Time Current Curves TD012030EN Effective September 2015
ContentsDescription Page
Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Digitrip 310+ Electronic Trip Unit types RGH, RGCLong Delay Response and Short Delay with Flat Response and Override (LSI, LSIG, ALSI, ALSIG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01210020E . . . . . . . .5Long Delay Response and Short Delay with I2T Response Curve and Override (LS, LSG) TC01210021E . . . . . . . .6Ground Fault Delay Response Curve (LSG, LSIG, ALSIG) . . . . . . . . . . . . . . . . . . . . . . . . . TC01210022E . . . . . . . .7Maintentance Mode / Instantaneous Setting 1600A / 2000A (ALSI, ALSIG) . . . . . . . . . . . TC01210024E . . . . . . . .8Maintentance Mode / Instantaneous Setting 2500A (ALSI, ALSIG) . . . . . . . . . . . . . . . . . TC01210023E . . . . . . . .9
Digitrip RMS 310 Electronic Trip Unit types
Typical Instantaneous Time-Phase Current Characteristic Curve Based on In . . . . . . . . . . . SC-5629-93 . . . . . . . .10Typical Long Delay/Short Delay Time-Phase Current Characteristic Curve Based on In . . . SC-5630-93 . . . . . . . .11Typical Ground Fault/Protection Time/Current Characteristic Curve Based on In . . . . . . . . . SC-5631-93 . . . . . . . .12
Note:The following curves meet the requirements of UL, CSA, IEC, CCC and CE .The following circuit breakers are derived from Eaton, Westinghouse, or Cutler-Hammer history .
Time Current Curves are engineering reference document for application and coordination purposes only .
Series G R-Frame 800-2500A, 240-690V
Proof 4 — October 19, 2015 11:49 AM
2
Time Current Curves AD012020ENEffective October 2013
Series G L-Frame
eaton www.eaton.com
otee:N Unless noted below, all curves remain unchanged from their prior revision .
Revision Curve Number Page Date
2
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
EATON www.eaton.com
Proof 4 — October 19, 2015 11:49 AM
Instantaneous curve adjusted
to meet tolerances.
ZSI times added to short delay curves.
TC01210020E
TC01210021E
5
6
5
6
9 - 2015
9 - 2015
Proof 4 — October 19, 2015 11:49 AM
3
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
EATON www.eaton.com
RG H 3 250 39 ZG E C
Frame
RG
Amperes
160 = 1600200250
= 2000= 2500
Rating
Blank = 80% ratedC = 100% rated (except 2500A)
Feature
Terminations
M = Metric tapped line/load conductors
E = Imperial tapped line/load conductors
Trip Unit
33323535B223636B2238
39
39B22
= 310+ Electronic LS= 310+ Electronic LSI= 310+ Electronic LSG= 310+ Electronic LS(A), GFA, no trip= 310+ Electronic LSIG= 310+ Electronic LSI(A), GFA, no trip= 310+ Electronic ALSI with Maintenance Mode= 310+ Electronic ALSIG with Maintenance Mode= 310+ Electronic ALSI(A) with Maintenance Mode and GFA, no trip
Poles
3 = Three4 = Four
BlankB20B21ZG
= No feature= High load alarm= Ground fault= Zone selective interlocking
Performance
600 480 415 240
H
C
50 65 70 12565 100 100 200
Table 1. RG Circuit Breaker/Frame
Catalog Number Selection
This information is presented only as an aid to understanding catalog numbers .It is not to be used to build catalog numbers for circuit breakers or trip units .
Proof 4 — October 19, 2015 11:49 AM
LS
LSG LSIG
LSI
ALSIG (With Maintenance Mode)
ALSI (With Maintenance Mode)
STATUS
TEST / ALARMIr∑
tr (s)LONG
E
GF
H
AB
DC
12
2015
24
24
107
NP 6635C07 H26
Isd (xIr)SHORT
Engaged
Remove67
23
54
89
I RatingChart
r
STATUS
TEST / ALARMIr∑
tr (s)LONG
E
GF
H
AB
DC
12
2015
24
24
107
NP 6635C07 H25
Isd (xIr)SHORT
Engaged
Remove
tsd (ms)SHORT120
300
Inst.
67
23
54
89
ChartI Ratingr
STATUS
TEST / ALARMIr∑
tr (s)LONG
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
CAUSE OF TRIP
Remote MM
NP 6635C07 H24
Isd (xIr)SHORT
Engaged
Remove
tsd (ms)SHORT120
300
50
2.5
76
Ii (xIn)INST
4
Maintenance Mode
Max8
67
23
54
89
ChartI Ratingr
1.01.2
.2.4
.8.6
STATUS
TEST / ALARMIr∑
tr (s)LONG
Ig (x 1000A)GND
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
G
CAUSE OF TRIP
NP 6635C07 H23
Isd (xIr)SHORT
Engaged
Remove
tg (ms)GND120
300
Inst.
67
23
54
89
1.01.2
.2.4
.8.6
STATUS
TEST / ALARMIr∑
tr (s)LONG
Ig (x 1000A)GND
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
G
CAUSE OF TRIP
N
PO
Q
JK
ML
R
tsd / tg (ms)SHORT / GND*
NP 6635C07 H22
Isd (xIr)SHORT
Engaged
Remove
tg (ms)
tsd(ms)
120
K N Q
300
L O R
* Inst.
J M P
Inst.120300
Settings
67
23
54
89
1.01.2
.2.4
.8.6
STATUS
TEST / ALARMIr∑
tr (s)LONG
Ig (x 1000A)GND
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
G
CAUSE OF TRIP
Remote MM
N
PO
Q
JK
ML
R
tsd / tg (ms)SHORT / GND*
NP 6635C07 H21
Isd (xIr)SHORT6
7
23
54
89
Engaged
Remove
tg (ms)
tsd(ms)
120
K N Q
300
L O R
* Inst.
