Transcript
Page 1: GEIEC Devices C-2000™ Overload Relays...These relays are ambient compensated and utilize a differential mechanism for single-phase sensitivity. The trip setting is adjustable for

GEIEC Devices

C-2000™ Overload RelaysRT3 Overload Relay

Type ofMounting

Direct- orPanel(Mount

Rated Current (Amps)

Min

55

63

90

110

140

Max.

80

90

120

140

190

Max. FuseRatingAmps

225

250

350

400

450

Max. CircuitBreaker

Rating Amps

200

225

300

350

500

Manual ResetOnly

Classic

RTN3B

RTN3C

RTN3D

RTN3E

RTN3F

Manual/Auto ResetStop/Reset only

Class 10

RT3B

RT3C

RT3D

RT3E

RT3F

Class 20

RT32C

RT32D

RT32E

RT32F

UstPrice,

GO-10C2

$185.00

185.00

185.00

225.00

225.00

RT4 Overload RelayType of

Mounting

SeparateMount®

Rated Current (Amps)

Mm

45

60

80

120

175

200

Max.

70

90

125

190

280

310

Max. FuseRatingAmps

225

300

400

600

800

900

Max. CircuitBreaker

Rating Amps

175

225

350

500

700

800

Manual ResetOnly

Classic

RTN4N

RTN4P

RTN4R

Manual/Auto ResetStop/Reset only

Classic

RT4N

RT4P

RT4R

Class 30

RT4LK

RT4LL

RT4LM

RT4LN

RT4LP

RT4LR

ListPrice,

GO-10C2

$285.00

285.00

285.00

285.00

285.00

380.00

® Can be mounted to contactor with Overload Jumpers (listed on page 3-13) and Base Plate (CKXB01) (listed onpage 3-13).

RT5 Overload RelayType of

Mounting

SeparateMount®

Rated Current (Amps)

Min

120

175

250

315

430

Max.

190

280

400

500

650

Max. FuseRatingAmps

800

1200®

1200®

1200®

1200®

Max. CircuitBreaker

Rating Amps

500

700

1000®

1200®

1200®

Manual ResetOnly

Class 10

RTN5A

RTN5B

RTN5C

RTN5D

RTN5E

Manual/Auto ResetStop/Reset only

Classic

RT5A

RT5B

RT5C

RT5D

RT5E

Class 30

RT5LA

RT5LB

RT5LC

RT5LD

RT5LE

UstPrice,

GO-10C2

$641.00

641.00

641.00

903.00

903.00

© Maximum fuse rating of 1000 amps/maximum circuit breaker rating of 600 amps when used with CK10CE or CK11CEcontactors. Use CK10BE or CK11gE with higher rated protective devices indicated. CK12BE suitable for all ratings listed.

® Can be mounted to contactor with Overload Jumpers (listed on page 3-13).Note: Do not exceed contactor current rating when selecting and adjusting overload relays.

Remote Electrical ResetRemote electrical resets are used in applications where the motor starter is inaccessible or in automatedcontrol systems where you want to reset the overload relay remotely after the fault has been cleared.Electrical reset coils are rated for intermittent duty and for use with momentary contacts. Minimum time.2 sec. on for reliable operation. Maximum time 1 sec. on/30 sec. off, 5 sec. on/90 sec. off, 10 sec. on/180 sec. off. Power consumption is 100VA/100 watts.

For use with

AIIRToverload relays

Voltage50/60HZ AC/DC

12V24V48V

1 10-120 V220-240 V380-41 5V440-480 V

Catalog No.

RTXRRBRTXRRDRTXRRGRTXRRJRTXRRNRTXRRURTXRRX

List Price,GO-10C2

$55.0055.0055.0055.0055.0055.0055.00

References:InstructionsGEH-6237 RT1 * (Class 10) OverloadDEH-040 RT12* (Class 20) OverloadGEH-6238 RT2* (Class 10) OverloadDEH-041 RT22* (Class 20) OverloadGEH-6239 RT3* (Class 10) Overload

Fixed Heater

Use with Contactorswith these prefixes:

CK75 CK08

Use with Contactorswith these prefixes:

CK09 CK95

Use with Contactorswith these prefixes:

CK10 CK11 CK12

DEH-042 RT32* (Class 20) OverloadGEH-6240 RT4* (Class 10, 30) OverloadGEH-6241 RT5* (Class 10, 30) OverloadGEH-5520 RT5 Overload Connection KitDEH-055 Remote Electrical Reset

