HDR Corporation
Derry Road West & Argentia Road
Report
Subsurface Utility Engineering Services
Project #61000235
Report Date: March 20, 2014
HDR Corporation Derry Road West and Argentia Road Report for Subsurface Utility Engineering Services March 20, 2014
i
Statement of Qualifications and Limitations The attached Report (the “Report”) has been prepared by T2 Utility Engineers Inc. (“Consultant”) for the benefit of the HDR Corpporation (“Client) in accordance with the agreement between Consultant and Client, including the scope of work detailed therein (the “Agreement”). The information, data, recommendations and conclusions contained in the Report (collectively, the “Information”):
is subject to the scope, schedule, and other constraints and limitations in the Agreement and the qualifications contained in the Report (the “Limitations”), represents Consultant’s professional judgement in light of the Limitations and industry standards for the preparation of similar reports, may be based on information provided to Consultant which has not been independently verified, has not been updated since the date of issuance of the Report and its accuracy is limited to the time period and circumstances in which it was collected, processed, made or issued, must be read as a whole and sections thereof should not be read out of such context, was prepared for the specific purposes described in the Report and the Agreement, in the case of subsurface conditions, may be based on limited inspections and on the assumption that such conditions are uniform and not variable either geographically or over time.
Consultant shall be entitled to rely upon the accuracy and completeness of information that was provided to it and has no obligation to update such information. Consultant accepts no responsibility for any events or circumstances that may have occurred since the date on which the Report was prepared and, in the case of subsurface conditions, is not responsible for any variability in such conditions, geographically or over time. Consultant agrees that the Report represents its professional judgement as described above and that the Information has been prepared for the specific purpose and use described in the Report and the Agreement, but Consultant makes no other representations, or any guarantees or warranties whatsoever, whether express or implied, with respect to the Report, the Information or any part thereof. The Report is to be treated as confidential and may not be used or relied upon by third parties, except:
as agreed in writing by Consultant and Client, as required by law, for use by governmental reviewing agencies.
Consultant accepts no responsibility, and denies any liability whatsoever, to parties other than Client who may obtain access to the Report or the Information for any injury, loss or damage suffered by such parties arising from their use of, reliance upon, or decisions or actions based on the Report or any of the Information (“improper use of the Report”), except to the extent those parties have obtained the prior written consent of Consultant to use and rely upon the Report and the Information. Any damages arising from improper use of the Report or parts thereof shall be borne by the party making such use. This Statement of Qualifications and Limitations is attached to and forms part of the Report and any use of the Report is subject to the terms hereof.
HDR Corporation Derry Road West and Argentia Road Report for Subsurface Utility Engineering Services March 20, 2014
ii
Report Revision Log
Revision # Revised By Date Issue / Revision Description
Report Prepared By: Matt Bourgeois, C. Tech
Branch Manager / Sr. Project Manager
HDR Corporation Derry Road West and Argentia Road Report for Subsurface Utility Engineering Services March 20, 2014
iii
Table of Contents:
Statement of Qualifications and Limitations
Report Revision Log
Page
1. Project Summary ................................................................................................................. 1
1.1 Project Area .............................................................................................................. 1
2. Equipment ............................................................................................................................ 1
2.1 Electromagnetic Designating Equipment ................................................................. 1 2.2 Survey Technologies ................................................................................................ 2
3. SUE Investigation Methodology ......................................................................................... 2
3.1 CI/ASCE Standard 38-02 Summary: ....................................................................... 2 3.2 SUE Investigation Scope of Work ........................................................................... 2
4. Field Investigation ............................................................................................................... 3
5. Utility Circulation Request ................................................................................................. 4
6. Conclusion ............................................................................................................................ 4
Appendices
Appendix A – Composite Utility Drawing Appendix B – Utility Circulation Contact List
HDR Corporation Derry Road West and Argentia Road Report for Subsurface Utility Engineering Services March 20, 2014
1
1. Project Summary
T2 Utility Engineers (T2ue) completed a Subsurface Utility Engineering (SUE) mapping investigation in accordance with CI/ASCE 38-02, for HDR Corporation as part a study for Derry Road and Argentia Road. The project involves Record request Circulation and SUE Mapping within the investigation area. HDR’s project includes a Schedule ‘B’ Class Environmental Assessment, intersection design and road improvements. HDR has requested the SUE investigation in order to determine the horizontal alignment of underground utilities.
1.1 Project Area
The Project Area is a 4-way intersection of Derry Road West and Argentia Road in Mississauga Ontario. The intersection is controlled/signal in all directions. Derry Road West is a major arterial road running north-south extending from Milburough Line through the project area and ending at Hwy 427. Argentia Road is a collector road running east-west extending from Tenth Line West through the project area ending at creditview Road. Derry Road West is a 6-lane road with center median, left turn lanes and right turn lanes with islands. Argentia Road is a 2-lane road to the west and a 3-lane road to the east with left and right turn lanes. The project area is largely a commercial area with grass and concrete sidewalks in the boulevards. According to the record documents obtained and field investigations the project area contains numerous underground utilities. Utilities confirmed within the investigation area include water, sewer, gas, Hydro and Telecommunications. Watermains within the area include Municipal owned 300mm PVC, 300mm DI, 400mm CPP, 600mm CPP and 750mm CCP. The Municipal owned sanitary and storm sewers are throughout the investigation area and range from small lateral connections to large box culverts. Enbridge gas distribution has a 750mm steel coated extra high pressure vital main running along the east side of Derry Road throughout the project area. Enbridge also has a 100mm polyethylene intermediate pressure distribution main running along the south side of Argentia Road throughout the project area. Underground hydro includes plant from single conduit street lighting to concrete encased structures. Telecommunications extensive throughout the project area owned by Bell, Rogers, Allstream, Cogeco, Toronto Hydro and Enersource. 2. Equipment
The following paragraphs represent a description of some of the common equipment used by T2ue to complete the investigation. T2ue uses the latest equipment and techniques available to designate all varieties of subsurface utilities and underground structures. We have assessed the merits of every technology outlined in the ASCE Standard 38-02 and CSA S250-11 for use in utility designating. Field Technicians utilize each technology according to the manufacturer’s instructions and the project conditions. Based on the project scope and discussions with HDR, T2ue has selected the appropriate equipment to ensure that our field technicians are trained and equipped with the latest information, techniques and technology.
2.1 Electromagnetic Designating Equipment
T2ue primarily uses single frequency and multi-frequency electromagnetic designating equipment. Electromagnetic designating equipment does not locate the actual pipes or cables, but instead locate the magnetic fields. Electromagnetic fields are either naturally present on
HDR Corporation Derry Road West and Argentia Road Report for Subsurface Utility Engineering Services March 20, 2014
2
conductors or are induced onto a target line by a transmitter. Signals may be distorted by any of the following:
ground conductivity construction layout (i.e. bends, connections) utility congestion causing bleed off of magnetic fields materials and/or age (i.e. PVC without tracer wire, corrosion in metallic pipes)
2.2 Survey Technologies
Both total station and survey grade GPS equipment is used to collect the data from the SUE Mapping investigation and tie in the results to local features and points that are obtained from the topographical base map. 3. SUE Investigation Methodology
T2 Utility Engineers Inc. performs SUE mapping investigations in accordance with the CI/ASCE Standard 38-02: Standard Guideline for the Collection and Depiction of Existing Subsurface Utility.
3.1 CI/ASCE Standard 38-02 Summary:
All utility information is assigned a quality level in accordance with the CI/ASCE Standard 38-02: Quality Level D (QL-D) – Information derived from existing utility records, or verbal recollections. Quality Level C (QL-C) – Information obtained by surveying and plotting visible above-ground utility features and by using professional judgment in correlating this information to Quality Level D information. Quality Level B (QL-B) – Information obtained through the application of appropriate surface geophysical methods to determine the existence and approximate horizontal position of subsurface utilities. Quality Level A (QL-A) – Precise horizontal and vertical location of utilities obtained by the actual exposure (or verification of previously exposed and surveyed utilities) and subsequent measurement of subsurface utilities at a specific point.
3.2 SUE Investigation Scope of Work
The following is a breakdown of the methodology used for the SUE investigation:
Records research completed by T2ue includes the review of record documents obtained through the utility circulation request (see Appendix B), information received from HDR and gathered records information to utilize for the investigation.
HDR provided T2ue with a base map for the area that is tied into proper coordinate systems (horizontal and vertical survey control points within the project area) including:
o Surface topographical features: curbs, asphalt, buildings, utility poles, signs, CB’s, MH’s, etc.
