Mitsubishi Integrated Compact Substation
MICSAdvantagesMinimum
Land Space
● Compactness● Reduction of S/S Area
ShortDelivery
● Standard Specification, Design, Maintenance & Test
● Pre-fabricated & Tested in the Factory
● Skid-mounted & Minimum Shipping Split
MinimumConstruction
Cost (Civil, Erection & Test)
● Reduction of S/S Area● Pre-fabricated & Tested
in the Factory● Skid-mounted & Minimum
Shipping Split
HighReliability
● Proven Equipment● Pre-fabricated & Tested
in the Factory● Gas Insulation Technology
MICS is an integrated compact substation incorporating all the substation equipment which are directly connected with each other and mounted on steel skid-bases. Compact substation can be constructed in a shorter period and will assure lower construction cost while maintaining the same high reliability as the conventional scheme.Digital controlled GIS, MV-Switchgear as well as digital protection equipment are adopted to realize this compact substation.Because it is skid-mounted and pre-fabricated in the factory, site work is limited to the interconnection between the skid-base units. Therefore, the high reliability built in the factory can be maintained.
MICS is an integrated compact substation incorporating all the substation equipment which are directly connected with each other and mounted on steel skid-bases. Compact substation can be constructed in a shorter period and will assure lower construction cost while maintaining the same high reliability as the conventional scheme.Digital controlled GIS, MV-Switchgear as well as digital protection equipment are adopted to realize this compact substation.Because it is skid-mounted and pre-fabricated in the factory, site work is limited to the interconnection between the skid-base units. Therefore, the high reliability built in the factory can be maintained.
PRE-FABRICATED AND SKID-MOUNTED COMPACT SUBSTATION
MICSProtection & Control System Power Transformer
MV Switchgear
HV Switchgear (GIS)
Protection PanelData Acquisition and Control Panel
Remote IO Panel
SUBSTATION SPACE SAVINGSUBSTATION SPACE SAVING
ONE-LINE DIAGRAM & LAYOUTONE-LINE DIAGRAM & LAYOUTSTANDARD ONE-LINE DIAGRAMS
GIB CONNECTION AIR CONNECTION
AIS (100%) MICSAIR CONNECTION(30%)
GIB CONNECTION(20%)
HV SwitchyardLine No.1 Line No.2
Protection & Control Panel,MV Switchgear Building
TRNo.1
TRNo.2
Protection & Control
MV SwitchgearHV Switchgear(GIS)
HV Switchgear(GIS) Protection & Control
MV Switchgear
TRNo.1
TRNo.2
TRNo.1
TRNo.2
HV Switchgear
TR
MV Switchgear
Specifications subject to change without notice.I-0336-A Printed in Japan (MDOC)
HEAD OFFICE: MITSUBISHI DENKI BLDG., MARUNOUCHI, TOKYO 100-8310. TELEX: J24532 CABLE: MELCO TOKYO( Internet : http://www.melco.co.jp, E-mail to:[email protected] )
Global Network of Transmission & Distribution Systems
For further information, please contact Mitsubishi Electric Corp. Transmission & Distribution, Transportation Systems Center,Amagasaki, Hyogo, Japan 661-8661 Telephone:+81(6)6497-8115 Facsimile : +81(6)6497-9338
Country/Area Address
ArgentinaAustraliaBrazilChina
EgyptHongKongKuwait
Saudi ArabiaSingaporeU.A.E.U.K.
U.S.A.
Melco Argentina, S.A. Florida 890-20-Piso, Buenos Aires, ArgentinaMitsubishi Electric Australia Pty. Ltd. 348 Victoria Road, Rydalmere, N.S.W. 2116, AustraliaMELCO-TEC Rep. Com. e Assessoria Technica Ltda. Av.Rio Branco,123,S/1507 Rio de Janeiro, RJ CEP 20040-005,BrazilMitsubishi Electric (H.K.)Ltd. Beijing Office Room No. 1502, Building A, Pacific Century Place, A-2 Worker's Stadium, Road North, Chaoyang District, Beijing, ChinaMitsubishi Electric (H.K.)Ltd. Shanghai Office 39th, Floor, Shanghai Senmao International Building 101 Yin Cheng East Road, Pudong New Area, Shanghai, ChinaMitsubishi Electric Europe B.V. Egypt Branch 4D El Gezira Street, 8th Floor, Zamalek, Cairo, EgyptMitsubishi Electric (H.K.)Ltd. 41st Floor, Manulife Tower, 169 Electric Road, North Point, HongKongMitsubishi Electric Corp. Kuwait Office Al-Wataniya Building, 1st Floor, Salem, Al-Mubarak Street, Salmiya, Kuwait P.O.Box 2707, Salmiya 22028, Salmia, KuwaitMitsubishi Electric Saudi Ltd. P.O.Box 2391, Riyadh 11451, Saudi ArabiaMitsubishi Electric Asia Pte, Ltd. 307 Alexandra Road #05-01/02, Mitsubishi Electric Building, Singapore 0315Mitsubishi Electric Corp. Dubai Branch P.O. Box 1554, Deira, Dubai, U.A.E.Mitsubishi Electric Europe B.V. Project Engineering Div. 15th Floor, Leon House, 233 High Street, Croydon, Surrey, CRO 9XT, England, U.K.Mitsubishi Electric Power Products, Inc. 512 Keystone Drive, Warrendale, Pennsylvania 15086, U.S.A.
Telephone
+54(1)311-4801+61(2)9684-7777+55(21)221-8343
+86(10)6539-2161
+86(21)6842-0606+20(2)737-0784+852(2510)0555
+965(574)7494+966(1)477-7947+65(473)2308+971(4)827763
+44(208)686-9551+1(724)772-2555
Ratings (Based on IEC Standard)
HV
Rated voltage
Rated current
Rated short-time withstand current
Rated short-duration power-frequency withstand voltage
Rated lightning impulse withstand voltageRated insulation level
72.5
140
325
100
185
450
20/25/31.5 20/25/31.5/40 (50/63)
1000/1250/1600/2000/2500/3150
(kV)
(A)
(kA)
(kV)
(kV,peak)
TRRated capacity
Inpedance
Type of cooling
10 to 30 (60)
10 to 15
OFAF
(MVA)
(%)
123
230
550
145
275
650
MV
Rated voltage
Rated current
Rated short-time withstand current
Rated short-duration power-frequency withstand voltage
Rated lightning impulse withstand voltageRated insulation level
12
28
75
24
630/1250/2000
50
125
25
(kV)
(A)
(kA)
(kV)
(kV,peak)
36
25/31.5
70
170
Ratings (Based on ANSI/IEEE Standard)
HV
Rated voltage
Rated current
Rated short-time withstand current
Low frequency withstand voltage
Rated BILRated insulation level
72.5
20/25/31.5
160
350
123
2000/2500/3150
215
550
20/25/31.5/40 (50/63)
(kV)
(A)
(kA)
(kV)
(kV,peak)
145
310
650
MV
Rated voltage
Rated current
Rated short-time withstand current
Low frequency withstand voltage
Rated BILRated insulation level
15
36
95
25.8
630/1250/2000
60
150
25
(kV)
(A)
(kA)
(kV)
(kV,peak)
38
25/31.5
80
200
TRRated capacity
Inpedance
Type of cooling
10 to 30 (60)
10 to 15
FOA
(MVA)
(%)
( ): Option