Presentation,description 1
Zelio Control-modular measurement and control relays 1
Level control relays RM35 L
Presentation Level control relays RM35 LM33MW and RM35 LV14MW control one or two levels,
with fill or empty function:
RM35 LM33MW: control by resistive level probe,
RM35 LV14MW: control by discrete sensor.
Settings are protected by a sealable cover.
Control status is indicated by a LED.
The relays are designed for clip-on mounting on ! rail
Applications
These devices monitor the levels of conductive liquid or non-conductive material.
They control the actuation of pumps or valves to regulate levels. They are also
suitable for protecting submersible pumps against dry running, or protecting tanks
from "overflow". They can also be used to control dosing of liquids in mixing
processes and to protect heating elements in the event of non immersion.
They have a transparent, hinged cover on their front panel to avoid any accidental
alteration of the settings. This cover can be directly sealed.
Application examples for RM35 LM33MW:
" spring, town, industrial and sea water,
" metallic salt, acid or base solutions,
" liquid fertilizers,
" non concentrated alcohol (< 40 %),
" liquids in the food-processing industry: milk, beer, coffee, etc.
Application examples for RM35 LV14MW:
" chemically pure water,
" fuels, liquid gasses (inflammable),
" oil, concentrated alcohol (> 40 %),
" ethylene, glycol, paraffin, varnish and paints.
DescriptionRM35 LM33MW
1 Configuration: selection of operating
mode: / and of sensitivity
range. LS, St, HS.
2 Sensitivity adjustment potentiometer. %
3 Switch for selecting the number of levels.
4 Time delay adjustment potentiometer. Tt
5 Spring for clip-on mounting on 35 mm
! rail.
RM35 LV14MW
1 Configuration: selection of operating
mode: / and of sensor type
PNP, NPN.
2 Time delay adjustment potentiometer. Tt
3 Switch for selecting the number of levels.
4 Spring for clip-on mounting on 35 mm
! rail.
Tt Yellow LED: indicates timing status.
Un Green LED: indicates that supply to the relay is on.
R Yellow LED: indicates relay output state.
RM35 L MW
105
68
5
A1
12 22 21 2411 14
A2 Min Max C
Tt
Un
R
5
1
2
34
12V
A1 12 11 14A2
12V Min Max 0V
Tt
Un
R
4
1
2
3
Operation:pages 53 to 55
Characteristics:pages 56 and 57
References, dimensions :page 57
53
Operation 1 Zelio Control-modular measurement and control relays 1
Level control relays RM35 L
Operating principleControl relays RM35 LM and RM35 LV are designed to control levels of:
Conductive liquid for RM35 LM,
Any other material for RM35 LV.
Relay RM35 LM measures the levels by means of resistive probes.
Relay RM35 LM controls the levels of conductive liquids.
The operating principle is based on measurement of the apparent resistance of the
liquid between two submerged probes. When this value is less than the threshold
setting on the front panel of the device, the relay changes state. To avoid electrolytic
phenomena, an a.c. current runs across the probes. A selector switch on the front
panel allows selection of the required function and sensitivity range. Control of one
single level can be achieved by using the 2nd selector switch.
In this case, the Max level probe stays up in the air and an adjustable time delay
avoids any wave effect.
Relay RM35 LV measures the levels by means of discrete sensors.
These two products activate their output relay when a tank is either emptying or
filling.
A green LED indicates that the supply is ON.
A yellow LED indicates the state of the output relay.
A yellow LED indicates that timing is in progress.
The green and yellow LEDs flash to indicate an unacceptable setting position.
Level control relay: RM35 LM33MW
Configuration
A selector switch on the front panel allows selection of the required sensitivity range
and of the empty or fill function.
A second switch allows selection of the number of levels (1 or 2) and the type of time
delay in the case of 1 level mode.
The configuration of these switches is taken into account on energisation.
If the switch is set to an unacceptable position, the product detects a fault, the output
relay stays open and the LEDs flash to signal the position error.
If the switch position is changed while the device is operating, all the LEDs flash, but
the product continues to operate normally with the function selected at the time of
energisation preceding the change of position.
The LED's return to their normal state if the switch is returned to the original position
selected prior to the last energisation.
Function diagram
Control of two levels
Fill/Empty function ! empty function
level: 2, function:
- LS (Low Sensitivity: 250 Ω…5 kΩ),
- St (Standard Sensitivity: 5 kΩ…100 kΩ),
- HS (High Sensitivity: 50 kΩ…1 MΩ).
