USER MANUALPSS/E Model for Vestas GridStreamer TM Wind Turbines
Version 8.0
: s ocument conta ns vaua e con ent a n ormat on o estas n ystems / . t s protecte y copyr g t aw as an unpu s e wor . estas reserves a patent, copyr g t ,trade secret, and other proprietary rights to it. The information in this document may not be used, reproduced, or disclosed except if and to the extent rights are expressly granted by Vestas in writing and subject to applicableconditions. Vestas disclaims all warranties except as expressly granted by written agreement and is not responsible for unauthorized uses, for which it may pursue legal remedies against responsible parties.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 2/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 2 of 53
DISCLAIMER
VESTAS MAKES NO WARRANTY OR REPRESENTATION EITHER EXPRESS OR IMPLIED IN RESPECTOF THE PSS/E MODEL, INCLUDING WITHOUT LIMITATION AS TO ACCURACY, COMPLETENESS,FUNCTIONALILTY, PRECISION, USEFULNESS, FITNESS FOR A PARTICULAR PURPOSE OF THE PSS/EMODEL OR OTHERWISE. THE PSS/E MODEL IS PROVIDED “AS IS” AND VESTAS SHALL HAVE NORESPONSIBILITY OR LIABILITY WHATSOEVER FOR RESULTS OF USE OR PERFORMANCE OF THEPSS/E MODEL. TO THE MAXIMUM EXTENT PERMITTED BY LAW, IN NO EVENT VESTAS SHALL BELIABLE FOR ANY CONSEQUENTIAL DAMAGES, DIRECT, INDIRECT, SPECIAL, PUNITIVE OR OTHERDAMAGES WHATSOEVER ARISING OUT OF OR IN ANY WAY RELATED TO THE USE OF OR INABLITYTO USE THE PSS/E MODEL, WHETHER BASED IN CONTRACT, TORT, NEGLIGENCE, STRICT LIABILITY
OR OTHERWISE.
For the avoidance of doubt, Vestas makes no warranty or representation either express or implied as tothe performance of the wind turbine model in terms of it being in accordance with the performance ofthe actual wind turbine generator, as other circumstances, including, but not limited to deviations in themarkets and optional features might have influence on the performance of the actual wind turbine gen-erator. The performance of the wind turbine model is expected only to be indicative to the performanceof the actual wind turbine generator.
Copyright Notice The documents are created by Vestas Wind Systems A/S and contain copyrighted material,trademarks, and other proprietary information. All rights reserved. No part of the documentsmay be reproduced or copied in any form or by any means—such as graphic, electronic, or
mechanical, including photocopying, taping, or information storage and retrieval systems—without the prior written permission of Vestas Wind Systems A/S, and its respective parentcompanies, subsidiaries, affiliates, successors, assigns, licensees, representatives andagents (together "Vestas"). The use of these documents by you, or anyone else authorizedby you, is prohibited unless specifically permitted by Vestas. You may not alter or removeany trademark, copyright or other notice from the documents.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 3/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 3 of 53
History of this Document
Changes in this document:
Rev. no.: Date: Description of change
00 2013-04-01 This document is based on a previous document with docu-ment number 0026-5729_V03.Updated document to reflect changes of Pre-sales model ofGridStreamer TM 3.3MW Turbines.Only parameters of GridStreamer TM 3.3MW Turbines areavailable in this version.
01 2013-04-05 Parameters of V164 8.0MW Mk0 concept model are included
in this version.02 2013-07-04 Parameters of V80/V90 2.0MW Mk8 model are included in this
version
03 2013-09-06 Updated document to reflect changes of As-built model ofGridStreamer TM Turbines.Only parameters of 3 MW Turbines are available in this ver-sion.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 4/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 4 of 53
Contents
History of this Document .......................................................................................................... 3
Contents .................................................................................................................................. 4
Abbreviations ........................................................................................................................... 6
Reading Guidelines ................................................................................................................. 7
1 Introduction ...................................................................................................................... 8
2 Vestas GridStreamer TM Model ......................................................................................... 9
2.1 Vestas GridStreamer TM Concept ............................................................................. 9
2.2 Model Structure ....................................................................................................... 9
2.3 Model Features ..................................................................................................... 10
3 Simulation Preparation .................................................................................................. 11
3.1 Load Flow Data ..................................................................................................... 11
3.2
Short Circuit Data .................................................................................................. 12
3.3 Dynamic Data ....................................................................................................... 12
4 Simulation Procedures in PSS/E ................................................................................... 15
4.1 Setting for Dynamic Simulation ............................................................................. 16
4.2 Simulation Steps ................................................................................................... 17
5 Vestas System Example................................................................................................ 19
5.1 System Model ....................................................................................................... 19
5.2 Simulation Steps ................................................................................................... 20
6 Description of related PSS/E Activities .......................................................................... 21
6.1 WTG Load Flow related Inputs ............................................................................. 21
6.2 WTG 2-Winding Transformer Load Flow Inputs .................................................... 22
6.3
Output Channels for Plotting ................................................................................. 23
7 User related Sub-models of Vestas Wind Turbines ....................................................... 25
7.1 Reactive Power Control ........................................................................................ 25
7.2 LVRT Control Settings .......................................................................................... 26
7.3 Protection & LVRT Settings .................................................................................. 27
7.3.1 Voltage Protection ...................................................................................... 27
7.3.2 LVRT Logic ................................................................................................. 28
7.3.3 Frequency Protection ................................................................................. 29
8 PSS/E Format Data Sheets ........................................................................................... 31
8.1 GSCORE .............................................................................................................. 32
8.2
GSVARS ............................................................................................................... 35
8.3 GSLVRT................................................................................................................ 36
8.4 GSPWRC .............................................................................................................. 38
8.5 GSMEAS............................................................................................................... 40
8.6 GSVPRT ............................................................................................................... 41
8.7 GSFPRT ............................................................................................................... 43
Appendix A. Data for V112 GS 3.075/3.0MW 50/60Hz................................................... 44
A.1 PQ Capability Chart .............................................................................................. 44
A.2 Generator Data ..................................................................................................... 45
A.3 Typical Transformer Data...................................................................................... 45
A.4 PSS/E DYR File Template .................................................................................... 45
Appendix B.
Data for V112/V117/V126 GS 3.3MW 50/60Hz .......................................... 50
B.1 PQ Capability Chart .............................................................................................. 50
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 5/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 5 of 53
B.2 Generator Data ..................................................................................................... 51
B.3 Typical Transformer Data...................................................................................... 51
B.4 PSS/E DYR File Template .................................................................................... 51
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 6/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 6 of 53
Abbreviations
Word / Abbreviation DescriptionAGO Advanced Grid Option
Bvbase Bus Voltage Base
GS GridStreamer
LVRT Low Voltage Ride Through
Mbase Machine MVA Base
OF Over Frequency
OV Over Voltage
P Active Power
PF Power Factor
PI Proportional and IntegralPPC Power Plant Controller
PSS/E Power System Simulator for Engineering
Q Reactive Power
SCR Short Circuit Ratio
Sbase System (Network) MVA Base
UF Under Frequency
UV Under Voltage
VXX V refers to Vestas & XX is the rotor diameter in meters
YY WTG Rated Power
ZZ WTG Rated Frequency
WTG Wind Turbine Generator
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 7/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 7 of 53
Reading Guidelines
This document covers the Vestas GridStreamer TM wind turbines model implementation in the
PSS/E environment. The targeted group of readers are expected to have: A good knowledge of the PSS/E simulation environment.
A strong background in the electrical power engineering field.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 8/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 8 of 53
1 Introduction
The description given in this document covers the design of the Vestas PSS/E wind turbine
user written model. The model is applicable to all Vestas GridStreamer TM wind turbines.
This document is a user manual that explains how to implement the Vestas GridStreamer TM wind turbines in an existing grid and states a number of steps that must be performed to geta successful simulation.
The document is a general overview of the PSS/E user written model version 8.0 for VestasGridStreamer TM wind turbines. The model is developed for the purpose of dynamic stabilityanalysis and therefore generally omits effects with time constants shorter than one AC cycle. A PSS/E time step (DELT) in the range 1ms to ½ cycle is recommended.
Vestas PSS/E Model Package
This user manual is part of a model package including the following files:
PSS/E Model for Vestas GridStreamer TM Wind Turbines Version 8.0 User Manual
A library file (.LIB) that includes all the sub models in the wind turbine is compiled for PSS/Eversion 29, 30, 31 and 32.
VestasGS_8_0_n_PSSE<m>.lib – Model library file for PSS/E ver. <m>
A Dynamic data file (.DYR).
V<xx>.GS.<yy>MW.<zz>Hz. Mk<k>.Df.v8.0.n.dyr – Dynamic Data file (.dyr)
Test case files as part of a system example.
V<xx>.GS.<yy>MW.<zz>Hz. Mk<k>.Df.v8.0.n_Base_29.raw
V<xx>.GS.<yy>MW.<zz>Hz. Mk<k>.Df.v8.0.n_Base_32.sav
Simulate_PFControl.psa
Simulate_QControl.psa
V<xx>.GS.<yy>MW.<zz>Hz. Mk<k>.Df.v8.0.n.dyr
This system example is provided for guidance only and do not represent actual configurationfor any specific site.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 9/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 9 of 53
2 Vestas GridStreamer TM
Model
This PSS/E user written model has been developed to support the Vestas GridStreamer TM wind turbines topology. This is explained – in short - in the following sections.
2.1 Vestas GridStreamer TM ConceptIn the full-scale converter system the generator is decoupled from the grid-side convertercompletely by the DC-link. In this case the converter will be in total control of the powerand the GridStreamer ™ WTG is coupled via a step-up transformer to the connection point.
2.2 Model Structure
The PSS/E user written model developed for the Vestas GridStreamer ™ wind turbine is asimplified ‘dynamic’ model of the WTG and omits some detail of mechanical componentsand the generator-side converter. However, this model was shown to accurately representthe complete GridStreamer™ turbine, because the mechanics and generator -side con-verter have very little impact on the grid-side output due to decoupling through the DC-link.
Figure 1 shows the generic model structure for Vestas GridStreamer TM wind turbines.Here the various signals and blocks may be observed as well as input and output of themodel. Note that the grey blocks are not part of the PSS/E model, and have directfeedthrough signals.
Figure 1 Illustration of the generic PSS/E model structure. Blocks marked as grey are not a part ofthe model
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 10/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 10 of 53
As mentioned in the Introduction, this model is intended for grid dynamic stability analysis.It may also be designated as a performance model, since it receives grid voltage and fre-quency and delivers active and reactive power as response.
2.3 Model FeaturesIt is important to decide the types of analysis and studies needed to be carried out beforedeciding which approach to use in modelling the physical system. The modelling approachshould reflect the intended types of analysis and studies.
These questions led to shape the modelling requirements and to give a better overview ofthe user’s needs in order to develop an analysis-dedicated model. The modelling of thewind turbine needs to be made according to the performance of the simulation tool, whichis the PSS/E.
The pre-modelling analysis has been done for using PSS/E simulation tool and the out-come is listed in Table 1.
Table 1 Outcome of the pre-modelling analysis
Model purpose Dynamic stability studies – 1s to 5 min.
Implementation in large bus system.
Aggregated Wind-power plant performance.
Model operational range Full power range of the WTG.
PF control mode. Reactive power control mode.
Full voltage and frequency range of WTG.
Studies Dynamic stability analysis.
Protection Voltage settings.
Frequency settings.
LVRT settings.
Model requirements Positive sequence based. Model bandwidth 0-10 Hz.
Maximum time step is ½ cycle.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 11/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 11 of 53
3 Simulation Preparation
This section explains how to add Vestas Wind Turbines Model and modify the user’s exist-ing system simulation files. With the package files provided by Vestas Wind Systems A/S,the end users should modify their load flow data (RAW or SAV file) as well as their dynam-ic data (DYR file). The suggested modifications are stated below.
