Definition of Fan
Fan is a rotary machine, which maintain acontinuous flow of air/gas at a pressureratio not normally exceeding 1:1.11
![Page 3: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/3.jpg)
Difference among Fans, Blowers And Compressors
![Page 4: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/4.jpg)
Content
Definition of DraughtPurposeClassification
Definition of FanTypes and purpose of fansWorking Principle of fansClassification of fansFan Controlling Devices
![Page 5: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/5.jpg)
Definition of Draught System
Draught defines a differential pressure between atmosphere & through out the fuel, air and flue gas path in the system. There should be sufficient arrangement to create necessary draft. The system is consisted of feeders, pulverizers, fans (PA, FD, ID, Seal Air, Scanner Air etc.), burners, Wind Box, SADC, boiler fire side, APH, ESP, and Chimney.
![Page 6: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/6.jpg)
To ensure sufficient, efficient and safe flow of fuel, air and products of combustion through the steam generator.
To maintain the standards of other combustion control parameters such as Oxygen in Flue Gas, Carbon in Ash, Sox & NOx in Flue Gas, Flue Gas Velocity, Flue Gas Exhaust Temperature etc.
Purpose of Draught System
![Page 7: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/7.jpg)
Classification
Natural Draught
Induced Draught
Forced Draught
Balanced Draught
![Page 8: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/8.jpg)
![Page 9: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/9.jpg)
![Page 10: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/10.jpg)
![Page 11: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/11.jpg)
Purpose of Fans
To develop moderate pressure of the Air or gas in order to transport it from one place to another at desired Parameters.
![Page 12: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/12.jpg)
Centrifugal Fans Single SuctionDouble Suction
Impeller may have Radial, Forward or Backward curved blades on the basis of application
Axial Fans Single StageDouble Stage
Axial fans are further classified as Propeller, Tube axial and Vane axial
Classification of Fans
![Page 13: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/13.jpg)
Types of Centrifugal Fans
![Page 14: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/14.jpg)
Types of Axial Fans
![Page 15: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/15.jpg)
Types of Boiler Fans
PA Fans FD Fans ID FansSeal Air fans Scanner Air Fans Igniter Air Fans
![Page 16: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/16.jpg)
FD Fan is required to provide air for ensure proper flow of products of combustion and to also to ensure complete combustion of coal or oil inside the furnace. This air is termed as “Secondary Air” because it is supplied after the primary air.
Forced Draught Fan
Application :Provide air for combustion of coal. Number per boiler : Two Type : Axial fan, Single stage Medium handled : Air Orientation : Vertical suction and Horizontal delivery Regulation : Blade pitch control
Specification Axial Fan Used as FD Fan:
![Page 17: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/17.jpg)
SUCTION HOOD
DIFFUSER
UPPER CASING OF IMPELLER
BOTTOM CASING OF IMPELLER
MOTOR
FD FAN
![Page 18: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/18.jpg)
![Page 19: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/19.jpg)
Technical specifications
FD FAN:
• Manufacturer Shanghai Blower Works Co. Ltd.• Fan Type FAF-28-14-1• Adjustment method Blade adjustable• Total pressure boost(Pa) 4523• Flow rate(m3/s) 341.30• Temperature of 32
incoming air(deg C)• Rotating speed(r/min) 990• Model YKK560-4• Motor rating power(KW) 1850• Voltage(KV) 3.3
![Page 20: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/20.jpg)
Induced Draught Fan
ID Fan is required to extract the product of combustion called flue gas form the furnace and discharge the same to the chimney, which in turn to the atmosphere.
Application : For extraction of Flue gases. Number per boiler : Two Type : Axial fan, single stage Medium handled : Flue gas Orientation : Axially suction delivery Regulation : Blade pitch control
Specification Centrifugal Fan Used as ID Fan:
![Page 21: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/21.jpg)
Suction hood
Motor
Impeller
ID FAN
![Page 22: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/22.jpg)
![Page 23: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/23.jpg)
ID FAN:
• Manufacturer Shanghai Blower Works Co. Ltd.• Fan Type 3AF-37.5-22.4-1• Adjustment method Blade adjustable• Total pressure boost(Pa) 6136• Flow rate(m3/s) 656.6• Temperature of 152.8
incoming air(deg C)• Rotating speed(r/min) 745• Model YKK560-4• Motor rating power(KW) 4950• Voltage(KV) 3.3
![Page 24: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/24.jpg)
Primary Air Fan
PA Fan is required to provide air to dry the coal in mill and transport it from mill to furnace. This air is termed as “ Primary Air”.Specification Axial Fan Used as PA Fan:
Application : For Coal transportation and drying Number per boiler : Two Type : Axial fan , Double stage Medium handled : Air Orientation : Vertical suction & Horizontal delivery Regulation : Blade pitch and damper control
![Page 25: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/25.jpg)
DIFFUSER
PA FANDOUBLE STAGE
![Page 26: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/26.jpg)
![Page 27: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/27.jpg)
PA FAN :
• Manufacturer Shanghai Blower Works Co. Ltd.• Fan Type PAF-21.1-12.5-2• Adjustment method Blade adjustable• Total pressure boost(Pa) 13139• Flow rate(m3/s) 20460 m3 /s
• Temperature of
incoming air(deg C) 50• Rotating speed(r/min) 1490• Model YKK560-4• Motor rating power(KW) 3300• Voltage(KV) 3.3
![Page 28: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/28.jpg)
Seal Air Fan
Seal air fan boost up the cold primary air pressure to cater the need of sealing the bearings of the rotating component of pulverizers. For example,three rollers and upper bearing of the bowl ofeach ‘Bowl & Roller Mill’ are supplied with seal airto protect its abrasion by coal particles.