HDR Corporation Derry Road West and Argentia Road Report for Subsurface Utility Engineering Services March 20, 2014
3
Utilized the topographic survey information provided to verify the position of surface features such as valves and pedestals that indicate the location of underground utilities.
Utilized geophysical utility designating techniques to determine the horizontal position of utilities identified within the project limits. Utilities investigated included water, gas, hydro and telecommunications. The investigation also included induction scanning in key areas to help identify utilities that were not identified on the record drawings. Equipment used included single frequency and multi-frequency electromagnetic designating equipment. This process identified an undocumented utility crossing Argentia towards the east limit of the project area. If collecting additional information is required a test hole should be completed to investigate further.
All designating marks were surveyed in order to generate the utility composite plan. T2ue produced a composite utility drawing based on the field findings and the records
research (Quality Level D, C and B as per ASCE 38-02 – SUE guidelines). 4. Field Investigation
The field investigation was completed in November 2013 within the limits described below. The initial field investigation for the SUE Mapping was completed and the preliminary drawings were submitted to HDR for review. After comments were provided final drawings we’re provided to HDR. The limits of investigation
Full right of way, 300m in each direction from the center of the intersection of Derry Road and Argentia Road.
HDR Corporation Derry Road West and Argentia Road Report for Subsurface Utility Engineering Services March 20, 2014
4
5. Utility Circulation Request
T2ue completed the utility circulation request on August 29, 2014. Record documents have been provided by the utility companies for the project area. A summary of the Utility Circulation Request completed by T2ue is attached in Appendix B. 6. Conclusion
The SUE investigation for this project provided key information regarding the location of the existing underground utilities to be used during the design. A combination of data from the field investigations and utility record information was used to create the composite utility drawings. The drawings show the utilities at the given quality levels as outlined in the CI/ASCE Standard 38-02. The investigation focused on determining the utility infrastructure that would be impacted, and as such the highest quality level of information is provided in those key areas, as requested by HDR. The data currently shown on the drawing should provide the designers adequate information to move forward with the design. During detailed design additional test holes or additional investigations may be required to further define any new areas that may be considered if revisions are made.
HDR Corporation Derry Road West and Argentia Road Report for Subsurface Utility Engineering Services March 20, 2014
APPENDIX A COMPOSITE UTILITY DRAWING
(Separate from report)
HDR Corporation Derry Road West and Argentia Road Report for Subsurface Utility Engineering Services March 20, 2014
APPENDIX B UTILITY CIRCULATION CONTACT LIST
Project Name: Derry & Argentia Completed by: N.F. Job Limits:Project Number: 61000235 Checked by: M.B.
Client: HDR Updated (dd/mm/yy) 19-Mar-14
Bell Canada [email protected] Oakley(Toronto)Chris Gill (Hamilton)
100 Borough Drive, Floor F5Toronto, ONM1P 4W2tel: 416-296-6587 29-Aug-13 07-Oct-13 MU 41167.dwg
Cogeco Data Services Inc. [email protected]
Samir PatelUtility Mark-upsNetworkImplementation(Primary)
P 416-840-8755F 416-626-7774
29-Aug-13 12-Sep-13
Cogeco Cable [email protected] Lynanne Cane
P.O. Box 5076 Stn. MainBurlington, OntarioL7R 4S6Tel: 905-548-8002 29-Aug-13 12-Sep-13
Enbridge Gas Distribution [email protected] Joe Marozzo
500 Consumers Road4th Floor - Post A2 - VPCNorth York, ONM2J 1P8tel: (416) 758-7956fax:(416) 758-4374
29-Aug-13 13-Sep-13 DERRY-ARGENTIA_EG_NOTES.pdf
3240 Mavis Road
Notes
Argentia - Derry W and Mississauga - As-Built_CDS.dwgDerry - Millcreek and Argentia - As-Built_CDS.dwg
Utility Contact Sheet:
Utility Email Address Contact Name Contact Information Info Requested(DD/MM/YY)
Info Received(DD/MM/YY) MATERIAL RECEIVED
Enersource HydroMississauga
[email protected] Rose Sawczyszyn
3240 Mavis RoadMississauga, ONL5C 3K1Tel: 905-283-4160Fax: 905-566-2712
29-Aug-13 11-Sep-13 EHM ARea Map - Derry and Argentia intersection.pdfEHM dwgs - Derry and Argentia intersection.pdf
Group Telecom [email protected] Tannis Raymond tel: 416-848-2267 29-Aug-13 9-25-13 No Conflict, Not in study area.
Hydro One [email protected] Mark Hamilton
49 Sarjeant Dr.Barrie, ONL4N 4V9tel: 705-792-3111P-705-797-4142*fax: 705-792-3116F-705-797-4199*
29-Aug-13 04-Sep-13 No Conflict, Not in study area.
Hydro One Telecom Inc. [email protected] MahonOSP EngineeringDept.
65 Kelfield StreetRexdale, OntarioF-416-540-6790P-416-240-6842or416-240-3751
29-Aug-13 29-Aug-13 No Conflict, Not in study area.
Project Name: Derry & Argentia Completed by: N.F. Job Limits:Project Number: 61000235 Checked by: M.B.
Client: HDR Updated (dd/mm/yy) 19-Mar-14
Notes
Utility Contact Sheet:
Utility Email Address Contact Name Contact Information Info Requested(DD/MM/YY)
Info Received(DD/MM/YY) MATERIAL RECEIVED
Level 3 Communications [email protected] PJ Foley
Level (3) Communications,LLC1025 Eldorado Blvd., 33A-615Broomfield, CO 80021P: (720) 888-6507F: (720) 567-2780E: [email protected]
29-Aug-13 04-Sep-13
Screen Shot.pdfTORBUF-01_103.pdfTORBUF-01_104.pdfTORBUF-01_105.pdfTORBUF-01_106.pdf
No Conflict, Not in study area.
MTS Allstream [email protected] Corey Knight
50 Worcester RdEtobicoke, ONM9W 5X2tel: 416-649-7509 29-Aug-13 03-Sep-13 61000235-AllstreamMarkup.pdf
PSN Fiber Network (PeelFiber) [email protected] Scott Rea 905-8406300 ext 4602 29-Aug-13 29-Aug-13 No Conflict, Not in study area.
Rogers CableCommunications Inc. [email protected] Manel De Silva
Markup Coordinator, OPEGTACTel: 416 446-6794
29-Aug-13 06-Sep-13 M133507_61000235.pdfM133507_Derry-Argentia.pdf
Telus [email protected]@prestigetel.com Stephen Hoy
2696 Matheson Blvd. E,1st Floor, West Tower,Mississauga, ONL4W 4V5tel: 905-804-6219p-416-883-6636*C-416-992-0617
29-Aug-13 05-Sep-13 No Conflict, Not in study area.
Region of Peel 29-Aug-13
07880_D.pdf36827_D.pdf36826_D.pdf36828_D.pdf36829_D.pdfC16489.pdf07881_D.pdf09821_D.pdf09822_D.pdf08477_D.pdf
TransCanada Pipelines [email protected] Darlene Presley
TransCanada PipeLinesLimitedC/O Lehman & Associates97 Collier Street, Barrie, ONL4M 1H2Phone: 1-866-602-0663Direct: 705-627-2302Fax: 705-727-9217
29-Aug-13 17-Sep-13 No Conflict, Not in study area.
INT
RB
K
OG
VC 6563512
WV
WV
CO
NC
OGINT
RB
K
OG
CO
NC
ST
M
CATB
CATB
CO
NC
INT
RB
K
ASP
H
MH
TVPE
D
INT
RB
K
ASP
H
ASP
H
CO
NC
LS
CATB
OG
MO
NIT
OR
MHCB
CATB
LS
BM
H
BM
H
LS
LS
GV
BM
H
MH
LS
OG
OG
TS
CATB
DINCB
MHCB
MH
CATB
OG
HC
M 21
LS
TS
CO
NC
TS
TVPE
D
VC 6563513
CO
NC
LS
LS
OG
EASEMENT
DERRY RD. W.
ROGERSROGERS ROGERS
ENERSOURCE ENERSOURCE
ENERSOURCE
450
CO
NP
450 CONP450 CONP450 CONP
450
CO
NP
STM#
300
825 825825
300
300
2700 2700
2400
2400
SAN#SAN#
SAN#
300
300
LIM
IT
OF
FIE
LD
INV
ES
TIG
ATIO
N600 CPP
600 CPP
600 CPP
FO
C
EN
ER
SO
UR
CE/
RO
GE
RS
UN
AB
LE
TO
VE
RIF
Y
WA
TE
RM
AIN
NO
RT
HE
AS
T
OF
THIS
LO
CA
TIO
N.