The output relay stays open until the liquid reaches the Max. level probe. As soon
as the Max. level is reached, the contact closes and then allows emptying of the tank
(valve opens, pump starts, ...). When the level drops below the Min. level, the
contact opens to stop the emptying process.
Note: When two levels are controlled, the anti-wave time delay function is not active.
! fill function
level: 2, function:
- LS (Low Sensitivity: 250 Ω…5 kΩ),
- St (Standard Sensitivity: 5 kΩ…100 kΩ),
- HS (High Sensitivity: 50 kΩ…1 MΩ).
The output relay stays energised until the liquid reaches the Max. level probe. As
soon as the Max. level is reached, the contact opens and the pump stops. When the
level drops below the Min. level, the contact closes again and pumping re-starts to
raise the level.
Note: When two levels are controlled, the anti-wave time delay function is not active.
11-12/11-1421-22/21-24
11-12/11-1421-22/21-24
Supply Un
Relays
Relays
Max. level
Min. level
Presentation, description :page 52
Characteristics:pages 56 and 57
References, dimensions :page 57
54
Operation (continued) 1 Zelio Control-modular measurement and control relays 1
Level control relays RM35 L
Level control relay: RM35 LM33MW (continued)
Configuration (continued)
Function diagrams
Control of one level, empty function
Empty function T on ! level: 1 - on delay functions:
- LS (Low Sensitivity: 250 Ω…5 kΩ),
- St (Standard Sensitivity: 5 kΩ…100 kΩ),
- HS (High Sensitivity: 50 kΩ…1 MΩ).
When the liquid level rises above the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
liquid level drops back down to the probe.
If the liquid drops back down to below the set level before the end of the time delay,
the relay does not energise.
Empty function T off ! level: 1 - off delay functions:
- LS (Low Sensitivity: 250 Ω…5 kΩ),
- St (Standard Sensitivity: 5 kΩ…100 kΩ),
- HS (High Sensitivity: 50 kΩ…1 MΩ).
When the liquid level rises above the probe, the relay instantly energises and stays
energised until the liquid again reaches the probe level for a time Tt set on the front
panel.
If the liquid drops back down to below the set level before the end of the time delay
period, the relay stays energised.
Control of one level, fill function
Fill function T on ! level: 1 - on delay functions:
- LS (Low Sensitivity: 250 Ω…5 kΩ),
- St (Standard Sensitivity: 5 kΩ…100 kΩ),
- HS (High Sensitivity: 50 kΩ…1 MΩ).
When the liquid level drops below the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
liquid level rises back up to the probe.
If the liquid rises back up to above the set level before the end of the time delay
period, the relay does not energise.
Fill function T off ! level: 1 - off delay functions:
- LS (Low Sensitivity: 250 Ω…5 kΩ),
- St (Standard Sensitivity: 5 kΩ…100 kΩ),
- HS (High Sensitivity: 50 kΩ…1 MΩ).
When the liquid level drops below the probe, the relay instantly energises and stays
energised until the liquid level again reaches the probe level and stays above it for
a time greater than the time delay period Tt set on the front panel.
If the liquid drops back down to below the set level before the end of the time delay
period, the relay stays energised.
11-12/11-1421-22/21-24
Tt Tt Tt
Supply Un
Relays
Level
11-12/11-1421-22/21-24
Tt Tt Tt Tt
Supply Un
Relays
Level
11-12/11-1421-22/21-24
Tt Tt Tt
Supply Un
Relays
Level
11-12/11-1421-22/21-24
Tt Tt Tt
Supply Un
Relays
Level
Presentation, description :page 52
Characteristics:pages 56 and 57
References, dimensions :page 57
55
Operation (continued) 1 Zelio Control-modular measurement and control relays 1
Level control relays RM35 L
Level control relay: RM35 LV14MW
Configuration
A selector switch on the front panel allows selection of the function (empty or fill) and
the type of sensor.
A second switch allows selection of the number of levels (1 or 2) and the type of time
delay in the case of 1 level mode.
The configuration of these switches is taken into account on energisation.
If the switch is set to an unacceptable position, the product detects a fault, the output
relay stays open and the LEDs flash to signal the position error.
If the switch position is changed while the device is operating, all the LEDs flash, but
the product continues to operate normally with the function selected at the time of
energisation preceding the change of position.
