Indoor Air Standards in Japan for Healthy Environment
Yoshika SekineSchool of Science, Tokai University, JapanSimon WattsBMS, Oxford Brookes University, UK
![Page 2: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/2.jpg)
2
Do you think ?
* The Last Samurai, Warner Bros.,2003** Sayuri, Columbia Pictures Industry, 2005
SAMURAIGEISHA
*
**
![Page 3: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/3.jpg)
3
Modern Japan
Economic power based on High-tech
Western style buildings
![Page 4: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/4.jpg)
4
Why Japanese companies are so good at making microchips?
M. Cross, New Scientist(1990)“…an important reason for Japan’s domination of the electronics market is that its people have a built-in “clean-room”mentality. It comes from the custom of changing shoes when stepping into another room.”
![Page 5: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/5.jpg)
5
Japanese climateJapanese climate
0
5
10
15
20
25
30
1 2 3 4 5 6 7 8 9 10 11 12Month
Tem
pera
ture
( ℃)
20
30
40
50
60
70
80
Rel
ativ
e hu
mid
ity(%
)
Temp.RH
![Page 6: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/6.jpg)
6
SHOSO-IN Treasure House
An eighth century building specially constructed to prevent the natural damage caused by Japanese damp climate. The raised floor structure ensures sufficient ventilation underneath to keep the inside dry.
![Page 7: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/7.jpg)
7
Raised floor structure in modern house
“Clean Room” mentality
*http://www.misawa.co.jp/kodate/
*
![Page 8: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/8.jpg)
8
“Sick House Syndrome”
“Sick Building Syndrome”Majority of patients: housewives and children in newly-built housesTypical air pollutants- Formaldehyde (HCHO)- Volatile Organic Compounds (VOCs)Why it happened in a house and invited a great social concern?
![Page 9: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/9.jpg)
9
Renewal cycle of house
141
103
86
79
30
0 50 100 150
UK
USA
Fr
Ger
J
Renewal cycle (year)
Renewal cycle= No. of present houses /No. of newly-built houses per year
![Page 10: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/10.jpg)
10
Indoor air pollution by chemicals
Japanesehouse
Chemicalintolerance
Indoor airpollution
Use of chemicals
Large supply of houses
Air-tight
Saving energyAir change rate
< 0.2/h
Volatilization of chemicals
1970s~ 1990s~
![Page 11: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/11.jpg)
11
Case of a victim in Tokyo
Middle aged single womanIn Apr.1999, moving to a newly built apartment house in TokyoHealth disorder- eye mucus, throat pain, bronchus irritation, headache, unpleasant feeling with muscles, diarrhea, fatigue and failure of memoryPart-time librarian of a hospitalIn Mar.2000, diagnosis at hospital- Multiple Chemical Sensitivity
![Page 12: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/12.jpg)
12
Multiple Chemical Sensitivity
Medically unexplained symptom- different from allergy, acute poisoning
Damage on nerve system etc.Repeated and intermittent exposure to chemicals (non-specific structure, property)Cross-sensitization
- drugs, physical or psychological stressIn the case of Sick House Syndrome,most patients have been forced to move to another old house or replace building materials, sometimes at their expense.
![Page 13: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/13.jpg)
13
Efforts of reduction of chemicals(2)炭入り枕
Bamboo charcoal
Pillow filled with charcoal
PlantsAir cleaners
Door with air pathwayPassive sampler
![Page 14: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/14.jpg)