3.1 Load Flow DataThe PSS/E user should begin by preparing a solved load flow case which includes a gen-erator and unit transformer for each WTG or WTG aggregate.
-The WTG’s Generator :
The wind power plant units can be included as separate units or as a single aggregatedgenerator, with appropriate steady-state real power (P) and reactive power (Q) for eachwind power plant (turbine). The relevant WTG generator should be implemented by theuser according to the parameters listed in Appendices and the set up instructions in Chap-ter 6.
NOTE : In newer versions of PSS/E a generator is added to the load flow case as either a‘classical machine’ or a ‘wind machine’. The Vestas wind turbines should be added as a
classical machine not a wind machine, as the model is designed to be back compatible toPSS/E version 29.
- The WTG’s Transformer :
In addition to the substation transformer, a step-up unit transformer should also be includ-ed in the load flow case by the user. The delivered model package does not include theWTG transformer and therefore this transformer should be implemented by the user ac-cording to the parameters of the transformer as given in Appendices and the set up in-structions provided in Chapter 6.
The user may refer to the raw file template in Template 1.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 12/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 12 of 53
0, 100.00 / PSS/E-30.3 TUE, OCT 30 2007 14:42
VESTAS TEST SYSTEM
/****************************************************************
/*existing bus data */*add WTG bus data here *
/****************************************************************
0 / END OF BUS DATA, BEGIN LOAD DATA
0 / END OF LOAD DATA, BEGIN GENERATOR DATA
/****************************************************************
/*existing generator data *
/*add WTG generator data here *
/****************************************************************
0 / END OF GENERATOR DATA, BEGIN BRANCH DATA
0 / END OF BRANCH DATA, BEGIN TRANSFORMER DATA
/****************************************************************
/*existing transformer data *
/*add WTG transformer data here */****************************************************************
0 / END OF TRANSFORMER DATA, BEGIN AREA DATA
0 / END OF AREA DATA, BEGIN TWO-TERMINAL DC DATA
0 / END OF TWO-TERMINAL DC DATA, BEGIN VSC DC LINE DATA
0 / END OF VSC DC LINE DATA, BEGIN SWITCHED SHUNT DATA
0 / END OF SWITCHED SHUNT DATA, BEGIN IMPEDANCE CORRECTION DATA
0 / END OF IMPEDANCE CORRECTION DATA, BEGIN MULTI-TERMINAL DC DATA
0 / END OF MULTI-TERMINAL DC DATA, BEGIN MULTI-SECTION LINE DATA
0 / END OF MULTI-SECTION LINE DATA, BEGIN ZONE DATA
0 / END OF ZONE DATA, BEGIN INTER-AREA TRANSFER DATA
0 / END OF INTER-AREA TRANSFER DATA, BEGIN OWNER DATA
0 / END OF OWNER DATA, BEGIN FACTS DEVICE DATA
0 / END OF FACTS DEVICE DATA Template 1: The PSS/E raw file template
3.2 Short Circuit DataUnder fault conditions the behaviour of the WTG is determined by the converter control.During a fault the converter controls will limit the magnitude of the fault current contributionto 1.05 p.u. (Ik”) and 1.45 p.u. (peak) on WTG rated current.
The WTG should be modelled as a current source for short circuit studies. The currentsource should contribute a maximum of 1.05 p.u. (Ik”) fault current.
In PSS/E the value of Zsource is obtained from the maximum short circuit current contri-bution (Ik”=1.05 p.u.). The recommended values are listed in Appendices and the set upinstructions provided in Chapter 6.
3.3 Dynamic DataThe user should prepare a DYR file (.dyr) containing the dynamics data. This will generallyinclude dynamic data records for other power system plant(s), as well as the dynamic datafor Vestas WTG model. In this package the user will find a parameter template(V<xx>.GS.<yy>MW.<zz>Hz.Mk<k>.Df.v8.0.n.dyr) as shown in Template 2. The template
for different Vestas GridStreamer
TM
wind turbines can be found in Appendices.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 13/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 13 of 53
/********************************************************************************
/
/ MODULE: Vestas Generic Model Dynamic Data Template for PSS/E
/ Model revision: 8.0.1/ WTG type: V112 GridStreamer 3.3MW 50Hz Mk2A
/
/********************************************************************************
/ The lines below must be repeated for each wind generator or composite
/ wind farm generator that occurs in the network.
/ Terms in <angle brackets> must be replaced as follows:
/ <bus> with the generator bus number
/ <mach> with the machine ID
/ <WTGmode> with the control mode at WTG level: 0 for Q control, 1 for PF control
/********************************************************************************
<bus> 'USRMDL' '<mach>' 'GSCORE' 1 1 2 45 23 104 1 0
3300.0000 650.0000 4144.0000 0.0100 0.0000 0.0000 0.0000
0.3500 7.8500 0.000082 940.0000 -3700.0000 3700.0000 -3300.00003300.0000 0.9700 0.8500 0.7500 1.0000 1.0000 0.0000
0.0000 0.0000 0.0000 0.0300 0.3000 0.0000 0.0000
0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVARS' 8 0 2 0 0 30 <bus> '<mach>' /
0 'USRMDL' 0 'GSLVRT' 8 0 3 65 10 35 <bus> '<mach>' 1
0.8500 0.0000 0.6000 10.0000 200.0000 100.0000 200.0000
0.0000 1.0800 0.0050 1.0050 1.4400 0.0000 650.0000
4144.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.9000 0.0000 0.0000 0.0100
0.0000 0.0000 2.0000 1.0000 0.0000 1.0500 -1.0000
1.2000 0.8500 0.1500 0.0500 0.1000 0.4900 0.50000.8000 0.3900 0.4000 0.0000 0.0000 0.0500 0.9000
1.1000 0.0000 0.8000 0.9000 1.1000 1.2000 0.1000
2.5000 0.6000 600.0000 60.0000 1.0000 1.0000 1.2500
1.2000 0.7000 /
0 'USRMDL' 0 'GSPWRC' 8 0 3 30 7 10 <bus> '<mach>' <WTGmode>
1.0000 0.6667 -0.6667 0.5002 0.4900 0.8630 0.9333
0.0000 0.0000 0.1000 0.1000 20.0000 20.0000 0.0160
0.0160 0.0000 1.1000 1.2000 1.1000 1.2000 0.2200
-1.4000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 /
0 'USRMDL' 0 'GSMEAS' 8 0 2 10 8 5 <bus> '<mach>'
0.0320 0.0320 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /0 'USRMDL' 0 'GSVPRT' 0 2 7 30 0 18 <bus> '<mach>' 1 1 0 0 0
0.8500 10.2000 0.8500 10.2000 0.9000 60.0000 1.1000
3600.0000 1.2100 2.0000 1.3600 0.1500 1.3600 0.1500
1.2000 0.0800 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.5500 0.7000 2.6000 0.7000 10.0000
0.7000 10.0000 /
0 'USRMDL' 0 'GSFPRT' 0 2 3 12 0 7 <bus> '<mach>' 0
47.0000 0.2000 47.0000 0.2000 47.0000 0.2000 53.0000
0.2000 53.0000 0.2000 53.0000 0.2000 /
/*********************************************************************************
Template 2: The PSS/E dyr file template – V112 GS 3.3MW 50Hz
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 14/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 14 of 53
The dynamic data file (DYR file) Template 2 supplied requires user modification, to insertthe details specific to each WTG. If there is more than one WTG in the PSS/E simulation,the user should duplicate the DYR file contents for each WTG added, and to modify each
of the user inputs denoted by the “<>” to reflect the particulars of each WTG. User inputparameters are listed in Table 2. The details that must be entered by the user for eachWTG are:
The PSS/E bus number (<bus>) and machine ID (<mach>) corresponding to thesingle or aggregate WTG generator.
The WTG reactive power control mode (<WTGmode>): 0 for direct reactive power(Q) control, 1 for power factor (PF) control.
Table 2 User input parameters to the dynamic data file (dyr file)
Parameter Description
<bus> The generator bus number
<mach> The machine ID
<WTGmode> WTG control mode: 0 for Q control, 1 for PF control
In case several WTGs are to be aggregated into one scaled WTG the set of data shouldnot be duplicated, this type is handled through the WTG load flow inputs as explained inChapter 6, where the Pgen, Pmax, Qgen, Qmax, Qmin, & Mbase, will be scaled to repre-sent the required amount of aggregated WTGs as per the instructions provided.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 15/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 15 of 53
4 Simulation Procedures in PSS/E
The model is developed for a maximum simulation time step of half a cycle. The model isdeveloped for PSS/E versions from 29 upwards.
The wind turbine(s) impacts on the system (grid) will be dependent on the short circuit ratio(SCR) and X/R at the bus to which the wind turbine(s) is (are) connected. In this sense it isvery important to assess the model performance taking into consideration the grid strengthseen from the connection point.
Section 4.1 gives the recommended settings for the dynamic simulation. In Section 4.2,the simulation procedure is given (dependent on the version of PSS/E). The list should befollowed exactly in order to get a successful simulation.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 16/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 16 of 53
4.1 Setting for Dynamic SimulationThe recommended settings for the dynamic simulation are as shown in Figure 2.
1 2
43
Figure 2 The PSS/E Dynamic simulation settings (activity ALTR)
Table 3 PSS/E Dynamic simulation settings (activity ALTR)
# Variable Description
1
Network Solution
Iters 25
Acceleration 1.0
Tolerance 0.0001
2Island Frequency
Acceleration 1.0
Tolerance 0.0005
3
Simulation Parameters
Delta Maximum ½ cycle (10 ms for 50 Hz and 8.33 ms for 60Hz)
Frequency filter 0.04
4
Delta Threshold
intermediate 0.06
Island freq 0.14
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 17/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 17 of 53
4.2 Simulation Steps
Simulation steps: PSS/E version 29 to 31
1. Create a working directory – where files related to this simulation set-up shallbe placed – including all relevant files listed.
2. Start up a command prompt in the working directory, ensuring the PATH isset correctly to be able to run PSS/E programs.
3. Start-up PSS/E dynamics (PSSDS4) in the working directory.4. Enter PSS/E load flow (LOFL).5. In case the user’s preferred method of representing the load flow case is a
raw file then read the load flow raw file (READ) to which the Vestas wind tur-bines have been added. If the user prefers to use an already created savedcase then open (CASE) the load flow case to which the Vestas wind turbineswill be added.
6. In case the user has chosen to use a Saved file (*.sav) then the following maybe necessary:
i. Modify this load flow case by adding the desired number of new buses,feeders and transformers necessary to model the WPP collector sys-tem up to the point of common coupling with the existing power sys-tem.
ii. Add the WPP aggregated generator(s), specifying P and Q output foreach.
iii. Add the wind turbine transformers as per the implemented structure:1. Aggregated transformer for aggregated WTGs (if applicable).
2. Separate transformer for separate WTGs (if applicable). 7. Solve the load flow case and save the solved case file.8. Convert the load flow case for dynamic simulations by using CONG and
CONL, followed by ORDR, FACT and TYSL.9. Make a copy of the relevant DYRE parameter template, and fill in the details of
each WPP. Add the DYRE records to any records for other system plant tocreate a system wide ‘.dyr’ file.
10. Enter PSS/E dynamics (RTRN).11. Read (DYRE) the new ‘.dyr’ file, and specify CONEC.FLX and CONET.FLX
files. Specify the name of the compile-file.12. Save the snapshot.