The LED's return to their normal state if the switch is returned to the original position
selected prior to the last energisation.
Function diagram
Control of two levels
!Fill/Empty function empty function. Level: 2
The output relay stays open until the material level reaches the Max. probe. As soon
as the Max. level is reached, the contact closes and then allows emptying of the tank
(valve opens, pump starts, ...). When the level drops below the Min. probe, the
contact opens to stop the emptying process.
fill function. Level: 2
The output relay stays energised until the material level reaches the Max. probe. As
soon as the Max. level is reached, the contact opens and the pump stops. When the
level drops below the Min. probe, the contact closes again and pumping re-starts to
raise the level.
Note: When two levels are controlled, the anti-wave time delay function is not active.
Function diagrams
Control of one level, empty function
!Empty function T on level: 1 - on delay
When the material level rises above the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
material level drops back down to the probe.
If the level rises above the probe before the end of the time delay period, the relay
does not energise.
!Empty function T off level: 1 - off delay
When the material level rises above the probe, the relay instantly energises and
stays energised until the material level again reaches the probe and stays below it
for a time greater than the time delay value Tt set on the front panel.
If the level drops back down to below the probe before the end of the time delay
period, the relay stays energised.
!Fill function T on
Control of one level, fill function
level: 1 - on delay
When the material level drops below the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
material level again reaches the probe.
If the level rises above the probe before the end of the time delay period, the relay
does not energise.
Fill function T off level: 1 - off delay
When the material level drops below the probe, the relay instantly energises and
stays energised until the material level again reaches the probe and stays above it
for a time greater than the time delay period Tt set on the front panel.
If the level drops back down to below the probe before the end of the time delay
period, the relay stays energised.
11-12/11-14
11-12/11-14
Supply Un
Relays
Relays
Max. level
Min. level
11-12/11-14
Tt Tt Tt
Supply Un
Relays
Level
11-12/11-14
Tt Tt Tt Tt
Supply Un
Relays
Level
11-12/11-14
Tt Tt Tt
Supply Un
Relays
Level
11-12/11-14
Tt Tt Tt
Supply Un
Relays
Level
Presentation, description :page 52
Characteristics:pages 56 and 57
References, dimensions :page 57
56
Characteristics 1 Zelio Control-modular measurement and control relays 1
Level control relays RM35 L
Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6
Product certifications Pending UL, CSA, GL, C-Tick, GOST
Marking : 73/23/EEC and EMC 89/336/EEC
Ambient air temperature around the device
Storage °C - 40…+ 70
Operation °C - 20…+ 50
Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)
Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 Hz
Shock resistance Conforming to IEC 60068-2-6 5 gn
Degree of protectionConforming to IEC 60529
Casing IP 30
Terminals IP 20
Degree of pollution Conforming to IEC 60664-1 3
Overvoltage category Conforming to IEC 60664-1 III
Insulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, 500 V
Rated insulation voltage Conforming to IEC 60664-1 V 250
Insulation test voltageConforming to IEC 60664-1/60255-5
Dielectric test kV 2,! 50 Hz, 1 min.
Shock wave kV 4 (1.2/50 µs)
ConnectionMaximum c.s.a.Conforming to IEC 60947-1
Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)
Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)
Tightening torque Conforming to IEC 60947-1 0.6…1N.m / 5.3…8.8 Lbf.In
Housing material Self-extinguishing plastic
