Kit Contents
Item Qty Description
A 1 Red grommet
B 1 Gland with threaded inserts
C 1 Gland with screws
D 1 Gland gasket
E 1 Locknut
F 1 Green/yellow tube
G 1 CS-100 core sealer
H 1 Terminal block
A
B
C
D
G
H
E
F
DescriptionThe C75-100-A is a NEMA 4X-rated gland kit used to transition heating cables into a junction box when making connections off of a pipe, tank or roof. It may be used for power, splice, or tee connections. The C75-100-A is for use with Raychem® BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT(1), LBTV2-CT(2), VPL-CT industrial parallel heating cables and GM-X and GM-XT roof and gutter de-icing heating cables. The kit does not include the junction box, flexible tubing, or tape, which are required to make a complete connection.For technical support call Tyco Thermal Controls at (800) 545-6258.
Tools Required
• Utilityknife • Needlenosepliers• Wirecutters • Adjustablepliers• No.2Phillipsor1/4in(6mm) • Marker slottedscrewdriver • 3/16in(4mm)orsmaller
• ForLBTV2-CTonly:Heatgun slottedscrewdriver ormini-torch • Wirestripper(forVPL)
Approvals
This component is an electrical device that must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all of the installation instructions.• Tominimizethedangeroffirefromsustained
electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of Tyco Thermal Controls, agency certifications, and the national electrical codes, ground-fault equipment protection must be used. Arcing may not be stopped by conventional circuit breakers.
• Componentapprovalsandperformancearebasedon the use of Tyco Thermal Controls-specified parts only. Do not use substitute parts or vinyl electrical tape.
• Theblackheatingcablecoreisconductiveandcanshort. They must be properly insulated and kept dry.
• Damagedbuswirescanoverheatorshort.Donotbreak bus wire strands when scoring the jacket or core.
• Keepcomponentsandheatingcableendsdrybefore and during installation.
• Useonlyfire-resistantinsulationmaterials,suchasfiberglass wrap or flame-retardant foam.
HealthHazard:Prolongedorrepeatedcontactwith the sealant in the core sealer may cause skin irritation.Washhandsthoroughly.Overheatingorburning the sealant will produce fumes that may cause polymer fume fever. Avoid contamination of cigarettesortobacco.ConsultMSDSVEN0033forfurther information.CHEMTREC24-houremergencytelephone: (800)424-9300.Non-emergencyhealthandsafetyinformation: (800) 545-6258.
WARNING: CAUTIoN:
Additional Materials Required
• AgencyapprovedNEMA4X-ratedjunctionboxwith3/4-inNPTthreadedentry or through hole.
• Tape GT-66 Installationtemperatureabove40°F(5°C) GS-54 Installationtemperatureabove–40°F(–40°C)
• Onelengthofflexibletubing,6ft(13/4m)maximum,Raychem HCTE-1000-0P/N3679754004
• (1)ForKTV-CTonly:OrderPMK-GP-10grommetP/N700823• (2)ForLBTV2-CTonly:HCS-100-Aheatshrinkcoresealer
P/N 257649-000 and PMK-GK-10 grommet P/N 222724-000•ForCSAZone1HazardousLocations:Zone1certifiedenclosure&DINrail
mounted terminal block.
Installation Instructions
C75-100-AHeating Cable Gland Kit
877Z
De-icing and snow melting equipment
GM-XT heating cable systemClass I, Div. 2, Groups A, B, C, D
Ex e II T(1) (2)(1) T-Rating, same as heating cable (2) Certified for use only when used withaCSAcertifiedZone1enclosure&DIN rail mounted terminal blocK
Hazardous Locations Nonhazardous Locations for GM-X and GM-XT Heating Cable Systems
Class I, Div. 2, Groups A, B, C, D Class II, Div. 2, Groups F, G Class III
C75-100-A Installation Instructions
2
Usecorrectgrommet(see Step 1)
Fully tighten gland into box andorient inserts to planeof heater, as shown.
Note:Usejunctionboxwith3/4-inNPTentry, only.
Flexible tube
15 in(40 cm)
12in(30cm)minimum Indentation(bus wire connection)
2a For threaded junction boxes
• Mountboxonwallor bracket.
• Installglandwiththreaded inserts into hub.
• Slidepartsonto heating cable.
• Slideheatingcablethroughgland and box until it extends 15 in (40 cm) beyond outside edge of box as shown.
• ForVPLheatingcablesonly: Cutheatingcable12in(30cm)fromthecenterof the first indentation.
BTV-CR, BTV-CT, LBTV2-CT, QTVR-CT, GM-X, GM-XT
Bus wire
Conductive core
Inner jacket
Braid
Outerjacket
Clear jacket
Inner jacket
Braid
Outerjacket
Heating element
Insulated bus wire
Bus wire connection
VPL-CT XTV-CT (for dry environments only)
Fluoropolymer inner jacket
Tinned-copper braid
Fluoropolymer outer jacket (-CT)
SpacerSelf-regulating polymeric-fiber heating element
Nickel-plated copper bus wire
Heating cable types
•Select correct grommet from the chart below. Heating Cable Grommet
GM-X, GM-XT, BTV-CR, BTV-CT, QTVR-CT, VPL-CT, XTV-CT Red LBTV2-CT K*KTV-CT P
*Orderseparately
WARNING: Use of the wrong grommet can result in leaks, cracked components, shock or fire, and will invalidate approvals and certifications.