FIELD NOTE:VERIFIED GAS MARKER AT THIS LOCATION. IT IS NOT A GAS VALVE.
750 SC XHP VITAL750 SC XHP VITAL
750 SC XHP VITALENBRIDGEENBRIDGE
GA
S
EN
BRID
GE 750 S
C
XH
P
VIT
AL
C.N.R.
ROGERS
ROGERSROGERS
NOTE:ROGER RECORDS INDICATE ROGERS FIBRE ALONG THIS APPROXIMATE ALIGNMENT. UNABLE TO FIELD VERIFY. POSSIBLY IN THE SAME TRENCH AS ENERSOURCE FIBRE.
TORONTO HYDRO
TORONTO HYDROTORONTO HYDRO
BPED#
B
HY
DR
O 100
X12
CO
NC
SPARE SPARE
SPARE
FIELD NOTE:UNABLE TO VERIFY
WATERMAIN SOUTHWEST OF THIS LOCATION.
FIELD NOTE:UNABLE TO DETERMINE UTILITY OWNERSHIP IN
FIELD.
FIELD NOTE:FIELD VERIFIED TORONTO HYDRO FIBRE,
RECORDS INDICATE TRENCH ALSO CONTAINS COGECO CABLE AND ALLSTREAM
FIBRE.
FIE
LD
VE
RIFIE
D
TO
RO
NT
O
HY
DR
O FIB
RE,
RE
CO
RD
S
INDIC
AT
E
TR
EN
CH
ALS
O
CO
NT
AIN
S
CO
GE
CO
CA
BLE
FIELD NOTE:FIELD VERIFIED TORONTO HYDRO FIBRE, RECORDS INDICATE TRENCH ALSO CONTAINS COGECO CABLE AND ALLSTREAM FIBRE.
NOTE:ENERSOURCE RECORDS INDICATE ONE SPARE DUCT ALONG THIS APPROXIMATE ALIGNMENT. UNABLE TO FIELD VERIFY.
1 5 Plan No.
Project No.
Sheet of
Drawn by
AreaCAD Area
Checked by
Date
1Om 0 10 20 30m
HORIZONTAL SCALE
Schedule B
61000235
FOR FULL SIZE USE 11002 FULL.TBLHALF SIZE USE 11002-11X17
U1
1-855-222-T2UE | WWW.T2UE.COM
ASCE QUALITY LEVELS
THE UTILITY INFORMATION SHOWN ON THIS DRAWING
WAS COLLECTED IN ACCORDANCE TO ASCE STANDARD
38-02. THE INFORMATION IS SHOWN BY QUALITY LEVEL
WHICH INDICATES THE LEVEL OF EFFORT USED TO
DETERMINE THE LOCATION OF THE DATA
QUALITY LEVEL "D" - INFORMATION DERIVED
FROM EXISTING RECORDS OR VERBAL
RECOLLECTIONS.
QUALITY LEVEL "C" - INFORMATION OBTAINED
BY SURVEYING AND PLOTTING VISIBLE ABOVE
GROUND UTILITY FEATURES AND BY USING
PROFESSIONAL JUDGEMENT IN CORRELATING
THIS INFORMATION TO THE QUALITY LEVEL "D"
INFORMATION.
QUALITY LEVEL "B" - INFORMATION OBTAINED
THROUGH THE APPLICATION OF APPROPRIATE
SURFACE GEOPHYSICAL METHODS TO DETERMINE
THE EXISTENCE AND APPROXIMATE HORIZONTAL
POSITION OF THE UTILITIES.
QUALITY LEVEL "A" - PRECISE HORIZONTAL
AND VERTICAL LOCATION OF UTILITES OBTAINED
BY THE ACTUAL EXPOSURE AND SUBSEQUENT
MEASUREMENT OF SUBSURFACE UTILITIES.
N
I
C
R
E
A
S
E
D
Y
T
I
L
A
U
Q
TEST HOLE (QL-A)
UNKNOWN
QUALITY LEVEL "C"
BURIED ELECTRIC
BURIED TELECOMMUNICATIONS
QUALITY LEVEL "B"
SANITARY SEWER
WATER
STORM SEWER
CABLE TV
GAS
LEGEND
FIBRE OPTIC CABLE
GAS SERVICE
WATER SERVICE
SANITARY LATERAL
STORM LATERAL
*
BURIED ELECTRIC STREET LIGHT
NOT SURVEYED, LOCATION
BASED ON RECORD INFORMATION#
BURIED ELECTRIC TRAFFIC LIGHT
DISCLAIMER:
G
B
TV
FOC
UNK
TL
SL
H
STM
SAN
WM
SAN
STM
NOT SURVEYED, LOCATION
BASED ON FIELD OBSERVATION
CLIENT:
WS
GS
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF T2UE’S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES, EXCEPT
AS AGREED BY T2UE AND ITS CLIENT, AS REQUIRED BY LAW OR FOR USE BY
GOVERNMENT REVIEWING AGENCIES. T2UE ACCEPTS NO RESPONSIBILITY, AND
DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY THAT MODIFIES THIS
DRAWING WITHOUT T2UE’S EXPRESS WRITTEN CONSENT.
ABANDONEDABD
THE ENGINEER’S SEAL HEREON IS TO CERTIFY THAT THE UTILITIES SHOWN
HAVE BEEN INVESTIGATED IN ACCORDANCE WITH STANDARD SUE INDUSTRY
PRACTICES. ALL OTHER INFORMATION HEREON HAS BEEN PROVIDED BY
OTHERS AND IS NOT A PART OF THIS CERTIFICATION.
SUBSURFACE UTILITY ENGINEERING INVESTIGATION
FLOW ARROW
PRELIMINARY
DATE DETAILS
REVISIONS
INIT.
MA
TC
H LIN
E S
EE D
WG.
U2
QUALITY LEVEL "D"XXX
XXX
XXX
XXX
OH OVERHEAD HYDRO
M.B. N.F.
OCTOBER 2013
(DERRY ROAD & ARGENTIA ROAD INTERSECTION)
DERRY-ARGENTIA
INTERSECTION IMPROVEMENTS
DERRY ROAD WEST
SAN 1802942
SAN
SAN
SAN 1802938
SAN 1802937
SANSAN
SAN 1802936
SAN 1800689
SAN
SAN 1800690
SAN 1800683
SAN 1800688
SAN 1800687
U1
U2
U3
U4
U5KEY PLAN (N.T.S.)
ARGENTIA ROAD
HIGHWAY 4
01
DER
RY R
OA
D
WEST
GENERAL NOTES
1. T2 UTILITY ENGINEERS (T2UE) SUE FIELD
INVESTIGATION WAS COMPLETED IN SEPTEMBER 2013.
CHANGES TO UTILITIES THAT OCCURRED FOLLOWING
OUR INVESTIGATION MAY NOT BE SHOWN.
CONSIDERATION SHOULD BE GIVEN TO UPDATING THIS
PLAN PRIOR TO FINAL DESIGN AND CONSTRUCTION.
2. LIMIT OF INVESTIGATION: 300m IN ALL DIRECTIONS
FROM CENTERLINE OF DERRY ROAD AND ARGENTIA
ROAD INTERSECTION.
3. FIELD VERIFICATION OF UTILITIES WAS COMPLETED
USING A COMBINATION OF ELECTROMAGNETIC PIPE
AND CABLE LOCATE EQUIPMENT.
4. EMPTY CONDUITS, SERVICES, STREETLIGHTING
CABLES, LATERALS TO BUILDINGS, ABANDONED
FACILITIES, WITHIN THE INVESTIGATION AREA MAY
NOT BE SHOWN ON THE DRAWING.
5. T2UE USED AVAILABLE MEANS IN AN ATTEMPT TO
DETERMINE THE LOCATION OF UNDOCUMENTED
UTILITIES HOWEVER CANNOT BE RESPONSIBLE FOR
FINDING ALL UNDOCUMENTED UTILITIES.
6. SURVEY OF T2UE’S UNDERGROUND UTILITY
INFORMATION WAS COMPLETED BY ACL.
7. THE BASEPLAN WAS PROVIDED BY THE CLIENT,
THEREFORE T2UE IS NOT RESPONSIBLE FOR ITS
ACCURACY.
