POWER & WIRING CABLES
Single Core PVC 6491X...................................................1:2Single Core PVC/PVC 6181Y 300/500V..........................1:4Flat Twin & Flat Three Core PVC 6242/3Y..................... 1:6Single Core PVC/PVC 6181Y 600/1000V........................1:8Single Phase Straight Concentric 600/1000V............... 1:10Single Phase Split Concentric 600/1000V..................... 1:12Three Phase Straight Concentric 600/1000V.................1:14PVC/PVC/SWA/PVC BS6346...........................................1:16PVC/PVC/SWA/PVC ESI 09-6 Control Cable................. 1:20Single Core XLPE/PVC BS7889......................................1:22Single Core XLPE/PVC/AWA/PVC BS5467....................1:24Multicore XLPE/PVC BS5467..........................................1:26Multicore XLPE/PVC/SWA/PVC BS5467........................1:30Single Core LSF 6491B................................................... 1:34Single Core XLPE/LSF/AWA/LSF BS6724.....................1:36Multicore XLPE/LSF/SWA/LSF BS6724......................... 1:38Three Core XLPE/LSF/SWA/LSF 6.35/11kV...................1:42FP200 Fire Resistant Cable............................................ 1:44FP200 Gold Fire Resistant Cable................................... 1:46FireTuf Fire Resistant Cable...........................................1:48Fire Resistant Armoured Power Cable BS7846............1:50Single Core XLPE/PVC BS6622......................................1:54Single Core XLPE/PVC/AWA/PVC BS6622....................1:56Three Core XLPE/PVC BS6622.......................................1:58Three Core XLPE/PVC/SWA/PVC BS6622.....................1:60Three Core PILC/SWA/PVC BS6480...............................1:62Three Core PICAS/PVC 6350/11000V ESI 09-12............1:64XLPE/LC/PVC/SWA/PVC EEMUA 133............................ 1:662/3.3/5 kV PE/PVC Airfield Lighting Cable M&E 42.......1:70XLPE Power Cable for 400Hz Supply.............................1:72Three Core Screened Type MCCMK SFS4880.............. 1:74XVB-F2 Multicore PowerCable....................................... 1:76Multicore XLPE/LSF 600/1000V IEC60502.....................1:78Technical Specifications.................................................1:80
CONTENTS
1:2
POWER & WIRING CABLES
A P P L I C A T I O N S P E C I F I C A T I O N S
Single Core PVC 6491X450/750 Volts
PVC insulated only cable for fixed
wiring purposes.
Used in trunking or conduit, or may be
surface mounted when used for
earthing.
• In accordance with BS6004 and
Cenelec.
Harmonised codes -
H07V-U (solid conductor)
H07V-R (stranded conductor)
• Conductors: Solid Class 1 or
Stranded Class 2 copper conductors
to BS6360.
• Insulation: PVC Insulation Type TI.1
to BS7655.
• Flame retardant to BS4066 Part 1.
• Normal colours available:
green/yellow, blue, black, brown,
yellow, grey, orange, pink, red,
turquoise, violet and white.
• Temp Rating: 700C max conductor
operating temperature.
• Voltage Rating: 450/750 volts.
®
1
Anixter Cenelec Nominal Conductor Insulation Max Approx Min BendingPart No. Code Conductor Class Thickness O/D Weight Radius
Area (fixed bend)mm2 mm mm kg/km mm
A3-A01-0015 H07V-U1 1.5 1 0.7 3.2 21 10
A3-A07-0015 H07V-R1 1.5 2 0.7 3.3 23 11
A3-A01-0025 H07V-U1 2.5 1 0.8 3.9 33 12
A3-A77-0025 H07V-R1 2.5 2 0.8 4.0 35 13
A3-A07-0004 H07V-R1 4 2 0.8 4.6 51 15
A3-A07-0006 H07V-R1 6 2 0.8 5.2 71 17
A3-A07-0010 H07V-R1 10 2 1.0 6.7 120 21
A3-A07-0016 H07V-R1 16 2 1.0 7.8 180 25
A3-A07-0025 H07V-R1 25 2 1.2 9.7 285 30
A3-A07-0035 H07V-R1 35 2 1.2 10.9 380 50
A3-A19-0050 H07V-R1 50 2 1.4 12.8 510 60
A3-A19-0070 H07V-R1 70 2 1.4 14.6 720 60
A3-A19-0095 H07V-R1 95 2 1.6 17.1 990 70
A3-A37-0120 H07V-R1 120 2 1.6 18.8 1230 80
A3-A37-0150 H07V-R1 150 2 1.8 20.9 1510 90
A3-A37-0185 H07V-R1 185 2 2.0 23.3 1900 100
A3-A61-0240 H07V-R1 240 2 2.2 26.6 2490 160
A3-A61-0300 H07V-R1 300 2 2.4 29.6 3100 180
A3-A61-0400 H07V-R1 400 2 2.6 33.2 3950 210
A3-A61-0500* A07V-R1 500 2 2.8 36.9 4950 230
A3-A12-0630* A07V-R1 630 2 2.8 41.1 6300 250
1:3
POWER & WIRING CABLES
®
* National TypeAll dimensions are nominal unless otherwise stated.For further technical information see page 1:80.For conductor short-circuit ratings see page 13:28.
1
1:4
POWER & WIRING CABLES
A P P L I C A T I O N S P E C I F I C A T I O N S
Single Core PVC/PVC 6181Y300/500 Volts
PVC insulated and sheathed cable for
fixed wiring purposes. Not suitable for
direct burial.
• In accordance with BS6004.
• Conductors: Solid Class 1 or stranded
Class 2 copper conductors to BS6360.
• Insulation: PVC insulation Type TI.1
to BS7655.
• Sheath: PVC sheath Type 6 to
BS7655.
• Flame retardant to BS4066 Part 1.
• Normal colours available.
(See 6491X page1:2)
• Temp Rating: 70oC max conductor
operating temperature.
• Voltage Rating: 300/500 volts.
®
1
POWER & WIRING CABLES
®
Anixter Nominal Conductor Insulation Min Max Approx Min BendingPart No. Conductor Class Thickness O/D O/D Weight Radius
Area (fixed bend)mm2 mm mm mm kg/km mm
A3-C01-0010 1.0 1 0.6 3.8 4.5 28 14
A3-C01-0015 1.5 1 0.7 4.2 4.9 34 15
A3-C01-0025 2.5 1 0.8 4.8 5.8 49 18
A3-C07-0004 4 2 0.8 5.4 6.8 75 21
A3-C07-0006 6 2 0.8 6.0 7.4 99 23
A3-C07-0010 10 2 1.0 7.2 8.8 155 27
A3-C07-0016 16 2 1.0 8.4 10.5 225 50
A3-C07-0025 25 2 1.2 10.0 12.5 340 50
A3-C07-0035 35 2 1.2 11.0 13.5 450 60
Sizes above 35mm2, are covered in BS6346.For further technical information see page 1:80.For conductor short-circuit ratings see page 13:28.
1:5
1
1:6
POWER & WIRING CABLES
A P P L I C A T I O N S P E C I F I C A T I O N S
Flat Twin & Flat Three Core PVC 6242Y & 6243Y Insulated & sheathed with uninsulated circuit protective conductor asoption.
PVC insulated and sheathed cable for
installation clipped to flat surfaces, or
embedded in plaster, etc.
For domestic and industrial wiring.
• In accordance with BS6004.
• Conductors: Solid Class 1 (up to
2.5mm2) and stranded Class 2 (above
2.5mm2) copper conductors to BS6360.
• Insulation: PVC insulation Type TI.1
to BS7655.
• Core identification:
2 core - red, black.
3 core - red, yellow, blue.
• PVC sheath Type 6 to BS7655.
• Position of protective conductor:
Twin - centrally placed between red
and black cores.
Three core - centrally placed between
yellow and blue cores.
• Flame retardant to BS4066 Part 1.
• Temp. Rating: 700C max conductor
operating temperature.
• Voltage Rating: 300/500V.
®
1
1:7
POWER & WIRING CABLES
®
Anixter Nominal Conductor Insulation Min Max Approx Min BendingPart No. Conductor Class Thickness O/D O/D Weight Radius
Area (fixed bend)mm2 mm mm mm kg/km mm
6192Y - Flat Twin
A3-D01-0010 1.0 1 0.6 4.0 x 6.2 4.7 x 7.4 54 23
A3-D01-0015 1.5 1 0.7 4.4 x 7.0 5.4 x 8.4 70 26
A3-D01-0025 2.5 1 0.8 5.2 x 8.4 6.2 x 9.8 105 30
A3-D07-0004 4 2 0.8 5.6 x 9.6 7.2 x 11.5 150 50
A3-D07-0006 6 2 0.8 6.4 x 10.5 8.0 x 13.0 205 60
A3-D07-0010 10 2 1.0 7.8 x 13.0 9.6 x 16.0 325 70
A3-D07-0016 16 2 1.0 9.0 x 15.5 11.0 x 18.5 465 80
6193Y - Flat Three Core
A3-D01-0310 1.0 1 0.6 4.0 x 8.4 4.7 x 9.8 77 30
A3-D01-0315 1.5 1 0.7 4.4 x 9.8 5.4 x 11.5 100 50
A3-D01-0325 2.5 1 0.8 5.2 x 11.5 6.2 x 13.5 150 60
A3-D07-0034 4 2 0.8 5.8 x 13.5 7.4 x 16.5 230 70
A3-D07-0036 6 2 0.8 6.4 x 15.0 8.0 x 18.0 300 80
A3-D07-0310 10 2 1.0 7.8 x 19.0 9.6 x 22.5 480 90
A3-D07-0316 16 2 1.0 9.0 x 22.0 11.0 x 26.5 700 160
For further technical information see page 1:84For conductor short-circuit ratings see page 13:28.
Nominal Insulation Min Max Nom Earth Approx Min BendingAnixter Conductor Conductor Thickness O/D O/D Conductor Weight RadiusPart No. Area Class Area (fixed bend)
mm2 mm mm mm mm2 kg/km mm
6242Y - Flat Twin + Earth
A3-D01-2110 1.0 1 0.6 4 x 7.2 4.7 x 8.6 1.0 69 26
A3-D01-2150 1.5 1 0.7 4.4 x 8.2 5.4 x9.6 1.0 85 29
A3-D01-2250 2.5 1 0.8 5.2 x 9.8 6.2 x11.5 1.5 120 50
A3-D07-2400 4 2 0.8 5.6 x10.5 7.2 x13 1.5 120 60
A3-D07-2600 6 2 0.8 6.4 x12.5 8.0 x15 2.5 240 60
A3-D07-2100 10 2 1.0 7.8 x15.5 9.6 x19 4 390 80
A3-D07-2160 16 2 1.0 9 x18 11 x 22.5 6 560 90
6243Y - Flat Three Core + Earth
A3-D01-3100 1.0 1 0.6 4.0 x 9.6 4.7 x11 1.0 92 50
A3-D01-3150 1.5 1 0.7 4.4 x10.5 5.4 x12.5 1.0 115 50
A3-D01-3250 2.5 1 0.8 5.2 x12.5 6.2 x14.5 1.0 170 60
A3-D07-3400 4 2 0.8 5.8 x14.5 7.4 x18 1.5 255 80
A3-D07-3600 6 2 0.8 6.4 x16.5 8 x 20 2.5 340 80
A3-D07-3100 10 2 1.0 7.8 x 21.0 9.6 x 25.5 4 550 160
A3-D07-3160 16 2 1.0 9 x 24.5 11 x 29.5 6 790 180
1
1:8
POWER & WIRING CABLES1
A P P L I C A T I O N S P E C I F I C A T I O N S
Single Core PVC/PVC 6181Y600/1000 Volts
PVC-insulated and sheathed cable for
fixed installations.
Not suitable for direct burial.
• In accordance with BS6346.
• Conductors: Stranded Class 2
copper conductors to BS6360.
• Insulation: PVC insulation Type TI.1
to BS7655.
• Sheath: PVC sheath Type TM.1 to
BS7655.
• Flame retardant to BS4066 Part 1.
• Normal colours available.
(See 6491X page1:2)
• Temp Rating: 70oC max conductor
operating temperature.
• Voltage Rating: 600/1000 volts.
®
1:9
1POWER & WIRING CABLES
®
Anixter Nominal Insulation Nom Approx Min BendingPart No. Conductor Thickness O/D Weight Radius
Area (fixed bend)mm2 mm mm kg/km mm
A2-Q01-1050 50 1.4 15.1 600 70
A2-Q01-1070 70 1.4 16.9 810 70
A2-Q01-1095 95 1.6 19.4 1110 80
A2-Q01-1012 120 1.6 21.0 1350 90
A2-Q01-1015 150 1.8 23.2 1650 100
A2-Q01-1018 185 2.0 25.8 2060 160
A2-Q01-1024 240 2.2 29.0 2670 180
A2-Q01-1030 300 2.4 32.1 3320 200
A2-Q01-1040 400 2.6 35.8 4190 220
A2-Q01-1500 500 2.8 39.6 5230 240
A2-Q01-1063 630 2.8 43.8 6630 270
A2-Q01-1080 800 2.8 48.3 8330 290
A2-Q01-1001 1000 3.0 53.7 10440 330
All dimensions are nominal unless otherwise stated.
For further technical information see page 1:80.For conductor short-circuit ratings see page 13:28.For XLPE/PVC type to BS7889 see page 1:22.
1:10
POWER & WIRING CABLES1
®
Single Phase Straight ConcentricPCU/PVC/Straight Concentric/PVC 600/1000 Volts 700C
Single phase concentric cable, for
household and street lighting services.
Incorporates CNE (Combined Neutral
and Earth) to meet the requirements of
PME (Protective Multiple Earthing) in
various distribution systems.
Suitable for direct burial.
• In accordance with ESI* 09-7 & BS7870.
• Conductors: Stranded Class 2
central copper conductor to BS6360.
• Insulation: Red PVC insulation
Type TI.1 to BS7655.
• Helical CNE (Combined Neutral and
Earth) straight concentric comprising
of solid plain copper wires to BS4109.
• Sheath: Black PVC sheath
Type TM.1 to BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 70oC max conductor
operating temperature.
• Voltage Rating: 600/1000 volts.
A P P L I C A T I O N S P E C I F I C A T I O N S
* ESI standards are now covered underEATS (Electricity Association TechnicalSpecification). Standard numberremains the same i.e. EATS 09-7
1:11
1POWER & WIRING CABLES
®
Also available with solid aluminium central conductor.
For further technical information see page 1:86.For conductor short-circuit ratings see page 13:28
Nominal Central Insulation No. and Nom Approx Min BendingAnixter Area of Conductor Thickness size of O/D Weight RadiusPart No. Central Stranding Concentric (fixed bend)
Conductor ConductorWires
mm2 #/mm mm #/mm mm kg/km mm
A3CE-0040 4 7/0.85 0.8 15/0.67 8.7 150 75
A3CE-0160 16 7/1.70 1.0 19/1.04 12.5 450 100
A3CE-0250 25 7/2.14 1.2 25/1.13 14.4 650 125
1:12
POWER & WIRING CABLES1
®
Single Phase Split ConcentricPCU/PVC/Split Concentric/PVC 600/1000 Volts 700C
Single phase split concentric cable, for
household and street lighting services.
Incorporates separate earth and
neutral wires.
Suitable for direct burial.
• In accordance with BS4553.
• Conductors: Stranded Class 2
central copper conductor to BS6360.
• Insulation: Red PVC insulation
Type TI.1 to BS7655.
• Helical Split Concentric comprising of:
• Solid plain copper earth wires to
BS4109 plus PVC insulated plain
copper neutral wires.
• Two or more PVC string fillers are
utilised to divide the bare copper
earth wires and the PVC insulated
neutral wires.
• Sheath: Black PVC sheath
Type TM.1 to BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 70oC max conductor
operating temperature.
• Voltage Rating: 600/1000 volts.
A P P L I C A T I O N S P E C I F I C A T I O N S
1:13
1POWER & WIRING CABLES
®
Also available with solid aluminium central conductor.For further technical information see page 1:86.For conductor short-circuit ratings see page 13:28.* Insulation thickness may be enhanced to allow split concentric to fit helically around the insulated central conductor
A3BN-0040 4 0.8* 7/0.85 3/1.35 10.2 206 100
A3BN-0060 6 1.0 7/1.04 4/1.53 11.2 281 100
A3BN-0100 10 1.0 7/1.35 4/1.78 12.6 394 125
A3BN-0160 16 1.0 7/1.70 4/2.25 14.6 583 125
A3BN-0250 25 1.2* 11/1.70 4/2.25 18.1 843 150
A3BN-0350 35 1.2* 15/1.70 6/2.25 22.6 1248 200
Nominal Insulation No. and No. and Nom Approx Min BendingAnixter Area of Thickness size of size of O/D Weight RadiusPart No. Central Neutral Earth (fixed bend)
Conductor Wires Wires
mm2 mm #/mm #/mm mm kg/km mm
1:14
POWER & WIRING CABLES1
®
Three Phase Straight ConcentricPCU/PVC/Straight Concentric/PVC 600/1000 Volts 700C
Three phase concentric cable for mains
services requiring 3-phase supply.
Incorporates CNE (Combined Neutral
and Earth) to meet the requirements of
PME (Protective Multiple Earthing) in
various distribution systems.
Suitable for direct burial.
• In accordance with ESI* 09-7 & BS7870.
• Conductors: Stranded Class 2
copper conductors to BS6360.
• Insulation: PVC insulation Type TI.1
to BS7655.
• Core Identification: Red, Yellow Blue
• PVC tape bedding applied over
laid-up cores.
• Helical CNE (Combined Neutral and
Earth) straight concentric comprising
of solid plain copper wires to BS4109.
• Sheath: Black PVC sheath
Type TM.1 to BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 70oC max conductor
operating temperature.
• Voltage Rating: 600/1000 volts.
A P P L I C A T I O N S P E C I F I C A T I O N S
* ESI standards are now covered underEATS (Electricity Association TechnicalSpecification). Standard numberremains the same i.e. EATS 09-7
1:15
1POWER & WIRING CABLES
®
Nominal Insulation No. and Nom Approx Min BendingAnixter Area Thickness size of O/D Weight RadiusPart No. of Phase Concentric (fixed bend)
Conductors ConductorWires
mm2 mm #/mm kg/km mm mm
A2EM-0160 16 * 1.0 48/0.67 22.1 900 200
A2EM-0250 25 * 1.2 56/0.75 26.0 1300 200
* Circular or circularcompacted stranded conductors.Also available with solid aluminium conductors.
For further technical information see page 1:86.For conductor short-circuit ratings see page 13:28.
1:16
POWER & WIRING CABLES1
A P P L I C A T I O N S P E C I F I C A T I O N S
PVC/PVC/SWA/PVC Armoured Power &Control Cable 600/1000 Volts
For use in fixed installations, indoor,
outdoor or direct burial.
Cables buried in sustained wet conditions
should have extruded bedding.
Where waterlogging is likely to occur,
technical advice should be sought as to
a suitable type of cable.
• In accordance with BS6346.• Conductors: Stranded Class 2 copper
conductors to BS6360. Solid Class 1 conductors are also available for 1.5 and 2.5mm2.
• Insulation: PVC insulation Type TI.1
to BS7655.
• Core identification:2 core - red, black3 core - red, yellow, blue4 core - red, yellow, blue, black5 core & above - number printed
• PVC inner sheath Type TM.1 to BS7655.
• Mild galvanised steel wires to BSEN10257-1
• Black PVC outer sheath Type TM.1 to
BS7655.• Flame retardant to BS4066 Part 1.
Improved fire performance is available by using a reduced propagation, low HCL emission PVCouter sheath.
• Temp Rating: 70oC max conductor
operating temperature.
• Voltage Rating: 600/1000 volts
®
1:17
1POWER & WIRING CABLES
®
Nominal Insulation Diam Armour Nom Approx Min BendingAnixter Conductor Conductor Thickness under wire O/D Weight RadiusPart No. Area Class armour size (fixed bend)
mm2 mm mm mm mm kg/km mm
Type 6942X - Two Core
A3-G02-2015 1.5 1 0.6 7.3 0.9 11.7 280 80
A3-G02-2015Q 1.5 2 0.6 7.9 0.9 12.3 300 80
A3-G02-2025 2.5 1 0.7 8.5 0.9 13.1 350 80
A3-G02-2025Q 2.5 2 0.7 9.0 0.9 13.6 360 90
A2-S02-2004 4 2 0.8 10.5 0.9 15.1 475 100
A2-S02-2006 6 2 0.8 11.7 0.9 16.5 550 100
A2-S02-2010 10 2 1.0 14.4 1.25 20.1 850 130
A2-S02-2016 16 2 1.0 16.2 1.25 21.9 990 140
Type 6943X - Three Core
A3-G03-3015 1.5 1 0.6 7.7 0.9 12.3 325 80
A3-G03-3015Q 1.5 2 0.6 8.2 0.9 12.8 340 80
A3-G03-3025 2.5 1 0.7 9.0 0.9 13.6 400 90
A3-G03-3025Q 2.5 2 0.7 9.5 0.9 14.1 410 90
A2-T03-3004 4 2 0.8 11.2 0.9 15.8 525 100
A2-T03-3006 6 2 0.8 12.5 1.25 18.0 750 110
A2-T03-3010 10 2 1.0 15.5 1.25 21.2 1025 130
A2-T03-3016 16 2 1.0 17.4 1.25 23.1 1120 140
Type 6944X - Four Core
A3-G04-4015 1.5 1 0.6 8.4 0.9 13.0 360 80
A3-G04-4015Q 1.5 2 0.6 8.9 0.9 13.5 390 90
A3-G04-4025 2.5 1 0.7 9.9 0.9 14.5 440 90
A3-G04-4025Q 2.5 2 0.7 10.4 0.9 15.0 460 90
A2-U04-4004 4 2 0.8 12.3 1.25 17.8 725 110
A2-U04-4006 6 2 0.8 13.7 1.25 19.2 850 120
A2-U04-4010 10 2 1.0 17.1 1.25 22.8 1200 140
A2-U04-4016 16 2 1.0 19.7 1.6 26.3 1530 160
Continued overleaf. . .
®
A3-H01-1005Q 5 1.5 2 0.6 9.7 0.9 14.3 410 90
A3-H01-1007Q 7 1.5 2 0.6 10.6 0.9 15.2 470 100
A3-H01-1010Q 10 1.5 2 0.6 13.5 1.25 19.0 730 120
A3-H01-1012Q 12 1.5 2 0.6 13.9 1.25 19.4 780 120
A3-H01-1019Q 19 1.5 2 0.6 16.5 1.25 22.2 1020 140
A3-H01-1027Q 27 1.5 2 0.6 20.1 1.6 26.7 1510 170
A3-H01-1037Q 37 1.5 2 0.6 22.4 1.6 29.2 1830 180
A3-H01-1048Q 48 1.5 2 0.6 25.9 1.6 32.9 2200 200
A3-H01-2005Q 5 2.5 2 0.7 11.5 0.9 16.3 530 100
A3-H01-2007Q 7 2.5 2 0.7 12.5 1.25 18.0 730 110
A3-H01-2010Q 10 2.5 2 0.7 16.2 1.25 21.9 950 140
A3-H01-2012Q 12 2.5 2 0.7 16.7 1.25 22.4 1050 140
A3-H01-2019Q 19 2.5 2 0.7 20.0 1.6 26.6 1600 160
A3-H01-2027Q 27 2.5 2 0.7 23.9 1.6 30.7 2040 190
A3-H01-2037Q 37 2.5 2 0.7 27.0 1.6 34.0 2520 210
A3-H01-2048Q 48 2.5 2 0.7 31.3 2.0 39.5 3340 240
A3-H04-4005 5 4 2 0.8 13.5 1.25 19.0 810 120
A3-H04-4007 7 4 2 0.8 14.8 1.25 20.5 950 130
A3-H04-4010 10 4 2 0.8 19.5 1.6 26.1 1460 160
A3-H04-4012 12 4 2 0.8 20.2 1.6 26.8 1560 170
A3-H04-4019 19 4 2 0.8 23.7 1.6 30.5 2080 190
A3-H04-4027 27 4 2 0.8 29.1 2.0 37.1 3030 230
1:18
POWER & WIRING CABLES1
Nominal Insulation Diam Armour Nom Approx Min Bending
Anixter No. of Conductor Conductor Thickness under wire O/D Weight Radius
Part No. Cores Area Class armour size (fixed bend)
(mm2) mm mm mm mm kg/km mm
PVC/PVC/SWA/PVC Armoured Power &Control Cable 600/1000 Volts Continued. . .