Power ON indicator Green LED
Relay state indicator Yellow LED
Timing indicator Yellow LED
Mounting positionwithout derating
In relation to normal vertical mounting plane
Any position
Mounting Conforming to IEC/EN 60715 On" rail
Supply characteristicsSupply voltage Un V !/ 24…240
Operating range V !/ 20.4…264
Voltage limits Of the power supply circuit - 15 %, + 10 %
Frequency Of the power supply circuit 50/60 Hz ± 10 %
Galvanic isolation, supply/measurement Yes
Maximum power consumption at Un VA !#5
W 1.5
Immunity to microbreaks ms ! 90, 100
Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 2002 / IEC 61000-6-2
Emission NF EN 61000-6-4NF EN 61000-6-3 IEC 61000-6-4IEC 61000-6-3
Measurement circuit and input characteristicsRelay type RM35 LM33MW RM35 LV14MW
Measurement range 250 Ω…1 MΩ –
Sub-measurement range LS 250 Ω…5 kΩ –
St 5 kΩ…100 kΩ –
HS 50 kΩ…1 MΩ –
Sensitivity adjustment 5…100 % of the range –
Setting accuracy ± 10 % of the full scale / ± 20 % for the HS range
Measurement error with temperature variation 0.5 % / °C
Maximum voltage at the probe terminals V 12
Maximum current across the probes mA < 1 40
Maximum probe cable length m 100 100
Maximum capacity of probe cable nF 1 for LS, 2.2 for St and 4.7 pour HS 10
Delay on pick-up ms 600 500
Presentation, description :page 52
Operation:pages 53 to 55
References, dimensions :page 57
57
Characteristics (continued)
references,dimensions,schemes 1
Zelio Control-modular measurement and control relays 1
Level control relays RM35 L
Time delay characteristicsRelay type RM35 LM33MW RM35 LV14MW
Time delay on crossing the threshold s 0.1…5, 0 + 10 %
Repeat accuracy (with constant parameters) ± 2 %
Reset time s 1.75 4 if 1 line broken / 1 if 2 lines broken
Output characteristicsType of output 2 C/O contacts 1 C/O contact
Contact type Cadmium-free
Nominal current A 5
Maximum switching voltage V /! 250
Rated breaking capacity VA 1250
Minimum breaking current mA 10/ ! 5 V
Maximum breaking current A /! 5
Electrical durability 1 x 105 operating cycles
Mechanical durability 30 x 106 operating cycles
Maximum operating rate 360 operations/hour under full load
Utilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13
ReferencesFunction Supply
voltageOutput Reference Weight
V kg
Detection by resistive probes(see page 58)
/! 24…240 2 C/O5 A
RM35 LM33MW 0.130
Detection by discrete sensors(see page 60)
/! 24…240 1 C/O5 A
RM35 LV14MW 0.130
Dimensions SchemesRM35 LM33MW, RM35 LV14MW RM35 LM33MW RM35 LV14MW
mm/In.
RM35 LM33MW RM35 LV14MW
10
56
85
10
56
86
/0
954
.3
35/1.38
2,8
0.1
1
76/2.99
72,5/2.85
72/2.83
1112 14 22 21 24
21
11
12
14
24
22
A1 A2 CMin Max
A1
A2
1112 14
11
12
14
A1 A2
0VMin Max12VNC 12V
A1
A2
Presentation, description :page 52
Operation:pages 53 to 55
Characteristics:pages 56 and 57
58
References 1 Zelio Control-modular measurement and control relays 1
Electrode holders and probes
ProbesApplication No.
of probes
Length Opera-ting temper-ature
Maximum pressure
Reference Weight
mm °C kg/cm2 kg
Recommendedfor drinks vending machines and where installation space is limited(Stainless steel)
3 1000 80 2 RM 79 696 044 0.800
Suitable for boilers, pressure vessels and under high temperature conditions (1)(304 stainless steel)
1 1000 200 25 RM 79 696 014 0.360
Description Material Reference Weightkg
Protected probefor mounting by suspension
Protective shellPUC (S7)Electrode : stainless steel
RM 79 696 043 0.150
Description Type ofinstallation
Maximum operating temperature
Reference Weight
°C kg
Liquid levelcontrol probe
Suspended by cable
100 LA9 RM201 0.100
Electrode holdersDescription Material Reference Weight
kg
Electrode for use up to 350 °Cand 15 kg/cm2 (2)
Stainless steel isolated by ceramic
RM 79 696 006 0.150
(1) 3/8" BSP mounting thread with hexagonal head. Use a 24 mm spanner for tightening.(2) 3/8" BSP mounting thread.
