InstallatIon notes
ness sCR PlUs Flexible ReceiverProduct Part No. 106-179 (304MHz)
•ReceivesARM/Disarm/PANIC/AUX/LowBattchannelsfromNessRadioKeysorRadioPIRs/RadioReeds.
•Supportsuptofourtransmitters.
•Simple“LearnMode”programmingforradiodevices.
•1xRelayoutputwithselectableToggle/Pulse,selectable
•4xOpenCollectoroutputsforPanic/Tamper,On/Alarm,Aux,LowBattery
Installationandsetupnotes.Rev1
2
TheNessSCR+FlexibleStandaloneReceiverisauniquehighperformanceradioreceiverdesignedtooperatewithanyNessproprietaryradiotransmittingdeviceincludingNessRadioKeys,RadioKeypendants,RadioReedswitches,RadioSmokeDetectorsandRadioPIRs.
TheSCR+isidealforconnectingtoalarmpanelswhichdonotprovideawirelessfacilityandcanbeusedforconnectingwirelessdevicesforzonealarms,PanicbuttonsorRadioKeysforArmingandDisarmingthePanel.
TheInhibitinputgivesthereceivertheuniqueabilitytoidentifytheArmed/Disarmedstatusofanalarmpanel.WhenusedwithaNessradiokeyitallowsthereceivertoalwayscorrectlyArmorDisarmthePanel.
TheSCR+isalsoideallysuitedforapplicationsthatrequirearemotelyswitchedrelayoutputforlowvoltageswitchingapplicationse.g.garagedooropening.
TheRelayoutputcanbeselectedtobePulsingorLatchedforalarmsignalsoraPulsingoutputforPanic/Tamper,AuxorLowBattsignals.
TheSCR+willacceptuptofourindividualRadioKeysandPanicButtonsoruptofouralarmtransmittingdevices(RadioReedSwitchesorPIRs).
Relay - TherelayoutputcanbeprogrammedtoprovideanOn/Off/Alarmoutputoritcanduplicateoneoftheopen-collectoroutputs.
TheReLAyOUTPUTCANBePROgRAMMeDTOPROvIDeONeOFTheFOLLOWINgTyPeSOFOUTPUT:
•AlatchingOn/Off,Alarm/Restore,orLowBatteryoutput.
•AtogglingPanicorAuxOutput.
•PulsedOn/Alarm,Panic/Tamper,Aux,orLowBatteryoutput
sCR+ is designed as a two-in-one solution to replace both the sCR single Channel Receiver and the aUX Receiver.
+12V
0V
Input
AuX
nO
nC
C
RE
LAY
LOW BAtt
pAnIC tAMpOn/ ALARM
Relay oUtPUtIntRodUCtIon
ProgrammableRelayOutput.Singlepolechangeoverdrycontactrated1A@28v.
3
on/alaRm-OpencollectoroutputpulsesfortwosecondswhenavalidONsignalorALARMsignalisreceived.
PanIC/tamPeR-OpencollectorpulsesfortwosecondswhenaPanicorTamperalarmisreceived.
aUX-OpencollectorpulsesfortwosecondswhenanAUXsignalisreceivedfromafourbuttonradiokey.
Note1:NessradiokeyswhichhaveanAUXbuttoninclude: 100-067RK4RadioKey 106-167RK4BRadioKey 106-299RK4PProxRadioKeys.
Note2:TheAUXbuttononthegrey106-178RK3+1radiokeysendsanONsignalnotanAUXsignal.
low Batt-OpencollectoroutputpulsesfortwosecondswhenaLowBatterysignalisreceivedfromeitheraRadioKeyoranAlarmDevice.Connecta12vbeeperoroptionalrelayforconnectiontoanalarmzoneifrequired.
Note:SCR+doesnotidentifywhichdevicehascausedtheLowBatteryalarm.Thebatteriesofallthetransmittingdevicesshouldbechecked.