Prices and data subject to change without notice 1999 Issue 3-9

Page 2: GEIEC Devices C-2000™ Overload Relays...These relays are ambient compensated and utilize a differential mechanism for single-phase sensitivity. The trip setting is adjustable for

GEIEC Devices

C-2000™ Overload RelaysFixed HeaterC2000 RT overload relays provide motor overload protection through fixed bimetal heaters. These relays are ambient compensated andutilize a differential mechanism for single-phase sensitivity. The trip setting is adjustable for the range listed.Overload relays may be set for 4 different operational modes—manual reset only, automatic reset only, manual reset/stop, or automaticreset/stop. Stop is initiated by pushing the reset button which interrupts the holding circuit in the latter two listed modes.Overload relays feature visible trip indication, reset on the upstroke, weld check, and trip test.

RT1 Overload Relay___________________________

Use with Contactorswith these prefixes:

CLOO CL25CL01 CL04CL02 CL45

Type ofMounting

DirectMount

Rated Current (Amps)

Min

0.16

0.25

0.4

0.65

1

1.3

1.8

2.5

4

5.5

8

10

14.5

17.5

21

25

30

Max.

0.26

0.41

0.65

1.1

1.5

1.9

2.7

4.1

6.3

8.5

12

16

18

22

26

32

40

Max. FuseRatingAmps

113

6

6

6

10

15

20

25

40

50

60

70

80

100

100

Max. CircuitBreaker

Rating Amps

15

15

15

15

15

15

15

15

15

15

30

35

40

50

60

80

80

Manual ResetOnly

Class 10

RTN1B

RTN1C

RTN1D

RTN1F

RTN1G

RTN1H

RTN1J

RTN1K

RTN1L

RTN1M

RTN1N

RTN1P

RTN1S

RTN1T

RTN1U

RTN1V

RTN1W

Manual/Auto ResetStop/Reset only

Classic

RT1B

RT1C

RT1D

RT1F

RT1G

RT1H

RT1J

RT1K

RT1L

RT1M

RT1N

RT1P

RT1S

RT1T

RT1U

RT1V

RT1W

Class 20

RT12K

RT12L

RT12M

RT12N

RT12P

RT12S

RT12T

RT12U

RT12V

RT12W

ListPrice,

GO-10C2

$55.00

55.00

55.00

55.00

55.00

55.00

55.00

55.00

55.00

57.00

57.00

57.00

57.00

57.00

57.00

65.00

78.00

Use with Contactorswith these prefixes:

CL06 CL09CL07 CL10CL08

RT2 Overload RelayType of

Mounting

DirectMount

Rated Current (Amps)

Min

11.5

14.5

18.5

24

30

42

54

64

78

90

Max.

15

19

25

32

43

55

65

82

97

110

Max. FuseRatingAmps

35

50

70

90

100

150

175

225

225

225

Max. CircuitBreaker

Rating Amps

25

45

60

80

100

125

150

200

225

250

Manual ResetOnly

Class 10

RTN2A

RTN2B

RTN2C

RTN2D

RTN2E

RTN2G

RTN2H

RTN2J

RTN2L

RTN2M

Manual/Auto ResetStop/Reset only

Class 10

RT2A

RT2B

RT2C

RT2D

RT2E

RT2G

RT2H

RT2J

RT2L

RT2M

Class 20

RT22D

RT22E

RT22G

RT22H

RT22J

RT22L

RT22M

ListPrice,

GO-10C2

$ 98.00

98.00

98.00

98.00

98.00

98.00

98.00

117.00

143.00

143.00

Note: Do not exceed contactor current ratineFor panel mount use base adapter RTXP or f

) when selecting and adjusting overload relays.IT2XP.

References:InstructionsGEH-6237 RT1' (Class 10) OverloadDEH-040 RT12* (Class 20) OverloadGEH-6238 RT2* (Class 10) OverloadDEH-041 RT22* (Class 20) OverloadGEH-6239 RT3* (Class 10) Overload

DEH-042 RT32* (Class 20) OverloadGEH-6240 RT4* (Class 10, 30) OverloadGEH-6241 RT5* (Class 10, 30) OverloadGEH-5520 RT5 Overload Connection KitDEH-055 Remote Electrical Reset

3-8 1999 Issue Prices and data subject to change without notice

©