RM 79 696 043
56
10
34
LA9 RM201
RM 79 696 006
56
10
35
56
10
36
Dimensions :page 59
59
Dimensions 1 Zelio Control-modular measurement and control relays 1
Electrode holders and probes
ProbesRM 79 696 044
38,5
32
7
3
14
26
Ø 27,5
Ø 1112
11
100
PF 1/2
RM 79 696 014
60
Ø6
1000 60
G 3/8A
RM 79 696 043
Ø 2
5
80
LA9 RM201
150
16
Electrode holderRM 79 696 006
46 29
84
6,5
49
20,7
13
9,5
Acro
ss f
lats
1/4
wh
it
5/3
2 w
hit
3/8 tapered NPT
References :page 58
60
References 1 Ultrasonic sensors 1
Osisonic®, Optimum and UniversalCylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5d.c. supply, solid-state output
Optimum sensorsSensors Sensing
distance (Sn)m
Function Output Reference Weight
kg
Ø 12 0.05 NO PNP/NPN XX5 12A1KAM8 0.011
0.10 NO NPN XX5 12A2NAM8 0.011
PNP XX5 12A2PAM8 0.011
Ø 18 0.15 NO PNP/NPN XX5 18A1KAM12 0.033
Universal sensorsØ 18 0.50 (adjustable) NO NPN XX5 18A3NAM12 0.033
PNP XX5 18A3PAM12 0.033
Ø 30 1 (adjustable) NO PNP/NPN XX6 30A1KAM12 0.091
NO + NC NPN XX6 30A1NCM12 (1) 0.091
PNP XX6 30A1PCM12 (1) 0.091
8 (adjustable) NO + NC NPN XX6 30A3NCM12 0.110
PNP XX6 30A3PCM12 0.110
AccessoriesTeach mode pushbutton
Teach mode pushbutton For use with sensors
Reference Weightkg
Selection of detection windowInput: M12 female connectorOutput: M12 male connector
XX5 18A3 AM12and XX7 V1A1 AM12
XXZ PB100 0.035
Cabling accessories (4-wire output) (3)
Connectors For use withsensor
Type Reference Weightkg
M8 Ø 12 Connection by in-line IDC
Straight XZ CC8FDM40V 0.010
Elbowed XZ CC8FCM40V 0.010
Connection to solder terminals
Straight XZ CC8FDM40S 0.010
Elbowed XZ CC8FCM40S 0.010
M12 Ø 18, Ø 30 Metalclamping ring
Straight XZ CC12FDM40B 0.020
Elbowed XZ CC12FCM40B 0.020
Plasticclamping ring
Straight XZ CC12FDP40B 0.020
Elbowed XZ CC12FCP40B 0.020
Pre-wired connectors
For use withsensor
Type Lengthm
Reference Weightkg
M8 Ø 12 Straight 2 XZ CP0166L2 0.080
5 XZ CP0166L5 0.180
10 XZ CP0166L10 0.360
Elbowed 2 XZ CP0266L2 0.080
5 XZ CP0266L5 0.180
10 XZ CP0266L10 0.360
M12 Ø 18, Ø 30 Straight 2 XZ CP1141L2 0.090
5 XZ CP1141L5 0.190
10 XZ CP1141L10 0.370
Elbowed 2 XZ CP1241L2 0.090
5 XZ CP1241L5 0.190
10 XZ CP1241L10 0.370
Fixing accessories
Description For use withsensor
Reference Weightkg
Fixing clamps Ø 12 XSZ B112 0.006
Ø 18 XSZ B118 0.010
90° fixing bracket Ø 12 XXZ 12 0.025
Ø 18 XUZ A118 0.038
Ø 30 XXZ 30 0.115
3D fixing kit (2) M12 rod Ø 12, Ø 18 and Ø 30 XUZ 2001 0.050
Support for M12 rod
Ø 12, Ø 18 and Ø 30 XUZ 2003 0.160
Ball-joint mounted fixing bracket
Ø 12 XUZ B2012 0.175
Ø 18 XUZ B2003 0.175
Ø 30 XUZ B2030 0.160
(1) Sensor available with stainless steel 303 case. To order, replace the 1st letter A by the letter S.(2) To obtain a 3D fixing kit, order:
rod support XUZ 2003, M12 rod XUZ 2001 and ball-joint mounted fixing bracket XUZ B20 .(3) For 3-wire cabling accessories, refer to the Global Detection catalogue.
XX5 18A1KAM12
56
64
547
56
45
31
XX6 30A1KAM12XX6 30A3!CM12
XX5 18A3!AM12
53
27
13
564
53
3
XXZ PB100
564
53
0
56
45
34
564
53
5
XSZ B11!
56
45
32
XUZ A118
XUZ 2003
XUZ 2001 B20XUZ
53
25
17
3D fixing kit example
Characteristics:page 61
Dimensions:page 62
Schemes:page 63
XX5 12A1KAM8
XZ CC12FD!40B
XZ CP1041L!
