    MA0305E060220

    Before you use, read safety precautions carefully, and use this productproperly. The precautions described in this manual contain importantcontents related with safety; therefore, please follow the instructions

    accordingly. The precautions are composed of DANGER, WARNING andCAUTION.

    There is a danger of occurring electric shock in the input/output terminals so

    please never let your body or conductive substance is touched.

    1. If there is a concern about a serious accident caused by a malfunctionor abnormality of this product, please install an external protection circuit

    and devise a scheme for preventing an accident.

    2. This product does not contain an electric switch or fuse, so the userneeds to install a separate electric switch or fuse externally. (Fuserating: 250V 0.5A)

    3. To prevent defection or malfunction of this product, apply a properpower voltage in accordance with the rating.

    4. To prevent electric shock or malfunction of product, do not supply thepower until the wiring is completed.

    5. Since this product is not designed with explosion-protective structure, do

    not use it any place with flammable or explosive gas.6. Do not decompose, modify, revise or repair this product. This may be a

    cause of malfunction, electric shock or fire.7. Reassemble this product while the power is OFF. Otherwise, it may be a

    cause of malfunction or electric shock.8. If you use the product with methods other than specified by the

    manufacturer, there may be bodily injuries or property damages.9. There is a possibility of occurring electric shock so please use this

    product after installing it onto a panel while it is operating.

    1. The contents of this manual may be changed without prior notification.2. Before using the product you purchased, make sure that it is exactly

    what you ordered.3. Make sure that there is no damage or abnormality of the product during

    the delivery.4. Use this product within the range of the operating ambient temperature,

    0 ~ 50 (When it is closely installed Max 40 ) and ambient humidity,

    35 ~ 85 % RH (No condensation).5. Do not use this product at any place with occurring corrosive (especially

    noxious gas or ammonia) or flammable gas.6. Do not use this product at any place with direct vibration or impact.7. Do not use this product at any place with liquid, oil, medical substances,

    dust, salt or iron contents. (Use at Pollution level 1 or 2)8. Do not polish this product with substances such as alcohol or benzene.

    (Use neutral detergent.)9. Do not use this product at any place with a large inductive difficulty or

    occurring static electricity or magnetic noise.10. Do not use this product at any place with possible thermal accumulation

    due to direct sunlight or heat radiation.11. Install this product at place under 2,000m in altitude.12. When the product gets wet, the inspection is essential because there is

    danger of an electric leakage or fire.13. In case of inputting thermocouple, use a compensating cable. (If using a

    normal wire, there is a possibility of occurring temperature error.)14. For R.T.D input, use a cable which is a lead wire has small resistance

    and resistances of three wires shall be the same. (If the three wireshave different resistances then there will be a temperature error.)

    15. To avoid an effect of inductive noise to input signal cables, use theproduct after separating the input signal cables from power, output andload cables.

    16. Separate an input signal cable from an output signal cable. If separating

    is not possible, please use the input signal cable after shielding it.17. Use non-earth sensor with thermocouple. (In case of using earth sensor,

    there is a possibility of occurring malfunction caused by a short circuit.)18. If there is excessive noise from the power supply, using insulating

    transformer and noise filter is recommended. The noise filter must beattached to a panel which is already connected to a ground and the wirebetween the filter output side and power supply terminal must be shortas possible.

    19. If twisting the power cables closely together then it is effective against

    noise.20. If the alarm functions are not properly set then it will not be output when

    the product is malfunctioning. Therefore, make sure its movements areproperly working before the operation.

    21. Turn the power OFF when replacing a sensor.22. Use an auxiliary relay in case of high frequent operation such as

    proportional operation or etc. its life span will be shorter if connecting aload without permissible rating of output relay. In this case, using SSRoutput type is recommended.

    Using Electromagnetic Switch: Proportional Cycle: set it above 20 sec.Using SSR: Proportional Cycle: set it above 1 sec.Life Span of Contact Point Output: above 10 million times (with no load)Electrical Life Span: 100 thousand times (250 V AC 3 A: with the rated

    load)

    23. Do not connect anything to the unused terminals.24. After checking the polarity of terminal, connect wires at the correct

    position.25. When this product is connected onto a panel, use a circuit breaker or

    switch approved with IEC947-1 or IEC947-3.26. Install a circuit breaker or switch at near place for convenient use.27. Write down on a label that if the circuit breaker or switch is operating

    then the power will be disconnected since the circuit breaker or switch isinstalled.

