These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.01Hardie Reveal2.0™ Panel Vertical Siding (7/16" Thick)• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panhead Screws into Furring
0
SCALE: 1" = 4"
2" 4"
SECTION DETAIL – FOUNDATION @ GRADE
WATER RESISTIVE BARRIER
EXTERIOR SHEATHING
GRADE
MINIMUM 3/4" FURRING
VENT STRIP
1/2" SPACING MINIMUM
DRAINAGE FLASHING
CODE APPROVED
SILL SEAL(AS REQ’D PER CODE) MIN. 6" UNFINISHED GRADE
CLEARANCE, 2" SLAB, DECK, ORSIDEWALK CLEARANCE, OR CODEREQ'D, WHICHEVER IS SMALLER
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
#10-12 T20W PAN HEAD SCREW
SECTION DETAIL – PANEL WITH HORIZONTAL TRIM
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.02Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
EXTERIOR SHEATHING
1/2" SPACING
HORIZONTAL TRIM
MINIMUM 3/4" FURRING
WATER RESISTIVE BARRIERCODE APPROVED
#10-12 T20W PAN HEAD SCREW
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
SECTION DETAIL – PANEL WITH HORIZONTALTRIM @ FLOOR BREAK
DETAIL:
Rev. 4 (2012)
Reveal2.0™
1.03Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panhead Screws into Furring
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
0
SCALE: 1" = 4"
2" 4"
HARDIE REVEAL2.0™ PANEL VERTICAL SIDINGHORIZONTAL TRIM CAN ALSO BEUSED AT THE FLOOR BREAK;HOWEVER A DRAINAGE FLASHINGIS REQUIRED TO BE USED EVERYOTHER FLOOR.
CODE APPROVEDWATER RESISTIVE BARRIER
EXTERIOR SHEATHING
MINIMUM 3/4” FURRING
TAPE
1/2” GAP, DO NOT CAULK
DRAINAGE FLASHING
NOTE: DO NOT FASTEN PANELACROSS A BRIDGED FLOOR ASSURE ACOMPLIMENTARY BREAK EXISTS FORPLYWOOD FURRING AND PANEL
NOTE: THE PANEL JOINT CAN BE ATTHE TOP OR BOTTOM OF THE JOIST.
#10-12 T20W PAN HEAD SCREW
PLAN DETAIL – PANEL WITH VERTICAL TRIM
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.04Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Countersunk Screws into Furring
0
SCALE: 1" = 2"
1" 2"
1/2"
CODE APPROVEDWATER RESISTIVE BARRIER
INTERIOR SHEATHING
EXTERIOR SHEATHING
MINIMUM 3/4” FURRINGVERTICAL TRIM
HARDIE REVEAL2.0™ PANEL VERTICAL SIDING
#10-12 T20W PAN HEAD SCREW
PLAN DETAIL – OUTSIDE CORNER TRIM
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.05Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
EXTERIOR SHEATHING
OUTSIDE CORNER TRIM
MINIMUM 3/4" FURRING
WATER RESISTIVE BARRIERCODE APPROVED
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
#10-12 T20WPAN HEAD SCREW
PLAN DETAIL – INSIDE CORNER TRIM
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.06Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
VERTICAL F-TRIM
CODE APPROVED
EXTERIOR SHEATHING
MINIMUM 3/4" FURRING
WATER RESISTIVE BARRIER
HARDIE REVEAL2.0™ PANEL VERTICAL SIDING
#10-12 T20W PAN HEAD SCREW
SECTION DETAIL – WALL & SOFFIT FORVENTED RAINSCREEN
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2012)
Reveal2.0™
1.07Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greater• Shown with Panyhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
EXTERIOR SHEATHING
WATER RESISTIVE BARRIER
J-CHANNEL TRIM
MINIMUM 3/4" FURRING
SOFFIT
CODE APPROVED
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
#10-12 T20W PAN HEAD SCREW
1/8" GAP
VENT STRIP
SECTION DETAIL – WALL & SOFFIT FORVENTILATED RAINSCREEN
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.08Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
EXTERIOR SHEATHING
WATER RESISTIVE BARRIER
SOFFIT
HORIZONTAL TRIM
MINIMUM 3/4" FURRING
CODE APPROVED
FRIEZE BOARD
DISCONTINUOUS BLK'G REQ'D FOR VENTING
VENT STRIP
FRIEZE BLOCK INTAKE VENT @ 3/8"
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
#10-12 T20W PAN HEAD SCREW
SECTION DETAIL – SOFFIT FLASHINGINTERSECTION
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.09Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
WATER RESISTIVE BARRIERCODE APPROVED
SOFFIT
FLASHING
DO NOT CAULKMINIMUM 1/2" GAP,
TAPE
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
#10-12 T20WPAN HEAD SCREW
SECTION DETAIL – DOOR HEADERINTERSECTION
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.10 Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
CODE APPROVEDWATER RESISTIVE BARRIER
WRB TURNEDINTO OPENING
INCLUDE AN AIR SEALB/W DOOR AND WRB
MINIMUM 3/4” FURRING
1/2”
MIN
.
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
DRAINAGE FLASHING
AIR SEAL
DOOR ORWINDOW HEADER
VENT STRIP
#10-12 T20WPAN HEAD SCREW
SECTION DETAIL – ALUMINUM WINDOW HEAD
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.11Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
WINDOW FRAME
VENT STRIP
DRAINAGE FLASHING
SEALANT
MIN. 1/2" GAP
WINDOW FLASHING
WATER RESISTIVE BARRIERCODE APPROVED
NOTE:FACTORY SEALED EDGES ARE BEST ATBOTTOM HORIZONTAL, BUT NOT REQUIRED
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
MINIMUM 3/4" FURRING
#10-12 T20W PAN HEAD SCREW
SECTION DETAIL – ALUMINUM WINDOW HEAD
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.11bHardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
WINDOW FRAME
VENT STRIP
DRAINAGE FLASHING
MIN. 1/2" GAP
WINDOW FLASHING
WATER RESISTIVE BARRIERCODE APPROVED
NOTE:ALL CUT EDGES MUST BE SEALED.