J M P
50120300
Settings
2.5
76
Ii (xIn)INST
4
Maintenance Mode
Max8
I RatingChart
rChart
I RatingrChart
I Ratingr
4
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
EATON www.eaton.com
0.01
1
2
3
4
5
6789
10
20
30
40
50
60
708090
100
1000900800700
600
500
400
300
200
2000
3000
4000
5000
6000
700080009000
10000
0.02
0.03
0.04
0.05
0.06
0.070.080.090.1
0.2
0.3
0.4
0.5
0.60.70.80.9
1
0.01
0.02
0.03
0.04
0.05
0.060.070.080.090.1
0.2
0.3
0.4
0.5
7
2
2
2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 1000.5 0.7
1 2 3 4 5 7 10 20 300.5 0.7
4
4
.15
.24
63
1.15
17500A
Application DeterminesEnd of Curve
7
.
5
.
300 ms(P,Q,R)
120 ms(M,N,O)
Inst.(J,K,L)
Available Short Delay Pickup
SettingsISD x Ir ± 5%(See Note 7)
.
.
.
12
12
7
9
8
Minimum TotalClearing Time
Maximum TotalClearing Time
Available Long Delay Time2, 4, 7, 10 ,12, 15, 20, 24 sec
Shown @ 6 x Ir +0/–30%
TIM
E IN
SE
CO
ND
S1
MIN
UT
E1
HO
UR
2 H
OU
RS
TIM
E IN
SE
CO
ND
S
Current in Multiples of (Ir)
Current in Multiples of (Ir) Current in 1000A Increments
Adjustable Flat Trip Style (LSI, LSIG, ALSI, ALSIG)
Instantaneous Override (See Note 8)
Figure 1. Digitrip 310+ Faceplates
*1600A/2000A Faceplates shown, 2500A Faceplates may differ
Proof 4 — October 19, 2015 11:49 AM
5
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
EATON www.eaton.com
0.01
1
2
3
4
5
6789
10
20
30
40
50
60
708090
100
1000900800700
600
500
400
300
200
2000
3000
4000
5000
6000
700080009000
10000
0.02
0.03
0.04
0.05
0.06
0.070.080.090.1
0.2
0.3
0.4
0.5
0.60.70.80.9
1
0.01
0.02
0.03
0.04
0.05
0.060.070.080.090.1
0.2
0.3
0.4
0.5
7
2
2
2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 1000.5 0.7
1 2 3 4 5 7 10 20 300.5 0.7
4
4
.15
.24
63
1.15
17500A
Application DeterminesEnd of Curve
7
.
5
.
300 ms(P,Q,R)
120 ms(M,N,O)
Inst.(J,K,L)
Available Short Delay Pickup
SettingsISD x Ir ± 5%(See Note 7)
.
.
.
12
12
7
9
8
Minimum TotalClearing Time
Maximum TotalClearing Time
Available Long Delay Time2, 4, 7, 10 ,12, 15, 20, 24 sec
Shown @ 6 x Ir +0/–30%
TIM
E IN
SE
CO
ND
S1
MIN
UT
E1
HO
UR
2 H
OU
RS
TIM
E IN
SE
CO
ND
S
Current in Multiples of (Ir)
Current in Multiples of (Ir) Current in 1000A Increments
Adjustable Flat Trip Style (LSI, LSIG, ALSI, ALSIG)
Instantaneous Override (See Note 8)
Circuit Breaker Time/Current Curves (Phase Current)
Series G R-Frame Circuit Breakers
Long Delay Response and Short Delay with Flat Response and Override
Catalog Types: RGH, RGC circuit breakers, three- and four-pole
Trip Unit Types: 32 (LSI), 36 (LSIG), 38 (ALSI), 39 (ALSIG)
Notes:
1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous ampere derating for ambient above 40°C, refer to Eaton . Temperatures above +85°C cause an over-temperature protection trip .
2 . Application frequency is 50/60 Hz .
3 . There is a memory effect that can act to shorten the long delay . If the breaker trips on a long delay overload and is quickly reset, the memory capacitor will still have charge, and a subsequent overload will cause the breaker to trip in a shorter time than normal . The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload . Approximately five minutes is required between overloads to completely reset memory .
4 . The right portion of the curve is determined by the interrupting rating of the circuit breaker .
5 . The left portion of the curve is shown as a multiple of the Long Delay Setting . (Long Delay Pickup = 115% of Ir ) . Range is 110–120% .
6 . Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current .
7 . The short delay pickup has nine settings/positions; 1600A/2000A - 2, 3, 4, 5, 6, 7, 8, 8, 9 2500A - 2, 2, 2, 3, 4, 5, 6, 6, 6
8 . For high fault current levels, an additional fixed instantaneous hardware override is provided to trip the breaker at 17,500A . Instantaneous tolerance is ± 20% .
9 . Maximum clearing time when using zone selective interlocking is 62ms .
Available Sensors(Ir) / (In)
Rated Amperes1600A 2000A 2500A
ABCDE F G H
800A 1000A 1600A900A 1200A 1700A1000A 1400A 1800A1100A 1600A 2000A1200A 1700A 2100A1400A 1800A 2200A1500A 1900A 2400A1600A 2000A 2500A
ALSI (With Maintenance Mode)
STATUS
TEST / ALARMIr∑
tr (s)LONG
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
CAUSE OF TRIP
Remote MM
NP 6635C07 H24
Isd (xIr)SHORT
Engaged
Remove
tsd (ms)SHORT120
300
50
2.5
76
Ii (xIn)INST
4
Maintenance Mode
Max8
67
23
54
89
ChartI Ratingr
LSI
STATUS
TEST / ALARMIr∑
tr (s)LONG
E
GF
H
AB
DC
12
2015
24
24
107
NP 6635C07 H25
Isd (xIr)SHORT
Engaged
Remove
tsd (ms)SHORT120
300
Inst.