    28. For the continuous and safe use of this product, the periodicalmaintenance is recommended.

    29. Some parts of this product have limited life span, and others arechanged by their usage.

    30. The warranty period for this product including parts is one year if thisproduct is properly used.

    31. When the power is on, the preparation period of contact output isrequired. In case of using signals of external interlock circuit or etc., useit with a delay relay.

    32. In case of replacing this unit with a spare unit, make sure itscompatibility because its operation can be different by differentparameter settings even though the model name is the same.

    Safety information

    Model Name and Suffix Code

    WARNING

    CAUTION

    DANGER

    HEAD OFFICE

    1381-3, Juan-Dong, Nam-Gu Incheon, Korea

    TEL: (82-32)876-4697 FAX:(82-32)876-4696

    MAIN PRODUCTS- DIGITAL : Temperature Controller, Counter, Timer,Speedmeter,

    Tachometer, Panel Meter, Recorder- SENSOR : Proximity Switch/Photo Electric Sensor,

    Rotary Encoder, Optical Fiber Sensor,Pressure Sensor

    - ANALOG : Timer, Temperature Controller

    Digital Temperatrue Controller

    KX series

    We appreciate you for purchasing HanYoung NUX Co.,Ltdproduct. Before using the product you have purchased,check to make sure that it is exactly what you ordered. Then,please use it following the instructions below.

    INSTRUCTION MANUAL

    CodeModel

    T.C

    RTD

    V DC /mA d.c

    NoteDescription

    KX2 / 3 / 4 / 7 / 9

    [K]-50 ~ 1300 (-50.0 ~ 999.9 )

    [J] -50 ~ 600 (-50.0 ~ 600.0 )

    [R]0 ~1700 (0.0 ~ 999.9 )

    [P] -199 ~ 650 (-199.9~650.0 )

    [D] -199 ~ 650 (-199.9~650 .0 )

    [A] 1 ~ 5 V (4~20 )[B] 0 ~10 V

    RELAY

    SSR

    SCR

    ALM (Selectable in ALH, ALL, LBA Mode)(1 Point)

    ALH, ALL (2Points)

    ALH + ALL+LBA (3Points)

    100 - 240 V AC 50 - 60 Hz

    CA

    IC

    PRR

    DIN Pt100

    KS Pt100(JIS Pt100)

    (-199 ~ 9999)(-199 ~ 9999)

    Only for KX4

    Basic for

    KX2/3/7/9Option for KX4

    Not available for KX4

    KX

    OPTION

    Power VOLTAGE

    INPUT

    OUTPUT

    STANDARD

    SELECTION

    K

    R

    P

    V

    M

    S

    C

    C

    E

    K

    4

    Option Input : E, T, R, B, S, L, N, U, W.

  • 7/28/2019 kx_eng.pdf

    2/4

    Ratings

    Aspect & Panel Cutout Dimension

    Each Parts Name

    Wiring Diagram

    Rated Voltage

    Power Consumption

    Input Sensor

    Display Accuracy

    Setting Accuracy

    Hysteresis

    (ON/OFF Operation)

    Control Output

    Control Operation

    Alarm Output

    Setting Method

    Options

    Operating Ambient

    Temperature/Humidity

    100 - 240 V AC ( 10 %), 50 - 60 Hz

    Below approx. 5 VA

    Thermocouple: K1, K2, J1, J2, E,T, R, B, S, L, N, U, W

    R.T.D: KS Pt100 (JIS Pt100 ), DIN Pt100

    DC Voltage Input: 1 ~ 5 V DC (4 ~ 20 mA), 0 ~ 10 V DC

    Thermocouple: (0.5 % of displayed value + 1digit) or 3

    (higher value among them) But, in case of R, B, L, U input,

    refer to input type & measuring range

    R.T.D: (0.5% of display value + 1digit) or 2

    (higher value among them)

    Same as Display Accuracy

    0.2 ~ 100.0

    Relay Contact Output: 250 V AC 3 A (resistive load) SPDT

    Electrical Life Expectancy: above 30,0000 times (rated load)

    Voltage Pulse Output: 12 V DC (Max. 50 mA)

    Current Output: 4 ~ 20 mA DC (above resistive load 600 )

    ON/OFF or P.I.D (Auto-Tuning Function)

    ALH/ALL/LBA: 250 V AC, 3 A (resistive load)

