Page 1: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

1

ASHRAE Standard 62.1

TRACE 700™

ASHRAE 62.1: Section 6.2Ventilation Rate Procedure (VRP)

• Prescribes quantity of outdoor air delivered to each zone based

• How to calculate outdoor air flow needed at the system intake

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 2: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

2

Learning objectives

• Describe the multi-zone calculation process

• Show how TRACE™ determines system level

• Common questions

Example: Two zone officeCalculate required outdoor air intake VAV reheat system

Block airflow : 2560 cfm

VAV diversity factor:0.8 1600 cfm

25% min stop

exhaustunconditioned outdoor air

sup

ply

air

retu

rn a

ir

VAV

VAV

1600 cfm 25% min stop

zone 1

zone 2

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 3: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

3

exhaust

ASHRAE Standard 62.1 Variables

Vpz = 1600 cfmVpz-min = 400 cfm

Vpz = 1600 cfmVpz-min = 400 cfm

outdoor airsu

pp

ly a

ir

retu

rn a

ir

VAV

VAV

Block airflow : Vps = 2560 cfm

Zone Airflow Rates

1. Define Zone Level Parametersa. Define zone airflow rates and distribution effectiveness

a. Ra = Outdoor airflow rate per unit area (Table 6-1)b. Rp = Outdoor airflow rate per person (Table 6-1)c. Ez = Define zone air distribution effectiveness (Table 6-2)

1

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 4: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

4

Zone Airflow Rates

1. Define Zone Level Parametersa. Define zone airflow rates and distribution effectiveness

a. Ra = Outdoor airflow rate per unit area (Table 6-1)b. Rp = Outdoor airflow rate per person (Table 6-1)c. Ez = Define zone air distribution effectiveness (Table 6-2)

2. Calculate Breathing Zone Outdoor Airflow (Vbz)a. Vbz= (Rp x Pz) + (Ra x Az),

where Pz is the number of people and Az is the zone area

1

2

Zone Airflow Rates

1. Define Zone Level Parametersa. Define zone airflow rates and distribution effectiveness

a. Ra = Outdoor airflow rate per unit area (Table 6-1)b. Rp = Outdoor airflow rate per person (Table 6-1)c. Ez = Define zone air distribution effectiveness (Table 6-2)

2. Calculate Breathing Zone Outdoor Airflow (Vbz)a. Vbz= (Rp x Pz) + (Ra x Az),

where Pz is the number of people and Az is the zone area

3. Calculate Zone Outdoor Airflow (Voz)a. Voz = Vbz/Ez

1

2

3

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 5: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

5

Zone Airflow Rates

Zone 2:• Rp = 5 cfm/p• Ra = 0.06 cfm/ft2

• Pz = 10 people• Az = 500 ft2

• Ez = 1.0 (cooling)

Calculate Vbz and Voz:Zone 1:• Rp = 5 cfm/p• Ra = 0.06 cfm/ft2

• Pz = 30 people• Az = 1500 ft2

• Ez = 1.0 (cooling)

exhaust

OA 

sup

ply

air

retu

rn a

ir

VAV

VAV

zone 1

zone 2

Voz = 240 cfm 

Voz = 80 cfm

ASHRAE Standard 62.1/TRACE demonstration

1. Area and occupancy ventilation rates: OA required to remove contaminants from people and building materials

2. Zone level efficiency: Effectiveness of zone level outdoor airflow to dilute indoor contaminants

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 6: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

6

3. Area and occupancy ventilation rates: Select an appropriate standard 62.1 calculation

ASHRAE Standard 62.1/TRACE demonstration

TRACE™ ASHRAE Standard 62.1 report

Ventilation Parameters

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 7: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

7

4. Determine Zone Primary OA Fraction (Zp) for each zone

exhaust

Vpz = 1600 cfmVpz-min = 400 cfm

Vpz = 1600 cfmVpz-min = 400 cfm

sup

ply

air

retu

rn a

ir

VAV

VAV

Zp = Voz/Vpz-min

WhereVozVpz-min

= zone outdoor airflow= minimum expected

zone primary airflow at the design condition analyzed

4

OA 

4. Determine critical zone (zone with maximum Zd)5

exhaust

Zd = 0.6

Zd = 0.2

sup

ply

air

retu

rn a

ir

VAV

VAV

critical zone

OA 

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 8: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