• ForLBTV2-CTaseparateheat-shrinkablecoresealerisrequired.OrderoneHCS-100 heat shrink core sealer.
1
C75-100-A Installation Instructions
3
1inches 2 3 4 5 6 7 8 9 10 11 12
10 20 30 40 50mm 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220
Usecorrectgrommet(see step 1)
Gasket
Gland with inserts
Lock nut
Flexible tube
15 in(40 cm)
12in(30cm)minimum Indentation(bus wire connection)
3/4-inNPTholeinbox=1.080 in diameter
2b For through hole junction boxes
• ForVPLheatingcablesonly: Cutheatingcable12in(30cm)fromthecenterof the first indentation.• Mountboxonwall
or bracket.
• Installglandwithgasket into box wall; secure with locknut.
• Slidepartsonto heating cable.
• Slideheatingcablethroughgland and box until it extends 15 in (40 cm) beyond outside edge of box as shown.
Usecorrectgrommet(see Step 1)
15 in(40 cm)
Y fittingSee 14b for details
2c For GM-X, GM-XT and threaded junction boxes (outdoor location)
• Threadthecapofthe Y fitting with 3/4-inNPTentry.
• Threadtheglandfitting without the captive screws into the cap of the Y fitting.
• Slidepartsonto heating cable.
• Slideheatingcablethroughgland and box until it extends 15 in (40 cm) beyond outside edge of box as shown.
• Threadjunctionboxontoglandfitting.
Note: If your installation requires that the heating cable be installed in flexible conduit as shown in 14b, add the appropriate amount of heating cable.
WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a non-metallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment.
C75-100-A Installation Instructions
4
7 1/2 in(190 mm)
3• Lightlyscoreouterjacketaroundand
down as shown.
• Bendheatingcabletobreakjacketatscore, then peel off jacket.
Do not cut braid
1inches 2 3 4 5 6 7 8 9 10 11 12
10 20 30 40 50mm 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220
Usecorrectgrommet(see step 1)
Gasket
Gland with captive screws
Lock nut
15 in(40 cm)
Y fittingSee 14c for details
3/4-inNPTholeinbox=1.080 in diameter
2d For GM-X, GM-XT and through hole junction boxes (indoor dry location)
• Slidepartsontoheating cable in the sequence and orientation shown.
• BringtheYfittingpart together and tighten the two screws.
• Slidethegasketthreaded end with captive screw.
• Insertthreadendinto box entry hole and loosely tighten lock nut.
• Slideheatingcablethroughglandand box until it extends 15 in (40 cm) beyond outside edge of box as shown.
• Tightenlocknuttojunctionboxon gland fitting.
Note: If your installation requires that the heating cable be installed in flexible conduit as shown in 14c, add the appropriate amount of heating cable.
WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a non-metallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment.
1inches 2 3 4 5 6 7 8
10 20 30 40 50mm 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220
6 in(152 mm)
6 in(152 mm)
VPL
1/2 in(13mm)
5a
• Pushbraidbackandbunchas tight as possible.
• Lightlyscoreinner jacket around and down as shown.
• Peeloffinnerjacket.
• Unwindheatingelement,cutand remove as shown.
• Lightlyscoreclear jacket around and down as shown.
• Bendheatingcable to break jacket at the score then peel off jacket.
• Pushbraidforward.Use a screwdriver to open braid as shown.
• Bendheatingcableandworkit through opening in braid.
• Removeinsulationfromends of bus wires.
• Pullbraidtightto make pigtail.
Go to Step 6
GM-X, GM-XT, BTV, QTVR, LBTV2
Go to Step 5a
Go to Step 5b
VPL
Go to Step 5cXTV
4
C75-100-A Installation Instructions
5
C75-100-A Installation Instructions
6
1inches 2 3 4 5 6 7 8 9 10 11 12
10 20 30 40 50mm 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220
1/4 in(5 mm)
6 1/2 in(165 mm)
GM-X, GM-XT, BTV, QTVR, LBTV25b
• Pushbraidbacktocreate a pucker.
• Atpuckeruseascrewdriver to open braid.
• Bendheatingcableandworkitthrough opening in braid.
• Lightlyscorebase jacket around and down as shown.
• Peeloffbasejacket.
• Notchcore.
• Peelbuswirefromcore.
• Scorecorebetweenbus wires at inner jacket.
• Bendandsnapcore.
• Peelcorefrombuswire.
• Removeanyremaining core material from bus wires.
• Pullbraidtightto make pigtail.
Go to Step 6
6 1/2 in(165 mm)
XTV5c
• Pushbraidbacktocreate a pucker.
• Atpuckeruseascrewdriver to open braid.
• Bendheatingcableandworkitthrough opening in braid.
• Lightlyscorebase jacket around and down as shown.
