![Page 1: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/1.jpg)
CFAA
![Page 2: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/2.jpg)
Outline for Today
Changing Perceptions Defining a Maglock What is the Code Appropriate Uses Questionable Uses Problems Alternatives
![Page 3: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/3.jpg)
Changing Perceptions
![Page 4: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/4.jpg)
Defining a Maglock
What is a Maglock Purpose of Maglocks Types of Maglocks Why are Maglocks Dangerous Why use Maglocks
![Page 5: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/5.jpg)
What is a Maglock?
Door Hardware appliance (Lock) Electrically powered coil magnet Matching armature plate Made of stainless and ferrous metals Generates
60 to 1800lbs of holding force
![Page 6: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/6.jpg)
What is a Maglock?
Options: Door Position Sensor Bond Sensor Delayed egress control module Voltage regulator module
Location: Normally at top of door on the inside Can be used outdoors* Can be used for tricky locking situations
![Page 7: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/7.jpg)
Deters Locked door is a deterrent*
Delays Locked door slows down a burglar*
*However: Maglocks release on fire and on loss of power, which limits these factors
Purpose of a Maglock
![Page 8: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/8.jpg)
Types of Maglocks
Standard Delayed Shear Gate (Exterior) Special Purpose
![Page 9: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/9.jpg)
Typical Office Building Single or Double “L” or “Z” bracket
Standard Maglock
![Page 10: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/10.jpg)
Typical in Retail Stores Built-in Delay (15sec) Alarmed Signage Required
Delayed Maglock
![Page 11: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/11.jpg)
Typical in Sliding Doors Often includes Pins or “Fingers” Rarely Used as “Strength is Unreliable”
Shear Maglock
![Page 12: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/12.jpg)
Typical in Daycare Outdoor Rated* Release is of Concern Swing or Sliding Action
Gate Maglock
![Page 13: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/13.jpg)
Floor Maglock Sliding action Strength is a concern Wear & Tear is a concern Rusting is an issue
*Not Recommended
Special Purpose Maglocks
![Page 14: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/14.jpg)
Why are Maglocks Dangerous
Locks the Door in both directions Requires Intervention to release Keys do not override If installed wrong, can trap people
![Page 15: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/15.jpg)
Why use Maglocks
Traditionally for Glass Doors High Security Doors For Mantrap Doors For Doors that need to lock in
both directions
![Page 16: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/16.jpg)
What is the Code
Alberta Fire Code 2014 Alberta Building Code 2014 ABC - Appendix A
![Page 17: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/17.jpg)
Division B - Part 3
Alberta Fire Code 2014
1) Means of Egress shall be provided in buildings in conformance with the ABC.
![Page 18: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/18.jpg)
Division B - Part 3.4.6.16
Alberta Building Code 2014
![Page 19: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/19.jpg)
ABC 3.4.6.16.(1) Exit Doors must: Release in one action Use no keys Use no special devices Require no training
English Translation
![Page 20: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/20.jpg)
Division B - Part 3.4.6.16
Alberta Building Code 2014
![Page 21: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/21.jpg)
ABC 3.4.6.16.(2) & (3) Door Hardware: All Public &/or High Volume doors: Require only 90N to operate Require only 90N to swing door open
“Every Public (or Popular) door, must be operable by a 90 year old 90lb Grandmother”
English Translation
![Page 22: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/22.jpg)
Division B - Part 3.4.6.16
Alberta Building Code 2014
![Page 23: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/23.jpg)
ABC 3.4.6.15.(4) Maglocks must: Release on fire alarm Release by a single switch (accessible by authorities) Have no pins or latching device Have no residual holding force Do not require keys Do not require special knowledge Release by use of door hardware (single action) Release with 90N of force or less Release immediately or within 15 seconds* *Requires Signage
English Translation
![Page 24: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/24.jpg)
Appendix A.3.4.6.15.(4)
Maglocks Should not replace regular hardware They must not be used indiscriminately Must be Fail-Safe in “Foreseeable Emergencies” All maglocks must be controlled from one switch Maglocks must not reset automatically
What is allowed by the Code
