BFR3000-NNA1
Real Time Automation Gateways
Modbus Router
Modbus RTU Master to Modbus TCP/IP Client The router becomes a shared block of Modbus registers and coils. Either protocol is able to read or write values to and from the shared block of data.
Modbus RTU Slaves to Modbus TCP/IP Client Modbus RTU slaves are presented as Modbus TCP/IP servers. Requests sent to a Modbus TCP/IP node ID will be routed to the matching slave ID on the Modbus RTU network.
Modbus TCP/IP Servers to Modbus RTU Master Modbus TCP/IP servers are presented as Modbus RTU slaves. Define the IP address and unit ID’s of your Modbus server devices in the router. Then define what slave ID they will be mapped to.
• Easily Connect
your Modbus TCP/
IP, RTU and ASCII
Devices
• Simple, Browser-
Based
Configuration
• UL & CE
• Supports Both
RTU and ASCII
Encoding
• Ability to Save
Configurations for
Backup or
Loading Multiple
Units
• Support For All
Modbus Function
Codes
• Amazing
Diagnostics
Screens and
Troubleshooting
Tools.
• SD Card Auto
Replacement
Backup
Contact Us! 1-800-249-1612
www.rtaautomation.com
A Solution, A Philosophy, the RTA Way. We understand the long hours
spent on a factory floor and the pressure to keep a line running and product flowing. That’s how Real Time Automation came to be. You want easy-to-use solutions where the hardest part is to open the box. You need customer support second to none. If you get all that and a fun customer experience, all the better. Thirty years later, our mission remains the same: to move your data where you need it, when you need it and how you need it.
Why Use RTA as Your Gateway Supplier?
The BFR3000 provides the simplest solution to connect serial and Ethernet Modbus devices. While there are certainly a number of other companies offering stand alone routers, there is no one who provides the level of support and service that you receive from RTA.
When you call, a live person answers the phone. When you talk with sales, you will get honest answers and recommendations even if that means recommending someone else's solution. When you get support, it is from an engineer who had a hand in the product’s development, and support doesn't require a ticket or 24 hour wait. We are unashamed of the fact that we are a smaller company because that means you mean a lot more to us.
Try the RTA difference today! Call us at 800-249-1612 or check out our solutions at www.rtaautomation.com.
You have just found the easiest way to move Modbus registers and coils between Modbus TCP/IP and Modbus RTU Network devices. The BFR3000 offers transparent data transfer between Modbus devices and controllers on different physical layers. The BFR3000 also has three operating modes making it your go-to device for moving data between Modbus networks.
Allen-Bradley, ControlLogix, CompactLogix, PLC-5 are registered trademarks of Rockwell Automation, Inc.
FEATURES
Configuration Mechanism Web Based Browser Configuration
Baud Rates Supported 110,300,600,1200,2400,4800,9600,14400,19200,28800,38400,56000,57600,62500,76800,115200
Physical Connections RS232, RS485, Ethernet
Modbus Variations Supported TCP/IP, RTU, ASCII
Modbus TCP Client / Modbus RTU Master Operating Mode
External Master Can Read / Write up to 64K Registers and 64K Coils In BFR3000 using RTU or ASCII Encoding
External Client (s) Can Read / Write up to 64K Registers and 64K Coils in BFR3000
Maximum Number TCP Client Connections 5
Function Codes Supported 1,2,3,4,5,6,15,16
Modbus TCP Client / Modbus RTU Slave Operating Mode
Number External Modbus TCP Clients Supported 5
Mapping Unit ID Field in the Client Modbus TCP Message becomes Modbus RTU Slave Address on the Modbus Network
Number of Modbus RTU Slaves Supported 255
Function Codes Supported All
Modbus RTU Master / Modbus TCP Server Operating Mode
Number External Modbus RTU Masters Supported 1
Mapping User Configurable Mapping Table translates RTU Slave ID to Modbus TCP Address/Unit ID Field
Number of Modbus TCP Servers Supported 255
Function Codes Supported All
CATALOG # DESCRIPTION
BFR3000-NNA1 Modbus TCP / Modbus RTU Router
NOT EXACTLY WHAT YOU WERE LOOKING FOR?
Real Time Automation offers a robust line of turnkey gateways and custom gateway products accommodating unique needs or proprietary protocols. Contact RTA’s solutions team at 800-249-1612 or visit www.rtaautomation.com/products.
DIMENSIONS
INCLUDED WITH GATEWAY
Complete, Unlimited Access to RTA’s Industry Leading Support Staff
Manual
CAT5 crossover cable for direct connection to PC during programming
5-Year Hardware Warranty
IPSetup software automatically locates the Gateway on your network
Unlimited Firmware Feature Upgrades for Life
ELECTRICAL/ENVIRONMENTAL
DC Input Voltage 8 V @ 230 mA to 28 V @ 80 mA
Maximum Baud Rate 115K Baud
Operating Temperature -40 C to 85 C
Certification RoHS-Compliant, UL, CUL, CE Approvals
ENCLOSURE / HARDWARE
Size 3.88” x 2.57”x 1.06”
Weight 5.5 oz.
Enclosure Type Anodized Aluminum
Mounting Din Rail
LEDs Power LED & 2 general purpose LEDS on side
Real Time Automation, Inc. - [email protected] - 1-800-249-1612