    KX4 : 250 V AC 1 A

    Relay Contact Life Expectancy: above 50,000 times (rated load)

    Digital Setting by Up/Down KeysLimiting High/Low Limit Setting Function

    Display Unit ( )

    Locking Setting data Function

    Compensating Input Function

    (Correcting Temperature Function)

    Displaying Decimal Point Function

    Direct/Reverse Selection Function

    0 ~ 50 (35 ~ 85 % RH)

    Meausring Value (PV) Indicator (Red)

    Control Loop Break Alarm (LBA)Operation Indicator (Red)

    Low Limit Alarm (ALL)Operation Indicator (Red)

    High Limit Alarm (ALH)Operation Indicator (Red)

    Incrementing SV Key

    Decrementing SV Key

    Shifting SV s digit Key

    SET Key

    Setting Value (SV) Indicator (Red)

    Auto-tuning (AT) Indicator (Red)

    Output Control (OUT) Indicator (Red)

    When using KX4, KX7, keep in mindthey do not have ground terminalNote: SCR OUTPUT : 4 ~ 20 mA DC

    SSR OUTPUT : 12 V DC(Max. 50 mA)

    ALM: Display output of ALH/ALL/LBA

    For KX9

    weight : 352 gunit: mmKX9 (96 96)

    weight : 255 gKX7 (72 72)

    weight : 277 gKX3 (96 48)

    KX7

    KX4

    KX2 / 3 / 9

    weight : 277 gKX2 (48 96)

    weight : 166 gKX4 (48 48)

  • 7/28/2019 kx_eng.pdf

    3/4

    How to Set SV

    When turning the power ON for the first time, Present Temperaturewill be displayed in PV indicator and Setting Temperature will bedisplayed in SV indicator.For example) Putting Setting Temperature = 70 ,

    Present Temperature = 25

    Press key to shift the flickering digit to the digitwhere desired to be set as SV.(In this case, press

    key one time to get the tens digit.)Every time you press key, theflickering digit will be moved likethe right picture.

    Set 7 by pressing key.Pressing key is increasing the flickering digitPressing key is decreasing the flickering digit.Setting Range: Set a negative number within input range

    Ex) when changing 70 to -70 then press key to getthe thousands digit. If you press key at thethousands digit then the flickering digit will bedecreased in order of 1, 0 and -.

    To enter SV Setting Mode, press key.If the least significant digit in SV indicator is flickeringthen you can start to change SV.

    Let , parameter symbol of Proportional Band, bein PV indicator by press key

    Example) Setting 20 in Proportional Band (P)

    Press key for 3 sec. to enter parameter settingmode (other than SV).Parameter symbol will be displayed in PV indicator.At this time, the least significant digit will be flickeringand the flickering digit can be settable.

    Move the position of flickering digit to the tens digitby pressing key.Every time you press key,the flickering digit will be movedlike the right picture.

    Set 2 by pressing key.Pressing key is increasing the flickering digit

    Pressing key is decreasing the flickering digit.

    Press key after the setting ends then it goes tothe next parameter. As following the procedure from2 to 5 , you can set other parameters.

    ON/OFF Control SettingWhen you want to select ON/OFF control, set 0 in Proportional Band( P ) of Normal Setting Mode then ON/OFF control will operate. Atthis time, if you want to give hysteresis width then set hysteresiswidth in HYS parameter of Normal Setting Mode.

    After completing setting other than P.I.D or ARW setting, pleasedo Auto-tuning.Starting Auto-tuning is pressing key and key together.A.T indicator will be flickering and Auto-tuning will start.If you want to stop Auto-tuning during Auto-tuning operation,press key and key together. A.T indicator will bedisappeared and Auto-tuning will be stopped.If you change SV during Auto-tuning Operation then Auto-tuningOperation will be stopped. It will be controlled by P.I.D valuewhich is the value before starting Auto-tuning

    How to Set Each Parameter (Other than SV)

    *After the settings of parameters are finished, press key for more than 5 sec

    then it will return to PV/SV display mode. Also, if you do not use the keys for 1

    minute then it will automatically return to PV/SV display mode.

    After finishing the setting, press key.The digit will not be flickered and the controller willreturn to PV/SV display mode.

    The setting data lock function is used to prevent changing each setting value by

    the front panel keys or activating the auto-tuning function. i.e., after finishing thesetting, the lock function helps to prevent misoperation.