13. Exit the PSS/E program (STOP).14. Ensure the command prompt is pointing to the correct working directory.15. Compile the CONEC.FLX and CONET.FLX subroutines – by typing the name
of the compile-file.16. Link the object codes using a command line of the following form:
CLOAD4 VestasGS_8_0_n_PSSE29.lib <other user models>17. You are now ready to run simulations: enter PSS/E dynamics (PSSDS4), open
the snapshot and load flow case.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 18/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 18 of 53
Simulation steps: PSS/E version 32 and above
1. Create a working directory – where files related to this simulation set-up shall
be placed – including all relevant files listed.2. Ensure the system PATH is set correctly to be able to run PSS/E programs
(using the PSS/E Environment Manager if necessary).3. Start-up PSS/E in the working directory.4. In case the user’s preferred method of representing the load flow case is a
raw file then read the load flow raw file (READ) to which the Vestas wind tur-bines have been added. If the user prefers to use an already created savedcase then open (CASE) the load flow case to which the Vestas wind turbineswill be added.
5. In case the user has chosen to use a Saved file (.sav) then the following maybe necessary:
i. Modify this load flow case by adding the desired number of new buses,feeders and transformers necessary to model the WPP collector sys-tem up to the point of common coupling with the existing power sys-tem.
ii. Add the WPP aggregated generator(s), specifying P and Q output foreach. Ensure the g enerator(s) spec ify ‘not a wind machine’.
iii. Add the wind turbine transformers:1. Aggregated transformer for aggregated WTGs (if applicable).2. Separate transformer for separate WTGs (if applicable).
6. Solve the load flow case and save the solved case file.7. Convert the load flow case for dynamic simulations by using CONG and
CONL, followed by ORDR, FACT and TYSL.8. Make a copy of the relevant DYRE parameter template, and fill in the details of
each WPP. Add the DYRE records to any records for other system plant tocreate a system wide ‘.dyr’ file.
9. Read (DYRE) the new ‘.dyr’ file, and specify CONEC.FLX and CONET.FLXfiles, and a name for the compile-file as appropriate.
10. Save the snapshot.11. Use the ‘Create User DLL’ function in the Dynamics menu to compile the
CONEC and CONET subroutines and link the model code into PSS/E. Specifythe library ‘VestasGS_8_0_n _PSSE32.lib’ when r equired.
12. You are now ready to run simulations: enter PSS/E dynamics (PSSDS4), openthe snapshot and load flow case.
Note : It is not necessary to specify the WPP real or reactive power output in the *.dyr fileas these will be taken from the load flow case at initialization (i.e. when using the activitySTRT).
Once the snapshot is taken and the model compiled and linked, the same dynamics snap-shot can be used with multiple load flow cases, provided the network topology and con-nected models did not change from one case to another. It is therefore possible to assem-ble a number of load flow cases, each with a different level of initial WTG power outputand/or voltage, without reassembling the snapshot or recompiling before using each differ-
ent case in a simulation.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 19/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 19 of 53
5 Vestas System Example
5.1 System ModelVestas has built a simple example to show how to setup and simulate with the WTG mod-els. The test grid is modelled with four buses and two branches, with the Vestas WT modelat one end, and a slack bus generator at the other. The middle bus is where the fault isapplied. The system is shown in Figure 3.
Figure 3 Network Diagram of Vestas test system
The files/folders listed in Table 4 are delivered for setting up the test cases for both, thereactive power control and the power factor control examples (for WTG level control).
Note that the example files provided represent a simple test case for Vestas GridStream-er TM wind turbines and do not reflect any particular site-specific configuration.
Table 4 Files included in the delivered package
Simulation Files DescriptionV<xx>.GS.<yy>MW.<zz>Hz.Mk<k>.Df.v8.0.n_Base_29.raw RAW file for Base case in Ver29
V<xx>.GS.<yy>MW.<zz>Hz. Mk<k>.Df.v8.0.n_Base_32.sav SAV file for Base case in Ver32
Simulate_QControl.psa PSA file for QContorl Simulation
Simulate_PFControl.psa PSA file for PFContorl Simulation
V<xx>.GS.<yy>MW.<zz>Hz. Mk<k>.Df.v8.0.n.dyr DYR file for Dynamic model
TG Z 20 to 30 Z 30 to 40
Wind Generator Bus Bus # 10 Bus Volt = 0.65 kV Bus Type ”2"
Wind turbine Transformer Bus Bus # 20 Bus Volt = 20.0 kV
Bus Type ”1"
Network Fault Bus Bus # 30 Bus Volt = 20.0 kV
Bus Type ”1"
Network Slack Bus Bus # 40 Bus Volt = 20.0 kV
Bus Type ”3"
SG
2-Windings Transformer
BASE MVA = Mbase BASE MVA = 100 MVA Sbase
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 20/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 20 of 53
5.2 Simulation StepsTo perform a simulation – following steps has to be carried out:
In PSS/E versions 29 to 31
1. Create a Working directory – where files related to this simulation set-up shallbe placed – including all relevant files listed.
2. Start up a command prompt in the working directory, ensuring the PATH isset correctly to be able to run PSS/E programs.
3. Start up PSS/E dynamics (PSSDS4) in the working directory.4. Read the load flow raw file “*.raw”, convert the load flow case for dynamic
simulations by using CONG and CONL, followed by ORDR, FACT and TYSL.5. Save the converted case file.6. Read (DYRE) the ‘*.dyr’ file, and specify CONEC.FLX and CONET.FLX files.
Specify the name of the compile-file.7. Save the snapshot.8. Exit the PSS/E program (STOP).9. Ensure the command prompt is pointing to the correct working directory.10. Compile the CONEC.FLX and CONET.FLX subroutines – by typing the name
of the compile-file.11. Link the object codes using a command line of the form:
CLOAD4 VestasGS_8_0_n_PSSE29.lib <other user models>12. Start up PSS/E dynamics (PSSDS4) and run “Simulate_QControl.psa” or
“Simulate_PFControl.psa”
13. Exit PSS/E14. Start plot program (PSSPLT)
In PSS/E version 32 or above
1. Create a Working directory – where files related to this simulation set-up shallbe placed – including all relevant files listed.
2. Ensure the system PATH is set correctly to be able to run PSS/E programs, byrunning the PSS/E Environment Manager if necessary.
3. Start up PSS/E in the working directory.4. Read the case file “*.sav”, convert the load flow case for dynamic simulations
by using CONG and CONL, followed by ORDR, FACT and TYSL.5. Save the converted case file.6. Read (DYRE) the ‘*.dyr’ file, and specify CONEC.FLX and CONET.FLX files.
Specify the name of the compile-file.7. Save the snapshot.8. Use the ‘Create User DLL’ function in the Dynamics menu to compile the
CONEC and CONET subroutines and link the model code. Specify the codelibrary “VestasGS_8_0_n _PSSE32.lib” when prompted.
9. Run “Simulate.idv” 10. Exit PSS/E11. Start plot program (PSSPLT)
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 21/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 21 of 53
6 Description of related PSS/E Activities
6.1 WTG Load Flow related Inputs
52 3 1098
4 6 71
Figure 4 The PSS/E load flow – plant & machine editor
Figure 4 shows the PSS/E plant and machine editor. The WTG is to be set on a bus hav-ing a voltage equal to the generator rated voltage (at the low voltage side of the transform-er).
The machine parameters in PSS/E load flow should be entered as indicated in the tablebelow. Note that for the purpose of the PSS/E WTG model, the MBASE value for a singleturbine is taken as the maximum MW output of the turbine.
Table 5 Variables as in plant & machine editor of Figure 4
# Name Units Description RecommendedValue for a Single
Turbine
RecommendedValue for an Ag-gregated Turbine
1 Pgen MW Is the generated active power User supplied value(0≤ P≤ Prate)
N*P
2 Pmax MW Is the maximum allowed activepower
Prate N*Prate
3 Pmin MW Is the minimum allowed activepower
Always ZERO 0
4 Qgen MVAR Is the generated / absorbed reac-tive power
User supplied value*(Qind≤ Q≤ Qcap)
N*Q
5 Qmax MVAR Is the absolute maximum allowedreactive power
Equals Qgen* N*Q
6 Qmin MVAR Is the absolute minimum allowedreactive power
Equals Qgen* N*Q
7 Mbase MVA Is the base apparent power for n Prate N*Prate
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 22/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 22 of 53
wind turbines
8 ZSource pu Is machine positive sequence im-pedance
Refer to Appendices Refer to Appendices
9 Rtran pu Is the Resistance of the internal
transformer
Always ZERO 0
10 Xtran pu Is the Reactance of the internaltransformer
Always ZERO 0
Where Prate is the rated MW value; Qind and Qcap are the turbine reactive power inductive and capacitive lim-its.
*Vestas WTGs are not configured for terminal voltage control. Therefore the user should select the appropri-ate reactive power condition and configure the load flow case accordingly.
In PSS/E the value of ‘Zsource’ is calculated from the maximum short circuit current con-tribution (Ik”=1.05 p.u.). Recommended values of source resistance and reactance aregiven in Appendices.
The bus to which the wind turbine(s) is (are) connected should have the same level ofvoltage as the generator terminals, in fact this bus is the low voltage side of the 2-windingstur bine’s transformer. The turbine’s transformer is not included in the model and is left tothe user to implement in the simulation as a PSS/E standard 2 winding transformer formore details see section 6.2.
For aggregated WTGs, parameters 1, 2, 4, 5, 6 & 7 needs to be scaled to represent thedesired number N of aggregated units.
6.2 WTG 2-Winding Transformer Load Flow InputsFigure 5 shows the PSS/E load flow 2-winding transformer editor, all data are to remain asdefault except the 9 encircled fields that are to be changed as specified in Table 6.
1 2 3 4 5
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 23/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 23 of 53
Figure 5 The PSS/E load flow – 2-winding transformer editor
Table 6 Input values for the 2-winding transformer editor of Figure 5
# Name Units Description
1 Name The transformer name (Optional)2 Impedance data I/O
codeMVA Base to use for the p.u. val-ues
3 Line R pu Winding resistance
4 Line X pu Leakage reactance
5 Winding MVA base MVA Winding MVA base
6 Rmax Maximum Tap
7 Rmin Minimum Tap
8 Tap Positions No of Taps
9 Connection Code Vector Grouping
** Vector grouping assumes that the LV side is declared as the primary winding.
It is important to be aware that aggregating WTGs also means aggregating WTG unittransformers, which means that voltage ratings remain the same but the MVA rating will bescaled.
The different transformer parameters are as per the data sheet in Appendices.
6.3 Output Channels for PlottingOne of the possible ways to call a channel in PSS/E is through the CHAN activity in theuser interface (Dynamics). Table 7 shows the possible useful channels that can be calledto represent the relevant inputs/outputs of the Vestas wind turbine model in PSS/E.
6 7 8
9
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 24/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 24 of 53
1 32 45
6
Figure 6 CHAN activity from the PSS/E dynamics
Table 7 Plotting channels from the CHAN activity
# Variable Description1 Machine PELEC Machine(s) Active Power, without the WTG’s transformer, p.u on SBASE
2 Machine QELEC Machine(s) Reactive Power, without the WTG’s transformer, p.u on SBASE
3 Machine Eterm Machine(s) Terminal voltage magnitude, p.u Bvbase
4 Bus Frequency Bus Frequency, p.u deviation from the systems nominal frequency
5 Bus Voltage Bus Voltage magnitude, p.u Bvbase
6 Bus Voltage andAng
Bus Voltage magnitude & Angle, p.u Bvbase & degrees respectively
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 25/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 25 of 53
7 User related Sub-models of Vestas Wind Turbines
This section describes different sub models in the dynamic data file.
7.1 Reactive Power ControlThe turbine can operate within certain limits for active and reactive power. The limits areprimarily determined by the converter and the generator. There are two possible controlmodes:
Q-Control.
