Q: Does Partial Height Containment Work?
A: Yes.
Partial Height Containment Architecture
POLARGY WE KEEP THE CLOUD COOLTM
Partial Height CFD Analysis
BASE LINE 562 kW of heat load
164 racks
Slab floor
CRAH Galleries
18” Rack Top Baffles
POLARGY WE KEEP THE CLOUD COOLTM
CFD Test #1 No containment
RESULTS Hot spots
Recirculation over cabinets
16 non-compliant cabinets
Inlet temps > 89.6°F
POLARGY WE KEEP THE CLOUD COOLTM
CFD Test #2 Rack Top Baffles & No Doors
RESULTS
18” Rack Top Baffles
Significant improvement
Non-compliant cabinets reduced from 16 to 2
POLARGY WE KEEP THE CLOUD COOLTM
RESULTS
18” Rack Top Baffles
Aisle End Doors
100% compliance
CFD Test #3 Rack Top Baffles with Doors
POLARGY WE KEEP THE CLOUD COOLTM
CFD Conclusions
• Partial height containment eliminated recirculation in the CFD modeling.
• Today, the room is operating within the Service Level Agreement terms with no cabinets out of compliance.
Site’s Data Center Manager, “Just a side note - the baffles work great.”