Magtech Electromagnetic Flowmeter Troubleshooting Guide
1. First of all, check the flowmeter indicator whether SYS alarmappeared. If appeared, pleasecheck the sensor that side junction box termination whether the terminal is affected by water ormoisture.If none of the alarm symbol appear on flow indicator, kindly proceeds to GUIDE 2.
GUIDE 2
First, run the pump to fully filled the pipeline with the medium and also ensure that theflowmeter section is fully filled with medium as well.
After the pipeline fully filled, stop the pump and let the medium static in the pipeline forabout 3 minute which mean no flow movement within the pipeline.
After about 3minutes, goto flowmeter indicator to perform zero calibration by following thesteps on the next page:
-
7/25/2019 Magtech Electromagnetic Flowmeter-zeroing
2/2
Main PV
Flow + Totalizer
Password
00000
Password
03210
+ Shift positionor +
or Edit value
Set the password to 03210
+
Language.
.
.
.
Flow Rspns
Flow Direct
Flow Zero
Parameters Set
-Proceed to parameter Flow Zero
or
Previous parameter
Next parameter
Enter into Flow Zero setting
FS=XXXXX
0000
*Edit the value 00000 until you observe the value of FS become 0,
then ENTER and Save the setting.
+ Shift positionor +
or Edit value
Flow Cutoff
Press & hold 5sec till exit to main PV page
Enter & save
Electromagnetic Flowmeter Setting Procedure
+