+12V
0V
Input
AuX
nO
nC
C
RE
LAY
LOW BAtt
pAnIC tAMpOn/ ALARM
+12V
0V
Input
AuX
nO
nC
C
RE
LAY
LOW BAtt
pAnIC tAMpOn/ ALARM
+12V
0V
Input
AuX
nO
nC
C
RE
LAY
LOW BAtt
pAnIC tAMpOn/ ALARM
note: the open Collector outputs require no programming and are always active. the dipswitch settings mentioned in this manual apply only to the Relay output.
INhIBITINPUT
POWeRINPUT
oPen ColleCtoR oUtPUts InhIBIt InPUt
PoweR InPUt
TheInhibitInputcanbeusedwithanoutputfromacontrolpaneltosynchronisetherelayandtheOn/Offbuttonsofaradiokeytothestateofthecontrolpanel.
TheInhibitInputisonlyactivewhentherelayissetforPulsemodeforOn/Offsignals,seeOperationTable2,page6.
Theinputshouldbepulledbelow0.5vtobeLowandabove1vtobehigh.Theinputishighwhenleftopen.
Powerrequirementis12vDC(10-15vDC).TheOpenCollectoroutputsareswitchedlow.100mAmaximumsinkcurrent.
4
InNormalMode
SLOWFLASh Normaloperation.
ONFOR2SeC validradiosignalreceivedfromaprogrammeddevice.
InProgramMode
FASTFLASh ProgramMode.
ON Theselectedcodeslotisprogrammedwitharadiodevice.
FASTFLASh Theselectedcodeslotisempty.
SINgLeFLASh Alearnmessagehasbeenreceived.
WhenthreelearnmessagesoravalidlearnmessagehasbeenreceivedtheLeDwillstayon.
TRIPLeFLASh Thedevicebeingprogrammedalreadyexistsinanothercodeslot.
SWItCh OFF On
1 nORMAL OpERAtIng MOdE pROgRAMMIng MOdE
OFF in nORMAL MOdE On in nORMAL MOdE On in pROgRAM MOdE
2 On/OFF/ALARM/REStORE signals LAtCh the relay
On/ALARM signal puLSES relay program Code 1
3 pAnIC/tAMpER signal tOggLES relay
pAnIC/tAMpER signal puLSES relay program Code 2
4 AuX signal tOggLES relay
AuX signal puLSES relay program Code 3
5 LOW BAttERY signal LAtChES relay
LOW BAttERY signal puLSES relay program Code 4
led oPeRatIon
taBle – dIPswItChes
NOTe2:TheRelaycanbecontrolledbyonesignaltypeonly.Not,forexample,byAUXsignalsandALARMsignalsatthesametime.
NOTe3:Dipswitches2–5onlycontroltheoperationoftheReLAyoutput.TheOpenCollectoroutputsrequirenoprogrammingandarealwaysactiveasPulseoutputs.
NOTe1:Whenselectingswitches2–5theremainingswitchesmustbeswitchedtotheoppositeposition.SeeOperationTables1–8forexamples.
5
TheSCR+canacceptuptofourNesstransmitterssuchasRadioKeys,RadioReedSwitches,RadioPIRs,RadioSmokeDetectorsandotherdevices.
InProgramMode,theSCR+willlearntheradiocodeofuptofourtransmittersintofourcode'slots'.Thedataisstoredinnon-volatilememoryandisretainedevenifpowerisremoved.
PRogRammIng stePs
1 Toenterprogrammodesetswitch1totheONposition. Setswitches2-5totheOFFposition.
1 On
23
45
ON
OFF
ProgramModeOFF/ON
CodeSlot1
CodeSlot2
CodeSlot3
CodeSlot4
The LED will flash fast to indicate program mode.
2 TurnONonlytheswitchforoneofthefourcodeslotstobeprogrammed.
1 On
23
45
ProgramModeOFF/ON
CodeSlot1
CodeSlot2
CodeSlot3
CodeSlot4
example. CodeSlot1isreadyforprogramming.
If the selected code slot is blank the LED
will remain flashing fast. If the code slot already has a device programmed the LED will be ON. The existing radio device must be erased before programming a new one. See How To Erase a Code.