56
45
46
53
22
43
61
Characteristics,setting-up
1
Ultrasonic sensors 1
Osisonic®, Optimum and UniversalCylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5d.c. supply, solid-state output
Sensor type XX5 12A1
XX5 12A2
XX5 18A1
XX5 18A3
XX6 30A1
XX6 30A3
CharacteristicsProduct certifications
Conformity to standards IEC 60947-5-2, UL508 pending and CSA C22-2 n° 14 pending
Connection Connector M8 - 4-pin M8 - 3-pin M12 - 4-pin
Sensing range mm 6.4…51 6.4…102 19…152 51…508 51…991 203…8000
Nominal sensing distance (Sn) m 0.05 0.1 0.15 0.50 1 8
Operating distance mm 6.4…51 Fixed
6.4…102 Fixed
25…152 Fixed
Adjustable using teach mode
Differential travel mm < 0.7 < 0.7 < 0.35 < 2.5 < 2.5 < 12.7
Blind zone (no object must pass through this zone whilst the sensor is operating)
mm 0…6.4 0…6.4 0…19 0…51 0…51 0…203
Transmission frequency kHz 500 300 200 75
Repeat accuracy mm ± 0.7 ± 1.27 ± 0.9 ± 2.54
Overall beam angle (see detection lobe) 11° 10° 8° 6° 10° 16°
Minimum size of object to be detected Cylinder Ø 2.5 mm or flat bar 1 mm wide
Cylinder Ø 1.6 mm
Cylinder Ø 2.5 mm up to a sensing distance of 150 mm
Cylinder Ø 1.6 mm up to a sensing distance of 635 mm
Cylinder Ø 50.8 mm up to a sensing distance of 4732 mm
Degree of protection Conforming to IEC 60529and IEC 60947-5-2
IP 67 IP 65
Storage temperature °C - 40…+ 80
Operating temperature °C - 20…+ 65 0…+ 50 - 20…+ 65 0…+ 60 - 20…+ 60
Materials Case ULTEM® Valox® ULTEM®
Sensing face Epoxy Silicone Epoxy Silicone Epoxy
Vibration resistance To IEC 60068-2-6 Amplitude ± 1 mm (f = 10…55 Hz)
Mechanical shock resistance To IEC 60068-2-27 30 gn, duration 11 ms, in all 3 axes
Resistance to electromagnetic interference
Electrostatic discharges To IEC 61000-4-2 kV 8, level 4
Radiated electromagnetic fields To IEC 61000-4-3 V/m 10, level 3
Fast transients To IEC 61000-4-4 kV 1, level 3
LED indicators Output state Yellow LED, rear
Yellow LED – Yellow LED Yellow LED, rear
Yellow LED, rear
Power on Green LED, rear
Green LED – Green LED – –
Setting-up assistance – – – Dual colour Multicolour LED, rear
Rated supply voltage V ! 12…24 V with protection against reverse polarity
Voltage limits (including ripple) V ! 10…28 V
Current consumption, no-load mA 25 60 40 50
Switching capacity mA < 100 (PNP and NPN) with overload and short-circuit protection
Voltage drop V < 1 (PNP and NPN)
Maximum switching frequency Hz 125 125 80 40 10 2
Delays First-up ms 20 20 350 100 720 800
Response ms 2 3 3 10 20 200
Recovery ms 2 3 3 10 20 200
Deviation angle from 90° of the object to be detected
± 10° ± 10° ± 10° ± 7° ± 7° ± 5°
Setting-up precautionsMinimum mounting distances
Side by side Face to face
e: respect the distances indicated on the detection curves shown on page 63.
e = 4 x Sn max.
ee
References:page 60
Dimensions:page 62
Schemes:page 63
62
Dimensions 1 Ultrasonic sensors 1
Osisonic®, Optimum and UniversalCylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5d.c. supply, solid-state output
DimensionsXX5 12A AM8 XX5 18A1KAM12 XX5 18A3 AM12
XXZ PB100 XX6 30A1KAM12 XX6 30A3 CM12
(1) Cable, length: 152.4 mm.
Accessories
XUZ A118 XXZ 12, XXZ 30
90° fixing bracket (Ø 18) 90° fixing bracket (Ø 12 and Ø 30)
XXZ a b c c1 e H G G1 Ø Ø1
12 35 40 33 18 2 31 18 18 25 13
30 67 65 52 25 3 51 35 33 50 31
XSZ B112, XSZ B118 XUZ 2001 XUZ 2003
Fixing clamps (Ø 12 and Ø 18) M12 rod Support for M12 rod
XSZ a a1 b b1 b2 Ø
B112 21.9 14.5 16 15.5 8.5 12
B118 26 15.7 22.3 20.1 11.5 18
(1) 2 elongated holes Ø 4 x 8.