For more technical information see page 1:88.
For conductor short-circuit ratings see page 13:28.For armour short-circuit ratings see page 13:41.
1:19
1POWER & WIRING CABLES
®
A P P L I C A T I O N S P E C I F I C A T I O N S
1:20
POWER & WIRING CABLES1
®
PVC/PVC/SWA/PVC Armoured ControlCable to ESI* 09-6 600/1000 Volts
Control cables for fixed installation,
indoor, outdoor or direct burial.
• In accordance with ESI 09-6
• Conductors:Stranded Class 2 copper
to BS6360.
• Insulation: PVC insulation Type TI.1
to BS7655.
• Core identification: Number printed in
black ink on white PVC insulation.
• Inner Sheath: PVC sheath Type
TM.1 to BS7655.
• Mild galvanised steel wires to BSEN10257-1
• Outer Sheath: Reduced propagation,
low HCL emission PVC sheath.
Meets Type TM.1 to BS7655 and in
addition displays following characteristics:
Oxygen Index: 30% min
HCL emission @ 8000C: 15% max
• Flame retardant to BS4066 Part 3.
• Temp Rating: 700C max conductor
operating temperature.
• Voltage Rating: 600/1000 volts* ESI standards are now covered underEATS (Electricity Association TechnicalSpecification). Standard numberremains the same i.e. EATS 09-6
1:21
1POWER & WIRING CABLES
®
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness under wire O/D Weight RadiusPart No. Cores Area armour size (fixed bend)
mm2 mm mm mm mm kg/km mm
A3-K02-2073 2 1.5 0.6 7.7 0.9 12.3 300 80
A3-K03-2078 3 1.5 0.6 8.2 0.9 12.8 340 80
A3-K04-2087 4 1.5 0.6 8.9 0.9 13.5 390 90
A3-K05-2099 5 1.5 0.6 9.7 0.9 14.3 430 90
A3-K07-2108 7 1.5 0.6 10.6 0.9 15.2 470 100
A3-K10-2148 10 1.5 0.6 13.5 1.25 19.0 730 120
A3-K12-2148 12 1.5 0.6 13.9 1.25 19.4 780 120
A3-K19-2178 19 1.5 0.6 16.5 1.25 22.2 1020 140
A3-K27-2219 27 1.5 0.6 20.1 1.6 26.7 1510 170
A3-K37-2248 37 1.5 0.6 22.4 1.6 29.2 1830 180
A3-K02-1073 2 2.5 0.7 8.9 0.9 13.6 360 90
A3-K03-1078 3 2.5 0.7 9.4 0.9 14.1 410 90
A3-K04-1087 4 2.5 0.7 10.3 0.9 15.0 460 90
A3-K05-1099 5 2.5 0.7 11.5 0.9 16.3 530 100
A3-K07-1108 7 2.5 0.7 12.4 1.25 18.0 720 110
A3-K10-1148 10 2.5 0.7 16.2 1.25 21.9 930 140
A3-K12-1148 12 2.5 0.7 16.5 1.25 22.4 1030 140
A3-K19-1178 19 2.5 0.7 19.8 1.6 26.6 1530 160
A3-K27-1219 27 2.5 0.7 23.9 1.6 30.7 1960 190
A3-K37-1248 37 2.5 0.7 26.8 1.6 34.0 2490 210
For further technical information see page 1:88.
For conductor short-circuit ratings refer to page 13:28.For armour short-circuit ratings refer to page 13:41.
1:22
POWER & WIRING CABLES1
A P P L I C A T I O N S P E C I F I C A T I O N S
Single Core XLPE/PVC600/1000 Volts
XLPE insulated and PVC sheathed
cable for fixed installation.
Not suitable for direct burial.
• In accordance with BS7889.
• Conductors: Stranded Class 2
copper conductors to BS6360.
• Insulation: XLPE insulation Type
GP8 to BS7655.
• Sheath: PVC sheath Type 9 to
BS7655.
• Flame retardant to BS4066 Part 1.
• Normal colours available.
(See 6491X page1:2)
• Temp. Rating: 90oC max conductor
operating temperature.
• Voltage Rating: 600/1000 volts.
®
1:23
1POWER & WIRING CABLES
®
Anixter Nominal Insulation Nom Approx Min BendingPart No. Conductor Thickness O/D Weight Radius
Area (fixed bend)mm2 mm mm kg/km mm
A2EG-0500 50 1.0 14.2 540 60
A2EG-0700 70 1.1 16.2 750 70
A2EG-0950 95 1.1 18.3 1010 80
A2EG-1200 120 1.2 20.2 1250 90
A2EG-1500 150 1.4 22.4 1530 90
A2EG-1850 185 1.6 24.7 1900 100
A2EG-2400 240 1.7 27.7 2470 170
A2EG-3000 300 1.8 30.6 3080 190
A2EG-4000 400 2.0 34.2 3890 210
A2EG-5000 500 2.2 38.0 4970 230
A2EG-6300 630 2.4 42.9 6370 260
A2EG-8000 800 2.6 47.8 8300 290
A2EG-1000 1000 2.8 53.0 10341 320
All dimensions are nominal unless otherwise stated.For further technical information see page 1:92.For conductor short-circuit ratings refer to page 13:29.Additional information refer to 1:104.
®
POWER & WIRING CABLES1
Single Core XLPE/PVC/AWA/PVC PowerCable 600/1000 Volts & 1900/3300 Volts
Armoured single core cable for use in
fixed installations, indoor, outdoor or
direct burial.
• In accordance with BS5467
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Insulation: XLPE insulation Type
GP8 to BS7655.
• Inner Sheath: PVC inner sheath
Type 9 to BS7655.
• Aluminium wires to BS2627
• Outer Sheath: Black PVC outer
sheath Type 9 to BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 900C max conductor
operating temperature.
• Voltage Rating: 600/1000 &
1900/3300 volts
1:24
A P P L I C A T I O N S P E C I F I C A T I O N S
1:25
1POWER & WIRING CABLES
®
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
600/1000V Cables
A2B0-0500 1 50 1.0 12.7 0.9 17.5 800 110
A2B0-0700 1 70 1.1 14.7 1.25 20.2 940 130
A2B0-0950 1 95 1.1 16.6 1.25 22.3 1220 140
A2B0-1200 1 120 1.2 18.5 1.25 24.2 1490 150
A2B0-1500 1 150 1.4 20.8 1.6 27.4 1870 170
A2B0-1850 1 185 1.6 23.2 1.6 30.0 2290 180
A2B0-2400 1 240 1.7 26.0 1.6 32.8 2880 200
A2B0-3000 1 300 1.8 28.6 1.6 35.6 3520 220
A2B0-4000 1 400 2.0 32.4 2.0 40.4 4500 250
A2B0-5000 1 500 2.2 36.0 2.0 44.2 5680 270
A2B0-6300 1 630 2.4 40.4 2.0 48.8 7160 300
A2B0-8000 1 800 2.6 45.6 2.5 55.4 9400 340
A2B0-10000 1 1000 2.8 50.6 2.5 60.6 11600 370
1900/3300V Cables
A2BX-0500 1 50 2.0 14.9 1.25 20.6 810 130
A2BX-0700 1 70 2.0 16.7 1.25 22.4 1040 140
A2BX-0950 1 95 2.0 18.6 1.25 24.3 1330 150
A2BX-1200 1 120 2.0 20.6 1.6 27.2 1680 170
A2BX-1500 1 150 2.0 22.2 1.6 28.8 1970 180
A2BX-1850 1 185 2.0 24.0 1.6 30.8 2370 190
A2BX-2400 1 240 2.0 26.6 1.6 33.4 2960 210
A2BX-3000 1 300 2.0 29.1 1.6 36.1 3610 220
A2BX-4000 1 400 2.0 32.4 2.0 40.4 4600 250
A2BX-5000 1 500 2.2 36.0 2.0 44.2 5680 270
A2BX-6300 1 630 2.4 40.4 2.0 48.8 7160 300
A2BX-8000 1 800 2.6 45.6 2.5 55.4 9400 340
A2BX-10000 1 1000 2.8 50.6 2.5 60.6 11600 370
For further technical information see page 1:100. (See 1:114 for technical informationon 1900/3300V cables)
For conductor and armour resistances refer page 13:31.For Gross Cross-Sectional area of armour refer to page 13:34.For conductor short-circuit ratings refer to page 13:29.For armour short-circuit ratings refer to page 13:36.
1:26
POWER & WIRING CABLES1
®
XLPE/PVC Multicore Power Cable 600/1000 Volts
Insulated and sheathed cable for use in
fixed installations.
Not suitable for direct burial.
• In accordance with BS5467
(1989 issue only)
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Insulation: XLPE insulation Type
GP8 to BS7655.
• Core identification:
2 core - red, black
3 core - red, yellow, blue
4 core - red, yellow, blue, black
• Outer Sheath: Black PVC outer
sheath Type 9 to BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 900C max conductor
operating temperature
• Voltage Rating: 600/1000 volts
* Circular or circular compacted stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.
A P P L I C A T I O N S P E C I F I C A T I O N S
1:27
1POWER & WIRING CABLES
®
Anixter Number Nominal Insulation Nom Approx Min BendingPart No. of Conductor Thickness O/D Weight Radius
Cores Area (fixed bend)mm2 mm mm kg/km mm
A2DT-0160 2 16* 0.7 17.2 490 70
A2DT-0250 2 25* 0.9 20.8 660 90
A2DT-0350 2 35* 0.9 23.2 880 100
A2DT-0500 2 50 \\ 1.0 21.0 1100 170
A2DT-0700 2 70 1.1 24.0 1520 200
A2DT-0950 2 95 1.1 26.9 2040 220
A2DT-1200 2 120 1.2 29.9 2570 240
A2DT-1500 2 150 1.4 33.4 3130 270
A2DT-1850 2 185 1.6 37.1 3920 300
A2DT-2400 2 240 1.7 41.7 5050 340
A2DT-3000 2 300 1.8 45.8 6350 370
A2DT-4000 2 400 2.0 51.6 8000 420
A2DU-0160 3 16* 0.7 18.3 640 80
A2DU-0250 3 25* 0.9 22.1 920 90
A2DU-0350 3 35* 0.9 24.8 1190 100
A2DU-0500 3 50 \\ 1.0 23.6 1580 190
A2DU-0700 3 70 1.1 27.4 2220 220
A2DU-0950 3 95 1.1 30.8 2980 250
A2DU-1200 3 120 1.2 34.2 3730 280
A2DU-1500 3 150 1.4 37.9 4580 310
A2DU-1850 3 185 1.6 42.5 5740 340
A2DU-2400 3 240 1.7 47.8 7450 390
A2DU-3000 3 300 1.8 52.6 9230 430
A2DU-4000 3 400 2.0 59.2 11720 480
A2DV-0160 4 16* 0.7 20.0 820 80
A2DV-0250 4 25* 0.9 24.3 1170 100
A2DV-0350 4 35* 0.9 27.3 1550 170
A2DV-0500 4 50 \\ 1.0 26.9 2050 220
A2DV-0700 4 70 1.1 31.5 2900 260
A2DV-0950 4 95 1.1 35.6 3920 290
A2DV-1200 4 120 1.2 39.5 4940 320
A2DV-1500 4 150 1.4 44.1 6040 360
A2DV-1850 4 185 1.6 49.3 7580 400
A2DV-2400 4 240 1.7 55.5 9860 450
A2DV-3000 4 300 1.8 61.4 12280 500
A2DV-4000 4 400 2.0 68.8 15000 560
Continued overleaf. . .
POWER & WIRING CABLES
®
A2DW-02516 4 25* 16* 0.9 0.7 23.3 900 100
A2DW-03516 4 35* 16* 0.9 0.7 25.7 1100 160
A2DW-05025 4 50 \\ 25† 1.0 0.9 26.1 1400 210
A2DW-07035 4 70 35 1.1 0.9 30.4 2600 250
A2DW-09550 4 95 50 1.1 1.0 34.8 3500 280
A2DW-12070 4 120 70 1.2 1.1 39.4 4500 320
A2DW-15070 4 150 70 1.4 1.1 42.5 5150 340
A2DW-18595 4 185 95 1.6 1.1 47.7 6600 390
A2DW-24012 4 240 120 1.7 1.2 53.4 8500 430
A2DW-30015 4 300 150 1.8 1.4 59.0 10200 480
A2DW-30018 4 300 185 1.8 1.6 61.2 10700 490
A2DW-40018 4 400 185 2.0 1.6 66.4 14350 540
1
Number Nominal Nominal Insulation Insulation Nom Approx Min BendingAnixter of Phase Neutral Thickness Thickness O/D Weight RadiusPart No. Cores Conductor Conductor (Phase) (Neutral) (fixed bend)
Area (mm2) Area (mm2) (mm) (mm) (mm) kg/km (mm)
XLPE/PVC Multicore Power Cable 600/1000 Volts Continued. . .
1:28
*Circular or circular compacted stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Neutral conductors of nominal area 25mm2 and above may have shaped, circular or circular compactedstranded conductors.
For further technical information see page 1:96.For conductor short-circuit ratings refer to page 13:29.
1:29
1POWER & WIRING CABLES
®
®
POWER & WIRING CABLES1
Multi-Core XLPE/PVC/SWA/PVC Power Cable 600/1000 Volts & 1900/3300 Volts
Armoured cables for use in fixed
installations for use indoor, outdoor or
for direct burial.
• In accordance with BS5467
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Insulation: XLPE insulation Type
GP8 to BS7655.
• Core identification:
2 core - red, black
3 core - red, yellow, blue
4 core - red, yellow, blue, black
5 core + above - number printed
• Inner Sheath: PVC inner sheath
Type 9 to BS7655.
• Mild galvanised steel wires to BSEN10257-1
• Outer Sheath: Black PVC outer
sheath Type 9 to BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 900C max conductor
operating temperature
• Voltage Rating: 600/1000 volts
NB: 1900/3300 Volts only available in3 core
1:30
A P P L I C A T I O N S P E C I F I C A T I O N S
1:31
1POWER & WIRING CABLES
®
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
600/1000V
A2BQ-0015Q 2 1.5* 0.6 7.7 0.9 12.3 295 80
A2BQ-0025Q 2 2.5* 0.7 9.0 0.9 13.6 345 90
A2BQ-0040 2 4* 0.7 10.1 0.9 14.7 409 90
A2BQ-0060 2 6* 0.7 11.3 0.9 15.9 485 100
A2BQ-0100 2 10* 0.7 13.2 0.9 18.0 635 110
A2BQ-0160 2 16† 0.7 14.5 1.25 20.0 900 120
A2BQ-0250 2 25† 0.9 18.4 1.25 24.1 1060 150
A2BQ-0350 2 35† 0.9 21.3 1.6 27.9 1490 170
A2BQ-0500 2 50 \\ 1.0 19.0 1.6 25.8 1800 210
A2BQ-0700 2 70 1.1 22.0 1.6 29.0 2320 240
A2BQ-0950 2 95 1.1 25.1 2.0 33.1 3160 270
A2BQ-1200 2 120 1.2 27.9 2.0 36.1 3790 290
A2BQ-1500 2 150 1.4 30.9 2.0 39.3 4500 320
A2BQ-1850 2 185 1.6 34.9 2.5 44.7 5820 360
A2BQ-2400 2 240 1.7 39.0 2.5 49.0 7220 400
A2BQ-3000 2 300 1.8 43.3 2.5 53.5 8710 430
A2BQ-4000 2 400 2.0 48.4 2.5 59.0 11100 480
A2BS-0015Q 3 1.5* 0.6 8.2 0.9 12.8 330 80
A2BS-0025Q 3 2.5* 0.7 9.5 0.9 14.1 390 90
A2BS-0040 3 4* 0.7 10.7 0.9 15.3 470 100
A2BS-0060 3 6* 0.7 12.0 0.9 16.6 570 100
A2BS-0100 3 10* 0.7 14.0 1.25 19.5 880 120
A2BS-0160 3 16† 0.7 15.5 1.25 21.2 1070 130
A2BS-0250 3 25† 0.9 20.1 1.6 26.7 1550 170
A2BS-0350 3 35† 0.9 22.8 1.6 29.6 1940 180
A2BS-0500 3 50 \\ 1.0 21.7 1.6 28.5 2360 230
A2BS-0700 3 70 1.1 25.2 1.6 32.2 3120 260
A2BS-0950 3 95 1.1 28.8 2.0 37.0 4310 300
A2BS-1200 3 120 1.2 32.0 2.0 40.4 5160 330
A2BS-1500 3 150 1.4 35.9 2.5 45.5 6610 370
A2BS-1850 3 185 1.6 40.0 2.5 49.8 7920 400
A2BS-2400 3 240 1.7 44.9 2.5 55.1 9930 450
A2BS-3000 3 300 1.8 49.8 2.5 60.2 11970 490
A2BS-4000 3 400 2.0 55.8 2.5 66.6 14770 540
*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors. Continued overleaf. . .
®
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
600/1000V
A2BU-0015Q 4 1.5* 0.6 8.9 0.9 13.5 380 90
A2BU-0025Q 4 2.5* 0.7 10.4 0.9 15.0 450 90
A2BU-0040 4 4* 0.7 11.8 0.9 16.4 560 100
A2BU-0060 4 6* 0.7 13.2 1.25 18.7 790 120
A2BU-0100 4 10* 0.7 15.6 1.25 21.1 1040 130
A2BU-0160 4 16† 0.7 17.2 1.25 22.9 1300 140
A2BU-0250 4 25† 0.9 22.3 1.6 28.9 1880 180
A2BU-0350 4 35† 0.9 25.3 1.6 32.1 2350 200
A2BU-0500 4 50 \\ 1.0 25.0 1.6 32.0 2950 260
A2BU-0700 4 70 1.1 29.5 2.0 37.7 4230 320
A2BU-0950 4 95 1.1 33.3 2.0 41.7 5390 340
A2BU-1200 4 120 1.2 37.5 2.5 47.1 6890 380
A2BU-1500 4 150 1.4 41.6 2.5 51.4 8300 420
A2BU-1850 4 185 1.6 46.4 2.5 56.6 10070 460
A2BU-2400 4 240 1.7 52.6 2.5 63.0 12680 510
A2BU-3000 4 300 1.8 58.0 2.5 68.8 15380 560
A2BU-4000 4 400 2.0 65.4 3.15 78.1 19950 630
A3AM-C007Q 7 1.5* 0.6 10.6 0.9 15.2 488 100
A3AM-C012Q 12 1.5* 0.6 13.9 1.25 19.4 817 120
A3AM-CO19Q 19 1.5* 0.6 16.5 1.25 22.2 1225 140
A3AM-C027Q 27 1.5* 0.6 20.1 1.6 26.7 1553 170
A3AM-C037Q 37 1.5* 0.6 22.4 1.6 29.2 1859 180
A3AP-C007Q 7 2.5* 0.7 12.5 0.9 17.1 685 110
A3AP-C012Q 12 2.5* 0.7 16.7 1.25 22.4 910 140
A3AP-C019Q 19 2.5* 0.7 20.0 1.6 26.6 1500 160
A3AP-C027Q 27 2.5* 0.7 23.9 1.6 30.7 1928 190
A3AP-C037Q 37 2.5* 0.7 27.0 1.6 33.8 2360 210
POWER & WIRING CABLES1
Multi-Core XLPE/PVC/SWA/PVC Power Cable 600/1000 Volts & 1900/3300 Volts
Continued. . .
1:32
1:33
1POWER & WIRING CABLES
®
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
1900/3300V Cables
A2BZ-0160 3 16† 2.0 22.1 1.6 28.9 1600 180
A2BZ-0250 3 25† 2.0 25.4 1.6 32.2 2060 200
A2BZ-0350 3 35† 2.0 28.0 1.6 35.0 2320 210
A2BZ-0500 3 50 \\ 2.0 26.7 2.0 34.7 3040 280
A2BZ-0700 3 70 2.0 29.8 2.0 38.0 3800 310
A2BZ-0950 3 95 2.0 33.0 2.0 41.4 4730 340
A2BZ-1200 3 120 2.0 36.1 2.5 45.7 6070 370
A2BZ-1500 3 150 2.0 38.7 2.5 48.5 7010 390
A2BZ-1850 3 185 2.0 41.9 2.5 51.9 8270 420
A2BZ-2400 3 240 2.0 46.7 2.5 56.9 10310 460
A2BZ-3000 3 300 2.0 50.8 2.5 61.2 12300 490
A2BZ-4000 3 400 2.0 55.8 2.5 66.6 15050 540
*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.
For further technical information see page 1:106. (See 1:114 for technical informationon 1900/3300V cables).
For conductor and armour resistances refer page 13:32.For Gross Cross-Sectional area of armour refer to page 13:35.For conductor short-circuit ratings refer to page 13:29.For armour short-circuit ratings refer to page 13:37.
A P P L I C A T I O N S P E C I F I C A T I O N S
1:34
POWER & WIRING CABLES1
®
Single Core LSF 6491B900C 300/500 & 450/750 Volts
LSF insulated only cable for fixed wiring
purposes. Used in trunking or conduit,
or may be surface mounted when used
for earthing.
Especially for use in areas where fire
would create dense smoke and toxic
fumes causing a major threat to life and
equipment.
• In accordance with BS7211 and
Cenelec harmonised codes
H07Z-U (Solid conductors)
H07Z-R (Stranded conductors)
• Conductors: Solid Class 1 or
Stranded Class 2 copper conductors
to BS6360.
• Insulation: Low smoke zero halogen
thermosetting insulation Type EI.5 to
BS7655, displaying following
characteristics:
Oxygen Index: 30% min
HCL emission @ 8000C: 0.5% max
• Flame retardant to BS4066 Part 2
(up to and incl. 1.0mm2) and BS4066
Part 1 (above 1.0mm2).
• Normal colours available.
(see 6491X p1:2)
• Temp Rating: 900C max conductor
operating temperature.
