6021
EQUIPMENTROOM6023
COLDROOM6047
COLDROOM6052
MEETINGAREA6059
OPENOFFICEAREA6007
INNOVATIONBAR6008
COPY6009
OPENOFFICEAREA6013
EQUIPMENTCORRIDOR
6018
DSE LAB6015
COLDROOM6017
EQUIPMENTCORRIDOR
6030
CORRIDOR6002
CORRIDOR6001
CORRIDOR6075
CORRIDOR6073
CORRIDOR6006
OPENOFFICEAREA6041
TEL/DATAIDF6072
CORRIDOR6071
CORRIDOR6037
D
E5
E6
E3
4
STORAGE6060
STORAGE6064
KITCHEN6065
BREAKRM6066
MEDIAPREPROOM6062
POD6033
POD6034
COPY/MAIL6044
CORRIDOR6026
CORRIDOR6020
CONFERENCE6061
6
STAIR 1S1-6
SERVICEELEVATOR
LOBBY602
STAIR 2S2-6
STAIR 3S3-6
ELEV #2
ELEV #3
ELEV #4
ELEV #8
ELEV #7
ELEV #6
ELEV #5
MECH.PIPING606
NORMALELECTRICAL
ROOM604
PLUMB.CLOSET621
LIFESAFETY605
PLUMB.CLOSET620
JANITOR607
MEN610
WOMEN609
SHOWER608
BIOWASTESTORAGE
651
EQUIPMENTLAB
CLINICALBIOMARKERS
OPEN LAB
ELEVATORLOBBY601
CORRIDOR6049
IMPORTANT NOTE:
SCOPE OF WORK
NORTH
ISSUED FOR BID
3/2/20
1
4
" = 1'-0"
E-301
POWER PLAN GENERAL NOTES:
1. REFER TO GENERAL DEMOLITION NOTES ON DRAWING E-001 FOR ADDITIONAL
REQUIREMENTS.
2. REFER TO DRAWING E-001 FOR LEGEND AND GENERAL NOTES.
3. RECEPTACLES, SWITCHES AND DEVICES SHALL BE INSTALLED AT MOUNTING HEIGHTS
AND LOCATIONS AS INDICATED ON THE ARCHITECTURAL ELEVATIONS, PART PLANS AND
DETAILS. CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR INFORMATION.
4. CIRCUIT NUMBERS ARE SHOWN FOR DESCRIPTIVE PURPOSES ONLY. EXACT NUMBERS
SHALL BE DETERMINED IN FIELD AND SHALL BE NOTED ON THE CONTRACTORS' AS-BUILT
DRAWINGS.
5. BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND INSTALLED FOR A MAXIMUM
VOLTAGE DROP OF 3%. CONTRACTOR SHALL PROVIDE #10AWG CONDUCTORS FOR ALL
120V CIRCUITS GREATER THAN 60 FEET IN LENGTH AND #10AWG CONDUCTORS FOR ALL
277V CIRCUITS GREATER THAN 140 FEET IN LENGTH. CONTRACTOR SHALL PROVIDE
#8AWG CONDUCTORS FOR ALL 120V CIRCUITS GREATER THAN 100 FEET IN LENGTH, BUT
LESS THAN 160 FEET IN LENGTH AND #8AWG CONDUCTORS FOR ALL 277V CIRCUITS
GREATER THAN 225 FEET, BUT LESS THAN 350 FEET IN LENGTH. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS AND OPTIONS.
6. COORDINATE EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITH HVAC, PLUMBING
AND FIRE PROTECTION DRAWINGS.
1
ELECTRICAL POWER NEW WORK PLAN
1/4"=1'-0"
Drawn By: DM Checked By: AJR
POWER PLAN TAGGED NOTES:
UTILIZE EXISTING SPARE 20A-1P CIRCUIT BREAKER IN PANEL INDICATED TO FEED NEW
LOAD.
1
V1 6th Floor Tissue CultureLabs
:3/13/20
FINISHED FLOOR
TELE/DATA OUTLET. FACEPLATE
TO MATCH RECEPTACLES UNLESS
OTHERWISE NOTED.
