PressosmartPressurisation set
Alfa Laval manufactures and sells a complete line of pres-surisation sets: the Pressosmart range. With a simple, unique design and very high reliability, these pressurisation sets allow control and efficiency, steadily maintaining constant pressure in a closed water loop. Pressurisation sets can be used in a very wide range of applications in heating, air conditioning and industrial fields where low temperature, high pressure, over-heated or chilled water closed loop systems are being used as heating or cooling sources.
When installed in a closed loop water system where tem-perature variations occur, the Pressosmart pressurisation set performs four main functions automatically:
− Maintenance of a constant and steady pressure − Expansion − Filling-up – Disconnection
Operating principleWhen water temperature rises: The internal pressure of the closed loop water system increases until it exceeds the pressure control valve setting value which then opens and lets water flow back to the open expansion vessel.
When water temperature decreases: The closed loop water system internal pressure falls until it reaches the pressure controller set point which then activates the pump(s).
Main components A pressurisation set of the Pressosmart range consists of two parts delivered separately that the contractor has to reassem-ble together on site:
A ‘’pump module’’ with a painted base frame fitted with: − One or two pumps (depending on model) − One or two pressure control valves (depending on model) − A set of black steel connecting pipes − An electronic pressure transducer (or pressure switches) − The electrical panel including the pressure controller contactors and overload protections for the pump motors
An open expansion vessel with disconnection constructed from mild steel sheets with internal/external corrosion protective coating fitted with: − A drain port − An overflow port − A port for connecting the automatic fill-up solenoid valve (delivered loose – 240V / 1Ph / 50 Hz coil) − Two ports for fitting the level control float devices − Two ports for connection of the pump module − A removable top cover enabling internal inspection of the vessel and introduction of chemical treatment products
MP5 – 400 litre tank
The above schematic shows the ‘’2 pump module’’ and the open expansion vessel which needs to be piped up together on site.
EF Cold water feed, DW Drain work connection S To the water system
1 Cold feed manual isolation valve 2 Strainer to protect the fill-up solenoid valve (option) 3 Filling-up solenoid valve – 230 V / 50 Hz coil 4 High level float switch 5 Low level float switch 6 Manual isolation valve 7 Fill-up water pump 8 Manual flow adjustment valve 9 Non-return valve 10 Main manual isolation valve (not provided) 11 Connection pipe 12 Pressure transducer or pressure switch 13 Strainer for protection of the flow control valve 14 Upstream pressure control valve (PCV) 15 Open expansion vessel 16 Drain cock 17 Control panel
P
5
P
P
1
EF
DW
S
2
3
15
L
16
6 7 89
6
14 136
14
Flex
Flex
Flex
Flex
12
17
11
10
136
7 89
4
Pressure
Ph
Open
Closed
P1 stop
P2 stop
P0 P1 run
Pb Low alarm
High alarm
Overflow valve
Neutral zone
Hst + 14
Hst + 9
Hst + 7
Hst + 2
Hst - 1
E
d d
Basic equipment
P2 run
E Hst + 5
Hst
Quick selection chart
The chart below should be used for installations utilising LPHW at 90/70°C (mean temperature of 80°C).
Example of use− Installation heating capacity: 1,800 kW − Building static height: 40 MWG
Remarks– Models in red are fitted with pumps the unitary flow rate of which equals 2/3 of the maximum expansion flow rate.
– Models in green are built on request. Please consult manu- facturer or supplier for information.
– Pumps of all the other models are sized for 100% of the maximum expansion flow rate.
Please consult manufacturer or supplier for higher capacities, static heights or pipework water content.
200 400 600 800 1,000 1,500 2,000 2,500 3,000 3,500 4,000 5,000
MP 4-90 MP 4-90 MP 4-90 MP 4-90 MP 4-90
MP 4-90 MP 5-90 MP 5-90 MP 5-90 MP 5-90 MP 5-90 MP 5-90 MP 5-90 SPD 90 SPD 90 SPD 90
MP 5-90 SPD 90 SPD 90 SPD 90 SPD 90 SPD 90 SPD 90 SPD 90 CP2K 90 CP2K 90 CP2K 90 CP4K 120
SPD 90 CP2K 90 CP2K 90 CP2K 90 CP2K 90 CP2K 90 CP2K 90 CP2K 90 CP4K 80 CP4K 100 CP4K 100 27
MP 4-70 MP 4-70 MP 4-70 MP 4-70 MP 4-70
MP 4-70 MP 5-70 MP 5-70 MP 5-70 MP 5-70 MP 5-70 MP 5-70 MP 5-70 SPD 70 SPD 70 SPD 70
