TP48200A. External Alarms.
Special for Vodafone ProjectTotal 13 Pages
Cabinet TP48200A.
External Alarms
Huawei Technologies Co., Ltd.
Website:http://support.huawei.com
E-MAIL:[email protected]
All Rights Reserved.Address:Huawei Technologies Co., Ltd.,
Postal Code:
1
![Page 2: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/2.jpg)
TP48200A. External Alarms.
Table of Contents1. External Alarms Description:……………………………………….…………………5
2. External Alarms Connections (4x Ethernet cable (RJ45)): …………….……………..6
3. External Alarms Integration:…………………………………………..………………9
4. Reference Pictures:…………………………………………………………………..13
2
![Page 3: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/3.jpg)
TP48200A. External Alarms.
List of FiguresFigure 1. UIM 02A.................................................................................................................................................5
Figure 2. Terminal Block........................................................................................................................................5Figure 3. Layout Connection All External Alarms.................................................................................................6Figure 4. Ethernet Cable Conexion from UPEU_0 to UIM 02A............................................................................7Figure 5. Ethernet Cable Conexion from UPEU_1 to Terminal Block..................................................................8Figure 7. Example of External Alarm Integration................................................................................................10Figure 8. M2000 Alarm Definition.......................................................................................................................11
3
![Page 4: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/4.jpg)
TP48200A. External Alarms.
List of TablesTable 1. Alarm Information to be Commissioned in LMT and M2000..............................................................12
4
![Page 5: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/5.jpg)
TP48200A. External Alarms.
1. External Alarms Description:
External Alarms by Default corresponding to PMU (UIM 02A):
ALM1 Smoke Alarm ALM2 Door Open ALM3 Rect Fault ; Rect Com Fault ALM4 Load Fuse Trip; Batt Fuse Trip ALM5 Batt Temp Alarm ALM6 NULL (Not Configured)
ALM7 Main Fault ALM8 Head Lamp
ALM9 SPD Fault
Figure 1. UIM 02A
External Alarms from outside the cabinet:
ALM10 Alternative power source ALM11 AC main failure
ALM12 Beacon failure ALM13 Low level gas
ALM14 Grupo en Marcha ALM15 Reserved
ALM16 Reserved ALM17 Reserved
5
![Page 6: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/6.jpg)
TP48200A. External Alarms.
Figure 2. Terminal Block
2. External Alarms Connections (4x Ethernet cable (RJ45)):
6
![Page 7: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/7.jpg)
TP48200A. External Alarms.
Figure 3. Layout Connection All External Alarms
Note: Red cable connects ALM_9 (UIM 02A) to Port_0 (Terminal Block) in order to take ALM9 to the first position in UPEU_1.
2.1. UPEU_0 UIM 02A
ALM1 ALM2 ALM3 ALM4
7
![Page 8: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/8.jpg)
TP48200A. External Alarms.
UIM 02A
Board+ - + - + - + -
DRY PIN
Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown
UPEU_0 Board
EXT_ALM0
UIM 02A
Board
ALM5 ALM7 ALM8 ALM9
+ - + - + - + -
DRY PIN
Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown
UPEU_0 Board
EXT-ALM1
Figure 4. Ethernet Cable Conexion from UPEU_0 to UIM 02A
2.2 UPEU_1 Terminal Block
8
![Page 9: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/9.jpg)
TP48200A. External Alarms.
Terminal
Block
Port_0 Port_1 Port_2 Port_3
+ - + - + - + -
DRY PIN Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown
UPEU_1 Board
EXT_ALM0
Terminal Block
Port_4 Port_5 Port_6 Port_7
+ - + - + - + -
DRY PIN Orange&White Orange Green&White Green Blue&White Blue Brown&White Brown
UPEU_1 Board
EXT-ALM1
Figure 5. Ethernet Cable Conexion from UPEU_1 to Terminal Block.
Note: For further details, please refer to Reference Pictures
3. External Alarms Integration:
1 st Step : Ethernet Cable Connection: UPEU_0 UIM 02A
9
![Page 10: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/10.jpg)
TP48200A. External Alarms.