Power Factor Control.
The PSS/E user written model will independent of which of the modes that is selected, pri-oritize the active power higher than the reactive power. This means that the highest possi-
ble active power – which is the user-defined (requested) active power – will be supplied tothe grid even though it might compromise the control mode performance.
Active Power PriorityThe model implemented always gives highest priority to the active power. That means thatif both P and Q are outside the valid operating area, Q is limited in order to bring the tur-bine inside the safe operating area. This is illustrated in Figure 7 (A typical PQ chart forVestas turbines) where the references (P* and Q*) are both outside the chart. In this caseQ is limited in order to bring the turbines operating point inside the operating area again.
Q
P
(P*,Q*)
Q*Lim
P*
P over Q
Q over P
Figure 7 Example of limiting function where P is given priority over Q
The value of P* and Q* are set in the load flow interface.
Q-Control A certain reactive power reference can be set. The reference must be within its lower andupper limits – vertical limits for each P according to Figure 11.
PF Control
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 26/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 26 of 53
When activated, the required Q will be calculated based on the P and the PF set point.Depending on the working point, whether it is a full or partial load operating point and alsowhether it is lead or lag, the PF set point is subject to possible minimum or maximum as
shown in Figure 11.
Changing Q and PF set point (Qset)Reactive power set point (Qset), defined in ‘GSVARS’ sub-routine. This set point is as-signed to VAR L+1 can be changed to desired value using ‘ALTR’ activity.
Table 8 Description of VAR set points P and Q or PF
VARs Description
L Available real power, Pset
L+1 Q or PF set point, Qset
7.2 LVRT Control SettingsDuring low-voltage-ride-through (LVRT), Vestas turbines switch from power control to cur-rent control mode. The following settings can be changed by the user in order to carry ondifferent system studies.
Active current Priority As default, Vestas turbines are designed to maintain and control reactive current duringLVRT. However the user could also select the active current priority, If supplying activepower is required during LVRT.
The Active current priority setting can be enabled by changing CON J+7 of ’GSLVRT’ to1.0, and be disabled by changing CON J+7 to 0.0.
Q-offset SettingIn case the turbine reactive output is not zero at pre-fault condition, the Q-offset can beused to remove the step change when Vestas turbines switches between power controland current control.
The Q-offset setting can be enabled by changing CON J+31 of ’GSLVRT’ to 1.0, and be
disabled by changing CON J+31 to 0.0.
Asymmetrical fault
If asymmetrical fault study is required, asymmetrical fault settings should be enabled andthe user should provide negative sequence magnitude (U-) input in VAR L+12 of’GSLVRT’.
The asymmetrical fault setting can be enabled by changing CON J+32 of ’GSLVRT’ to 1.0,and be disabled by changing CON J+32 to 0.0.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 27/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 27 of 53
7.3 Protection & LVRT SettingsThis section describes the WTG protection and LVRT scheme and settings.
At any kind of trip, an error message will be generated in order to identify the event trippingthe turbine.
Table 9 Protection error messages
Event Error message
Under voltage 1 “Under voltage 1 Trip” + WTG bus number + “at time”
Under voltage 2 “Under voltage 2 Trip” + WTG bus number + “at time”
Under voltage 3 “Under voltage 3 Trip” + WTG bus number + “at time”
LVRT under voltage “LVRT under voltage Trip” + WTG bus number + “at time”
Over voltage 1 “Over voltage 1 Trip” + WTG bus number + “at time”
Over voltage 2 “Over voltage 2 Trip” + WTG bus number + “at time”
Over voltage 3 “Over voltage 3 Trip” + WTG bus number + “at time”
Over voltage 4 “Over voltage 4 Trip” + WTG bus number + “at time”
Over voltage 5 “Over voltage 5 Trip” + WTG bus number + “at time”
Under frequency 1 “Under frequency 1 Trip” + WTG bus number + “at time”
Under frequency 2 “Under frequency 2 Trip” + WTG bus number + “at time”
Under frequency 3 “Under frequency 3 Trip” + WTG bus number + “at time”
Over frequency 1 “Over frequency 1 Trip” + WTG bus number + “at time”
Over frequency 2 “Over frequency 2 Trip” + WTG bus number + “at time”
Over frequency 3 “Over frequency 3 Trip” + WTG bus number + “at time”
7.3.1 Voltage Protection
The voltage protection is implemented having three protection levels for high voltages andthree protection levels for low voltages.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 28/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 28 of 53
Figure 8 Voltage protection limits defined in the protection model VWVPR6
The WTG will be disconnected if the voltage limits are exceeded and the protection timesout. Table 10 shows the protection settings for a Vestas GridStreamer TM wind turbine with-out the LVRT option.
Table 10 Voltage protection settings (LVRT not enabled)
Voltage limit Setting Timeout Setting
UV1 0.90 tUV1 60 s
UV2 0.85 tUV2 11 s
UV3 0.85 tUV3 11 s
OV1 1.10 tOV1 3600 s
OV2 1.21 tOV2 2 s
OV3 1.36 tOV3 150 ms
OV4 1.36 tOV4 150 ms
OV5 1.36 tOV5 150 ms
Note : the voltage protection settings may vary with different turbine models. The user issuggested to check the General Specification of the specified turbine for the voltage pro-
tection settings.
7.3.2 LVRT Logic
As default, the Vestas GridStreamer TM wind turbines is a LVRT enabled turbine, and theVestas PSS/E model will represent this. The turbine is designed to stay connected on thegrid in case of a number of severe faults.
The LVRT option is affected by two user defined parameters (LVRT_flag and AGO_enable) as explained in Table 11.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 29/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 29 of 53
Table 11 Parameters of LVRT function
ICON Parameter Module Description
I+3 LVRT_flag GSVPRT LVRT protection flag
I+2 AGO_enable GSLVRT AGO enableLVRT mode can be enabled (set both “LVRT_flag” and “AGO_enable” to 1) or disabled(set both “LVRT_flag” and “AGO_enable” to 0) by changing these two parameters in thedyr file template.
The LVRT under voltage protection curve is represented by the parameters shown inTable 12.
Table 12 LVRT settings (LVRT enabled)
Voltage limit Setting Timeout Setting
ULVRT1 0.00 tLVRT1 0.55 sULVRT2 0.70 tLVRT2 2.6 s
ULVRT3 0.70 tLVRT3 10 s
ULVRT4 0.70 tLVRT4 10 s
Note : the LVRT protection settings may vary with different turbine models. The user issuggested to check the General Specification of the specified turbine for the LVRT protec-tion settings.
The default low voltage ride-through protection settings for a connected turbine is illustrat-ed in Figure 9.
Figure 9 LVRT protection limits for Vestas GridStreamer TM
wind turbine defined in the protection sub-routine VWVPR6
7.3.3 Frequency Protection
The frequency protection is implemented having three protection levels for high frequen-
cies and three protection levels for low frequencies.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 30/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 30 of 53
Each protection level can be accepted within a certain time-window. If this window is ex-ceeded, the turbine disconnects. Setting frequency and time limit equal to zero disables
the protection level.
The frequency protection setting may be seen below in Figure 10.
Frequency variation
Time
Hz50 of 1 of 2 of 3
tof1
tof2
tof3
uf 1uf 2uf 3
tuf1
tuf2
tuf3
Figure 10 Frequency protection limits defined in the protection model VWFPR6
Table 13 Frequency protection settings
Frequency limit Setting for 50Hz Setting for 60Hz Timeout Setting
OF1 53 Hz 63.6 Hz tOF1 200 ms
OF2 53 Hz 63.6 Hz tOF2 200 ms OF3 53 Hz 63.6 Hz tOF3 200 ms UF1 47 Hz 56.4 Hz tUF1 200 ms UF2 47 Hz 56.4 Hz tUF2 200 ms UF3 47 Hz 56.4 Hz tUF3 200 ms
Note : the frequency protection settings may vary with different turbine models. The user issuggested to check the General Specification of the specified turbine for the frequency protection settings.
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 31/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 31 of 53
8 PSS/E Format Data Sheets
The PSS/E format data sheets for different modules of Vestas Ver 8.0 model are providedin this Chapter.
Table 14 Summary of Vestas Ver 8.0 model
Module Description
GSCORE Core generator and grid converter functions
GSVARS Common variable storage
GSLVRT LVRT mode logic
GSPWRC Generator power control
GSMEAS Measured variablesGSVPRT Voltage protection
GSFPRT Frequency protection
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 32/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 32 of 53
8.1 GSCORE
VESTAS R&D Nonstandard Model Data SheetModel Version 8.0.1 GSCORE
GSCORE
VESTAS WIND TURBINE GENERATOR (BEHAVIOURAL MODEL)
This model is located at system bus # ________ (IBUS)Machine ID # ________ (IMACH)This model uses 2 ICONs starting with # ________ (I)and 45 CONs starting with # ________ (J)and 23 STATEs starting with # ________ (K)and 104 VARs starting with # ________ (L)
ICON # Value Description
I Not in use
I+1 Flag for internal loop mode,FI 0 = not in internal loop mode
1 = in internal loop
CON # Vaule Description
J Generator kVA rating, S
J+1 Gen voltage rating, V
J+2 Rated rotor current, IR
J+3 Time constant for 10msmoving average filter
J+4 Disp.
J+5 Disp. J+6 Disp. J+7 P proportional gain
J+8 P integral gain
J+9 Q proportional gain
J+10 Q integral gain
J+11 Lower limit for P control loop
J+12 Upper limit for P control loop
J+13 Lower limit for Qref
J+14 Upper limit for QrefJ+15 Limit for P (LVRT) J+16 Limit for P at zero voltage
(LVRT) J+17 Slope for the power derate
curve (LVRT)
J+18 P positive slope J+19 P negative slope J+20 Disp. J+21 Disp. J+22 Disp. J+23 Model interface, MI
J+24 Stator volt. filter time const
(current injection)
J+25 Stator volt. threshold (currentinjection)
J+26 Current injection mode.
J+27 Reserved for Future Version J+28 Reserved for Future Version J+29 Reserved for Future Version J+30 Reserved for Future Version J+31 Reserved for Future Version J+32 Reserved for Future Version J+33 Reserved for Future Version J+34 Reserved for Future Version J+35 Reserved for Future Version J+36 Reserved for Future Version J+37 Reserved for Future Version
J+38 Reserved for Future Version
J+39 Reserved for Future Version
J+40 Reserved for Future Version
J+41 Reserved for Future Version
J+42 Reserved for Future Version
J+43 Reserved for Future Version
J+44 Reserved for Future Version
STATE # Description
K Integ for active powerK+1 Integ for reactive power
K+2 Integ for measured voltage (10msmoving average)
K+3 Transient volt. real part
K+4 Transient volt. imag part
K+5 Disp. K+6 Disp. K+7 Stator volt. filtered real part (current
injection)
K+8 Stator volt. filtered imag part (currentinjection)
K+9 Reserved for Future Version
K+10 Reserved for Future Version
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 33/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 33 of 53
K+11 Reserved for Future Version K+12 Reserved for Future Version K+13 Reserved for Future Version K+14 Reserved for Future Version
K+15 Reserved for Future Version K+16 Reserved for Future Version K+17 Reserved for Future Version K+18 Reserved for Future Version K+19 Reserved for Future Version K+20 Reserved for Future Version K+21 Reserved for Future Version K+22 Reserved for Future Version
VARs # Description
L Disp.
L+1 Active current
L+2 Storage for raw real powerL+3 Storage for raw reactive power
L+4 Saved angle of stator voltage.
L+5 Reactive current
L+6 Voltage in power flow, real part
L+7 Voltage in power flow, imag prt
L+8 P from P_loop after limiter (pu)
L+9 Qref after limiter (pu)
L+10 Q from Q_loop after limiter (pu)
L+11 Active current from P_loop (pu)
L+12 Rective current from Q_loop (pu)
L+13 Memory for delay.
