Urban Acoustics
Disclaimer: This presentation was developed by a third party and is not funded by WoodWorks or the Softwood Lumber Board.
Steve(n) Thorburn, PE, LEED AP, CTS-I, CTS-D [email protected], TECHNOLOGY, AND LIGHTING DESIGNHORBURN ASSOCIATES
![Page 2: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/2.jpg)
“The Wood Products Council” is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES), Provider #G516.
Credit(s) earned on completion of this course will be reported to AIA CES for AIA members. Certificates of Completion for both AIA members and non-AIA members are available upon request.
This course is registered with AIA CESfor continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product.
______________________________
Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.
![Page 3: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/3.jpg)
As with any issue of building performance, the acoustics of a mixed-use wood-frame
structure can be designed to meet or far exceed minimal requirements. It is the
responsibility of the design team to determine acoustical expectations for the project and
meet them within the available budget.
Through the use of case studies, this fast-paced, interactive session will explore how multi-
story wood systems can be used to meet acoustical privacy goals. Discussion will focus on
the detailing and construction of units, and how consideration of the construction process
can help keep acoustical costs down.
With the objective of providing implementable solutions, the session will include
construction details and photos showing what has and hasn’t worked in actual buildings.
Steve(n) Thorburn, PE, LEED AP, CTS-I, CTS-D, Thorburn [email protected]
Urban Acoustics – Course Description
![Page 4: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/4.jpg)
At the end of this program, participants will be able to:
- Evaluate the acoustical impact of ICC Building Code vs. Residential Expectations
- Develop cost effective / acoustically centric space planning ideas for wood frame design
- Produce practical and constructible acoustical isolation detailing for wood frame design
- Identify common acoustical compromises during construction
![Page 5: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/5.jpg)
Copyright Materials
This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written permission of the speaker is
prohibited.
© Thorburn Associates Inc.
![Page 6: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/6.jpg)
![Page 7: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/7.jpg)
![Page 8: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/8.jpg)
![Page 9: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/9.jpg)
![Page 10: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/10.jpg)
Mixed Use
![Page 11: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/11.jpg)
![Page 12: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/12.jpg)
Urban AcousticsThe Building Code
![Page 13: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/13.jpg)
Our Goal Control the Transfer of Noise!
![Page 14: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/14.jpg)
Slide 16
Acoustical Expectations
Luxury? Market Rate? Entry Level?
![Page 15: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/15.jpg)
Entry Level HousingSTC 50 / IIC 50 (STC /IIC 48)*
Market Rate HousingSTC 55 / IIC 55 (STC/IIC 52)*
Luxury Rate HousingSTC 60+ / IIC 60+ (STC/IIC 55)*
IIC 60+ very hard to achieve with wood or tile surfaces
* Actual 1962 values – adjust when IBC set “50” as minimum
FHA Rules of Thumb from 1962NOTE THIS IS NOT A CODE, IT HAS BECOME the DE FACTO STANDARD BUT NOT CODE
![Page 16: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/16.jpg)
ICC G2 2010 Guideline for Acoustics
Acceptable Performance“Grade B Performance”
55 / 52(Laboratory / Field)
Airborne - STC / NNICImpact - IIC / NISR
Preferred Performance“Grade A Performance”
60 / 57 (Laboratory / Field)
Airborne - STC / NNICImpact - IIC / NISR
STILL NOT A CODE, IT IS FROM THE ICC –FROM WHAT APPEARS TO BE A RESEARCH PAPER FROM THE INTERNET!
![Page 17: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/17.jpg)
Exterior to Interior
![Page 18: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/18.jpg)
Land Use Compatibility For Community Noise
Exterior Day/Night Noise Levels (Ldn, dBA)Land Use Category
Single Family
Multi Family
Motel, Hotels
Outside Use
55 60 65 70 75 80
NormallyAcceptable
ConditionallyAcceptable
NormallyUnacceptable
ClearlyUnacceptable
![Page 19: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/19.jpg)
Mixed Use – Bar to Housing
![Page 20: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/20.jpg)
Not Addressed by Building Code- Implied at 45 dBA /Ldn
(Interior Noise Criterion)- Enforced as Nuisance Complaints- Enforced by “Local Codes”
THIS IS CHANGING – THE IgCC IS PLACING LIMITS ON
COMMERCIAL TO RESIDENTIAL
Commercial to Residential
![Page 21: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/21.jpg)
Urban Acoustics Vocabulary
![Page 22: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/22.jpg)
Terms (They Are Changing!)