8. UTILITY MATERIALS AND SIZES SHOWN ON
DRAWING ARE BASED ON RECORDS INFORMATION
RECEIVED, PROFESSIONAL JUDGEMENT, OR FIELD
OBSERVATIONS.
9. UTILITY OWNERSHIP SHOWN ON DRAWING IS BASED
ON RECORDS INFORMATION RECEIVED, PROFESSIONAL
JUDGEMENT, OR FIELD OBSERVATIONS.
10. SEE PROJECT REPORT FOR ADDITIONAL
INFORMATION.
CA
TB
CA
TB
HV 20
2603
1
STM
CA
TB
G
CA
TB
LS
TS
CA
TB
LS
TVPED
SAN 18
0068
8
TS
TVPED
GV
TS
INTRBK
BMH
WV 2
0595
49
WV 2
0595
50
SAN 18
0068
7
TVPED
MB
WV ?
MH
DC
B
MH
MB
TLS BMH
TS
TS
TS
LS
VC 2
0596
34TVPED
HE
TS
LS
TVPED
HV 2.
2603
5
TLS
DC
B
TLS
TLS
TVPED
SAN 18
0293
6
MH
VC 2
0596
35
STM
TVPED
HEHE
HCM 20
SAN 18
0068
9
TS
TVPED HV 20
2724
2
TLS
SCB
TLS
LS
BPED
CA
TB
MH
CA
TB
MH
TLS
MH
WV 6
4881
79
MH
CB
BMH
CA
TB
TS
HE
TVPED
SANSAN
SAN
TLS
CA
TB
HV 64
8817
5
MH
WV
TLS
SIGN
WV
HCM 21
JB
TS
SIGN
CONC
TVPED
LS
TS
LS
CA
TB
CA
TB
TS
SAN 18
0293
7
ARGENTIA RD.
DE
RR
Y
RD.
W.
RO
GE
RS
ROGERS
ROGERS
RO
GE
RS
EN
ERS
OU
RCE
ALLSTREAM
ROGERS
FOC ALLSTREAM
EN
ER
SO
UR
CE
FOC ALLSTREAM
250 PVC 250 PVC 250 PVC
300
300
300
300
300
250
PVC
825 CONC
825
CONC
825 CONC1050
CONC
300
750
CP
P
300 PVC
300 DI
WV#
750 CPP 750 CPP 400 CPP
750
CP
P
750
CP
P
250
300
600
CP
P
600
CP
P
600
CP
P
FOC ENERSOURCE/ROGERS
FOC BELL
FOC ROGERS
BELL
RO
GERS
FOC BELL
300
PV
C
FPED*
FOC ENERSOURCE/ROGERS
FOC ENERSOURCE
FOC ENERSOURCE/ROGERS
FOC ENERSOURCE/ROGERS
RO
GE
RS
FOC ALLSTREAM
FOC ENERSOURCE
FIELD NOTE:UNABLE TO VERIFY
WATERMAIN SOUTHWEST OF THIS
LOCATION.
ROGERS
RO
GE
RS
FOC ALLSTREAM
NOTE:MUNICIPAL RECORDS INDICATE 300mm WATERMAIN ALONG THIS APPROXIMATE ALIGNMENT TO BLOW-OFF VALVE.
FIELD NOTE:UNABLE TO VERIFY WATERMAIN NORTHEAST OF THIS LOCATION.
TO
RO
NT
O
TO
RO
NT
O
FIELD NOTE:UNABLE TO VERIFY WATERMAIN NORTHWEST OF THIS LOCATION.
FIELD NOTE:UNABLE TO VERIFY BELL FIBRE BEYOND THIS POINT. LIKELY IN THE SAME TRENCH AS BELL.
GS
ROGERSENERSOURCE
750 S
C
XH
P
VIT
AL
750 S
C
XH
P
VIT
AL
EN
BRID
GE
TORONTO
GAS ENBRIDGE 750 SC XHP VITAL
100 PE IP
100 PE IP
100 PE IP
100 PE IP
ENBRIDGEENBRIDGE
TV ROGERS
TV ROGERS
RO
GE
RS
ROGERS
ROGERS
FOC ROGERS
NOTE:RECORDS INDICATE ROGERS ALONG THIS APPROXIMATE ALIGNMENT. UNABLE TO FIELD VERIFY.
NOTE:RECORDS INDICATE ROGERS TV ALONG THIS ALIGNMENT, HOWEVER, THE FIELD VERIFIED IT AS FIBRE.
NOTE:ROGER RECORDS INDICATE ROGERS TV ALONG THIS APPROXIMATE ALIGNMENT.
LIKELY IN THE SAME TRENCH AS ROGERS FIBRE. UNABLE TO CONFIRM IN FIELD. NOT
SHOWN ON DRAWING.
RO
GE
RS
RO
GE
RS
FOC ROGERS
HY
DR
O
HY
DR
O
HYDRO
FIELD NOTE:FIELD VERIFIED TORONTO HYDRO FIBRE TRENCH ALSO CONTAINS COGECO CABLE AND ALLSTREAM FIBRE. ALLSTREAM JOINS TRENCH AT THIS LOCATION.
FOC ALLSTREAM
BPED# BPED#
BELL
B
FOC ROGERS
100
X8
CO
NC
FOC ALLSTREAM
HYDRO 100X12 CONC
100
X9
CO
NC
H
100X8 CONC
HYDRO 100X9 CONC
100
X6
CO
NC
250
PVC
100
X8
100
X6
CO
NC
CO
NC
SP
AR
E
SP
AR
E
SPARE
SPARE
50
X2
CO
NC
FIELD NOTE:FIELD VERIFIED TORONTO HYDRO FIBRE, RECORDS INDICATE TRENCH ALSO CONTAINS COGECO CABLE AND ALLSTREAM FIBRE.
2 5 Plan No.
Project No.
Sheet of
Drawn by
AreaCAD Area
Checked by
Date
1Om 0 10 20 30m
HORIZONTAL SCALE
Schedule B
61000235
FOR FULL SIZE USE 11002 FULL.TBLHALF SIZE USE 11002-11X17
U2
1-855-222-T2UE | WWW.T2UE.COM
ASCE QUALITY LEVELS
THE UTILITY INFORMATION SHOWN ON THIS DRAWING
WAS COLLECTED IN ACCORDANCE TO ASCE STANDARD
38-02. THE INFORMATION IS SHOWN BY QUALITY LEVEL
WHICH INDICATES THE LEVEL OF EFFORT USED TO
DETERMINE THE LOCATION OF THE DATA
QUALITY LEVEL "D" - INFORMATION DERIVED
FROM EXISTING RECORDS OR VERBAL
RECOLLECTIONS.
QUALITY LEVEL "C" - INFORMATION OBTAINED
BY SURVEYING AND PLOTTING VISIBLE ABOVE
GROUND UTILITY FEATURES AND BY USING
PROFESSIONAL JUDGEMENT IN CORRELATING
THIS INFORMATION TO THE QUALITY LEVEL "D"
INFORMATION.
QUALITY LEVEL "B" - INFORMATION OBTAINED
THROUGH THE APPLICATION OF APPROPRIATE
SURFACE GEOPHYSICAL METHODS TO DETERMINE
THE EXISTENCE AND APPROXIMATE HORIZONTAL
POSITION OF THE UTILITIES.
QUALITY LEVEL "A" - PRECISE HORIZONTAL
AND VERTICAL LOCATION OF UTILITES OBTAINED
BY THE ACTUAL EXPOSURE AND SUBSEQUENT
MEASUREMENT OF SUBSURFACE UTILITIES.
N
I
C
R
E
A
S
E
D
Y
T
I
L
A
U
Q
TEST HOLE (QL-A)
UNKNOWN
QUALITY LEVEL "C"
BURIED ELECTRIC
BURIED TELECOMMUNICATIONS
QUALITY LEVEL "B"
SANITARY SEWER
WATER
STORM SEWER
CABLE TV
GAS
LEGEND
FIBRE OPTIC CABLE
GAS SERVICE
WATER SERVICE
SANITARY LATERAL
STORM LATERAL
*
BURIED ELECTRIC STREET LIGHT
NOT SURVEYED, LOCATION
BASED ON RECORD INFORMATION#
BURIED ELECTRIC TRAFFIC LIGHT
DISCLAIMER:
G
B
TV
FOC
UNK
TL
SL
H
STM
SAN
WM
SAN
STM
NOT SURVEYED, LOCATION
BASED ON FIELD OBSERVATION
CLIENT:
WS
GS
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF T2UE’S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES, EXCEPT
AS AGREED BY T2UE AND ITS CLIENT, AS REQUIRED BY LAW OR FOR USE BY
GOVERNMENT REVIEWING AGENCIES. T2UE ACCEPTS NO RESPONSIBILITY, AND
DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY THAT MODIFIES THIS
DRAWING WITHOUT T2UE’S EXPRESS WRITTEN CONSENT.