• Voltage Rating:
Up to and including 1.0mm2 - 300/500V
1.5mm2 and above - 450/750V
1:35
1POWER & WIRING CABLES
®
Anixter Cenelec Nominal Conductor Insulation Max Approx Min BendingPart No. Code Conductor Class Thickness O/D Weight Radius
Area (fixed bend)mm2 mm mm kg/km mm
A3BR-0015 H07Z-U1 1.5 1 0.7 3.3 20 10
A3BT-0015 H07Z-R1 1.5 2 0.7 3.4 22 11
A3BR-0025 H07Z-U1 2.5 1 0.8 4.0 31 12
A3BT-0025 H07Z-R1 2.5 2 0.8 4.1 33 13
A3BT-0040 H07Z-R1 4 2 0.8 4.7 49 15
A3BT-0060 H07Z-R1 6 2 0.8 5.4 69 17
A3BT-0100 H07Z-R1 10 2 1.0 7.0 116 21
A3BT-0160 H07Z-R1 16 2 1.0 8.0 175 24
A3BT-0250 H07Z-R1 25 2 1.2 10.1 273 30
A3BT-0350 H07Z-R1 35 2 1.2 11.3 367 50
A3BT-0500 H07Z-R1 50 2 1.4 13.2 495 60
A3BT-0700 H07Z-R1 70 2 1.4 15.1 699 60
A3BT-0950 H07Z-R1 95 2 1.6 17.6 968 70
A3BT-1200 H07Z-R1 120 2 1.6 19.4 1164 80
A3BT-1500 H07Z-R1 150 2 1.8 21.6 1413 90
A3BT-1850 H07Z-R1 185 2 2.0 24.1 1828 100
A3BT-2400 H07Z-R1 240 2 2.2 27.5 2320 160
A3BT-3000 H07Z-R1 300 2 2.4 30.6 2988 180
A3BT-4000 H07Z-R1 400 2 2.6 34.3 3800 210
A3BT-5000 H07Z-R1 500 2 2.8 38.2 4750 230
A3BT-6300* A07Z-R1 630 2 2.8 42.5 6050 250
* = National TypeAll dimensions are nominal unless otherwise stated.For further technical information see page 1:92.For conductor short-circuit ratings refer to page 13:29 for XLPE insulated cable.
1:36
POWER & WIRING CABLES1
®
Single Core XLPE/LSF/AWA/LSF PowerCable 600/1000 Volts & 1900/3300 Volts
• In accordance with BS6724
• Conductors: Stranded Class 2
copper conductors.
• Insulation: XLPE insulation Type
GP8 to BS7655.
• Inner Sheath: LSF inner sheath
Type LTS1 to BS7655.
• Aluminium wires to BS2627.
• Outer Sheath: Black LSF outer
sheath Type LTS1 to BS7655.
• Flame retardant to BS4066/IEC60332
Part 3 Category A (NMV7).
• Temp Rating: 90oC max conductor
operating temperature.
• Voltage Rating: 600/1000 &
1900/3300V.
LSF insulated, armoured and
sheathed, single core power cable for
use in fixed installations.
Especially for use in areas where fire
would create dense smoke and toxic
fumes causing a major threat to life and
equipment.
A P P L I C A T I O N S P E C I F I C A T I O N S
600/1000V Cables
A2-AT-0500 1 50 1.0 12.7 0.9 17.5 710 110
A2-AT-0700 1 70 1.1 14.7 1.25 20.2 940 130
A2-AT-0950 1 95 1.1 16.6 1.25 22.3 1220 140
A2-AT-1200 1 120 1.2 18.5 1.25 24.2 1480 150
A2-AT-1500 1 150 1.4 20.8 1.6 27.4 1870 150
A2-AT-1850 1 185 1.6 23.2 1.6 30.0 2280 180
A2-AT-2400 1 240 1.7 26.0 1.6 32.8 2880 200
A2-AT-3000 1 300 1.8 28.6 1.6 35.6 3520 220
A2-AT-4000 1 400 2.0 32.4 2.0 40.4 4520 250
A2-AT-5000 1 500 2.2 36.0 2.0 44.2 5640 270
A2-AT-6300 1 630 2.4 40.4 2.0 48.8 7110 300
A2-AT-8000 1 800 2.6 45.6 2.5 55.4 9390 340
A2-AT-10000 1 1000 2.8 50.6 2.5 60.6 11580 370
1900/3300V Cables
A2-AY-0500 1 50 2.0 14.9 1.25 20.6 800 130
A2-AY-0700 1 70 2.0 16.7 1.25 22.4 1020 140
A2-AY-0950 1 95 2.0 18.6 1.25 24.3 1300 150
A2-AY-1200 1 120 2.0 20.6 1.6 27.2 1650 170
A2-AY-1500 1 150 2.0 22.2 1.6 28.8 1930 180
A2-AY-1850 1 185 2.0 24.0 1.6 30.8 2330 190
A2-AY-1240 1 240 2.0 26.6 1.6 33.4 2910 210
A2-AY-1300 1 300 2.0 29.1 1.6 36.1 3540 220
A2-AY-1400 1 400 2.0 32.4 2.0 40.4 4520 250
A2-AY-1500 1 500 2.2 36.0 2.0 44.2 5640 270
A2-AY-1630 1 630 2.4 40.4 2.0 48.8 7110 300
A2-AY-1800 1 800 2.6 46.6 2.5 56.4 9390 340
A2-AY-10000 1 1000 2.8 50.6 2.5 60.6 11580 370
1:37
1POWER & WIRING CABLES
®
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
CONDUCTORS MAY BE CIRCULAR OR CIRCULAR COMPACTED.For further technical information refer to page 1:100. (See 1:114 for technical informationon 1900/3300V cables).
For conductor and armour resistances refer page 13:31.For Gross Cross-Sectional area of armour refer to page 13:34.For conductor short-circuit ratings refer to page 13:29.For armour short-circuit ratings refer to page 13:36.
1:38
POWER & WIRING CABLES1
®
Multi-Core XLPE/LSF/SWA/LSF Power &Control Cable 600/1000 and 1900/3300 Volts
• In accordance with BS6724.
• Conductors: Stranded Class 2 copper
conductors.
• Insulation: XLPE insulation Type
GP8 to BS7655.
• Core identification:
2 core - red, black
3 core - red, yellow, blue
4 core - red, yellow, blue, black
5 core + above - number printed
• Inner Sheath: LSF inner sheath
Type LTS1 to BS7655.
• Mild galvanised steel wires to BSEN10257-1
• Outer Sheath: Black LSF outer
sheath Type LTS1 to BS7655.
• Flame retardant to BS4066/IEC60332
Part 3 Category A (NMV7).
• Temp Rating: 900C max conductor
operating temperature.
• Voltage Rating: 600/1000 &
1900/3300V.
NB:1900/3300V only available in 3 core
LSF insulated, armoured and
sheathed, multi-core power cable.
Especially for use in areas where fire
would create dense smoke and toxic
fumes causing a major threat to life and
equipment.
A P P L I C A T I O N S P E C I F I C A T I O N S
600/1000V Cables
A2-AU-0015 2 1.5* 0.6 7.7 0.9 12.3 310 80
A2-AU-0025 2 2.5* 0.7 9.0 0.9 13.6 360 90
A2-AU-0040 2 4* 0.7 10.1 0.9 14.7 420 90
A2-AU-0060 2 6* 0.7 11.3 0.9 15.9 500 100
A2-AU-0100 2 10* 0.7 13.2 0.9 18.0 800 110
A2-AU-0160 2 16† 0.7 14.5 1.25 20.0 940 120
A2-AU-0250 2 25† 0.9 18.4 1.25 24.1 1250 150
A2-AU-0350 2 35† 0.9 21.3 1.6 27.9 1720 170
A2-AU-0500 2 50 \\ 1.0 19.0 1.6 25.8 1800 210
A2-AU-0700 2 70 1.1 22.0 1.6 29.0 2330 240
A2-AU-0950 2 95 1.1 25.1 2.0 33.1 3170 270
A2-AU-1200 2 120 1.2 27.9 2.0 36.1 3810 290
A2-AU-1500 2 150 1.4 30.9 2.0 39.3 4530 320
A2-AU-1850 2 185 1.6 34.9 2.5 44.7 5860 360
A2-AU-2400 2 240 1.7 39.0 2.5 49.0 7300 400
A2-AU-3000 2 300 1.8 43.3 2.5 53.3 8790 430
A2-AU-4000 2 400 2.0 48.4 2.5 59.0 10770 480
A2-AV-0015 3 1.5* 0.6 8.2 0.9 12.8 340 80
A2-AV-0025 3 2.5* 0.7 9.5 0.9 14.1 400 90
A2-AV-0040 3 4* 0.7 10.7 0.9 15.3 500 100
A2-AV-0060 3 6* 0.7 12.0 0.9 16.6 770 100
A2-AV-0100 3 10* 0.7 14.0 1.25 19.5 900 120
A2-AV-0160 3 16† 0.7 15.5 1.25 21.2 1180 130
A2-AV-0250 3 25† 0.9 20.1 1.6 26.7 1720 170
A2-AV-0350 3 35† 0.9 22.8 1.6 29.6 2130 180
A2-AV-0500 3 50 \\ 1.0 21.7 1.6 28.5 2380 230
A2-AV-0700 3 70 1.1 25.2 1.6 32.2 3150 260
A2-AV-0950 3 95 1.1 28.8 2.0 37.0 4320 300
A2-AV-1200 3 120 1.2 32.0 2.0 40.4 5200 330
A2-AV-1500 3 150 1.4 35.9 2.5 45.5 6630 370
A2-AV-1850 3 185 1.6 40.0 2.5 49.8 7980 400
A2-AV-2400 3 240 1.7 44.9 2.5 55.1 9960 450
A2-AV-3000 3 300 1.8 49.8 2.5 60.2 12060 490
A2-AV-4000 3 400 2.0 55.8 2.5 66.6 14980 540
1:39
1POWER & WIRING CABLES
®
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.
continued overleaf. . .
®
A2-AX-0015 4 1.5* 0.6 8.9 0.9 13.5 390 90
A2-AX-0025 4 2.5* 0.7 10.4 0.9 15.0 470 90
A2-AX-0040 4 4* 0.7 11.8 0.9 16.4 580 100
A2-AX-0060 4 6* 0.7 13.2 1.25 18.7 820 120
A2-AX-0100 4 10* 0.7 15.6 1.25 21.1 1060 130
A2-AX-0160 4 16† 0.7 17.2 1.25 22.9 1410 140
A2-AX-0250 4 25† 0.9 22.3 1.6 28.9 2090 180
A2-AX-0350 4 35† 0.9 25.3 1.6 32.1 2590 200
A2-AX-0500 4 50 \\ 1.0 25.0 1.6 32.0 2960 260
A2-AX-0700 4 70 1.1 29.5 2.0 37.7 4240 310
A2-AX-0950 4 95 1.1 33.3 2.0 41.7 5410 340
A2-AX-1200 4 120 1.2 37.5 2.5 47.1 6980 380
A2-AX-1500 4 150 1.4 41.6 2.5 51.4 8320 420
A2-AX-1850 4 185 1.6 46.4 2.5 56.6 10080 460
A2-AX-2400 4 240 1.7 52.6 2.5 63.0 12690 510
A2-AX-3000 4 300 1.8 58.0 2.5 68.8 15420 560
A3-03-C007 7 1.5* 0.6 10.6 0.9 15.2 490 100
A3-03-C012 12 1.5* 0.6 13.9 1.25 19.4 830 120
A3-03-C019 19 1.5* 0.6 16.5 1.25 22.2 1070 140
A3-03-C027 27 1.5* 0.6 20.1 1.6 26.7 1580 170
A3-03-C037 37 1.5* 0.6 22.4 1.6 29.2 1880 180
A3-P3-C007 7 2.5* 0.7 12.5 0.9 17.1 600 110
A3-P3-C012 12 2.5* 0.7 16.7 1.25 22.4 1020 140
A3-P3-C019 19 2.5* 0.7 20.0 1.6 26.6 1530 160
A3-P3-C027 27 2.5* 0.7 23.9 1.6 30.7 1960 190
A3-P3-C037 37 2.5* 0.7 27.0 1.6 33.8 2370 210
A3-Q3-C007 7 4* 0.7 14.2 1.25 19.7 830 120
A3-Q3-C012 12 4* 0.7 19.3 1.6 25.7 1440 160
A3-Q3-C019 19 4* 0.7 22.7 1.6 29.3 1930 180
A3-Q3-C027 27 4* 0.7 27.4 1.6 34.4 2530 210
A3-Q3-C037 37 4* 0.7 31.2 2.0 39.2 3470 240
1:40
POWER & WIRING CABLES1
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
Multi-Core XLPE/LSF/SWA/LSF Power &Control Cable 600/1000 and 1900/3300 Volts
. . . Continued
1:41
1POWER & WIRING CABLES
®
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
1900/3300V Cables
A2-AZ-0250 3 25† 2.0 25.4 1.6 32.2 2100 200
A2-AZ-0350 3 35† 2.0 28.0 1.6 35.0 2520 210
A2-AZ-0500 3 50\\ 2.0 26.7 2.0 34.7 3030 280
A2-AZ-0700 3 70 2.0 29.8 2.0 38.0 3810 310
A2-AZ-0950 3 95 2.0 33.0 2.0 41.4 4730 340
A2-AZ-1200 3 120 2.0 36.1 2.5 45.7 6020 360
A2-AZ-1500 3 150 2.0 38.7 2.5 48.5 6980 390
A2-AZ-1850 3 185 2.0 41.9 2.5 51.9 8250 420
A2-AZ-2400 3 240 2.0 46.7 2.5 56.9 10200 460
A2-AZ-3000 3 300 2.0 50.8 2.5 61.2 12210 490
A2-AZ-4000 3 400 2.0 55.8 2.5 66.6 15160 540
*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.
For more technical information see page 1:106. (See 1:114 for technical informationon 1900/3300V cables).
For conductor and armour resistances refer page 13:32.For Gross Cross-Sectional area of armour refer to page 13:35.For conductor short-circuit ratings refer to page 13:29.For armour short-circuit ratings refer to page 13:37.
1:42
POWER & WIRING CABLES1
®
A P P L I C A T I O N S P E C I F I C A T I O N S
Three Core XLPE/LSF/SWA/LSF PowerCable 6.35/11kV
• In accordance with BS7835.
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Extruded semi-conducting layer.
• Insulation: XLPE insulation.
• Extruded semi-conducting layer.
• Plain copper tape screen.
• Inner Sheath: LSF inner sheath
Type LTS1 to BS7655.
• Mild galvanised steel wires to BSEN10257-1
• Outer Sheath: Red LSF outer sheath
Type LTS1 to BS7655.
• Flame retardant to BS4066 Part 3
Category A (IEC 60332 Part 3 Category A)
• Temp Rating: 900C max conductor
operating temperature.
• Voltage Rating: 6350/11000V
LSF armoured power cable for use in
fixed installations. Especially for use in
areas where fire would create dense
smoke and toxic fumes causing a
major threat to life and equipment.
For further technical information refer to page 1:118.
1:43
1POWER & WIRING CABLES
®
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size mm
mm2 mm mm mm mm kg/km During AdjacentInstallation to joints and
Termination
A2EN-
3016-03 3 16 3.4 35.6 2.0 44.2 3400 540 450
3025-03 3 25 3.4 38.1 2.5 47.9 4300 580 480
3035-03 3 35 3.4 40.3 2.5 50.3 4700 610 510
3050-03 3 50 3.4 42.9 2.5 53.1 5500 640 540
3070-03 3 70 3.4 46.7 2.5 57.1 6400 690 580
3095-03 3 95 3.4 50.6 2.5 61.2 7500 740 620
3120-03 3 120 3.4 54.0 2.5 65.0 8600 780 650
3150-03 3 150 3.4 56.8 2.5 68.0 9600 820 680
3185-03 3 185 3.4 60.9 2.5 72.3 11200 870 730
3240-03 3 240 3.4 65.9 3.15 79.0 14200 950 790
3300-03 3 300 3.4 71.0 3.15 84.5 16500 1020 850
3400-03 3 400 3.4 77.0 3.15 90.9 19700 1100 910
1:44
POWER & WIRING CABLES1
®
FP200® Fire Resistant Cable Incorporating circuit protective conductor (CPC) 300/500 Volts
• In accordance with BS7629 Part 1.
• BASEC Approved.
• Conductors: Solid Class 1 or stranded
Class 2 copper conductors to BS6360.
• Insulation: Silicone rubber insulation
type EI2 to BS7655.
• Core identification:
2 core - red, black
3 core - red, yellow, blue
4 core - red, yellow, blue, black
7, 12, 19 core 1.0 & 1.5mm2 red and
blue marker cores in each layer,
remaining cores black.
7, 12, 19 core 2.5mm2 red and blue
marker cores in each layer, remaining
cores yellow.
• Solid tinned copper CPC
• Aluminium laminate tape bonded to:
• Low smoke zero halogen sheath
Type LTS3 to BS7655 (red or white).
• Fire resistant to IEC60331 and categories
A, B, C, S, W, X and Z of BS6387.
• Flame retardant to BS4066 Part 1.
• Meets BS7622 and IEC 61034 3m
cube smoke emission test.
• Temp Rating: 700C max conductor
operating temperature.
• Voltage Rating: 300/500V
Unarmoured fire resistant cable for use
in fixed wiring installations where it is
necessary for the cable to retain circuit
integrity in the event of a fire, e.g.
emergency services, alarm systems,
lighting.
FP200® is a registered trade name of
Pirelli Cables.
A P P L I C A T I O N S P E C I F I C A T I O N S
A3BC-0210 2 1.0 1 1.0 1 0.6 7.5 65 50
A3BC-0215 2 1.5 1 1.5 1 0.6 8.0 85 50
A3BC-0225 2 2.5 2 2.5 2 0.6 9.0 115 60
A3BC-0240 2 4 2 4 2 0.6 11.1 165 70
A3BC-0310 3 1.0 1 1.0 1 0.6 8.0 80 50
A3BC-0315 3 1.5 1 1.5 1 0.6 9.0 105 60
A3BC-0325 3 2.5 2 2.5 2 0.6 10.1 150 70
A3BC-0340 3 4 2 4 2 0.6 12.1 210 80
A3BC-0410 4 1.0 1 1.0 1 0.6 8.5 100 60
A3BC-0415 4 1.5 1 1.5 1 0.6 10.1 130 70
A3BC-0425 4 2.5 2 2.5 2 0.6 11.1 180 70
A3BC-0440 4 4 2 4 2 0.6 13.1 255 80
A3BC-0710 7 1.0 1 0.5 1 0.6 10.6 140 70
A3BC-0715 7 1.5 1 0.5 1 0.6 11.1 180 70
A3BC-1215 12 1.5 1 0.5 1 0.6 15.2 310 100
A3BC-1915 19 1.5 1 0.5 1 0.6 17.4 455 110
A3BC-0725 7 2.5 2 0.5 1 0.6 13.7 285 90
A3BC-1225 12 2.5 2 0.5 1 0.6 17.9 470 110
A3BC-1925 19 2.5 2 0.5 1 0.6 21.4 720 130
®
1POWER & WIRING CABLES
No. Nominal Conductor Nominal Conductor Insulation Nom Approx Min Anixter of Conductor Class C.P.C. Class Thickness O/D Weight BendingPart No. Cores Area Area Radius
(fixed bend)mm2 mm2 mm mm kg/km mm
1:45
For further technical information see page 1:110.For white sheath add suffix -01, for red sheath add -03 to part number.
1:46
POWER & WIRING CABLES1
®
FP200 Gold® Fire Resistant Cable Incorporating circuit protective conductor (CPC) 300/500 Volts
• In accordance with BS7629 Part 1.
• BASEC Approved.
• Conductors: Solid Class 1 or stranded
Class 2 copper conductors to BS6360.
• Insulation: High impact and moisture
resistant Insudite™ insulation
• Core identification:
2 core - red, black
3 core - red, yellow, blue
4 core - red, yellow, blue, black
7, 12, 19 core red and blue marker
cores in each layer, remaining cores
white. In addition cores will be numbered.
• Solid or stranded tinned copper CPC
(full size)
• Aluminium laminate tape bonded to:
• Red Low smoke zero halogen sheath
Type LTS3 to BS7655.
• Fire resistant to IEC60331 and categories
A, B, C, S, W, X and Z of BS6387.
• Flame retardant to BS4066 Part 1.
• Meets BS7622 and IEC 61034 3m
cube smoke emission test.
• Temp Rating: 700C max conductor
operating temperature.
• Voltage Rating: 300/500V
• When sheath is terminated at entry,
900C rating for insulation is acceptable.
Unarmoured fire resistant cable for use
in fixed wiring installations where it is
necessary for the cable to retain circuit
integrity in the event of a fire, e.g.
emergency services, alarm systems,
lighting.
Incorporating high impact and moisture
resistant insulation which does not
require additional sleeving. Due to
moisture resistance of material, pot seals
are not required during termination.
FP200 Gold® and Insudite™ are
registered trade name/marks of Pirelli
Cables.
A P P L I C A T I O N S P E C I F I C A T I O N S
1:47
1POWER & WIRING CABLES
®
A3BC-
0215G-03 2 1.5 1/1.38 0.7 9.3 115 60
0225G-03 2 2.5 7/0.67 0.8 11.0 164 70
0240G-03 2 4 7/0.85 0.8 13.2 238 85
0315G-03 3 1.5 1/1.38 0.7 9.8 142 65
0325G-03 3 2.5 7/0.67 0.8 12.0 212 75
0340G-03 3 4 7/0.85 0.8 14.0 301 90
0415G-03 4 1.5 1/1.38 0.7 10.5 169 70
0425G-03 4 2.5 7/0.67 0.8 13.2 264 70
No. Nominal Nominal Insulation Nom Approx Min Anixter of Conductor Conductor Thickness O/D Weight BendingPart No. Cores Area Stranding Radius
(fixed bend)mm2 #/mm mm mm kg/km mm
For further technical information see page 1:110
1:48
POWER & WIRING CABLES1
®
A P P L I C A T I O N S P E C I F I C A T I O N S
Firetuf® Fire Resistant Cable Incorporating circuit protective conductor (CPC) 300/500 Volts
• In accordance with BS7629 Part 1.• BASEC Approved.• Conductors: Solid Class 1 or stranded
Class 2 copper conductors to BS6360.• Insulation: Silicone rubber insulation
type EI2 to BS7655• Core identification:
2 core - red, black3 core - red, yellow, blue4 core - red, yellow, blue, black7, 12, 19 core red and blue marker cores in each layer, remaining cores black.
• Woven glass tape to BS EN 61067 • Tnned copper CPC (Class 1, 2 or 5)
under and in contact with aluminium/ mylar tape.
• Low smoke zero halogen sheath Type LTS3 to BS7655 (red or white).
• Fire resistant to IEC60331 and categories A, B, C, S, W, X and Z ofBS6387.
• Flame retardant to BS4066 Part 1.• Meets BS7622 and IEC 61034 3m
cube smoke emission test.• Temp Rating: 700C max conductor
operating temperature.• Voltage Rating: 300/500V
Unarmoured fire resistant cable for use
in fixed wiring installations where it is
necessary for the cable to retain circuit
integrity in the event of a fire, e.g.
emergency services, alarm systems,
lighting.
Firetuf® is a registered trade name of
Delta Crompton Cables.