67
23
54
89
ChartI Ratingr
LSIG
1.01.2
.2.4
.8.6
STATUS
TEST / ALARMIr∑
tr (s)LONG
Ig (x 1000A)GND
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
G
CAUSE OF TRIP
N
PO
Q
JK
ML
R
tsd / tg (ms)SHORT / GND*
NP 6635C07 H22
Isd (xIr)SHORT
Engaged
Remove
tg (ms)
tsd(ms)
120
K N Q
300
L O R
* Inst.
J M P
Inst.120300
Settings
67
23
54
89
ChartI Ratingr
ALSIG (With Maintenance Mode)
1.01.2
.2.4
.8.6
STATUS
TEST / ALARMIr∑
tr (s)LONG
Ig (x 1000A)GND
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
G
CAUSE OF TRIP
Remote MM
N
PO
Q
JK
ML
R
tsd / tg (ms)SHORT / GND*
NP 6635C07 H21
Isd (xIr)SHORT6
7
23
54
89
Engaged
Remove
tg (ms)
tsd(ms)
120
K N Q
300
L O R
* Inst.
J M P
50120300
Settings
2.5
76
Ii (xIn)INST
4
Maintenance Mode
Max8
ChartI Ratingr
Figure 2. Digitrip 310+ Long Delay Response and Short Delay with Flat Response and Override Curve (LSI, LSIG, ALSI, ALSIG) - Curve Number TC01210020E, September 2015
*1600A/2000A Faceplates shown, 2500A Faceplates may differ
Proof 4 — October 19, 2015 11:49 AM
6
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
EATON www.eaton.com
0.01
1
2
3
4
5
6789
10
20
70
90
1000900800700
600
500
400
300
200
2000
3000
4000
5000
6000
700080009000
10000
0.02
0.03
0.04
0.05
0.06
0.070.080.090.1
0.2
0.3
0.4
0.5
0.60.70.80.9
1
3
4
5
6789
10
30
40
50
60
80
100
0.01
0.02
0.03
0.04
0.05
0.060.070.080.090.1
0.2
0.3
7
Application DeterminesEnd of Curve
2
InstantaneousOverride (See Note 8)
1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 1000.5 0.7
1 2 3 4 5 7 10 20 300.5 0.7
Minimum TotalClearing Time
I2T Short Delay(See Note 9)
5
.15
24
3
1.15
17500A
67 ms
12
12
7
See Note 9
4
.4
.
.
.
0.5
2
Available Long Delay Time2, 4, 7, 10, 12, 15, 20, 24 secShown at 6 x Ir +0 / –30%
9
.
6
8
Current in Multiples of (Ir) Current in 1000A Increments
Maximum TotalClearing Time
Current in Multiples of (Ir)
1 H
OU
R2
HO
UR
S1
MIN
UT
ET
IME
IN S
EC
ON
DS
TIM
E IN
SE
CO
ND
S
Available Short DelayPickup Settings2–8, 9 x Ir ± 5%
(See Notes 7 and 10)
I2T Trip Style (LS, LSG)
0.01
2
3
4
5
6
8
10
20
30
40
50
60708090
100
1000900800700
600
500
400
300
200
0.02
0.03
0.04
0.05
0.06
0.070.080.090.1
0.2
0.3
0.4
0.5
0.6
0.70.80.9
1
7
9
2000
3000
4000
5000
6000
700080009000
10000
1M
INU
TE
0.1 0.2 0.3 0.4 0.5 0.7 1.0 2.0
0.1 0.2 0.3 0.4 0.5 0.7 1.0 2.0
TIM
EIN
ES
CO
NS
D
0.2x Ig
1.2x Ig
0.4x Ig 0.6x Ig
0.8x Ig
1.0x Ig
Inst.(J, M, P)
300 ms(L, O, R)
Ground Current in Multiples of Ig x 1000
Ground Fault Pickup Settings(Tolerance ±10%)
120 ms(K, N, Q)
Ig = 1000A for all RG Frames
Circuit Breaker Time/Current Curves (Phase Current)
Series G R-Frame Circuit Breakers
Long Delay Response and Short Delay with I2T Response Curve and Override
Catalog Types: RGH, RGC circuit breakers, three- and four-pole
Trip Unit Types: 33 (LS), 35 (LSG)
Notes:
1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous ampere derating for ambient above 40°C, refer to Eaton . Temperatures above +85°C cause an over-temperature protection trip .
2 . Application frequency is 50/60 Hz .
3 . There is a memory effect that can act to shorten the long delay . If the breaker trips on a long delay overload and is quickly reset, the memory capacitor will still have charge, and a subsequent overload will cause the breaker to trip in a shorter time than normal . The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload . Approximately five minutes is required between overloads to completely reset memory .
4 . The right portion of the curve is determined by the interrupting rating of the circuit breaker .
5 . The left portion of the curve is shown as a multiple of the Long Delay Setting . (Long Delay Pickup = 115% of Ir ) . Range is 110–120% .
6 . Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current .
7 . The short delay pickup has nine settings/positions; 1600A/2000A - 2, 3, 4, 5, 6, 7, 8, 8, 9 2500A - 2, 2, 2, 3, 4, 5, 6, 6, 6
8 . For high fault current levels, an additional fixed instantaneous hardware override is provided to trip the breaker at 17,500A . Instantaneous tolerance is ± 20% .