    For Setting Data Lock Function, After letting Loc be in PV indicator by pressing

    key in Parameter Mode(Other than SV), set a number shown in the below.

    The number makes the function ON/OFF.

    0: Cancellation of Setting Data Lock Function

    1: Changeable only SV when Setting Data Lock Function

    2: Lock all setting data

    PV/SV Setting Mode

    When turning the power ON, it will display Measuring Value in PVindicator and Setting Value in SV indicator. Except PV/SV Display orSV Setting Mode, there are Normal Setting Mode and Initial SettingMode which display or set integers.

    *1: SV is a target of control. Setting is possible within the input range.

    Setting Value(SV)

    Measuring Value(PV)

    DescriptionSetting Value

    (SV) Indicator

    Measuring Value

    (PV) Indicator

    Displaying Measuring Value(PV).SV can be set *1

    High Limit

    Alarm (ALH)

    Low Limit

    Alarm (ALL)

    Proportional

    Band (P)

    Anti-rest

    Windup

    (ARW)

    Integral Time

    (I)

    Differential

    Time (D)

    Control LoopBreak

    Alarm (LBA)

    Proportional

    Cycle (C)

    Hysteresis

    (HYS)

    Lock Setting

    Data (LOC)

    PV indicator Description DefaultName

    Displaying SV of High Limit Alarm

    Max range of Input Range

    Displaying SV of Low Limit Alarm

    Min range of Input RangeSetting Proportional

    Band Control 0 : ON/OFF Control

    1 ~ Span or 0.1~Span

    ( 0 or 0.0 : ON/OFF Operation)

    Preventing overshoot/undershoot

    caused by Integral Effect

    1 ~ Span or 0.1 ~ Span

    ( 0 Integral Operation OFF)

    Eliminating offset (residual deviation)

    caused by Proportional Control and

    it makes reaching to a target

    faster.(0: Integral Operation OFF)

    1~3600s ( 0 Integral Operation OFF)

    Preventing ripple by predicting output

    change thereby improving control

    stability ( 0 Differential Operation OFF)

    1~7200 ( 0 LBA OFF) Displaying

    SV of LBA

    1~100s ( 0.0 can not be set)

    Displaying cycle (sec.) of control output

    0.2~100.0 Setting adjusting sensitivityof output control (main output) (whencontrolling ON/OFF)

    ON/OFF Lock Function of Setting Data

    0: Lock OFF Setting Data

    1: Only SV is changeable when

    locking setting data

    2: Lock ON All Setting Data

    20

    20

    240

    60

    480

    20

    1.0

    0

    Press

    Key

    Press Key for 3 seconds

    How to Operate

    Normal Setting Mode

    Description of Each Parameter

    Setting for Each Parameter

    Setting Data Lock function

    Auto-tuning (AT) Function

  • 7/28/2019 kx_eng.pdf

    4/4

    Initial Setting Mode

    Alarm Function

    Deviation

    AlarmS

    etting

    High/Low Limit Alarm

    Band Alarm(Within Range Alarm)

    Each Alarm Operation can be set in the below.( : Setting Value(SV) : Alarm Setting Value)

    Absolute

    AlarmS

    etting

    High/Low Limit Alarm

    Band Alarm(Within Range Alarm)

    High/Low Limit Deviation Alarm will operate when Alarm Setting valueis higher or lower than SV.

    Ex1) If SV=200 , want to operateHigh Limit Alarm(ALH) at 205Low Limit Alarm(ALL) at 190

    Set 5 at ALH (Deviation from SV to ALH = 5 )Set 10 at ALL (Deviation from SV to ALL = 10 )

    Ex2) From Ex1) if SV is changed to 300 thenALH will operate at 305ALL will operate at 290

    In case of increasing PV by a short circuit of input or etc., if the PVexceeds the range of Max Settable Temperature (SL7) then Out ofMax Range Symbol is flickering in PV indicator.In case of decreasing PV, if the PV is lower than the range of MinSettable Temperature(SL8) then Out of Min Range Symbol

    is flickering in PV indicator.

    Note) Absolute High/Low Limit Alarm will operate at set temperature ofALH/ALL regardless SV.

    For the band alarm, the relay of low limit alarm will not operate andonly the relay of high limit alarm will operate in Deviation andAbsolute Alarm setting.