3 SendaLearnsignalfromtheradiodevicetobeprogrammed.
TosendaLearntransmission:
RADIOKeyS,unencrypted -PresstheOFFButton3times.
RADIOKeyS,encrypted -PressandholdPanicforatleast8seconds.
RADIOPIRS-Insertthebattery.
RADIOKeyPeNDANT-PressthePanicbutton3times(beawareofthe1.5seconddelayonthebuttonpress).
RADIOReeDSWITCh-Insertthebattery.
If the device being programmed already exists in another code slot the LED will triple flash on receiving the learn signals. If so the device does not need to be programmed.
to program more devices repeat steps 1 and 2 for the remaining code slots.
4 Whenfinishedprogrammingsetswitch1OFF.
The LED will flash slowly indicating normal operating mode.
5 Setswitches2to5totherequiredpositiontoselecttoggleorpulsemodesforthe
relayoutput.SeetheDipswitchesTable.
how to eRase a Code
Toeraseaprogrammedcodeslot.
1 enterprogrammodebysettingswitch1totheONposition.
2 TurnONtheswitchforthecodeslottobeerased.
The LED will be ON indicating the slot is programmed.
3 PresstheONbuttononanyNessradiokey.
The LED will flash fast indicating the code slot is blank.
PRogRammIng / leaRnIng tRansmItteRs
6
SIgNALTyPe ON/ALARM
ReLAyMODe PULSe
ReLAyACTION
On/Alarmsignal: RelayPulses2sec(WhenInhibitinputisopenorpulledhigh)
Off/Restoresignal: *DependsonthestateoftheInhibitInput,seebelow
SWITChSeTTINgS Switch2on
ToprogramtheReLAyOUTPUTtooperatebyON/ALARM/OFF/ReSTOResignals.
Relay oUtPUt oPeRatIon
1 On
23
45
ProgramMode
ON/ALARMPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFF/ALRMLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
1 On
23
45
ProgramMode
ON/ALARMPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFF/ALRMLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
Alarm>RelayOn
Restore>RelayOff
Whenusingmultipleradioreedswitches,therelaywillturnoffwhenallreedswitcheshaveclosed
ThismodeisnotrecommendedforradioPIRs.
OPeRATIONTABLe1 OPeRATIONTABLe2
ONButton>RelayOn
OFFButton>RelayOff
ONButton>Noaction
OFFButton>RelayPulses2sec
ThisappliestoradioPIRs,radioreedswitchesandradiosmokedetectors
Alarm>Relaypulses2sec
ONButton>RelayPulses2sec
OFFButton>Noaction
SIgNALTyPe ON/OFFALARM/ReSTORe
ReLAyMODe LATChINg
ReLAyACTION
On/Alarmsignal: LatchOnOff/Restoresignal: LatchOff
SWITChSeTTINgS Alloff
OPeRATION
OPeRATION Inhibitinputisopenorpulledhigh.
OPeRATION Inhibitinputispulledlow.
7
ToprogramtheReLAyOUTPUTtooperatebyPANIC/TAMPeRsignals.
Relay oUtPUt oPeRatIon
1 On
23
45
ProgramMode
ON/ALARMPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFF/ALRMLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
1 On
23
45
ProgramMode
ON/ALARMPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFF/ALRMLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
PANICButton>RelaytogglesOn/Off
PANICButton=RelayPulses2sec
TAMPeR>RelaytogglesOn/Off
TAMPeR>RelayPulses2sec
ThisappliestoNesstransmitterswithatamperswitch,suchasLUXRadioPIR,RR1RadioReed
ThisappliestoNesstransmitterswithatamperswitch,suchasLUXRadioPIR,RR1RadioReed
SIgNALTyPe PANIC/TAMPeR
ReLAyMODe TOggLe
ReLAyACTION
Panic/Tampersignal: ToggleOn/OffSWITChSeTTINgS Switch3off,Switches
2,4,5mustbeon
SIgNALTyPe PANIC/TAMPeR
ReLAyMODe PULSe
ReLAyACTION
Panic/Tampersignal: PulseSWITChSeTTINgS Switch3on,Switches
2,4,5off
OPeRATION OPeRATION
OPeRATIONTABLe3 OPeRATIONTABLe4
8
ToprogramtheReLAyOUTPUTtooperatebyanAUXsignalfromRK4radiokeys.