![Page 25: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/25.jpg)
Reset Switch (ABC A.3.4.6.15.(4)) Single Switch is to control all Maglocks Normally installed in or beside main fire panel Maglocks may not rearm when panel returns to
normal Switch is used to reset the Maglocks Switch is part of the Fire alarm system and is to
be supervised Switch is usually keyed (Building Master)
What is allowed by the Code
![Page 26: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/26.jpg)
Maglock with Panic Hardware • Maglock • Fire Alarm tie-in • Power transfer • Cardreader • Door Hardware
with request to exit
Code Compliant Example
![Page 27: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/27.jpg)
Code Compliant Example
Panic Hardware Works with Glass
![Page 28: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/28.jpg)
Maglock with Delayed Egress • Delayed Egress • Maglock • Fire Alarm tie-in • Power transfer • Cardreader
Code Compliant Example
![Page 29: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/29.jpg)
Calgary “Local Customs” that were allowed Maglock Fire Alarm tie-in Push button exit Push/Pull Glass door Blue Pull station*
*Recommended
Previously Accepted Installs
![Page 30: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/30.jpg)
Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for:
○ Single Suite or Tenancy ○ Public not allowed unescorted into the space ○ Group D occupancy only (i.e. Business or Service) ○ Push button is within 600mm of door frame ○ Sign is next to button describing what it does
Issued in 1995 Not renewed in 2000 Therefore, Not Valid
History behind “Local Customs”
![Page 31: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/31.jpg)
Why they are not code compliant Secondary action Specialized device Requires specialized knowledge
How to Wire them if used Shunts power to Maglock Acts as request to exit to controller
Push Buttons
![Page 32: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/32.jpg)
Why they are not compliant Secondary action Specialized device Requires specialized knowledge
How to Wire them when they are used Shunt power to Maglock Alarm input to controller
Blue Pull Stations
![Page 33: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/33.jpg)
Why Use them both? Software freezes Push button shunts power
“but only when Held” Blue pull station removes
power permanently Blue pull station requires
tool to reset
Blue Pull Stations
![Page 34: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/34.jpg)
Why we don’t use them? They release door when triggered They can be released from the outside They will bypass the alarm They rely on software They are not ULC rated
Motion Sensors
![Page 35: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/35.jpg)
Code Compliant Maglock Door Standard = $ 6,000/door Delayed Egress = $ 7,000
Previously “Accepted” Door Maglock with push button = $ 5,500 By Comparison….. Electric Lock = $ 5,000*
Cost of Door Control
![Page 36: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/36.jpg)
Retail Exit Doors Need to prevent shoplifting
Cash Cages & Bank Doors Prevent theft
911 Call Centres Prevent Disruptions, Terrorism & Retaliation
Hospitals & Retirement Homes Protect Patients & Hospital Staff
Where do we use Maglocks?
![Page 37: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/37.jpg)
Maglocks release on Fire & Power Loss Ergo, not as secure
Maglocks lock the door in both directions Ergo, not as safe
Maglocks are more expensive Require Fire Alarm Tie-in (often a hidden/forgotten cost)
The problem with Maglocks
![Page 38: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/38.jpg)
Framed Doors Panic Hardware with Electric Strike Wireless Battery Operated Hardware
Maglock Alternatives
![Page 39: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/39.jpg)
All Glass Door Alternatives
Framed Doors (Allows Traditional Hardware)
![Page 40: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/40.jpg)
Glass Door Alternatives
Panic Hardware Using Electric Strike
![Page 41: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/41.jpg)
All Glass Door Alternatives
Wireless Battery Operated Hardware
![Page 42: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/42.jpg)
Glass Door Alternatives
Stand-alone Battery Operated Use Caution*
*Not all are
Approved Exit Devices
![Page 43: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/43.jpg)
Conclusion
Maglocks always require: Careful Consideration To be used sparingly To use Alternatives when possible To be used safely
Seek advice, if you have questions
![Page 44: Outline for Today. James Sanford.pdf · Standata ABC 3.4.6.15.(4) Maglocks could be installed on office doors for: Single Suite or Tenancy Public not allowed unescorted into the space](https://reader034.vdocuments.us/reader034/viewer/2022050509/5f99d6be8a41dd693c7d3d2a/html5/thumbnails/44.jpg)