ABANDONEDABD
THE ENGINEER’S SEAL HEREON IS TO CERTIFY THAT THE UTILITIES SHOWN
HAVE BEEN INVESTIGATED IN ACCORDANCE WITH STANDARD SUE INDUSTRY
PRACTICES. ALL OTHER INFORMATION HEREON HAS BEEN PROVIDED BY
OTHERS AND IS NOT A PART OF THIS CERTIFICATION.
SUBSURFACE UTILITY ENGINEERING INVESTIGATION
FLOW ARROW
PRELIMINARY
DATE DETAILS
REVISIONS
INIT.
MA
TC
H LIN
E S
EE D
WG.
U5
MA
TC
H LIN
E S
EE D
WG.
U4
QUALITY LEVEL "D"XXX
XXX
XXX
XXX
OH OVERHEAD HYDRO
M.B. N.F.
OCTOBER 2013
(DERRY ROAD & ARGENTIA ROAD INTERSECTION)
DERRY-ARGENTIA
INTERSECTION IMPROVEMENTS
MATCH LINE SEE DWG. U1
MATCH LINE SEE DWG. U3
DERRY ROAD WEST
SAN 1802942
SAN
SAN
SAN 1802938
SAN 1802937
SANSAN
SAN 1802936
SAN 1800689
SAN
SAN 1800690
SAN 1800683
SAN 1800688
SAN 1800687
U1
U2
U3
U4
U5KEY PLAN (N.T.S.)
ARGENTIA ROAD
HIGHWAY 4
01
DER
RY R
OA
D
WEST
GENERAL NOTES
1. T2 UTILITY ENGINEERS (T2UE) SUE FIELD
INVESTIGATION WAS COMPLETED IN SEPTEMBER 2013.
CHANGES TO UTILITIES THAT OCCURRED FOLLOWING
OUR INVESTIGATION MAY NOT BE SHOWN.
CONSIDERATION SHOULD BE GIVEN TO UPDATING THIS
PLAN PRIOR TO FINAL DESIGN AND CONSTRUCTION.
2. LIMIT OF INVESTIGATION: 300m IN ALL DIRECTIONS
FROM CENTERLINE OF DERRY ROAD AND ARGENTIA
ROAD INTERSECTION.
3. FIELD VERIFICATION OF UTILITIES WAS COMPLETED
USING A COMBINATION OF ELECTROMAGNETIC PIPE
AND CABLE LOCATE EQUIPMENT.
4. EMPTY CONDUITS, SERVICES, STREETLIGHTING
CABLES, LATERALS TO BUILDINGS, ABANDONED
FACILITIES, WITHIN THE INVESTIGATION AREA MAY
NOT BE SHOWN ON THE DRAWING.
5. T2UE USED AVAILABLE MEANS IN AN ATTEMPT TO
DETERMINE THE LOCATION OF UNDOCUMENTED
UTILITIES HOWEVER CANNOT BE RESPONSIBLE FOR
FINDING ALL UNDOCUMENTED UTILITIES.
6. SURVEY OF T2UE’S UNDERGROUND UTILITY
INFORMATION WAS COMPLETED BY ACL.
7. THE BASEPLAN WAS PROVIDED BY THE CLIENT,
THEREFORE T2UE IS NOT RESPONSIBLE FOR ITS
ACCURACY.
8. UTILITY MATERIALS AND SIZES SHOWN ON
DRAWING ARE BASED ON RECORDS INFORMATION
RECEIVED, PROFESSIONAL JUDGEMENT, OR FIELD
OBSERVATIONS.
9. UTILITY OWNERSHIP SHOWN ON DRAWING IS BASED
ON RECORDS INFORMATION RECEIVED, PROFESSIONAL
JUDGEMENT, OR FIELD OBSERVATIONS.
10. SEE PROJECT REPORT FOR ADDITIONAL
INFORMATION.
DCB
CATB
DINCB
OG
OG
OG
LS
CATB
CATB
TS
OG
JB
LS
CATB
CATB
LS
TS
DERRY RD. W.
ENERSOURCE
FOC ALLSTREAM
FOC ENERSOURCE
1050
300
300
300
CATB#
300
300
1050
MHCB#
MHCB#
MHCB#
300
300
300
MHCB#
300
MHCB#300
300
CATB#
CATB#
1050
1050
1050
1050
NOTE:TWO LARGE TWIN 6X15m
CULVERTS LOCATED JUST OUTSIDE LIMITS OF INVESTIGATION. NOT
SHOWN ON DRAWING.
CATB#
CATB#
300
CATB#
1500
X6000 B
OX C
ULV.
300
300
300 750
CPP
750 CPP
750 CPP
HV#
HIG
HW
AY 401
VC#
600 CPP
600 CPP
600 CPP
NOTE:RECORDS INDICATE
BURIED VALVE STRUCTURE IN
THIS APPROXIMATE LOCATION.
NOTE:RECORDS INDICATE 600mm CPP
WATERMAIN IS IN 1050mm STEEL CASING NORTH OF VALVE
CHAMBER AND ENDS NORTH OF CULVERT CROSSING OUTSIDE
LIMITS.
FO
C
ALLS
TR
EA
M
FO
C
EN
ER
SO
UR
CE
TVPED*
FIELD NOTE:VERIFIED TV PED WITH
EMPTY CONDUITS AT THIS APPROXIMATE LOCATION.
HW
LS*
HW
LS*
BMH
LS*
750 SC XHP VITAL
ENBRIDGE
750 SC XHP VITAL
ROGERS
FOC ALLSTREAM
FOC ALLSTREAM
FOC ENERSOURCE
ROGERS
FOC ALLSTREAM
FOC ROGERS
NOTE:ROGERS RECORDS INDICATE ROGERS
FIBRE ALONG THIS APPROXIMATE ALIGNMENT. POSSIBLY IN THE SAME
TRENCH AS ENERSOURCE FIBRE. UNABLE TO FIELD VERIFY.
LIMIT
OF FIE
LD
INV
ES
TIG
ATIO
N
NOTE:MUNICIPAL RECORDS INDICATE
TELECOM ALONG THIS APPROXIMATE ALIGNMENT. LIKELY ABANDONED AND
POSSIBLY REMOVED.
B
FOC ALLSTREAM
BPED#BPED#
100X4 CONC
100X12 CONC
NOTE:ENERSOURCE HYDRO RECORDS INDICATE CONCRETE ENCASED CONDUITS WITHIN THE HIGHWAY 401 CORRIDOR.
SPARE
SPARE HYDRO
SPARE HYDRO
3 5 Plan No.
Project No.
Sheet of
Drawn by
AreaCAD Area
Checked by
Date
1Om 0 10 20 30m
HORIZONTAL SCALE
Schedule B
61000235
FOR FULL SIZE USE 11002 FULL.TBLHALF SIZE USE 11002-11X17
U3
1-855-222-T2UE | WWW.T2UE.COM
ASCE QUALITY LEVELS
THE UTILITY INFORMATION SHOWN ON THIS DRAWING
WAS COLLECTED IN ACCORDANCE TO ASCE STANDARD
38-02. THE INFORMATION IS SHOWN BY QUALITY LEVEL
WHICH INDICATES THE LEVEL OF EFFORT USED TO
DETERMINE THE LOCATION OF THE DATA
QUALITY LEVEL "D" - INFORMATION DERIVED
FROM EXISTING RECORDS OR VERBAL
RECOLLECTIONS.
QUALITY LEVEL "C" - INFORMATION OBTAINED
BY SURVEYING AND PLOTTING VISIBLE ABOVE
GROUND UTILITY FEATURES AND BY USING
PROFESSIONAL JUDGEMENT IN CORRELATING
THIS INFORMATION TO THE QUALITY LEVEL "D"
INFORMATION.
QUALITY LEVEL "B" - INFORMATION OBTAINED
THROUGH THE APPLICATION OF APPROPRIATE
SURFACE GEOPHYSICAL METHODS TO DETERMINE
THE EXISTENCE AND APPROXIMATE HORIZONTAL
POSITION OF THE UTILITIES.