RECEPTACLE, REFER TO SYMBOL
LIST FOR SPECIFICATION
6'-8"
(MIN)
LIGHT SWITCHES OR DIMMERS. REFER
TO SYMBOL LIST FOR SPECIFICATION.
FINISHED
CEILING
(VARIES)
NOTES:
1. ALL MOUNTING HEIGHTS SHALL BE
MEASURED FROM FINISHED FLOOR TO
CENTERLINE OF DEVICE EXCEPT FIRE
ALARM VISUAL DEVICES.
2. DEVICES SHALL BE INSTALLED ON A
COMMON VERTICAL CENTERLINE
WHEREVER POSSIBLE
3. ALL DEVICES SHALL BE INSTALLED AT
MOUNTING HEIGHTS AS INDICATED ON
THIS DETAIL UNLESS OTHERWISE NOTED.
4. MOUNT DEVICE ABOVE COUNTER AT 4'-0"
A.F.F. TO CENTER
ABOVE
COUNTER
DEVICE SEE
NOTE 4
BACKSPLASH
TYPICAL MOUNTING HEIGHTS
8'-0"
4'-6"
4'-0"
4'-0"
C
1'-6"
NTS TYPICAL RECEPTACLE LABELING NTS TYPICAL COVERPLATE AND SWITCH NTS21 3
NORMAL POWER
RECEPTACLES SHALL BE
WHITE WITH BRUSHED
STAINLESS STEEL ENGRAVED
COVERPLATE; EMERGENCY
POWER RECEPTACLES SHALL
BE RED WITH BRUSHED
STAINLESS STEEL ENGRAVED
COVERPLATE
NOTES:
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE PTOUCH LABEL TO MATCH BUILDING STANDARDS.
PANEL AND CIRCUIT NUMBER SHALL BE INDICATED.
S291-16
DUPLEX RECEPTACLE NEMA 5-20R
SEE NOTE 1
COVER PLATE, JUNCTION BOX, ETC. LINE VOLTAGE AND LOW
VOLTAGE SWITCHES
R251-16 R251-16
SEE NOTE 1
NOTES:
1. THE ELECTRICAL CONTRACTOR SHALL PROVIDE PTOUCH LABEL TO MATCH BUILDING STANDARDS.
PANEL AND CIRCUIT NUMBER SHALL BE INDICATED.
LIGHTING FIXTURE SCHEDULE
FIXTURE
TYPE
DESCRIPTION
LIGHT FIXTURE ACCEPTABLE MANUFACTURERS AND CATALOG NUMBER LAMPS
FIXTURE
TOTAL
WATTAGE
MOUNTING VOLTAGE NOTES
MANUFACTURER CATALOG NUMBER QUANTITY TYPE
L1 8' LINEAR RECESSED LED FIXTURE
AMERLUX GRUV6-HE-GRID-A16-PL-8-30-HW-120/277-*-IND-HILUME-5-ECO
- LED 8W/FT RECESSED UNV
LIGHTING FIXTURE SCHEDULE NOTES:
LF1. REFER TO ARCHITECT'S REFLECTED CEILING PLANS AND ELEVATIONS FOR FINAL LOCATIONS AND MOUNTING
HEIGHTS OF ALL FIXTURES.
LF2. CATALOG NUMBERS INDICATED ARE FOR REFERENCE ONLY. CONTRACTOR IS RESPONSIBLE FOR FINAL
FIXTURE COORDINATION AND INSTALLATION. CONTRACTOR SHALL PROVIDE ALL ACCESSORIES REQUIRED FOR
INSTALLATION OF LIGHT FIXTURES INCLUDING, BUT NOT LIMITED TO, BAR HANGERS, SWIVEL STEM HANGERS,
PENDANTS, END CAPS, CONNECTORS, MOUNTING BOXES, MOUNTING CLIPS,
LF3. COORDINATE LIGHTING FIXTURE INSTALLATION AND TRIM KIT WITH CEILING TYPE. PROVIDE FRAME KIT AS
REQUIRED TO INSTALL FIXTURE IN CEILING TYPE.
LF4. FINAL FINISHES AND COLORS OF ALL LIGHT FIXTURES SHALL BE APPROVED BY ARCHITECT AND LIGHTING
DESIGNER.