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
MINIMUM 3/4" FURRING
#10-12 T20W PAN HEAD SCREW
SECTION DETAIL – ALUMINUM WINDOW SILL
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.12Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
SEALANT W/ BACKER ROD
WINDOW FRAME
SILL FLASHING
WATER RESISTIVE BARRIERCODE APPROVED
HORIZONTAL EDGE TRIM
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
MINIMUM 3/4" FURRING
#10-12 T20W PAN HEAD SCREW
SECTION DETAIL – FLANGED WINDOW SILL
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.12bHardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
SEALANT W/ BACKER ROD
WINDOW FRAME
SILL FLASHING
WATER RESISTIVE BARRIERCODE APPROVED
HORIZONTAL EDGE TRIM
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
MINIMUM 3/4" FURRING
#10-12 T20W PAN HEAD SCREW
PLAN DETAIL – ALUMINUM WINDOW FLANGEWITH METAL TRIM
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.13Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
#10-12 T20WPAN HEAD SCREW
WATER RESISTIVE BARRIERCODE APPROVED
DOOR / WINDOW JAMB
BACKER ROD & SEALANT
FLASHING TAPE
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
MINIMUM 3/4" FURRING
VERTICAL F-TRIM
PLAN DETAIL – ALUMINUM WINDOW FLANGEWITH METAL TRIM
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.13bHardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
#10-12 T20WPAN HEAD SCREW
WATER RESISTIVE BARRIERCODE APPROVED
DOOR / WINDOW JAMB
BACKER ROD & SEALANT
FLASHING TAPE
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
MINIMUM 3/4" FURRING
VERTICAL F-TRIM
PLAN DETAIL – ALUMINUM WINDOW FLANGEWITH TRIM BOARDS
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.14Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
CODE APPROVED
VERTICAL F-TRIM
WATER RESISTIVE BARRIER
JAMBDOOR / WINDOW
BACKER ROD & SEALANT
FLASHING TAPE
HARDIETRIM® BOARDSLEAVE MIN. 1/8" GAP & CAULK
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
MINIMUM 3/4" FURRING
SECTION DETAIL – 1 1/2" OR LESS HOLEPENETRATION TREATMENT
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.15Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 2"
1" 2"
SEALANT W/ BACKER ROD
SEALANT
PIPE 1-1/2" OR LESS
EXTERIOR SHEATHING
FOAM SEALANT
MINIMUM 3/4" FURRING
MINIMUM 3/4" FURRING
WATER RESISTIVE BARRIERCODE APPROVED
SELF ADHERED FLASHING
NOTE:EXTERNAL BLOCKING IS RECOMMENDED WHEN PENETRATION OCCURS AFTER THE INSTALLATION OF PANEL
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
SECTION DETAIL – BLOCK PENETRATIONTREATMENT
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.16Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 4"
2" 4"
EXTERIOR SHEATHING
BLOCKING AS REQ'D
FURRING AROUND FIXTURE
FLASHING
TRIM AROUND OPENING
MIN. 1/2" GAP, DO NOT CAULK
HARDIETRIM® BOARDS / BLOCKING
VENT OPENING
LEAVE MIN. 1/8" GAP AND CAULK
BENT DRYER FLANGE
MINIMUM 3/4" FURRING
WATER RESISTIVE BARRIERCODE APPROVED
OPTIONAL:USE HORIZONTAL EDGE TRIM ON SILL& VERTICAL F-TRIM ON SIDES
NOTE:CAULK 3 SIDES, BUT NOT TOP.J-CHANNEL TRIM IS OPTIONAL
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
#10-12 T20W PAN HEAD SCREW
SECTION DETAIL – VENTED PARAPET WALL
These drawings are published as an information guide only. These CAD drawings are intended as templates to assist the designer. They do not contain the full details required for construction and must be read in conjunction with the installation instructions on www.jameshardiecommercial.com. You should obtain architectural, engineering or other technical advice to assess the suitability of these drawings to the requirements of your particular project. James Hardie accepts no liability in respect to the use of these drawings.
For fastener specifications and complete installation instructions refer to appropriate documentation at www.JamesHardieCommercial.com.
DETAIL:
Rev. 4 (2013)
Reveal2.0™
1.17Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
0
SCALE: 1" = 4"
2" 4"
VENT STRIP
CAPPINGUNDERLAY TO PROVIDE ISOLATIONOF METAL FLASHING TO TIMBER
EXTERIOR SHEATHING
SELF-ADHERED FLASHING
CODE APPROVEDWATER RESISTIVE BARRIER
1/8" GAP
HARDIE REVEAL2.0™ PANELVERTICAL SIDING
NOTE:DO NOT USE HARDIE TRIM OR BOARD AS CAP FLASHING
MINIMUM 3/4" FURRING
#10-12 T20WPAN HEAD SCREW
HORIZONTAL TRIM - TERMINATIONDETAIL:
Rev. 4 (2013)
Reveal2.0™
1.18Hardie Reveal2.0™ Panel Vertical Siding• Wood Framing• OSB or Plywood Sheathing• Pressure-Treated Wood Furring (Minimum 3/4" Nominal, 23/32" Actual Thickness) having specific gravity of 0.42 or greate• Shown with Panhead Screws into Furring
FACTORY CUT ENDSHORIZONTAL TRIMTERMINATION END CUTS