14
Concentration of formaldehyde
1999 2002
guideline
0
0.05
0.1
0.15
0.2
0.25
26 Sep. 7 Oct. 12 Oct.12 Mar. 18 May21 Aug. 15 Oct.
HC
HO
con
c.(
ppm
)
0
5
10
15
20
25
30
Roo
m te
mpe
ratu
re(
℃)
![Page 15: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/15.jpg)
15
Nation-wide survey
Questionnaire study for Japanese 4,000 adults (> age 20) (Uchiyama,2003)Quick Environmental Exposure and Sensitivity Inventory (QEESI)- developed by C. Miller (1998)Results- respondents: 2,851- suspected as chemical sensitivity: 0.74%Underestimate?- children: more sensitive to chemicals
![Page 16: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/16.jpg)
16
Governmental countermeasures
Setting Indoor Air Quality Guidelines of Chemicals (since 1997)Emission control and installation of ventilation system- Standard Building Law, 2003
Monitoring of indoor air concentrations ofchemicals in newly-built houses - Housing Quality Assurance Law , 2002
formaldehyde in buildings and school- Building Sanitation Law,2002
![Page 17: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/17.jpg)
17
Indoor Air Quality Guidelines- Ministry of Health, Labour and Welfare, Japan
date chemicals CAS No. concnetration
1997.6 formaldehyde 50-00-0 100µg/m3(0.08ppm)
2000.6 toluene 108-88-3 260µg/m3(0.07ppm)
xylene 1330-20-7 870µg/m3(0.20ppm)
p -dichlorobenzene 106-46-7 240µg/m3(0.04ppm)
2000.12 ethylbenzene 100-41-4 3800µg/m3(0.88ppm)
styrene 100-42-5 220µg/m3(0.05ppm)
chlorpyriphos 2921-88-2 1µg/m3(0.07ppb)
0.1µg/m3(0.007ppb)for infant
di-n-butylphthalate 84-74-2 220µg/m3(0.02ppm)
TVOC 400µg/m3 *2001.7.5 tetradecane 629-59-4 330µg/m3
(0.04ppm)di-2-ethylhexylphthalate 84-66-2 120µg/m3
(7.6ppb)diazinone 33-41-5 0.29µg/m3
(0.02ppb)nonanal 124-19-6 41µg/m3
(7.0ppb)*2002.1 acetaldehyde 75-07-0 48µg/m3
(0.03ppm)fenobucarb 3766-81-2 33µg/m3
(3.8ppb)( ): coverted at 25 degC, *Draft value
![Page 18: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/18.jpg)
18
Formaldehyde (HCHO)
Emission sourceadhesives used for - plywood, MDF, particle board, - vinyl wall paperIndoor concentrations
Survey for 4,600 housing units in 2000 (by MLIT)- average 0.071ppm- 27.3% of the units
> the guidelinePlywood used for flooring
![Page 19: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/19.jpg)
19
The amended Building Standard Law
Enforced in July, 2003Applied to every habitable room of all buildingsRegulation on Chlorpyrifos- The use of Chlorpyrifos is bannedRegulation of Formaldehyde (HCHO)- Area size of HCHO-emitting materials used for interior finishing is restricted- Installation of 24h-ventilation system is mandatory to keep >0.5 ACH
![Page 20: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/20.jpg)
20
HCHO-emitting materials
Formaldehydeemitting buildingmaterials
Emission rateRestrictions oninterior finishingmaterials
Type 4 up to 5µg/m2h No restrictions
Type 3 5~20µg/m2h Limited area
Type 2 20~120µg/m2h
Type 1 over 120µg/m2h Prohibited
Determined by a small chamber method (JIS A 1901,2003)
![Page 21: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/21.jpg)
21
Housing Quality Assurance Law- Ministry of Land, Infrastructure and Transport
IAQ : One of the housing performanceMeasurement of indoor concentrations included in fields of the Housing Performance Indication SystemBy request of the house purchaser, house builders have to make a monitoring of indoor air conc. of chemicals in a newly-built house.Sampling & analytical methods: Standard protocol prepared by MOHLW
![Page 22: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/22.jpg)
22
Monitoring of Chemicals
Target substances;formaldehydetoluene, xylene, styrene and ethylbenzene
Standard sampling methods1) Active samplings (30min)2) Passive samplings (24h)
Passive samplers are commonly used for IAQ monitoring
Passive samplers
![Page 23: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/23.jpg)
23
IAQ standard for museum
substance limit values frequencyPM 0.15mg/m3
CO2 1000ppmCO 10ppmtemperature 17 - 28℃relative humidity 40 - 70 %air stream 0.5m/s
HCHO 0.1mg/m3in summer afterbeing built, reformedand fitted up
bi-monthly
*HCHO was added in 2002.