LF5. ALL FIXTURES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE BY THREADED ROD OR CHAIN. REFER TO
THE SPECIFICATIONS FOR METHOD. SUPPORTING FIXTURES FROM HUNG CEILING IS NOT ALLOWED.
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
NORTH
ISSUED FOR BID
3/2/20
ELECTRICAL
SCHEDULES AND
DETAILS
N.T.S.
E-401
Drawn By: DM Checked By: AJR
V1 6th Floor Tissue CultureLabs
:3/13/20
FIRE ALARM STROBE ONLY DEVICE, UNIT RATED OUTPUT
75cd UNLESS OTHERWISE NOTED
HEAT DETECTOR, COMBINATION FIXED TEMPERATURE AND
RATE-OF-RISE TYPE - 195° UNLESS OTHERWISE INDICATED
FIRE ALARM SYSTEM LEGEND
MANUAL PULL STATION
SMOKE DETECTOR
REMOTE TEST AND ALARM INDICATING STATION
REMOTE ALARM INDICATOR
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
ADDRESSABLE MONITOR MODULE
ADDRESSABLE CONTROL MODULE
F
FACP
FATC
S
H
RELAY
FIRE/SMOKE DAMPER
RI
RTS
EXISTING DEVICE SHALL BE REMOVED INCLUDING ALL ASSOCIATED RACEWAYS
AND CIRCUITRY BACK TO ITS SOURCE
EXISTING DEVICE SHALL REMAIN AND SHALL BE MAINTAINED
EXISTING DEVICE SHALL BE RELOCATED
NEW LOCATION OF EXISTING TO BE RELOCATED DEVICE. EXTEND AND MODIFY
EXISTING WIRING AS REQUIRED TO NEW DEVICE LOCATION. MATCH EXISTING
WIRING
EXISTING DEVICE TO BE REMOVED AND REPLACED WITH NEW MAINTAIN
EXISTING CIRCUITRY FOR CONNECTION OF NEW DEVICE
DETAIL IDENTIFIER
"1" INDICATES DETAIL NUMBER
"FA-000" INDICATES SHEET NUMBER
DRAWING REVISION MARKER
DRAWING REVISION CLOUD
1. REFER TO THE ARCHITECTURAL DRAWINGS FOR THE FULL EXTENT OF THE
SCOPE OF DEMOLITION. DISCONNECT AND MAKE SAFE ALL FIRE ALARM
EQUIPMENT IDENTIFIED FOR REMOVAL ON THE ARCHITECTURAL, HVAC,
PLUMBING AND FIRE PROTECTION PLANS. THE FIRE ALARM SCOPE MAY EXTEND
BEYOND THE AREA DEFINED BY THE ARCHITECTURAL DEMOLITION LIMITS TO
FULLY COMPLY WITH THE VARIOUS REQUIREMENTS DEFINED BY THESE NOTES.
2. THE FIRE ALARM DEMOLITION PLANS INDICATE GENERAL INTENT AND ARE NOT
INTENDED TO SHOW ALL COMPONENTS AND ITEMS TO BE REMOVED OR
RETAINED. THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO
SUBMISSION OF THEIR BID TO BECOME FAMILIAR WITH THE ACTUAL WORKING
CONDITIONS AND EXTENT OF WORK. DEVICES AND EQUIPMENT LOCATED ON
WALLS AND/OR CEILINGS DESIGNATED TO BE REMOVED SHALL BE
DISCONNECTED AND MADE SAFE. THE ELECTRICAL CONTRACTOR SHALL
IMMEDIATELY NOTIFY THE OWNER'S REPRESENTATIVE AND ARCHITECT OF ANY
UNANTICIPATED OR HIDDEN CONDITIONS ENCOUNTERED DURING DEMOLITION.
3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF
ALL SYSTEMS OR BUILDING COMPONENTS DAMAGED DURING EXECUTION OF
THE WORK. DAMAGE SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
DESTRUCTION OR DISPOSAL OF ITEMS INTENDED TO REMAIN OR BE SALVAGED.