L+14 Memory for delay.
L+15 Memory for delay.
L+16 Memory for delay.
L+17 Memory for delay.
L+18 Memory for delay.
L+19 Memory for delay.
L+20 Memory for delay.
L+21 Memory for delay.
L+22 Memory for delay.
L+23 Memory pos. for delay. .
L+24 Required no. of pos. for delay.
L+25 Delta time for delay.
L+26 Next time step for update delay.
L+27 Delayed angle of voltage.L+28 Limited Pref in normal control L+29 Pref after slope limiter L+30 Saved time for slope limiter L+31 P before LVRTslope limiter L+32 Limited Pref in LVRT L+33 Pref before slope limiter L+34 Max value for active current in LVRT L+35 Reserved for Future Version L+36 Reserved for Future Version L+37 Reserved for Future Version L+38 Save internal loop store(K) for
GSCORE
L+39 Save internal loop store(K+1) for
GSCORE
L+40 Save internal loop store(K+2) forGSCORE
L+41 Save internal loop store(K+3) for
GSCOREL+42 Save internal loop store(K+4) forGSCORE
L+43 Save internal loop store(K+5) forGSCORE
L+44 Save internal loop store(K+6) forGSCORE
L+45 Save internal loop store(K+7) forGSCORE
L+46 Save internal loop store(K+8) forGSCORE
L+47 Save internal loop store(K+9) forGSCORE
L+48 Save internal loop store(K+10) for
GSCOREL+49 Save internal loop store(K+11) forGSCORE
L+50 Save internal loop store(K+12) forGSCORE
L+51 Save internal loop store(K+13) forGSCORE
L+52 Save internal loop store(K+14) forGSCORE
L+53 Save internal loop store(K+15) forGSCORE
L+54 Save internal loop store(K+16) forGSCORE
L+55 Save internal loop store(K+17) for
GSCOREL+56 Save internal loop store(K+18) forGSCORE
L+57 Save internal loop store(K+19) forGSCORE
L+58 Save internal loop store(K+20) forGSCORE
L+59 Save internal loop store(K+21) forGSCORE
L+60 Save internal loop store(K+22) forGSCORE
L+61 Save internal loop store(K) forGSLVRT
L+62 Save internal loop store(K+1) for
GSLVRTL+63 Save internal loop store(K+2) forGSLVRT
L+64 Save internal loop store(K+3) forGSLVRT
L+65 Save internal loop store(K+4) forGSLVRT
L+66 Save internal loop store(K+5) forGSLVRT
L+67 Save internal loop store(K+6) forGSLVRT
L+68 Save internal loop store(K+7) forGSLVRT
L+69 Save internal loop store(K+8) forGSLVRT
L+70 Save internal loop store(K+9) for
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 34/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 34 of 53
GSLVRT
L+71 Save internal loop store(K) forGSPWRC
L+72 Save internal loop store(K+1) for
GSPWRCL+73 Save internal loop store(K+2) forGSPWRC
L+74 Save internal loop store(K+3) forGSPWRC
L+75 Save internal loop store(K+4) forGSPWRC
L+76 Save internal loop store(K+5) forGSPWRC
L+77 Save internal loop store(K+6) forGSPWRC
L+78 Save internal loop store(K) forGSMEAS
L+79 Save internal loop store(K+1) for
GSMEASL+80 Save internal loop store(K+2) forGSMEAS
L+81 Save internal loop store(K+3) forGSMEAS
L+82 Save internal loop store(K+4) forGSMEAS
L+83 Save internal loop store(K+5) for
GSMEAS
L+84 Save internal loop store(K+6) forGSMEAS
L+85 Save internal loop store(K+7) for
GSMEASL+86 Reserved for Future Version L+87 Reserved for Future Version L+88 Reserved for Future Version L+89 Reserved for Future Version L+90 Reserved for Future Version L+91 Reserved for Future Version L+92 Reserved for Future Version L+93 Reserved for Future Version L+94 Reserved for Future Version L+95 Reserved for Future Version L+96 Reserved for Future Version L+97 Reserved for Future Version L+98 Reserved for Future Version L+99 Reserved for Future Version
L+100 Reserved for Future Version L+101 Reserved for Future Version L+102 Reserved for Future Version L+103 Reserved for Future Version
Note: The synchronous generator arrays (SPEED, PMECH, XADIFD and ECOMP) are used for identifyingthe CONEC models placement in the ICON, CON, STATE and VAR arrays.Note: The synchronous generator arrays (EFD) is used for identifying models connected to the same bus.
DYRE input line:
IBUS 'USRMDL' IMACH 'GSCORE' 1 1 2 45 23 104 ICON(I) ICON(I+1) CON(J)…CON(J+44)/
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 35/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 35 of 53
8.2 GSVARS
VESTAS R&D Nonstandard Model Data SheetModel Version 8.0.1 GSVARS
GSVARS
VESTAS WIND TURBINE VARIABLES INTERFACE
This model is located at system bus # ________ (IBUS)Machine ID # ________ (IMACH)This model uses 2 ICONs starting with # ________ (I)and no CONsand no STATEsand 30 VARs starting with # ________ (L)
ICON # Value Description
I No. of wind farm bus, IBUS
I+1 Wind farm machine ID, IMACH
VARs # Description
L Available real power, Pset
L+1 Q or PF setpoint, Qset
L+2 Real power after PQ chart, Ptrim
L+3 React pwr after PQ chart, Qtrim
L+4 Real power after slope lim, Plim
L+5 React pwr after slope lim, Qlim
L+6 Real power request, Pref L+7 Reactive power request, Qref
L+8 Real power output, Pactual
L+9 Reactive power output, Qactual
L+10 Real power measurement, Pmeas
L+11 React pwr measurement, Qmeas
L+12 Disp.
L+13 Disp. L+14 Disp. L+15 AGO (LVRT) status, S AGO
L+16 Active current for LVRT, IP
L+17 Reactive current for LVRT, IQ
L+18 Reserved for Future Versions L+19 Reserved for Future Versions L+20 Reserved for Future Versions L+21 Reserved for Future Versions L+22 Reserved for Future Versions L+23 Reserved for Future Versions
L+24 Reserved for Future Versions L+25 Reserved for Future Versions L+26 Reserved for Future Versions L+27 Reserved for Future Versions
L+28 Reserved for Future Versions
L+29 Reserved for Future Versions
Note: All power quantities are in per unit on the machine base.
DYRE input line:
0 'USRMDL' 0 'GSVARS' 8 0 2 0 0 30 ICON(I) ICON(I+1) /
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 36/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 36 of 53
8.3 GSLVRT
VESTAS R&D Nonstandard Model Data SheetModel Version 8.0.1 GSLVRT
GSLVRT
VESTAS WIND TURBINE GENERATOR LOW VOLTAGE RIDE THROUGH
This model is located at system bus # ________ (IBUS)Machine ID # ________ (IMACH)This model uses 3 ICONs at # ________ (I)and 65 CONs starting with # ________ (J)and 10 STATEs starting with # ________ (K)
and 35 VARs starting with # ________ (L)
ICON # Value Description
I WTG bus number, IBUS
I+1 WTG machine ID, IMACH
I+2 AGO enabler (1=enable)
CONs # Value Description
J AGO threshold, V AGO
J+1 Disp.
J+2 RegainPQ delay
J+3 LVRT IP pos slope, RIP+, Ifequal zero then disabled
J+4 LVRT IP neg slope, RIP-, Ifequal zero then disabled
J+5 LVRT IQ pos slope, RIQ+, Ifequal zero then disabled
J+6 LVRT IQ neg slope, RIQ-, Ifequal zero then disabled
J+7 Active Current Priority1- Active current priority0- Reactive current priority
J+8 Current Overload Factor (Ippriority)
J+9 Offset (Ip priority)
J+10 Gain (Ip priority)J+11 Short term current overload
threshold, IR*
J+12 Disp.
J+13 Rated voltage, V
J+14 Rated current, IR
J+15 Disp. J+16 Disp. J+17 Disp. J+18 Disp. J+19 Disp. J+20 Disp.
J+21 Disp.
J+22 Disp. J+23 Disp. J+24 AGO threshold, V AGO2.,
Leaving AGO [pu]
J+25 Disp.
J+26 Disp.
J+27 Time Constant for FRTVoltage Filter [s] (10ms filter)
J+28 Disp.
J+29 I_offset for LVRT curve
J+30 K Parameter for LVRT curve
J+31 QoffsetEnab for LVRT curve(1 to enable offset)
J+32 Fassym flag for Asymmetricalfault(1 to enable asymmetricalDerating; 0 is default)
J+33 Upper limit of reactive current(CC_Lim)
J+34 Lower limit of reactive current(IC_Lim)
J+35 Reactive Current Point1U
J+36 Reactive Current Point2U
J+37 Reactive Current Point4U
J+38 Reactive Current Point5U
J+39 Active Current Zone3U2
J+40 Active Current Zone3U1
J+41 Active Current Zone2U2
J+42 Active Current Zone2U1
J+43 Active Current Zone3I
J+44 Active Current Zone2I
J+45 Reactive Current Point1I
J+46 Reactive Current Point2I
J+47 Reactive Current Point5I
J+48 Lower limit of voltage
(U_LL_LIM)
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 37/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 37 of 53
J+49 Higher limit of voltage(U_HL_LIM)
J+50 Disp. J+51 Qref Derate1
J+52 Qref Derate2J+53 Qref Derate3
J+54 Qref Derate4
J+55 Asym Reduc deadband
J+56 Asym Reduc kfactor
J+57 Asym Reduc limit
J+58 TotalCF
J+59 Time Constant for one minVoltage Filter [s]
J+60 Upper limit of OneMinAvg
J+61 Lower limit of OneMinAvg
J+62 HVRT Entry Threshold
J+63 HVRT Leaving ThresholdJ+64 LVRT instantaneous Voltage
Threshold
STATE # Description
K State for 10ms FRT Filter
K+1 State for 1 min Average Filter
K+2 Not in use K+3 Not in use K+4 Not in use K+5 Not in use K+6 Not in use K+7 Not in use K+8 Not in use K+9 Not in use
VARs # Description
L Saved time for slope limiters
L+1 Slope limit value for IP
L+2 Slope limit value for IQ
L+3 Disp.
L+4 Input voltage for Ip calculation (Ippriority)
L+5 Active current (Ip priority)
L+6 Upper limit of Iq (Ip priority)L+7 Lower limit of Iq (Ip priority)
L+8 Voltage signal used to compare withthe threshold
L+9 Limited value of One minute movingaverage
L+10 Disp.