    While pressing + keys, if you turn the power source on thenyou can enter SL1 mode.By pressing key, Setting Item can be changed like the below.

    Not Used

    SV Indicator

    PV IndicatorPV

    indicator

    0 0000

    1 000.0

    2 00.00

    3 0.000

    Applicable in

    Absolute Alarm

    Function

    Default:0

    (Reverse

    Operation)

    Resolution

    0.1

    Display [0000]

    or [1111] of SL1

    in the input

    mode

    Contents

    Decimal Point

    Selection

    (Only available in DC

    voltage/current input)

    Compensating Input

    Value Setting

    High Limit Alarm (ALH)

    hysteresis Setting

    Max Temperature

    Setting

    Min Temperature

    Setting

    Direct/Reverse

    Operation of Control

    Output Selection

    Low Limit Alarm (ALL)

    hysteresis Setting

    Filtering Measuring

    Value Function

    5.000

    1.000

    0 ~ 3

    -100.0 ~ 100.0

    0.2 ~ 100.0

    -199 ~ 2300

    (-199.9 ~ 999.9 )

    -199 ~ 2300

    (-199.9 ~ 999.9 )

    0: Reverse Operation

    1: Direct Operation

    0.2 ~ 100.0

    No display

    Max Input Range Settingwhen inputting DC

    voltage/current

    Min Input Range Settingwhen inputting DC

    voltage/current

    SV indicator

    (Setting Range)Note

    In case of getting out of Initial Setting Mode, turn POWER off and set

    Normal Setting in the inner dip switch.

    Indicator/Controller

    SV Indicator

    PV Indicator

    Celsius ( )

    Deviation Alarm or Absolute Alarm Selection

    SV Indicator

    PV Indicator

    Alarm function Type Selection

    Retransmission Output Selection (Not used)

    Setting Value(SV)

    Deviation Alarm

    Absolute Alarm

    Description

    0

    1

    Alarm Hold Operation Selection

    Setting Value(SV)

    Band (Within Range) Alarm

    High/Low Limit Alarm

    Description

    0

    1

    Setting Value(SV)Retransmission Output

    No Retransmission Output

    Description0

    1

    Setting Value(SV)

    Hold Operation

    No Hold Operation

    Description

    0

    1

    Decimal Point

    Output Selection (Not used)

    Setting Value(SV)

    Decimal point function

    None

    Description

    0

    1

    Setting Value(SV)

    Current output

    Relay or SSR output

    Description

    0

    1

    Setting Value(SV)

    Indicator

    Controller

    Description

    0

    1

    Setting Value(SV) Description

    1

    Output Selection is decided in the SYSTEM MODE when the products areshipped out from the factory so changing output is not possible. If you want tochange output, please inquire of the agency or the head office s A/S.

    The input sensors of this product are composed of the partial multi-inputs of T.C Input (11 types), R.T.D input (3 types) orVoltage/Current (2 types).

    Out of Max/Min Range Symbol

    CAUTION

    CAUTION

    Type Input Type

    Input Type & Range

    Range ( )SLI

    1 (SL2 : X1XX) 1/10 (SL2 : X0XX)

    0001

    0101

    1100

    1101

    0100

    0110

    0111

    1000

    1001

    1010

    1011

    0010

    0011

    0000

    1111

    Thermo

    couple

    (T.C)

    RTD

    V DC/

    mA DC

    K

    J

    E

    T

    R

    B

    S

    L

    N

    U

    W

    D(KPt, JPt)

    P(DPt)

    1~5 V DC / 4~20 mA

    0 ~ 10 V DC

    -50 ~ 1300

    -50 ~ 600

    -199 ~ 999

    -199 ~ 400

    0 ~ 1700

    0 ~ 1800

    0 ~ 1700

    -199 ~ 900

    -199 ~ 1300

    -199 ~ 400

    0 ~ 2300

    -199 ~ 500

    -199 ~ 640

    -199 ~ 9999

    -50 ~ 999.9

    -50.0 ~ 600.0

    -199.9 ~ 999.9

    -199.9 ~ 400.0

    0.0 ~ 999.9

    0.0 ~ 999.9

    0.0 ~ 999.9

    -199.9 ~ 900.0

    -199.9 ~ 999.9

    -199.9 ~ 400.0

    -199.9 ~ 500.0

    -199.9 ~ 640.0

    Use 4 ~ 20 mA Current Input After attaching 250 0.1 % to input signalterminals