![Page 24: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/24.jpg)
24
Yearly change of HCHO conc.
0
0.02
0.04
0.06
0.08
0.1
0.12
2000 2001 2002 2003 2004
Fiscal year
HC
HO
con
c.(p
pm)
0
5
10
15
20
25
30
35
Perc
enta
ge o
fex
ceed
ence
(%)
HCHO conc. exceedence
Indoor air concentrations of HCHO in newly-built houses (n=2,000)
http://www.skkm.org/houkoku/
![Page 25: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/25.jpg)
25
Air-cleaning materials based on “Clean-room” mentality
Air cleaner Air cleaning paint Air cleaning board
![Page 26: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/26.jpg)
26
Removal of airborne chemicalsprinciple methods/materials
physisorption activated charcoalporous ceramics
natural fiberschemisorption inorganic compounds
organic compoundsextracts
decomposition photocatalystozonolysis
catalytic decompositionmodified charcoalplasma discharge
minus ionsactivated oxygen
digestion bacterialblocking resins
![Page 27: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/27.jpg)
27
Passive air cleaning board
H2O+
CO2
HCHO
Pre-filter
MnO2 filterHCHO+2[O]→H2O+CO2
at room temperature
![Page 28: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/28.jpg)
28
Manganese dioxide
0
100
200
300
400
500
600
0 5 10 15 20Time(h)
HC
HO
con
c.(p
pm)
0
100
200
300
400
500
600
Prod
uced
CO
2(pp
m)
(MnO2:10g、PTFE Bag: 100L、21℃)
![Page 29: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/29.jpg)
29
Possible pathways
HCHO(g)+O(a)→ HCHOO(a) ……(1)
H C H O O ( a ) → H C O O ( a ) + H ( a )… … ( 2 )
H C O O ( a ) → C O 2 ( g ) + H ( a )… … ( 3 )
2 H ( a ) + O ( a ) → H 2 O… … ( 4 )
H C H O + 2 O → H 2 O + C O 2
… … ( 5 )Sekine,Y, Atmospheric Environment, 36,5543(2002)
![Page 30: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/30.jpg)
30
Field tests
Bath
Bedroom(b)
Bedroom(a)
Toilet
Kitchen
Living dining roomair-cleaning board total 9.8m2
air sampling site
Closet
N
1.5m2 1.0m2
0.8m2
1.5m2
3.0m2
1.0m2
1.0m2
Japanesestyle room
i Air-cleaning board
i Newly built and unoccupied apartment houses
i 3LDK(230m3)i N=0.15/hi May – Nov., 1998
Sekine,Y, et al. Atmospheric Environment, 35,2001(2001)
![Page 31: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/31.jpg)
31
Variation of HCHO concentrationIn
door
con
cent
ratio
n of
HC
HO
(ppm
)
0 30 60 90 120 150 180 2100.0
0.1
0.2
air conditioner off
house without the board
house with the board
Elapsed time(days)
guideline
![Page 32: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/32.jpg)
32
Air cleaning materials with legal basis
In the Standard Building Law,Exemption from the restrictions for HCHOHabitable room- equipped with centrally controlled air
conditioner- in which the HCHO concentration can be
maintained at no more than 0.1mg/m3
Air-cleaning materials can be used with approval of the Minister of MLIT
![Page 33: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/33.jpg)
33
On-site colorimetric detector of HCHO
Virgin sample
Exposed to HCHO
Put on the surface
HCHOemittingmaterials
Colorimetric reagent
![Page 34: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/34.jpg)
34
User friendly technology
![Page 35: Indoor Air Standards in Japan for Healthy Environment · Indoor Air Standards in Japan for Healthy Environment ... Setting Indoor Air Quality Guidelines of Chemicals ... IAQ : One](https://reader030.vdocuments.us/reader030/viewer/2022013006/5b5125df7f8b9a35278ba26e/html5/thumbnails/35.jpg)
35
Find out Japanese businessman