1:49
1POWER & WIRING CABLES
®
Solid ConductorsA3BC-0210FT 2 1.0 1/1.13 1.0 1/1.13 0.6 7.0 83 50A3BC-0215FT 2 1.5 1/1.38 1.5 1/1.38 0.7 7.9 110 50A3BC-0225FT 2 2.5 1/1.78 2.5 1/1.78 0.8 9.3 160 60
A3BC-0310FT 3 1.0 1/1.13 1.0 1/1.13 0.6 7.3 91 50A3BC-0315FT 3 1.5 1/1.38 1.5 1/1.38 0.7 8.3 128 50A3BC-0325FT 3 2.5 1/1.78 2.5 1/1.78 0.8 9.9 160 60
A3BC-0410FT 4 1.0 1/1.13 1.0 1/1.13 0.6 8.2 115 50A3BC-0415FT 4 1.5 1/1.38 1.5 1/1.38 0.7 9.5 160 60A3BC-0425FT 4 2.5 1/1.78 2.5 1/1.78 0.8 11.3 235 70
A3BC-0710FT 7 1.0 1/1.13 1.0 32/0.2 0.6 10.5 175 70A3BC-1210FT 12 1.0 1/1.13 1.0 32/0.2 0.6 13.5 275 80A3BC-1910FT 19 1.0 1/1.13 1.0 32/0.2 0.6 15.7 405 90
A3BC-0715FT 7 1.5 1/1.38 1.5 30/0.25 0.7 12.2 250 70A3BC-1215FT 12 1.5 1/1.38 1.5 30/0.25 0.7 15.2 390 100A3BC-1915FT 19 1.5 1/1.38 1.5 30/0.25 0.7 18.2 560 110
A3BC-0725FT 7 2.5 1/1.78 2.5 50/0.25 0.8 14.6 375 90A3BC-1225FT 12 2.5 1/1.78 2.5 50/0.25 0.8 19.5 610 120A3BC-1925FT 19 2.5 1/1.78 2.5 50/0.25 0.8 22.8 900 140Stranded ConductorsA3BC-0215FTQ 2 1.5 7/0.53 1.5 7/0.53 0.7 8.4 125 60A3BC-0225FTQ 2 2.5 7/0.67 2.5 7/0.67 0.8 9.7 175 60A3BC-0240FT 2 4.0 7/0.85 4.0 7/0.85 0.8 11.1 243 70
A3BC-0315FTQ 3 1.5 7/0.53 1.5 7/0.53 0.7 8.9 142 60A3BC-0325FTQ 3 2.5 7/0.67 2.5 7/0.67 0.8 10.6 210 70A3BC-0340FT 3 4.0 7/0.85 4.0 7/0.85 0.8 12.2 297 80
A3BC-0415FTQ 4 1.5 7/0.53 1.5 7/0.53 0.7 10.2 177 70A3BC-0425FTQ 4 2.5 7/0.67 2.5 7/0.67 0.8 12.3 265 80A3BC-0440FT 4 4.0 7/0.85 4.0 7/0.85 0.8 13.8 365 90
A3BC-0715FTQ 7 1.5 7/0.53 1.5 30/0.25 0.7 12.9 275 80A3BC-0725FTQ 7 2.5 7/0.67 2.5 50/0.25 0.8 15.0 400 90
A3BC-1215FTQ 12 1.5 7/0.53 1.5 30/0.25 0.7 16.7 427 110A3BC-1225FTQ 12 2.5 7/0.67 2.5 50/0.25 0.8 19.8 640 120
A3BC-1915FTQ 19 1.5 7/0.53 1.5 30/0.25 0.7 19.4 617 120A3BC-1925FTQ 19 2.5 7/0.67 2.5 50/0.25 0.8 23.1 930 140
No. Nominal Nominal Nominal Nominal Insulation Nom Approx Min Anixter of Conductor Conductor C.P.C. C.P.C. Thickness O/D Weight BendingPart No. Cores Area Stranding Area Stranding Radius
(fixed bend)mm2 #/mm mm2 #/mm mm mm kg/km mm
For further technical information see page 1:110.For white sheath add suffix -01, for red sheath add -03 to part number.
1:50
POWER & WIRING CABLES1
®
Fire Resistant Armoured Power Cable 600/1000 Volts
• In accordance with BS7846.
• BASEC Approved.
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Mica/glass tape (S)
• Insulation: XLPE insulation type GP8
to BS7655.
• Core identification:
2 core - red, black
3 core - red, yellow, blue
4 core - red, yellow, blue, black
5 core + above - number printed
• Inner Sheath: LSF inner sheath
Type LTS1 to BS7655.
• Mild galvanised steel wires to BSEN10257-1
• Outer Sheath: Black LSF outer
sheath Type LTS1 to BS7655.
• Fire resistant to IEC60331 and
category CWZ of BS6387.
• Flame retardant to BS4066 Part 3
Category A (NMV7).• Meets BS7622 and IEC 61034 3m
cube smoke emission test.
• Temp Rating: 900C max conductor
operating temperature.
• Voltage Rating: 600/1000V
Armoured fire resistant cable for use in
fixed wiring installations where it is
necessary for the cable to retain circuit
integrity in the event of a fire, e.g. emergency
services, alarm systems, lighting, etc.,
and in situations where power must be
maintained to allow controlled
closedown of equipment.
A P P L I C A T I O N S P E C I F I C A T I O N S
A2EF-
020015-02 2 1.5* 0.6 8.6 0.9 13.4 313 90
020025-02 2 2.5* 0.7 9.9 0.9 14.6 384 90
020040-02 2 4.0* 0.7 11.1 0.9 15.8 434 100
020060-02 2 6.0* 0.7 12.2 0.9 16.9 505 110
020100-02 2 10* 0.7 14.1 0.9 19.1 808 120
020160-02 2 16† 0.7 16.3 1.25 21.3 949 130
020250-02 2 25† 0.9 19.3 1.25 24.6 1263 150
020350-02 2 35† 0.9 22.0 1.6 27.5 1737 170
020500-02 2 50// 1.0 20.0 1.6 27.0 1826 220
020700-02 2 70 1.1 23.0 1.6 30.3 2342 250
020950-02 2 95 1.1 25.5 2.0 33.8 3234 280
021200-02 2 120 1.2 28.5 2.0 37.0 4064 300
021500-02 2 150 1.4 31.2 2.0 40.0 4668 320
021850-02 2 185 1.6 35.0 2.5 45.0 5974 360
022400-02 2 240 1.7 39.5 2.5 50.0 7614 400
023000-02 2 300 1.8 44.0 2.5 54.5 8967 440
024000-02 2 400 2.0 49.0 2.5 60.0 10930 480
A2EF-
030015-02 3 1.5* 0.6 9.2 0.9 13.9 343 90
030025-02 3 2.5* 0.7 10.5 0.9 15.2 414 100
030040-02 3 4.0* 0.7 11.8 0.9 16.5 505 100
030060-02 3 6.0* 0.7 13.1 0.9 17.8 778 110
030100-02 3 10* 0.7 15.1 1.25 20.0 909 120
030160-02 3 16† 0.7 17.5 1.25 22.7 1192 140
030250-02 3 25† 0.9 21.2 1.6 26.7 1737 170
030350-02 3 35† 0.9 23.6 1.6 29.3 2151 180
030500-02 3 50 // 1.0 23.5 1.6 30.6 2516 250
030700-02 3 70 1.1 27.0 1.6 34.3 3273 280
030950-02 3 95 1.1 30.5 2.0 39.1 4513 320
031200-02 3 120 1.2 33.8 2.0 42.6 5533 350
031500-02 3 150 1.4 37.6 2.5 47.6 6912 390
031850-02 3 185 1.6 41.9 2.5 52.0 8306 420
032400-02 3 240 1.7 46.5 2.5 57.2 10504 460
033000-02 3 300 1.8 51.8 2.5 62.8 12431 510
034000-02 3 400 2.0 56.2 2.5 70.0 15280 560
1:51
1POWER & WIRING CABLES
®
No. Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
Continued overleaf. . .
®
A2EF-
040015-02 4 1.5* 0.6 10.0 0.9 14.8 394 90
040025-02 4 2.5* 0.7 11.5 0.9 16.3 475 100
040040-02 4 4.0* 0.7 13.1 0.9 17.8 586 110
040060-02 4 6.0* 0.7 14.4 1.25 20.1 828 130
040100-02 4 10* 0.7 16.7 1.25 22.4 1071 140
040160-02 4 16† 0.7 19.3 1.25 25.2 1424 160
040250-02 4 25† 0.9 23.5 1.6 29.6 2111 180
040350-02 4 35† 0.9 26.2 1.6 32.6 2616 200
040500-02 4 50 // 1.0 26.4 1.6 33.7 3161 270
040700-02 4 70 1.1 30.6 2.0 39.1 4430 320
040950-02 4 95 1.1 34.4 2.0 43.2 5706 350
041200-02 4 120 1.2 38.4 2.5 48.4 7422 390
041500-02 4 150 1.4 42.6 2.5 52.9 8797 430
041850-02 4 185 1.6 47.1 2.5 57.8 10629 470
042400-02 4 240 1.7 53.5 2.5 64.5 13556 520
043000-02 4 300 1.8 59.0 2.5 69.9 15953 560
044000-02 4 400 2.0 65.9 2.5 79.9 20372 640
A2EF-
070015-02 7 1.5* 0.6 13.0 0.9 18.0 561 110
120015-02 12 1.5* 0.6 17.5 1.25 23.0 962 140
190015-02 19 1.5* 0.6 19.9 1.25 26.0 1217 160
270015-02 27 1.5* 0.6 24.5 1.6 31.0 1722 190
370015-02 37 1.5* 0.6 27.5 1.6 34.0 2132 210
1:52
POWER & WIRING CABLES1
Fire Resistant Armoured Power Cable 600/1000 Volts Continued. . .
No. Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
®
A2EF-
070025-02 7 2.5* 0.7 13.9 0.9 18.5 638 120
120025-02 12 2.5* 0.7 18.0 1.25 24.0 1086 150
190025-02 19 2.5* 0.7 22.0 1.6 28.5 1641 180
270025-02 27 2.5* 0.7 26.5 1.6 33.5 2122 210
370025-02 37 2.5* 0.7 30.0 1.6 37.0 2605 230
A2EF-
070040-02 7 4.0* 0.7 15.5 1.25 21.0 922 130
120040-02 12 4.0* 0.7 21.0 1.6 27.0 1593 170
190040-02 19 4.0* 0.7 24.5 1.6 31.5 2076 190
270040-02 27 4.0* 0.7 30.0 1.6 37.0 2732 230
370040-02 37 4.0* 0.7 34.0 2.0 42.0 3751 260
1POWER & WIRING CABLES
1:53
*Circular stranded conductors.// Cables having conductors of nominal area 50mm2 and above will have shaped stranded conductors† Circular or circular compacted stranded conductors.
For more technical information refer to page 1:112.For conductor and armour resistances refer to page 13:32For gross cross-sectional area of armour refer to page 13:35For conductor short-circuit ratings refer to page 13:29For armour short-circuit ratings refer to page 13:37
Dimensions are based on Pirelli BS7846 Armoured cables.
NB: 25mm2 and 35mm2 cables may be supplied with SHAPED conductors. Detailson dimensions, weights etc available on request.
No. Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
1:54
POWER & WIRING CABLES
®
Single Core XLPE/PVC Power Cable3.8/6.6, 6.35/11 and 8.7/15 kV
Power cable for use on fixed installations
Not suitable for direct burial.
• In accordance with BS6622.
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Extruded semi-conducting layer.
• Insulation: XLPE insulation.
• Extruded semi-conducting layer.
• Screen: Plain copper tape screen
• Outer Sheath: PVC outer sheath
Type 9 to BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 900C max conductor
operating temperature.
• Voltage Rating: 3800/6600V,
6350/11000V, 8700/15000V
For black sheath add suffix -02, for red sheath -03.For further technical information refer to page 1:118.
A P P L I C A T I O N S P E C I F I C A T I O N S
1
1:55
1POWER & WIRING CABLES
®
Number Nominal Insulation Nom Approx Min BendingAnixter of Conductor Thickness O/D Weight RadiusPart No. Cores Area (mm) (mm) kg/km (fixed bend)
(mm2) During AdjacentInstallation to joints and
Termination
3800/6600V Cables
A2CJ-1050U 1 50 2.5 20.0 800 400 300
A2CJ-1070U 1 70 2.5 22.0 1000 440 330
A2CJ-1095U 1 95 2.5 23.7 1300 480 360
A2CJ-1120U 1 120 2.5 25.5 1600 510 390
A2CJ-1150U 1 150 2.5 26.8 1900 540 410
A2CJ-1185U 1 185 2.5 28.8 2200 580 440
A2CJ-1240U 1 240 2.6 31.2 2800 630 470
A2CJ-1300U 1 300 2.8 34.2 3500 690 520
A2CJ-1400U 1 400 3.0 37.7 4300 760 570
A2CJ-1500U 1 500 3.2 41.3 5400 830 620
A2CJ-1630U 1 630 3.2 44.9 6700 900 680
6350/11000V Cable
A2CT-1050U 1 50 3.4 22.2 900 450 340
A2CT-1070U 1 70 3.4 24.0 1100 480 360
A2CT-1095U 1 95 3.4 26.0 1400 520 390
A2CT-1120U 1 120 3.4 27.5 1700 550 420
A2CT-1150U 1 150 3.4 29.0 2000 580 440
A2CT-1185U 1 185 3.4 30.8 2400 620 470
A2CT-1240U 1 240 3.4 33.2 2900 670 500
A2CT-1300U 1 300 3.4 35.7 3500 720 540
A2CT-1400U 1 400 3.4 38.6 4400 780 580
A2CT-1500U 1 500 3.4 41.8 5400 840 630
A2CT-1630U 1 630 3.4 45.4 6800 910 690
8700/15000V Cables
A2DE-1050U 1 50 4.5 24.6 1000 500 370
A2DE-1070U 1 70 4.5 26.7 1200 540 410
A2DE-1095U 1 95 4.5 28.6 1500 580 430
A2DE-1120U 1 120 4.5 30.1 1800 610 460
A2DE-1150U 1 150 4.5 31.2 2100 630 470
A2DE-1185U 1 185 4.5 33.4 2500 670 510
A2DE-1240U 1 240 4.5 35.8 3100 720 540
A2DE-1300U 1 300 4.5 38.3 3700 770 580
A2DE-1400U 1 400 4.5 41.3 4600 830 620
A2DE-1500U 1 500 4.5 44.4 5600 890 670
A2DE-1630U 1 630 4.5 48.0 7000 960 720
1:56
POWER & WIRING CABLES1
®
Single Core XLPE/PVC /AWA/PVC PowerCable 3.8/6.6, 6.35/11 and 8.7/15 kV
Power cable for use on fixed installations,
indoor, outdoor or direct burial.
• In accordance with BS6622
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Extruded semi-conducting layer.
• Insulation: XLPE insulation.
• Extruded semi-conducting layer.
• Plain copper tape screen.
• Inner Sheath: PVC inner sheath
Type 9 to BS7655.
• Aluminium wires to BS2627.
• Outer Sheath: PVC outer sheath
Type 9 to BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 900C max conductor
operating temperature.
• Voltage Rating: 3800/6600,
6350/11000, & 8700/15000V
For black sheath add suffix -02, for red sheath -03.For further technical information refer to page 1:118.
A P P L I C A T I O N S P E C I F I C A T I O N S
3800/6600V Cables
A2CJ-1050 1 50 2.5 18.9 1.6 25.7 1200 390 310
A2CJ-1070 1 70 2.5 20.7 1.6 27.5 1400 420 330
A2CJ-1095 1 95 2.5 22.4 1.6 29.4 1800 450 360
A2CJ-1120 1 120 2.5 23.9 1.6 30.9 2000 470 380
A2CJ-1150 1 150 2.5 25.2 1.6 32.4 2300 490 390
A2CJ-1185 1 185 2.5 27.0 2.0 35.0 2800 530 420
A2CJ-1240 1 240 2.6 29.4 2.0 37.6 3500 570 460
A2CJ-1300 1 300 2.8 32.4 2.0 40.8 4200 620 490
A2CJ-1400 1 400 3.0 35.5 2.0 44.1 5100 670 530
A2CJ-1500 1 500 3.2 39.0 2.5 49.0 6400 740 590
A2CJ-1630 1 630 3.2 42.6 2.5 52.8 7400 800 640
6350/11000V Cable
A2CT-1050 1 50 3.4 20.9 1.6 27.7 1300 420 340
A2CT-1070 1 70 3.4 22.7 1.6 29.7 1600 450 360
A2CT-1095 1 95 3.4 24.4 1.6 31.4 1900 480 390
A2CT-1120 1 120 3.4 25.9 1.6 33.1 2200 500 400
A2CT-1150 1 150 3.4 27.2 2.0 35.4 2600 540 430
A2CT-1185 1 185 3.4 29.0 2.0 37.2 3000 560 450
A2CT-1240 1 240 3.4 31.4 2.0 39.8 3600 600 480
A2CT-1300 1 300 3.4 33.7 2.0 42.3 4300 640 510
A2CT-1400 1 400 3.4 36.4 2.0 45.2 5200 680 550
A2CT-1500 1 500 3.4 39.5 2.5 49.5 6500 750 600
A2CT-1630 1 630 3.4 43.1 2.5 53.3 7900 800 640
8700/15000V Cables
A2DE-1050 1 50 4.5 23.3 1.6 30.3 1400 460 370
A2DE-1070 1 70 4.5 25.1 1.6 32.1 1700 490 390
A2DE-1095 1 95 4.5 26.8 2.0 34.8 2100 530 420
A2DE-1120 1 120 4.5 28.3 2.0 36.5 2400 550 440
A2DE-1150 1 150 4.5 29.6 2.0 37.8 2700 570 460
A2DE-1185 1 185 4.5 31.6 2.0 40.0 3200 600 480
A2DE-1240 1 240 4.5 33.8 2.0 42.4 3800 640 510
A2DE-1300 1 300 4.5 36.1 2.0 44.7 4500 680 540
A2DE-1400 1 400 4.5 39.0 2.5 49.0 5600 740 590
A2DE-1500 1 500 4.5 41.9 2.5 52.1 6700 790 630
A2DE-1630 1 630 4.5 45.5 2.5 55.9 8200 840 680
1:57
1POWER & WIRING CABLES
®
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size mm kg/km mm
mm2 mm mm mm During AdjacentInstallation to joints and
Termination
A P P L I C A T I O N S P E C I F I C A T I O N S
1:58
POWER & WIRING CABLES1
®
Three Core XLPE/PVC Power Cable3.8/6.6, 6.35/11 and 8.7/15 kV
Multicore power cable for use on fixed
installations. Indoor or outdoor use.
Not suitable for direct burial.
• In accordance with BS6622
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Extruded semi-conducting layer.
• Insulation: XLPE insulation.
• Extruded semi-conducting layer.
• Plain copper tape screen.
• Sheath: PVC outer sheath Type 9 to
BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 900C max conductor
operating temperature.
• Voltage Rating: 3800/6600,
6350/11000, & 8700/15000V
For black sheath add suffix -02, for red sheath -03 to part number.For further technical information refer to page 1:118.
1:59
1POWER & WIRING CABLES
®
Number Nominal Insulation Nom Approx Min BendingAnixter of Conductor Thickness O/D Weight RadiusPart No. Cores Area (fixed bend) mm
mm2 mm mm kg/km During AdjacentInstallation to joints and
Termination
3800/6600V Cables
A2CM-3016U 3 16 2.5 33.3 1300 500 400
A2CM-3025U 3 25 2.5 35.8 1700 540 430
A2CM-3035U 3 35 2.5 38.2 2000 580 460
A2CM-3050U 3 50 2.5 40.9 2600 620 500
A2CM-3070U 3 70 2.5 44.9 3300 680 540
A2CM-3095U 3 95 2.5 48.8 4200 740 590
A2CM-3120U 3 120 2.5 52.2 5000 790 630
A2CM-3150U 3 150 2.5 55.2 5800 830 670
A2CM-3185U 3 185 2.5 59.4 7100 900 720
A2CM-3240U 3 240 2.6 65.0 9000 980 780
A2CM-3300U 3 300 2.8 71.4 10900 1080 860
A2CM-3400U 3 400 3.0 78.8 13800 1190 950
6350/11000V Cable
A2CW-3016U 3 16 3.4 38.0 1700 570 460
A2CW-3025U 3 25 3.4 40.3 2000 610 490
A2CW-3035U 3 35 3.4 42.8 2400 650 520
A2CW-3050U 3 50 3.4 45.4 2900 690 550
A2CW-3070U 3 70 3.4 49.4 3600 750 600
A2CW-3095U 3 95 3.4 53.5 4500 810 650
A2CW-3120U 3 120 3.4 57.0 5400 860 690
A2CW-3150U 3 150 3.4 60.0 6300 900 720
A2CW-3185U 3 185 3.4 64.1 7500 970 770
A2CW-3240U 3 240 3.4 69.1 9300 1040 830
A2CW-3300U 3 300 3.4 74.5 11200 1120 900
A2CW-3400U 3 400 3.4 80.7 14000 1220 970
8700/15000V Cables
A2DH-3025U 3 25 4.5 46.0 2400 690 560
A2DH-3035U 3 35 4.5 48.4 2800 730 590
A2DH-3050U 3 50 4.5 50.9 3200 770 620
A2DH-3070U 3 70 4.5 55.0 4000 830 660
A2DH-3095U 3 95 4.5 59.0 5000 890 710
A2DH-3120U 3 120 4.5 62.4 5900 940 750
A2DH-3150U 3 150 4.5 65.4 6800 990 790
A2DH-3185U 3 185 4.5 69.5 8000 1050 840
A2DH-3240U 3 240 4.5 74.6 9900 1120 900
A2DH-3300U 3 300 4.5 80.1 11900 1210 970
A2DH-3400U 3 400 4.5 86.3 14600 1300 1040
A P P L I C A T I O N S P E C I F I C A T I O N S
1:60
POWER & WIRING CABLES1
®
Three Core XLPE/PVC/SWA/PVC PowerCable 3.8/6.6, 6.35/11 and 8.7/15 kV
• In accordance with BS6622.
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Extruded semi-conducting layer.
• Insulation: XLPE insulation.
• Extruded semi-conducting layer.
• Plain copper tape screen.
• Inner Sheath: PVC inner sheath
Type 9 to BS7655.
• Mild galvanised steel wires to BSEN10257-1
• Outer Sheath: PVC outer sheath
Type 9 to BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 900C max conductor
operating temperature.
• Voltage Rating: 3800/6600,
6350/11000, & 8700/15000V
Multicore power cable for use on fixed
installations. Indoor or outdoor use, or
for direct burial.
For black sheath add suffix -02, for red sheath -03 to part number.For further technical information refer to page 1:118.