8

*

TRACE™ ASHRAE Standard 62.1 report

Ventilation Calculation for Cooling Design

Vou = D Σall zones Rp Pz + Σall zones Ra Az, where D represents the occupancy diversity within the system

Assume D =1 Vou = 320 cfm

4. Determine uncorrected OA intake (Vou)6

exhaust

Vbz = 240 cfm

Vbz = 80 cfm

sup

ply

air

retu

rn a

ir

VAV

VAV

OA 

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 9: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

9

TRACE™ ASHRAE Standard 62.1 report

System Ventilation Requirements

Xs = Vou/Vpswhere Vps is system primary airflow (VAV block airflow)

4. Determine Average Outdoor Air Fraction (Xs)7

exhaust

sup

ply

air

retu

rn a

ir

VAV

VAV

OA 

Vou = 320 cfmVps = 2560 cfm (fan block)Xs= 0.125

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 10: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

10

TRACE™ ASHRAE Standard 62.1 report

System Ventilation Requirements

Ev = 1+Xs‐Zd‐max = 1+0.125‐0.6 = 0.525

4. Determine system ventilation efficiency (Ev): Table 6‐3 or App. A

8

exhaust

Vbz = 240 cfm

Vbz = 80 cfm

sup

ply

air

retu

rn a

ir

VAV

VAV

OA 

Equation A‐1

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 11: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

11

Vot = Vou/Ev = 320/0.525 = 610 cfm 23.8% OA at cooling design (610 cfm/2560  cfm)

Vot = 610 cfm 

4. Find outdoor intake flow (Vot): 9

exhaust

sup

ply

air

retu

rn a

ir

VAV

VAV

OA 

TRACE™ ASHRAE Standard 62.1 report

System Ventilation Requirements

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 12: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

12

TRACE and ASHRAE Standard 62.1

Common Questions

• Why is my system 100% OA?

• Why does my ASHRAE multi-zone spreadsheet does not match the TRACE 700 output?

• Why does TRACE calculate Zd using Vpz-min?

Resolving 100% OA • Set Max Vent Allowed (Max Zd) in Create Systems>Advanced• Increase VAV min in critical zone in Create Rooms>Airflows

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 13: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

13

ASHRAE Standard 62.1Lesson 2: Program Methodology100% OA

Max Zd = 75%

Pros

Reduce OA cfm• Reduced outdoor air

cfm

• Reduced ventilation load

Cons

Increased airflows• Increased minimum stop

• Increased fan power

• Increased reheat loads

Max Zd

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 14: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

14

Note: These values are for the 2 zone example

Impact of Zd-max on Vot and Vpz-min

TRACE and ASHRAE Standard 62.1

Common Questions

• Why is my system 100% OA?

• Why does my ASHRAE multi-zone spreadsheet does not match the TRACE 700 output?

• Why does TRACE calculate Zd using Vpz-min?

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 15: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

15

TRACE and ASHRAE Standard 62.1

Common Questions

• Why is my system 100% OA?

• Why does my ASHRAE multi-zone spreadsheet does not match the TRACE 700 output?

• Why does TRACE calculate Zd using Vpz-min?

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.

Page 16: Trane C.D.S. eLearning - ASHRAE Standard 62.1 and … · 3/31/2015 1 ASHRAE Standard 62.1 TRACE™ 700 ASHRAE 62.1: Section 6.2 Ventilation Rate Procedure (VRP) • Prescribes quantity

3/31/2015

16

Additional resources

• TRACE™ 700 User’s Manual

• TRACE online (F1) help

• Trane.com/EN

• Trane.com/ContinuingEducation

phone I 608.787.3926

fax I 608.787.3005

email I [email protected]

Web  I www.tranecds.com

contact us

Trane C.D.S. eLearning Tutorial ASHRAE Standard 62.1 and TRACE™ 700

©2015 Trane. All rights reserved.