XUZ B2012 XUZ B2003 XUZ 2030
Ball-joint mounted fixing bracket (Ø 12) Ball-joint mounted fixing bracket (Ø 18) Ball-joint mounted fixing bracket (Ø 30)
M12x1
50
38
65
51
M18x1 M18x1
77,7
43 4,7
63
1614,5
(1) M12x1
20
85
45 20
M30x1,5
117,35
42,164,3
M30x1,5
Ø43,2
2,5 Ø18,2
35
28
1
15
206,5
6,5
=
10
=
16,5
= =
50
a
10Ø5
Ø1
G1 Ø
G
H
c1
c
e
b
4 822,3
(1)
38,3
b
b2
a
3,5
b1
a1
12
65
05
5
13
2
40 23
40
M12
1,9
12
19
53
36
19
19
5,7
22,9
40
33
36
76,5
M4
Ø12,4
67
5,7
22,9
403
3
36
76,5
M4
Ø18,5
67
6
22,9
46,32
4,1
42,2
90,5
M3
81,7
13
Ø30,5
63
Curves,schemes 1
Ultrasonic sensors 1
Osisonic®, Optimum and UniversalCylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5d.c. supply, solid-state output
Detection curvesXX5 12A1KAM8 XX5 12A2 NAM8 XX5 18A1KAM12 XX5 18A3 AM12
XX6 30A1 CM12 XX6 30A3 CM12
Blind zone
Wiring schemesM8 connector
XX5 12A1KAM8 XX5 12A2
4-wire type NO outputs, PNP and NPN 3-wire type NO outputs, NPN NO outputs, PNP
1 (+) 2 PNP output3 (-) 4 NPN output
(-) BU (Blue) (+) BN (Brown)WH (White) BK (Black)
1 (+) 3 (-)4 NPN or PNP output
(-) BU (Blue) (+) BN (Brown)BK (Black)
M12 connector
XX5 18A1KAM12 XX5 18A3
4-wire type NO outputs, PNP and NPN 3-wire type NO outputs, NPN NO outputs, PNP
1 (+) 2 PNP output3 (-) 4 NPN output
(-) BU (Blue) (+) BN (Brown)WH (White) BK (Black)
1 (+) 3 (-)4 NPN or PNP output
(-) BU (Blue) (+) BN (Brown)BK (Black)
XX6 30A1KAM12 XX6 30A CM12
4-wire type NO outputs, PNP and NPN NO + NC outputs, NPN NO + NC outputs, PNP
1 (+) 2 PNP output3 (-) 4 NPN output
(-) BU (Blue) (+) BN (Brown)WH (White) BK (Black)
(-) BU (Blue) (+) BN (Brown)WH (White) BK (Black)
XXZ PB100 (teach mode pushbutton for XX5 18A3 AM12)
1 (+) BN (Brown) 2 WH (White)3 (-) BU (Blue) 4 BK (Black)
0 10 20 30 40 50 60
-20
-30
-10
10
20
30mm
mm cm2 4 6 8 100
10
-10
20
30
-20
-30
mm
100 150 200500mm
40
-40
80
120
-80
-120
mm
65 190 320 445 570mm
0
mm
100
-100
200
300
-200
-300
20 40 60 80 100cm
0
100
-100
200
300
400
-200
-300
-400
mm
2 4 6 8 m0
100
-100
200
300
400
-200
-300
-400
cm
4
3
2
12/WH
3/BU
4/BK
1/BN
NPNPNP
4
1 3 3/BU
4/BK
1/BN
NPN
4/BK
3/BU
1/BN
PNP
3
2
4
1
2/WH
3/BU
4/BK
1/BN
NPNPNP
3
2
4
13/BU
4/BK
1/BN
NPN
4/BK
3/BU
1/BN
PNP
3
2
4
1
2/WH
3/BU
4/BK
1/BN
NPNPNP
3/BU
2/WH 4/BK
1/BN
NPNNC
NO
3/BU
2/WH
4/BK
1/BN
NPN NC
NO
4
41
13
3
4
1
3
2
2
4
1
3
Sensor side
M12 male connector
M12 female connector
OutputXXZ PB100
3/BU
1/BN 1/BN
NO2/WH
4/BK
3/BU
4/BK
XX5 18A3 XXZ PB100