4. IN ANY AREA REQUIRING THE PERFORMANCE OF ANY TRADE'S WORK, THE
ELECTRICAL CONTRACTOR SHALL CAREFULLY REMOVE AND STORE ANY OR
ALL FIRE ALARM ITEMS IN PATH OF WORK, REINSTALLING AND RECONNECTING
SAME AS REQUIRED, IN ACCORDANCE WITH THE PLANS AND/OR AS DIRECTED
AFTER COMPLETION OF OTHER TRADES WORK IN THAT AREA.
5. THE ELECTRICAL CONTRACTOR SHALL IDENTIFY ALL SYSTEM COMPONENTS
WHICH ARE TO REMAIN WITHIN THE AREA OF DEMOLITION SCOPE. THERE
SHALL BE NO INTERRUPTION OF SERVICE TO ANY AREA OUTSIDE THE SCOPE
LIMITS WITHOUT WRITTEN APPROVAL FROM THE OWNER'S REPRESENTATIVE.
EXISTING EQUIPMENT TO REMAIN SHALL BE LEFT IN A CODE COMPLAINT
CONDITION .
6. THE ELECTRICAL CONTRACTOR SHALL TAKE INVENTORY OF FIRE ALARM ITEMS
THAT ARE REMOVED AND PROVIDE A LIST TO THE OWNER FOR THEIR
SELECTION OF ITEMS TO BE RETAINED. ALL ITEMS REJECTED BY THE OWNER
SHALL BECOME THE PROPERTY OF THE CONTRACTOR, AND SHALL BE
REMOVED FROM THE SITE AND DISPOSED OF LEGALLY.
7. IN ALL EXISTING OR NEW AREAS SPECIFIED OR SHOWN TO BE PAINTED, THE
ELECTRICAL CONTRACTOR SHALL REMOVE ALL FIRE ALARM ITEMS AS
REQUIRED, INCLUDING BUT NOT LIMITED TO, FIRE ALARM DEVICES, REMOTE
INDICATING DEVICES, DEVICE PLATES, ETC. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR STORING THE REMOVED DEVICES IN A SAFE AND SECURE
PLACE. THE ELECTRICAL CONTRACTOR SHALL REINSTALL THE SAME DEVICES
AFTER COMPLETION OF PAINTING. ANY ITEM NOT REMOVED AND PAINTED
OVER SHALL BE SUITABLY CLEANED OR REPLACED WITH A NEW ITEM BY THE
ELECTRICAL CONTRACTOR.
8. ALL EXISTING FIRE ALARM EQUIPMENT THAT ARE TO BE RELOCATED SHALL BE
STORED IN A SAFE MANNER UNTIL SUCH TIME AS TO BE REINSTALLED. ANY
DAMAGE INCURRED TO EQUIPMENT SHALL BE RECTIFIED BY THE ELECTRICAL
CONTRACTOR.
9. ALL REMOVED ITEMS SHALL BE LEGALLY DISPOSED OF UNLESS IDENTIFIED FOR
REUSE. THE OWNER'S REPRESENTATIVE SHALL INSPECT ALL RETAINED ITEMS,
PRIOR TO PLACEMENT IN THE IDENTIFIED STORAGE LOCATION BY THE
ELECTRICAL CONTRACTOR.
10.THE WORK ON THIS PROJECT MAY BE PERFORMED IN PHASES. THE
ELECTRICAL CONTRACTOR SHALL COORDINATE AND SCHEDULE HIS WORK AND
ALLOW SUFFICIENT TIME AND COSTS TO ACCOMMODATE THE PHASING OF
WORK. ANY ADDITIONAL COSTS INCURRED DUE TO LACK OF PROPER
COORDINATION AND COMMUNICATION BY THE ELECTRICAL CONTRACTOR, WITH
THE GENERAL CONTRACTOR, OTHER TRADES OR OWNER'S REPRESENTATIVE,
SHALL BE ABSORBED BY THE ELECTRICAL CONTRACTOR WITHOUT ANY COSTS
TO THE OWNER. COORDINATE PHASING REQUIREMENTS WITH THE ARCHITECT
AND THE OWNER.
