SmartStruxure™ Lite Solution
Course SmartStruxure Lite IntroductionHOW ALL FITS TOGETHER
PPT ver. 1.1.0.0
Schneider Electric 2- SmartStruxure™ Lite solution Training
Monitor
BACnet points collected by the monitor
http
Cost effective solution for small-to-medium buildings
StruxureWare Building Expert (in web browser)Allows to configure and monitor your deployment.
IP/Ethernet network design
Stand-alone deployment, everything goes through the monitor
Ethernet LAN
Passive nodes
LAN
(A monitor is needed if more then 1 MPM in the network and if a network functionality is required)
Schneider Electric 3- SmartStruxure™ Lite solution Training
Ethernet LAN BACnet points collected by the BMS directly
BACnet IP /BACnet Ethernet
Schneider Electric or third-party BACnet Building Management System (BMS)
Passive nodes
LAN
IP/Ethernet network design (cont’d)
Integration to BACnet systemNo need for a monitor if all nodes are connected through IP
Schneider Electric 4- SmartStruxure™ Lite solution Training
●Guidelines – network traffic only● CANBus, Ethernet, ZigBee: ● Ratio of 24 passive nodes to 1 monitor node
Monitor
Ethernet LANor
CANbusor
ZigBee
Group A
Monitor Monitor
Group B Group C
BMS
General network design
LAN
Up to 24 nodes per group
Schneider Electric 5- SmartStruxure™ Lite solution Training
Ethernet
LAN
Monitor
Network discoveryStruxureWare Building Expert(in web browser)
Monitor send a heartbeat request
By the network discover y command and every 10 minutes
Schneider Electric 6- SmartStruxure™ Lite solution Training
Passive nodes
Remote database download
End-devices
LAN
StruxureWare Building Expert(in web browser)
Ethernet
Network discovery (continued)
Monitor
The Monitor plays a significant role both for monitoring and for networking
Schneider Electric 7- SmartStruxure™ Lite solution Training
Property Casts sent on change of value (COV) 30 seconds by default.
22.8 °C23.0 °C
Normal operation – COV based
Passive nodes
LAN
StruxureWare Building Expert(in web browser)
Ethernet
Monitor
Schneider Electric 8- SmartStruxure™ Lite solution Training
●120 Ohms resistors must be placed at both termination points of the CANbus chain link.
●CANbus transfer rate is proportional to total chain-link length.
● 125 Kbps: Up to 500 m● 250 kbps: Up to 250 m (default setting)● 500 kbps: Up to 100 m● Must be the same speed configuration for all
MPMs
BMS
Monitor passive nodes
CANbus network design
LAN
Schneider Electric 9- SmartStruxure™ Lite solution Training
● ZigBee coordinator is a device that sets up the network, is aware of all the nodes within its network. Every ZigBee network must contain a network coordinator.
● ZigBee router can act as an intermediate router, passing on data from other devices.
MonitorRouter nodes
End-devices
Coordinator
ZigBee concepts
BMS
LAN
Schneider Electric 10- SmartStruxure™ Lite solution Training
●Route redundancy●Ideally no more than 5 wireless hops●Example respecting guidelines
Site Monitor
Router / Passive nodes
Coordinator
BMS
LAN
Building Expert
ZigBee network design – best practices
Schneider Electric 11- SmartStruxure™ Lite solution Training
●No Route redundancy●Example not respecting guidelines
Monitor
Passive nodes
Coordinator
BMS
LAN
Building Expert
BAD wireless network design
Passive nodes
& Routers& Routers
Schneider Electric 12- SmartStruxure™ Lite solution Training
●Possible if the Monitor is the originating point of each technology segment.
BMS
Monitor
Passive nodes
Web browser
Coordinator
ZigBee
Ethernet
CANBus
Passive nodes
Passive nodes
LAN
Using multiple network technology
Caution!This is a theoretical and principal schematic.