1:61
1POWER & WIRING CABLES
®
Number Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Under Wire O/D Weight RadiusPart No. Cores Area Armour Size mm
mm2 mm mm mm mm kg/km During AdjacentInstallation to joints and
Termination
3800/6600V Cables
A2CM-3016 3 16 2.5 31.3 2.0 39.7 2900 480 400
A2CM-3025 3 25 2.5 33.6 2.0 42.0 3300 510 420
A2CM-3035 3 35 2.5 35.8 2.0 44.4 3700 540 440
A2CM-3050 3 50 2.5 38.4 2.5 48.4 4900 590 490
A2CM-3070 3 70 2.5 42.2 2.5 52.4 5800 630 530
A2CM-3095 3 95 2.5 46.1 2.5 56.5 6900 680 570
A2CM-3120 3 120 2.5 49.5 2.5 60.1 7900 730 610
A2CM-3150 3 150 2.5 52.2 2.5 63.1 8900 760 640
A2CM-3185 3 185 2.5 56.4 2.5 67.4 10400 810 680
A2CM-3240 3 240 2.6 61.8 2.5 73.2 12700 880 740
A2CM-3300 3 300 2.8 68.0 3.15 81.3 16000 980 820
A2CM-3400 3 400 3.0 75.1 3.15 88.8 19400 1070 890
6350/11000V Cables
A2CW-3016 3 16 3.4 35.6 2.0 44.2 3400 540 450
A2CW-3025 3 25 3.4 38.1 2.5 47.9 4300 580 480
A2CW-3035 3 35 3.4 40.3 2.5 50.3 4700 610 510
A2CW-3050 3 50 3.4 42.9 2.5 53.1 5500 640 540
A2CW-3070 3 70 3.4 46.7 2.5 57.1 6400 690 580
A2CW-3095 3 95 3.4 50.6 2.5 61.2 7500 740 620
A2CW-3120 3 120 3.4 54.0 2.5 65.0 8600 780 650
A2CW-3150 3 150 3.4 56.8 2.5 68.0 9600 820 680
A2CW-3185 3 185 3.4 60.9 2.5 72.3 11200 870 730
A2CW-3240 3 240 3.4 65.9 3.15 79.0 14200 950 790
A2CW-3300 3 300 3.4 71.0 3.15 84.5 16500 1020 850
A2CW-3400 3 400 3.4 77.0 3.15 90.9 19700 1100 910
8700/15000V Cables
A2DH-3025 3 25 4.5 43.5 2.5 53.7 5000 650 540
A2DH-3035 3 35 4.5 45.7 2.5 56.1 5500 680 570
A2DH-3050 3 50 4.5 48.2 2.5 58.8 6100 710 590
A2DH-3070 3 70 4.5 52.1 2.5 62.9 7100 760 630
A2DH-3095 3 95 4.5 56.0 2.5 67.0 8300 810 670
A2DH-3120 3 120 4.5 59.4 2.5 70.6 9400 850 710
A2DH-3150 3 150 4.5 62.2 2.5 73.6 10500 890 740
A2DH-3185 3 185 4.5 66.3 3.15 79.4 12900 960 800
A2DH-3240 3 240 4.5 71.2 3.15 84.7 15200 1020 850
A2DH-3300 3 300 4.5 76.4 3.15 90.1 17600 1090 910
A2DH-3400 3 400 4.5 82.4 3.15 96.7 20800 1170 970
1:62
POWER & WIRING CABLES1
®
Three Core PILC/SWA/PVC Power Cable6350/11000 Volts "BELTED" M.I.N.D.
• In accordance with BS6480.
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• 2 layers semi-conducting carbon
paper tapes.
• Insulating paper tape(s).
• Core identification:
white numbers on outer layer of
insulating paper(s).
• Paper belt.
• All insulation mass impregnated non
draining.
• Lead sheath to BS801
• 2 carbon papers + hessian tape
textile bedding.
• Mild galvanised steel wires to BSEN10257-1
• PVC outer sheath Type TM.1 to BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 650C max conductor
operating temperature.
• Voltage Rating: 6350/11000 V
For fixed applications, supplying public
and industrial distribution systems.
Suitable for direct burial.
A P P L I C A T I O N S P E C I F I C A T I O N S
1:63
1POWER & WIRING CABLES
®
No. Nominal Insulation Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Over Wire O/D Weight RadiusPart No. Cores Area (mm2) (mm) Lead Size (fixed bend)
Between Between mm mm mm kg/km mmConductors Conductors
& Sheath
A2-J03-0016C 3 16† 3.4 5.6 29.3 2.0 40.3 4300 490
A2-J03-0025C 3 25† 3.4 5.6 32.4 2.0 43.6 5230 530
A2-J03-0035C 3 35† 3.4 5.6 35.3 2.0 46.7 5890 570
A2-J03-0050C 3 50\\ 3.4 5.6 33.6 2.5 46.2 6620 560
A2-J03-0070C 3 70 3.4 5.6 36.9 2.5 49.7 7820 600
A2-J03-0095C 3 95 3.4 5.6 40.3 2.5 53.3 9240 640
A2-J03-0120C 3 120 3.4 5.6 43.0 2.5 56.2 10400 680
A2-J03-0150C 3 150 3.4 5.6 45.8 2.5 59.2 11770 720
A2-J03-0185C 3 185 3.4 5.6 49.2 2.5 62.8 13550 760
A2-J03-0240C 3 240 3.4 5.6 54.0 2.5 67.8 16390 820
A2-J03-0300C 3 300 3.4 5.6 58.3 3.15 73.6 19870 890
A2-J03-0400C 3 400 3.4 5.6 63.7 3.15 79.4 23700 960
\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.
For more technical information see page 1:124.
1:64
POWER & WIRING CABLES1
®
Three Core PICAS/PVC Power Cable6350/11000 Volts "BELTED" M.I.N.D. Aluminium Conductors
• In accordance with ESI* 09-12.
• Conductors: Stranded Class 2
aluminium conductors to BS6360.
• 2 layers semi-conducting carbon
paper tapes.
• Insulating paper tape(s).
• Core identification:
white numbers on outer layer of
insulating papers.
• Paper belt.
• Corrugated aluminium sheath.
• Red PVC outer sheath Type TM.1 to
BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 650C max conductor
operating temperature.
• Voltage Rating: 6350/11000 V
For fixed applications, supplying public
and industrial distribution systems.
Suitable for direct burial.
* ESI standards are now covered underEATS (Electricity Association TechnicalSpecification). Standard numberremains same i.e. EATS 09-12.
A P P L I C A T I O N S P E C I F I C A T I O N S
1:65
1POWER & WIRING CABLES
®
No. Nominal Insulation Diam Nom Approx Min BendingAnixter of Conductor Thickness Over O/D Weight RadiusPart No. Cores Area (mm2) (mm) Alum mm
Between Between Sheath mm kg/km During AdjacentConductors Conductors mm Install. to joints and
& Sheath terminations
A2EP-3095-03 3 95\\ 3.4 5.6 43.7 49.2 3400 600 500
A2EP-3185-03 3 185\\ 3.4 5.6 54.6 60.7 5200 750 600
A2EP-3300-03 3 300\\ 3.4 5.6 65.5 72.5 7500 900 700
\\ Shaped stranded conductors.
For more technical information see page 1:127.
1:66
POWER & WIRING CABLES1
®
Multi-Core XLPE/LC/PVC/SWA/PVC Power& Control Cable 600/1000 Volts to EEMUA 133 Spec.
• In accordance with BS5467 and
EEMUA 133.
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Insulation: XLPE insulation Type
GP8 to BS7655.
• Core identification:
2 core - red, black
3 core - red, yellow, blue
4 core - red, yellow, blue, black
5 core + above - number printed
• Lead sheath to BS801.
• Inner Sheath: PVC inner sheath
Type 9 to BS7655.
• Mild galvanised steel wires to BSEN10257-1
• Outer Sheath: Black PVC outer
sheath Type 9 to BS7655.
• Flame retardant to BS4066 Part 1.
• Temp Rating: 900C max conductor
operating temperature
• Voltage Rating: 600/1000V
• Also available up to 11000V.
Lead sheathed power and control
cables for use underground where
cables may be subject to solvent
penetration or corrosive attack.
A P P L I C A T I O N S P E C I F I C A T I O N S
1:67
1POWER & WIRING CABLES
®
Number Nominal Insulation Diam Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Over Under Wire O/D Weight RadiusPart No. Cores Area Lead Armour Size (fixed bend)
mm2 mm mm mm mm mm kg/km mm
A2EB-0015Q 2 1.5* 0.7 8.5 10.1 0.9 14.5 690 180
A2EB-0025Q 2 2.5* 0.7 9.6 11.2 0.9 15.8 772 190
A2EB-0040 2 4* 0.7 10.6 12.2 0.9 16.8 883 210
A2EB-0060 2 6* 0.7 11.8 13.4 0.9 18.2 1001 220
A2EB-0100 2 10* 0.7 13.7 15.3 0.9 20.1 1227 250
A2EB-0160 2 16† 0.7 16.1 17.7 1.25 23.2 1565 280
A2EB-0250 2 25† 0.9 19.8 21.4 1.25 27.1 2094 330
A2EB-0350 2 35† 0.9 22.3 24.3 1.6 30.9 2868 380
A2EB-0500 2 50\\ 1.0 19.3 21.3 1.6 28.1 2783 340
A2EB-0700 2 70 1.1 22.1 24.1 1.6 31.1 3566 380
A2EB-0950 2 95 1.1 24.7 27.1 2.0 35.1 4678 430
A2EB-1200 2 120 1.2 27.9 30.3 2.0 38.5 5641 470
A2EB-1500 2 150 1.4 31.0 33.4 2.0 41.8 6660 510
A2EB-1850 2 185 1.6 34.5 37.3 2.5 47.1 8457 570
A2EB-2400 2 240 1.7 39.5 42.3 2.5 52.3 10286 630
A2EB-3000 2 300 1.8 43.3 46.5 2.5 56.7 12245 690
A2EB-4000 2 400 2.0 48.8 52.0 2.5 62.6 15077 760
A2EC-0015Q 3 1.5* 0.7 9.0 10.6 0.9 15.0 744 180
A2EC-0025Q 3 2.5* 0.7 10.1 11.7 0.9 16.3 842 200
A2EC-0040 3 4* 0.7 11.3 12.9 0.9 17.5 967 210
A2EC-0060 3 6* 0.7 12.6 14.2 0.9 18.8 1122 230
A2EC-0100 3 10* 0.7 14.6 16.2 1.25 21.7 1493 270
A2EC-0160 3 16† 0.7 17.1 18.7 1.25 24.4 1813 300
A2EC-0250 3 25† 0.9 21.1 23.1 1.6 29.7 2673 360
A2EC-0350 3 35† 0.9 23.8 25.8 1.6 32.6 3338 400
A2EC-0500 3 50 1.0 22.6 24.6 1.6 31.4 3572 380
A2EC-0700 3 70 1.1 26.2 28.2 1.6 35.2 4639 430
A2EC-0950 3 95 1.1 29.5 31.9 2.0 40.1 6023 490
A2EC-1200 3 120 1.2 32.8 35.2 2.0 43.6 7392 530
A2EC-1500 3 150 1.4 36.5 39.3 2.5 48.9 9242 590
A2EC-1850 3 185 1.6 40.7 43.5 2.5 53.3 11054 640
A2EC-2400 3 240 1.7 45.9 48.7 2.5 58.9 13792 710
A2EC-3000 3 300 1.8 50.5 53.7 2.5 64.1 16519 770
A2EC-4000 3 400 2.0 56.7 59.9 2.5 70.7 20331 850
*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.
Continued overleaf. . .
®
A2ED-0015Q 4 1.5* 0.7 9.8 11.4 0.9 16.0 813 200
A2ED-0025Q 4 2.5* 0.7 11.0 12.6 0.9 17.2 934 210
A2ED-0040 4 4* 0.7 12.3 13.9 0.9 18.5 1089 230
A2ED-0060 4 6* 0.7 13.8 15.4 1.25 20.9 1402 260
A2ED-0100 4 10* 0.7 16.0 17.6 1.25 23.1 1710 280
A2ED-0160 4 16† 0.7 19.1 20.7 1.25 26.4 2191 320
A2ED-0250 4 25† 0.9 23.5 25.5 1.6 32.1 3204 390
A2ED-0350 4 35† 0.9 26.5 28.5 1.6 35.3 4043 430
A2ED-0500 4 50 // 1.0 25.5 27.5 1.6 34.5 4456 420
A2ED-0700 4 70 1.1 29.6 32.0 2.0 40.2 6160 490
A2ED-0900 4 95 1.1 33.4 35.8 2.0 44.2 7592 540
A2ED-1200 4 120 1.2 37.2 40.0 2.5 49.5 9802 600
A2ED-1500 4 150 1.4 41.5 44.3 2.5 54.1 11757 650
A2ED-1850 4 185 1.6 46.3 49.1 2.5 59.3 14117 720
A2ED-2400 4 240 1.7 52.2 55.4 2.5 65.8 17700 790
A2ED-3000 4 300 1.8 57.5 60.7 2.5 71.5 21173 860
A2ED-4000 4 400 2.0 64.7 68.3 3.15 81.0 27405 980
A3BT-C007Q 7 1.5* 0.7 11.5 13.1 0.9 17.7 1002 220
A3BT-C012Q 12 1.5* 0.7 15.0 16.6 1.25 22.3 1461 270
A3BT-C019Q 19 1.5* 0.7 17.5 19.1 1.25 24.8 1898 300
A3BT-C027Q 27 1.5* 0.7 21.2 23.2 1.6 30.0 2663 360
A3BT-C037Q 37 1.5* 0.7 23.9 25.9 1.6 32.7 3717 400
A3BU-C007Q 7 2.5* 0.7 13.1 14.7 0.9 19.3 1158 240
A3BU-C012Q 12 2.5* 0.7 17.1 18.7 1.25 23.9 1800 290
A3BU-C019Q 19 2.5* 0.7 20.3 22.3 1.6 28.9 2465 350
A3BU-C027Q 27 2.5* 0.7 24.5 26.5 1.6 33.3 3277 400
A3BU-C037Q 37 2.5* 0.7 27.7 29.7 1.6 36.7 3876 450
1:68
POWER & WIRING CABLES1 Multi-Core XLPE/LC/PVC/SWA/PVC Power
& Control Cable 600/1000 Volts
Continued. . .
Number Nominal Insulation Diam Diam Armour Nom Approx Min BendingAnixter of Conductor Thickness Over Under Wire O/D Weight RadiusPart No. Cores Area Lead Armour Size (fixed bend)
mm2 mm mm mm mm mm kg/km mm
*Circular stranded conductors.\\ Cables having conductors of nominal area 50mm2 and above have shaped stranded conductors.† Circular or circular compacted stranded conductors.
For more technical information see page 1:106.For conductor short-circuit ratings refer to page 13:29.
1:69
1POWER & WIRING CABLES
®
NB. Cables up to and including 16mm2 conductor size may be supplied with anextruded bedding under the lead sheath, leading to a variance in dimension andweights from those given. Details available upon request
POWER & WIRING CABLES
®
12kV PE/PVC Airfield Lighting Cable
For use in underground installations for
airfield lighting.
• In accordance with D.O.E.
(Department of the Environment)
Spec M&E 42 and BAA (British
Airports Authority) Spec *
ENG/2505/CEE 2kV only.
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Insulation: Polythene insulation Type
03 to BS6234.
• Sheath: PVC sheath Type TM.1 to
BS7655.
• Flame retardant to BS4066 Part 1.
• Various colours available upon
request.
• Temp Rating: 700C max conductor
operating temperature.
• Voltage Rating: 2000V/3300V/5000V.
* Embossing will state either M&E spec. or BAAspec. Standard stock is M&E spec.
1:70
A P P L I C A T I O N S P E C I F I C A T I O N S
AnixterPart No.
Numberof
Cores
ConductorStranding
#/mm
InsulationThickness
mm
NomO/Dmm
ApproxWeightkg/km
Min BendingRadius
(fixed bend)
VoltageRatingVolts
A3BB-1006 1 7/1.04 2.3 10.4 145 50 2000A3BB-2006 1 7/1.04 2.3 10.4 145 50 3300A3BB-5006 1 7/1.04 4.2 14.5 235 60 5000
All dimensions are nominal unless otherwise stated.
1POWER & WIRING CABLES
1:71
1:72
POWER & WIRING CABLES1
®
A P P L I C A T I O N S P E C I F I C A T I O N S
XLPE Power Cable for 400Hz Supply900C 600/1000V
Power cable for 400Hz use in fixed
installations, for use indoor, outdoor or
for direct burial.
E.g. Aircraft ground supply, converters,
etc.
NB. For direct buried applications, wire
armoured cable should be used.
• Generally in accordance with BS5467
or BS6724
• Conductors: Stranded Class 2 copper
conductors to BS6360.
• Insulation: XLPE insulation Type
GP8 to BS7655
• Core Identification:
Cores will be number printed
• Inner Sheath: LSF inner sheath to
BS6724 or PVC inner sheath Type 9
to BS7655
• Aluminium wires to BS2627 or plain
copper tape.
• Outer Sheath: Black LSF outer sheath
to BS6724 or PVC outer sheath Type 9
to BS7655.
• Flame retardant to BS4066 Part 1.
NB. Cables having LSF inner and
outer sheaths will be flame retardant
to BS4066 Part 3 Category C (IEC
60332 Category C) as a minimum NMV 1.5.
• Temp Rating: 900C max conductor
operating temperature.
• Voltage Rating: 600/1000V
1:73
1POWER & WIRING CABLES
®
Anixter No. Nom Insulation Daim Armour Nom Approx Min Bending
Part No. of Cond. Thickness Under Wire O/D Weight Radius
Cores Area Armour Size (fixed bend)
mm2 mm mm mm mm kg/km mm
XLPE/LSF/CU TAPE/LSF
A2EH-0350 7 35 0.9 29.2 0.1* 33.0 2900 200
XLPE/PVC/AWA/PVC
A2EK-0350 7 35 0.9 29.2 2.0 37.0 3300 230
XLPE/LSF/AWA/LSF
A2EL-0350 7 35 0.9 29.2 2.0 37.0 3300 230
* Indicates nominal thickness of copper tapeFor further technical information see page 1:128.For conductor short-circuit ratings refer to page 13:29.
1:74
POWER & WIRING CABLES1
®
A P P L I C A T I O N S P E C I F I C A T I O N S
Three Core Screened Power CablePVC Insulated Screened, PVC 600/1000V 700C Type MCCMK
For connection between frequency
convertor and motor on variable speed
drive systems. The screened cable
ensures that the radiated emissions
from the complete system meet the
requirements of EMC directive
89/336/EEC (amend 92/31/EEC), thus
ensuring operation of nearby radio,
telecommunication, medical equipment
and other devices are not affected. The
screen also offers immunity from other
electrical phenomena such as ESD,
fast transient bursts, radiating magnetic
fields etc. May also be used in
applications where mains cable must
be shielded to prevent disturbance on
nearby sensitive equipment. Screen
also provides low resistance path.
• In accordance with SFS4880
• Conductors: Solid Class 1 or stranded
Class 2 to BS6360/IEC60228
• Insulation: PVC insulation.
• Core Identification: Cores will be
numbered 1-3 in white ink on black
insulation
• Screening: Helically applied plain
copper tape and an open helix of
plain copper wires
• Outer Sheath: Black PVC
• Flame retardant to BS4066 Part 1
/IEC60332 Part 1
• Temp Rating: 700C max conductor
operating temperature.
• Voltage Rating: 600/1000V
AnixterPart No.
No.of
Cores
NomCond.Areamm2
Nom.Cond.
Stranding#/mm
InsulationThickness
mm
NomScreen
Areamm2
SheathThick-nessmm
NomO/Dmm
ApproxWeightkg/km
Min BendingRadius
(fixed bend)mm
A2EQ-030025-02 3 2.5 1/1.76 0.8 2.5 1.8 14.0 260 120030060-02 3 6.0 1/2.76 1.0 6.0 1.8 18.0 470 150030100-02 3 10* 7/1.35 1.0 10 1.8 21.0 700 170030160-02 3 16* 7/1.70 1.0 16 1.8 24.0 1050 200030250-02 3 25// 7/2.37 1.2 16 1.8 23.0 1190 190030350-02 3 35 7/2.74 1.2 16 1.8 25.0 1500 200030500-02 3 50 7/3.21 1.4 25 1.9 28.0 2010 230030950-02 3 95 19/2.60 1.6 50 2.2 37.0 3750 300031500-02 3 150 32/2.60 1.8 70 2.4 44.0 5640 360031850-02 3 185 37/2.60 2.0 95 2.6 49.0 7200 400
*Circular stranded conductors//Cables having conductors on nominal area of 25mm² and above have shapedstranded conductorsFor further technical information see page 1:130
Recommended by ABB for use on their ACS 600 & ACV range of frequencyconverters.
1POWER & WIRING CABLES
1:75
1:76
POWER & WIRING CABLES1
®
A P P L I C A T I O N S P E C I F I C A T I O N S
XVB-F2 Multicore Power Cable600/1000V XLPE/PVC 900C
XVB-F2 power cables are suitable for
use indoor, in cable ducts, etc. in
industrial and power plant applications.
For applications where mechanical
damage is not envisaged.
• In accordance with NBN-IEC502-NAD
• Conductors: Solid Class 1 (RE) or
stranded Class 2 (RM) to VDE 0295
(equivalent to IEC60228 and BS6360).
• Insulation: XLPE insulation Type
GP8 to BS7655/IEC 60502 Table 7.
• Core Identification:
2 core - blue, brown
3 core - green/yellow, blue, brown
4 core - green/yellow, blue, brown,
black
5 core + above - green/yellow +
remaining cores black insulation with
white printed numbers
• Outer Sheath: Grey (RAL7001) PVC
Type 9 to BS7655 and Type ST2 to
IEC60502
• Flame retardant to BS4066/IEC60332
Part 3 Category C (NMV1.5), VDE0472
Part 804 Test C and F2 compliant as
per NBN C30-004.
• Temp Rating: 900C max conductor
operating temperature.
• Voltage Rating: 600/1000V
1:77
1POWER & WIRING CABLES
®
Number Nominal Conductor Insulation Nom Approx Approx Min BendingAnixter of Conductor Class Thickness O/D Copper Cable RadiusPart No. Cores Area Weight Weight (fixed bend)
mm2 mm mm kg/km kg/km mm
B1FE-
020015-09 2 1.5 1 (RE) 0.7 9.0 29 118 50
020025-09 2 2.5 1 (RE) 0.7 9.9 48 155 50
030015J-09 3 1.5 1 (RE) 0.7 9.4 43 134 50
030025J-09 3 2.5 1 (RE) 0.7 10.3 72 177 60
040015J-09 4 1.5 1 (RE) 0.7 10.2 58 158 60
040025J-09 4 2.5 1 (RE) 0.7 11.2 96 215 60
040040J-09 4 4.0 1 (RE) 0.7 12.6 154 300 80
040060J-09 4 6.0 2 (RM) 0.7 13.8 230 393 90
040100J-09 4 10 2 (RM) 0.7 16.0 384 591 100
040160J-09 4 16 2 (RM) 0.7 20.2 614 936 130
040250J-09 4 25 2 (RM) 0.9 24.7 960 1432 150
050015J-09 5 1.5 1 (RE) 0.7 11.2 72 194 60
050025J-09 5 2.5 1 (RE) 0.7 12.1 120 255 80
050040J-09 5 4.0 1 (RE) 0.7 13.7 192 359 90
050060J-09 5 6.0 2 (RM) 0.7 15.0 288 450 90
050100J-09 5 10 2 (RM) 0.7 17.4 480 714 110
050160J-09 5 16 2 (RM) 0.7 22.3 768 1147 140
050250J-09 5 25 2 (RM) 0.9 27.3 1200 1760 170
070015J-09 7 1.5 1 (RE) 0.7 12.2 101 240 80
070025J-09 7 2.5 1 (RE) 0.7 13.3 168 323 80
For further technical information see page 1:132
For conductor short-circuit ratings refer to page 13:29
POWER & WIRING CABLES
1LSF Multicore Power & Control Cables
600/1000 Volts XLPE/LSF 90°C
•
•
Insulated and sheathed cable for
use in fixed applications. Not
suitable for direct burial. Especially
for use in areas where fire would
create dense smoke and toxic
fumes causing a major threat to life
and equipment.
•
•
•
•
•
•
•
•
•
SPECIFICATIONS
APPLICATIONGenerally in accordance with
HD/604/5G and IEC60502.
Meets the requirements of
various BNFL Caesar cable
types.
Conductors: Stranded Class 2
copper conductors to BS6360.
Insulation: XLPE insulation
Type GP8 to BS7655.
Core identification:
3 core - red, black, green/yellow
4 core - red, yellow, blue,
green/yellow
Inner covering: Extruded “easy
strip” LSZH.