11.THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN FULLY FUNCTIONAL DURING
THE ENTIRE DEMOLITION AND CONSTRUCTION PERIOD. REUSE OF EXISTING
FIRE ALARM RACEWAYS SHALL NOT BE ALLOWED. ALL REQUIRED SYSTEM
SHUTDOWNS SHALL BE COORDINATED WITH AND APPROVED BY THE OWNER'S
REPRESENTATIVE AND THE AUTHORITY HAVING JURISDICTION. DEMOLITION OF
THE EXISTING SYSTEM SHALL NOT COMMENCE UNTIL THE NEW SYSTEM HAS
BEEN COMPLETELY INSTALLED, TESTED AND APPROVED BY THE AUTHORITY
HAVING JURISDICTION.
12.EXISTING FIRE ALARM SYSTEM SHALL REMAIN AND INTACT DURING
CONSTRUCTION. AT NO TIME SHALL ANY PART OF THE BUILDING BE WITHOUT
FIRE ALARM COVERAGE.
13.HEAT DETECTORS SHALL BE INSTALLED BY THE ELECTRICAL CONTRACTOR AT
THE START OF DEMOLITION IN ANY AREAS WHERE THE SPRINKLER SYSTEM HAS
BEEN DISABLED UNTIL THE NEW SPRINKLER SYSTEM HAS BEEN FULLY
INSTALLED AND COMMISSIONED. HEAT DETECTORS SHALL BE CONNECTED TO
THE EXISTING FIRE ALARM SYSTEM VIA A NEW ADDRESSABLE MODULE.
EXISTING DEVICE, EQUIPMENT OR WIRING TO BE REMOVED
EXISTING DEVICE, EQUIPMENT OR WIRING TO REMAIN
NEW DEVICE, EQUIPMENT OR WIRING
DEMOLITION GENERAL NOTES
PROJECT GENERAL NOTES
1
E-004
1
DRAWING NOTES AND DESIGNATIONS
EXISTING CONDITIONS DESIGNATIONS
LINE TYPE LEGEND
1. THE CONTRACTOR SHALL FURNISH LABOR, MATERIALS, TOOLS AND OTHER
EQUIPMENT REQUIRED TO INSTALL THE WORK SHOWN AND SPECIFIED. THE
CONTRACTOR SHALL FURNISH AND INSTALL ITEMS NECESSARY FOR A
COMPLETE ELECTRICAL SYSTEM. MATERIALS SHALL BE NEW AND SHALL BEAR
THE REGISTERED UL MARK. WORK SHALL CONFORM WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION STANDARD 70 (NEC), THE NATIONAL ELECTRICAL
CODE (NEC), AND APPLICABLE FEDERAL, STATE AND LOCAL CODES.
CONTRACTOR SHALL SECURE PERMITS AND PAY THE FEES REQUIRED TO CARRY
OUT HIS WORK. THE CONTRACTOR SHALL FURNISH COPIES OF CERTIFICATES
AND PERMITS TO THE ARCHITECT.
2. THE DRAWINGS AND SPECIFICATIONS INDICATE THE INTENT OF THE DESIGN AND
SHALL BE CONSIDERED AS DIAGRAMMATIC ONLY. EXACT LOCATIONS FOR
OUTLETS AND EQUIPMENT SHALL BE DETERMINED AT THE SITE, AS WORK
PROGRESSES DIMENSIONS AND CONDITIONS SHALL BE CHECKED AND VERIFIED
BY THE CONTRACTOR AT THE SITE. FINAL WORK SHALL BE DOCUMENTED ON AS
BUILT RECORD DRAWINGS.
3. SMOKE DETECTORS, FIRE ALARM DEVICES, ETC INDICATE QUANTITY, EXACT
LOCATIONS OF DEVICES SHALL BE DETERMINED IN THE FIELD AND
COORDINATED WITH ARCHITECT.
4. THIS IS A STANDARD SYMBOL LIST. ALL DEVICE SYMBOLS AND ABBREVIATIONS
MAY NOT NECESSARILY APPEAR ON THE FLOOR PLANS OR DETAIL SHEET. ONLY
THOSE SYMBOLS INDICATED ON THE FLOORS PLANS ARE USED AND OTHERS
SHOULD BE DISREGARDED.
5. MOUNTING HEIGHTS SHALL BE AS INDICATED ON ARCHITECTURAL DRAWINGS.
THE MOUNTING HEIGHT DETAIL SHALL BE USED AS A GUIDE IN THE ABSENCE OF
THE ARCHITECTURAL DRAWINGS.