Other
Get started
Application package
Schneider Electric 14- SmartStruxure™ Lite solution Training
Schneider Electric 15- SmartStruxure™ Lite solution Training
Uses cases
Schools
Hotels
Schneider Electric 17- SmartStruxure™ Lite solution Training
Water based heating systems● Perimeter heating with radiators● Perimeter heating with fan coils
School schedules● Can’t disturb classes● Can’t afford overtime pay
Out-buildings
Hazards in the walls● Dust or asbestos fears
Tight budget● Fixed costs of front-end, servers
and gateways limiting the ROI?
Proven solution● Smart wireless actuator● Wireless room and terminal controllers
Wireless retrofit during school days● Limit wiring to a minimum● Limit invasiveness and disturbance
Bring them in wirelessly with ZigBee
Avoid renovation, repair & repaint work● Keep parents and administrators happy
StruxureWare™ Building Expert● No license fee! Low fixed costs!● Scalable to StruxureWare™ Building
Operation, BACnet, EcoStruxure Web Services, oBIX
School NeedsSmartStruxure™ Lite answers
Schneider Electric 18- SmartStruxure™ Lite solution Training
Perimeter heating school retrofit jobProblem● Single loop perimeter heating● Comfort & energy cost issues
Objectives● Add zone & remote control● With a short payback
Solution● Managers
● Network throughout the building● Control actuators● Receive data from sensors● Host Building Expert over the LAN
● Smart wireless actuators
● EnOcean T° sensors
● Management via Building Expert
Boiler
LAN
Schneider Electric 19- SmartStruxure™ Lite solution Training
Unit ventilator/fan coil school retrofit jobWireless manager(one unit can manage many zones)
If there are no old stats or existing wiring isn’t usable, place SEC-TE inside unit
Swap old stat with SE7000
Network to other zones Light relay
with dimming
Light sensor and light switch
LAN
Building Expert
Unit ventilator or fan coil
Schneider Electric 20- SmartStruxure™ Lite solution Training
Out-buildings & school trailersSchools run out of space and use out-buildings to fill gap● Integrating these buildings into an automation system is difficult & costly● SmartStruxure™ Lite can integrate them easily and at a low cost● Manage multiple buildings from StruxureWare Building Expert or use larger
systems
Up to 300 m line of sight
StruxureWare™Building Expert
EcoStruxureWebService
internet
internet
Schneider Electric 21- SmartStruxure™ Lite solution Training
Use case: simple & complete automationObjectives: happy guests & bottom line● Control heating and cooling costs
● Get your guests in the comfort zone
● Remote management for more efficiency
Solution● SE7000 to control HVAC in each room
● Embedded PIR motion sensor (optional) sets temperature for occupied/unoccupied mode
● Guests can adjust setpoints for comfort
● Networking and integration performed by MPM devices each handling several zones
● Management can set high and low limits according to schedules
● Management can put rooms into vacant mode for maximum energy savings
Room 205
Room 207
Room 209
Room 211
Room 204
Room 206
Room 208
Room 210
MPM-GW
SE7000
FC, HP
Schneider Electric 22- SmartStruxure™ Lite solution Training
Room 205
Use case: simple & complete automation
Solution (cont’d)● Management via StruxureWare™
Building Expert
● Can import hotel floorplans and define custom zones with color codes for user-friendly visualizations
Scale over time with wireless● Easily add points with EnOcean and
ZigBee
● Lighting control
● Additional sensors
● Other applications
● Can integrate wireless keycard reader to set occupied/unoccupied mode
Light relay
Keycard reader
Schneider Electric 23- SmartStruxure™ Lite solution Training
Use case: comfort, efficency & branding
Swap old stat with SE8000
PIR motion sensor included
my Hotel
Create loyalty with your brandCustomizable cover, color, language and screensaver
Direct integration to BACnet
Fan coil, heat pump or other system
Or integration via MPM devices
StruxureWare Building Expert for small hotels and motels. Integrate to other systems for larger buildings.