9 . Short delay I2T band has a tolerance of ±15% .
10 . Breakpoint back to FLAT response occurs at 8 x Ir for upper line of the I2T curve .
11 . Maximum clearing time when using zone selective interlocking is 62ms .
Available Sensors(Ir) / (In)
Rated Amperes1600A 2000A 2500A
ABCDE F G H
800A 1000A 1600A900A 1200A 1700A1000A 1400A 1800A1100A 1600A 2000A1200A 1700A 2100A1400A 1800A 2200A1500A 1900A 2400A1600A 2000A 2500A
LSG
1.01.2
.2.4
.8.6
STATUS
TEST / ALARMIr∑
tr (s)LONG
Ig (x 1000A)GND
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
G
CAUSE OF TRIP
NP 6635C07 H23
Isd (xIr)SHORT
Engaged
Remove
tg (ms)GND120
300
Inst.
67
23
54
89
I RatingChart
r
LS
STATUS
TEST / ALARMIr∑
tr (s)LONG
E
GF
H
AB
DC
12
2015
24
24
107
NP 6635C07 H26
Isd (xIr)SHORT
Engaged
Remove67
23
54
89
I RatingChart
r
Figure 3. Digitrip 310+ Long Delay Response and Short delay with I2T Response Curve (LS, LSG) - Curve Number TC01210021E, September 2015
*1600A/2000A Faceplates shown, 2500A Faceplates may differ
Proof 4 — October 19, 2015 11:49 AM
7
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
EATON www.eaton.com
0.01
2
3
4
5
6
8
10
20
30
40
50
60708090
100
1000900800700
600
500
400
300
200
0.02
0.03
0.04
0.05
0.06
0.070.080.090.1
0.2
0.3
0.4
0.5
0.6
0.70.80.9
1
7
9
2000
3000
4000
5000
6000
700080009000
10000
1M
INU
TE
0.1 0.2 0.3 0.4 0.5 0.7 1.0 2.0
0.1 0.2 0.3 0.4 0.5 0.7 1.0 2.0
TIM
EIN
ES
CO
NS
D
0.2x Ig
1.2x Ig
0.4x Ig 0.6x Ig
0.8x Ig
1.0x Ig
Inst.(J, M, P)
300 ms(L, O, R)
Ground Current in Multiples of Ig x 1000
Ground Fault Pickup Settings(Tolerance ±10%)
120 ms(K, N, Q)
Ig = 1000A for all RG Frames
Circuit Breaker Time/Current Curves (Ground Current)
Series G R-Frame Circuit Breakers
Ground Fault Delay Response Curve
Catalog Types: RGH, RGC circuit breakers, three- and four-pole
Trip Unit Types: 35 (LSG), 36 (LSIG), 39 (ALSIG)
Ground fault delay response notes:
1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous ampere derating for ambient above 40°C, refer to Eaton . Temperatures above +85°C cause an over-temperature protection trip .
2 . Application frequency is 50/60 Hz .
3 . Trip units are suitable for functional field testing with test kit cat no: MTST230V .
4 . For LD Response and SD with Flat Responses curve, see TC01210020E .
5 . For LD Responses and SD with I2T Response curve, see TC01210021E .
6 . For testing information, please contact Eaton .
LSIG
1.01.2
.2.4
.8.6
STATUS
TEST / ALARMIr∑
tr (s)LONG
Ig (x 1000A)GND
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
G
CAUSE OF TRIP
N
PO
Q
JK
ML
R
tsd / tg (ms)SHORT / GND*
NP 6635C07 H22
Isd (xIr)SHORT
Engaged
Remove
tg (ms)
tsd(ms)
120
K N Q
300
L O R
* Inst.
J M P
Inst.120300
Settings
67
23
54
89
ChartI Ratingr
LSG
1.01.2
.2.4
.8.6
STATUS
TEST / ALARMIr∑
tr (s)LONG
Ig (x 1000A)GND
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
G
CAUSE OF TRIP
NP 6635C07 H23
Isd (xIr)SHORT
Engaged
Remove
tg (ms)GND120
300
Inst.
67
23
54
89
I RatingChart
r
ALSIG (With Maintenance Mode)
1.01.2
.2.4
.8.6
STATUS
TEST / ALARMIr∑
tr (s)LONG
Ig (x 1000A)GND
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
G
CAUSE OF TRIP
Remote MM
N
PO
Q
JK
ML
R
tsd / tg (ms)SHORT / GND*
NP 6635C07 H21
Isd (xIr)SHORT6
7
23
54
89
Engaged
Remove
tg (ms)
tsd(ms)
120
K N Q
300
L O R
* Inst.
J M P
50120300
Settings
2.5
76
Ii (xIn)INST
4
Maintenance Mode
Max8
ChartI Ratingr
tg (ms)
tsd(ms)
120
K N Q
300
L O R
* Inst.