L+11 Memory for old value of realVoltStat
L+12 negative sequence magnitude (U-)
L+13 Recorded Time for FRT entry L+14 Reserved for Future Version L+15 Reserved for Future Version L+16 Reserved for Future Version
L+17 Reserved for Future Version L+18 Reserved for Future Version L+19 Reserved for Future Version L+20 Reserved for Future Version L+21 Reserved for Future Version L+22 Reserved for Future Version L+23 Reserved for Future Version L+24 Reserved for Future Version L+25 Reserved for Future Version L+26 Reserved for Future Version L+27 Reserved for Future Version L+28 Reserved for Future Version
L+29 Reserved for Future Version L+30 Reserved for Future Version L+31 Reserved for Future Version L+32 Reserved for Future Version L+33 Reserved for Future Version L+34 Reserved for Future Version
Note: All power quantities are in per unit on the machine base. Slope limits are in p.u. per second.Note: For the parameters that are not used for GridStreamer
TM, please use the default values as given in the
dyr template.DYRE input line:
0 ' USRMDL ' 0 'GSLVRT ' 8 0 3 65 10 35 ICON(I) ICON(I+1) CON(J)…CON(J+64) /
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 38/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 38 of 53
8.4 GSPWRC
VESTAS R&D Nonstandard Model Data SheetModel Version 8.0.1 GSPWRC
GSPWRC
VESTAS WIND TURBINE GENERATOR POWER CONTROL
This model is located at system bus # ________ (IBUS)Machine ID # ________ (IMACH)This model uses 3 ICONs at # ________ (I)and 30 CONs starting with # ________ (J)and 7 STATEs starting with # ________ (K)
and 10 VARs starting with # ________ (L)
ICONs # Value Description
I No. of wind farm bus, IBUS
I+1 Wind farm machine ID, IMACH
I+2 Control mode (0 = Q control,1 = PF control)
CONs # Value Description
J Real power export lim
J+1 Reactive pwr export lim
J+2 Reactive pwr import lim
J+3 Max active power when Q atexport limit
J+4 Max active power when Q atimport limit
J+5 Min power factor for exportat max real pwr
J+6 Min power factor for importat max real pwr
J+7 Min power factor for exportat any pwr level
J+8 Min power factor for importat any pwr level
J+9 P pos slope limit, RP+
J+10 P neg slope limit, RP- J+11 Q pos slope limit, RQ+
J+12 Q neg slope limit, RQ-
J+13 P ref time constant, TP
J+14 Q ref time constant, TQ
J+15 QoverP Flag(0 for P priority and 1 for QPriority; 0 is default)
J+16 Qcap Degrade startingVoltage (pu)
J+17 Qcap Degrade completeVoltage (pu)
J+18 Qind Degrade starting
Voltage (pu)
J+19 Qind Degrade completeVoltage (pu)
J+20 Degrade Qcap Level (pu)
J+21 Degrade Qind Level (pu)
J+22 Reserved for Future Version
J+23 Reserved for Future Version
J+24 Reserved for Future Version
J+25 Reserved for Future Version
J+26 Reserved for Future Version
J+27 Reserved for Future Version
J+28 Reserved for Future Version
J+29 Reserved for Future Version
STATEs # Description
K Active power reference filter
K+1 Reactive power reference filter
K+2 Reserved for Future Version
K+3 Reserved for Future Version
K+4 Reserved for Future Version
K+5 Reserved for Future Version
K+6 Reserved for Future Version
VARs # Description
L Saved time for slope limiters
L+1 Slope limit value for Pref
L+2 Slope limit value for Qref
L+3 Recorded AGO states
L+4 Reserved for Future Version
L+5 Reserved for Future Version
L+6 Reserved for Future Version
L+7 Reserved for Future Version
L+8 Reserved for Future Version
L+9 Reserved for Future Version
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 39/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 39 of 53
Note: All power quantities are in per unit on the machine base. Slope limits are in p.u. per second.DYRE input line:0 'USRMDL' 0 'GSPWRC' 8 0 3 30 7 10 ICON(I) ICON(I+1) ICON(I+2) CON(J)…CON(J+29)/
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 40/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 40 of 53
8.5 GSMEAS
VESTAS R&D Nonstandard Model Data SheetModel Version 8.0.1 GSMEAS
GSMEAS
VESTAS WIND TURBINE MEASUREMENTS MODEL
This model is located at system bus # ________ (IBUS)Machine ID # ________ (IMACH)This model uses 2 ICONsand 10 CONs starting with # ________ (J)and 8 STATEs starting with # ________ (K)
and 5 VARs # ________ (L)
ICON # Value DescriptionI No. of wind farm bus, IBUS
I+1 Wind farm machine ID, IMACH
CON # Value DescriptionJ Real pwr time const, TP
J+1 React pwr time const, TQ J+2 Reserved for Future Version J+3 Reserved for Future Version J+4 Reserved for Future Version J+5 Reserved for Future Version
J+6 Reserved for Future VersionJ+7 Reserved for Future VersionJ+8 Reserved for Future Version
J+9 Reserved for Future Version
STATE # DescriptionK Active power filter
K+1 Reactive power filter
K+2 Reserved for Future Version K+3 Reserved for Future Version K+4 Reserved for Future Version K+5 Reserved for Future Version K+6 Reserved for Future Version K+7 Reserved for Future Version
VARs # Description
L Saved AGO stateL+1 Reserved for Future Version L+2 Reserved for Future Version L+3 Reserved for Future Version L+4 Reserved for Future Version
DYRE input line:
0 'USRMDL' 0 'GSMEAS' 8 0 2 10 8 5 ICON(I) ICON(I+1) CON(J)… CON(J+9)/
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 41/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 41 of 53
8.6 GSVPRT
VESTAS R&D Nonstandard Model Data SheetModel Version 8.0.1 GSVPRT
GSVPRT
VOLTAGE PROTECTION FOR VESTAS WIND TURBINE GENERATORS
This model is located at system bus # ________ (IBUS)Machine ID # ________ (IMACH)This model uses 7 ICONs starting with # ________ (I)and 30 CONs starting with # ________ (J)and no STATEs
and 18 VARs starting with # ________ (L)
ICON # Value Description
I No. of wind farm bus, IBUS
I+1 Wind farm machine ID, IMACH
I+2 Protection enable flag,
SPROT
I+3 LVRT protection flag, SLVRT
I+4 Lockout state (memory)
I+5 Relay state (memory)
I+6 Relay state (memory)
CONs # Value Description
J Extreme UV limit
J+1 Extreme UV timeout
J+2 Short-term UV limit
J+3 Short-term UV timeout
J+4 Continuous UV limit
J+5 Continuous UV timeout
J+6 Continuous OV limit
J+7 Continuous OV timeout
J+8 Short-term OV limit
J+9 Short-term OV timeout
J+10 Extreme OV1 limitJ+11 Extreme OV1 timeout
J+12 Extreme OV2 limit
J+13 Extreme OV2 timeout
J+14 Extreme OV3 limit
J+15 Extreme OV3 timeout
J+16 Reserved for Future Version J+17 Reserved for Future Version J+18 Reserved for Future Version J+19 Reserved for Future Version J+20 Reserved for Future Version
J+21 Reserved for Future Version
J+22 LVRT extreme UV limit
J+23 LVRT extreme UV limittimeout
J+24 LVRT short-term UV
J+25 LVRT Short-term UV timeout
J+26 LVRT mid-term UV
J+27 LVRT mid-term UV timeout
J+28 LVRT continuous UV limit
J+29 LVRT continuous UV
timeout
VARs # Description
L Saved time for extreme UV
L+1 Saved time for short-term UV
L+2 Saved time for mid-term UV
L+3 Not used, but holds last UV recoverytime
L+4 Saved time for mid-term OV
L+5 Saved time for short-term OV
L+6 Saved time for extreme OV1
L+7 Saved time for extreme OV2
L+8Saved time for extreme OV3
L+9 Reserved for Future Version L+10 Reserved for Future Version L+11 Reserved for Future Version
L+12 Reserved for Future Version
L+13 Reserved for Future Version
L+14 Saved time for LV extreme UV
L+15 Saved time for LV mid-t UV
L+16 Saved time for LV short-t UV
L+17 Not used, but holds last LVRT recoverytime
Note: All voltage quantities are in pu, time quantities in seconds. ‘UV’ = undervoltage, ‘OV’ = overvoltage. Iffewer than three distinct undervoltage and overvoltage levels are required, set two consecutive limit values
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 42/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 42 of 53
equal, and ensure both have the same timeout figure. Also, the following relationships must hold fordeclaring the voltage limits if they are utilised:
ExtremeUV limit ≤ Short-term UV limit ≤ Continuous UV limit
Continous OV limit ≤ Short-term OV limit ≤ Extreme OV1 limit ≤Extreme OV2 limit ≤ Extreme OV3 limit
LVRT extreme UV limit (Lowest LVRT voltage limit) ≤LVRT short-term UV limit ≤ LVRT mid-term UVlimit ≤ LVRT continuous UV limit
DYRE input line:
0 'USRMDL' 0 'GSVPRT' 0 2 7 30 0 18 ICON(I)…ICON(I+6) CON(J)…CON(J+29) /
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 43/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 43 of 53
8.7 GSFPRT
VESTAS R&D Nonstandard Model Data SheetModel Version 8.0.1 GSFPRT
GSFPRT
FREQUENCY PROTECTION FOR VESTAS WIND TURBINE GENERATORS
This model is located at system bus # ________ (IBUS)Machine ID # ________ (IMACH)This model uses 3 ICONs starting with # ________ (I)and 12 CONs starting with # ________ (J)and no STATEs
and 7 VAR at # ________ (L)
ICON # Value Description
I No. of wind farm bus, IBUS
I+1 Wind farm machine ID, IMACH
I+2 Relay state (memory)
CONs # Value Description
J Extreme Under-Freq limit
J+1 Extreme Under-Freqtimeout
J+2 Short-term Under-Freq limit
J+3 Short-term Under-Freqtimeout
J+4 Continuous Under-freq limit
J+5 Continuous Under-freqtimeout
J+6 Continuous Over-freq limit
J+7 Continuous Over-freq
timeout
J+8 Short-term Over-Freq limit
J+9 Short-term Over-Freqtimeout
J+10 Extreme Over-Freq limit
J+11 Extreme Over-Freq timeout
VARs # Description
L Saved time for Extreme Under-Freq
L+1 Saved time for Short-term Under-Freq
L+2 Saved time for Continuous Under-Freq
L+3 Not_used, but can hold last Under-Freqrecovery time
L+4 Saved time for Continuous Over-Freq
L+5 Saved time for Short-term Over-Freq
L+6 Saved time for Extreme Over-Freq
Note: All frequency quantities are in pu, time quantities in seconds. If fewer than three distinct under frequencyand over frequency levels are required, set two consecutive limit values equal, and ensure both have the sametimeout figure. Also, the following relationships must hold for declaring the frequency limits if they are utilised:
Extreme Under-Freq limit ≤ Short-term Under-Freq limit ≤ Continuous Under-Freq limit
Continous Over-Freq limit ≤ Short-term Over-Freq limit ≤ Extreme Over-Freq limit
DYRE input line:
0 'USRMDL' 0 'GSFPRT' 0 2 3 12 0 7 ICON(I) ICON(I+1) ICON(I+2) CON(J)…CON(J+11)/
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 44/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 44 of 53
Appendix A. Data for V112 GS 3.075/3.0MW 50/60Hz
A.1 PQ Capability Chart
Figure 11 Vestas V112 GS 3.075MW wind turbine PQ Capability Chart with active power (P) on X-axisand reactive power (Q) on Y-axis. The above plot refers to LV (0.65kV) side of the WTG transformer and
with the LV side voltage between 0.9 p.u. and 1.1 p.u.
Table 15 Parameters of the PQ capability for V112 GS 3.075MW
Parameter Units ValuesMbase MW 3.075
[ X1, X2, X3, X4 ] p.u. [ 0.0 0.5002 1.0 0.5035]
[ Y1, Y2, Y3, Y4 ] p.u. [ 0.6504 0.5691 -0.3761 -0.6504]
PF_Cap_Max (Full Load) - 0.8691
PF_Ind_Max (Full Load) - 0.9360
PF_Cap_Min (Partial Load) - 0.0
PF_Ind_Min (Partial Load) - 0.0
P(X1,Y1) P(X2,Y1)
P(X3,Y2)
P(X3,Y3)
P(X4,-Y1)P(X1,-Y1)
Y4 = -Y1
(0 , 0)
Y1
X3 = Mbase
0.90.80.70.60.3 0.50.40.20.1
P a r t i
a l L
o a d
P F
_ C a p
_ M i n
Full Load
PF_ Cap_ Ma x
F u l l L o a d P F _I n d _M a x P a r t i a l L o a d
P F _
I n d _
M i n
P
Q
-Q
Y4
P(X1,Y4) P(X4,Y4)
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 45/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 45 of 53
A.2 Generator Data
Table 16 WTG’s generator data for V112 GS 3.075MW
Rated Power Rated Voltage Machine Rsource* (pu) Machine Xsource* (pu)
3.075 MW 0.65 kV 0.0044 0.8267
*Per-unit parameters are on machine base.