Use relay pack for high voltage fan coils
LAN
300 ft
200 ft
● Small retail outlet● 4 zones - HVAC● Monitoring only
Example scenario 1
300 ft
200 ft
● A few SE7000● One MPM connected to the LAN● Management with StruxureWare
Building Expert
Example scenario 1
LAN
Example scenario 2
300 ft
200 ft
● Small retail outlet● 5 zones - Lighting● Monitoring and Override
Example scenario 2
200 ft
● Two MPM-GW communicating via ZigBee● Control of multiple EnOcean switches and relays● Management with Building Expert
300 ft
LAN
ZigBee RouterPassive
ZigBee CoordinatorSite MonitorConnected to LAN
Example scenario 3
300 ft
200 ft
● Small retail outlet● 5 zones - Lighting● Monitoring and Override● Energy Metering
Example scenario 3● Add MPM-UN with Modbus
to connect power meter
LAN
ZigBee RouterPassive
ZigBee RouterPassive
ZigBee CoordinatorSite MonitorConnected to LAN
Modbus power meter
Schneider Electric 30- SmartStruxure™ Lite solution Training
Application:
Hotel room,Dorm room,Old age unitorHospital room
FancoilUnit
Room 101
SmartStruxure LiteMonitoring & Control Solution
Window Sensor
ThermostatDoor
Sensor
Floor / HotelController
Web-pages for simple monitoring
& control
SmartStruxure SolutionFull Building Management System
AutomationServer
SmartStruxureEntreprise Server
or
SmartStruxureBuilding Operation
Schneider Electric 31- SmartStruxure™ Lite solution Training
VAV applications
VAV managers(MPM-VA)
Terminal controllers(if direct control of RTUs is needed)
Building Expert
MPM device
If requiredAdditional wired and wireless sensors for
T°, H%, motion, CO2, etc.
Each VAV manager has:• Embedded pressure sensor• 6 inputs and 6 outputs• EnOcean wireless I/O• Support for ZigBee peripherals
RTU or other HVAC equipment
Zoning
HVACAggregation & management
VAV boxes
Use VAV managers● Each unit has:
● Pressure sensor● Actuator (optional)
● Wireless networking ● Makes installation
faster and easier
●Building Expert● Has a PID loop
object to help manage VAVs.
● Programming is stored locally on each VAV manager for redundancy.
Schneider Electric 32- SmartStruxure™ Lite solution Training
Metering and Sub-metering
For electrical, gas & water metering● Multi-purpose managers can integrate
Modbus, EnOcean and ZigBee metering and pulse-counting devices
● Building Expert has objects to facilitate the integration of select Schneider Electric and Veris products. Currently, these products are:
● ION6200● PM750● Veris E5 series● Veris H803 series● iEM3250/5● PM3250/5
● Data can be:● Viewed in Building Expert● Integrated into larger iBMS● Exported over FTP
Building Expert
MPM-UN
Metering
Schneider Electric and Veris meters with objects in Building Expert to facilitate their integration.
Other Modbus meters.
You can network to reach metering points separated by long distances
Pulse counting and smart plugs
Terminal controllers can be used for fast pulse counting
MPM-UN can integrate various devices using Modbus, EnOcean and ZigBee protocols
Schneider Electric 33- SmartStruxure™ Lite solution Training
Basic and advanced lightingOffice single load, common areas and outdoor lighting
Wired and/or wireless lighting control● For wired and wireless
control, use the MPM-UN● For wireless control only,
use the MPM-GW
Building Expert and EnOcean● Objects to facilitate the
integration of light switches and relays already exist.
● New objects are coming up for the following sensors: motion, light (lux), door contact and window contact
Building Expert
MPM-UN
Basic lighting Daylight harvesting
Connection to Modbus lighting
panel or wired contacts
Relay
Switch
Occupancy sensor
Light sensor
Dimmingrelay
Relays for motorized
blinds & smart windows
MPM-GW
Schneider Electric 34- SmartStruxure™ Lite solution Training
●StruxureWare Building Expert is a complete building automation IP
interface available from any internet connection.
●The Web server is active on every Manager (MPM).
●No license, no software to install
●Used to monitor and commission your network
●Supported browser: Firefox ESR
●From version 2.7 are the most
common browsers supported
●Local port : 80
StruxureWare™ Building Expert
Schneider Electric 35- SmartStruxure™ Lite solution Training
Resources for you
●Product Support Services (PPS) – After an approved certification test●The Schneider Electric Exchange Download Center
● (https://buildingsdownloads.schneider-electric.com)
●Documentation.SmartStruxureLite.com● Still valid but the above download center is the recommended solution