SoundSTCFSTC NIC
ASTCNNIC
ImpactIIC
FIICAIICNISR
GeneralNRdBALdn
CNELOITC
NC NRC
![Page 23: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/23.jpg)
Urban Acoustics - Vocabulary
![Page 24: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/24.jpg)
Acoustical Test Laboratory
![Page 25: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/25.jpg)
Acoustical Test Chamber
![Page 26: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/26.jpg)
STC vs ASTC (NIC, FSTC)
STC Testing ASTC Testing
![Page 27: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/27.jpg)
IIC vs AIIC (FIIC)
IIC Testing AIIC Testing
![Page 28: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/28.jpg)
How STC or IIC Rating Is Found
7 8 10 9 86 4 3
3
2
GOAL STC 50
MEASURED
![Page 29: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/29.jpg)
How STC or IIC Rating Is Found
6 7 9 8 75 3 2
2
1
NOW STC 49
MEASURED
![Page 30: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/30.jpg)
How STC or IIC Rating Is Found
5 6 8 7 64 2 1
1
NOW STC 48
MEASURED
![Page 31: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/31.jpg)
How STC or IIC Rating Is Found
4 5 7 6 5 3 1
NOW STC 47
MEASURED
![Page 32: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/32.jpg)
Acoustical Detailing is Systems
![Page 33: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/33.jpg)
Urban Acoustics Acoustical
Wall Systems
![Page 34: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/34.jpg)
Acoustical Detailing – The Givens• Walls are Full Height
(Deck to Deck)• Insulated (Unfaced Batt)
In all Stud or Joist Cavities• Sealed Air Tight• Floor Sheeting
Is Glued and Screwed
![Page 35: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/35.jpg)
Wall Progression – Sound Isolation
STC 34 STC 38 STC 45
![Page 36: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/36.jpg)
Wall Progression – Sound Isolation
STC 50 STC 63 STC 49
![Page 37: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/37.jpg)
Metal Channels
Hat ChannelsAre Not
Acoustical Channels
Resilient ChannelsAre
Acoustical Channels
![Page 38: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/38.jpg)
Slide 40
![Page 39: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/39.jpg)
Hat Channel Resilient Isolators
![Page 40: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/40.jpg)
Hat Channel Resilient Isolators
![Page 41: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/41.jpg)
Lot Line Wall – Sound Isolation
![Page 42: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/42.jpg)
Urban AcousticsAcoustical
Floor / Ceiling SystemsSound and Impact
![Page 43: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/43.jpg)
Floor Systems
STC 37
![Page 44: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/44.jpg)
Floor Systems
STC 43
![Page 45: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/45.jpg)
Floor Systems
STC 49
![Page 46: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/46.jpg)
Floor Systems – Topping Slab
Gypcreteor
Light Weigh Concrete
![Page 47: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/47.jpg)
Floor Systems
STC 56
![Page 48: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/48.jpg)
Floor Systems
STC 62
![Page 49: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/49.jpg)
Floor Systems
Batt insulation not show for clarity
![Page 50: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/50.jpg)
Floor Systems
Batt insulation not show for clarity
![Page 51: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/51.jpg)
Floor Systems
Batt insulation not show for clarity
![Page 52: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/52.jpg)
Floor Systems
Batt insulation not show for clarity
![Page 53: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/53.jpg)
Independently Framed Ceiling System
![Page 54: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/54.jpg)
Impact Noise
![Page 55: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/55.jpg)
The Tapper
![Page 56: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/56.jpg)
The Tapper
![Page 57: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/57.jpg)
Impact Isolation
• Impact noise changes as it travels in the building.• Impact noise is best controlled at the source.