MP 5-70 SPD 70 SPD 70 SPD 70 SPD 70 SPD 70 SPD 70 SPD 70 CP2K 70 CP2K 70 CP2K 70 CP4K 100
SPD 70 CP2K 70 CP2K 70 CP2K 70 CP2K 70 CP2K 70 CP2K 70 CP2K 70 CP4K 70 CP4K 80 CP4K 80 27
MP 195 MP 4-60 MP 4-60 MP 4-60 MP 4-60 MP 4-60
MP 4-60 MP 5-60 MP 5-60 MP 5-60 MP 5-60 MP 5-60 MP 5-60 MP 5-60 SPD 60 SPD 60 SPD 60
MP 5-60 SPD 60 SPD 60 SPD 60 SPD 60 SPD 60 SPD 60 SPD 60 CP2K 60 CP2K 60 CP2K 60 CP4K 100
SPD 60 CP2K 60 CP2K 60 CP2K 60 CP2K 60 CP2K 60 CP2K 60 CP2K 60 CP4K 60 CP4K 60 CP4K 60 27
MP 195 MP 4-50 MP 4-50 MP 4-50 MP 4-50 MP 4-50
MP 4-50 MP 5-50 MP 5-50 MP 5-50 MP 5-50 MP 5-50 MP 5-50 MP 5-50 SPD 50 SPD 50 SPD 50
MP 5-50 SPD 50 SPD 50 SPD 50 SPD 50 SPD 50 SPD 50 SPD 50 CP2K 50 CP2K 50 CP2K 50 CP4K 70
SPD 50 CP2K 50 CP2K 50 CP2K 50 CP2K 50 CP2K 50 CP2K 50 CP2K 50 CP4K 50 CP4K 50 CP4K 50 27
MP 195 MP 4-50 MP 4-50 MP 4-50 MP 4-50 MP 4-50
MP 4-50 MP 5-50 MP 5-50 MP 5-50 MP 5-50 MP 5-50 MP 5-50 MP 5-50 SPD 50 SPD 50 SPD 50
MP 5-50 SPD 50 SPD 50 SPD 50 SPD 50 SPD 50 SPD 50 SPD 50 CP2K 40 CP2K 40 CP2K 40 CP4K 50
SPD 50 CP2K 40 CP2K 40 CP2K 40 CP2K 40 CP2K 40 CP2K 40 CP2K 40 CP4K 40 CP4K 40 CP4K 40 27
MP 195 MP 4-40 MP 4-40 MP 4-40 MP 4-40 MP 4-40
MP 4-40 MP 5-40 MP 5-40 MP 5-40 MP 5-40 MP 5-40 MP 5-40 MP 5-40 SPD 30 SPD 30 SPD 30
MP 5-40 SPD 30 SPD 30 SPD 30 SPD 30 SPD 30 SPD 30 SPD 30 CP2K 30 CP2K 30 CP2K 30 CP4K 40
SPD 30 CP2K 30 CP2K 30 CP2K 30 CP2K 30 CP2K 30 CP2K 30 CP2K 30 CP4K 30 CP4K 30 CP4K 30 27
0 500 1,000 1,500 2,000 2,500 3,750 5,000 6,850 7,500 8,750 10,000 12,500
Global capacity of the installation in kW
Size of the open expansion vessel in litres
65
55
45
35
25
15
Sta
tic h
eig
ht o
f th
e in
stal
latio
n in
MW
G
Water content of the installation in m³
0 6 12 18 24 30 40 60 75 90 105 120 150
Selection− Unit model MP 4-60, MP 5-60, SPD 60 or CP2K 60 − 800 litre expansion vessel
Number of pumps
Number of PCV (1)
Electrical supply
Power input kW
FLA A (2)
Static height MWG (3)
Weight without tank kg (4)
Connection size (5)
MP 195 S1
1 1230 V 1 Ph
50 Hz
0.8 3.8 35 96
DN 25 1"
MP 195 S2 0.9 4.2 45 96
MP 195 L1 0.8 3.8 35 96
MP 195 L2 0.9 4.2 45 96
MP 4 30
1 1230 V 1 Ph
50 Hz
0.6 2.4 15 45
DN 25 1"
MP 4 50 0.8 3.8 35 47
MP 4 60 0.9 4.2 45 48
MP 4 70 0.75 5.1 55 60
MP 4 90 1.1 7.5 65 65
MP 5 30
2 1 or 2230 V 1 Ph
50 Hz
1.2 4.8 15 57
DN 40 1½"
MP 5 50 1.6 7.6 35 58
MP 5 60 1.8 8.4 45 61
MP 5 70 1.5 10.2 55 87
MP 5 90 2.2 15.0 65 90
SPD 30
2 1 or 2400 V + N
3 Ph 50 Hz
0.75 1.92 15 100
DN 50 2"
SPD 40 1.1 2.88 15 102
SPD 50 1.6 2.88 35 102
SPD 60 1.8 3.72 45 106
SPD 70 1.5 3.72 55 108
SPD 90 2.2 5.30 65 110
CP 2 K 30
2 1 or 2400 V + N
3 Ph 50 Hz
0.75 1.92 15 105
DN 50 2"
CP 2 K 40 1.1 2.88 15 107
CP 2 K 50 1.6 2.88 35 107
CP 2 K 60 1.8 3.72 45 113
CP 2 K 70 1.5 3.72 55 115
CP 2 K 90 2.2 5.30 65 117
ECE00007EN 0509
How to contact Alfa LavalUp-to-date Alfa Laval contact details for all countries are always available on our website at www.alfalaval.com
All rights reserved for changes in specifications
General features
(1) PCV stands for Pressure Control Valve (Upstream pressure actually controlled) (2) When operating at full load conditions under 230/1/50 (400/3/50 for SPD and CP2K)
Options 89 micron core water strainer – For protection of the expansion vessel fill-up solenoid valve. – To be fitted in the cold water feed pipe upstream of the fill-up solenoid valve.
Anti-water hammer– To be fitted every time the distance of the pipe connecting the Pressosmart pressurisation set to the installation is significant. – Standard for the MP 195 range.
Impulsion meter– Memorises the normal operation of the installation regarding complementary water fill-up. – Should their frequency or duration be increasing, the
pressurisation set would be shutdown and an alarm would be triggered (in case of pipework leakage for example).
Fill-up bypassEnables a rapid fill-up of the water system through a manual valve (normally closed) bypassing the automatic fill-up system.
Flood detector– Allows detection of the presence of water at ground level in the plant room where the Pressosmart pressurisation set is installed. – The sensor is fixed onto the side of the pump module base frame. To be made on site by others.
(3) Building maximum static height (4) Weight without the open expansion vessel except for models MP 195 (5) Minimum diameter for the connection pipe to the installation