J M P
Inst.120300
Settings
SD / GF Delay Settings Table
Figure 4. Ground Fault Delay Response Curve (LSG, LSIG, ALSIG) Curve Number TC01210022E, June 2012
*1600A/2000A Faceplates shown, 2500A Faceplates may differ
Proof 4 — October 19, 2015 11:49 AM
8
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
EATON www.eaton.com
0.01
2
0.02
0.03
0.04
0.05
0.060.070.080.09
0.1
0.2
0.3
0.4
0.5
0.60.70.80.9
1
3
4
5
6789
10
0.01
1 2 3 40.5
0.6
0.7
0.8
0.9
10
20
30
40
50 5 6 7 8 9
0.02
0.03
0.04
0.05
0.060.070.080.090.1
0.2
0.3
0.4
0.5
0.6
0.70.80.9
ND
ST
IME
IN S
EC
O
100
7.0
2.5
10 1
8.0
11.0
9.0
6.0
TIM
E IN
SE
CO
ND
S
4.0
2
3
4
5
6789
10
1
Max. for1600AFrame
Maintenance Mode Trip Instantaneous Mode Trip
Current in Multiples of Rating (In)
ApplicationDetermines
End of Curve
ApplicationDetermines
End of Curve
Max. for2000AFrame
Instantaneous Mode Pickup Tolerance (+/- 15%)
Maintenance Mode Pickup tolerance (+/- 15%)
0.01
2
0.02
0.03
0.04
0.05
0.060.070.080.090.1
0.2
0.3
0.4
0.5
0.60.70.80.9
1
3
4
5
6789
10
0.01
1 2 3 40.5
0.6
0.7
0.8
0.9
10
20
30
40
50 5 6 7 8 9
0.02
0.03
0.04
0.05
0.060.070.080.090.1
0.2
0.3
0.4
0.5
0.6
0.70.80.9
ND
ST
IME
IN S
EC
O
100
7.0
2.5
10 1
6.0
TIM
E IN
SE
CO
ND
S
4.0
2
3
4
5
6789
10
1
ApplicationDetermines
End of Curve
Maintenance Mode Trip Instantaneous Mode Trip
Current in Multiples of Rating (In)
ApplicationDetermines
End of Curve
Instantaneous Mode Pickup Tolerance (+/- 15%)
Maintenance Mode Pickup tolerance (+/- 15%)
Notes:
1 . The Maintenance Mode feature must be ENABLED for these curves to apply . The LED indicator is blue when in Maintenance Mode .
2 . The end of the curve is determined by the interrupting rating of the circuit breaker .
3 . Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current .
4 . Available pickup settings ( x In) (tolerance is ±15%) 1600A Frame: 2 .5, 4, 6, 7, 8, 8, 11 2000A Frame: 2 .5, 4, 6, 7, 8, 8, 9
5 . These curves are comprehensive for the complete family of Series G R-Frame electronic breakers, including all frame sizes, ratings, and constructions . The total clearing times shown are conservative and consider the maximum response times of the trip unit, the circuit breaker opening, and the interruption of the current in worst case conditions such as: maximum rated voltages, single-phase interruption, and minimum power factor . Faster clearing times are possible depending on the specific system conditions .
Contact Eaton for additional information .
Figure 5. Maintenance Mode/Instantaneous Setting 1600A/2000A (ALSI, ALSIG) - Curve Number TC01210024E, September 2015
Digitrip 310+ Circuit Breaker Time/Current Curves
Maintenance Mode/Instantaneous
Setting (1600A/2000A)
Series G R-Frame Trip Unit Nameplates
ALSI (With Maintenance Mode)
STATUS
TEST / ALARMIr∑
tr (s)LONG
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
CAUSE OF TRIP
Remote MM
NP 6635C07 H24
Isd (xIr)SHORT
Engaged
Remove
tsd (ms)SHORT120
300
50
2.5
76
Ii (xIn)INST
4
Maintenance Mode
Max8
67
23
54
89
ChartI Ratingr
ALSIG (With Maintenance Mode)
1.01.2
.2.4
.8.6
STATUS
TEST / ALARMIr∑
tr (s)LONG
Ig (x 1000A)GND
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
G
CAUSE OF TRIP
Remote MM
N
PO
Q
JK
ML
R
tsd / tg (ms)SHORT / GND*
NP 6635C07 H21
Isd (xIr)SHORT6
7
23
54
89
Engaged
Remove
tg (ms)
tsd(ms)
120
K N Q
300
L O R
* Inst.
J M P
50120300
Settings
2.5
76
Ii (xIn)INST
4
Maintenance Mode
Max8
ChartI Ratingr
*1600A/2000A Faceplates shown, 2500A Faceplates may differ
Proof 4 — October 19, 2015 11:49 AM
9
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
0.01
2
0.02
0.03
0.04
0.05
0.060.070.080.090.1
0.2
0.3
0.4
0.5
0.60.70.80.9
1
3
4
5
6789
10
0.01
1 2 3 40.5
0.6
0.7
0.8
0.9
10
20
30
40
50 5 6 7 8 9
0.02
0.03
0.04
0.05
0.060.070.080.090.1
0.2
0.3
0.4
0.5
0.6
0.70.80.9
ND
ST
IME
IN S
EC
O
100
7.0
2.5
10 1
6.0
TIM
E IN
SE
CO
ND
S
4.0
2
3
4
5
6789
10
1
ApplicationDetermines
End of Curve
Maintenance Mode Trip Instantaneous Mode Trip
Current in Multiples of Rating (In)
ApplicationDetermines
End of Curve
Instantaneous Mode Pickup Tolerance (+/- 15%)
Maintenance Mode Pickup tolerance (+/- 15%)
Notes:
1 . The Maintenance Mode feature must be ENABLED for these curves to apply . The LED indicator is blue when in Maintenance Mode .
2 . The end of the curve is determined by the interrupting rating of the circuit breaker .
3 . Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current .
4 . Available pickup settings ( x In) (tolerance is ±15%) 2 .5, 4, 6, 6, 6, 7 .
5 . These curves are comprehensive for the complete family of Series G R-Frame electronic breakers, including all frame sizes, ratings, and constructions . The total clearing times shown are conservative and consider the maximum response times of the trip unit, the circuit breaker opening, and the interruption of the current in worst case conditions such as: maximum rated voltages, single- phase interruption, and minimum power factor . Faster clearing times are possible depending on the specic system conditions .