![Page 29: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/29.jpg)
Scanner Air Fan
These fan takes suction either from FD Fan discharge duct or from atmosphere and always supply its discharge air to the ‘Flame Scanners’for their cooling and cleaning.
![Page 30: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/30.jpg)
Fans convert kinetic energy of a prime mover partially into pressure head and remaining into velocity head (kinetic energy), which in turn also converted into pressure head by the diffuser and thus build up the pressure of air or gas being displaced.
Working Principle of Fans
![Page 31: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/31.jpg)
Fan Controlling Devices
Damper Control Inlet Guide Vane Control Pitch Control Speed Control
![Page 32: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/32.jpg)
Damper Control
Fan flow and pressure can be changed by varying the cross section at the suction or discharge side of the fan. This type of control has been provided on the suction ducts having rectangular cross section, which is achieved by damper regulating mechanism powered by different types of motors.
![Page 33: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/33.jpg)
![Page 34: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/34.jpg)
![Page 35: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/35.jpg)
Inlet Guide Vane Control
This type of control has been provided on the suction ducts having circular cross section. In principle, it same as that of damper control but reported to more effective.
![Page 36: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/36.jpg)
![Page 37: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/37.jpg)
Blade Pitch Control
Variation in blade pitch vary the flow and pressure of the air/gas being handled.
Blade pitch is controlled by means of Servomotor.
Control oil is used for the operation of Servomotor.
![Page 38: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/38.jpg)
![Page 39: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/39.jpg)
![Page 40: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/40.jpg)
Speed Control
Flow and pressure can be controlled by varying the speed of the fan by using either a infinitely variable speed hydraulic couplingby using a variable frequency electric motor. Many ID Fans in the thermal power plant have been provided with infinitely variable speed hydraulic coupling.
![Page 41: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/41.jpg)
Sectional view of hydraulic coupling
![Page 42: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/42.jpg)
![Page 43: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/43.jpg)
LUBE OIL CIRCUIT
FD FAN
![Page 44: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/44.jpg)
![Page 45: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/45.jpg)
PA FAN
![Page 46: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/46.jpg)
![Page 47: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/47.jpg)
ID FAN
![Page 48: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/48.jpg)
![Page 49: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/49.jpg)
OPERATION OVERVIEW
![Page 50: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/50.jpg)
1 Oil level -- alarm-fill reservoir2 Lube oil flow >3lt /min -- alarm3 Low oil pressure -- alarm-start aux. pump4 Pump switch-over
event-- alarm-determine cause
of switch over
5 Pump #1 running -- No action-into only6 Pump #2 running -- No action-into only7 Heater on -- No action-into only8 Heater off -- No action-into only9 Bearing temperature
high > 900c-- alarm-check oil cooling
10 Bearing temperature high > 1200c
-- trip fan-leave oil running for 10 min.
11 Fan vibration >4mm /s -- alarm-analyze problem12 Fan vibration >11mm /s -- trip fan
13 Fan operating in stall -- alarm-reduce fan output by reducing blade pitch (closing blades)
14 Pump #1 or #2 running and reservoir temperature< 300C(FD,PA), <250C(ID)
-- turn on heaters
15 Reservoir temperature > 400C(FD,PA), <35OC(ID)
-- shut off heaters
![Page 51: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/51.jpg)
PERFORMANCE CURVE
![Page 52: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/52.jpg)
![Page 53: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/53.jpg)
![Page 54: Overview on Fans](https://reader033.vdocuments.us/reader033/viewer/2022061107/544be541af79599c438b5613/html5/thumbnails/54.jpg)
Thank You