Outer sheath: Black low smoke
zero halogen Type HM4 to
HD604/5G
Flame retardant to BS4066 Part
3 Category C.
Temperature Rating: 90°C max
conductor operating
temperature.
Voltage Rating: 600/1000V.
1:78
AnixterPart No.
Numberof
Cores
NominalConductor
Area
BNFLType
InsulationThickness
NomO/D
ApproxCable
Weight
Min BendingRadius
(fixed bend)mm2 mm mm kg/km mm
A3CE-030015J-02 3 1.5 P48 0.7 9.5 134 80030025J-02 3 2.5 P21 0.7 10.3 173 90030040J-02 3 4.0 P22 0.7 11.9 248 100030060J-02 3 6.0 P23 0.7 13.2 328 110030100J-02 3 10.0 P24 0.7 15.3 493 130030160J-02 3 16.0 P25 0.7 17.6 710 140
040025J-02 4 2.5 P26 0.7 11.3 207 90
For further technical information see page 1:135 of the cable handbook
For conductor short-circuit ratings refer to page 13:29 of the cable handbook
POWER & WIRING CABLES
11:79
1:80
POWER & WIRING CABLES
®
1
Conductor Reference Method 4 Reference Method 3 Referenced Method 1cross (enclosed in conduit (enclosed in conduit ("clipped direct")
Sectional in thermally on a wall or inarea insulating wall etc.) trunking etc.)
2 cables, 3 or 4 2 cables, 3 or 4 2 cables, 3 or 4single- cables single- cables single- cablesphase three- phase three- phase three-a.c or phase a.c. a.c or phase a.c. a.c or phase a.c.d.c. d.c. d.c. flat and
flat and touchingtouching or trefoil
1 2 3 4 5 6 7
mm2 A A A A A A1 11 10.5 13.5 12 15.5 14
1.5 14.5 13.5 17.5 15.5 20 182.5 20.0 18 24 21 27 254 26 24 32 28 37 336 34 31 41 36 47 4310 46 42 57 50 65 5916 61 56 76 68 87 7925 80 73 101 89 114 10435 99 89 125 110 141 12950 119 108 151 134 182 16770 151 136 192 171 234 21495 182 164 232 207 284 261120 210 188 269 239 330 303150 240 216 300 262 381 349185 273 245 341 296 436 400240 320 289 400 346 515 472300 367 328 458 394 594 545400 - - 546 467 694 634500 - - 626 533 792 723630 - - 720 611 904 826800 - - - - 1030 9431000 - - - - - 1058
Technical Information• Single Core PVC• Single Core PVC/PVC (300/500V)• Single Core PVC/PVC (6181Y Types - 600/1000V)• Single Core PVC/PVC (6381Y Types - 450/750V)
C U R R E N T - C A R R Y I N G
1:81
1POWER & WIRING CABLES
®
Referenced Method 11 Reference Method 12 (free air)(on a perforated cable Horizontal Vertical Trefoil
tray horizontal or flat flatvertical) spaced spaced
2 cables, 3 or 4 2 cables, 2 cables, 3 cablessingle- cables single- single- trefoil
phase a.c. three- phase phase three-or d.c. phase a.c. a.c. or a.c. or phase
flat flat and d.c. or d.c. or a.c.and touching 3 cables 3 cables
touching or trefoil three- three-phase a.c. phase a.c.
8 9 10 11 12
A A A A A- - - - -- - - - -- - - - -- - - - -- - - - -- - - - -- - - - -
126 112 146 130 110156 141 181 162 137191 172 219 197 167246 223 281 254 216300 273 341 311 264349 318 396 362 308404 369 456 419 356463 424 521 480 409549 504 615 569 485635 584 709 659 561732 679 852 795 656835 778 982 920 749953 892 1138 1070 8551086 1020 1265 1188 9711216 1149 1420 1337 1079
C A P A C I T Y ( A m p e r e s ) :
If cables are to be used in ambient air temperatures other than 300C the following rating factors
should be applied:
Ambient air temp 0C 25 30 35 40 45 50 55 60
Rating Factor 1.02 1.0 0.94 0.87 0.79 0.71 0.61 0.50
1:82
POWER & WIRING CABLES
®
1
V O L T A G E D R O P
2 cables - single phase a.c.
Conductor 2 Reference Reference Referencecross cables Methods 3 & 4 Methods 1 & 11 Method 12
sectional d.c. (Enclosed in (Clipped direct (Spaced*)area conduit etc in or on trays,
or on a wall) touching)1 2 3 4 5
mm2 mV mV mV mV
1 44 44 44 441.5 29 29 29 292.5 18 18 18 184 11 11 11 116 7.3 7.3 7.3 7.310 4.4 4.4 4.4 4.416 2.8 2.8 2.8 2.8
r x z r x z r x z
25 1.75 1.80 0.33 1.80 1.75 0.20 1.75 1.75 0.29 1.8035 1.25 1.30 0.31 1.30 1.25 0.195 1.25 1.25 0.28 1.3050 0.93 0.95 0.30 1.00 0.93 0.19 0.95 0.93 0.28 0.9770 0.63 0.65 0.29 0.72 0.63 0.185 0.66 0.63 0.27 0.6995 0.46 0.49 0.28 0.56 0.47 0.180 0.50 0.47 0.27 0.54
120 0.36 0.39 0.27 0.47 0.37 0.175 0.41 0.37 0.26 0.45150 0.29 0.31 0.27 0.41 0.30 0.175 0.34 0.29 0.26 0.39185 0.23 0.25 0.27 0.37 0.24 0.170 0.29 0.24 0.26 0.35240 0.18 0.195 0.26 0.33 0.185 0.165 0.25 0.185 0.25 0.31300 0.145 0.16 0.26 0.31 0.15 0.165 0.22 0.150 0.25 0.29
400 0.105 0.13 0.26 0.29 0.12 0.160 0.20 0.115 0.25 0.27500 0.086 0.11 0.26 0.28 0.098 0.155 0.185 0.093 0.24 0.26630 0.068 0.094 0.25 0.27 0.081 0.155 0.175 0.076 0.24 0.25800 0.053 - 0.068 0.150 0.165 0.061 0.24 0.251000 0.042 - 0.059 0.150 0.160 0.050 0.24 0.24
Technical Information• Single Core PVC• Single Core PVC/PVC (300/500V)• Single Core PVC/PVC (6181Y Types - 600/1000V)• Single Core PVC/PVC (6381Y Types - 450/750V)
1:83
1POWER & WIRING CABLES
®
( p e r a m p e r e p e r m e t r e ) :
3 or 4 cables - three-phase a.c.
Reference Reference Reference ReferenceMethods 3 & 4 Methods Methods Methods(Enclosed in 1, 11, & 12 1 & 11 (Flat spaced*)conduit etc in (In trefoil) (Flat touching)or on a wall)
6 7 8 9
mV mV mV mV
38 38 38 3825 25 25 2515 15 15 159.5 9.5 9.5 9.56.4 6.4 6.4 6.43.8 3.8 3.8 3.82.4 2.4 2.4 2.4
r x z r x z r x z r x z
1.50 0.29 1.55 1.50 0.175 1.50 1.50 0.25 1.55 1.50 0.32 1.551.10 0.27 1.10 1.10 0.170 1.10 1.10 0.24 1.10 1.10 0.32 1.15 0.81 0.26 0.85 0.80 0.165 0.82 0.80 0.24 0.84 0.80 0.32 0.86 0.56 0.25 0.61 0.55 0.160 0.57 0.55 0.24 0.60 0.55 0.31 0.630.42 0.24 0.48 0.41 0.155 0.43 0.41 0.23 0.47 0.40 0.31 0.51
0.33 0.23 0.41 0.32 0.150 0.36 0.32 0.23 0.40 0.32 0.30 0.440.27 0.23 0.36 0.26 0.150 0.30 0.26 0.23 0.34 0.26 0.30 0.400.22 0.23 0.32 0.21 0.145 0.26 0.21 0.22 0.31 0.21 0.30 0.360.17 0.23 0.29 0.16 0.145 0.22 0.16 0.22 0.27 0.16 0.29 0.340.14 0.23 0.27 0.13 0.140 0.19 0.13 0.22 0.25 0.13 0.29 0.32
0.12 0.22 0.25 0.105 0.14 0.175 0.105 0.21 0.24 0.10 0.29 0.310.10 0.22 0.25 0.086 0.135 0.16 0.086 0.21 0.23 0.081 0.29 0.300.08 0.22 0.24 0.072 0.135 0.15 0.072 0.21 0.22 0.066 0.28 0.29
- 0.06 0.130 0.145 0.06 0.21 0.22 0.053 0.28 0.29- 0.052 0.130 0.140 0.052 0.20 0.21 0.044 0.28 0.28
For further guidance refer to 16th Edition of IEE Wiring regulations.* spaced by one cable diameter.
POWER & WIRING CABLES
1Technical Information
• Flat Twin, Flat Twin & Earth• Flat Three Core, Flat Three Core & Earth
Multicore PVC-insulated cables, non-armoured, with or without protectiveconductor (copper conductors).
Conductor CrossSectional Area
Reference Method 4 (enclosed in aninsulated wall etc.)
Rc
1 two core cable*single phase a.c
or d.c
1 three core cable* or1 four core cable,three phase a.c
1 tsin
1 2 3mm2 A A
1 11.5 101.5 14.5 132.5 20 17.54 26 236 32 29
10 44 3916 57 52
Conductorcross-sectional
area
Two -corecable d.c.
Two-core cablesingle phase a.c
1 2 3mm2 mV mV
1 44 441.5 29 292.5 18 184 11 116 7.3 7.3
10 4.4 4.416 2.8 2.8
CURRENT - CARRYING
eference Method 3 (enclosed inonduit on a wall or in trunkingetc.)wo core cable*gle phase a.c
or d.c
1 three corecable* or 1 four
core cable, threephase a.c
4 5A A12 11.515 1521 2027 2735 3447 4663 62
VOLTAGE DROP (per ampere per metre):
.Three-or-four-core cable
three phase a.c.
4mV3825159.56.43.82.4
1:84
BS6004 – Flat Twin, Flat Three Core
Ambient temperature: 30°C Conductor operating temperature: 70°C
Reference Method 1 ("clipped direct") Reference Method 11 (on a perforated cable tray ), orReference Method 13 (free air)
1 two cable corecable* single phase
a.c or d.c
1 three core cable* or 1four core cable, three
phase a.c
1 two core cable singlephase a.c or d.c
1 three core cable* or 1four core cable, three
phase a.c6 7 8 9A A A A16 13.5 - -20 17.5 - -27 24 - -37 32 - -47 41 - -64 57 - -85 76 - -
If cables are to be used in ambient air temperatures other than 30°C the following ratingfactors should be applied:
Ambient air temp 0C 25 30 35 40 45 50 55 60 65Rating Factor 1.03 1.0 0.94 0.87 0.79 0.71 0.61 0.50 0.35
For further guidance refer to 16th Edition of IEE Wiring regulations.* With or without protective conductor.
POWER & WIRING CABLES
1CAPACITY (Amperes)
1:85
1:86
POWER & WIRING CABLES
®
1
Standard depth of laying 0.5mThermal resistivity of soil 1.20C m/WStandard ground temperature 150CAmbient air temperature 250CMaximum conductor temperature 700C
Conductor Current Rating Voltage DropSize Single Phase a.c. Single Phase a.c.
In Single-Way Directmm2 Ducts Burial Air mV/A/m
4 44 53 42 11.0
6 55 66 54 7.2
10 73 88 74 4.3
16 96 115 97 2.7
25 125 150 130 1.7
35 150 185 160 1.2
Technical Information• Single Phase, Straight & Split Concentric
CURRENT CARRYING CAPACITY (amperes) &VOLTAGE DROP (per ampere per metre):
Conductor Current Rating Voltage DropSize Three Phase a.c. Three Phase a.c.
In Single-Way Directmm2 Ducts Burial Air mV/A/m
16 80 98 83 2.4
25 105 130 110 1.5
CURRENT CARRYING CAPACITY (amperes) &VOLTAGE DROP (per ampere per metre):
• Three Phase, Straight Concentric
1:87
1POWER & WIRING CABLES
®
For ambient air and ground temperatures other than those specified, the following
rating factors should be applied:
Cables Laid in Air
Ambient air temperature 0C 25 30 35 40 45 50 55
Rating factor 1.0 0.94 0.88 0.82 0.75 0.67 0.58
Cables Laid Direct in Ground and in Single-Way Ducts
Ground temperature 0C 10 15 20 25 30 35 40 45 50
Rating factor 1.04 1.0 0.95 0.90 0.85 0.80 0.74 0.67 0.60
1:88
POWER & WIRING CABLES
®
1Technical Information• PVC/PVC/SWA/PVC (694*)• ESI 09-6
D i r e c t B u r i a l D u c t
Nominal Nominalconductor 2 3 & 4 conductor 2 3 & 4
area core core area core core
mm2 Armrd Armrd mm2 Armrd Armrd
1.5 32 27 1.5 26 222.5 41 35 2.5 34 294 55 47 4 45 386 69 59 6 57 4810 92 78 10 76 6416 119 101 16 98 83
Ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036.
For further guidance refer to 16th Edition IEE Wiring Regulations and ERA
publication 69-30 Part 3.
Standard depth of laying 0.5m
Thermal resistivity of soil 1.20C m/W
Standard ground temperature 150C
Ambient air temperature 250C
Maximum conductor temperature 700C
C U R R E N T - C A R R Y I N G C A P A C I T Y
1:89
1POWER & WIRING CABLES
®
BS6346 & ESI 09-6
Copper
2, 3 and 4 Core 600/1000V 50Hz
PVC/PVC/SWA/PVC
For cables of 5 core and above it is assumed only two cores are loaded
simultaneously (i.e. live and neutral) and the two core rating should be taken. In
instances where several cores are loaded simultaneously, the following factors
should be applied to the 2 core current rating:-
Number of cores 2 3 4 5 6 7 10 12
Factor 1.0 0.87 0.78 0.72 0.67 0.63 0.56 0.53
Number of cores 14 19 24 27 30 37 44 46 48
Factor 0.51 0.45 0.42 0.4 0.39 0.36 0.34 0.33 0.33
A i r
Nominalconductor 2 3 & 4
area core core
mm2 Armd Armrd
1.5 24 212.5 33 284 44 386 56 4810 77 6616 102 87
( A m p e r e s ) :
1:90
POWER & WIRING CABLES
®
1
VOLTAGE DROP (per ampere per metre):
Conductor Two -core Two-core cable Three-or-four-core cablecross-sectional cable d.c. single phase a.c. three phase a.c.
area1 2 3 4
mm2 mV mV mV1.5 29 29 252.5 18 18 154 11 11 9.56 7.3 7.3 6.410 4.4 4.4 3.816 2.8 2.8 2.4
If cables are to be used in ambient air or ground temperatures other than those
specified, the following rating factors should be applied:-
Cables Laid in Air
Ambient air temperature 25 30 35 40 45 50 55
Rating factor 1.0 0.94 0.88 0.82 0.75 0.67 0.58
Cables Laid Direct in Ground
Ground temperature 0C 10 15 20 25 30 35 40 45 50
Rating factor 1.04 1.0 0.95 0.90 0.85 0.80 0.74 0.67 0.60
Cables Laid in Ducts
Ground temperature 0C 10 15 20 25 30 35 40 45 50
Rating factor 1.04 1.0 0.95 0.90 0.85 0.80 0.74 0.67 0.60
Technical Information• PVC/PVC/SWA/PVC (694*)• ESI 09-6
1:91
1POWER & WIRING CABLES
®
ELECTRICAL CHARACTERISTICS
Conductor Max DC Max AC Reactance Impedance @Size conductor conductor @ 50Hz 700C, 50Hz
resistance resistance@ 200C @ 700C
mm2 ohms/km ohms/km ohms/km ohms/km
1.5 12.1 14.5 0.103 14.52.5 7.41 8.87 0.101 8.874.0 4.61 5.52 0.0985 5.526.0 3.08 3.69 0.0935 3.6910 1.83 2.19 0.0925 2.1916 1.15 1.38 0.088 1.38
Technical Information• Multicore PVC/PVC/SWA/PVC (694*) 600/100V• Multicore ESI 09-6 600/1000V
1:92
POWER & WIRING CABLES
®
1
C U R R E N T - C A R R Y I N G
Technical Information• Single Core LSF• Single Core XLPE/PVC (6181) Types 600/1000 Volts
Conductor Reference Method 4 Reference Method 3 Referenced Method 1cross (enclosed in conduit (enclosed in conduit ("clipped direct")
Sectional in thermally on a wall or inarea insulating wall etc.) trunking etc.)
2 cables, 3 or 4 2 cables, 3 or 4 2 cables, 3 or 4single- cables single- cables single- cablesphase three- phase three- phase three-a.c or phase a.c. a.c or phase a.c. a.c or phase a.c.d.c. d.c. d.c. flat and
flat and touchingtouching or trefoil
1 2 3 4 5 6 7mm2 A A A A A A
1 14 13 17 15 19 17.51.5 18 17 22 19 25 232.5 24 23 30 26 34 314 33 30 40 35 46 416 43 39 51 45 59 5410 58 53 71 63 81 7416 76 70 95 85 109 9925 100 91 126 111 143 13035 124 111 156 138 176 16150 149 135 189 168 228 20970 189 170 240 214 293 26895 228 205 290 259 355 326120 263 235 336 299 413 379150 300 270 375 328 476 436185 341 306 426 370 545 500240 400 358 500 433 644 590300 459 410 513 493 743 681400 - - 683 584 868 793500 - - 783 666 990 904630 - - 900 764 1130 1033800 - - - - 1288 11791000 - - - - 1443 1323
1:93
1POWER & WIRING CABLES
®
Ambient air temp 0C 25 30 35 40 45 50 55 60 65 70 75 80 85
Rating Factor 1.04 1.0 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41 0.29
For ambient air temperatures other than 300C, the following rating factors should beapplied:
C A P A C I T Y ( A m p e r e s ) :
Referenced Method 11 Reference Method 12 (free air)(on a perforated cable Horizontal Vertical Trefoil
tray horizontal or flat flatvertical) spaced spaced
2 cables, 3 or 4 2 cables, 2 cables, 3 cablessingle- cables single- single- trefoil
phase a.c. three- phase phase three-or d.c. phase a.c. a.c. or a.c. or phase
flat flat and d.c. or d.c. or a.c.and touching 3 cables 3 cables
touching or trefoil three- three-phase a.c. phase a.c.
8 9 10 11 12A A A A A- - - - -- - - - -- - - - -- - - - -- - - - -- - - - -- - - - -
158 140 183 163 138195 176 226 203 171293 215 274 246 209308 279 351 318 270375 341 426 389 330436 398 495 453 385505 461 570 524 445579 530 651 600 511686 630 769 711 606794 730 886 824 701915 849 1065 984 8201044 973 1228 1150 9361191 1115 1423 1338 10691358 1275 1581 1485 12141520 1436 1775 1671 1349
1:94
POWER & WIRING CABLES
®
1
mm2 mV mV mV mV
1 46 46 46 461.5 31 31 31 312.5 19 19 19 194 12 12 12 126 7.9 7.9 7.9 7.910 4.7 4.7 4.7 4.716 2.9 2.9 2.9 2.9
r x z r x z r x z
25 1.85 1.85 0.31 1.90 1.85 0.19 1.85 1.85 0.28 1.8535 1.35 1.35 0.29 1.35 1.35 0.18 1.35 1.35 0.27 1.3550 0.99 1.00 0.29 1.05 0.99 0.18 1.00 0.99 0.27 1.0070 0.68 0.70 0.28 0.75 0.68 0.175 0.71 0.68 0.26 0.7395 0.49 0.51 0.27 0.58 0.49 0.170 0.52 0.49 0.26 0.56
120 0.39 0.41 0.26 0.48 0.39 0.165 0.43 0.39 0.25 0.47150 0.32 0.33 0.26 0.43 0.32 0.165 0.36 0.32 0.25 0.41185 0.25 0.27 0.26 0.37 0.26 0.165 0.30 0.25 0.25 0.36240 0.19 0.21 0.26 0.33 0.20 0.160 0.25 0.195 0.25 0.31300 0.155 0.175 0.25 0.31 0.16 0.160 0.22 0.155 0.25 0.29
400 0.120 0.140 0.25 0.29 0.13 0.155 0.20 0.125 0.24 0.27500 0.093 0.12 0.25 0.28 0.105 0.155 0.185 0.098 0.24 0.26630 0.072 0.10 0.25 0.27 0.086 0.155 0.175 0.078 0.24 0.25800 0.056 - 0.072 0.150 0.170 0.064 0.24 0.251000 0.045 - 0.063 0.150 0.165 0.054 0.24 0.24
2 cables - single phase a.c.
Conductor 2 Reference Reference Referencecross cables Methods 3 & 4 Methods 1 & 11 Method 12
sectional d.c. (Enclosed in (Clipped direct (Spaced*)area conduit etc in or on trays,
or on a wall) touching)
1 2 3 4 5
V O L T A G E D R O P
Technical Information• Single Core LSF• Single Core XLPE/PVC (6181) Types 600/1000VContinued. . .
*Spaced by one cable diameter
1:95
1POWER & WIRING CABLES
®
For further guidance refer to 16th Edition of IEE Wiring regulations.
mV mV mV mV
40 40 40 4027 27 27 2716 16 16 1610 10 10 106.8 6.8 6.8 6.84 4 4 4
2.5 2.5 2.5 2.5
r x z r x z r x z r x z
1.60 0.27 1.65 1.60 0.165 1.60 1.60 0.19 1.60 1.60 0.27 1.651.15 0.25 1.15 1.15 0.155 1.15 1.15 0.18 1.15 1.15 0.26 1.20 0.87 0.25 0.90 0.86 0.155 0.87 0.86 0.18 0.87 0.86 0.26 0.89 0.60 0.24 0.65 0.59 0.150 0.61 0.59 0.175 0.62 0.59 0.25 0.650.44 0.23 0.50 0.43 0.145 0.45 0.43 0.170 0.46 0.43 0.25 0.49
0.35 0.23 0.42 0.34 0.140 0.37 0.34 0.165 0.38 0.34 0.24 0.420.29 0.23 0.37 0.28 0.140 0.31 0.28 0.165 0.32 0.28 0.24 0.370.23 0.23 0.32 0.22 0.140 0.26 0.22 0.165 0.28 0.22 0.24 0.330.185 0.22 0.29 0.17 0.140 0.22 0.17 0.165 0.24 0.17 0.24 0.290.15 0.22 0.27 0.14 0.140 0.195 0.135 0.160 0.21 0.135 0.24 0.27
0.125 0.22 0.25 0.11 0.135 0.175 0.11 0.160 0.195 0.11 0.24 0.260.10 0.22 0.24 0.09 0.135 0.16 0.088 0.160 0.180 0.085 0.24 0.250.088 0.21 0.23 0.074 0.135 0.150 0.071 0.160 0.170 0.068 0.23 0.24
- 0.062 0.130 0.145 0.059 0.155 0.165 0.055 0.23 0.24- 0.055 0.130 0.140 0.050 0.155 0.165 0.047 0.23 0.24
3 or 4 cables - three-phase a.c.
Reference Reference Reference ReferenceMethods 3 & 4 Methods Methods Method 12(Enclosed in 1, 11, & 12 1 & 11 (Flat spaced*)conduit etc in (In trefoil) (Flat touching)or on a wall)
6 7 8 9
( p e r a m p e r e p e r m e t r e ) :
1:96
POWER & WIRING CABLES
®
1Technical Information• Multicore XLPE/PVC 600/1000V
C U R R E N T - C A R R Y I N G
Conductor Reference Method 4 Reference Method 3cross (enclosed in an (enclosed in conduit
Sectional insulating wall etc.) on a wall or inarea trunking etc.)