Relay oUtPUt oPeRatIon
1 On
23
45
ProgramMode
ON/ALARMPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFF/ALRMLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
1 On
23
45
ProgramMode
ON/ALARMPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFF/ALRMLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
SIgNALTyPe AUX
ReLAyMODe TOggLe
ReLAyACTION
AUXsignal: ToggleOn/OffSWITChSeTTINgS Switch4off,Switches
2,3,5on
SIgNALTyPe AUX
ReLAyMODe PULSe
ReLAyACTION
AUXsignal: PulseSWITChSeTTINgS Switch4on,Switches
2,3,5off
OPeRATION OPeRATION
AUXButton>RelayPulses2sec
AUXButton>RelaytogglesOn/Off
NessradiokeyswithanAUXbuttoninclude: 100-067RK4RadioKey 106-167RK4BRadioKey 106-299RK4PProxRadioKeys.
Note:Thisdoesnotincludethe106-178RK3+1radiokey(greybody).TheAUXbuttononthismodelsendsanONsignalnot anAUXsignal.
OPeRATIONTABLe5 OPeRATIONTABLe6
9
ToprogramtheReLAyOUTPUTtooperatebyaLOWBATTeRysignalfromtransmitters.
Relay oUtPUt oPeRatIon
1 On
23
45
ProgramMode
ON/ALARMPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFF/ALRMLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
1 On
23
45
ProgramMode
ON/ALARMPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFF/ALRMLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
SIgNALTyPe LOWBATT
ReLAyMODe LATChINg
ReLAyACTION
LOWBATTsignal: LatchOnSWITChSeTTINgS Switch5off,Switches
2,3,4on
SIgNALTyPe LOWBATT
ReLAyMODe PULSe
ReLAyACTION
LOWBATTsignal: PulseSWITChSeTTINgS Switch5on,Switches
2,3,4off
OPeRATION OPeRATION
LOWBATTfromanyprogrammeddevice >RelayLatchesOn
Therelaywilllatchoffwhenalldevicessendabatteryrestoralsignal
LOWBATTfromanyprogrammeddevice >RelayPulses2sec
OPeRATIONTABLe7 OPeRATIONTABLe8
aCtIon swItChes 2-5 InhIBIt InPUt Relay
RadioKeyorReedSwitchOn/Off/Alarm AllOff InputIgnored Latch
DeviceAlarm,PIRorReedOff/Restore Switch2On InputIgnored NoChange
DeviceAlarm,PIRorReedOn Switch2On InputIgnored Pulse
KeyON Switch2On Low NoChange
KeyON Switch2On high Pulse
KeyOFF Switch2On Low Pulse
KeyOFF Switch2On high NoChange
taBle - Relay oPeRatIon wIth InhIBIt InPUt
10
+12V
0V
Input
AuX
nO
nC
C
RE
LAY
LOW BAtt
pAnIC tAMpOn/ ALARM
+12V
0V
Input
AuX
nO
nC
C
RE
LAY
LOW BAtt
pAnIC tAMpOn/ ALARM
ConneCtIon eXamPles
NeSSRADIOPIRSONANyCONTROLPANeL
NeSSRADIOReeDSWITCheSONANyCONTROLPANeL
NessSCR+Receiver
NessSCR+Receiver
Toazoneinputonthecontrolpanel
Toazoneinputonthecontrolpanel
Note:ForfullyintegratedradiooperationonNesscontrolpanelsusetheNess100-200RadioInterface.