• Peeloffbasejacket.
• Notchcore.
• Cutandremove all fiber strands.
• Scoreandremove center spacer.
• Bendandsnapcore.
• Removeanyremaining fiber material from bus wires.
• Pullbraidtightto make pigtail.
Go to Step 6
C75-100-A Installation Instructions
7
5/8 in(15 mm)
TubesMake sure all strands
go into the tubes.
6 7
8 9
• Markthejacketasshown. CAUTIoN: Health Hazard.
Wash hands after contact with sealant. Consult material safety data sheet VEN0033.
• Ifneeded,re-twistandstraightenbuswires, then insert into the guide tubes as shown.
• Pushcoresealerontotheheatingcabletothe mark made in Step 6.
• Extraforcemayberequiredforlargercablesor at lower temperatures.
• Removetheguidetubesanddisposeofthem in a plastic bag.
1 in(25 mm)
10
Make sure the bus wires do not kink, bunch, or crossover.
• Apply3wrapsofglasstape(RaychemGT-66orGS-54). • Slipthegreen/yellowtubeontothebraid.Heatshrinking is not required.
1inches 2 3 4 5 6 7 8
10 20 30 40 50mm 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220
C75-100-A Installation Instructions
8
Tape(hidden)
Grommet
Gland with screws
Gland with Inserts
Flexible tube
11a For threaded junction boxes
• Pullcablebackthroughglandandboxuntiltapeislocated just inside hub.
• Seatgrommetinglandasshown.
• Positionglandwithscrewsnexttogrommetand tighten screws.
• Threadflexibletubeontogland.• Installconduitandpullinpowerandground
wires for power connections.
Tape(hidden)
Grommet
Gland with screws
Gland with inserts
Flexible tube
11b For through hole junction boxes
• Pullcablebackthroughglandandboxuntiltape is located just inside gland with inserts.
• Seatgrommetinglandasshown.
• Positionglandwithscrewsnexttogrommetand tighten screws.
• Threadflexibletubeontogland.• Installconduitandpullinpowerandground
wires for power connections.
C75-100-A Installation Instructions
9
• Connectbuswiresandbraidtoterminalblock.• Connectpowerwiresandgroundwiretoterminalblock
for power connections. This connection must be protected by a ground-fault equipment protection device.
Note: For CSA Zone 1 hazardous locations, discard terminal block supplied with the C75-100-A kit & use a CSA certified Zone 1 DIN rail mounted terminal block.
1/2 in(13mm)
3/8in(10 mm)
1312Note the following instructions on buswirepreparation: For tee, install two wires in one terminal:- Twist appropriate wire pair
together.- Trim twisted wires to 1/2in(13mm).
Otherwise,trimsinglewiresto3/8in(10mm).
Thermal insulation
Tyco Thermal Controlsrecommends the use of a conduit drain to prevent water condensation build-up. Heating cable
Weather seal
Flexible tube(HCTE-1000-0)
Tape
6 feet maximum(13/4m)
Water tightconduit seal
14a• Stowwiresinboxandinstalllid.• Secureflexibletubewithtape
(Raychem GT-66 or GS-54).
Note: For CSA certified Zone 1 DIN rail mounted terminal blocks, install bus wire in accordance with manufacturer’s specifications.
C75-100-A Installation Instructions
10
• Installthejunctionboxeitherdirectlytotheglandfitting in the cap of the Y fitting or to the end of the flexible conduit as shown below.
• Stowwiresinboxandinstalllid.
14b For GM-X, GM-XT and threaded junction boxes (outdoor location)
Tyco Thermal Controls recommends the use of a conduit drain to prevent water condensation build-up.
14c For GM-X, GM-XT and through hole junction boxes (indoor dry location)
• Installthejunctionboxeitherdirectlytotheglandfitting in the cap of the Y fitting or to the end of the flexible conduit as shown below.
• Stowwiresinboxandinstalllid.
WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a non-metallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment.
WARNING: Prevent mechanical damage. When installed as shown, the junction box is supported by a non-metallic mounting gland. This method may only be used where the box is not exposed to mechanical stress, static loads, or impact. Protect it with a shield or mount it out of the reach of people or moving equipment.
Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls' only obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make changes—without notification to Buyer—to processing or materials that do not affect compliance with any applicable specification.
C75-100-A Installation Instructions
11
©2010TycoTherm
alContro
lsLLC
PN
391663-000H
5634301/10
Worldwide HeadquartersTyco Thermal Controls307ConstitutionDriveMenlo Park, CA 94025-1164USATel (800) 545-6258Fax(800)[email protected]
Tyco is a trademark of Tyco Thermal Controls LLC or its affiliates.
CanadaTyco Thermal Controls250WestSt.Trenton,OntarioCanada K8V 5S2Tel (800) 545-6258Fax(800)527-5703
Heat-tracing cable
C75-100-A
Power junction box
14d For installation in instrument enclosures
• Installthepowerjunctionboxeitherdirectlytotheinstrument enclosure or to the end of the flexible conduit.
• InstallC75-100-Aandassociated heat-tracing cable inside the instrument enclosure and close the lid.