1 two- 3 or 4 1 two- 3 or 4core cable core cable core cable core cable
single phase three- single phase three-a.c or d.c. phase a.c. a.c or d.c. phase a.c.
1 2 3 4 5
mm2 A A A A
16 76 68 91 8025 99 89 119 10535 121 109 146 12850 145 130 175 15470 183 164 221 19495 220 197 265 233
120 253 227 305 268150 290 259 334 300185 329 295 384 340240 386 346 459 398300 442 396 532 455400 - - 625 536
Ambient temperature: 300C
Conductor operating temperature: 900C
1:97
1POWER & WIRING CABLES
®
For further guidance refer to 16th Edition IEE Wiring Regulations.
For ambient air temperatures other than 300C, the following factors should be
applied.
Ambient air temperature 25 30 35 40 45 50 55 60 65 70 75 80 85
Rating factor 1.04 1.0 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41 0.29
C A P A C I T Y ( A m p e r e s ) :
Referenced Method 1 Referenced Method 11("clipped direct") (on a perforated cable
tray horizontal orvertical)
1 two- 3 or 4 1 two- 3 or 4core cable core cable core cable core cable
single phase three- single phase three-a.c or d.c. phase a.c. a.c. or d.c. phase a.c.
6 7 8 9
A A A A
107 96 115 100138 119 149 127171 147 185 158209 179 225 192269 229 289 246328 278 352 298
382 322 410 346441 371 473 399506 424 542 456599 500 641 538693 576 741 621803 667 865 741
1:98
POWER & WIRING CABLES
®
1
VOLTAGE DROP (per ampere per metre):
Conductor Two -core Two-core cable Three-or-four-core cablecross-sectional cable d.c. single phase a.c. three phase a.c.
area1 2 3 4
mm2 mV mV mV16 2.9 2.9 2.5
r x z r x z25 1.85 1.85 0.160 1.90 1.60 0.140 1.6535 1.35 1.35 0.155 1.35 1.15 0.135 1.1550 0.98 0.99 0.155 1.00 0.86 0.135 0.8770 0.67 0.67 0.150 0.69 0.59 0.130 0.6095 0.49 0.50 0.150 0.52 0.43 0.130 0.45
120 0.39 0.40 0.145 0.42 0.34 0.130 0.37150 0.31 0.32 0.145 0.35 0.28 0.125 0.30185 0.25 0.26 0.145 0.29 0.22 0.125 0.26240 0.195 0.200 0.140 0.24 0.175 0.125 0.21300 0.155 0.160 0.140 0.21 0.140 0.120 0.185
400 0.120 0.130 0.145 0.195 0.115 0.125 0.170
Conductor operating temperature: 900C
Technical Information• Multicore XLPE/PVC 600/1000V
1:99
1POWER & WIRING CABLES
®
1:100
POWER & WIRING CABLES
®
1Technical Information• XLPE/PVC/AWA/PVC Single Core• XLPE/LSF/AWA/LSF 600/1000V
Direct Buried BS5467
Nominal 2 cables 3 cablesconductor
area Touching Spaced Trefoil Touching Spaced
mm2 Armrd Armrd Armrd Armrd Armrd
50 274 279 231 231 242
70 337 342 284 283 295
95 403 408 340 337 350
120 458 461 386 381 395
150 510 508 431 424 434
185 574 566 485 474 482
240 661 643 558 542 545
300 739 709 623 601 597
400 820 761 691 657 637
500 910 825 765 720 688
630 1001 887 841 781 737
800 1055 909 888 816 760
1000 1115 952 942 860 797
CURRENT CARRYING CAPACITY (amperes)
Air BS5467 & BS6724
Nominal 2 cables conductor Horizontally Vertically Trefoil
area spaced spaced
mm2 Unarm Armrd Unarm Armrd Unarm Armrd
50 289 297 268 280 223 231
70 366 376 342 355 284 295
95 452 459 423 434 352 362
120 527 530 495 502 412 420
150 604 596 570 567 475 483
185 699 677 662 646 551 555
240 835 788 792 752 658 654
300 966 886 919 847 761 745
400 1129 978 1077 936 887 851
500 1315 1086 1257 1041 1027 963
630 1533 1199 1469 1149 1186 1084
800 1765 1267 1694 1216 1327 1178
1000 1993 1357 1916 1303 1503 1278
1:101
1POWER & WIRING CABLES
®
For further guidance refer to
16th Edition IEE Wiring
Regulations and ERA 69-30
Part 5.
Ratings do not apply if the
cable is protected by a
semi-enclosed fuse to
BS3036.
Continued overleaf. . . .
Standard depth of laying 0.5m Thermal resistivity of soil 1.20C m/WStandard ground temp 150C Ambient air temp 250CMaximum conductor temp 900C
In Single-Way Duct BS5467
Nominal 2 cables 3 cablesconductor
area Flat Trefoil Flat
mm2 Armrd Armrd Armrd
50 252 231 232
70 305 278 279
95 360 327 328
120 404 366 367
150 439 396 398
185 486 437 438
240 546 489 490
300 597 534 534
400 638 567 567
500 694 615 613
630 752 664 661
800 788 692 690
1000 839 735 732
3 cablesVertically Horizontallyspaced spaced
Unarm Armrd Unarm Armrd
260 271 289 296
331 342 366 373
411 417 452 452
482 480 527 519
554 536 604 577
644 604 699 649
772 694 834 745
896 770 965 825
1050 829 1127 887
1226 906 1312 968
1434 983 1529 1049
1655 1029 1761 1097
1878 1096 1993 1168
1:102
POWER & WIRING CABLES
®
1
VOLTAGE DROP (per
2 cables - single phase a.c.
Conductor 2 Reference Methods Reference Methodcross-sectional cables 1 & 11 12
area d.c. (Touching) (Spaced*)
1 2 3 4
mm2 mV mV mVr x z r x z
50 0.98 0.99 0.21 1.00 0.98 0.29 1.0070 0.67 0.68 0.200 0.71 0.69 0.29 0.7595 0.49 0.51 0.195 0.55 0.53 0.28 0.60120 0.39 0.41 0.190 0.45 0.43 0.27 0.51150 0.31 0.33 0.185 0.38 0.36 0.27 0.45185 0.25 0.27 0.185 0.33 0.30 0.26 0.40240 0.195 0.21 0.180 0.28 0.24 0.26 0.35300 0.155 0.170 0.175 0.25 0.195 0.25 0.32400 0.115 0.145 0.170 0.22 0.180 0.24 0.30500 0.093 0.125 0.170 0.21 0.165 0.24 0.29630 0.073 0.105 0.165 0.195 0.150 0.23 0.27800 0.056 0.090 0.160 0.190 0.145 0.23 0.271000 0.045 0.092 0.155 0.180 0.140 0.21 0.25
* spaced by one cable diameter.
For ambient air and ground temperatures other than those specified, the following
factors should be applied.
Cables laid in air:
Ambient air temperature 25 30 35 40 45 50 55
Rating factor 1.0 0.96 0.92 0.88 0.83 0.78 0.73
Cables laid direct in ground and in single-way ducts:
Ground temperature 10 15 20 25 30 35 40
Rating factor 1.03 1.0 0.97 0.93 0.89 0.86 0.82
Technical Information• XLPE/PVC/AWA/PVC Single Core• XLPE/LSF/AWA/LSF 600/1000V
1:103
1POWER & WIRING CABLES
®
ampere per metre):
3 or 4 cables - three phase a.c.
Reference Methods Reference Methods Reference Methods1, 11 and 12 1 & 11 12
(in trefoil touching) (Flat touching) (Flat spaced*)
5 6 7
mV mV mVr x z r x z r x z
0.86 0.180 0.87 0.84 0.25 0.88 0.84 0.33 0.900.59 0.170 0.62 0.60 0.25 0.65 0.62 0.32 0.700.44 0.170 0.47 0.46 0.24 0.52 0.49 0.31 0.580.35 0.165 0.39 0.38 0.24 0.44 0.41 0.30 0.510.29 0.160 0.33 0.31 0.23 0.39 0.34 0.29 0.450.23 0.160 0.28 0.26 0.23 0.34 0.29 0.29 0.410.180 0.155 0.24 0.21 0.22 0.30 0.24 0.28 0.370.145 0.150 0.21 0.170 0.22 0.28 0.20 0.27 0.340.125 0.150 0.195 0.160 0.21 0.27 0.20 0.27 0.330.105 0.145 0.180 0.145 0.20 0.25 0.190 0.24 0.310.092 0.145 0.170 0.135 0.195 0.24 0.175 0.23 0.290.086 0.140 0.165 0.130 0.180 0.23 0.175 0.195 0.260.080 0.135 0.155 0.125 0.170 0.21 0.165 0.180 0.24
1:104
POWER & WIRING CABLES
®
1Technical Information• Single core XLPE/PVC 600/1000V to BS7889• Single core PCU/XLPE/PVC/AWA/PVC 600/1000V to BS5467• Single core PCU/XLPE/LSF/AWA/LSF 600/1000V to BS6724
ELECTRICAL CHARACTERISTICS
Conductor Max DC Max AC conductor Reactance @ 50Hz Impedance @ 900C, 50HzSize conductor resistance
resistance @ 900C Single core cables Single core cables@200C in trefoil in trefoil
Unarm’d Arm’d Unarm’d Arm’d Unarm’d Arm’dmm2 ohms/km ohms/km ohms/km ohms/km ohms/km ohnms/km ohms/km
50 0.387 0.494 0.494 0.0904 0.104 0.502 0.50570 0.268 0.342 0.342 0.0871 0.101 0.353 0.35795 0.193 0.247 0.246 0.0845 0.0969 0.261 0.264120 0.153 0.196 0.196 0.0822 0.0920 0.213 0.217150 0.124 0.160 0.160 0.0823 0.0945 0.180 0.186185 0.0991 0.128 0.128 0.0812 0.0932 0.152 0.158240 0.0754 0.0990 0.0985 0.0798 0.0902 0.127 0.134300 0.0601 0.0802 0.0799 0.0790 0.0883 0.113 0.119400 0.0470 0.0645 0.0639 0.0782 0.0886 0.101 0.109500 0.0366 0.0523 0.0513 0.0776 0.0870 0.0936 0.101630 0.0283 0.0430 0.0420 0.0768 0.0847 0.0880 0.0945800 0.0221 0.0364 0.0349 0.0758 0.0850 0.0841 0.0919
1000 0.0176 0.0318 0.0303 0.0750 0.0840 0.0815 0.0893
1:105
1POWER & WIRING CABLES
®
1:106
POWER & WIRING CABLES
®
1Technical Information• Multicore XLPE/PVC/SWA/PVC 600/1000V• Multicore XLPE/LSF/SWA/LSF 600/1000V• Multicore XLPE/LC/PVC/SWA/PVC 600/1000V
D i r e c t B u r i a l I n S i n g l e - W a y D u c t
Nominal Nominalconductor 2 3 & 4 conductor 2 3 & 4
area core core area core core
mm2 Armrd Armrd mm2 Armrd Armrd
1.5 38 32 1.5 31 262.5 49 42 2.5 41 344 65 55 4 53 456 81 69 6 67 5610 109 92 10 89 7516 141 119 16 115 9625 183 152 25 148 12435 219 182 35 178 14950 259 217 50 211 17770 317 266 70 260 21895 381 319 95 313 263120 433 363 120 357 300150 485 406 150 401 338185 547 458 185 455 382240 632 529 240 527 442300 708 592 300 592 496400 799 667 400 669 570
Standard depth of laying 0.5m
Thermal resistivity of soil 1.20C m/W
Standard ground temperature 150C
Ambient air temperature 250C
Maximum conductor temperature 900C
2 core - single phase a.c. 3&4 core - three phase a.c.
Ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036.
For further guidance refer to 16th Edition IEE Wiring Regulations and ERA
publication 69-30 Part 5.
CURRENT CARRYING CAPACITY
1:107
1POWER & WIRING CABLES
®
For cables of 5 core and above it is assumed only two cores are loaded
simultaneously (i.e. live and neutral) and the two core rating should be taken. In
instances where several cores are loaded simultaneously, the following rating factors
should be applied to the 2 core current rating:
Number of cores 2 3 4 5 6 7 10 12
Factor 1.0 0.87 0.78 0.72 0.67 0.63 0.56 0.53
Number of cores 14 19 24 27 30 37 44 46 48
Factor 0.51 0.45 0.42 0.4 0.39 0.36 0.34 0.33 0.33
A i r
Nominalconductor 2 3 & 4
area core core
mm2 Armrd Armrd
1.5 31 262.5 41 354 55 476 70 5910 95 8216 126 10725 164 14035 202 17250 244 20970 306 26395 378 324120 437 376150 499 430185 576 495240 680 584300 775 666400 892 766
(Amperes)
Cables laid direct in ground and in single-way ducts
Ground temp 0C 10 15 20 25 30 35 40Rating factor 1.03 1.0 0.97 0.93 0.89 0.86 0.82
1:108
POWER & WIRING CABLES
®
1
VOLTAGE DROP (per ampere per metre):Conductor Two -core Two-core cable Three-or-four-core cable
cross-sectional cable d.c. single phase a.c. three phase a.c.area
1 2 3 4
mm2 mV mV mV1.5 31 31 272.5 19 19 164 12 12 106 7.9 7.9 6.810 4.7 4.7 4.016 2.9 2.9 2.5
r x z r x z25 1.85 1.85 0.160 1.90 1.60 0.140 1.6535 1.35 1.35 0.155 1.35 1.15 0.135 1.1550 0.98 0.99 0.155 1.00 0.86 0.135 0.8770 0.67 0.67 0.150 0.69 0.59 0.130 0.6095 0.49 0.50 0.150 0.52 0.43 0.130 0.45
120 0.39 0.40 0.145 0.42 0.34 0.130 0.37150 0.31 0.32 0.145 0.35 0.28 0.125 0.30185 0.25 0.26 0.145 0.29 0.22 0.125 0.26240 0.195 0.20 0.140 0.24 0.175 0.125 0.21300 0.155 0.16 0.140 0.21 0.140 0.120 0.185
400 0.120 0.13 0.145 0.195 0.115 0.125 0.170
Technical Information• XLPE/PVC/SWA/PVC• XLPE/LSF/SWA/LSF• XLPE/LC/PVC/SWA/PVC 600/1000V
Conductor operating temperature 900CNB. for ambient air and ground temperatures other than those specified the followingrating factors should be applied:
Cables Laid in AirAmbient air temp 0C 25 30 35 40 45 50 55Rating factor 1.0 0.96 0.92 0.88 0.83 0.78 0.73
1:109
1POWER & WIRING CABLES
®
Technical Information• Multicore PCU/XLPE/PVC 600/1000V to BS5467• Multicore PCU/XLPE/PVC/SWA/PVC 600/1000V to BS5467• Multicore PCU/XLPE/LSF/SWA/LSF 600/1000V to BS6724• Multicore PCU/XLPE/LC/PVC/SWA/PVC 600/1000V
ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance
Size conductor conductor @ 50Hz @ 900C, 50Hzresistance resistance
@ 200C @ 900Cmm2 ohms/km ohms/km ohms/km ohms/km
1.5 12.1 15.4 0.103 15.42.5 7.41 9.45 0.101 9.454.0 4.61 5.88 0.0929 5.886.0 3.08 3.93 0.0885 3.9310 1.83 2.33 0.0835 2.3316 1.15 1.47 0.0815 1.4725 0.727 0.927 0.0818 0.93135 0.524 0.668 0.0771 0.67250 0.387 0.494 0.0765 0.50070 0.268 0.342 0.0754 0.35095 0.193 0.247 0.0727 0.257120 0.153 0.197 0.0723 0.210150 0.124 0.160 0.0728 0.176185 0.0991 0.128 0.073 0.147240 0.0754 0.0989 0.0722 0.122300 0.0601 0.0802 0.0717 0.108400 0.047 0.0656 0.0715 0.0970
1:110
POWER & WIRING CABLES
®
1Technical Information• FP200 & FireTuf Fire Resistant Cable
Ratings do not apply if the cable is protected by a semi-enclosed fuse to BS3036.
For further guidance refer to 16th Edition IEE Wiring Regulations.
For cables of 5 core and above it is assumed only two cores are loaded
simultaneously (i.e. live and neutral) and the two core rating should be taken.
For ambient air temperatures other than 300C, the following factors should be
applied.
Ambient air temperature 25 35 40 45 50 55 60 65
Rating factor 1.03 0.94 0.87 0.79 0.71 0.61 0.50 0.35
1:111
1POWER & WIRING CABLES
®
Installation MethodNominal ('Enclosed') in Trunking Clipped DirectCross One Twin One, 3 or One Twin One, 3 or 4
Sectional Cable 4 Core Cable Cable Core Cablearea of a.c. or d.c. 3 Phase a.c. or d.c. 3 Phase
Conductor a.c. a.c.
Current Volt drop Current Volt drop Current Volt drop Current Volt drop
carrying per amp carrying per amp carrying per amp carrying per amp
capacity per m capacity per m capacity per m capacity per m
mm2 A mV A mV A mV A mV
1.0 13.5 44 11.5 38 15 44 13.5 38
1.5 16.5 29 15 25 19.5 29 17.5 25
2.5 23 18 20 15 27 18 24 15
4.0 30 11 27 9.5 36 11 32 9.5
Ambient air temperature 300C
Conductor operating temperature 700C
CURRENT CARRYING CAPACITY (amperes)& VOLTAGE DROP (per ampere per metre)
ADDITIONAL TECHNICAL INFORMATION ON FIRETUF
Conductor Capacitance Capacitance L/R RatioSize Core-Core Core-Screenmm2 pF/m pF/m µH/Ω
1.0 100 175 25
1.5 102 180 40
2.5 115 205 50
4.0 125 230 65
1:112
POWER & WIRING CABLES
®
1Technical Information• Fire Resistant Armoured Cables to BS7846 600/1000V
For further guidance refer to 16th Edition IEE Wiring Regulations.
For cables of 7 core and above it is assumed only two cores are loaded
simultaneously (i.e. live and neutral) and the two core rating should be taken.
For ambient air temperatures other than 300C, the following factors should be
applied.
Ambient air temperature 25 30 35 40 45 50 55 60 65 70 75 80
Rating factor 1.04 1.0 0.94 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41
Nominal One Twin One 3 orCross 4 Core
Sectional Cablearea of 3 Phase
Conductor a.c. d.c. a.c.
mm2 mV mV mV
1.5 31 31 27
2.5 19 19 16
4 12 12 10
6 7.9 7.9 6.8
10 4.7 4.7 4.0
16 2.9 2.9 2.5
25 1.90 1.85 1.65
35 1.35 1.35 1.15
50 1.00 0.98 0.87
70 0.69 0.67 0.60
95 0.52 0.49 0.45
120 0.42 0.39 0.37
150 0.35 0.31 0.30
185 0.29 0.25 0.25
240 0.24 0.195 0.21
300 0.21 0.155 0.185
400 0.19 0.120 0.165
VOLTAGE DROP (per ampere per metre):
Installation MethodNominal In Free Air or on perforated cable tray Clipped DirectCross One Twin One, 3 or One Twin One, 3 or 4
Sectional Cable 4 Core Cable Cable Core Cablearea of a.c. or d.c. 3 Phase a.c. or d.c. 3 Phase
Conductor a.c. a.c.
mm2 A A A A
1.5 29 25 27 23
2.5 39 33 36 31
4 52 44 49 42
6 66 56 62 53
10 90 78 85 73
16 115 99 110 94
25 152 131 146 124
35 188 162 180 154
50 228 197 219 187
70 291 251 279 238
95 354 304 338 289
120 410 353 392 335
150 472 406 451 386
185 539 463 515 441
240 636 546 607 520
300 732 628 698 599
400 847 728 787 673
CURRENT CARRYING CAPACITY (amperes)
Conductor operating temperature 900CAmbient air temperature 300C
If ratings for these cables buried direct in ground or in single-way duct arerequired, refer to ratings for XLPE/SWA cables detailed on page 1:104
1:113
1POWER & WIRING CABLES
®
1:114
POWER & WIRING CABLES
®
1Technical Information• 1.9/3.3 kV 1core & 3 cores XLPE Insulated, Armoured CablesBS5467 & BS6724
For further guidance refer to 16th Edition IEE Wiring Regulations and ERA 69-30Part 5.For ambient air and ground temperatures other than those specified, the followingfactors should be applied,
Cables laid in air
Ambient air temp 0C 25 30 35 40 45 50 55Rating factor 1.0 0.96 0.92 0.88 0.83 0.78 0.73
Cables laid direct in ground and in single-way ducts
Ground temp 0C 10 15 20 25 30 35 40Rating factor 1.03 1.0 0.97 0.93 0.89 0.86 0.82
Direct Buried - BS5467 In Single-Way Duct - BS5467
Nominal Trefoil 3 cables Spaced Nominal 3 Cablesconductor Touching conductor
Trefoil Flatarea
mm2 Armrd Armrd Armrd mm2 Armrd Armrd
50 222 221 230 50 219 220
70 271 269 279 70 264 265
95 324 321 331 95 310 311
120 366 361 369 120 342 342
150 409 402 409 150 376 376
185 460 449 454 185 414 414
240 528 513 512 240 464 463
300 589 568 560 300 506 504
400 651 619 595 400 535 532
500 720 677 641 500 579 574
630 789 733 684 630 624 618
800 831 763 703 800 650 644
1000 880 802 735 1000 689 682
CURRENT CARRYING CAPACITY (amperes)Single Core 1900/3300V 50Hz
1:115
1POWER & WIRING CABLES
®
Direct Buried - BS5467 In Single-Way Duct - BS5467 Air - BS5467 & BS6724
Nominal 3 Nominal 3 Nominal 3conductor core conductor core conductor core
area area area
mm2 Armrd mm2 Armrd mm2 Armrd
16 114 16 96 16 112
25 147 25 124 25 149
35 175 35 147 35 177
50 207 50 174 50 213
70 254 70 214 70 268
95 304 95 257 95 328
120 345 120 293 120 380
150 387 150 328 150 432
185 436 185 371 185 496
240 502 240 428 240 583
300 563 300 480 300 667
400 633 400 549 400 765
CURRENT CARRYING CAPACITY (amperes)3 Core 1900/3300V 50Hz XLPE/PVC/SWA/PVC, XLPE/LSF/SWA/LSF
Standard depth of laying 0.8mThermal resistivity of soil 1.20C m/WStandard ground temp 150CAmbient air temp 250CMaximum conductor temp 900C
Air - BS5467 & 6724
Nominal Trefoil 3 cables Horizontallyconductor vertical spaced
arae spaced
mm2 Armrd Armrd Armrd
50 240 277 299
70 300 345 372
95 368 420 452
120 428 478 513
150 487 536 576
185 556 604 648
240 656 695 745
300 747 771 826
400 851 829 887
500 963 906 968
630 1084 983 1049
800 1178 1030 1098
1000 1278 1096 1168
XLPE/PVC/AWA/PVC XLPE/LSF/AWA/LSF
1:116
POWER & WIRING CABLES
®
1Technical Information• Single core PCU/XLPE/PVC/AWA/PVC 1900/3300V to BS5467• Single core PCU/XLPE/LSF/AWA/LSF 1900/3300V to BS6724
ELECTRICAL CHARACTERISTICS
Conductor Max DC Max AC Reactance ImpedanceSize conductor conductor @ 50Hz @ 900C, 50Hz
resistance resistance Single core cables Single core cables@ 200C @ 900C in trefoil in trefoil
mm2 ohms/km ohms/km ohms/km ohms/km
50 0.387 0.493 0.116 0.50670 0.268 0.342 0.110 0.35995 0.193 0.246 0.104 0.267120 0.153 0.195 0.104 0.221150 0.124 0.160 0.100 0.189185 0.0991 0.128 0.098 0.161240 0.0754 0.0984 0.094 0.136300 0.0601 0.0795 0.091 0.121400 0.0470 0.0639 0.0886 0.109500 0.0366 0.0513 0.0870 0.101630 0.0283 0.0420 0.0847 0.0945800 0.0221 0.0349 0.0850 0.0919
1000 0.0176 0.0303 0.0840 0.0893
1:117
1POWER & WIRING CABLES
®
Technical Information• Multicore PCU/XLPE/PVC 1900/3300V to BS5467• Multicore PCU/XLPE/PVC/SWA/PVC 1900/3300V to BS5467• Multicore PCU/XLPE/LSF/SWA/LSF 1900/3300V to BS6724
ELECTRICAL CHARACTERISTICS
Conductor Max DC Max AC Reactance ImpedanceSize conductor conductor @ 50Hz @ 900C, 50Hz
resistance resistance@ 200C @ 900C
mm2 ohms/km ohms/km ohms/km ohms/km
16 1.15 1.47 0.104 1.4725 0.727 0.927 0.094 0.93235 0.524 0.668 0.091 0.67450 0.387 0.494 0.088 0.50270 0.268 0.342 0.084 0.35295 0.193 0.247 0.081 0.260120 0.153 0.197 0.079 0.212150 0.124 0.160 0.077 0.178185 0.0991 0.128 0.076 0.149240 0.0754 0.0989 0.074 0.124300 0.0601 0.0802 0.073 0.108400 0.047 0.0656 0.0717 0.0972
1:118
POWER & WIRING CABLES
®
1Technical Information• 1 and 3 core XLPE Insulated Cables3800/6600V, 6350/11000V & 8700/15000V
For further guidance refer to 16th Edition IEE Wiring Regulations .