6. MODIFICATIONS TO THE EXISTING FIRE ALARM SYSTEM SHALL BE COORDINATED
WITH THE FIRM WHO HOLDS THE EXISTING SYSTEM MAINTENANCE CONTRACT.
THE FIRM WHO HOLDS THE EXISTING SYSTEM MAINTENANCE CONTRACT SHALL
MAKE ALL FINAL CONNECTIONS, AND PERFORM ALL PROGRAMMING AND
TESTING. ALL COSTS ASSOCIATED WITH FINAL CONNECTIONS, PROGRAMMING
AND TESTING SHALL BE INCLUDED UNDER THIS CONTRACT AND SHALL BE THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
7. WHEN AVAILABLE FROM THE MANUFACTURER, ALL FIRE ALARM STROBES SHALL
BE FIELD ADJUSTABLE AND THE POWER SUPPLY SHALL BE SIZED BASED ON ALL
THE STROBES' HIGHEST SETTING.
FIRE ALARM SPEAKER/STROBE COMBINATION UNIT, RATED
90db OUTPUT AND 75cd UNLESS OTHERWISE NOTED
NOTES:
1. AT A MINIMUM, ELECTRICAL CONTRACTOR SHALL PROVIDE TYPED
LABELS WITH PTOUCH MACHINE TO INDICATE FIRE ALARM DEVICE AND
ADDRESS OR ZONE NUMBER. COORDINATE EXACT NAMING WITH
FACILITY'S PERSONNEL. IF FACILITY STANDARD IS ENGRAVED
COVERPLATES, THE ELECTRICAL CONTRACTOR SHALL PROVIDE
ENGRAVED COVERPLATES TO MATCH FACILITY REQUIREMENTS.
TYPICAL FIRE ALARM LABELING
COVER PLATE, JUNCTION BOX, ETC.
SEE NOTE 1
RED LED
SEE NOTE 1
CONTROL MODULE
ADDRESS #2-002
NTS
J
1
FIRE ALARM
PULL STATION
FINISHED FLOOR
6'-8"
(MIN)
NOTES:
1. ALL MOUNTING HEIGHTS SHALL BE
MEASURED FROM FINISHED FLOOR TO
CENTERLINE OF DEVICE EXCEPT FIRE
ALARM VISUAL DEVICES.
2. DEVICES SHALL BE INSTALLED ON A
COMMON VERTICAL CENTERLINE
WHEREVER POSSIBLE
3. ALL DEVICES SHALL BE INSTALLED AT
MOUNTING HEIGHTS AS INDICATED ON
THIS DETAIL UNLESS OTHERWISE NOTED.
TYPICAL MOUNTING HEIGHTS
4'-0"
NTS
EXISTING
FIRE ALARM NOTES:
FA1. REFER TO FIRE ALARM DRAWINGS FOR EXACT QUANTITIES OF FIRE ALARM DEVICES.
FA2. NEW FIRE ALARM EQUIPMENT SHALL MATCH EXISTING MANUFACTURER
FA3. ELECTRICAL CONTRACTOR SHALL RE-PROGRAM, TEST AND RE-CERTIFY FIRE ALARM SYSTEM
UPON COMPLETION OF WORK.
FA4. FIRE ALARM SYSTEM AND INSTALLATION SHALL COMPLY WITH APPLICABLE REGULATIONS OF
NFPA #72, LIFE-SAFETY CODE #101, NATIONAL ELECTRIC CODE AND LOCAL FIRE DEPARTMENT.
FA5. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY HARDWARE AND SOFTWARE FOR A
COMPLETE AND OPERABLE EXTENSION OF THE EXISTING FIRE ALARM SYSTEM.
FA6. FIRE ALARM WIRING TERMINATIONS SHALL BE MADE ON TERMINAL BLOCKS; NO SPLICES ARE
ALLOWED.