Contact Eaton for additional information .
Digitrip 310+ Circuit Breaker Time/Current Curves
Maintenance Mode/Instantaneous Setting (2500A)
Figure 6. Maintenance Mode/Instantaneous Setting 2500A (ALSI, ALSIG) Curve Number TC01210023E, September 2015
Series G R-Frame Trip Unit Nameplates
ALSI (With Maintenance Mode)
STATUS
TEST / ALARMIr∑
tr (s)LONG
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
CAUSE OF TRIP
Remote MM
NP 6635C07 H24
Isd (xIr)SHORT
Engaged
Remove
tsd (ms)SHORT120
300
50
2.5
76
Ii (xIn)INST
4
Maintenance Mode
Max8
67
23
54
89
ChartI Ratingr
ALSIG (With Maintenance Mode)
1.01.2
.2.4
.8.6
STATUS
TEST / ALARMIr∑
tr (s)LONG
Ig (x 1000A)GND
E
GF
H
AB
DC
12
2015
24
24
107
RESET
L
S
I
G
CAUSE OF TRIP
Remote MM
N
PO
Q
JK
ML
R
tsd / tg (ms)SHORT / GND*
NP 6635C07 H21
Isd (xIr)SHORT6
7
23
54
89
Engaged
Remove
tg (ms)
tsd(ms)
120
K N Q
300
L O R
* Inst.
J M P
50120300
Settings
2.5
76
Ii (xIn)INST
4
Maintenance Mode
Max8
ChartI Ratingr
EATON www.eaton.com
*1600A/2000A Faceplates shown, 2500A Faceplates may differ
Proof 4 — October 19, 2015 11:49 AM
6X
8X
4X
3X
2X
Standard FixedRating Plug
200 ms
100 ms
I
300 ms
5X
�
FrameRatingAmperes(Max.)
Available Rating PlugsAmpereRating (In)
Type Short DelayPickup RangeAmperes
CatalogNumber
(Icu)
500V
4265
380-415V
065100
IEC 947-2220-240V
125200
600V
5065
480V
065100
UL/CSA240V
125200
Short DelayPickup
In
Short DelayTime
Sec
NP6645C79H02
In_Cat._Engaged
Remove
NP6635C68H07 Made in U.S.A.
Digitrip RMS 310
Cell No.
Digitrip RMS 310 Rating PlugFor Use in R Circuit Breaker Only
WestinghouseDigitalProtection
�
Circuit Breaker Time/Current Curves (Phase Current) �
Series C® R-Frame Circuit BreakersEquipped With Type Digitrip RMS 310 Trip Units
Interrupting Ratings – 50/60 HzRMS Sym. Amperes (kA)
Utilization Category AIcs = 0.25 IcuUimp = 8 kV
Typical Trip Unit Nameplate
For use with Trip Unit Catalog Numbers
2000A Max.RES2000LSIRES2000LSIGRES2000LSI
2500A Max.RES2500LSIRES2500LSIGRES2500LSI
16001400125012001000800800, 1000, 1200, 1600800, 1000, 1250, 1600
2000160014001250120010001000, 1200, 1600, 20001000, 1250, 1600, 2000
250020001600125012001200, 1600, 2000, 25001250, 1600, 2000, 2500
FixedFixedFixedFixedFixedFixedAdj.Adj.
FixedFixedFixedFixedFixedFixedAdj.Adj.
FixedFixedFixedFixedFixedAdj.Adj.
16RS16T16RS14T16RS125T�16RS12T16RS10T16RS08TA16RS16T1A16RS16T2�
20RS20T20RS16T20RS14T20RS125T�20RS12T20RS10TA20RS20T1A20RS20T2�
25RES25T25RES20T25RES16T25RES125T�25RES12TA25RES25T1A25RES25T2�
3200-128002800-112002500-100002400-96002000-80001600-64001600-128001600-12800
4000-160003200-128002800-112002500-100002400-96002000-80002000-160002000-16000
5000-150004000-120003200-96002500-75002400-720024000-150002500-15000
1600
2000
2500
BreakerType
1600A Max.RES1600LSIRES1600LSIGRES1600LSI
TIM
E IN
SEC
ONDS
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1 HO
UR1
MIN
UTE
2 HO
URS
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
.5
.5 201054321.8.6
1.8.6CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
.7 .9 6 7 8 9
20105432 6 7 8 9
Short DelayPick UpSettings(Tolerance±10%)
Minimum TotalClearing Time
Maximum TotalClearing Time
.7 .9
.02
.03
.04
.05Fixed InstantaneousOverride �
InterruptingRatingDeterminesEnd ofCurve �
.1
.01
10,0
00
20,0
00
.001
SECO
NDS
CURRENT IN AMPS
30,0
00
40,0
00
50,0
00
100,
000
7X
�
200,
000
RD, CRDRDC, CRDC
For 2500A styles, maximum short delay pickup setting = 6X.For high fault current levels a fixed instantaneous override is provided at 17,500A(Tolerance ±15%).The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.For ground fault time-current curves see SC-5631-93.Not UL/CSA Listed.
��
�
��
NotesCurve accuracy applies from –20°C to +55°C ambient. For possible ampere derating forambient above 40°C, refer to Cutler-Hammer.
Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No.STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991.