QUALITY LEVEL "A" - PRECISE HORIZONTAL
AND VERTICAL LOCATION OF UTILITES OBTAINED
BY THE ACTUAL EXPOSURE AND SUBSEQUENT
MEASUREMENT OF SUBSURFACE UTILITIES.
N
I
C
R
E
A
S
E
D
Y
T
I
L
A
U
Q
TEST HOLE (QL-A)
UNKNOWN
QUALITY LEVEL "C"
BURIED ELECTRIC
BURIED TELECOMMUNICATIONS
QUALITY LEVEL "B"
SANITARY SEWER
WATER
STORM SEWER
CABLE TV
GAS
LEGEND
FIBRE OPTIC CABLE
GAS SERVICE
WATER SERVICE
SANITARY LATERAL
STORM LATERAL
*
BURIED ELECTRIC STREET LIGHT
NOT SURVEYED, LOCATION
BASED ON RECORD INFORMATION#
BURIED ELECTRIC TRAFFIC LIGHT
DISCLAIMER:
G
B
TV
FOC
UNK
TL
SL
H
STM
SAN
WM
SAN
STM
NOT SURVEYED, LOCATION
BASED ON FIELD OBSERVATION
CLIENT:
WS
GS
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF T2UE’S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES, EXCEPT
AS AGREED BY T2UE AND ITS CLIENT, AS REQUIRED BY LAW OR FOR USE BY
GOVERNMENT REVIEWING AGENCIES. T2UE ACCEPTS NO RESPONSIBILITY, AND
DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY THAT MODIFIES THIS
DRAWING WITHOUT T2UE’S EXPRESS WRITTEN CONSENT.
ABANDONEDABD
THE ENGINEER’S SEAL HEREON IS TO CERTIFY THAT THE UTILITIES SHOWN
HAVE BEEN INVESTIGATED IN ACCORDANCE WITH STANDARD SUE INDUSTRY
PRACTICES. ALL OTHER INFORMATION HEREON HAS BEEN PROVIDED BY
OTHERS AND IS NOT A PART OF THIS CERTIFICATION.
SUBSURFACE UTILITY ENGINEERING INVESTIGATION
FLOW ARROW
PRELIMINARY
DATE DETAILS
REVISIONS
INIT.
MA
TC
H LIN
E S
EE D
WG.
U2
QUALITY LEVEL "D"XXX
XXX
XXX
XXX
OH OVERHEAD HYDRO
M.B. N.F.
OCTOBER 2013
(DERRY ROAD & ARGENTIA ROAD INTERSECTION)
DERRY-ARGENTIA
INTERSECTION IMPROVEMENTS
DERRY ROAD WEST
SAN 1802942
SAN
SAN
SAN 1802938
SAN 1802937
SANSAN
SAN 1802936
SAN 1800689
SAN
SAN 1800690
SAN 1800683
SAN 1800688
SAN 1800687
U1
U2
U3
U4
U5KEY PLAN (N.T.S.)
HIGHWAY 4
01
DER
RY R
OA
D
WEST
ARGENTIA ROAD
GENERAL NOTES
1. T2 UTILITY ENGINEERS (T2UE) SUE FIELD
INVESTIGATION WAS COMPLETED IN SEPTEMBER 2013.
CHANGES TO UTILITIES THAT OCCURRED FOLLOWING
OUR INVESTIGATION MAY NOT BE SHOWN.
CONSIDERATION SHOULD BE GIVEN TO UPDATING THIS
PLAN PRIOR TO FINAL DESIGN AND CONSTRUCTION.
2. LIMIT OF INVESTIGATION: 300m IN ALL DIRECTIONS
FROM CENTERLINE OF DERRY ROAD AND ARGENTIA
ROAD INTERSECTION.
3. FIELD VERIFICATION OF UTILITIES WAS COMPLETED
USING A COMBINATION OF ELECTROMAGNETIC PIPE
AND CABLE LOCATE EQUIPMENT.
4. EMPTY CONDUITS, SERVICES, STREETLIGHTING
CABLES, LATERALS TO BUILDINGS, ABANDONED
FACILITIES, WITHIN THE INVESTIGATION AREA MAY
NOT BE SHOWN ON THE DRAWING.
5. T2UE USED AVAILABLE MEANS IN AN ATTEMPT TO
DETERMINE THE LOCATION OF UNDOCUMENTED
UTILITIES HOWEVER CANNOT BE RESPONSIBLE FOR
FINDING ALL UNDOCUMENTED UTILITIES.
6. SURVEY OF T2UE’S UNDERGROUND UTILITY
INFORMATION WAS COMPLETED BY ACL.
7. THE BASEPLAN WAS PROVIDED BY THE CLIENT,
THEREFORE T2UE IS NOT RESPONSIBLE FOR ITS
ACCURACY.
8. UTILITY MATERIALS AND SIZES SHOWN ON
DRAWING ARE BASED ON RECORDS INFORMATION
RECEIVED, PROFESSIONAL JUDGEMENT, OR FIELD
OBSERVATIONS.
9. UTILITY OWNERSHIP SHOWN ON DRAWING IS BASED
ON RECORDS INFORMATION RECEIVED, PROFESSIONAL
JUDGEMENT, OR FIELD OBSERVATIONS.
10. SEE PROJECT REPORT FOR ADDITIONAL
INFORMATION.
LS
CATB
CATB
TS
STM
SAN 1802937
WV
HV 2027244
OG
LSSIGN
HCM 22
TS
OG
LS
CATB
VCWV
OG
STM
SAN 1802938
CATB
CATB
TS
BPED
OG
JB
OG
BPED
SAN
OG
LS
OG
OG
HV 2027243
OG
SAN
JB
CATB
CATB
OG
LS
FP
OG
SAN 1802942
TS
FP
WV B
FP
VC 2062018
OGOG
HV 2027241
OG
WV 2062019
VC 2062017
ARGENTIA RD.
RO
GER
S
RO
GE
RS
FPED*
250 PVC 250 PVC
250 PVC
250 PVC825 CONC
825 CONC
750 CONC750 CONC
300 PVC
300 PVC
300 PVC
LIMIT OF FIELD INVESTIGATION
FOC BELL
FOC BELL
FOC ENERSOURCE/ROGERS FOC ENERSOURCE/ROGERS
FOC ENERSOURCE/ROGERS
FIELD NOTE:UNABLE TO VERIFY
STREETLIGHTING BETWEEN THESE LOCATIONS.
FOC BELL
H
H
FOC BELL
BELL
100 PE IP
100 PE IP 100 PE IP
ENBRIDGE
ENBRIDGE
RO
GE
RS
BELL
100
X9
CO
NC
HYDRO 100X6 CONC
100X4 CONC100X4 CONC
NOTE:ENERSOURCE HYDRO RECORDS
INDICATE 100X4 CONCRETE ENCASED CONDUIT UNDER
DRIVEWAY.
NOTE:ENERSOURCE HYDRO RECORDS INDICATE 100X4 CONCRETE ENCASED CONDUIT UNDER DRIVEWAY.
SPARE SPARE
SPARE
FIELD NOTE:UNABLE TO VERIFY
WATERMAIN IN THIS AREA. TRACER VISIBLE IN THIS
CHAMBER, HOWEVER, WIRE IS NOT ACCESSIBLE FROM
SURFACE.
FIELD NOTE:UNABLE TO VERIFY ENERSOURCE AND ROGERS FIBRE SOUTH OF THIS LOCATION.
4 5 Plan No.
Project No.
Sheet of
Drawn by
AreaCAD Area
Checked by
Date
1Om 0 10 20 30m
HORIZONTAL SCALE
61000235
FOR FULL SIZE USE 11002 FULL.TBLHALF SIZE USE 11002-11X17
U4
1-855-222-T2UE | WWW.T2UE.COM
ASCE QUALITY LEVELS
THE UTILITY INFORMATION SHOWN ON THIS DRAWING
WAS COLLECTED IN ACCORDANCE TO ASCE STANDARD
38-02. THE INFORMATION IS SHOWN BY QUALITY LEVEL
WHICH INDICATES THE LEVEL OF EFFORT USED TO
DETERMINE THE LOCATION OF THE DATA
QUALITY LEVEL "D" - INFORMATION DERIVED
FROM EXISTING RECORDS OR VERBAL
RECOLLECTIONS.