FA7. ELECTRICAL CONTRACTOR SHALL FIELD CONFIRM THAT ENOUGH BATTERY CAPACITY EXISTS FOR
THE FIRE ALARM SYSTEM TO OPERATE FOR 60 HOURS IN NON-ALARM CONDITION AND CAPABLE
OF OPERATING IN ALARM FOR 15 MINUTES AT THE END OF THE 60 HOUR PERIOD WITH THE
ADDITION OF THE NEW FIRE ALARM DEVICES. PROVIDE ADDITIONAL POWER SUPPLY AND BATTERIES
FA8. EXISTING FIRE ALARM SYSTEM SHALL REMAIN ACTIVE AND INTACT DURING CONSTRUCTION. AT
NO TIME SHALL ANY PART OF THE BUILDING BE WITHOUT FIRE ALARM COVERAGE.
FA9. SYSTEM MANUFACTURER SHALL PROVIDE SITE SPECIFIC INSTALLATION WIRING DIAGRAM OF THE
FIRE ALARM SYSTEM, AND VERIFICATION CERTIFICATE OF SYSTEM OPERATING PRIOR TO FINAL ACCEPTANCE.
FA10. ALL FIELD WIRING AND EQUIPMENT SHALL BE AS REQUIRED PER MANUFACTURERS WIRING
DIAGRAMS.
FA11. ALL FIRE ALARM WIRING SHALL BE CLASS A (OUTGOING AND RETURNING CIRCUITS SHALL BE
NOT BE PHYSICALLY INSTALLED IN THE SAME RACEWAY); FAULT ISOLATOR MODULES SHALL BE
INSTALLED IN THE FACP TO PROTECT SIGNAL LINE CIRCUITS WHEN THEY LEAVE THE FACP & WHEN
THEY RETURN TO FACP. ALSO, FAULT ISOLATOR MODULES WILL BE PROVIDED FOR EVERY 18
ADDRESSABLE FIRE ALARM DEVICES.
IF REQUIRED.
AND BE COMPLETELY COMPATIBLE WITH EXISTING SYSTEM.
FA12. INTERCEPT EXISTING SIGNAL LOOP AND EXTEND TO NEW DEVICES. MATCH EXISTING WIRING.
XMXM
XM
X X X X X
X X X X X X X X X X X X
XR
REFER TO
NOTE FA12
REFER TO
NOTE FA12
XM
XM
XM
XM
S SS
F
FA13. INTERCEPT EXISTING INITIATION LOOP AND EXTEND TO NEW DEVICES. MATCH EXISTING WIRING.
XM
XM
XM
XM XM
XM
XM
XM
XM
XM
X X
SMOKE DAMPER
FA14. 24VDC SHALL BE SUPPLIED FROM THE FIRE ALARM SYSTEM TO ALL EQUIPMENT WHICH
IS LISTED TO OPERATE AT 24VDC
PATIENT ROOM FIRE ALARM ANNUNCIATOR
FAA
TAMPER SWITCH
FLOW SWITCH
FIRE ALARM VISUAL DEVICE. BOTTOM OF
LENS SHALL BE A MINIMUM OF 80" AFF OR
6" BELOW CEILING, WHICHEVER IS LOWER.
WHERE POSSIBLE, DEVICE SHALL BE
LOCATED DIRECTLY ABOVE LIGHT SWITCH
OR PULL STATION.
LENS
LENS
1
PARTIAL FIRE ALARM RISER
N.T.S.
XM
S
XM
S
XM
S
XM
S
XM
S
XM XM XM XM XM XM
XM
X X X X X X X X XX
X
X
X
X
X
X
X
FATC
X
XM
XR
XL
XN
2
F F F FF
F XL
CM
MM
FSD
R
SD
TS
TS
F
S
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
NORTH
ISSUED FOR BID
3/2/20
FIRE ALARM
LEGEND, GENERAL
NOTES, RISER, AND
DETAILS
N.T.S.