6X
8X
4X
7X
2X
Minimum TotalClearing Time
Maximum TotalClearing Time
Standard FixedRating Plug
Short DelayPick UpSettings(Tolerance ±10%)
5X
3X
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
.5
.5
TIM
E IN
SEC
ONDS
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1 HO
UR1
MIN
UTE
2 HO
URS
201054321.8.6
1.8.6CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
.7 .9 6 7 8 9
20105432 6 7 8 9.7 .9
CURRENT IN AMPS
.02
.03
.04
.05Fixed InstantaneousOverride
10,0
00
.1
.01
20,0
00
.001
SECO
NDS
30,0
00
40,0
00
50,0
00
100,
000
InterruptingRatingDeterminesEnd ofCurve
NP6645C79H01
Short DelayPickup
In
In_Cat._Engaged
Remove
NP6635C68H07 Made in U.S.A.
Digitrip RMS 310
Cell No.
Digitrip RMS 310 Rating PlugFor Use in R Circuit Breaker Only
WestinghouseDigitalProtection
∑
FrameRatingAmperes(Max.)
Available Rating PlugsAmpereRating (In)
Type Short DelayPickup RangeAmperes
CatalogNumber
(Icu)
500V
4265
380-415V
065100
IEC 947-2220-240V
125200
600V
5065
480V
065100
UL/CSA240V
125200
RD, CRDRDC, CRDC
Circuit Breaker Time/Current Curves (Phase Current)
Series C® R-Frame Circuit BreakersEquipped With Type Digitrip RMS 310 Trip Units
Interrupting Ratings – 50/60 HzRMS Sym. Amperes (kA)
For 2500A styles, maximum short delay pickup setting = 6X.
For high fault current levels a fixed instantaneous override is provided at 17,500A(Tolerance ±15%).
The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.
For ground fault time-current curves see SC-5631-93.
Not UL/CSA Listed.
Utilization Category AIcs = 0.25 IcuUimp = 8 kV
Typical Trip Unit Nameplate
For use with Trip Unit Catalog Numbers
2000A Max.RES2000LSRES2000LSGRES2000LS
2500A Max.RES2500LSRES2500LSGRES2500LS
16001400125012001000800800, 1000, 1200, 1600800, 1000, 1250, 1600
2000160014001250120010001000, 1200, 1600, 20001000, 1250, 1600, 2000
250020001600125012001200, 1600, 2000, 25001250, 1600, 2000, 2500
FixedFixedFixedFixedFixedFixedAdj.Adj.
FixedFixedFixedFixedFixedFixedAdj.Adj.
FixedFixedFixedFixedFixedAdj.Adj.
16RES16T16RES14T16RES125T16RES12T16RES10T16RES08TA16RES16T1A16RES16T2
20RES20T20RES16T20RES14T20RES125T20RES12T20RES10TA20RES20T1A20RES20T2
25RES25T25RES20T25RES16T25RES125T�25RES12TA25RES25T1A25RES25T2�
3200-128002800-112002500-100002400-96002000-80001600-64001600-128001600-12800
4000-160003200-128002800-112002500-100002400-96002000-80002000-160002000-16000
5000-150004000-120003200-96002500-75002400-720024000-150002500-15000
1600
2000
2500
BreakerType
1600A Max.RES1600LSRES1600LSGRES1600LS
NotesCurve accuracy applies from –20°C to +55°C ambient. For possible ampere derating forambient above 40°C, refer to Cutler-Hammer.
Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No.STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991.
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
Proof 4 — October 19, 2015 11:49 AM
10 EATON www.eaton.com
Figure 7. Typical Instantaneous Time-Phase Current Characteristic Curve Based on In - Curve Number SC-5629-93, October 1997
AB DE-ION Circuit Breakers Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units Typical Instantaneous Time-Phase Current Characteristic Curve Based on In
6X
8X
4X
3X
2X
Standard FixedRating Plug
200 ms
100 ms
I
300 ms
5X
�
FrameRatingAmperes(Max.)
Available Rating PlugsAmpereRating (In)
Type Short DelayPickup RangeAmperes
CatalogNumber
(Icu)
500V
4265
380-415V
065100
IEC 947-2220-240V
125200
600V
5065
480V
065100
UL/CSA240V
125200
Short DelayPickup
In
Short DelayTime
Sec
NP6645C79H02
In_Cat._Engaged
Remove
NP6635C68H07 Made in U.S.A.
Digitrip RMS 310
Cell No.
Digitrip RMS 310 Rating PlugFor Use in R Circuit Breaker Only
WestinghouseDigitalProtection
�
Circuit Breaker Time/Current Curves (Phase Current) �
Series C® R-Frame Circuit BreakersEquipped With Type Digitrip RMS 310 Trip Units
Interrupting Ratings – 50/60 HzRMS Sym. Amperes (kA)
Utilization Category AIcs = 0.25 IcuUimp = 8 kV
Typical Trip Unit Nameplate
For use with Trip Unit Catalog Numbers
2000A Max.RES2000LSIRES2000LSIGRES2000LSI
2500A Max.RES2500LSIRES2500LSIGRES2500LSI
16001400125012001000800800, 1000, 1200, 1600800, 1000, 1250, 1600
2000160014001250120010001000, 1200, 1600, 20001000, 1250, 1600, 2000
250020001600125012001200, 1600, 2000, 25001250, 1600, 2000, 2500
FixedFixedFixedFixedFixedFixedAdj.Adj.
FixedFixedFixedFixedFixedFixedAdj.Adj.
FixedFixedFixedFixedFixedAdj.Adj.