QUALITY LEVEL "C" - INFORMATION OBTAINED
BY SURVEYING AND PLOTTING VISIBLE ABOVE
GROUND UTILITY FEATURES AND BY USING
PROFESSIONAL JUDGEMENT IN CORRELATING
THIS INFORMATION TO THE QUALITY LEVEL "D"
INFORMATION.
QUALITY LEVEL "B" - INFORMATION OBTAINED
THROUGH THE APPLICATION OF APPROPRIATE
SURFACE GEOPHYSICAL METHODS TO DETERMINE
THE EXISTENCE AND APPROXIMATE HORIZONTAL
POSITION OF THE UTILITIES.
QUALITY LEVEL "A" - PRECISE HORIZONTAL
AND VERTICAL LOCATION OF UTILITES OBTAINED
BY THE ACTUAL EXPOSURE AND SUBSEQUENT
MEASUREMENT OF SUBSURFACE UTILITIES.
N
I
C
R
E
A
S
E
D
Y
T
I
L
A
U
Q
TEST HOLE (QL-A)
UNKNOWN
QUALITY LEVEL "C"
BURIED ELECTRIC
BURIED TELECOMMUNICATIONS
QUALITY LEVEL "B"
SANITARY SEWER
WATER
STORM SEWER
CABLE TV
GAS
LEGEND
FIBRE OPTIC CABLE
GAS SERVICE
WATER SERVICE
SANITARY LATERAL
STORM LATERAL
*
BURIED ELECTRIC STREET LIGHT
NOT SURVEYED, LOCATION
BASED ON RECORD INFORMATION#
BURIED ELECTRIC TRAFFIC LIGHT
DISCLAIMER:
G
B
TV
FOC
UNK
TL
SL
H
STM
SAN
WM
SAN
STM
NOT SURVEYED, LOCATION
BASED ON FIELD OBSERVATION
CLIENT:
WS
GS
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF T2UE’S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES, EXCEPT
AS AGREED BY T2UE AND ITS CLIENT, AS REQUIRED BY LAW OR FOR USE BY
GOVERNMENT REVIEWING AGENCIES. T2UE ACCEPTS NO RESPONSIBILITY, AND
DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY THAT MODIFIES THIS
DRAWING WITHOUT T2UE’S EXPRESS WRITTEN CONSENT.
ABANDONEDABD
THE ENGINEER’S SEAL HEREON IS TO CERTIFY THAT THE UTILITIES SHOWN
HAVE BEEN INVESTIGATED IN ACCORDANCE WITH STANDARD SUE INDUSTRY
PRACTICES. ALL OTHER INFORMATION HEREON HAS BEEN PROVIDED BY
OTHERS AND IS NOT A PART OF THIS CERTIFICATION.
SUBSURFACE UTILITY ENGINEERING INVESTIGATION
FLOW ARROW
PRELIMINARY
DATE DETAILS
REVISIONS
INIT.
MA
TC
H LIN
E S
EE D
WG.
U2
QUALITY LEVEL "D"XXX
XXX
XXX
XXX
OH OVERHEAD HYDRO
M.B. N.F.
OCTOBER 2013
(DERRY ROAD & ARGENTIA ROAD INTERSECTION)
DERRY-ARGENTIA
INTERSECTION IMPROVEMENTS
ARGENTIA ROAD
SAN 1802942
SAN
SAN
SAN 1802938
SAN 1802937
SANSAN
SAN 1802936
SAN 1800689
SAN
SAN 1800690
SAN 1800683
SAN 1800688
SAN 1800687
U1
U2
U3
U4
U5KEY PLAN (N.T.S.)
ARGENTIA ROAD
HIGHWAY 4
01
DER
RY R
OA
D
WEST
GENERAL NOTES
1. T2 UTILITY ENGINEERS (T2UE) SUE FIELD
INVESTIGATION WAS COMPLETED IN SEPTEMBER 2013.
CHANGES TO UTILITIES THAT OCCURRED FOLLOWING
OUR INVESTIGATION MAY NOT BE SHOWN.
CONSIDERATION SHOULD BE GIVEN TO UPDATING THIS
PLAN PRIOR TO FINAL DESIGN AND CONSTRUCTION.
2. LIMIT OF INVESTIGATION: 300m IN ALL DIRECTIONS
FROM CENTERLINE OF DERRY ROAD AND ARGENTIA
ROAD INTERSECTION.
3. FIELD VERIFICATION OF UTILITIES WAS COMPLETED
USING A COMBINATION OF ELECTROMAGNETIC PIPE
AND CABLE LOCATE EQUIPMENT.
4. EMPTY CONDUITS, SERVICES, STREETLIGHTING
CABLES, LATERALS TO BUILDINGS, ABANDONED
FACILITIES, WITHIN THE INVESTIGATION AREA MAY
NOT BE SHOWN ON THE DRAWING.
5. T2UE USED AVAILABLE MEANS IN AN ATTEMPT TO
DETERMINE THE LOCATION OF UNDOCUMENTED
UTILITIES HOWEVER CANNOT BE RESPONSIBLE FOR
FINDING ALL UNDOCUMENTED UTILITIES.
6. SURVEY OF T2UE’S UNDERGROUND UTILITY
INFORMATION WAS COMPLETED BY ACL.
7. THE BASEPLAN WAS PROVIDED BY THE CLIENT,
THEREFORE T2UE IS NOT RESPONSIBLE FOR ITS
ACCURACY.
8. UTILITY MATERIALS AND SIZES SHOWN ON
DRAWING ARE BASED ON RECORDS INFORMATION
RECEIVED, PROFESSIONAL JUDGEMENT, OR FIELD
OBSERVATIONS.
9. UTILITY OWNERSHIP SHOWN ON DRAWING IS BASED
ON RECORDS INFORMATION RECEIVED, PROFESSIONAL
JUDGEMENT, OR FIELD OBSERVATIONS.
10. SEE PROJECT REPORT FOR ADDITIONAL
INFORMATION.
CA
TB
CA
TB
LS
BPED
TVPED
TS
VC 205
9537
HV 2026
029
HCM
MH
LS
LS
TVPED
LS
TS
CA
TB
WVWV
CA
TB
BMH
STM
BMH
LS
SAN 1800
690
TS
MH
SAN 1800
683
HV 2026
030
MB
LS
TSSTOP
LS
TS
CA
TB
MB
TS
STOP
CA
TB
BPED
TS
TVPED
LS
TVPED
TS
TS
HV 2026
031
STM
TS
LS
VC
WV
ARGENTIA RD.
450 CONP 450 CONP
450 C
ONP
450 CONP
250
PV
C
1050 CONC
250 PVC
1050
CONC
SAN#
STM#
1050
CO
NC
2400
2400
ST
M
2400
2400
400 CPP
400 CPP400 CPP
750
CP
P
750
CP
P
NOTE:MUNICIPAL RECORDS INDICATE 450mm SANITARY IS CONCRETE ENCASED ALONG STORM INTAKE STRUCTURE.
NOTE:MUNICIPAL RECORDS INDICATE 450mm SANITARY IS CONCRETE ENCASED UNDER 2400mm TWIN STORM PIPES.
STM 1050
FOC BELL
FIELD NOTE:UNABLE TO VERIFY WATERMAIN EAST OF THIS LOCATION.
FOC BELL
FOC ROGERS
BE
LL
FOC ENERSOURCE
FOC ROGERS
FOC ROGERS
FOC ROGERS
FOC ENERSOURCE
LIM
IT
OF
FIE
LD
INV
ES
TIG
ATIO
N
NOTE:UNABLE TO OBTAIN MUNICIPAL RECORDS EAST OF THIS LOCATION.
TORONTO
TORONTO TORONTO
100 PE IP
100 PE IP100 PE IP
ENBRIDGE
ENBRIDGE
NOTE:ROGER RECORDS INDICATE ROGERS TV ALONG THIS APPROXIMATE ALIGNMENT. UNABLE TO FIELD VERIFY.
RO
GE
RS
TV ROGERSNOTE:
ROGER RECORDS INDICATE ROGERS TV ALONG THIS
APPROXIMATE ALIGNMENT. UNABLE TO FIELD VERIFY.
FIELD NOTE:ALLSTREAM FIBRE SLICE BOX.
NOTE:ROGER RECORDS INDICATE ROGERS TV ALONG THIS APPROXIMATE ALIGNMENT. LIKELY IN THE SAME TRENCH AS ROGERS FIBRE. UNABLE TO CONFIRM IN FIELD. NOT SHOWN ON DRAWING.