Alarm>RelayOn
Restore>RelayOff
Whenusingmultipleradioreedswitches,therelaywillturnoffwhenallreedswitcheshaveclosed
1 On
23
45
ProgramMode
ON/OFFPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFFLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
1 On
23
45
ProgramMode
ON/ALARMPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFF/ALRMLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
12vDCsupply
12vDCsupply
11
+12V
0V
Input
AuX
nO
nC
C
RE
LAY
LOW BAtt
pAnIC tAMpOn/ ALARM
+12V
0V
Input
AuX
nO
nC
C
RE
LAY
LOW BAtt
pAnIC tAMpOn/ ALARM
ConneCtIon eXamPles
NeSSRADIOKeySARMINg/DISARMINgANyCONTROLPANeLUSINgINhIBITINPUT
NeSSRK4RADIOKeyAUXBUTTONOPeRATINgAgARAgeDOOR
NessSCR+Receiver
NessSCR+Receiver
Tothekeyswitchinputonthepanel
Fromanoutputonthecontrolpanelwhichishighwhendisarmedandlowwhenarmed.
Requiresanoutputfromthecontrolpanelwhichishighwhendisarmedandlowwhenarmed.
Togaragedoorcontrollerinput
AUXbutton
1 On
23
45
ProgramMode
ON/ALARMPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFF/ALRMLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
1 On
23
45
ProgramMode
ON/ALARMPulsesrelay
PANIC/TAMPRPulsesrelay
AUXPulsesrelay
LOWBATTPulsesrelay
OperatingMode
ON/OFF/ALRMLatchesrelay
PANIC/TAMPRTogglesrelay
AUXTogglesrelay
LOWBATTLatchesrelay
ONButton>RelayPulses2secwhentheInhibitInputishigh
OFFButton>RelayPulses2secwhentheInhibitInputisLow
12vDCsupply
12vDCsupply
12
NessSCR+FLeXIBLeSINgLeChANNeLReCeIveRInstallationNotesRev1.Jan2016
Documentpartnumber890-441Fortheproducts:106-179SCR+Receiver304Mhz106-180SCR+Receiver868Mhz
©2016NessCorporationPtyLtdABN28069984372Specificationsmaychangewithoutnotice.
www.nesscorporation.com
NationalCustomerServiceCentrePh:1300551991
NessCorporationmanufacturingprocessesareaccreditedtoISO9001qualitystandardsandallpossiblecareanddiligencehasbeenappliedduringmanufacturetoensurethereliableoperationofthisproduct.howevertherearevariousexternalfactorsthatmayimpedeorrestricttheoperationofthisproductinaccordancewiththeproduct’sspecification.
Thesefactorsinclude,butarenotlimitedto:
1.erraticorreducedradiorange.Nessradioproductsaresophisticatedlowpowerdevices,howeverthepresenceofin-bandradiosignals,highpowertransmissionsorinterferencecausedbyelectricalappliancessuchaswirelessrouters,cordlessphones,computers,Tvsandotherelectronicdevicesmayreducetherangeperformance.Whilesuchoccurrencesareunusual,theyarepossible.InthiscaseitmaybenecessarytoeitherincreasethephysicalseparationbetweentheNessreceiverandotherdevicesorifpossiblechangetheradiofrequencyorchanneloftheotherdevices.
2.Unauthorisedtampering,physicaldamage,electricalinterruptionssuchasmainsfailure,electricalspikesorlightning.
sPeCIfICatIons
OPeRATINgvOLTAge 10–15vDC
QUIeSCeNTCURReNTDRAW 25mA(withrelayactivated)
ReLAyOUTPUT C.O.contactsrated1A@28vmax.
OPeNCOLLeCTOROUTPUTS
LOWBATT,AUX,PANIC/TAMP,ON/OFFOpenCollector100mA@12v(lowonalarm)
RADIOFReQUeNCy 304Mhz/868Mhzdependingonregion
RADIOTyPe Superhetrodyne
BANDWIDTh(3DB) 300Khz
SeNSITIvITy >-100db
COMPATIBILITy AllNess304Mhz&868Mhztransmitters
MAX.RADIODevICeS 4
DIMeNSIONS 73(h)x73(w)x27(d)mm
WeIghT 73g