16RS16T16RS14T16RS125T�16RS12T16RS10T16RS08TA16RS16T1A16RS16T2�
20RS20T20RS16T20RS14T20RS125T�20RS12T20RS10TA20RS20T1A20RS20T2�
25RES25T25RES20T25RES16T25RES125T�25RES12TA25RES25T1A25RES25T2�
3200-128002800-112002500-100002400-96002000-80001600-64001600-128001600-12800
4000-160003200-128002800-112002500-100002400-96002000-80002000-160002000-16000
5000-150004000-120003200-96002500-75002400-720024000-150002500-15000
1600
2000
2500
BreakerType
1600A Max.RES1600LSIRES1600LSIGRES1600LSI
TIM
E IN
SEC
ONDS
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1 HO
UR1
MIN
UTE
2 HO
URS
CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
.5
.5 201054321.8.6
1.8.6CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)
.7 .9 6 7 8 9
20105432 6 7 8 9
Short DelayPick UpSettings(Tolerance±10%)
Minimum TotalClearing Time
Maximum TotalClearing Time
.7 .9
.02
.03
.04
.05Fixed InstantaneousOverride �
InterruptingRatingDeterminesEnd ofCurve �
.1
.01
10,0
00
20,0
00
.001
SECO
NDS
CURRENT IN AMPS
30,0
00
40,0
00
50,0
00
100,
000
7X
�
200,
000
RD, CRDRDC, CRDC
For 2500A styles, maximum short delay pickup setting = 6X.For high fault current levels a fixed instantaneous override is provided at 17,500A(Tolerance ±15%).The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.For ground fault time-current curves see SC-5631-93.Not UL/CSA Listed.
��
�
��
NotesCurve accuracy applies from –20°C to +55°C ambient. For possible ampere derating forambient above 40°C, refer to Cutler-Hammer.
Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No.STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991.
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
Proof 4 — October 19, 2015 11:49 AM
11EATON www.eaton.com
Figure 8. Typical Long Delay/Short Delay Time-Phase Current Characteristic Curve Based on In - Curve Number SC-5630-93, October 1997
AB DE-ION Circuit Breakers Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units Typical Long Delay/Short Delay Time-Phase Current Characteristic Curve Based on In
1200
A.
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
TIME IN SECONDS
1,000
500
300
200
5,000
3,000
2,000
1 HO
UR
1 MIN
UT
E2 H
OU
RS
TIM
E IN
SEC
ONDS
10,000
100
50
30
20
10
5
3
2
1
.5
.3
.2
.1
.05
.03
.02
.01
.005
.003
.002
.001
1,000
500
300
200
5,000
3,000
2,000
1 H
OU
R1
MIN
UT
E2
HO
UR
S
100
8060 907050 1000
800
600
900
700
500
400
300
200
4000
3000
2000
4000
3000
2000
1000800
600
900
700
500
400
300
200
1008060 907050
CURRENT IN AMPERES
CURRENT IN AMPERES
10,000
600
A.
I
.15 SEC
Ground Fault PickupSettings(Tolerance ±10% Except,±20% on 200 A. Setting)
400
A.
200
A.
1000
A.
800
A.
.3 SEC
.5 SEC
NP6645C79H05
Short DelayPickup
In
In_Cat._Engaged
Remove
NP6635C68H07 Made in U.S.A.
Digitrip RMS 310
Cell No.
WestinghouseDigitalProtection
�
NP6645C79H06
In_Cat._Engaged
Remove
NP6635C68H07 Made in U.S.A.
Digitrip RMS 310
Cell No.
WestinghouseDigitalProtection
�
Gnd. FaultPickup
*
Gnd. FaultTime
Sec
Gnd.
Gnd. FaultPickup
*
Gnd. FaultTime
Sec
Gnd.
Short DelayPickup
In
Short DelayTime
Sec
*Gnd. Fault Pickup
A
BCDEFHK
200A
400A600A800A1000A1200A1200A1200A
SETTING CURRENT*Gnd. Fault Pickup
A
BCDEFHK
200A
400A600A800A1000A1200A1200A1200A
SETTING CURRENT
Digitrip RMS 310 Rating PlugFor Use in R Circuit Breaker Only
Digitrip RMS 310 Rating PlugFor Use in R Circuit Breaker Only
Circuit Breaker Time/Current Curves (Phase Current) �
Series C® R-Frame Circuit BreakersEquipped with Type Digitrip RMS 310 Trip Unitsfor Ground Fault Protection
For use with Trip Unit Catalog Numbers1600A Max.RES1600LSGRES1600LSIG
2000A Max.RES2000LSGRES2000LSIG
2500A Max.RES2500LSGRES2500LSIG
NotesCurve accuracy applies from –20°C to +55°C ambient.
Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2.For field testing using primary injection methods, follow NEMA publication AB-4-1991.
� For phase time-current curves see SC-5629-93 and SC-5630-93.
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
Proof 4 — October 19, 2015 11:49 AM
12 EATON www.eaton.com
Figure 9. Typical Ground Fault/Protection Time/Current Characteristic Curve Based on In - Curve Number SC-5631-93, October 1997
AB DE-ION Circuit Breakers Types RD, CRD, RDC, CRDC Equipped With Digitrip RMS 310 Trip Units Typical Ground Fault/Protection Time/Current Characteristic Curve Based on In
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
Proof 4 — October 19, 2015 11:49 AM
13EATON www.eaton.com
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
Proof 4 — October 19, 2015 11:49 AM
14 EATON www.eaton.com
Time Current Curves TD012030ENEffective September 2015
Series GR-Frame
Proof 4 — October 19, 2015 11:49 AM
15EATON www.eaton.com
Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton .com
© 2014 EatonAll Rights ReservedPrinted in USAPublication No . TD012030EN / KDCApril 2014
Eaton is a registered trademark .
All other trademarks are property of their respective owners .
Series GR-Frame
Time Current Curves TD012030ENEffective September 2015
Proof 4 — October 19, 2015 11:49 AM