A.3 Typical Transformer Data
Table 17 Transformer data for V112 GS 3.075MW
No. Parameter Values
1 Rated Power, MW 3.0752 Winding base, MVA 3.45
3 Low Voltage rating, kV 0.65
4 High Voltage rating, kV 20.0
5 R*(pu) 0.007
6 X* (pu) 0.080
7 Vector Group Dyn5
8 Tap Range ±2 x 2.5%
*Per-unit parameters are on winding MVA base.
A.4 PSS/E DYR File Template
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 46/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 46 of 53
/********************************************************************************
/
/ MODULE: Vestas Generic Model Dynamic Data Template for PSS/E
/ Model revision: 8.0.1
/ WTG type: V112 GridStreamer 3.075MW 50Hz Mk0E
//********************************************************************************
/ The lines below must be repeated for each wind generator or composite
/ wind farm generator that occurs in the network.
/ Terms in <angle brackets> must be replaced as follows:
/ <bus> with the generator bus number
/ <mach> with the machine ID
/ <WTGmode> with the control mode at WTG level: 0 for Q control, 1 for PF control
/********************************************************************************
<bus> 'USRMDL' '<mach>' 'GSCORE' 1 1 2 45 23 104 1 0
3075.0000 650.0000 3862.6569 0.0100 0.0000 0.0000 0.0000
0.3500 7.8500 0.000082 940.0000 -3500.0000 3500.0000 -3000.0000
3000.0000 1.0500 0.9000 0.7500 1.0000 1.0000 0.0000
0.0000 0.0000 0.0000 0.0300 0.3000 0.0000 0.00000.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVARS' 8 0 2 0 0 30 <bus> '<mach>' /
0 'USRMDL' 0 'GSLVRT' 8 0 3 65 10 35 <bus> '<mach>' 1
0.8500 0.0000 0.6000 10.0000 200.0000 100.0000 200.0000
0.0000 1.0800 0.0050 1.0050 1.4400 0.0000 650.0000
3862.6569 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.9000 0.0000 0.0000 0.0100
0.0000 0.0000 2.0000 1.0000 0.0000 1.0500 -1.0000
1.2000 0.8500 0.1500 0.0500 0.1000 0.4900 0.5000
0.8000 0.3900 0.4000 0.0000 0.0000 0.0500 0.9000
1.1000 0.0000 0.8000 0.9000 1.1000 1.2000 0.10002.5000 0.6000 750.0000 60.0000 1.0000 1.0000 1.2500
1.2000 0.7000 /
0 'USRMDL' 0 'GSPWRC' 8 0 3 30 7 10 <bus> '<mach>' <WTGmode>
1.0000 0.6504 -0.6504 0.5002 0.5035 0.8691 0.9360
0.0000 0.0000 0.1000 0.1000 20.0000 20.0000 0.0160
0.0160 0.0000 1.1000 1.2000 1.1000 1.2000 0.2200
-1.4000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 /
0 'USRMDL' 0 'GSMEAS' 8 0 2 10 8 5 <bus> '<mach>'
0.0320 0.0320 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVPRT' 0 2 7 30 0 18 <bus> '<mach>' 1 1 0 0 0
0.8500 11.0000 0.8500 11.0000 0.9000 60.0000 1.10003600.0000 1.2100 2.0000 1.3600 0.1500 1.3600 0.1500
1.2000 0.0800 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.5500 0.7000 2.6000 0.7000 10.0000
0.7000 10.0000 /
0 'USRMDL' 0 'GSFPRT' 0 2 3 12 0 7 <bus> '<mach>' 0
47.0000 0.2000 47.0000 0.2000 47.0000 0.2000 53.0000
0.2000 53.0000 0.2000 53.0000 0.2000 /
/*********************************************************************************
Template 3: The PSS/E dyr file template for V112 GS 3.075MW 50Hz
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 47/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 47 of 53
/********************************************************************************
/
/ MODULE: Vestas Generic Model Dynamic Data Template for PSS/E
/ Model revision: 8.0.1
/ WTG type: V112 GridStreamer 3.0MW 50Hz Mk0E
//********************************************************************************
/ The lines below must be repeated for each wind generator or composite
/ wind farm generator that occurs in the network.
/ Terms in <angle brackets> must be replaced as follows:
/ <bus> with the generator bus number
/ <mach> with the machine ID
/ <WTGmode> with the control mode at WTG level: 0 for Q control, 1 for PF control
/********************************************************************************
<bus> 'USRMDL' '<mach>' 'GSCORE' 1 1 2 45 23 104 1 0
3000.0000 650.0000 3768.4458 0.0100 0.0000 0.0000 0.0000
0.3500 7.8500 0.000082 940.0000 -3500.0000 3500.0000 -3000.0000
3000.0000 1.0500 0.9000 0.7500 1.0000 1.0000 0.0000
0.0000 0.0000 0.0000 0.0300 0.3000 0.0000 0.00000.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVARS' 8 0 2 0 0 30 <bus> '<mach>' /
0 'USRMDL' 0 'GSLVRT' 8 0 3 65 10 35 <bus> '<mach>' 1
0.8500 0.0000 0.6000 10.0000 200.0000 100.0000 200.0000
0.0000 1.0800 0.0050 1.0050 1.4400 0.0000 650.0000
3768.4458 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.9000 0.0000 0.0000 0.0100
0.0000 0.0000 2.0000 1.0000 0.0000 1.0500 -1.0000
1.2000 0.8500 0.1500 0.0500 0.1000 0.4900 0.5000
0.8000 0.3900 0.4000 0.0000 0.0000 0.0500 0.9000
1.1000 0.0000 0.8000 0.9000 1.1000 1.2000 0.10002.5000 0.6000 900.0000 60.0000 1.0000 1.0000 1.2500
1.2000 0.7000 /
0 'USRMDL' 0 'GSPWRC' 8 0 3 30 7 10 <bus> '<mach>' <WTGmode>
1.0000 0.6504 -0.6504 0.5002 0.5035 0.8691 0.9360
0.0000 0.0000 0.1000 0.1000 20.0000 20.0000 0.0160
0.0160 0.0000 1.1000 1.2000 1.1000 1.2000 0.2200
-1.4000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 /
0 'USRMDL' 0 'GSMEAS' 8 0 2 10 8 5 <bus> '<mach>'
0.0320 0.0320 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVPRT' 0 2 7 30 0 18 <bus> '<mach>' 1 1 0 0 0
0.8500 11.0000 0.8500 11.0000 0.9000 60.0000 1.10003600.0000 1.2100 2.0000 1.3600 0.1500 1.3600 0.1500
1.2000 0.0800 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.5500 0.7000 2.6000 0.7000 10.0000
0.7000 10.0000 /
0 'USRMDL' 0 'GSFPRT' 0 2 3 12 0 7 <bus> '<mach>' 0
47.0000 0.2000 47.0000 0.2000 47.0000 0.2000 53.0000
0.2000 53.0000 0.2000 53.0000 0.2000 /
/*********************************************************************************
Template 4: The PSS/E dyr file template for V112 GS 3.0MW 50Hz
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 48/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 48 of 53
/********************************************************************************
/
/ MODULE: Vestas Generic Model Dynamic Data Template for PSS/E
/ Model revision: 8.0.1
/ WTG type: V112 GridStreamer 3.075MW 60Hz Mk0E
//********************************************************************************
/ The lines below must be repeated for each wind generator or composite
/ wind farm generator that occurs in the network.
/ Terms in <angle brackets> must be replaced as follows:
/ <bus> with the generator bus number
/ <mach> with the machine ID
/ <WTGmode> with the control mode at WTG level: 0 for Q control, 1 for PF control
/********************************************************************************
<bus> 'USRMDL' '<mach>' 'GSCORE' 1 1 2 45 23 104 1 0
3075.0000 650.0000 3862.6569 0.0100 0.0000 0.0000 0.0000
0.3500 7.8500 0.000082 940.0000 -3500.0000 3500.0000 -3000.0000
3000.0000 1.0500 0.9000 0.7500 1.0000 1.0000 0.0000
0.0000 0.0000 0.0000 0.0300 0.3000 0.0000 0.00000.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVARS' 8 0 2 0 0 30 <bus> '<mach>' /
0 'USRMDL' 0 'GSLVRT' 8 0 3 65 10 35 <bus> '<mach>' 1
0.8500 0.0000 0.6000 10.0000 200.0000 100.0000 200.0000
0.0000 1.0800 0.0050 1.0050 1.4400 0.0000 650.0000
3862.6569 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.9000 0.0000 0.0000 0.0100
0.0000 0.0000 2.0000 1.0000 0.0000 1.0500 -1.0000
1.2000 0.8500 0.1500 0.0500 0.1000 0.4900 0.5000
0.8000 0.3900 0.4000 0.0000 0.0000 0.0500 0.9000
1.1000 0.0000 0.8000 0.9000 1.1000 1.2000 0.10002.5000 0.6000 750.0000 60.0000 1.0000 1.0000 1.2500
1.2000 0.7000 /
0 'USRMDL' 0 'GSPWRC' 8 0 3 30 7 10 <bus> '<mach>' <WTGmode>
1.0000 0.6504 -0.6504 0.5002 0.5035 0.8691 0.9360
0.0000 0.0000 0.1000 0.1000 20.0000 20.0000 0.0160
0.0160 0.0000 1.1000 1.2000 1.1000 1.2000 0.2200
-1.4000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 /
0 'USRMDL' 0 'GSMEAS' 8 0 2 10 8 5 <bus> '<mach>'
0.0320 0.0320 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVPRT' 0 2 7 30 0 18 <bus> '<mach>' 1 1 0 0 0
0.8500 11.0000 0.8500 11.0000 0.9000 60.0000 1.10003600.0000 1.2100 2.0000 1.3600 0.1500 1.3600 0.1500
1.2000 0.0800 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.5500 0.7000 2.6000 0.7000 10.0000
0.7000 10.0000 /
0 'USRMDL' 0 'GSFPRT' 0 2 3 12 0 7 <bus> '<mach>' 0
56.4000 0.2000 56.4000 0.2000 56.4000 0.2000 63.6000
0.2000 63.6000 0.2000 63.6000 0.2000 /
/*********************************************************************************
Template 5: The PSS/E dyr file template for V112 GS 3.075MW 60Hz
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 49/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 49 of 53
/********************************************************************************
/
/ MODULE: Vestas Generic Model Dynamic Data Template for PSS/E
/ Model revision: 8.0.1
/ WTG type: V112 GridStreamer 3.0MW 60Hz Mk0E
//********************************************************************************
/ The lines below must be repeated for each wind generator or composite
/ wind farm generator that occurs in the network.