UPEU_1 Terminal Block
Note: Refer to External Alarm Connections to check connection configuration details.
2 nd Step: Add External Alarm in UPEU Board:
Note: Refer to External Alarm Description to check Alarm ID for each external alarm.
Example:
Normally the configuration will be done on the 2G BTS as follow ,
SET BTSENVALMPORT: IDTYPE=BYID, BTSID=222, CN=0, SRN=0, SN=18, PN=0, SW=OPEN, AID=65133, PT=BOOL, AVOL=HIGH;SET BTSENVALMPORT: IDTYPE=BYID, BTSID=222, CN=0, SRN=0, SN=18, PN=1, SW=OPEN, AID=65134, PT=BOOL, AVOL=HIGH;....
Or From 3G NodeB
10
![Page 11: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/11.jpg)
TP48200A. External Alarms.
SET ALMPORT: CN=0, SRN=0, SN=18, PN=0, SW=ON, AID=65133, PT=BOOL, AVOL=HIGH;SET ALMPORT: CN=0, SRN=0, SN=18, PN=, SW=ON, AID=65133, PT=BOOL, AVOL=HIGH;Example:
SET ALMPORT: CN=0, SRN=0, SN=18, PN=0, SW=ON, AID=65033, PT=BOOL, AVOL=HIGH;
Figure 6. Example of External Alarm Integration
3 rd Step : M2000 External Alarm Definition: Assign Alarm Name to Alarm ID.
Note: Refer to External Alarm Description to check Alarm Name associated to Alarm ID.
Enter M2000 Server:Monitor / Alarm Setting / NE Alarm Setting Add
11
![Page 12: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/12.jpg)
TP48200A. External Alarms.
Figure 7. M2000 Alarm Definition.
ALARM
Cabinet No
Subrack No Slot No Port No Switch
Alarm ID
Port Type
Alarm Voltage
Alarm Name
Alarm Severity
Level (Configure
d from M2000)
(Configured from
M2000)
ALM1 0 0 18 0 ON 65133 BOOL HIGH Fuego / Major
ALM2 0 0 18 1 ON 65134 BOOL HIGH Intrusión Major
ALM3 0 0 18 2 ON 65135 BOOL HIGHFallo menor
Continua Major
ALM4 0 0 18 3 ON 65136 BOOL HIGHDistribución
Continua Major
ALM5 0 0 18 4 ON 65137 BOOL HIGHTemperatur
a Alta Major
ALM6 NULL NULL NULL NULL NULL NULL NULL NULL NULL NULL
12
![Page 13: Tp48200a External Alarms v1 0(Corregido)](https://reader033.vdocuments.us/reader033/viewer/2022061414/55cf99ec550346d0339fc1af/html5/thumbnails/13.jpg)
TP48200A. External Alarms.
ALM7 0 0 18 5 ON 65138 BOOL HIGHFallo
Alterna Major
ALM8 0 0 18 6 ON 65139 BOOL HIGHFallo Mayor
Continua Major
ALM9 0 0 18 7 ON 65140 BOOL HIGH
Fallo Prot. Sobretensió
n Major
ALM10 0 0 19 0 ON 65141 BOOL HIGHSuministro Alternativo Major
ALM11 0 0 19 1 ON 65142 BOOL HIGHFallo
Alterna Major
ALM12 0 0 19 2 ON 65143 BOOL HIGH Baliza Major
ALM13 0 0 19 3 ON 65144 BOOL HIGHBajo Nivel
Gasóleo Major
ALM14 0 0 19 4 ON 65145 BOOL HIGHGrupo en Marcha Major
ALM15 0 0 19 5 ON 65146 BOOL HIGH Reserva Major
ALM16 0 0 19 6 ON 65147 BOOL HIGH Reserva Major
ALM17 0 0 19 7 ON 65148 BOOL HIGH Reserva Major
Table 1. Alarm Information to be Commissioned in LMT and M2000.