![Page 58: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/58.jpg)
Effects of Floor Covering on Impact Isolation
Batt insulation not show for clarity
IIC 73 IIC 64 IIC 56 IIC 43 IIC 32
STC 56
![Page 59: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/59.jpg)
Cross-Laminated Timber
70+
![Page 60: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/60.jpg)
Cross-Laminated Timber
70+
ACOUSTICALLY STILL REALLY NEW
We Need More Test Data
In absence of test data we compare to known acoustical systems
![Page 61: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/61.jpg)
Cross-Laminated Timber
"Volume generally assumed for the density of hardened concrete is
150 lb./ft3. (2400 kg/m3)“
McGraw-Hill Encyclopedia of Science and
Technology.
![Page 62: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/62.jpg)
Cross-Laminated Timber
6 inch thick 20 lb./ft3. CLTSame Mass as
1.6 inch thick Concrete
Based on AcousticsMass Law STC Rating
about 38 STC
![Page 63: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/63.jpg)
Cross-Laminated Timber
![Page 64: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/64.jpg)
Cross-Laminated Timber
70+ IIC 35
![Page 65: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/65.jpg)
Urban Acoustics Leaks - Doors and Windows
![Page 66: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/66.jpg)
Slide 68
Leaks: Where air can flow... ...so will sound.
![Page 67: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/67.jpg)
Air Tight Seal
![Page 68: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/68.jpg)
Batt Insulation
![Page 69: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/69.jpg)
Blow In Insulation
OPEN CELL FOAMCLOSED CELL FOAMCELLULOUS / FIBER
![Page 70: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/70.jpg)
Rigid “Foam” Insulation
![Page 71: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/71.jpg)
Urban Acoustics Other Issues to Consider
![Page 72: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/72.jpg)
Acoustical Fiction!• Fiber Board
![Page 73: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/73.jpg)
Acoustical Fiction!• Trapped Channel
![Page 74: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/74.jpg)
Trapped Air Space and Screws
STC 55
STC 38
![Page 75: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/75.jpg)
Installation Issues - RC
![Page 76: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/76.jpg)
Plumbing Isolation
![Page 77: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/77.jpg)
Other Noise Issues
![Page 78: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/78.jpg)
Condominium Noise
![Page 79: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/79.jpg)
Now We See the Problem
![Page 80: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/80.jpg)
Installation Issues - RC
![Page 81: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/81.jpg)
Installation Issues - RC
![Page 82: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/82.jpg)
Slide 84
![Page 83: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/83.jpg)
Slide 85
![Page 84: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/84.jpg)
Sprinkler Lines / Heads
![Page 85: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/85.jpg)
![Page 86: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/86.jpg)
RESILIENT CEILING SYSTEMS
![Page 87: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/87.jpg)
Duct Work
![Page 88: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/88.jpg)
HOLES IN SYSTEMS
![Page 89: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/89.jpg)
Recessed Light Fixtures
![Page 90: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/90.jpg)
RESILIENT CHANNELS INSTALLATION
![Page 91: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/91.jpg)
Framing Issues
![Page 92: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/92.jpg)
Framing Issues … (ok Plumbing)
![Page 93: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/93.jpg)
ACOUSTICAL GYPSUM BOARD
![Page 94: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/94.jpg)
DAMPING
![Page 95: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/95.jpg)
OMG!
THIS IS VERYBAD! DO NOTBELIEVE THE INTERNET!
![Page 96: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/96.jpg)
OMG!
THIS IS VERYBAD! DO NOTBELIEVE THE INTERNET!
![Page 97: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/97.jpg)
OMG!
![Page 98: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/98.jpg)
When it comes to AcousticsOnly Believe Real Laboratory
Test Data or Someone you Pay and can Sue!
![Page 99: THORBURN - Urban Acoustics - 2018 01 29 · 2018-12-17 · Urban Acoustics Disclaimer: ... * Actual 1962 values –adjust when IBC set “50” as minimum FHA Rules of Thumb from 1962](https://reader033.vdocuments.us/reader033/viewer/2022060304/5f0901fe7e708231d424c95b/html5/thumbnails/99.jpg)
This concludes The American Institute of Architects Continuing Education Systems Course
QUESTIONS?
Steve(n) Thorburn, PE, LEED AP