/ Terms in <angle brackets> must be replaced as follows:
/ <bus> with the generator bus number
/ <mach> with the machine ID
/ <WTGmode> with the control mode at WTG level: 0 for Q control, 1 for PF control
/********************************************************************************
<bus> 'USRMDL' '<mach>' 'GSCORE' 1 1 2 45 23 104 1 0
3000.0000 650.0000 3768.4458 0.0100 0.0000 0.0000 0.0000
0.3500 7.8500 0.000082 940.0000 -3500.0000 3500.0000 -3000.0000
3000.0000 1.0500 0.9000 0.7500 1.0000 1.0000 0.0000
0.0000 0.0000 0.0000 0.0300 0.3000 0.0000 0.00000.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVARS' 8 0 2 0 0 30 <bus> '<mach>' /
0 'USRMDL' 0 'GSLVRT' 8 0 3 65 10 35 <bus> '<mach>' 1
0.8500 0.0000 0.6000 10.0000 200.0000 100.0000 200.0000
0.0000 1.0800 0.0050 1.0050 1.4400 0.0000 650.0000
3768.4458 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.9000 0.0000 0.0000 0.0100
0.0000 0.0000 2.0000 1.0000 0.0000 1.0500 -1.0000
1.2000 0.8500 0.1500 0.0500 0.1000 0.4900 0.5000
0.8000 0.3900 0.4000 0.0000 0.0000 0.0500 0.9000
1.1000 0.0000 0.8000 0.9000 1.1000 1.2000 0.10002.5000 0.6000 900.0000 60.0000 1.0000 1.0000 1.2500
1.2000 0.7000 /
0 'USRMDL' 0 'GSPWRC' 8 0 3 30 7 10 <bus> '<mach>' <WTGmode>
1.0000 0.6504 -0.6504 0.5002 0.5035 0.8691 0.9360
0.0000 0.0000 0.1000 0.1000 20.0000 20.0000 0.0160
0.0160 0.0000 1.1000 1.2000 1.1000 1.2000 0.2200
-1.4000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 /
0 'USRMDL' 0 'GSMEAS' 8 0 2 10 8 5 <bus> '<mach>'
0.0320 0.0320 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVPRT' 0 2 7 30 0 18 <bus> '<mach>' 1 1 0 0 0
0.8500 11.0000 0.8500 11.0000 0.9000 60.0000 1.10003600.0000 1.2100 2.0000 1.3600 0.1500 1.3600 0.1500
1.2000 0.0800 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.5500 0.7000 2.6000 0.7000 10.0000
0.7000 10.0000 /
0 'USRMDL' 0 'GSFPRT' 0 2 3 12 0 7 <bus> '<mach>' 0
56.4000 0.2000 56.4000 0.2000 56.4000 0.2000 63.6000
0.2000 63.6000 0.2000 63.6000 0.2000 /
/*********************************************************************************
Template 6: The PSS/E dyr file template for V112 GS 3.0MW 60Hz
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 50/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 50 of 53
Appendix B. Data for V112/V117/V126 GS 3.3MW 50/60Hz
B.1 PQ Capability Chart
Figure 12 Vestas V112/V117/V126 GS 3.3MW wind turbine PQ Capability Chart with active power (P) onX-axis and reactive power (Q) on Y-axis. The above plot refers to LV (0.65kV) side of the WTG trans-
former and with the LV side voltage between 0.9 p.u. and 1.1 p.u.
Table 18 Parameters of the PQ capability for V112/V117/V126 GS 3.3MW Offshore
Parameter Units ValuesMbase MW 3.3
[ X1, X2, X3, X4 ] p.u. [ 0.0 0.5002 1.0 0.4900]
[ Y1, Y2, Y3, Y4 ] p.u. [ 0.6667 0.5854 -0.3848 -0.6667]
PF_Cap_Max (Full Load) - 0.8630
PF_Ind_Max (Full Load) - 0.9333
PF_Cap_Min (Partial Load) - 0.0
PF_Ind_Min (Partial Load) - 0.0
P(X1,Y1) P(X2,Y1)
P(X3,Y2)
P(X3,Y3)
P(X4,-Y1)P(X1,-Y1)
Y4 = -Y1
(0 , 0)
Y1
X3 = Mbase
0.90.80.70.60.3 0.50.40.20.1
P a r t i
a l L
o a d
P F
_ C a p
_ M i n
Full Load
PF_ Cap_ Ma x
F u l l L o a d P F _I n d _M a x P a r t i a l L o a d
P F _
I n d _
M i n
P
Q
-Q
Y4
P(X1,Y4) P(X4,Y4)
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 51/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 51 of 53
B.2 Generator Data
Table 19 WTG’s generator data for V112/V117/V126 GS 3.3MW
Rated Power Rated Voltage Machine Rsource* (pu) Machine Xsource* (pu)
3.3 MW 0.65 kV 0.0047 0.8219
*Per-unit parameters are on machine base.
B.3 Typical Transformer Data
Table 20 Transformer data for V112/V117/V126 GS 3.3MW
No. Parameter Values
1 Rated Power, MW 3.32 Winding base, MVA 3.75
3 Low Voltage rating, kV 0.65
4 High Voltage rating, kV 20.0
5 R*(pu) 0.007
6 X* (pu) 0.080
7 Vector Group Dyn5
8 Tap Range ±2 x 2.5%
*Per-unit parameters are on winding MVA base.
B.4 PSS/E DYR File Template
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 52/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
Page: 52 of 53
/********************************************************************************
/
/ MODULE: Vestas Generic Model Dynamic Data Template for PSS/E
/ Model revision: 8.0.1
/ WTG type: V112 GridStreamer 3.3MW 50Hz Mk2A
//********************************************************************************
/ The lines below must be repeated for each wind generator or composite
/ wind farm generator that occurs in the network.
/ Terms in <angle brackets> must be replaced as follows:
/ <bus> with the generator bus number
/ <mach> with the machine ID
/ <WTGmode> with the control mode at WTG level: 0 for Q control, 1 for PF control
/********************************************************************************
<bus> 'USRMDL' '<mach>' 'GSCORE' 1 1 2 45 23 104 1 0
3300.0000 650.0000 4144.0000 0.0100 0.0000 0.0000 0.0000
0.3500 7.8500 0.000082 940.0000 -3700.0000 3700.0000 -3300.0000
3300.0000 0.9700 0.8500 0.7500 1.0000 1.0000 0.0000
0.0000 0.0000 0.0000 0.0300 0.3000 0.0000 0.00000.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVARS' 8 0 2 0 0 30 <bus> '<mach>' /
0 'USRMDL' 0 'GSLVRT' 8 0 3 65 10 35 <bus> '<mach>' 1
0.8500 0.0000 0.6000 10.0000 200.0000 100.0000 200.0000
0.0000 1.0800 0.0050 1.0050 1.4400 0.0000 650.0000
4144.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.9000 0.0000 0.0000 0.0100
0.0000 0.0000 2.0000 1.0000 0.0000 1.0500 -1.0000
1.2000 0.8500 0.1500 0.0500 0.1000 0.4900 0.5000
0.8000 0.3900 0.4000 0.0000 0.0000 0.0500 0.9000
1.1000 0.0000 0.8000 0.9000 1.1000 1.2000 0.10002.5000 0.6000 600.0000 60.0000 1.0000 1.0000 1.2500
1.2000 0.7000 /
0 'USRMDL' 0 'GSPWRC' 8 0 3 30 7 10 <bus> '<mach>' <WTGmode>
1.0000 0.6667 -0.6667 0.5002 0.4900 0.8630 0.9333
0.0000 0.0000 0.1000 0.1000 20.0000 20.0000 0.0160
0.0160 0.0000 1.1000 1.2000 1.1000 1.2000 0.2200
-1.4000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 /
0 'USRMDL' 0 'GSMEAS' 8 0 2 10 8 5 <bus> '<mach>'
0.0320 0.0320 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVPRT' 0 2 7 30 0 18 <bus> '<mach>' 1 1 0 0 0
0.8500 10.2000 0.8500 10.2000 0.9000 60.0000 1.10003600.0000 1.2100 2.0000 1.3600 0.1500 1.3600 0.1500
1.2000 0.0800 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.5500 0.7000 2.6000 0.7000 10.0000
0.7000 10.0000 /
0 'USRMDL' 0 'GSFPRT' 0 2 3 12 0 7 <bus> '<mach>' 0
47.0000 0.2000 47.0000 0.2000 47.0000 0.2000 53.0000
0.2000 53.0000 0.2000 53.0000 0.2000 /
/*********************************************************************************
Template 7: The PSS/E dyr file template for V112/V117/V126 GS 3.3MW 50Hz
8/9/2019 PSSE Model User Manual wind Vestas
http://slidepdf.com/reader/full/psse-model-user-manual-wind-vestas 53/53
Item no.:0037-5870_V03 User Manual
PSS/E Model for Vestas GridStreamerTM
Wind Turbines
Version 8.0
Date: 06/09/2013
Issued by: Plant Products &Technologies
Class: Restricted
Type: 05
/********************************************************************************
/
/ MODULE: Vestas Generic Model Dynamic Data Template for PSS/E
/ Model revision: 8.0.1
/ WTG type: V112 GridStreamer 3.3MW 60Hz Mk2A
//********************************************************************************
/ The lines below must be repeated for each wind generator or composite
/ wind farm generator that occurs in the network.
/ Terms in <angle brackets> must be replaced as follows:
/ <bus> with the generator bus number
/ <mach> with the machine ID
/ <WTGmode> with the control mode at WTG level: 0 for Q control, 1 for PF control
/********************************************************************************
<bus> 'USRMDL' '<mach>' 'GSCORE' 1 1 2 45 23 104 1 0
3300.0000 650.0000 4144.0000 0.0100 0.0000 0.0000 0.0000
0.3500 7.8500 0.000082 940.0000 -3700.0000 3700.0000 -3300.0000
3300.0000 0.9700 0.8500 0.7500 1.0000 1.0000 0.0000
0.0000 0.0000 0.0000 0.0300 0.3000 0.0000 0.00000.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVARS' 8 0 2 0 0 30 <bus> '<mach>' /
0 'USRMDL' 0 'GSLVRT' 8 0 3 65 10 35 <bus> '<mach>' 1
0.8500 0.0000 0.6000 10.0000 200.0000 100.0000 200.0000
0.0000 1.0800 0.0050 1.0050 1.4400 0.0000 650.0000
4144.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 0.9000 0.0000 0.0000 0.0100
0.0000 0.0000 2.0000 1.0000 0.0000 1.0500 -1.0000
1.2000 0.8500 0.1500 0.0500 0.1000 0.4900 0.5000
0.8000 0.3900 0.4000 0.0000 0.0000 0.0500 0.9000
1.1000 0.0000 0.8000 0.9000 1.1000 1.2000 0.10002.5000 0.6000 600.0000 60.0000 1.0000 1.0000 1.2500
1.2000 0.7000 /
0 'USRMDL' 0 'GSPWRC' 8 0 3 30 7 10 <bus> '<mach>' <WTGmode>
1.0000 0.6667 -0.6667 0.5002 0.4900 0.8630 0.9333
0.0000 0.0000 0.1000 0.1000 20.0000 20.0000 0.0160
0.0160 0.0000 1.1000 1.2000 1.1000 1.2000 0.2200
-1.4000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 /
0 'USRMDL' 0 'GSMEAS' 8 0 2 10 8 5 <bus> '<mach>'
0.0320 0.0320 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.0000 /
0 'USRMDL' 0 'GSVPRT' 0 2 7 30 0 18 <bus> '<mach>' 1 1 0 0 0
0.8500 10.2000 0.8500 10.2000 0.9000 60.0000 1.10003600.0000 1.2100 2.0000 1.3600 0.1500 1.3600 0.1500
1.2000 0.0800 0.0000 0.0000 0.0000 0.0000 0.0000
0.0000 0.0000 0.5500 0.7000 2.6000 0.7000 10.0000
0.7000 10.0000 /
0 'USRMDL' 0 'GSFPRT' 0 2 3 12 0 7 <bus> '<mach>' 0
56.4000 0.2000 56.4000 0.2000 56.4000 0.2000 63.6000
0.2000 63.6000 0.2000 63.6000 0.2000 /
/*********************************************************************************
Template 8: The PSS/E dyr file template for V112/V117/V126 GS 3.3MW 60Hz