NB. High voltage cables are not specifically covered in IEE Wiring Regulations but
reference should be made to ensure compliance.
For ambient air and ground temperatures other than those specified, the following
factors should be applied.
Cables Laid in Air
Ambient air temperature 25 30 35 40 45 50 55
Rating factor 1.0 0.96 0.92 0.88 0.83 0.78 0.73
Cables Laid Direct and in single-way ducts
Ground temperature 0C 10 15 20 25 30 35 40
Rating factor 1.03 1.0 0.97 0.93 0.89 0.86 0.82
Standard depth of laying 0.8m
Thermal resistivity of soil 1.20C m/W
Standard ground temperature 150C
Ambient air temperature 250C
Maximum conductor temperature 900C
NOTE
All circuits thermally independent
Cables in trefoil group are solidly bonded
Cables in flat formation are single point bonded
1:119
1POWER & WIRING CABLES
®
Direct Burial Duct Air3 cables 3 cables 3 cables
Nominal Trefoil Flat Nominal Trefoil Flat Nominal Trefoil Flat conductor spaced conductor spaced conductor spaced
area area area
mm2 Arm Arm mm2 Unarm Arm Unarm Arm mm2 Unarm Arm Unarm Arm
25 - - 25 - - - - 25 - - - -
35 - - 35 - - - - 35 - - - -
50 220 230 50 225 220 220 220 50 235 250 295 300
70 270 280 70 270 260 270 270 70 285 310 370 370
95 320 335 95 320 305 325 325 95 360 375 455 460
120 360 380 120 360 340 370 370 120 415 430 520 530
150 410 430 150 400 375 415 410 150 470 490 600 600
185 455 485 185 440 410 465 460 185 540 550 690 690
240 520 560 240 505 470 540 540 240 640 650 820 820
300 580 640 300 560 500 610 610 300 740 740 940 940
400 650 730 400 610 530 690 690 400 840 840 1100 1100
500 710 830 500 680 570 790 780 500 980 930 1280 1280
630 760 940 630 750 620 890 890 630 1110 1040 1500 1480
CURRENT CARRYING CAPACITY (Amperes)
Single Core 3.8/6.6 kV, 6.35/11 kV, 8.7/15 kV 50 Hz
Direct Burial In Single-Way Duct Air
Nominal 3 Nominal 3 Nominal 3conductor core conductor core conductor core
area area area
mm2 Armrd mm2 Armrd mm2 Armrd
25 140 25 125 25 145
35 170 35 150 35 175
50 210 50 180 50 220
70 255 70 215 70 270
95 300 95 255 95 330
120 340 120 290 120 375
150 380 150 330 150 430
185 430 185 370 185 490
240 490 240 425 240 570
300 540 300 470 300 650
400 600 400 530 400 740
3 Core 3.8/6.6 kV, 6.35/11 kV, 8.7/15 kV 50 Hz XLPE/PVC/SWA/PVC &XLPE/LSF/SWA/LSF
1:120
POWER & WIRING CABLES
®
1 Technical Information• Single core PCU/XLPE/PVC 3800/6600V to BS6622• Single core PCU/XLPE/AWA/PVC 3800/6600V to BS6622
ELECTRICAL CHARACTERISTICSConductor Max DC Max AC conductor Reactance @ 50Hz Impedance @ 900C, 50Hz
Size conductor resistanceresistance @ 900C Single core cables Single core cables
@200C in trefoil in trefoilUnarm’d Arm’d Unarm’d Arm’d Unarm’d Arm’d
mm2 ohms/km ohms/km ohms/km ohms/km ohms/km ohnms/km ohms/km
50 0.387 0.494 0.494 0.118 0.134 0.507 0.51170 0.268 0.343 0.343 0.111 0.125 0.360 0.36495 0.193 0.248 0.248 0.105 0.119 0.268 0.274120 0.153 0.196 0.196 0.101 0.114 0.220 0.227150 0.124 0.159 0.159 0.0991 0.111 0.187 0.193185 0.0991 0.128 0.128 0.0958 0.109 0.160 0.167240 0.0754 0.098 0.098 0.0933 0.105 0.135 0.143300 0.0601 0.080 0.080 0.0917 0.103 0.122 0.130400 0.0470 0.064 0.064 0.0898 0.0999 0.110 0.118500 0.0366 0.057 0.057 0.088 0.0992 0.102 0.111630 0.0283 0.042 0.042 0.0855 0.0959 0.095 0.104
Technical Information• Three core PCU/XLPE/PVC 3800/6600V to BS6622• Three core PCU/XLPE/PVC/SWA/PVC 3800/6600V to BS6622
ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance
Size conductor conductor @ 50Hz @ 900C, 50Hzresistance resistance
@ 200C @ 900Cmm2 ohms/km ohms/km ohms/km ohms/km
16 1.15 1.47 0.128 1.4825 0.727 0.927 0.121 0.93535 0.524 0.668 0.113 0.67750 0.387 0.494 0.108 0.50670 0.268 0.343 0.102 0.35895 0.193 0.248 0.0962 0.266120 0.153 0.196 0.0931 0.217150 0.124 0.159 0.0908 0.183185 0.0991 0.128 0.0881 0.155240 0.0754 0.098 0.859 0.130300 0.0601 0.080 0.0847 0.117400 0.047 0.064 0.0832 0.105
Also applicable to LSF sheathed versions to BS7835
1:121
1POWER & WIRING CABLES
®
Technical Information• Single core PCU/XLPE/PVC 6350/11000V to BS6622• Single core PCU/XLPE/AWA/PVC 6350/11000V to BS6622
ELECTRICAL CHARACTERISTICSConductor Max DC Max AC conductor Reactance @ 50Hz Impedance @ 900C, 50Hz
Size conductor resistanceresistance @ 900C Single core cables Single core cables
@200C in trefoil in trefoilUnarm’d Arm’d Unarm’d Arm’d Unarm’d Arm’d
mm2 ohms/km ohms/km ohms/km ohms/km ohms/km ohnms/km ohms/km
50 0.387 0.494 0.494 0.124 0.138 0.508 0.51270 0.268 0.343 0.343 0.117 0.130 0.361 0.36695 0.193 0.248 0.248 0.110 0.123 0.270 0.276120 0.153 0.196 0.196 0.107 0.118 0.223 0.229150 0.124 0.159 0.159 0.104 0.117 0.190 0.197185 0.0991 0.128 0.128 0.100 0.112 0.162 0.169240 0.0754 0.0980 0.098 0.0972 0.109 0.138 0.146300 0.0601 0.0800 0.080 0.0940 0.105 0.123 0.131400 0.0470 0.0640 0.064 0.0912 0.101 0.111 0.119500 0.0366 0.0510 0.051 0.0888 0.0998 0.102 0.112630 0.0283 0.0420 0.042 0.0862 0.0965 0.0959 0.105
Technical Information• Three core PCU/XLPE/PVC 6350/11000V to BS6622• Three core PCU/XLPE/PVC/SWA/PVC 6350/11000V to BS6622
ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance
Size conductor conductor @ 50Hz @ 900C, 50Hzresistance resistance
@ 200C @ 900Cmm2 ohms/km ohms/km ohms/km ohms/km
16 1.15 1.47 0.137 1.4825 0.727 0.927 0.129 0.93635 0.524 0.668 0.121 0.67950 0.387 0.494 0.115 0.50670 0.268 0.343 0.108 0.36095 0.193 0.248 0.102 0.268120 0.153 0.196 0.0988 0.220150 0.124 0.159 0.0962 0.186185 0.0991 0.128 0.0931 0.158240 0.0754 0.098 0.090 0.134300 0.0601 0.080 0.0874 0.119400 0.047 0.064 0.0849 0.106
Also applicable to LSF sheathed versions to BS7835
1:122
POWER & WIRING CABLES
®
1Technical Information• Single core PCU/XLPE/PVC 8700/15000V to BS6622• Single core PCU/XLPE/PVC/AWA/PVC 8700/15000V to BS6622
ELECTRICAL CHARACTERISTICSConductor Max DC Max AC conductor Reactance @ 50Hz Impedance @ 900C, 50Hz
Size conductor resistanceresistance @ 900C Single core cables Single core cables
@200C in trefoil in trefoilUnarm’d Arm’d Unarm’d Arm’d Unarm’d Arm’d
mm2 ohms/km ohms/km ohms/km ohms/km ohms/km ohnms/km ohms/km
50 0.387 0.494 0.494 0.131 0.144 0.510 0.51470 0.268 0.343 0.343 0.123 0.135 0.363 0.36895 0.193 0.248 0.248 0.116 0.129 0.273 0.279120 0.153 0.196 0.196 0.112 0.124 0.226 0.232150 0.124 0.159 0.159 0.109 0.121 0.192 0.198185 0.0991 0.128 0.128 0.106 0.117 0.165 0.172240 0.0754 0.098 0.098 0.102 0.113 0.141 0.148300 0.0601 0.080 0.080 0.0984 0.108 0.126 0.133400 0.0470 0.064 0.064 0.0954 0.107 0.114 0.124500 0.0366 0.051 0.051 0.0927 0.103 0.105 0.114630 0.0283 0.042 0.042 0.0897 0.0995 0.0986 0.107
Technical Information• Three core PCU/XLPE/PVC 8700/15000V to BS6622• Three core PCU/XLPE/PVC/SWA/PVC 8700/15000V to BS6622
ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance
Size conductor conductor @ 50Hz @ 900C, 50Hzresistance resistance
@ 200C @ 900Cmm2 ohms/km ohms/km ohms/km ohms/km
16 1.15 1.47 0.147 1.4825 0.727 0.927 0.138 0.93735 0.524 0.668 0.129 0.68050 0.387 0.494 0.123 0.50870 0.268 0.343 0.115 0.36195 0.193 0.248 0.109 0.270120 0.153 0.196 0.105 0.223150 0.124 0.159 0.102 0.189185 0.0991 0.128 0.0986 0.162240 0.0754 0.098 0.0952 0.137300 0.0601 0.080 0.0922 0.123400 0.047 0.064 0.0893 0.110
Also applicable to LSF sheathed versions to BS7835
1:123
1POWER & WIRING CABLES
®
1:124
POWER & WIRING CABLES
®
1Technical Information• Three Core PILC/SWA/PVC Power Cable6350/11000V, "Belted"
Laid Direct in In Single-Way Ducts In Air
Nom Area the ground
of Conductor Armoured Armoured Armoured
mm2 A A A
16 89 76 80
25 115 99 105
35 140 120 130
50 165 140 155
70 205 175 195
95 245 210 240
120 280 240 275
150 315 265 315
185 355 300 360
240 410 355 425
300 460 395 490
400 520 445 560
Standard depth of laying 0.8mThermal resistivity of soil 1.20C m/WStandard ground temperature 150CAmbient air temperature 250CMaximum conductor temperature 650C
CURRENT CARRYING CAPACITY (Amperes)
1:125
1POWER & WIRING CABLES
®
For further guidance refer to 16th Edition IEE Wiring Regulations.
NB: High voltage cables are not specifically covered in IEE Wiring Regulations but
reference should be made to ensure compliance.
For ambient air and ground temperatures other than those specified, the following
factors should be applied.
Cables Laid in Air
Ambient air temperature 25 30 35 40 45
Rating factor 1.0 0.93 0.85 0.77 0.68
Cables Laid Direct and in Single-Way Ducts
Ground Temperature 0C 10 15 20 25 30
Rating Factor 1.05 1.0 0.95 0.89 0.84
1:126
POWER & WIRING CABLES
®
1Technical Information• Three core PCU/PILC/SWA/PVC 6350/11000V “Belted” to BS6480
ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance
Size conductor conductor @ 50Hz @ 650C, 50Hzresistance resistance
@ 200C @ 650Cmm2 ohms/km ohms/km ohms/km ohms/km
16 1.15 1.354 0.112 1.3625 0.727 0.856 0.105 0.86235 0.524 0.617 0.0930 0.62450 0.387 0.456 0.0945 0.46670 0.268 0.316 0.0900 0.32995 0.193 0.228 0.0870 0.244120 0.153 0.181 0.0835 0.199150 0.124 0.147 0.0820 0.168185 0.0991 0.118 0.080 0.143240 0.0754 0.0907 0.0780 0.120300 0.0601 0.0732 0.0765 0.106400 0.047 0.0585 0.0750 0.0951
1:127
1POWER & WIRING CABLES
®
CURRENT CARRYING CAPACITY (Amperes)Nom. Area Laid Direct In Single-Way In Air
of Conductor in Ground Ductsmm2 A A A
95 185 160 180185 270 230 270300 355 270 370
Standard depth of laying 0.8m
Thermal resistivity of soil 1.20C m/WStandard ground temperature 150C
Ambient air temperature 250C
Maximum comductor temperature 650C
Technical Information• Three core PICAS/PVC 6350/11000V “Belted” M.I.N.D
ALUMINIUM Conductors
ELECTRICAL CHARACTERISTICSConductor Max DC Max AC Reactance Impedance
Size conductor conductor @ 50Hz @ 650C, 50Hzresistance resistance
@ 200C @ 650Cmm2 ohms/km ohms/km ohms/km ohms/km
95 0.320 0.379 0.087 0.389185 0.164 0.195 0.080 0.211300 0.100 0.120 0.077 0.143
1:128
POWER & WIRING CABLES
®
1Technical Information400Hz Power Cable
Nominal Current Carrying Voltage Drop
Conductor Capacity in Three Phase a.c.
Area Free Air (300C) 400Hzmm2 700C 900C 700C 900C
Cond Cond Cond CondTemp Temp Temp Temp
A A mV/A/m mV/A/mr x z r x z
35 220 261 0.549 0.492 0.74 0.594 0.492 0.77
Max DC conductor resistance @ 200C ohms/km 0.524 Max AC conductor resistance @ 900C 400Hz
Per phase ohms/km 0.343Neutral ohms/km 0.686
Max AC conductor resistance @ 700C 400HzPer phase ohms/km 0.317Neutral ohms/km 0.630
Reactance @ 400HzPer phase (diametrically opposite cores) ohms/km 0.284Neutral (to adjacent cores) ohms/km 0.500
CURRENT RATINGS & VOLTAGE DROP
ELECTRICAL CHARACTERISTICS
1:129
1POWER & WIRING CABLES
®
For ambient air temperatures other than 300C, the following rating factors should
be applied.
900C conductor operating temp.
Ambient air temperature 0C 25 30 35 40 45 50 55
Rating factor 1.04 1.0 0.96 0.91 0.87 0.82 0.76
700C conductor operating temp.
Ambient air temperature 0C 25 30 35 40 45 50 55
Rating factor 1.06 1.0 0.94 0.87 0.79 0.71 0.61
Technical Information
• Three core type MCCMK screened power cable
NominalConductor
Areamm2
Current CarryingCapacity in
Free AirA
Current CarryingCapacity Buried
DirectA
Voltage DropThree Phase a.c.
mV/A/m
2.5 26 36 156.0 45 57 6.410 63 78 3.816 84 101 2.425 107 130 1.5235 133 156 1.1050 162 185 0.8295 252 271 0.43150 338 349 0.30185 385 389 0.25
Standard depth of laying 0.7mThermal resistivity of soil 1.0°C m/WStandard ground temperature 15°CAmbient conductor temperature 25°CMaximum conductor temperature 70°C
CURRENT RATING & VOLTAGE DROP
POWER & WIRING CABLES1
1:130
NomCond.Size
Max DCconductorresistance@ 200C
Max DCscreenresistance@ 200C
Max ACconductorresistance@700C
Reactance@ 50Hz
Impedance@ 700C,50Hz
Conductorshort-circuitrating (1s)
Screenshort-circuitrating (1s)
mm2 ohms/km ohms/km ohms/km ohms/km ohms/km kA kA2.5 7.41 7.41 8.87 0.101 8.87 0.3 0.426.0 3.08 3.08 3.69 0.095 3.69 0.7 1.010 1.83 1.83 2.19 0.093 2.19 1.1 1.716 1.15 1.15 1.38 0.088 1.38 1.8 2.725 0.727 1.15 0.871 0.087 0.875 2.8 2.735 0.524 1.15 0.628 0.082 0.633 3.9 2.750 0.387 0.727 0.465 0.082 0.472 5.5 4.495 0.193 0.387 0.234 0.079 0.247 10.5 7.2150 0.124 0.268 0.153 0.076 0.171 16.5 10.4185 0.0991 0.193 0.124 0.076 0.145 20.3 13.4
For ambient air and ground temperatures other than those specified, the followingrating factors should be applied:
Cables Laid in Air
Ambient air temperature 20 25 30 35 40 45 50Rating factor
Cables Laid Direct in Ground
Ground temperature °C 10 15 20 25 30 35 40 45 50Rating factor 1.04 130 0.95 0.90 0.85 0.74 0.60 0.67 0.60
Transfer Impedance (screen effectiveness)
Maximum transfer impedance<10 mohms/m at frequencies up to 1GHz*.
*Maximum recommended limit from ABB installation guide for frequency convertersis 100mΩ/m.
1POWER & WIRING CABLES
ELECTRICAL CHARACTERISTICS
1:131
1:132
POWER & WIRING CABLES
®
1
CURRENT RATINGS & VOLTAGE DROP
Technical Information• XVB-F2 Multicore Power Cable600/1000 V XLPE/PVC 900C
Conductor Reference Method 3 Reference Method 1 Reference Method 11 or 13 Voltage DropSize (enclosed in (clipped direct) (in cable tray/free air)
conduit/trunking etc)Single Three Single Three Single Three Single ThreePhase Phase Phase Phase Phase Phase Phase Phase
a.c./d.c. a.c. a.c./d.c. a.c. a.c./d.c. a.c. a.c./d.c. a.c.mm2 A A A A A A mV/A/m mV/A/m
1.5 22 19.5 24 22 26 23 31 272.5 30 26 33 30 36 32 19 164.0 40 35 45 40 49 42 12 106.0 51 44 58 52 63 54 7.9 6.810 69 60 80 71 86 75 4.7 4.016 91 80 107 96 115 100 2.9 2.525 119 105 138 119 149 127 1.9 1.65
Ambient air temperature: 300C
Conductor operating temperature: 900C
For ambient temperatures other than 300C, the following factirs should be applied:
Ambient air temperature 0C 20 25 30 35 40 45 50 55
Rating factor 1.08 1.04 1.0 0.96 0.91 0.87 0.82 0.76
The above current ratings for single phase are based on only two cores loaded simultaneously.
Where more than two cores are loaded simultaneously and known to carry appreciable
current*, the following factors apply:
No. of cores loaded 3 4 5 6 7 10 12 14 19
Rating factor 0.87 0.78 0.72 0.67 0.63 0.56 0.53 0.51 0.45
* The normal two core rating may be taken in cases where the number of cores carrying
appreciable current does not exceed the square root of the total number of cores.
1:13 31
1POWER & WIRING CABLES
®
ELECTRICAL CHARACTERISTICS
Conductor Max. DC Max. AC Reactance Impedance @Size conductor conductor @ 50 Hz 900C, 50 Hz
resistance @ resistance @200C 900C
mm2 ohms/km ohms/km ohms/km ohms/km
1.5 12.1 15.4 0.108 15.42.5 7.41 9.45 0.100 9.454.0 4.61 5.88 0.094 5.886.0 3.08 3.93 0.0885 3.9310 1.83 2.33 0.0835 2.3316 1.15 1.47 0.0815 1.4725 0.727 0.927 0.0818 0.931
1:134
POWER & WIRING CABLES
®
1
Technical Information
• 600/1000 Volts XLPE/LSF 90°C
Referen
(enccondu
Conductor
Size
SinglePhasea.c./d.c
mm² A1.5 222.5 304.0 406.0 5110 6916 9125 119
Ambient air temp
Conductor opera
For ambient temp
Ambient air tempRating Factor
POWER & WIRING CABLES
CURRENT RATING & VOLTAGE DROP
ce Method3
losed init/trunkingetc)
Reference Method 1(clipped direct)
ReferenceMethod 11 or 13
(on cabletray/freeair)
Voltage Drop
ThreePhase
a.c.
SinglePhasea.c./d.c
ThreePhase
a.c.
SinglePhasea.c./d.c
ThreePhase
a.c
SinglePhasea.c/d.c
ThreePhasea.c/d.c
A A A A A mV/A/m mV/A/m19.5 24 22 26 23 31 2726 33 30 36 32 19 1635 45 40 49 42 12 1044 58 52 63 54 7.9 6.860 80 71 86 75 4.7 4.080 107 96 115 100 2.9 2.5
105 138 119 149 127 1.9 1.65
erature: 30°C
ting temperature: 90°C
eratures other than 30°C, the following factors should be applied:
. C° 20 25 30 35 40 45 50 551.08 1.04 1.0 0.96 0.91 0.87 0.82 0.76
1
1:135
POWER & WIRING CABLES
1Electrical CharacteristicsConductorSize Max. DC
conductorresistance @
20°C
Max. ACconductor
resistance @90°C
Reactance@ 50 Hz
Impedance @90°C, 50 Hz
mm² ohms/km ohms/km ohms/km ohms/km1.5 12.1 15.4 0.104 15.42.5 7.41 9.45 0.101 9.454.0 4.61 5.88 0.094 5.886.0 3.08 3.93 0.0952 3.9310 1.83 2.33 0.0856 2.3316 1.15 1.47 0.0818 1.47
S
1:136
ELECTRICAL CHARACTERISTIC