FA-001
Drawn By: DM Checked By: AJR
V1 6th Floor Tissue CultureLabs
:3/13/20
5 6
TISSUE CULTURELAB6029
TISSUE CULTURELAB6019
MONITORING LAB6028
EQUIPMENT LAB6027
CORRIDOR6002
EQUIPMENTCORRIDOR
6030
PLUMBING CLOSET621
COLD ROOM6017
MICROSCOPEROOM6022
EQUIPMENTCORRIDOR
6021
EQUIPMENT ROOM6023
EQUIPMENTCORRIDOR
6018
CORRIDOR6020
6019
-A
VIPERLAB6014
DSE LAB6015DSE
LAB6016
MECH.PIPING606
LIFESAFETY605
F
F
F
XL
XL
XM
AREA OF RENOVATION
FIRE ALARM
LEVEL 6
NEW WORK PLAN
Scale: Date Issued:
Project Number:
Isgenuity LLC
500 Harrison Avenue, Suite 5F
Boston, MA 02118
Tel 617 419 4660
Fax 617 419 4661
www.isgenuity.com
Architect
R.W. Sullivan Engineering
The Schrafft Center
529 Main Street, Suite 203
Boston, MA 02129
Tel 617 523 8227
Fax 617 523 8016
MEP/FP Engineer
Job #: 200041.00
Issuance Schedule
Number Date Description
NOT FOR CONSTRUCTION
179-27-00
Vertex Pharmaceuticals, Inc.
Tissue Culture Lab
KEY PLAN
1 2 3 5 7
8
A.7
B
C
C.5
E
F
G
OFFICE6010
OFFICE6011
OFFICE6012
DSELAB6016
6019
MICROSCOPEROOM6022
EQUIPMENTLAB6027
MONITORINGLAB6028
EQUIPMENTLAB6029
STORAGEROOM6031
SOLVENTSTORAGE6032
GLASSWASH6069
OPENOFFICEAREA6063
CELLCULTURE6058
MASSSPEC6057
OPEN LAB6056
EQUIPMENTCORRIDOR
6053
DNAROOM6055
TISSUECULTURE6054
6050
EQUIPMENT6048
STORAGE/FREEZERROOM6045
HUMANBIOLOGY
LABORATORY6046
OFFICE6042
OFFICE6043
EQUIPMENTROOM6039
STABILITYCHAMBER
6040
MASSSPEC6038
MASSSPEC6025
ELECROOM6036
LABSUPPLYROOM6035
BIOREPOSITORYROOM6068
SAMPLERECEIVING
ROOM6074
CONFERENCE6067
CONFERENCE6003
CONFERENCE6004
CONFERENCE6005
VIPERLAB6014
EQUIPMENTCORRIDOR
6021
EQUIPMENTROOM6023
COLDROOM6047
COLDROOM6052
MEETINGAREA6059
OPENOFFICEAREA6007
INNOVATIONBAR6008
COPY6009
OPENOFFICEAREA6013
EQUIPMENTCORRIDOR
6018
DSE LAB6015
COLDROOM6017
EQUIPMENTCORRIDOR
6030
CORRIDOR6002
CORRIDOR6001
CORRIDOR6075
CORRIDOR6073
CORRIDOR6006
OPENOFFICEAREA6041
TEL/DATAIDF6072
CORRIDOR6071
CORRIDOR6037
D
E5
E6
E3
4
STORAGE6060
STORAGE6064
KITCHEN6065
BREAKRM6066
MEDIAPREPROOM6062
POD6033
POD6034
COPY/MAIL6044
CORRIDOR6026
CORRIDOR6020
CONFERENCE6061
6
STAIR 1S1-6
SERVICEELEVATOR
LOBBY602
STAIR 2S2-6
STAIR 3S3-6
ELEV #2
ELEV #3
ELEV #4
ELEV #8
ELEV #7
ELEV #6
ELEV #5
MECH.PIPING606
NORMALELECTRICAL
ROOM604
PLUMB.CLOSET621
LIFESAFETY605
PLUMB.CLOSET620
JANITOR607
MEN610
WOMEN609
SHOWER608
BIOWASTESTORAGE
651
EQUIPMENTLAB
CLINICALBIOMARKERS
OPEN LAB
ELEVATORLOBBY601
CORRIDOR6049
IMPORTANT NOTE:
SCOPE OF WORK
NORTH
ISSUED FOR BID
3/2/20
1
4
" = 1'-0"
FA-101
1
FIRE ALARM NEW WORK PLAN
1/4"=1'-0"
Drawn By: DM Checked By: AJR
V1 6th Floor Tissue CultureLabs
:3/13/20