NOTE:MUNICIPAL RECORDS INDICATE TWO PIPES ALONG THESE APPROXIMATE ALIGNMENTS. FUNCTIONS ARE UNKNOWN. UNABLE TO FIELD VERIFY. FURTHER INVESTIGATIONS ARE REQUIRED TO CLARIFY.
HYDRO
HYDRO HYDRO
FIELD NOTE:FIELD VERIFIED TORONTO HYDRO FIBRE TRENCH ALSO CONTAINS COGECO CABLE AND ALLSTREAM FIBRE.
FIELD NOTE:FIELD VERIFIED TORONTO HYDRO FIBRE TRENCH ALSO CONTAINS COGECO CABLE AND ALLSTREAM FIBRE.
B
BELL
FOC ROGERSBPED#
FOC BELL
250 PVC
100
X8
100
X6
CO
NC
CO
NC
HYDRO 100X12 CONC
HYDRO 100X12 CONC
100
X4
CO
NC
100
X4
CO
NC
100
X8
CO
NC
100
X4
CO
NC
FIELD NOTE:UNABLE TO FIELD VERIFY BELL FIBRE NORTHWEST OF THIS LOCATION. LIKELY IN THE SAME TRENCH AS BELL.
FIELD NOTE:VERIFIED EMPTY CONDUITS IN TV PED.
FIELD NOTE:UNABLE TO FIELD VERIFY
ROGERS FIBRE EAST OF THIS LOCATION.
FIELD NOTE:UNABLE TO FIELD VERIFY
WATERMAIN WEST OF THIS LOCATION.
5 5 Plan No.
Project No.
Sheet of
Drawn by
AreaCAD Area
Checked by
Date
1Om 0 10 20 30m
HORIZONTAL SCALE
Schedule B
61000235
FOR FULL SIZE USE 11002 FULL.TBLHALF SIZE USE 11002-11X17
U5
1-855-222-T2UE | WWW.T2UE.COM
ASCE QUALITY LEVELS
THE UTILITY INFORMATION SHOWN ON THIS DRAWING
WAS COLLECTED IN ACCORDANCE TO ASCE STANDARD
38-02. THE INFORMATION IS SHOWN BY QUALITY LEVEL
WHICH INDICATES THE LEVEL OF EFFORT USED TO
DETERMINE THE LOCATION OF THE DATA
QUALITY LEVEL "D" - INFORMATION DERIVED
FROM EXISTING RECORDS OR VERBAL
RECOLLECTIONS.
QUALITY LEVEL "C" - INFORMATION OBTAINED
BY SURVEYING AND PLOTTING VISIBLE ABOVE
GROUND UTILITY FEATURES AND BY USING
PROFESSIONAL JUDGEMENT IN CORRELATING
THIS INFORMATION TO THE QUALITY LEVEL "D"
INFORMATION.
QUALITY LEVEL "B" - INFORMATION OBTAINED
THROUGH THE APPLICATION OF APPROPRIATE
SURFACE GEOPHYSICAL METHODS TO DETERMINE
THE EXISTENCE AND APPROXIMATE HORIZONTAL
POSITION OF THE UTILITIES.
QUALITY LEVEL "A" - PRECISE HORIZONTAL
AND VERTICAL LOCATION OF UTILITES OBTAINED
BY THE ACTUAL EXPOSURE AND SUBSEQUENT
MEASUREMENT OF SUBSURFACE UTILITIES.
N
I
C
R
E
A
S
E
D
Y
T
I
L
A
U
Q
TEST HOLE (QL-A)
UNKNOWN
QUALITY LEVEL "C"
BURIED ELECTRIC
BURIED TELECOMMUNICATIONS
QUALITY LEVEL "B"
SANITARY SEWER
WATER
STORM SEWER
CABLE TV
GAS
LEGEND
FIBRE OPTIC CABLE
GAS SERVICE
WATER SERVICE
SANITARY LATERAL
STORM LATERAL
*
BURIED ELECTRIC STREET LIGHT
NOT SURVEYED, LOCATION
BASED ON RECORD INFORMATION#
BURIED ELECTRIC TRAFFIC LIGHT
DISCLAIMER:
G
B
TV
FOC
UNK
TL
SL
H
STM
SAN
WM
SAN
STM
NOT SURVEYED, LOCATION
BASED ON FIELD OBSERVATION
CLIENT:
WS
GS
THIS DRAWING HAS BEEN PREPARED FOR THE USE OF T2UE’S CLIENT AND
MAY NOT BE USED, REPRODUCED OR RELIED UPON BY THIRD PARTIES, EXCEPT
AS AGREED BY T2UE AND ITS CLIENT, AS REQUIRED BY LAW OR FOR USE BY
GOVERNMENT REVIEWING AGENCIES. T2UE ACCEPTS NO RESPONSIBILITY, AND
DENIES ANY LIABILITY WHATSOEVER, TO ANY PARTY THAT MODIFIES THIS
DRAWING WITHOUT T2UE’S EXPRESS WRITTEN CONSENT.
ABANDONEDABD
THE ENGINEER’S SEAL HEREON IS TO CERTIFY THAT THE UTILITIES SHOWN
HAVE BEEN INVESTIGATED IN ACCORDANCE WITH STANDARD SUE INDUSTRY
PRACTICES. ALL OTHER INFORMATION HEREON HAS BEEN PROVIDED BY
OTHERS AND IS NOT A PART OF THIS CERTIFICATION.
SUBSURFACE UTILITY ENGINEERING INVESTIGATION
FLOW ARROW
PRELIMINARY
DATE DETAILS
REVISIONS
INIT.
MA
TC
H LIN
E S
EE D
WG.
U2
QUALITY LEVEL "D"XXX
XXX
XXX
XXX
OH OVERHEAD HYDRO
M.B. N.F.
OCTOBER 2013
(DERRY ROAD & ARGENTIA ROAD INTERSECTION)
DERRY-ARGENTIA
INTERSECTION IMPROVEMENTS
ARGENTIA ROAD
SAN 1802942
SAN
SAN
SAN 1802938
SAN 1802937
SANSAN
SAN 1802936
SAN 1800689
SAN
SAN 1800690
SAN 1800683
SAN 1800688
SAN 1800687
U1
U2
U3
U4
U5KEY PLAN (N.T.S.)
ARGENTIA ROAD
HIGHWAY 4
01
DER
RY R
OA
D
WEST
GENERAL NOTES
1. T2 UTILITY ENGINEERS (T2UE) SUE FIELD
INVESTIGATION WAS COMPLETED IN SEPTEMBER 2013.
CHANGES TO UTILITIES THAT OCCURRED FOLLOWING
OUR INVESTIGATION MAY NOT BE SHOWN.
CONSIDERATION SHOULD BE GIVEN TO UPDATING THIS
PLAN PRIOR TO FINAL DESIGN AND CONSTRUCTION.
2. LIMIT OF INVESTIGATION: 300m IN ALL DIRECTIONS
FROM CENTERLINE OF DERRY ROAD AND ARGENTIA
ROAD INTERSECTION.
3. FIELD VERIFICATION OF UTILITIES WAS COMPLETED
USING A COMBINATION OF ELECTROMAGNETIC PIPE
AND CABLE LOCATE EQUIPMENT.
4. EMPTY CONDUITS, SERVICES, STREETLIGHTING
CABLES, LATERALS TO BUILDINGS, ABANDONED
FACILITIES, WITHIN THE INVESTIGATION AREA MAY
NOT BE SHOWN ON THE DRAWING.
5. T2UE USED AVAILABLE MEANS IN AN ATTEMPT TO
DETERMINE THE LOCATION OF UNDOCUMENTED
UTILITIES HOWEVER CANNOT BE RESPONSIBLE FOR
FINDING ALL UNDOCUMENTED UTILITIES.
6. SURVEY OF T2UE’S UNDERGROUND UTILITY
INFORMATION WAS COMPLETED BY ACL.
7. THE BASEPLAN WAS PROVIDED BY THE CLIENT,
THEREFORE T2UE IS NOT RESPONSIBLE FOR ITS
ACCURACY.
8. UTILITY MATERIALS AND SIZES SHOWN ON
DRAWING ARE BASED ON RECORDS INFORMATION
RECEIVED, PROFESSIONAL JUDGEMENT, OR FIELD
OBSERVATIONS.
9. UTILITY OWNERSHIP SHOWN ON DRAWING IS BASED
ON RECORDS INFORMATION RECEIVED, PROFESSIONAL
JUDGEMENT, OR FIELD OBSERVATIONS.
10. SEE PROJECT REPORT FOR ADDITIONAL
INFORMATION.