Download - motor alta eficiencia
-
No.:
Date: 12-JUN-2015
TECHNICAL PROPOSAL
Three-phase induction motor - Squirrel cage rotor
Customer :
Product line : W22 IEEE-841 NEMA Premium Efficiency Motors
Catalog Number : List Price : $
Notes:
Performed by: Checked:
-
No.:
Date: 12-JUN-2015
DATA SHEETThree-phase induction motor - Squirrel cage rotor
Customer : Product line : W22 IEEE-841 NEMA Premium Efficiency Motors
Frame : 404/5TOutput : 100 HPFrequency : 60 HzPoles : 4Full load speed : 1775Slip : 1.39 %Voltage : 460 VRated current : 111 ALocked rotor current : 722 ALocked rotor current (Il/In) : 6.5No-load current : 38.0 AFull load torque : 404 NmLocked rotor torque : 240 %Breakdown torque : 260 %Design : BInsulation class : FTemperature rise : 80 KLocked rotor time : 13 s (hot)Service factor : 1.25Duty cycle : S1Ambient temperature : -20C - +40CAltitude : 1000Degree of Protection : IP55Approximate weight : 517 kgMoment of inertia : 1.2598 kgmNoise level : 68 dB(A)
D.E. N.D.E. Load Power factor Efficiency (%)Bearings 6316 C3 6314 C3 100% 0.88 95.4Regreasing interval 10000 h 12000 h 75% 0.84 95.0Grease amount 34 g 27 g 50% 0.77 95.0
Notes:
Performed by Checked
-
Percent of rated output (%)
A - E
ffici
ency
(%)
B - P
ower
fact
or
C - Slip
D - C
urrent at 460V (A)
0 10 20 30 40 50 60 70 80 90 100 110 120 130
40
50
60
70
80
90
100
0.4
0.5
0.6
0.7
0.8
0.9
1.0 0.0
1.0
2.0
3.0
4.0
5.0
0
40
80
120
160
A
B
C
D
No.:
Date: 12-JUN-2015
PERFORMANCE CURVES RELATED TO RATED OUTPUTThree-phase induction motor - Squirrel cage rotor
Customer : Product line : W22 IEEE-841 NEMA Premium Efficiency Motors
Frame : 404/5TOutput : 100 HPFrequency : 60 HzFull load speed : 1775Voltage : 460 VRated current : 111 AInsulation class : F
Locked rotor current (Il/In) : 6.5Duty cycle : S1Service factor : 1.25Design : BLocked rotor torque : 240 %Breakdown torque : 260 %
Notes:
Performed by Checked
-
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
A
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
B
0 10 20 30 40 50 60 70 80 90 100Speed related to rated speed (%)
A - T
orqu
e re
late
d to
rate
d to
rque
(C/C
n)
B - Current related to rated current (I/In)
No.:
Date: 12-JUN-2015
CHARACTERISTIC CURVES RELATED TO SPEEDThree-phase induction motor - Squirrel cage rotor
Customer : Product line : W22 IEEE-841 NEMA Premium Efficiency Motors
Frame : 404/5TOutput : 100 HPFrequency : 60 HzFull load speed : 1775Voltage : 460 VRated current : 111 AInsulation class : F
Locked rotor current (Il/In) : 6.5Duty cycle : S1Service factor : 1.25Design : BLocked rotor torque : 240 %Breakdown torque : 260 %
Notes:
Performed by Checked
-
1 2 3 4 5 6 7 8
A
B
C
D
E
F
12-JUN-2015Three-phase induction motorFrame 404/5T - IP55
Notes:
Performed by:
Checked:
Customer: W22 IEEE-841 NEMA Premium Efficiency Motors
2E15.984
J3.937
A19.921
P19.134
AB16.016
2F12.244/13.740
K5.669
B18.386
BA6.625
U2.875
N-W7.250
ES5.708
S0.750
R2.449
depth0.750
D10.000
G1.811
HB5.252
O19.566
HH14.213
HK6.024
H0.810
C39.730
LL10.591
LM11.267
AANPT 3"
d1DUNC 3/4"-10
d2DUNC 3/4"-10
-
L2L1 L3L2L1T1
T6
L3T2 T3
T4 T5
T1
T6
T2 T3
T4 T5
RUN ONLY FOR START
1 2 3 4 5 6 7 8
A
B
C
D
E
F
12-JUN-2015Three-phase induction motorFrame 404/5T - IP55
Notes:
Performed by:
Checked:
Customer: W22 IEEE-841 NEMA Premium Efficiency Motors